BA-T1 Digital temperature indicator for L&S T1 sensors


Single point digital temperature indicator for L&S T1 sensors. Suitable for mounting on front of control panels.

321

BA-T1

Technical data
Supply voltage Nominal voltage Max. voltage tolerance Power consumption Primary fuse Measuring input: T1 sensor input T1 supply voltage Calibration of measured value Display Height of digits Measuring range Resolution Accuracy Measuring cycle Error indication Frame colour (front) Maintenance Connection terminals Connecting cable Weight (including packaging) Dimensions (W x H x D) General ambient conditions Conditions of use Temperature range: Operation Storage / transport Ambient humidity: Operation Storage/ transport Mounting Orientation Safety Product safety Overvoltage category Contamination level Electrical safety Conformity Low voltage (SELV, PELV) AC 24 V, 50/60 Hz +10/15 % 2.5 VA None Input resistance 100 M 10 k from 15 Vref. 2.5 K (trimmer potentiometer) LCD, 3 -digit, with 1 character space for engineering unit [C] 10 mm 50 ...150 C 0.1 C 0.6 C 0.3 s Open circuit: ' I ' Short circuit: ' I' NCS 5005 R20B (light grey) None required Screw terminals for max. 2.5 mm2 See installation notes 0.16 kg 72 x 36 x 90 mm For indoor use, inside control panel 0 ... 50 C 20 ... 60 C 5 ... 85 %rh, without condensation Max. 95 %rh, without condensation Flush-mounted on panel fronts Any EN60730-1 II 2 SELV-E (PELV to IEC364-4-41) Meets the requirements for marking

Principle of operation
The temperature, measured by an external L&S T1 temperature sensor is displayed digitally. The supply voltage and input signal for the indicator are electrically isolated by a built-in isolating transformer. The digital indicator is compatible with controllers which use the L&S T1 measuring bridge. The BA-T1 indicator may also be used as a (stand-alone) thermometer. The temperature display can be calibrated with a trimmer potentiometer.
Trimmer potentiometer

60256

2.5 K +

Siemens Building Technologies Landis & Staefa Division

CA1N5321E / 11.1998 1/2

Construction
Single-part plastic housing, incorporating the front cover, with electronic printed circuit board and LCD digital display.

Mounting / Installation
The BA-T1 single point digital indicator is suitable for flush-mounting on the front of control panels and electrical enclosures. It is inserted into the required cut-out from the front, and secured from the rear with the two side clips on the indicator housing. Disposal Separate and recycle the printed circuit board, housing and (LCD) display.

Dimensions [mm]
72 90
60257

36

5.5

Drilling diagram
68+0.7

78

Terminal layout
60258

32 31 30 29 28 27

NS

AC 24 V LS SGND T1 input T1 supply when no controller connected

Connection diagram
T1 sensor without controller
NS LS SGND T1 Input A
10 k 60259

T1 sensor with controller


NS LS SGND T1 Input A
10 k 60260

AC 24 V

32 31 30

AC 24 V

32 31 30

To controller
29 28 27

T1 supply

D
V ref.

29 28 27

33+0.6

D
V ref.

1998 Siemens Building Technologies Ltd. CA1N5321E / 11.1998 2/2 Siemens Building Technologies Landis & Staefa Division