Professional Documents
Culture Documents
ISHRAE
INDIAN SOCIETY OF HEATING REFRIGERATING AND AIRCONDITIONING ENGINEERS ISHRAE INSTITUTE OF EXCELLENCE
# 76, I FLOOR, KASTURI COMPLEX, MISSION ROAD, BANGALORE 560 027, PHONE: 080-22245523, 41495045 WEB SITE: www.iiebangalore.org
ACKNOWLEDGEMENT
IIE acknowledges with thanks the following eminent personalities whose lectures are used to compile this refresher course materials. D. NIRMAL RAM, G.V. RAO, LESLIE DSOUZA, MAHESH U. V. ACHAR, K. V. PRADEEP, RAKESH SAHAY AND MANY OTHERS Bibilography : ISHRAE Hand Book ASHRAE Hand Books Carrier System Design Manual KUMAR,
LOAD COMPONENTS:
1. SOLAR GAIN a. Through Wall b. Through Roof c. Through Glass
2.
10. Material of construction of walls, ceiling/roof. 11. Outside dry and wet bulb temperatures (all seasons) 12. Inside design dry bulb temperature and relative humidity. 13. No. of persons. 14. Are they smoking? Type of activity 15. Lighting load and type of lights. 16. Machinery loads with diversity 17. Other additional loads. 18. Duration of operation 19. Space to locate various equipments 20. Ventilation required 21. Details of exhaust, if any. 22. Level of cleanliness to be maintained 23. Availability of soft water and electricity 24. Other relevant information
NOTE: Air-conditioning load estimations are based on quantity of air required to produce the design conditions. As such in high altitudes where air conditioning is required, when the density decreases, more quantity of air is required to satisfy the given sensible load. The weight of the air to meet the latent load decreases owing to the higher wet bulb temperature and relative humidity, the wet bulb temperature decreases as the altitude increases corresponding to the sea level. Load estimations are based on either normal design conditions or maximum design conditions. In normal design conditions, the outdoor design conditions are the simultaneously occurring dry bulb and wet bulb temperature and humidity which are permitted to exceed a few times a year for shorter periods. This is generally recommended for comfort and normal industrial applications and it is occasionally permissible to exceed the inside design conditions. In cases where inside temperature swings on the higher side is not tolerable then the design should be based on the maximum outside design conditions. The maximum design dry and wet bulb temperatures are simultaneous peaks and not individual peaks that are considered for the load estimation. A constant temperature is required for many industrial applications instead of a temperature level. The actual cooling load will generally be below the peak total instantaneous heat gain, thus requiring a smaller equipment to perform a specific job. If the equipment is allowed to run at a few degrees higher than design requirement during peak periods, a smaller capacity plant will meet the requirement. A smaller system running for longer duration at full load will result in saving in power and is more efficient than a bigger system running at part load conditions for a shorter duration. Reasons for the difference in the actual heat gain and the total instantaneous peak heat gain is due to storage effect, diversity and stratification. If the cooling capacity supplied to the space matches with the cooling load, the temperature in the space remains constant. On the contrary, if the cooling capacity supplied to the space is more than the cooling load then lower temperatures are maintained. Precooling a space below the design conditions increases the storage of heat at the time of peak load. Precooling is useful in reducing the cooling load in applications such as churches, theaters and auditoriums. Diversity of cooling load results from the probable non occurrence of part of the cooling load such as lighting,
people and equipment load. The size of the diversity factor has to be based on the accurate judgment of the user or his engineer. Heat may be stratified in rooms with high ceiling and where the air is exhausted through the ceiling or the return air is taken above the false ceiling.
A=Area of the separating section in sqft. T1=Average air temperature in adjacent space deg. F T2= Air temperature in conditioned space deg. F U=1/R where R=Addition of thermal resistance of all the surfaces coming in between the conditioned space and adjacent space. (Refer tables for Thermal Resistance R of various building and insulating materials).
More heat is reflected and less heat is transmitted inside the conditioned area if the angle of incidence is more. The total solar heat gain in the conditioned area is the heat transmitted together with around 40% of the heat absorbed by the glass windows. Depending on the latitudes, for each month in a year and for different exposures and on different timings there are tables for the solar heat gain. This solar heat gain in Btu /hr/sqft. area is multiplied with the area of the glass and the factor depending on the shade. For ordinary glass the factor is 1.0 whereas for inside Venetian blinds of light color the factor is 0.56.
the film coefficient, when working out the transmission co-efficient. It is the resistance offered by the film of air which clings to the surface of the wall. The resistance is more when the air is still and is less when there is wind velocity. Whenever a false ceiling is provided in a room having an exposed roof, the space enclosed between the false ceiling and the roof is called as attic space. If this attic space is not properly ventilated the space temperature may exceed the outside temperature. The space temperature can be worked out considering that the rate of heat flow from outside into the attic space is equal to the rate of flow of heat from the attic space into the room.
LIGHTS
Lights produce sensible heat and are dissipated by radiation and convection. About 80% of the input is radiated and around 10% is convected for an incandescent lamp. For a fluorescent lamp 25% of the input is radiated 50% is convected. For a fluorescent lamp, approximately 25% more heat is generated than the input and this is due to the ballast. It is preferred to get the exact number of lights and its wattage and type. It is also a common practice to give this load in watts/sq.ft depending on the application. The wattage is multiplied by 3.413 to arrive at the heat dissipated in BTU/hr.
reason that for air-conditioning, outdoor air is introduced which develops a positive pressure inside the conditioned area and only exfiltration does occur. However infiltration may occur if wind velocity outside is higher. Infiltration is also a predominant feature for high rise buildings due to stack effect. Infiltration of air and by pass of air through the cooling coil becomes a room load. Outdoor air is introduced into the conditioned area so as to dilute the odours given off by the people, smoking and other fumes and contaminations generated inside the room. The quantity of fresh air depends upon the volume of the room or the number of people and the activity. Ventilation standards for different applications are shown in the enclosed tabulations. For comfort applications during the peak load when it is permitted the outdoor air quantity may be reduced resulting in smaller equipment. However during periods other than the peak load the required maximum fresh air has to be introduced into the room which will do the flushing. However in any case the air quantity during peak load should not be lesser than 50% of the required air quantity. Indoor air quality (IAQ) is now talked loudly by all. Minimum requirement of fresh air for applications having lesser occupancy is one air change per hour. Solar gain through walls, glass, roof and transmission gain through partition walls, ceiling, floors, internal loads such as people, light, equipment and infiltration of fresh air(due to by pass in the cooling coil) constitute Room Sensible Heat (RSH). When the system gain is added to this, this becomes Effective Room Sensible Heat (ERSH). Heat gain through infiltration, people and other sources which adds moisture in the room constitute Room Latent Heat (RLH). When system gain is added it becomes Effective Room Latent Heat (ERLH). The summation of room sensible / effective room sensible and room latent / effective room latent heat is called as Room Total Heat (RTH)/Effective Room Total Heat (ERTH). When outdoor sensible and latent heat is added it becomes Grand Total Heat (GTH) based on which the air-conditioning system is designed. The effective room sensible heat over the effective room total heat is called as effective room sensible heat factor. With this factor and the inside design conditions, Apparatus Dew Point (ADP) is calculated. Dew point is the temperature at which condensation occurs when the air is cooled and the effective surface temperature of the coil should match with the dew point to meet the design parameters. Temperature rise is the difference in temperature between the room
5
ELECTRIC MOTORS
Electric motors generate sensible heat which is dissipated inside the conditioned area depending on the location of the prime mover and the driven equipment. The heat dissipated by the motor is input multiplied by the motor inefficiency. The rest of the heat is dissipated by the driven machinery. When a motor is overloaded or partially loaded the heat generated will not obey the above law. As such in case of heavy machinery load it is advisable to measure the input and not to depend on the rated horse power of the motors. When the motor rating is in KW it is multiplied by 3413 and when the rating is in HP it is multiplied by 2545 to obtain the heat dissipation in BTU/hr. Suitable diversity has to be applied to the connected electrical load depending on the actual running of the motor at a particular period of time. Other internal loads that may constitute the room load may be gas burners, electric/steam heaters and water fountains, hot water/steam pipes and tanks.
and the apparatus dew point multiplied by the factor (1-bypass factor). Effective room sensible heat over 1.08 and the temperature rise gives the dehumidified air quantity which has to be pumped into the room to offset the room load and to meet the design conditions. In high latent load applications the dehumidified air quantity will work out to be low. In such cases some air has to be bypassed across the cooling coil to reduce the temperature of air entering the room which
AIR QUANTITY EQUATIONS ERSH cfmda = 1.08 x (1-BF)(t rm- tadp) (1)
otherwise will cause a cold blast on the occupants. The dehumidified air quantity and the bypassed air is the total air quantity on which the equipment is selected. Similarly for applications such as clean rooms minimum required air changes are required to be met. During such occasions also more air will be bypassed across the cooling coil.
ERTH cfmda = 4.45 x (1 -BF)(hrm hadp) TSH cfmda = 1.08 (tedb-tldb) (4) (3)
0.68 =
60 13.5
1076 7000
where 6 0 = min/hr 13.5 = specific volume of moist air at 70 F db and 50% rh 1 0 7 6 = average heat removal required to condense one pound of water vapor from the room air 7 0 0 0 = grains per pound
4.45 = 60
13.5
* RSHS, RLHS and GTHS are supplementary loads due to duct heat gain, duct leakage loss, fan and pump horsepower gains, etc. To simplify the various examples, these supplementary loads have not been used in the calculations. However, in actual practice, these supplementary loads should be used where appropriate. When no air is to be physically bypassed around the conditioning apparatus, cfmda = cfmsa. ** When tm, Wm and hm are equal to the entering conditions at the cooling apparatus, they may be substituted for tedb, Wea and hea respectively.
(10)
Note: cfm da will be less than cfmsa only when air is physically bypassed around the conditioning apparatus.
(11)
Date : Page No. : ______ of ______ Local Time DB WB Peak Load LOCAL TIME SUN TIME %RH DP Gr/Lb
= Factor
Cu.Ft. Btu/Hour
Roof Shaded Sq Ft X All Glass Partition Ceilling Floor Infiltration Outside Air People Power LIghts Appliances, Etc Sq Sq Sq Sq
Open doors X CFM/DOOR = Exhaust Fan Crack Feet X Cfm/Ft = CFM OUTSIDE AIR THRU APPARATUS * SENSIBLE HEAT FACTOR & APPARATUS DEWPOINT
(A) Eff. room Sens. Heat (C) Eff. room total Heat Indicated ADP (1-BF) X Room Sensible heat 1.08 X Dehumidified rise
F Selected ADP
(Room Temp-ADP) = =
FX
INTERNAL HEAT
NOTES
% + SAFETY FACTOR %
EFFECTIVE ROOM LATENT HEAT (B) EFFECTIVE ROOM TOTAL HEAT (C)=(A+B)
Sensible: Latent: Return Duct Heat Gain%
Tons = E/12,000
OUTSIDE AIR HEAT Cfm X FX (1-BF) X 1.08 Cfm X gr/lb X (1-BF) X 0.68
(D) = (C+Outside Air Heat)
Pump H.P.%
= (D+Losses)
DISCLAIMER
Ishare Foundation Trust, Bangalore and IIE Bangalore confirm that the materials are compiled from various lectures, seminars, workshops conducted by various ISHRAE members, faculties of repute from ISRHAE Bangalore Chapter. This is not a book but a collection of course materials to refresh and train the freshers and others belonging to the HVAC & R and allied fraternity.