Pressure Transmitters (820/860 and I/A Series): 02, 04, 0B, 0D, 0E 0A, 03, 2F 07, 0C, 20, 21, 22, 25, 26, 29 Turn off transmitter power. If error continues when power is turned on, contact Foxboro. Check configuration. Change as required. If error continues, contact Foxboro. Sensor or Electronics Failure. Contact Foxboro.
Instruction
MI 020-400
January 1997
Magnetic Flowmeters: 02, 0C, 0D, 10, 11, 1B, 30 12, 14 13 20 21, 22 31 32 Mass Flowmeters: 2, 3, 13, 1F4, 1F5, 1F6, 1F7 Contact Foxboro Repair. Contact Foxboro. Refer to MI 021-384. Check Coil Wiring and Configuration. Check Multi-conductor Wiring; Clean Electrodes. Low Flow. Reverse Flow. High Flow or Configuration. Use transmitter pushbuttons and re-enter data. Use HHT and re-enter data.
21 25 2F 32
Temperature Transmitters 2n 4n 6n 8n An Cn En Bad Sensor #1 Bad Sensor #2 Bad Sensor #1 and #2 Standards fail. Replace electronics module. Combination of 2n and 8n Combination of 4n and 8n. Combination of 2n, 4n, and 8n.
258, 259, 25A, 25B Measurements are invalid. Provide warmer climate for transmitter. 320, 321, 322, 323 2BC 2BD 324, 388, 389 384 385 386 387 388,389 Measurements are invalid. Check RTD. Measurements are invalid. Check Process. Transmitter is off-line. Contact Foxboro. Mass flow is too high. Process temperature is too low or RTD is miswired. Process temperature is too high or RTD is miswired. Process density is too low or Tube Parameter. Process density is too high or Tube Parameter. Flow exceeds calibration limit. Adjust process or calibration limit.
ISSUE DATES MAY 1990 AUG 1991 MAY 1993 JUN 1994 JUL 1995 JAN 1997 Foxboro and I/A Series are registered trademarks of the Foxboro Company. Siebe is a registered trademark of Siebe, plc. MB 100 Printed in U.S.A. 0197
This Operating Guide summarizes the menus used for operating, calibrating, and configuring I/A Series Transmitters using Hand-Held Terminal (HHT) having Program Pak L0122EV, Revision D.
SET HHT
HHT
Update
Reset
Reconnect
PulsePreset
XmtrPar Frequency
LoopCal Status
Selftest SerialNo
Test
MENU SUMMARY
FieldRep
User Data
MemPak
TRANSMITTER OUTPUT MODE: 4 TO 20 mA = m Digital = d Both = b TRANSMITTER TYPE: Pressure = P Temperature = T Magnetic Flow = M Mass Flow (Coriolis) = C Vortex = V
Off
Convert
CONFIGURE TRANSMITTER
PreCfg RdFile
Setup
DATA UPLOADS/DOWNLOADS
*FUNCTIONS THAT READ FROM XMTR
XMTR
1
C = Change P = Previous N = Next E = End Meas GrpDisp ChgCfg Config
RAM
2 3 4
MEASUREMENT
HHT_to_PC
PC_to_HHT
EmptyPipeDetect
FileXfer
PC10
ZeroTotal
ON
Trancal
MEM PAK
Default
Meas
CALIBRATE TRANSMITTER
MENU LEVEL 1
MENU LEVEL 2
MENU LEVEL 3
MENU LEVEL 4
*1 = SETUP - CHGCFG-CONFIG (SAVE ON EXIT) 2 = SETUP - MEMPAK - SAVETOPAK - USERDATA SETUP - MEMPAK - SAVETOPAK - SAVEALLTOPAK 3 = SETUP - FIELDREP - RESTOREPAKFILE 4 = SETUP- MEMPAK - FILEXFER - PC_TO_HHT 5 = SETUP- MEMPAK - FILEXFER - HHT_TO_PC 6 = SETUP - MEMPAK - PRECFG 7 = SETUP - MEMPAK - RDFILE
Cal