PT.

Integra Automasi

FUNCTION DESIGN SPECIFICATIONS

SSE SCADA UPGRADING PENGABUAN STATION

2 3

SEP 28, 2012 NOV 13, 2012

FOR REVIEW FOR REVIEW

NM NM

HT HT

HH HH

REV

DATE

ISSUE TYPE

PREPD BY

REVD BY

APPD BY

CLIENT APPD

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 2 of 9

REVISION CONTROL SHEET


Latest Rev DATE ISSUED PRED BY REVD BY APPD BY CLIENT APPD COMMENTS

0 1 2 3

FEB 19, 2012 SEP 4, 2012 SEP 28, 2012 NOV 13, 2012

AT NM NM NM

HT HT HT HT

HH HH HH HH

Pengabuan Station Function Design Specification

2 OF 9

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 3 of 9

TABLE OF CONTENT

1 1.1 1.2 1.3 1.4 2 2.1 2.2 2.3 3

SYSTEM ARCHITECTURE SCADA System Architecture Pengabuan Station Existing System Architecture Pengabuan Station Proposed System Architecture Bandwidth Requirement SCADA/HMI DESIGN Overview Pengabuan Station Alarms Trending BILL OF MATERIALS

4 4 4 5 6 7 7 7 8 9

Pengabuan Station Function Design Specification

3 OF 9

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 4 of 9

1 SYSTEM ARCHITECTURE
The Operator Station shall be based on standard off-the-shelf workstation hardware running on a Windows based operating system. Vijeo Citect is using full 32 bit (65 million) colors. For integration with existing Historian we use Matrikon OPC Server client for ODBC. This OPC server is using for logging data to SQL Server. 1.1 SCADA System Architecture

SCADA System centralizes in Soka Office. All parameter in all stations can be monitor in Central Monitoring room SCADA at Soka Office.

1.2

Pengabuan Station Existing System Architecture

An Existing HMI runtime is Experion HS. and set of redundant PLC system using Honeywell PLC MasterLogic 200.
Pengabuan Station Function Design Specification

4 OF 9

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 5 of 9

1.3

Pengabuan Station Proposed System Architecture

Pengabuan Station Function Design Specification

5 OF 9

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 6 of 9

1.4

Bandwidth Requirement

Bandwidth requirement for SCADA is less than 32 Kbps. Please find this example below. This example is for bandwidth calculation. Status Register The 128 Status Register will be retrieve every 250 ms and using Modbus Function code 2 Request 8 bytes Response 15 bytes

This results is 23 bytes every 250 ms = 92 bytes per second or 736 bits per second = 0.7 kbps

Input Register The 64 Input Register will be retrieve every 250 ms and using Modbus Function code 4 Request 8 bytes Response 133 bytes

This results is 141 bytes every 250 ms = 564 bytes per second or 4512 bits per second = 4.5 kbps

Pengabuan Station Function Design Specification

6 OF 9

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 7 of 9

2 SCADA/HMI DESIGN
2.1 Overview Pengabuan Station

2.2

Alarms

Pengabuan Station Function Design Specification

7 OF 9

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 8 of 9

2.3

Trending

Pengabuan Station Function Design Specification

8 OF 9

SSE SCADA UPGRADING


TITLE Functional Design Specification DOCUMENT NUMBER MEP-SCUP-ENG-02.7 REV 3 DATE 13-11-12 PAGE 9 of 9

3 BILL OF MATERIALS
ITEM NO. DESCRIPTION Hardware & Software Pengabuan Station SCADA Hardware Wall Mounted Panel Cable and Accessories Engineering and Services Pengabuan Station Engineering Documents Manufacture Model Qty Unit

1 1.1

Fortuna

12 U

1 1 1

Ea Lot Lot

Pengabuan Station Function Design Specification

9 OF 9