PowerLogicTM Ethernet Gateway EGX300

User Guide
63230-319-216B4 06/2013

Safety Information
Important Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of either symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.

CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.

NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.

Please note
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

Notices
FCC Part 15 Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The Ringer Equivalence Number (REN) for the device optional internal modem is 0.6. Connection to the device internal modem should be made via an FCC Part 68 compliant telephone cord (not supplied). The device cannot be used on a public coin phone service or party line services. This Class A digital apparatus complies with Canadian ICES-003.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Table of Contents

Table of Contents
Introduction .......................................................................................................................... 1 Additional Resources ............................................................................................................. 1 Accessing the EGX Over a Network ................................................................................... 2 Logging in to the EGX ............................................................................................................ 2 EGX User Interface Overview .............................................................................................. 3 Setup ..................................................................................................................................... 4 Ethernet and TCP/IP Settings ................................................................................................ 4 Advanced Ethernet Settings ............................................................................................. 5 Duplicate IP Address Detection........................................................................................ 7 Serial Port .............................................................................................................................. 8 Advanced Serial Port Settings.......................................................................................... 9 Remote Device Connections ................................................................................................ 10 EGX Device List ................................................................................................................... 11 Connecting Devices to an EGX ...................................................................................... 11 Device List Setup............................................................................................................ 12 Device Discovery............................................................................................................ 14 Device Logging .................................................................................................................... 16 Interval Data Logging ..................................................................................................... 16 Set Up Interval Logging .................................................................................................. 17 Topics to Log .................................................................................................................. 18 Device Log Export ................................................................................................................ 19 E-mail Export .................................................................................................................. 19 FTP Export ..................................................................................................................... 20 HTTP Export................................................................................................................... 21 Date and Time ...................................................................................................................... 24 Network Time Synchronization....................................................................................... 24 SNMP Parameters ............................................................................................................... 25 Modbus TCP/IP Filtering ...................................................................................................... 26 Documentation Links ............................................................................................................ 27 User Accounts ...................................................................................................................... 28 Web Page Access ................................................................................................................ 29 Add/Remove Custom Web Pages.................................................................................. 30 Adding Web Pages Using FTP....................................................................................... 30 Deleting Web Pages Using FTP..................................................................................... 30 Add/Remove Web Pages to/from the Web Interface...................................................... 31 Preferences .......................................................................................................................... 31 Viewable Device Types ........................................................................................................ 32 Audit Trail ............................................................................................................................. 33 System Access Point ........................................................................................................... 36 Monitoring ........................................................................................................................... 37 Real Time Data .................................................................................................................... 37 Single Device Pages ...................................................................................................... 37 Basic Readings Settings................................................................................................. 37 Analog Gauge Range ..................................................................................................... 38 Summary Device Pages ................................................................................................. 38 Trending ......................................................................................................................... 39 Device Logging .................................................................................................................... 40 Single Device Pages ...................................................................................................... 40 Getting a Data Log ......................................................................................................... 41 Log Format ..................................................................................................................... 42 Error Codes for Data Logs.............................................................................................. 43 Getting an Interval Data Log using FTP ......................................................................... 43 Getting an Interval Data Log Using the Data Points Button ........................................... 43
2009-2013 Schneider Electric. All Rights Reserved. i

PowerLogicTM Ethernet Gateway EGX300

63230-319-216B4 06/2013

Getting an Interval Data Log Using the Microsoft Web Query Feature .......................... 44 Getting an Interval Data Log Using E-mail ..................................................................... 44 Getting an Interval Data Log Using HTTP ...................................................................... 44 Summary Device Pages ................................................................................................. 44 Dashboards .......................................................................................................................... 46 Viewing a Dashboard ..................................................................................................... 46 Getting Dashboard Data Using the Data Points Button.................................................. 47 Saving a Dashboard Link ............................................................................................... 47 Saving a Dashboard as an Image .................................................................................. 48 System Access Point ........................................................................................................... 49 Documentation ................................................................................................................... 49 Control ................................................................................................................................ 50 Diagnostics ......................................................................................................................... 50 Statistics ............................................................................................................................... 50 Interpreting Statistics ...................................................................................................... 52 Read Device Registers ........................................................................................................ 55 Communications Check ....................................................................................................... 56 Automated Communications Check ............................................................................... 56 Manual Communications Check..................................................................................... 56 Maintenance ....................................................................................................................... 57 Firmware ............................................................................................................................. 57 Finding the Firmware Version .............................................................................................. 57 Executable Binary Component Firmware Version.......................................................... 58 Disk Image Version ........................................................................................................ 58 Getting New Firmware ......................................................................................................... 58 Updating the Firmware ......................................................................................................... 59 Appendix ASupported Ethernet Protocols .................................................................. 60 Hardware .............................................................................................................................. 60 Appendix BSupported Device Types ............................................................................ 61

ii

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Introduction

INTRODUCTION

The EGX300 is an Ethernet-based device providing a transparent interface between Ethernet-based networks and field devices. Field devices include meters, monitors, protective relays, PLCs, trip units, motor controls, and other devices that communicate using Modbus, Jbus, or PowerLogic protocol. The EGX300 uses Modbus TCP/IP protocol to access field device information across a local area network (LAN) or a wide area network (WAN). This capability allows the use of monitoring software to access information from devices for data collection, trending, alarm/event management, analysis, and other functions. The EGX300 supports real-time data reporting from many common device types providing several device-specific features. Reports such as on-board device and circuit summary pages, as well as on-board data logging and real-time trending are available. Figure 1: EGX300 Overview
Real-Time Views View device data through a simple browser - no software Real-Time Trends

EGX300 Web Pages

Data Log Trends Control Resets

EGX300

Pull information into web pages from other PowerLogic gateways and Modbus TCP/IP interfaces such as ECC21s and PM8ECCs.

EGX100

ION 6200

PM800

Micrologic

Sepam

Additional Resources

Go to www.schneider-electric.com and enter EGX300 in the search field. Navigate to the EGX Documents & Downloads.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300 Accessing the EGX Over a Network

63230-319-216B4 06/2013

ACCESSING THE EGX OVER A NETWORK

After you set up the EGX Ethernet parameters (see the EGX installation guide), you can access the EGX over an Ethernet LAN using any standard web browser.

Logging in to the EGX


Action
1. Launch the web browser. 2. In the Address bar, type the address of your EGX (169.254.0.10 is the default), then press Enter.

Result
Opens the web browser. Opens the Login dialog box.

3. Type your user name (Administrator is the Enters the user name and password, then default) and password (Gateway is the opens the EGX home page. default) into the text boxes, then click OK. NOTE: The user name and password are case-sensitive. 4. Click the appropriate item from the Menu bar. Opens the selected Menu item.

Figure 2:

The EGX Home Page

Menu bar

We recommend logging out whenever you do not need access to the EGX. To log out of the EGX session, click Log Out or just close your browser.

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 EGX User Interface Overview

EGX USER INTERFACE OVERVIEW

The EGX user interface consists of multiple web pages used for device monitoring and control, and EGX diagnostics and setup. See Table 1 for a description of each web page. Table 1: EGX Pages
Description See Page
4 8 10 11

EGX Web Page


Setup Ethernet & TCP/IP Serial Port

Configure Ethernet and TCP/IP communication settings. Configure serial communication parameters.

Remote Device Connections Configure remote Modbus TCP/IP device connections. Device List Configure, identify, or verify local serial devices on the daisy chain. Remote devices can only be configured or verified. Configure device logging parameters. Configure device logging export options. Set date and time manually or with SNTP parameters. Configure Simple Network Management Protocol (SNMP). Configure which IP addresses can access the EGX through Modbus TCP/IP. Configure file and URL documentation links. Create and edit groups and users. Configure web page access rights for each user group. Configure EGX preferences. Configure which supported device types are viewable in the EGX Device List web page. Configure the ways in which the EGX will report system messages: via the maintenance log, e-mail, and remote Syslog server. Enable and configure the group IP address for multiple EGX300s, allowing them to discover each other, viewing each others information.

Device Logging Device Log Export Date and Time1 SNMP Parameters1 Modbus TCP/IP Filtering1 Documentation Links User Accounts1 Web Page Access1 Preferences Viewable Device Types Audit Trail1

16 19 23 24 25 26 27 28 30 31 32

System Access Point1

35

Monitoring Real Time Data The Single Device Pages table view provides basic readings of selected devices. The Summary Device Pages table view provides summaries of one or more selected devices. The Trending Page view provides real-time graphic and table trending of common topics across multiple devices. The Single Device Pages provide graphic and table trending logs of user-selectable quantities for selected devices. The Summary Device Pages provide graphic trending logs of multiple devices with a common topic. The Dashboards provide graphic and table representations of energy consumption information aggregated over time for all devices enabled for data logging. The System Access Point page displays EGX300s and other networked system devices that are accessible from this EGX300. Each line is a hyperlink to the EGX300 log-in page. 36

Device Logging

39

Dashboards

45

System Access Point

48

Documentation Documentation Control Resets Provides for the execution of resets defined for the device, and displays the date and time each reset function was performed. Date and time resets are shown only when the device supports them. 49 Accesses relevant EGX documentation and user configured documentation links. 48

Accessible by administrator only

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Table 1:

EGX Pages
Description See Page
49

EGX Web Page


Diagnostics Statistics

Displays diagnostic data used to troubleshoot network problems. This page also contains information about your specific EGX, including the serial number, manufacturing date, and Media Access Control (MAC) address. Allows users to read register data from local and remote devices connected to the EGX. Verifies the communications health of all devices configured on the EGX. Shows the date, time, and user who last performed maintenance on the equipment, and provides entry detail on the maintenance performed

Read Device Registers Communications Check Maintenance Maintenance Log

54 55

56

Accessible by administrator only

SETUP
Ethernet and TCP/IP Settings

To access the Setup web page links, click Setup on the EGX menu bar.

Action
1. From the Setup menu, click Ethernet & TCP/IP. 2. Select your frame format and media type. Contact your network administrator if you do not know. 3. Enter your IP address, subnet mask, and default gateway address assigned to your EGX by your network administrator.

Result
Opens the Ethernet & TCP/IP page. Selects the frame format and media type.

Enters the Ethernet parameters for the EGX. NOTE: If you enter an IP address that is used by another device, you will be prompted to select a new IP address. See Duplicate IP Address Detection on page 7. Updates the EGX Ethernet and TCP/IP settings.

4. Click Apply. * See Table 2 below for a list of options.

Figure 3:

Ethernet & TCP/IP Page

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Table 2:
Option

EGX Ethernet and TCP/IP Settings


Description Setting

Frame Format Media Type

Used to select the format for data sent over Ethernet II, 802.3 SNAP an Ethernet connection. Default: Ethernet II Used to define the physical Ethernet connection or media type. 10T/100Tx Auto 10BaseT-HD 10BaseT-FD 100BaseTX-HD 100BaseTX-FD

Default: 10T/100Tx Auto Obtain IP Address Automatically Used to automatically obtain an IP address Enabled or disabled from a BootP server. Default: Disabled NOTE: Requires network administration support. Used to enter the static IP address of the EGX. Default: 169.254.0.10

IP Address Subnet Mask Default Gateway

Used to enter the Ethernet IP subnet mask Default: 255.255.0.0 address of your network. Used to enter the gateway (router) IP Default: 0.0.0.0 address used for wide area network (WAN) communications.

Advanced Ethernet Settings

IMPAIRED NETWORK PERFORMANCE Only qualified workers should modify the advanced Ethernet settings of the EGX. Such modifications should be performed only after reading about and understanding the advanced Ethernet settings. Failure to follow these instructions can impair network performance.

Action

Result

1. Click Advanced on the Ethernet & TCP/IP Opens the Advanced Ethernet Settings page. page. 2. Configure the advanced Ethernet settings (see Table 3 on page 6 for available options). Click Defaults to select the default values for all options. 3. Click Apply. NOTE: Applying changes to the Advanced Ethernet Settings page does not save changes to the Ethernet & TCP/IP page. 4. Click OK to approve the changes and to reset the EGX. Sets up the advanced Ethernet settings.

Updates the EGX Ethernet and TCP/IP settings.

The EGX reboots.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Figure 4:

Advanced Ethernet Settings Page

Table 3:

EGX Advanced Ethernet Settings


Description Setting

Option
Time To Live TCP Keep Alive

Identifies the number of routers a TCP packet 1 to 255 hops can pass. Default: 60 hops A timer that detects when a connected device 0 to 65,000 seconds on an idle connection becomes unavailable Default: 30 seconds due to events such as a reboot or shutdown. A setting of 0 disables this setting. Used to specify how long the EGX will wait for 0 to 60 seconds a BootP server to assign its IP address. (The Default: 15 seconds default IP address is used after timeout if no IP address is assigned.) Used to specify how long entries in the 0 to 65,000 minutes Address Resolution Protocol (ARP) table are Default: 15 minutes kept. Controls whether the FTP server initializes during startup. Disabled or Enabled Default: Enabled

BootP Timeout

ARP Cache Timeout

FTP Server FTP Connection Idle Time HTTP Connection Idle Time HTTP Port Number

A timer that closes the FTP connection after a 30 to 900 seconds specified amount of idle time. Default: 120 seconds A timer that closes the HTTP connection after 0 to 65,000 seconds a specified amount of idle time. Default: 4 seconds The TCP port used for HTTP messages. The 0 to 65,000 following port numbers are reserved for other Default: 80 network protocols and cannot be used: 20 0 - disables HTTP port and 21 (FTP) and 502 (Modbus TCP/IP). The TCP port used for HTTPS messages. 1 to 65,000 The EGX comes with a self-signed certificate. Default: 443 To make the EGX a fully trusted server, you 0 - disables HTTPS port must acquire a certificate from a Certificate Authority (e.g., VeriSign Authentication Services). To add/install a digital certificate, manually navigate to the certificate update page using the URL http://x.x.x.x./update_certs_shtml, where x.x.x.x is the IP address of the EGX.

HTTPS Port Number

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Table 3:

EGX Advanced Ethernet Settings


Description
Used to specify the maximum number of HTTP keepalives available.

Option
HTTP Maximum Keepalives

Setting
0 to 65,000 Default: 100 16 to 64 Default: 32

Modbus TCP/IP Server Used to specify the number of Modbus Connections TCP/IP server connections available. Modbus Broadcast

Determines how Modbus TCP/IP messages Disabled, Enabled, or with Unit IDs of 0 are handled on the serial Enabled with Response subnetwork. Disabled = all messages are Default: Disabled ignored. Enabled = all messages are treated as broadcasts to serial ports with no response expected. Enabled with Response = all messages are treated as regular messages to serial ports with a response expected back. Setting that determines if Modbus TCP/IP messages from remote clients will be routed to remote Modbus TCP/IP devices that are defined in the EGX. Disabled or Enabled Default: Enabled

Modbus TCP Proxy

Modbus TCP/IP Client Timeout Modbus TCP/IP Client Connection Timeout

Amount of time the EGX will wait for a remote 0.1 to 10 Modbus TCP/IP device to respond to a Default: 5 seconds Modbus TCP/IP request initiated by the EGX. Amount of time the EGX will wait for a remote 1 to 10 Modbus TCP/IP device to respond to a Default: 2 seconds Modbus TCP/IP connection request initiated by the EGX. 0 to 32,767 seconds Default: 0

Modbus TCP/IP Server A timer that closes the Modbus TCP/IP Connection Idle Time connection after a specified amount of idle time. A setting of 0 disables this setting.

Duplicate IP Address Detection

While connected to your network, the EGX publishes its IP address. To avoid any duplicate IP address conflicts, the EGX uses the Address Resolution Protocol (ARP) to see if any other device on your network is using the same IP address. Table 4 below explains how the EGX handles a duplicate IP address when it is detected. Table 4: Duplicate IP Detection Scenarios
Duplicate IP Detected Power/Status LED

Scenario
Boot Process / Power Restore Ethernet Link Detected

Reverts to the default EGX IP address, Four blinks, pause pattern subnet mask, and gateway address. ARP requests are sent every 15 seconds until the IP address is available. When the IP address becomes available, the EGX will use it.

Manual Address Change EGX keeps its previous IP address and displays a message indicating that the IP address is already in use by another device.

Receives an ARP request Reverts to the default EGX IP address, Four blinks, pause pattern subnet mask, and gateway address if a connected device sends four ARP requests for the EGXs IP address. The EGX will send ARP requests every 15 seconds until the IP address is available again. When the IP address becomes available, the EGX will use it.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Serial Port
Action
1. From the Setup menu, click Serial Port.

Result
Opens the Serial Port page.

2. Select your physical interface, Selects the serial port options. transmission mode, baud rate, parity, and response timeout (see Table 5 on page 8). 3. Click Apply. Updates the EGX Serial Port settings.

Figure 5:

Serial Port Page

Table 5:
Option

Serial Port Settings


Description
Used to select how the EGX serial port is physically wired.

Setting
RS485 4-wire, RS485 2-wire, or RS232 Default: RS485 2-wire Automatic Modbus ASCII

Physical Interface

Transmission Mode

Used to select how data is transmitted over a serial connection.

NOTE: Automatic mode allows you to communicate to Modbus RTU, Jbus, and PowerLogic (SY/MAX) slave devices on the same daisy chain. Baud Rate Used to select the data transmission speed 2400, 4800, 9600, 19200, over a serial connection. 38400, 56000*, or 57600* Default: 19200 Used to select the type of parity required to Even, Odd, or None check data accuracy by using a parity bit. Default: Even

Parity

Response Timeout Used to select how long the EGX will wait 0.1 to 10 seconds to receive a response from a serial device. Default: 3 seconds * Available only if the physical interface and transmission mode is RS232/Modbus ASCII.

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Advanced Serial Port Settings

IMPAIRED NETWORK PERFORMANCE Only qualified workers should modify the advanced serial port settings of the EGX. Such modifications should be performed only after reading about and understanding the advanced serial port settings. Failure to follow these instructions can impair serial communication performance.

Action
1. Click Advanced on the Serial Port page.

Result
Opens the Advanced Serial Port Settings page.

2. Configure the advanced serial port settings Sets up the advanced serial port settings. (see Table 6 on page 11 for available options). Click Defaults to select the default values for all options. 3. Click Apply. NOTE: Applying changes to the Advanced Serial Port Settings page does not save changes to the Serial Port page. Updates the EGX advanced serial port settings.

Figure 6:

Advanced Serial Port Page

Table 6:
Option

Advanced Serial Port Settings


Description
Defines the minimum silent time between the end of a received response and the beginning of a new request on the serial line.

Setting
0 to 100 milliseconds Default: 50 milliseconds

Delay Between Frames

Silent Interval Extension

Allows the silent interval used to signify the 0 to 15 characters end of a ModbusRTU packet to be Default: 6 characters extended beyond the 3.5 characters defined by the standard.

Modbus TCP/IP Indicates the exception response code 0x0A or 0x0B Timeout Exception returned when a serial device connected to Default: 0x0B Code the EGX does not respond before the serial port timeout. Modbus TCP/IP uses 0x0B. However, in some legacy software suites, 0x0A was used.

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Remote Device Connections

The EGX can open connections for up to 16 unique, user-defined remote Modbus TCP/IP devices. You can enter connections manually or select them from a table of System Access Point-discovered connections (see Figure 7). These connections are made available to the Device List Setup for remote device configuration.
Action
1. From the Setup menu, click Remote Device Connections.

Result
Opens the Remote Device Connections page.

2. To manually add a connection, enter the IP Enters the IP addresses of the remote devices. addresses for the remote devices to which you want to connect. 3. To add a System Access Point-discovered Enters the IP address of the selected System connection, click Add (to the right of the Access Point-discovered connection. desired connection in the Discovered Connections table). 4. Click Apply. Updates the EGX Remote Device Connections settings.

Figure 7:

Remote Device Connections

10

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

EGX Device List

Before you begin, keep in mind that you must not use serial slave addresses 1 or 16 in Automatic transmission mode on a daisy chain with mixed protocols (for example, a single daisy chain with some devices using PowerLogic protocol and others using Modbus RTU/Jbus protocol).

Connecting Devices to an EGX

Figure 8 and Figure 9 illustrate how devices can be connected to the EGX. To add those devices to the Device List, follow the steps in Device List Setup on page 12. Figure 8: Topology - Serial Slave Devices Only

Ethernet Connection EGX

EGX300 Web Pages

RS485 connection

Serial Slave Devices

Figure 9:

Topology - Serial Slave and Remote Devices


Ethernet Connection

EGX300 Web Pages EGX100 IP address: 169.254.0.28 EGX300 IP address: 169.254.0.75

Up to 16 remote IP connections are possible

RS485 connection

RS485 connection

Remote Slave Devices

Serial Slave Devices

2009-2013 Schneider Electric. All Rights Reserved.

11

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Device List Setup


Action
1. From the Setup menu, click Device List.

Result
Opens the Device List page. (See Figure 10 for local-only connections, or see Figure 11 if remote connections are available.) Opens the Device Discovery page to discover all locally connected devices.

2. You can use Discover to find locally connected devices (see Device Discovery on page 14). If remote device configuration is required, proceed to step 3. 3. Refer to Figure 11 on page 13 and select the number of viewable devices (1 to 64). 4. Select the Connection from the drop-down list.* 5. Select the Device Type from the drop-down list.* 6. In the Device Name text box, type the device name.

Selects the number of viewable locations that can be used to define devices connected to the EGX. Selects the connection. Selects the device type. Enters the device name.

7. In the Local ID text box, type the address Enters the local address of the device. of the serial slave device if it is on the serial port, or type the address you want to use to access a remote device.* 8. In the Remote ID text box, type the address of the remote device.* 9. Repeat steps 4 through 8 until all of the devices are entered. 10. Click Apply. Enters the address of the remote device. Enters all of the connected devices. Updates the Device List settings.

* This configuration parameter can only be changed if data logging is disabled for the device being updated. See Device Logging on page 16.

Figure 10:

Device List Page

12

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Figure 11:

Device List Page with Remote Connections Supported

Table 7:

Device List Settings


Description
1 to 64 Default: 8 Serial Port or IP Address Default: Serial Port

Option

Setting

Number of Viewable Selects the number of devices to be Devices displayed. Connection Device Type Device Name Local ID Remote ID Selects the connection site.

Selects the device type to appear in the list. Range of supported devices. Allows you to name individual devices. You must define the Local ID. You must define the Remote ID

2009-2013 Schneider Electric. All Rights Reserved.

13

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Device Discovery

The Device Discovery option enables the EGX to discover Modbus devices residing on the serial port that are not in the Device List. Devices that have been previously entered into the Device List are validated regardless of the discovery range set. Discovery When you begin Device Discovery, the EGX queries the local serial port using a user-defined address range (see Figure 12 on page 15). Modbus ASCII or RTU protocol is used for discovery on the serial connection, depending on the current serial port configuration. If the device replies to the query, the Local ID is set to the current discovery address, and the device is given a default device name. The EGX then tries to identify the device type. If the EGX recognizes the device type of the discovered device, the EGX enters the recognized device type name in the Device Type field. If the EGX does not recognize the device type, the Device Type field is set to the default Modbus. A status field displays the discovery status. Validation All previously defined Device List entries for all connections (serial and remote, in and out of the discovery start and end address range) are validated during the discovery process. The validation protocol on the serial connection is determined by the current configuration of the device in the device list. Modbus TCP/IP protocol is used for validation of remote devices. The EGX displays the local ID, stored device name, and stored device type from the Device List, then queries the device. The device type identified by the query is displayed, then compared to what was previously defined. The status will then show if there is a difference found, or if the previously defined configuration is valid. NOTE: You can edit the device name and device type, and individually select which devices to store in the Device List. However, if logging is enabled for a device, you can only modify the name.

Action
1. From the Setup menu, click Device List. 2. To discover locally connected devices, click Discover.

Result
Opens the Device List page. Opens the Device Discovery page.

3. Enter a Start Address and End Address. Enters the discovery address range. NOTE: Devices previously entered in the device list with addresses (Local IDs) outside the discovery range will be validated. 4. Click Start Discover. (click Stop Discover Begins to discover all connected and defined to stop the process) devices. NOTE: Discovery only finds local serial Modbus devices connected to the EGX. Remote devices must be added manually. See Remote Device Connections on page 10. 5. Enter a new device name in the Name text Renames the device. box. 6. Check the Save checkbox next to the Selects or deselects a device entry to be saved device you want to save to the Device List. or removed. 7. Click Apply in the Device Discovery page. Saves to the device list the device configuration for all devices that have been marked to be saved.

14

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Figure 12:

Device Discovery

Table 8:
Option

Device Discovery Options


Description Setting

Start/End Address Defines the Modbus address range that will 1 to 247 be used to discover devices on the EGX Default: Start: 1 End: 10 serial port. Save Connection Defined Assigned Name Local ID Remote ID Status Allows you to save the selected device to the Device List. Displays the connection on which the device was discovered or validated. Lists the device type that was defined for this device. Allows you to assign the device type from the drop-down list. Allows you to enter a custom name for the device. Displays the Local ID. Displays the Remote ID. Enabled or Disabled Default: Enabled Serial Port or IP Address (for remote device validation).

Displays the discovery or validation status. Valid, Unknown, Failed, Found, Discovering, or Attempting

2009-2013 Schneider Electric. All Rights Reserved.

15

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Device Logging

Logging is available for every device type supported by the EGX. The EGX can log data received from both local and remotely connected devices at predefined intervals (5, 10, 15, 20, 30, and 60 minutes). Below is an explanation of how the EGX logs data and how to set up logging for a device.

Interval Data Logging

Many devices in a power monitoring system do not have the ability to record data in non-volatile memory. The EGX300 provides this data logging at predefined intervals for up to 64 serially and remotely connected devices. The EGX stores the recorded data in non-volatile FIFO (First In First Out) files. The logging capacity for each data-log file is variable and dependent on the selected logging interval. Logging capacity of each data-log file can be calculated by dividing the maximum possible number of recorded intervals a data-log file can contain (171,072) by the product of the number of topics logged and the intervals recorded per day. Log File Capacity = Intervals (max) / (topics per interval * intervals recorded per day) For example, the logging capacity for a device data-log recording three topics every 10-minutes would be determined as follows: Intervals Recorded Per Day = Minutes per day / Logging Interval (in minutes) = 1440 / 10 = 144 intervals Log File Capacity = Maximum Possible Intervals / (Topics logged per interval * Intervals recorded per day) = 171072 / (3 * 144) = 396 days

The logging capacity is dynamically calculated and displayed on the Topic Selection Page (see Table 9 for samples). Table 9: Sample Recording intervals
Log Capacity (in Days) for Designated Logging Intervals 5 Min Interval
1 2 3 4 5 6 594 297 198 148 118 99

# of Topics

10 Min Interval
1188 594 396 297 237 198

15 Min Interval
1782 891 594 445 356 297

16

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Set Up Interval Logging

Each device in the device list may be independently enabled for logging. Topics to log are unique to each device. To view interval data logs, see Device Logging on page 39. NOTE: To enable the Device Logging feature, there must be a time value selected in the Logging Interval drop-down window. We recommend that you disable the logging feature for the specific device being configured. To do this, see Figure 13 on page 17, and uncheck the logging check box for the device being selected.
Action
1. From the Setup menu, click Device Logging (see Figure 13). 2. See Figure 13 and check Logging for the device(s) you want to log. To select all devices, click select all, then click Apply. To deselect all devices, click clear, then click Apply. 3. Select the Logging Interval. 4. Click Apply. OPTIONS To customize logging content, enable device logging, then do the following: 1. Select a logging interval other than zero, and uncheck the specific device logging selection checkbox. 2. Click topics under Customize for the device you want to configure. 3. See Figure 14 and check the topics you want to log.

Result
Opens the Device Logging page. Selects the devices to log.

Selects the logging interval for the selected devices. Updates the EGX Device Logging settings.

Selects the device topics to be logged, then returns to the main Device Logging page. NOTE: If you change the default topics logged for a device, an asterisk (*) appears next to topics in the Customize column for that device. Changing the topics of a device log that has already been active will clear all previously logged data for that device. If needed, the data should be retrieved from the EGX prior to the changes.

To select all topics, click select all, then click Apply. To deselect all topics, click clear, then click Apply. To select the default topics, click Defaults at the bottom of the screen. To delete a data log, check Purge Data for the Selects the data logs to purge. one(s) you want to delete. NOTE: To purge a data log, the device 1. To select all devices, click select all, then must not have the Logging check box click Apply. enabled. 2. To deselect all devices, click clear, then click Apply. To disable logging, select a logging interval of Turns off the logging feature. zero, ensure the logging selections are unchecked, then click Apply.

Figure 13:

Device Logging Page

2009-2013 Schneider Electric. All Rights Reserved.

17

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Topics to Log

Topics for each device may be individually selected for logging.


Action
1. From the Device Logging page, click the topics link for the desired device. 2. See Figure 14 and check the topic(s) you want to log. To select all topics, click select all. To deselect all topics, click clear. To select the default topics, click Defaults. Saves the topic selection to log.

Result
Opens the topics selection page. Selects the topics to log.

3. Click Apply.

Figure 14:

Topic Selection Page

18

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Device Log Export

This option allows you to export device logs in three ways: by E-Mail, FTP, or HTTP. Each method is described in the following sections. NOTE: If the E-Mail, FTP, or HTTP servers are not located on the same Ethernet network segment as the EGX, be sure the EGX Default Gateway is properly configured. See Ethernet and TCP/IP Settings on page 4.

E-mail Export
Action
1. From the Setup page, click Device Log Export. 2. Select E-Mail as the mode of transport. 3. Check the Incremental check box. NOTE: If the transport is scheduled for Hourly or Logging interval, the incremental check box will be automatically selected. NOTE: If the Incremental check box is not selected, the whole log file is sent via email attachment on each scheduled interval. 4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are sent. Logging interval. 5. Depending on which options you selected Selects when the data logs are sent. in the previous step, select the time of day, day of the week, and/or the day of the month. 6. In the From Address text box, type the e- Enters from whom the e-mail was sent. mail address of the person administering the device. NOTE: A From e-mail address is required because most SMTP servers require it. 7. In the To Addresses text boxes, type the Enters the e-mail addresses of the recipients e-mail addresses (5 maximum) that will be receiving the data logs (one address per text box). 8. In the Server IP Address text boxes, enter Enters the address of the server delivering the the address of the outgoing mail server e-mail data logs. (0.0.0.0 to 255.255.255.255). NOTE: Contact your network administrator if you do not know the address of the Simple Mail Transfer Protocol (SMTP) server. 9. In the Server TCP Port text box, enter the Enters the outgoing mail server delivery port. outgoing mail server delivery port. Default: 25 10. If the SMTP server requires login information, enable the SMTP server requires login check box. NOTE: The EGX supports Plain, Login, CRAM-MD5, and Digest-MD5 access authentication. 11. If you have checked the SMTP server Records your SMTP server login information. requires login check box, enter your username and password in the text boxes. 12. Click Test E-mail to send a test e-mail using the parameters you set, or click Apply. NOTE: Clicking Test E-mail applies the log export e-mail settings and sends a test e-mail, and clicking Apply only applies the settings. Sends a test e-mail, and/or applies the log export e-mail settings. Allows you to enter SMTP server login information.

Result
Opens the Device Log Export page. Opens the E-Mail device log export options. Selects only new interval data logged since the last successful data export.

2009-2013 Schneider Electric. All Rights Reserved.

19

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Figure 15:

Device Log Export Page - E-mail

FTP Export
Action
1. From the Setup page, click Device Log Export. 2. Select FTP as the mode of transport. 3. Enable the Incremental check box. NOTE: If the transport is scheduled for Hourly or Logging interval, the incremental check box will be automatically selected. NOTE: If the Incremental check box is not selected, the whole log file is sent via FTP on each scheduled interval. 4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are Logging interval. transported. 5. Depending on which options you selected Selects when the data logs are transported. in the previous step, select the time of day, day of the week, and/or the day of the month. 6. In the Server IP Address text boxes, enter Enters the address of the server transporting the address of the outgoing FTP server the data logs. (0.0.0.0 to 255.255.255.255). NOTE: Contact your network administrator if you do not know the address of the File Transfer Protocol (FTP) server. 7. In the Directory text box, enter the directory. 8. Enter your username and password in the text boxes. 9. Enable the Passive check box. Allows you to enter directory information for the remote server. Records your server login information. Sets FTP file transfer mode to passive.

Result
Opens the Device Log Export page. Opens the FTP device log export options. Selects only new data logged since the last good send interval to be sent.

20

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Action
10. If you are exporting data to StruxureWare Energy Operation, click the Append MAC Address to File Name checkbox. NOTE: Selecting this checkbox prevents merging of data in the event that two files sent to Energy Operation have the same name.See Getting a Data Log on page 40 for details on log file format.

Result
Appends the MAC address to create a unique file name.

11. Click Test FTP to test the FTP parameters Sends a test file to the FTP server and you set, or click Apply. directory, and/or applies the FTP settings. NOTE: Clicking Test FTP applies the log export FTP settings and transfers a test file, and clicking Apply only applies the settings.

Figure 16:

Device Log Export Page - FTP

NOTE: If the transport is scheduled for Hourly or Logging interval, the incremental check box will automatically be selected.

HTTP Export
Action
1. From the Setup page, click Device Log Export. 2. Select HTTP as the mode of transport. 3. Enable the Incremental check box. NOTE: If the transport is scheduled for Hourly or Logging interval, the incremental check box will be automatically selected. NOTE: If the Incremental check box is not selected, the whole log file is sent via HTTP on each scheduled interval. 4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are Logging interval. transported. 5. Depending on which options you selected Selects when the data logs are transported. in the previous step, select the time of day, day of the week, and/or day of the month.

Result
Opens the Device Log Export page. Opens the HTTP device log export options. Selects only new data logged since the last good send interval to be sent.

2009-2013 Schneider Electric. All Rights Reserved.

21

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Action

Result

6. In the Server IP Address text boxes, enter Enters the IP address of the server transporting the address of the HTTP server. the data logs. NOTE: Contact your network administrator if you do not know the address of the Hyper Text Transfer Protocol (HTTP) server. 7. In the Server TCP Port text box, enter the Enters the outgoing delivery TCP port. HTTP server port. Default: 80 NOTE: If you want to export using a secure socket layer, enter the HTTPS Server TCP Port number, normally 443. 8. If you are using a proxy server, enter the IP Enters the IP address of the proxy server address in Proxy Server IP Address text transporting the data logs. boxes. NOTE: Contact your network administrator if you do not know the address of the proxy server. 9. In the Proxy Server TCP Port text box, enter the HTTP server port. NOTE: If you want to export using a secure socket layer, enter the HTTPS Server TCP Port number, normally 443. 10. In the Path text box, enter the path to the Enters the server script path. server script the web server will execute as a result of the EGX posting data to it. 11. In the Field Name box, enter the name Allows the EGX to push files to an existing under which the web server will expect the WWW server script. file name. NOTE: If there is no such requirement, use the default value datafile1. 12. In the Host Name box, enter the domain name of the host. Identifies a specific host on the WWW server if it is hosting multiple domains on a single IP address. (Blank by default) Enters the outgoing delivery TCP port. Default: 0

13. Enter your user name and password in the Records your server login information. text boxes. 14. If you want to export using a secure socket All device logs that are exported via HTTP will layer, check SSL. instead use the secure socket layer (HTTPS). 15. If you are exporting data to StruxureWare Energy Operation, click the Append MAC Address to File Name checkbox. NOTE: Selecting this checkbox prevents merging of data in the event that two files sent to Energy Operation have the same name.See Getting a Data Log on page 40 for details on log file format. 16. Click Test HTTP to test the HTTP parameters you set, or click Apply. NOTE: Clicking Test HTTP applies the log export HTTP settings and transfers a test file. Clicking Apply only applies the settings. Sends a test file to the HTTP server and directory, and/or applies the HTTP settings. Appends the MAC address to create a unique file name.

22

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Figure 17:

Device Log Export Page - HTTP

Date and Time

The Date and Time page allows you to set the date and time for the EGX.
Action
1. From the Setup menu, click Date and Time. 2. Configure the year, month, day, hour, minutes, and seconds. 3. Select the Time Zone Offset.

Result
Opens the Date and Time page. Sets up the date and time. Sets the clock to the selected time zone.

4. To set the clock to automatically adjust to Allows you to set the clock to adjust to Daylight Daylight Savings Time, enable the Enable Savings Time automatically. Automatic Daylight Savings Time Adjustment check box. 5. Enter the number, day, month, and hour to Sets the beginning and end of the Daylight begin and end Daylight Savings Time. Savings Time adjustment. 6. Click Apply. Saves the Date and Time settings.

Figure 18:

Date and Time Page

2009-2013 Schneider Electric. All Rights Reserved.

23

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Network Time Synchronization

Enabling network time synchronization allows the time and date of the EGX system clock to be set by a Network Time Protocol (NTP) server. NOTE: If the NTP server is not located on the same Ethernet network segment as the EGX, be sure the EGX Default Gateway is properly configured.

Action

Result

1. Select the Enable Network Time Reveals the SNTP Parameters section, and the Synchronization check box in the Date and last successful time synchronization. Time page. 2. Configure the time zone offset, poll interval, and the primary and secondary NTP server IP addresses (see Table 10). 3. Click Apply. Sets up the SNTP parameters.

Saves the SNTP settings.

Figure 19:

Enable Network Time Synchronization

Table 10: SNTP Parameters Settings


Option
TIme Zone Offset Enable Automatic Daylight Savings Time Adjustment

Description
The time is set based on the Coordinated Universal Time (UTC) value selected. Allows you to define when Daylight Savings Time begins and ends.

Setting
UTC-12:00 to UTC+13:00 Default: UTC (GMT) First to Fifth or Final, Sunday to Saturday, January to December, 0:00 to 23:00 Default: Begins Second Sunday of March at 2:00. Ends Second Sunday of November at 2:00. 1 hour to 1 week Default: 1 week

Poll Interval Primary NTP Server IP Address Secondary NTP Server IP Address

Controls how often the EGX contacts the NTP server for the correct time.

The IP address of the primary NTP server 0.0.0.0 to 255.255.255.255 the EGX contacts for the correct time. Default: 0.0.0.0 The IP address of the secondary NTP server the EGX contacts for the correct time. 0.0.0.0 to 255.255.255.255 Default: 0.0.0.0

SNMP Parameters

The EGX supports SNMP, allowing a network administrator to remotely access an EGX with an SNMP manager and view the networking status and diagnostics of the EGX in the MIB-II format.

24

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Action
2. Check Enable SNMP to turn ON the simple network management protocol. Activates SNMP.

Result

1. From the Setup menu, click SNMP Parameters. Opens the SNMP Parameters page.

3. Enter the system contact, system name, system Enters the SNMP system information and location, read-only community name, and the community access names. read-write community name. 4. Click Apply. Saves the SNMP settings.

Figure 20:

SNMP Parameters Page

Modbus TCP/IP Filtering

This function allows the administrator to assign the level of access Modbus TCP/IP clients have to the devices (local or remote) connected to the EGX. NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that can be set to Read-only or None. Setting it to Read-only allows any Modbus TCP/IP client not in the filtered list to access serial slave devices with read-only access. Setting it to None blocks all Modbus TCP/IP clients not in the filtered list.
Action
1. From the Setup menu, click Modbus TCP/IP Filtering. 2. Check Enable Filtering. 3. In the IP address column, enter the Modbus TCP/IP client address

Result
Opens the Modbus TCP/IP Filtering page. Activates filtering. Enters an IP address for a Modbus TCP/IP client that will have access to the devices connected to the EGX.

4. In the Access Level column, select Read- Selects the access level for the corresponding only or Full. IP address. When set to Read-only, the following Modbus TCP/IP function codes are allowed: Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100 Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18, 2B, 64 5. Repeat steps 3 and 4 to add more IP addresses. 6. Click Apply. Continues adding IP addresses for filtering. Saves the Modbus TCP/IP address filtering list.

2009-2013 Schneider Electric. All Rights Reserved.

25

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Figure 21:

Modbus TCP/IP Filtering Page

Documentation Links

The EGX supports two types of documentation links: 1. Local file access (documentation stored onboard the EGX) 2. External URL access. NOTE: Local file documents you want to appear on the Documentation web page must be placed in the EGX www/documentation folder using FTP.
Action
1. From the Setup menu, click Documentation Links. 2. For File Access: Check Enabled for the File Name link(s) you want to enable. For URL Access: Check Enabled for the URL link(s) you want to enable. 3. Check New Window if you want the selected files and URLs to open in a new window when clicked. 4. Name the documentation link title in the Link Text text box. 5. Click Apply. Checks which files and URLs open in a new window when clicked. Sets the documentation link title that will appear on the Documentation page. Updates the EGX Documentation Link settings.

Result
Opens the Documentation Links page. Checks which files and URLs appear on the Documentation page.

Figure 22:

Documentation Links Page

NOTE: For information on accessing the loaded documentation, see Documentation on page 48.

26

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

User Accounts

EGX users are assigned user names and passwords. Each user belongs to a group, and each group has access rights to the EGX Web pages assigned by the EGX administrator. NOTE: There are two default user accounts: Administrator (the default password is Gateway) and Guest (the default password is Guest).
Action
2. If you want to change a group name, type a new name in one of the Groups text boxes (the Administrator group name cannot be changed). 3. In the Users section, enter a Name (1 to 24 characters) and Password (0 to 12 characters) for a new user. NOTE: User names and passwords are case-sensitive and can contain only alphanumeric characters.

Result
Enters a new group name.

1. From the Setup menu, click User Accounts. Opens the User Accounts page.

Enters the name and password for a user. The EGX300 checks the strength of the password, displaying both a color and textual indication of strength: Red = Blank Password/ Weak Password Yellow = Medium Strength Password Blue = Strong Password Green = Very Strong Password Selects the group and language for a user. Continues adding users. Saves all of the user account settings.

4. Select a group and the default language for the new user. 5. Repeat steps 3 and 4 for each additional user you want to add. 6. Click Apply.

Table 11: EGX accounts and passwords


Account
Administrator Guest User-defined accounts (up to 11 accounts possible) Gateway Guest No default Password is user-defined

Default Password

Figure 23:

User Accounts Page

2009-2013 Schneider Electric. All Rights Reserved.

27

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Web Page Access


Action
2. Select the access level (None, Read-only, or Full) that each user group will have for the web pages. 3. To allow Guest access to the web page, select Read-only under the Guest column. NOTE: If the Guest group is Read-only, other groups may only be set to Read-only or Full. 4. Repeat steps 2 and 3 for the options in each section. 5. Click Apply. Selects the access level for each web page. Saves the password settings.

Result
See Table 12 below for an explanation of access levels for each group. Allows the default Guest group to access the web page.

1. From the Setup menu, click Web Page Access. Opens the Web Page Access page.

Table 12: Group Access


Group
Administrator

Access
Full access to all web pages NOTE: We recommend that you change the default administrator password for system security the first time you log in. Read-only access to selected web pages. Choosing from the following options, the administrator assigns web page access for each group. Access levels are as follows: None: a group has no access to selected web page Read-only: password grants a group read-only access to the selected web page Full: a group has the same access as the Administrator group to the selected web page

Guest Three user-defined groups

Figure 24:

Web Page Access Page

28

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Add/Remove Custom Web Pages

Custom web pages and other file types can be transferred from your computer to the EGX via FTP. Files sent by FTP to the www/monitoring, www/maintenance, or www/control directories with extensions of .htm, .html, or .shtml will be automatically secured. Each folder has a corresponding link on the menu bar in the web interface. When the link is clicked on the menu bar, the web pages you added will appear in the menu on the left side of the browser window under Custom Pages. NOTE: You cannot create new folders inside of the Monitoring, Control, or Maintenance folders. After custom web pages or other files have been transferred to the EGX with FTP, they can be added and removed from the web interface without removing them from the EGX by using the Add/Remove Web Pages page. This page is opened from the Web Page Access page.

Adding Web Pages Using FTP

Action
1. Launch Windows Explorer, type ftp:// and the IP address of the EGX (for example, ftp://169.254.0.10) in the Address text box, then press Enter. 2. Type the user name Administrator and the administrator password in the text boxes, then click Log On. 3. Open a new Windows Explorer window, locate the custom web page you want to send to the EGX, right-click it, then click Copy. 4. Switch back to the EGX Windows Explorer window you opened in Step 1, then open the folder where the web page will be copied (for example, /www/monitoring/).

Result
Opens the Log On As dialog box.

Opens an FTP session with the EGX.

Copies the file to the clipboard.

Opens the folder where the web page will be stored on the EGX.

5. Right-click in the right pane of the Windows Copies the custom web page to the EGX. Explorer window, then click Paste. NOTE: Instead of copying and pasting the file, you can drag-and-drop the file into Windows Explorer. 6. Click Close on the Windows Explorer window. Closes Windows Explorer.

Deleting Web Pages Using FTP


Action
1. Launch Windows Explorer, type ftp:// and the IP address of the EGX (for example, ftp://169.254.0.10) in the Address text box, then press Enter. 2. Type the user name Administrator and the administrator password in the text boxes, then click Log On.

Result
Opens the Log On As dialog box.

Opens an FTP session with the EGX.

3. Open the folder where the custom web Opens the folder where the custom web page page is located, right-click the file you want is located, then deletes file. to delete, then click Delete. 4. Click Close on the Windows Explorer window. Closes Windows Explorer.

2009-2013 Schneider Electric. All Rights Reserved.

29

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Add/Remove Web Pages to/from the Web Interface

Action
1. From the Setup menu, click Web Page Access. 2. Click Add/Remove Web Pages (see Figure 25).

Result
Opens the Web Page Access page. Opens the Add/Remove Web Pages page.

3. If you added custom web pages to any of Selects or deselects a custom web page. the EGX folders, you will see a list of file names underneath the name of each folder. Select the web pages you want your users to see. Deselect web pages you do not want your users to see. NOTE: Deselecting a web page does not delete it from the EGX. 4. Click Apply. Adds or removes a custom web page from the EGX web interface.

Figure 25:

Add/Remove Web Pages Page

Preferences

This option allows each EGX to be individually customized.


Action
1. From the Setup menu, click Preferences. 2. Enter the equipment name, default home page, real time sample rate, and communications check rate. 3. Click Apply.

Result
Opens the Preferences page. Sets the preferences.

Updates the EGX Preferences settings.

Figure 26:

Preferences Page

30

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Table 13: Preferences Settings


Option
Equipment Name

Description

Setting

Allows you to enter a custom name for Default: Powerlogic the EGX and associated equipment. This EGX300 name will be used in the web interface banner. Allows you to select the default homepage. Home, Circuit Summary, Load Current Summary, Demand Current Summary, Power Summary, or Energy Summary Default: Home

Default Home Page

Real Time Sample Rate Controls how often data is read from the 5 to 60 seconds device(s) in the standard Monitoring Default: 5 seconds Table views. Communications Check Controls how often a communications Rate check is performed while the browser is displaying real time readings in the standard Monitoring Table views. This function will attempt to automatically bring any out of service devices back into service. Disabled, 5 to 30 minutes Default: 15 minutes

Viewable Device Types

The Viewable Device Types page provides a means of managing the device types available for user selection in the Device List Setup web page. Because the EGX300 supports many different device types, removing device types from the list of Available Device Types may simplify configuration of the Device List Setup web page.
Action
1. From the Setup menu, click Viewable Device Types. 2. Select the device types to make available for the device list configuration. NOTE: Click Select All to enable all devices and Clear to disable all devices. NOTE: Device Type Availability may not be changed for devices that are currently in use. 3. Click Apply. Saves the Viewable Device Type settings.

Result
Opens the Viewable Device Types page. Selects device types to be made available for device list configuration.

2009-2013 Schneider Electric. All Rights Reserved.

31

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Figure 27:

Viewable Device Types Page

Audit Trail

The Audit trail is a time-stamped sequence of records or messages. It records configuration change, error, and failed authentication events; and it identifies the user who initiated the event. Use the Audit Trail page to set up the four report groups and message channels. For each channel, you choose the report group(s) for which you want to see messages. When you choose a report group for a channel, you will see any of the messages that are generated in that report group. The message channels are:

EGX on-board maintenance log file Remote Syslog server (Syslog is a standard for logging messages) E-Mail

All messages are date-time stamped, and they include the report group and user identifying information. The Audit Trail page is divided into three boxes that correspond to the three message channels: Maintenance Log, Syslog, and E-Mail. (See Figure 28 on page 34.) You can independently configure the messages that are sent to each channel. From the Setup window, click Audit Trail. The Audit Trail page opens. Follow instructions in the table below.

32

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Table 14: Audit Trail Setup


Option
Maintenance Log Controls the report types for which you want messages to display in the Message Log. Syslog Server IP Address. As messages are generated, they Enter the IP address for the will be forwarded to the server remote server to which you that you indicate. want messages to be forwarded. Syslog messages will be sent from this server UDP port. The four report types for which messages can be forwarded. Provides a rough clue as to the location in the system that generated the message. Will display in the Syslog. Tells the user the relative importance of the message. You must determine for your facility the importance of each type. Enter the UDP port number for this IP address. Default = 514. Check the report types for which you want messages to be forwarded. Choose the appropriate category. As messages are generated, they Check the report options will display in the EGX on-board that you want to include. maintenance log. Default: no options checked

Description

Setting

Server UDP (user datagram protocol) port Report

Facility drop-down list

Severity drop-down list

Choose the appropriate category.

E-Mail From Address When messages are generated, the originator e-mail address will display in the from field. The body of the e-mail will include: EGX IP address, report group name, user name, user IP address, and the message from the report group. Enter the From e-mail address (address of the originator) for e-mails. Maximum 49 characters.

To Addresses

When messages are generated, they will be sent to the recipient e-mail address(es).

Enter the To e-mail address (address of the recipient of all message emails). Maximum 49 characters per address. If you do not enter a server IP address, no e-mails will be sent. Enter the TCP port number. The default is 25. Check the box to begin adding login information. Type the username required by the SMTP server (max 31 characters).

Server IP Address

This is the IP address for the server where the e-mails will be sent. This is the TCP port number for the server IP address. Use this check box to enable login for receiving e-mails. The SMTP server requires login. This is the user name the EGX will use to log on to the SMTP server.

Server TCP Port SMTP server requires login

Username

Password

This is the password the EGX will Type the password required use to log on to the SMTP server. by the SMTP server (max 31 characters). These are the report types for which messages can be forwarded. You can check as many as you want. Check the report types for which you want messages.

Report

Defaults/Apply

Click Apply to save the entries Click Apply or Defaults. you have made. Click Defaults to return each field to its default state.

2009-2013 Schneider Electric. All Rights Reserved.

33

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4 06/2013

Figure 28:

Audit Trail Setup

34

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

System Access Point

The system access point provides a means of discovering and linking to other Schneider Electric devices connected to the network. This feature is configured to run by default, with no need for additional configuration. Use this setup screen to enter the group IP address and related information.
Action
1. From the Setup menu, click System Access Point. 2. Enabled

Result
Opens the System Access Point window. When checked, EGX300s with the same Group IP Addresses will be able to discover each other. Default = Enabled. Type the port number (from 165535) for the UDP port used by the System Access Point discovery. Default = 59. Type the group IP address, which will support multicast or unicast addresses. Default = 224.0.1.2. This is the period of time between Hello messages emitted by this EGX300 announcing its presence to other Schneider Electric System Access devices on the network. 1 65535 seconds, default = 300 seconds. This is the period of time that Hello messages sent by this EGX300 should be held by recipients before considering this EGX300 unavailable. From 2 to 65535 seconds, default = 600 seconds. You can control how wide an area of the network will be included to discover other devices. This is controlled by the number of times that the multicast is allowed to be forwarded to others. The range of permitted router hops is 1255. Default = 1. EGX300s in a group can be divided into communities. EGX300s with the same group IP address and community number are able to discover each other. Setting the community number to `0' allows an EGX300 to discover all EGX300s with the same group IP address without regard to the community setting. Default: 0

3. UDP Port

4. Group IP Address

5. Hello Time

6. Hold TIme

7. Multicast Time-to-Live

8. Community

9. Defaults/Apply

Click Apply to save your entries; click Defaults to return to the defaults that are listed.

Figure 29:

System Access Point Setup Page

2009-2013 Schneider Electric. All Rights Reserved.

35

PowerLogicTM Ethernet Gateway EGX300 Monitoring

63230-319-216B4 06/2013

MONITORING

The EGX provides screen displays to view real-time data and trends along with historical data log trends.

Real Time Data

The Real Time Data pages provide basic readings of selected devices in real time, as well as device summaries.

Single Device Pages

To view a table of real time data, go to the Monitoring menu and select a device under Real Time Data > Single Device Pages.

Basic Readings Settings


Action Result
1. At the top of the display, select either Load Current, Selects the quantities to be displayed Power, Voltage LL, or Voltage LN to be displayed on the Analog Gauge graphic display. on the Analog Gauge graphic display. NOTE: Analog gauges are not available for all device types. 2. By default, the gauges will automatically adjust their Controls the display range of the display range. For a fixed range, select Range. Analog Gauges. Instructions for configuring the analog gauge range are listed in the next table. 3. Click Apply. Updates the Gauge selection for the device page.

Figure 30:

Basic Readings Page

36

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Monitoring

Analog Gauge Range

The range of the Graphic Analog Gauges on the Basic Readings page may be configured or set to scale automatically (Figure 31).
Action Result

1. Under Enable Auto Scale, check the Enables auto scale for selected devices. devices you wish the gauges to auto-scale. NOTE: Click Select All to enable auto scale for all devices and Clear to disable auto scale for all devices. 2. For devices with auto scale disabled, enter Set gauge range. the Min and Max limits for each gauge type. 3. Click Apply. Updates the Auto Scale settings.

Figure 31:

Range Setup Page

Summary Device Pages

The Summary Device table views provide summaries of one or more selected devices.
Action
1. From the Monitoring menu, click Summary Device Pages. 2. Select which summary page you want to view. 3. Select a device(s) from the Available Devices list, then click Next (see Figure 32). NOTE: Click >> to select all available devices.

Result
Expands tree for summary page selection choices. Opens the device selection list. Selects a device(s) for the summary options.

Figure 32:

Device Selection Page

Figure 33:

Circuit Summary Page

2009-2013 Schneider Electric. All Rights Reserved.

37

PowerLogicTM Ethernet Gateway EGX300 Monitoring

63230-319-216B4 06/2013

Trending

To view a real time trend of multiple devices and topics, go to the Monitoring Menu and select Real Time Data > Trending.
Action
1. From the Monitoring menu, select Real Time Data. 2. Select Trending. 3. Select Real Time Trending. 4. Select up to four device from the Available Devices list. 5. Select a topic(s) from the Available Topics list. NOTE: Only topics common to all selected devices are available for trending. The maximum number of topics to trend is dependent on the number of devices selected. The product of the selected devices and topics must be 8 or less. 6. Click Next to open the Real Time Trending display page. Real Time Trending display page opens. 7. To set the trending parameters, continue to the procedure in the next table and refer to Figure 35. Allows trending parameters to be set.

Result
Expands the data tree for real time data option selection. Expands the data tree for time trending option selection Opens the Real Time Trending setup page. Selects devices for trending. Selects topics for trending.

Figure 34:

Select Devices and Topics

Action
1. Select Absolute or Relative trending. NOTE: Absolute redraws the graphs x-axis after each sample, filling it with all the data collected since the start of the trend. Relative updates the graph with the latest data after each sample while the x-axis stays constant to show the overall trend time selected. 2. Choose a trend time of 1 to 15 minutes. This will be the duration of the trend. NOTE: Data samples are taken as fast as possible but may take longer depending on the communications load on the serial sub-net and/or remote devices.

Result
Selects graph mode.

Selects the amount of time of the trend.

3. Select Start Sampling to start the trending of the selected Starts trending. device topics. NOTE: Trending may be stopped before reaching the trend time by clicking Stop Sampling. If after stopping the sampling, Start Sampling is pressed, a new trend is started.

38

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Monitoring

Action
4. Press Data Points to view a log of all the sampled topics recorded during the trend time. NOTE: After each interval, the Present value of all topics along with the calculated Min, Max, and Average value is populated in the table below the graph.

Result
Displays a log of all topic values sampled during the trend.

5. Press New Topics to reselect devices and topics to trend. Navigates back to the Real Time Trending setup page.

Figure 35:

Real Time Trending

Device Logging

Device Logging Pages provide graphic and table representations of selected device log data. For more details on configuring device logging, see Device Logging on page 16.

Single Device Pages

Single Device pages provide graphic and table representations of data logged from a single device.
Action
1. From the Monitoring menu, click Device Logging. 2. Under Device Logging, click Single Device Pages. 3. Select a device from the Device Logging list. 4. To view a data range, select a range from the data range drop down list. 5. Hold down the left mouse button and drag a selection box around a graph area to zoom in on it.

Result
Expands tree to show available device logging choices. Expands tree to show available devices that have logged data available for viewing. Displays the device log for the selected device. Plots the selected data range. Zooms in on the selected graph area.

6. To return to the original full view, type Z on The view zooms out. your keyboard, or double-click on the graph. 7. Click Data Points to view the selected interval data log table (see Figure 37 below). Opens the selected Interval Data Log table.

8. To view different topics, click New Enables the display of the selected topic(s). Topic(s). Enable the check box(es) of the topic(s) you wish to display, and then click Apply.

2009-2013 Schneider Electric. All Rights Reserved.

39

PowerLogicTM Ethernet Gateway EGX300 Monitoring

63230-319-216B4 06/2013

The data logged from each device is displayed in a web page in a time-trend chart format. The time-trend chart is preconfigured to display data from the Last Full Day, Last Full Week, Last Full Month, or All Data. Energy parameters are logged as accumulating values but are displayed as incremental values on an interval basis. All other parameters are logged and displayed as the actual value recorded. Figure 36: Interval Data Log Graph

Figure 37:

Interval Data Log Data Points Table

Getting a Data Log

Interval data logs can be retrieved using the methods in Table 15: Table 15: Interval data log retrieval methods and file formats
Retrieval Method
FTP Data points button Microsoft WebQuery E-mail HTTP HTML HTML CSV CSV

File Format Retrieved


Comma separated variable (CSV)

To view a list of all available log files, follow steps 2 through 4 in the section Getting an Interval Data Log using FTP on page 42. Files will be in the format: Device Name_Local ID.csv where Device Name is the name given to the slave device and Local ID is the numerical Local ID assigned to it. For example, a device named Building 1 Utility Entrance with a Local ID of 3 would be Building 1 Utility Entrance_3.csv. When log files are exported the date and time are appended to the file name in the following format: _YYYYMMDDHHMMSS. For example, Building 1 Utility Entrance_3_20100218115216.csv. This indicates that the file was exported on 2010 February 18 at 11:52:16 AM.

40

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Monitoring

Log Format

Data is logged in the following format (see Figure 38 on page 41): Table 16: Interval data log format
Row
1

Data in CSV Format

Description

(BOM)Gateway Name,Gateway This row contains the column headings SN,Gateway Address,Device Name,Device for the information in row 2. Local ID,Device Type Name,Logging Interval NOTE: (BOM) The first three bytes of the file will be a 3-character Byte Order Mark indicating UTF-8. EGX300SD,23227,157.198.184.116,Building This row contains the information about 1 Utility Entrance,3, CM4000,15 the EGX and the logged device. This row is blank. ,,,Topic ID 1,Topic ID 2,Topic ID 3 This row contains the column headings for the topic IDs in row 5. A topic ID is a numerical reference to the quantity being logged. The name given to a quantity may differ slightly between devices and languages. Topic IDs are used to identify the quantity, regardless of the device or language. The first three commas are used for layout purposes in a spreadsheet application. This row contains the topic IDs of the values logged.

2 3 4

5 6 7

,,,1617,1621,1625 This row is blank.

Error,UTC Offset (Minutes),Local Time This row contains the column headings Stamp,Apparent Energy (kVAh),Real Energy for the data logged in rows 8 and higher. (kWh), Reactive Energy (kVARh)

8 and These rows contain the logged data. higher 0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15 0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15 0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

If you use a spreadsheet application to view the CSV file, your data should look similar to Figure 38 on page 41. Figure 38: Interval Data Log Opened in a Spreadsheet Application

2009-2013 Schneider Electric. All Rights Reserved.

41

PowerLogicTM Ethernet Gateway EGX300 Monitoring

63230-319-216B4 06/2013

Error Codes for Data Logs

The below error codes may be seen when troubleshooting data logs (see Figure 36 on page 40 and Figure 37 on page 40):
Error Code
19 25

Definition
Communication Error occurred (for example: CRC, protocol, or exception). Timeout occurred when a request was sent without receiving a corresponding response within the allowed time. Invalid data.

Result
Logging is left enabled unless the last interval was missed. Logging is left enabled unless the last interval was missed.

38 100

Interval time expired before data could be recorded. Missed interval.

Contact Technical Support if you need assistance in resolving these or other error conditions.

Getting an Interval Data Log using FTP

You can use FTP to retrieve a data log file by connecting to the EGX via FTP and transferring the .csv file, as shown in the steps below. NOTE: If you want the EGX to automatically send the data log file via FTP, the Device Log Export must be configured for FTP (see FTP Export on page 20).
Action Result

1. Create a folder on your computer, such as Creates a folder to store the EGX data log. c:\egx_logs. 2. Launch Windows Explorer, type ftp:// and the IP address of the EGX in the Address text box (for example, ftp://169.254.0.10), then press Enter. Opens the Log On As dialog box.

3. Type the user name Administrator and the Opens an FTP session with the EGX and administrator password in the text boxes, displays the files stored in the EGX. then click Log On. 4. Navigate to the directory /logging/data on Opens the data logging directory on the EGX. the EGX 5. Copy the log file, then paste it into the folder you created in step 1. Copies the data log to your folder.

Getting an Interval Data Log Using the Data Points Button

Action
1. From the Device Logging web page (see Figure 36), click Data Points. 2. Press CTRL+A, then press CTRL+C. 3. Open Excel, then press CTRL+V.

Result
Opens a new window displaying the logged data. Selects all of the data, then copies the data to the clipboard. Pastes the data into an Excel spreadsheet.

42

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Monitoring

Getting an Interval Data Log Using the Microsoft Web Query Feature

Action
1. Launch your web browser.

Result
Opens the web browser.

2. Verify that the log file is available by typing Opens the data log page. the EGX300 IP address followed by /stream/devlog_data.html?device=x (where x is the device local ID). 3. Launch Excel, then click Data > Import External Data > New Web Query. NOTE: The path shown is typical for Microsoft Excel 2003. 4. In the New Web Query dialog box, type the address of the log you entered in step 2, then click Go. 5. Click the outer-most arrow to select all of the data, then click Import. 6. Click OK. Opens the data log file. Opens the Excel New Web Query dialog box.

Selects the data, then opens the Import Data dialog box. Imports the data.

NOTE: If you want to display the latest data each time you open the spreadsheet, click Properties on the Import Data dialog and select Refresh data on file open.

Getting an Interval Data Log Using E-mail

The EGX must be configured to deliver data logs to an e-mail address. For more information, see E-mail Export on page 19.

Getting an Interval Data Log Using HTTP

The EGX must be configured to deliver data logs to a web server. For more information, seeHTTP Export on page 21.

Summary Device Pages

The Summary Device views provide summaries of one or more selected devices.
Action
1. From the Monitoring menu, click Device Logging. 2. Under Device Logging, click Summary Device Pages. 3. Under Summary Device Pages, click Multiple Devices, Single Topic. 4. Select a device from the Available Devices list. NOTE: A maximum of four devices may be selected. 5. Select a topic from the Available Topics list. NOTE: Only topics that are common between the selected devices are available. 6. Select Next. 7. Hold down the left mouse button and drag a selection box around a graph area to zoom in on it. Opens the Multiple Devices, Single Topic display page Zooms in on the selected graph area. Selects the topic to display for each selected device. Opens the setup page for the Multiple Devices, Single Topic page. Selects the devices for the summary options.

Result
Expands the tree for device logging choices.

8. To return to the original full view, type Z on The view zooms out. your keyboard, or double-click on the graph.

The topic logged from the selected devices is displayed in a web page in a time-trend chart format. The time-trend chart is preconfigured to display data from the Last Full Day, Last Full Week, Last Full Month, or All Data.

2009-2013 Schneider Electric. All Rights Reserved.

43

PowerLogicTM Ethernet Gateway EGX300 Monitoring

63230-319-216B4 06/2013

Energy parameters are displayed as incremental values on an interval basis. All other parameters are logged and displayed as the actual value recorded.

Figure 39:

Multiple Devices, Single Topic Setup Page

Figure 40:

Multiple Devices, Single Topic Trend Page

44

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Monitoring

Dashboards

The EGX supports four categories of dashboards that display energy consumption information aggregated over time. Table 17 lists the dashboards and their subsets. Table 17: Dashboard Types
Dashboard By Hours Past Day by Hours Present Day by Hours Present Day over Past Day by Hours By Days Past Week by Days Present Week by Days Present Week over Past Week by Days Past Month by Days Present Month by Days Present Month over Past Month by Days By Weeks Past Quarter by Weeks Present Quarter by Weeks Present Quarter over Past Quarter by Weeks Trailing 13 Weeks by Weeks By Months Past Year by Months Present Year by Months Present Year over Past Year by Months NOTE: Requires each device data log file to have the capacity for two years of historical data. See Interval Data Logging on page 16 for more information. Trailing 12 Months by Month Subset

Viewing a Dashboard
Action
1. From the Monitoring menu, click Dashboards.

Result
Displays dashboard menu (see Figure 41).

2. Select a device from the Device drop-down Selects device for displaying data. list. NOTE: The dashboard displays data from a single device. 3. Select a topic from the Topic Name dropdown list. NOTE: Topics are limited to incremental consumption topics provided by the device. 4. Select time parameters from the Time drop- Selects time range of logged data for selected down list. topic. 5. Click Apply. Opens the selected dashboard. Selects topic to be graphed.

Figure 41:

Dashboards Menu

2009-2013 Schneider Electric. All Rights Reserved.

45

PowerLogicTM Ethernet Gateway EGX300 Monitoring

63230-319-216B4 06/2013

The data from each dashboard displays in a web page in bar graph format. As you hover over a bar in the graph, the data point value for the selected interval displays (Figure 42). Figure 42: Dashboard Graph

Figure 43:

Dashboard Table

Getting Dashboard Data Using the Data Points Button

You can save data from a dashboard in a spreadsheet application, as shown in the steps below.
Action Result

1. From the dashboard containing the desired Displays data points for the selected dashboard data, click Data Points. (Figure 43 on page 46). 2. Press CTRL+A, then press CTRL+C. 3. Open Excel, then press CTRL+V. Selects all of the data, then copies the data to the clipboard. Pastes the data into an Excel spreadsheet.

Saving a Dashboard Link

You can save a dashboard link to avoid having to select from the main menu each time you access the dashboard. Table 18 describes the methods for saving dashboard link. Table 18: Saving a Dashboard Link
Option Browser Bookmark Description Allows users to access the saved dashboard on the computer where the bookmark is created. Allows all EGX users to access a saved dashboard from the Documentation page. Allows users to send a dashboard URL in the body of an E-mail. Setting Follow instructions for setting a bookmark in your preferred browser. See Documentation Links on page 26 for setting URL access. E-mail recipient must have an EGX user account to view a dashboard. See User Accounts on page 27.

Documentation Link

Email

46

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Monitoring

Saving a Dashboard as an Image

You can save a dashboard graph as an image using the steps below.
Action
1. Follow the steps in Viewing a Dashboard on page 45. 2. Click Show as Image... in the top right corner of the page (Figure 44). 3. Right click on the image and select Save image as...

Result
Displays the dashboard graph. Opens a new window with the dashboard displayed as an image. Opens the Save As dialogue box.

4. Enter a file name, select a location to save Saves the image. the file, and click Save. NOTE: The default file type is PNG image. To change the file type, replace .png in the file name field with your preferred extension.

NOTE: This feature is not available with Internet Explorer version 8 or earlier. Figure 44: Saving a Dashboard Image

2009-2013 Schneider Electric. All Rights Reserved.

47

PowerLogicTM Ethernet Gateway EGX300 Documentation

63230-319-216B4 06/2013

System Access Point

The EGX can discover and provide links to EGX300s and other Schneider Electric devices that are connected to the network. This provides an access point to a system of networked Schneider Electric devices. The System Access Point page lists each of the discovered Schneider Electric devices as a hyperlink. As you hover over a device in the list, additional details about the device displays to the left of the listing. Click any device to go to the log-in page for that device.

Figure 45:

System Access Point Page, Showing Device Detail

DOCUMENTATION

The Documentation page allows you to access information that has been stored as files on the EGX and as URL web links. For information on loading documentation links, see Documentation Links on page 26. To open a documentation link, click the Documentation link at the top of the page, then select the link you want.

Figure 46:

Documentation Page

48

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Control

CONTROL

The EGX has the ability to manually execute one or more of a set of predefined reset commands per device type.
Action
1. From the Control menu, click Resets.

Result
Opens the Resets page.

2. Select a device in the Resets list you want Selects a device and shows its reset options, to view or reset. and the date and time of the last reset. 3. Select the device parameters you want to reset. 4. Click Reset. Selects the reset operation to be performed on the selected device. Send reset command(s) for the requested reset(s) to the selected device, and displays the status.

Figure 47:

Resets

NOTE: The date and time shown for the Date/Time parameter is the current date and time in the selected device. If this parameter is selected to be reset, the EGX date and time will be sent to the device. Date/Time values are reported only when the device supports them. For example, if a device does not support the Min/Max value for "Date/Time Last Reset," the "Min/Max" value will not be populated here.

DIAGNOSTICS

To access the Diagnostics web page links, click Diagnostics on the EGX menu bar.

Statistics

This page shows accumulated readings since the EGX was last activated. If power to the EGX is lost or the device is reset due to a configuration change or other event, all cumulative values reset to zero.
Action
1. From the Diagnostics menu, click Statistics. 2. View the data. 3. Click Reset.

Result
Opens the Statistics page (see Figure 48 below). See Interpreting Statistics below. Resets the EGX cumulative diagnostic data to 0.

2009-2013 Schneider Electric. All Rights Reserved.

49

PowerLogicTM Ethernet Gateway EGX300 Diagnostics

63230-319-216B4 06/2013

Figure 48:

Statistics Page

50

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Diagnostics

Interpreting Statistics
Statistic
Ethernet Link Status A status string that represents the speed and duplex setting being used to communicate with the linking partner. A counter that increments each time a frame is successfully transmitted. A counter that increments each time a frame is retransmitted due to collision detection. A counter that increments each time a frame is not able to be sent due to reaching the maximum collision status based on the Truncated Binary Exponential Backoff algorithm. A counter that increments each time a frame is successfully received. A counter that increments each time a frame is received that has a checksum/CRC that does not match what is calculated. A counter that increments each time a frame is received that has a checksum/CRC error and does not end on an 8-bit frame boundary. A counter that increments each time a frame is received that is larger than the allowed maximum size defined in the standards (frames larger than 1518 bytes). A counter that increments each time a frame is received that is smaller than the allowed minimum size defined in the standards (frames smaller than 64 bytes).

Description

Frames Transmitted OK Collisions Excessive Collisions

Frames Received OK CRC Errors

Alignment Errors

Frames Too Long

Frames Too Short

Modbus TCP/IP Server Frames Sent Frames Received Protocol Errors Active Connections1 A counter that increments each time a frame is sent. A counter that increments each time a frame is received. A counter that increments each time an ill-formed message is received. A status value that represents the number of connections that are active at the moment the diagnostics page is refreshed. A maximum of 64 connections are supported. Clicking Active Connections opens a new window with a list of all of the active client connections. A counter that increments each time a connection is made to the EGX. A status value that represents the maximum number of connections that were active at any given moment. A counter that increments each time a read request message is received. A counter that increments each time a write request message is received. A counter that increments each time a reply message is sent.

Accumulative Connections Maximum Connections

Inbound Read Messages Inbound Write Messages Outbound Reply Messages Client Frames Sent Frames Received Protocol Errors
1

A counter that increments each time a frame is sent. A counter that increments each time a frame is received. A counter that increments each time an ill-formed message is received.

Click the link for additional, detailed information.

2009-2013 Schneider Electric. All Rights Reserved.

51

PowerLogicTM Ethernet Gateway EGX300 Diagnostics

63230-319-216B4 06/2013

Statistic
Timeouts

Description
A counter that increments each time a request message is sent without receiving a corresponding response message within the allowed time. Timeouts are typically the result of configuration errors or a non-responsive device. A counter that increments each time the connection is lost. A counter that increments each time an exception is received. A counter that increments each time a read request message is sent. A counter that increments each time a write request message is sent. A counter that increments each time a reply message is received. A detailed table providing remote and serial statistics per device.

Connection Timeouts Exceptions Received Outbound Read Messages Outbound Write Message Inbound Reply Messages Details1 Serial Port Frames Sent Frames Received CRC Errors

A counter that increments each time a frame is sent. A counter that increments each time a frame is received. A counter that increments each time a message is received that has a CRC that does not match what is calculated. Typically the result of wiring issues. A counter that increments each time an illformed message is received. A counter that increments each time a request message is sent without receiving a corresponding response message within the allowed time. Timeouts are typically the result of configuration errors or a non-responsive device. A counter that increments each time an exception is received. A counter that increments each time a read request message is sent. A counter that increments each time a write request message is sent. A counter that increments each time a read request message is received. A counter that increments each time a write request message is received. A detailed table providing serial and remote statistics per device.

Protocol Errors Timeouts

Exceptions Received Outbound Read Messages Outbound Write Messages Inbound Read Messages Inbound Write Messages Details1 HTTP Server Frames Sent Frames Received Active Connections1

A counter that increments each time a frame is sent. A counter that increments each time a frame is received. A status value that represents the number of connections that are active at the moment the diagnostics page is refreshed. A maximum of 20 connections are supported. Click Active Connections to open a new window with a list of all of the active client connections. A counter that increments each time a connection is made to the EGX. A status value that represents the maximum number of connections that were active at any given moment.

Accumulative Connection1 Maximum Connections

1Click

the link for additional, detailed information.

52

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Diagnostics

Statistic
Gateway Information Firmware Version System Idle Time MAC Address Serial Number Model Number Hardware Version Manufacture Date HTTP Client Send OK Connect Error Authentication Error

Description

The firmware version that is installed on the EGX. A percentage from 0% to 100% indicating the average processor time that is not being used. The unique Ethernet hardware address of an EGX. The serial number of the EGX. The EGX model number. EGX hardware version. Date the EGX was manufactured.

A counter that increments each time a file is sent successfully to the HTTP server. A counter that increments each time the EGX is unable to connect to the HTTP server. A counter that increments each time the HTTP server is unable to authenticate the user or password credentials. A counter that increments each time a file is unable to be transferred to the HTTP server. A counter that increments each time a file is unable to be transferred due to the inability of the EGX to originate the transaction.

Send Error General Error

FTP Client Send OK Connect Error Authentication Error A counter that increments after each successful transfer to an FTP server. A counter that increments each time the EGX is unable to connect to the FTP server. A counter that increments each time the FTP server is unable to authenticate the User/Password credentials. A counter that increments each time the FTP server is unable to locate the requested directory. A counter that increments each time a file is unable to be transferred to the FTP server. A counter that increments each time a file is unable to be transferred due to the inability of the EGX to originate the transaction.

Directory Error

Send Error General Error

SMTP Client Send OK Connect Error Authentication Error A counter that increments each time an e-mail is sent successfully to the SMTP server. A counter that increments each time the EGX is unable to connect to the SMTP server. A counter that increments each time the SMTP server is unable to authenticate the user or password credentials. A counter that increments each time an e-mail is unable to be sent to the SMTP server. A counter that increments each time an e-mail is unable to be sent due to the inability of the EGX to create the e-mail.

Send Error General Error

File System Total Space Free Space


1

The total amount of the EGX disk space in kilobytes. The total amount of unused disk space on the EGX disk in kilobytes.

Click the link for additional, detailed information.

2009-2013 Schneider Electric. All Rights Reserved.

53

PowerLogicTM Ethernet Gateway EGX300 Diagnostics

63230-319-216B4 06/2013

Read Device Registers

This option allows the EGX to read from its local or remote devices. Figure 49: Read Device Registers Page

Action
1. From the Diagnostics menu, click Read Device Registers. 2. Enter local device ID (or choose from the defined device list), starting data address, and the number of registers to read. 3. Select a data type.

Result
Opens the Read Device Registers page. Enters the registers to read from the specified device. Selects the appropriate data type.

4. To change how the data is displayed in the Selects how the data values are displayed. Value column, select Decimal, Hexadecimal, Binary, or ASCII. 5. Click Read. Reads the device registers according to the selected configuration.

Table 19: EGX Read Device Register Settings


Option
Device Name

Description
Selects a device to read from the list of previously added devices. A device not defined in the device list can be read by entering its Local ID number. The address (Local ID) of the device that is to be read. The first register to read. The number of registers to read (1 to 125). Lists the register numbers Lists the data stored for a register. Values retrieved depend on the device connected to the EGX. Refer to the documentation for the connected device for more information about stored register values. Select Holding Registers, Input Registers, Output Coils, Input Coils, or Device ID.

Default

Device ID Starting Register Number of Registers Register column Value column

1 1000 10

Data Type

Holding Registers Decimal

Decimal, Hexadecimal, Select an option to specify how the Value column Binary, or ASCII options data is displayed.

54

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Diagnostics

Communications Check
Automated Communications Check When browsing the Real Time Data views, the EGX has an automated communications check that runs every 15 minutes by default. To change the timing, see Preferences on page 30). This check will verify the communications health of all devices configured on the EGX, and will attempt to re-establish communication to any device marked Out of Service within the current browser session.

Manual Communications Check

In certain cases, you may not want to wait for the automated communications check interval and need to force the check to run manually.
Action
1. From the Diagnostics menu, click Communications Check. 2. Click Check Device Status.

Result
Opens the Communications Check page. Runs a communications check. Communicating devices display Passed in the Comms column and In Service in the Status column. A device that is not communicating displays Failed in the Comms column and Out of Service in the Status column, if it has failed multiple times.

Figure 50:

Communications Check Page

2009-2013 Schneider Electric. All Rights Reserved.

55

PowerLogicTM Ethernet Gateway EGX300 Maintenance

63230-319-216B4 06/2013

MAINTENANCE

The Maintenance Log provides you with a way to document maintenance performed on the EGX, the connected equipment, or the system of which the EGX is a part. Each entry is recorded with the date and time the entry was made, and the name of the user who made it. This log will also automatically list system activity, such as enabling or disabling features. You do not need to add entries for these items. Finally, this log will list all activities that are specified for the Maintenance Log in the Audit Trail setup page (see Audit Trail on page 32).
Action
1. From the Maintenance menu, click Maintenance Log.

Result
Opens the Maintenance Log page.

2. Select the Delete checkbox next to the Deletes the selected entry. entry you want to delete, then click Delete Entries. 3. Click Delete Log to delete all entries in the Clears the maintenance log. maintenance log. 4. To add a new log entry, click Add Log Entry, then enter the maintenance text in the Entry Detail text box (see Figure 52 below). Opens the Add Log Entry page and allows the user to enter maintenance details.

Figure 51:

Maintenance Log

Figure 52:

Add Log Entry

FIRMWARE

Firmware on the EGX can be updated using File Transfer Protocol (FTP). Check www.schneider-electric.com or with your local sales representative for the latest firmware update.

Finding the Firmware Version

The EGX consists of two firmware components: the executable binary component and the disk image component.

56

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Firmware

Executable Binary Component Firmware Version

Action
1. Open the web browser and log into the EGX. 2. Locate the firmware version on the bottom-left corner of the page. NOTE: If you recently updated your firmware, press F5 to refresh the web page and update the displayed firmware number.

Result
Opens the EGX home page. Determines the firmware version of the EGX.

3. Alternatively, you can select Diagnostics Also determines the firmware version of the > Statistics to find the firmware version in EGX. the Gateway Information section.

Disk Image Version


Action
1. Open the web browser and log into the EGX. 2. Locate the firmware version on the bottom-left corner of the page. NOTE: If you recently updated your firmware, press F5 to refresh the web page and update the displayed firmware number. 3. Alternatively, you can access the EGX through FTP, locate the file version.txt, then double-click the file to open it. Determines the disk image firmware version of the EGX.

Result
Opens the EGX home page. Determines the disk image firmware version of the EGX.

Getting New Firmware


Action
1. Launch the web browser, type www.powerlogic.com in the Address text box, then press Enter. 2. Select your country, then click Go. NOTE: If you selected the United States, continue to Step 3. Otherwise, follow the country-specific website navigation to get the EGX firmware. 3. Click Support > Downloads. 4. Click the EGX300 Firmware link. 5. Click the firmware file link (egxxxxx.bin, where xxxx is the firmware version number), then click Save.

Result
Opens the PowerLogic website.

Opens the PowerLogic website for your country.

Opens the downloads page. Opens the EGX300 Firmware page. Opens the File Download dialog box, then opens the Save As dialog box.

6. In the Save As dialog box, select or create Saves the firmware file in the designated a local directory/file folder where the directory/folder. firmware file will be stored, then click Save. 7. Click the egxxxxx.upd link (where xxxx is the firmware number), then click Save. Opens the File Download dialog box, then opens the Save As dialog box.

8. In the Save As dialog box, select or create Saves the firmware .upd file in the designated a local directory/file folder where the directory/folder. firmware file will be stored, then click Save.

2009-2013 Schneider Electric. All Rights Reserved.

57

PowerLogicTM Ethernet Gateway EGX300 Firmware

63230-319-216B4 06/2013

Updating the Firmware

Do not remove power from the EGX while firmware is being downloaded. If power is removed during the programming process, the EGX will no longer function. The Status LED will rapidly blink while programming is in progress. When the flashing stops, programming is complete.
Action
1. Launch Windows Explorer, type ftp:// and the IP address of the EGX in the Address text box (for example, ftp://169.254.0.10), then press Enter.

Result
Opens the Log On As dialog box.

2. Type the user name Administrator and the Opens an FTP session with the EGX. administrator password in the text boxes, then click Log On. 3. Locate the saved firmware file Copies the firmware file to the clipboard. (egxxxxx.bin) directory/folder on your computer, right-click on the file name, then click Copy. 4. Right-click in the Windows Explorer window, then click Paste. NOTE: Instead of copying and pasting the firmware file, you can drag-and-drop the firmware file into Window Explorer. Copies the firmware to the EGX, and the EGX reboots. NOTE: The Power/Status light will blink rapidly while the file is being transferred and programmed to the EGX. Once the programming is complete, the EGX will reset. The amount of time for programming is between 1.5 and 2 minutes.

5. Locate the saved disk update file Copies the disk update file to the clipboard. (egxxxxx.upd) on your computer, right-click on the file name, then click Copy. 6. Right-click in the Windows Explorer window, then click Paste. NOTE: Instead of copying and pasting the firmware file, you can drag-and-drop the firmware file into Window Explorer. 7. To verify that the firmware version was updated successfully, follow the steps in Finding the Firmware Version on page 56. 8. Click Close on the Windows Explorer window. Verifies the updated firmware version. Copies the file to the EGX, and the EGX reboots.

Closes Windows Explorer and ends the FTP connection to the EGX.

58

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Appendix ASupported Ethernet Protocols

APPENDIX ASUPPORTED ETHERNET PROTOCOLS

The EGX supports the following Ethernet protocols:

Modbus TCP/IP: Modbus TCP/IP is a combination of the Modbus protocol, which provides master-slave communication between devices, and TCP/IP, which provides communications over an Ethernet connection. Modbus TCP/IP is used to exchange data between the EGX and other compatible Modbus TCP/IP devices via TCP port 502. Hypertext Transfer Protocol (HTTP): HTTP is a network protocol that handles the delivery of files and data on the World Wide Web. It provides web server functionality via TCP port 80. Hypertext Transfer Protocol Secure (HTTPS): HTTPS is a network protocol that handles the encrypted delivery of files and data on the World Wide Web with the use of SSL. It provides secure web server functionality via TCP port 443. File Transfer Protocol (FTP): FTP is a network protocol that provides the ability to transfer files over the Internet from one computer to another. Active and passive FTP modes are supported, primarily using TCP port 21. Simple Network Management Protocol (SNMP): Based on MIB2 format, SNMP provides the ability to store and send identifying and diagnostic information used for network management purposes via UDP port 161. Address Resolution Protocol (ARP): ARP is used to convert IP addresses to Ethernet addresses. ARP requests are sent by the EGX to determine if its address is a duplicate IP address (see Duplicate IP Address Detection on page 7). Simple Network Time Protocol (SNTP): SNTP is a protocol used to synchronize the clocks of networked devices using a NTP server via UDP port 123.

Hardware
RJ45 Ethernet port Control power

RS485 serial port LEDs for Ethernet and serial communications Power and Status LED Bias, termination, and 2-wire/4-wire jumper switches Reset button

RS232 serial port (RJ45 connector)

2009-2013 Schneider Electric. All Rights Reserved.

59

PowerLogicTM Ethernet Gateway EGX300 Appendix BSupported Device Types

63230-319-216B4 06/2013

APPENDIX BSUPPORTED DEVICE TYPES

The EGX supports the following device types. This list of supported devices was accurate at the time this document was published. Check www.schneider-electric.com for updates. Table 20: EGX300-Supported Device Types
Device Group Active Harmonic Filter Circuit Breakers Devices Accusine Compact NSX-A Compact NSX-E PowerPact - A PowerPact - E CM100/200 CM2000 CM3000 CM4000 ION7500 ION7550 ION7600 ION7650 DM6000 DM6300 Model 98 ATV61 ATV71 Energy Meter Enercept E5600 EM1200 EM1210 EM1250 EM1251 EM26-96 EM3550 EM3555 EM4800 EM6400 EM6433 EM6436 EM6436DUAL EM6438 EM7230 EM7280 iEM3150 iEM3155 iEM3250 iEM3255 ION8600 Vigilohm IM20 Vigilohm IM20-H TeSys T BCPM-Model A BCPM-Model B BCPM-Model C BCM50A BCM100A MCM MotorLogic Plus MotorLogic Plus II Varlogic PM9c PM200 PM300 PM500 PM600

Circuit Monitors

Digital Meters Digital Temp Controller Drives Energy Meters

Insulation Monitoring Devices Motor Management Multi-Circuit Monitors

Overload Relays (SSOLR) Power Factor Controller Power Meters

60

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTM Ethernet Gateway EGX300 Appendix BSupported Device Types

Table 20: EGX300-Supported Device Types


Device Group Devices PM700 PM800 PM1000 PM3250 PM5100 PM5300 PM5350 PM5350BW PM5560 ION6200 (Standard and Mega) ION7300 Sepam 2000 Sepam Series 10 Sepam Series 20 Sepam Series 40 Sepam Series 80 SIM10Z SIM10M SIM6BZ ATS48 MVSS/RVSS ZED-THL-M Micrologic A Micrologic E Micrologic H Micrologic P Acti9 SmartLink Conext TL Inverters

Protective Relays

Smart Interface Modules

Soft Starters Temperature/Humidity/Light Sensors Trip Units

Other

2009-2013 Schneider Electric. All Rights Reserved.

61

PowerLogicTM Ethernet Gateway EGX300 Appendix BSupported Device Types

63230-319-216B4 06/2013

62

2009-2013 Schneider Electric. All Rights Reserved.

63230-319-216B4 06/2013

PowerLogicTMEthernet Gateway EGX300 Index advanced 5 executable binary component firmware version 58 exporting the device log 19 setup 24

Index
A
access levels to the EGX 26 accessing the EGX over a network 2 additional resources 1 analog gauge range 38 ARP (address resolution protocol) 7 audit trail 33 maintenance log 34 Syslog box 34

P
password strength color indication 28 preferences customizing the EGX 31

F
file image component firmware version 58 firmware getting new 58 updating 59 updating via ftp 57 ftp export device log 20 using to add web pages 30 using to delete web pages 30 using to retrieve data log 43

R
read device registers 55 real-time data 37 remote device connections 10

B
basic readings settings 37

S
serial port settings advanced 9 serial port setup 8 setup device list 12 EGX 4 single device pages 37, 40 SNMP parameters setup 25 statistics 50 interpreting 52 summary device pages 38, 44 supported device types 61 supported ethernet protocols 60 Syslog audit trails 34 system access point links to other EGX300s 49 setup 36

C
communications check 56 automated 56 manual 56 connecting devices 11 control 50 custom web pages setup 30

H
hardware 60 HTTP export device log 21 port number setup 6 retrieving interval data log 44 HTTPS port number setup 6

D
dashboards 46 data log error codes 43 retrieved via ftp 43 retrieving 41 data log format 42 data points button interval data log 43 date and time setup 24 device discovery 14 device list EGX 11 device log export setup 19 device logging 16, 40 device registers reading 55 device types supported 61 diagnostics 50 documentation links setup 27 documentation page 49 duplicate IP address detection 7

I
interval data log via data points button 43 via e-mail 44 via ftp 43 via HTTP 44 via Microsoft Web Query 44 intervals logging 16 introduction 1 IP address detecting duplicate 7

T
TCP/IP settings 4 time synchronization network 24 trending 39 trusted certificate HTTPS port number 6

L
logging 16, 40 data format 42 topics 18 logging in to EGX 2 logging intervals 16

U
user accounts setup 28 user interface EGX 3

M
maintenance log 57 audit trail 34 Microsoft Web Query interval data log 44 Modbus devices discovering 14 Modbus TCP/IP filtering setup 26 monitoring 37

V
viewable device types 32 viewing real-time data and trends 37

E
EGX device list 11 login 2 user interface 3 e-mail export device log 19 interval data log 44 error codes data log 43 Ethernet and TCP/IP settings 4 Ethernet protocols 60 Ethernet settings

W
web pages adding/removing from the web interface 31 setup 29 custom 30

N
network access via 2 network time synchronization 63

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTMEthernet Gateway EGX300 Index

63230-319-216B4 06/2013

64

2009-2013 Schneider Electric. All Rights Reserved.

PowerLogicTMEthernet Gateway EGX300 User Guide

PowerLogic is a trademark or registered trademark of Schneider Electric in France, the USA and other countries. Other trademarks used are the property of their respective owners. This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations. As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication. 63230-319-216B4 06/2013 Replaces 63230-319-216B3 03/2013 2009-2013 Schneider Electric. All Rights Reserved.

Schneider Electric
35, rue Joseph Monier CS 30323 F - 92506 Rueil-Malmaison Cedex www.schneider-electric.com

Pasarela Ethernet EGX300 de PowerLogicTM


Manual del usuario
63230-319-216B4_ES 06/2013

Informacin de seguridad
Informacin importante
Lea estas instrucciones atentamente y examine el equipo para familiarizarse con el dispositivo antes de instalarlo, manipularlo, revisarlo o realizar el mantenimiento de este. Los siguientes mensajes especiales pueden aparecer a lo largo de este manual o en el equipo para advertir de posibles riesgos o remitirle a otras informaciones que le ayudarn a aclarar o simplificar los procedimientos. La adicin de uno de estos dos smbolos a una etiqueta de seguridad del tipo Peligro o Advertencia indica la existencia de un riesgo de descarga elctrica que ocasionar lesiones si no se siguen las instrucciones. Este es el smbolo de alerta de seguridad. Sirve para alertar de posibles riesgos de lesiones. Siga las recomendaciones de todos los mensajes de seguridad precedidos por este smbolo para evitar posibles lesiones e incluso la muerte.

PELIGRO
PELIGRO indica una situacin de riesgo inmediato que, si no se evita, causar la muerte o lesiones graves.

ADVERTENCIA
ADVERTENCIA indica una situacin de riesgo potencial que, si no se evita, puede causar la muerte o lesiones graves.

PRECAUCIN
PRECAUCIN indica una situacin de riesgo potencial que, si no se evita, puede causar lesiones moderadas o leves.

AVISO
AVISO sirve para indicar prcticas no relacionadas con lesiones fsicas. El smbolo de alerta de seguridad no debe utilizarse junto con esta advertencia impresa.

Por favor, tenga en cuenta lo siguiente


Slo el personal cualificado puede instalar, manipular y revisar el equipo electrnico as como realizar el mantenimiento de este. Schneider Electric no asume ninguna responsabilidad de las consecuencias que se deriven de la utilizacin de este manual. Por personal cualificado se entiende aquellas personas que poseen destrezas y conocimientos sobre la estructura, la instalacin y el funcionamiento de equipos elctricos y que han recibido formacin en materia de seguridad para reconocer y prevenir los peligros implicados.

Avisos
Aviso sobre la seccin 15 de la normativa de la FCC
Este equipo ha sido probado y cumple los lmites establecidos para los dispositivos digitales Clase A, segn la seccin 15 de la normativa de la FCC (Comisin Federal de Comunicaciones de los EE. UU.). Estos lmites se establecen para proporcionar la proteccin adecuada contra interferencias que puedan daar el equipo cuando este se utiliza en un entorno comercial. Este equipo genera, utiliza y puede emitir energa de radiofrecuencia y, si no se instala y utiliza siguiendo las indicaciones del manual de instrucciones, puede provocar interferencias que afecten a las radiocomunicaciones. Si se utiliza en una zona residencial, las interferencias podran causar daos. En tal caso, el usuario es el responsable de corregir dichas interferencias por su propia cuenta y riesgo. El nmero de equivalencia de dispositivos, o nmero REN (Ringer Equivalence Number), del mdem interno opcional del dispositivo es 0,6. La conexin al mdem interno del dispositivo se debe realizar por medio de un cable para telfono (no se suministra) que cumpla la seccin 68 de la normativa de la FCC. El dispositivo no se puede utilizar en un servicio de telfono de monedas pblico ni en servicios de lnea compartida. Este aparato digital Clase A cumple con la normativa canadiense ICES-003.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Contenido

Contenido
Introduccin .............................................................................................. 1 Otros recursos ............................................................................................. 1 Acceso a la EGX a travs de una red ...................................................... 2 Inicio de sesin en la EGX .......................................................................... 2 Descripcin general de la interfaz de usuario de la EGX ...................... 3 Configuracin ............................................................................................ 5 Configuracin de Ethernet y TCP/IP ........................................................... 5 Configuracin avanzada de Ethernet .................................................... 6 Deteccin de direcciones IP duplicadas................................................ 8 Puerto serie ................................................................................................. 8 Configuracin avanzada del puerto serie .............................................. 9 Conexiones con dispositivos remotos ....................................................... 10 Lista de dispositivos de la EGX ................................................................. 12 Conexin de dispositivos a una EGX .................................................. 12 Configuracin de la lista de dispositivos.............................................. 13 Deteccin de dispositivos .................................................................... 15 Registro de dispositivos ............................................................................ 17 Registro de datos de intervalo............................................................. 17 Configurar registro por intervalos ........................................................ 17 Temas que registrar ............................................................................ 18 Exportacin del registro de dispositivos .................................................... 19 Exportacin por correo electrnico...................................................... 19 Exportacin por FTP............................................................................ 21 Exportacin por HTTP ......................................................................... 23 Fecha y hora ............................................................................................. 24 Sincronizacin horaria de red.............................................................. 25 Parmetros del SNMP .............................................................................. 26 Filtrado de Modbus TCP/IP ....................................................................... 27 Vnculos de documentacin ...................................................................... 28 Cuentas de usuario ................................................................................... 29 Acceso a pgina Web ............................................................................... 30 Agregar o quitar pginas web personalizadas .................................... 31 Adicin de pginas web mediante FTP ............................................... 31 Eliminacin de pginas web mediante FTP ........................................ 31 Agregar o quitar pginas web a o de la interfaz web .......................... 32 Preferencias .............................................................................................. 33 Tipos de dispositivos visualizables ........................................................... 34 Historial de auditora ................................................................................. 34 Punto de acceso del sistema .................................................................... 36 Supervisin .............................................................................................. 38 Datos en tiempo real ................................................................................. 38 Pginas de dispositivo nico ............................................................... 38 Configuracin de lecturas bsicas....................................................... 38 Rango de los indicadores analgicos.................................................. 39 Pginas de resumen de dispositivos ................................................... 39 Tendencias .......................................................................................... 40 Registro de dispositivos ............................................................................ 41 Pginas de dispositivo nico ............................................................... 42 Obtencin de registros cronolgicos de datos .................................... 43 Formato de registro ............................................................................. 43 Cdigos de error para los registros cronolgicos de datos ................. 44 Obtencin de un registro de datos de intervalo mediante FTP ........... 44

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM Contenido

63230-319-216B4_ES 06/2013

Obtencin de un registro de datos de intervalo mediante el botn Puntos de datos..................................................................... 45 Obtencin de un registro de datos de intervalo mediante la funcin de consulta Web de Microsoft............................................. 45 Obtencin de un registro de datos de intervalo mediante correo electrnico ................................................................................ 45 Obtencin de un registro de datos de intervalo mediante HTTP......... 45 Pginas de resumen de dispositivos ................................................... 46 Panel de instrumentos .............................................................................. 47 Visualizacin de un panel de instrumentos ......................................... 48 Obtencin de los datos del panel de instrumentos mediante el botn Puntos de datos..................................................................... 49 Guardar un enlace a un panel de instrumentos .................................. 49 Guardar un panel de instrumentos como imagen ............................... 49 Punto de acceso del sistema .................................................................... 50 Documentacin ....................................................................................... 51 Control ..................................................................................................... 51 Diagnsticos ............................................................................................ 52 Estadsticas ............................................................................................... 52 Interpretacin de las estadsticas ........................................................ 53 Lectura de registros de dispositivo ............................................................ 56 Comprobacin de las comunicaciones ..................................................... 57 Comprobacin de comunicaciones automatizada............................... 57 Comprobacin de comunicaciones manual......................................... 57 Mantenimiento ......................................................................................... 58 Firmware .................................................................................................. 58 Identificacin de la versin del firmware ................................................... 58 Versin del firmware del componente binario ejecutable .................... 59 Versin de imagen de disco ................................................................ 59 Obtencin de firmware nuevo ................................................................... 59 Actualizacin del firmware ........................................................................ 60 Apndice A: Protocolos Ethernet compatibles .................................... 61 Equipo fsico .............................................................................................. 61 Apndice B: Tipos de dispositivos admitidos ..................................... 62

ii

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Introduccin

INTRODUCCIN

La EGX300 es un dispositivo basado en Ethernet que proporciona una interfaz transparente entre redes basadas en Ethernet y dispositivos que pueden ser instalados por el usuario. Entre estos ltimos se incluyen medidores, monitores, rels protectores, autmatas programables (PLC), unidades de control, controles de motores y otros dispositivos que se comunican mediante protocolos Modbus, Jbus o PowerLogic. La EGX300 utiliza el protocolo Modbus TCP/IP para acceder a informacin de dispositivos que puede instalar el usuario a travs de una red de rea local (LAN) o a travs de una red de rea extendida (WAN). Esta capacidad permite utilizar software de supervisin para acceder a la informacin de los dispositivos y recolectar datos, establecer tendencias, gestionar alarmas y eventos, efectuar anlisis y ejecutar otras funciones. La EGX300 permite generar informes de datos en tiempo real a partir de muchos tipos de dispositivos corrientes y proporciona varias funciones especficas de estos, tales como informes de pginas de resumen incorporadas de dispositivos y circuitos, registro de datos incorporado y establecimiento de tendencias en tiempo real. Figura 1: Descripcin general de la EGX300
Vistas en tiempo real Tendencias en tiempo real Pginas web de la EGX300

Ver datos del dispositivo con un sencillo navegador, sin software

Restablecimientos de control

Tendencias de los registros de datos

EGX300

Extraiga a pginas web informacin proveniente de otras pasarelas PowerLogic e interfaces TCP/IP Modbus como ECC21 y PM8ECC.

EGX100

ION6200

PM800

Micrologic

Sepam

Otros recursos

Visite www.schneider-electric.com y escriba EGX300 en el campo de bsqueda. Vaya a Documents & Downloads (Documentos y descargas) de la EGX.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM Acceso a la EGX a travs de una red

63230-319-216B4_ES 06/2013

ACCESO A LA EGX A TRAVS DE UNA RED

Una vez que haya configurado los parmetros de Ethernet de la EGX (consulte el manual de instalacin de esta), podr acceder a la EGX a travs de una LAN Ethernet utilizando cualquier explorador web.

Inicio de sesin en la EGX


Accin
1. Inicie el explorador web. 2. En la barra de direcciones, escriba la direccin de la EGX (la direccin predeterminada es 169.254.0.10) y, a continuacin, pulse Intro.

Resultado
Abre el explorador web. Abre el cuadro de dilogo Iniciar sesin.

3. Escriba su nombre de usuario Introduce el nombre de usuario y la contrasea (Administrator es el valor predeterminado) y, a continuacin, abre la pgina de inicio de y la contrasea (Gateway es la la EGX. predeterminada) en los cuadros de texto y despus haga clic en Aceptar. NOTA: El nombre de usuario y la contrasea respetan maysculas y minsculas. 4. Haga clic en el elemento correspondiente de la barra de mens. Abre el elemento de men seleccionado.

Figura 2:

Pgina de inicio de la EGX

barra de mens

Le aconsejamos que se desconecte cuando no necesite acceder a la EGX. Para salir de la sesin de la EGX, haga clic en Desconexin o cierre el explorador.

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Descripcin general de la interfaz de usuario de la EGX

DESCRIPCIN GENERAL DE LA INTERFAZ DE USUARIO DE LA EGX

La interfaz de usuario de la EGX consta de mltiples pginas web que se utilizan en la supervisin y el control de dispositivos, as como el diagnstico y la configuracin de la EGX. Consulte la Tabla 1 para ver una descripcin de cada pgina web. Tabla 1: Pginas de la EGX
Descripcin Consulte la pgina
5 8 10 12

Pgina web de la EGX


Configuracin Ethernet y TCP/IP Puerto serie Conexiones con dispositivos remotos Lista de dispositivos

Configure los parmetros de las comunicaciones Ethernet y TCP/IP. Configure los parmetros de las comunicaciones serie. Configure las conexiones de los dispositivos Modbus TCP/IP remotos. Configure, identifique o verifique los dispositivos serie locales del bus de comunicaciones serie. Los dispositivos remotos solamente se podrn configurar o verificar. Configure los parmetros de registro de los dispositivos. Configure las opciones de exportacin del registro de dispositivos. Establezca la fecha y la hora manualmente o con parmetros del SNTP. Configure el Protocolo simple de administracin de redes (SNMP). Configure las direcciones IP que podrn acceder a la EGX a travs de Modbus TCP/IP.

Registro de dispositivos Exportacin del registro de dispositivos Fecha y hora1 Parmetros del SNMP1 Filtrado de Modbus TCP/IP1

17 19 24 26 27 28 29 30 33 34

Vnculos de documentacin Configure archivos y vnculos de documentacin de URL. Cuentas de usuario1 Acceso a pgina Web1 Preferencias Tipos de dispositivos visualizables Historial de auditora1 Cree y modifique grupos y usuarios. Configure los derechos de acceso a las pginas web para cada grupo de usuarios. Configure las preferencias de la EGX. Configure qu tipos de dispositivos admitidos se podrn visualizar en la pgina web Lista de dispositivos de la EGX. Configure la manera en que la EGX notificar los mensajes del sistema: por medio del registro de mantenimiento, por correo electrnico y por el servidor Syslog remoto. Habilite y configure la direccin IP de grupo para varias EGX300, permitindolas que se detecten entre s y vean la informacin de las dems.

34

Punto de acceso del sistema1 Supervisin Datos en tiempo real

36

La vista de tabla Pginas de dispositivo nico proporciona lecturas bsicas de los dispositivos seleccionados. La vista de tabla Pginas de resumen de dispositivos facilita resmenes relativos a uno o ms dispositivos seleccionados. La vista de la pgina Tendencias ilustra tendencias en forma de grficos y tablas en tiempo real correspondientes a temas comunes de varios dispositivos. Pginas de dispositivo nico proporciona registros de tendencias en forma de grficos y tablas que ilustran cantidades, seleccionables por el usuario, correspondientes a los dispositivos seleccionados. Pginas de resumen de dispositivos proporciona registros de tendencias en forma de grficos de varios dispositivos acerca de un tema especfico.

38

Registro de dispositivos

41

Slo el administrador tiene acceso.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM Descripcin general de la interfaz de usuario de la EGX

63230-319-216B4_ES 06/2013

Tabla 1:

Pginas de la EGX
Descripcin
Los paneles de instrumentos proporcionan representaciones en forma de grficos y tablas de la informacin de consumo de energa recopilada a lo largo del tiempo correspondiente a todos los dispositivos a los que se ha habilitado para el registro de datos. La pgina Punto de acceso del sistema muestra las EGX300 y otros dispositivos en red del sistema que son accesibles desde esta EGX300. Cada lnea es un hipervnculo a la pgina de inicio de sesin de la EGX300.

Pgina web de la EGX


Panel de instrumentos

Consulte la pgina
47

Punto de acceso del sistema

50

Documentacin Documentacin Accede a la documentacin pertinente de la EGX y a vnculos de documentacin que podr configurar el usuario. 51

Control Restablecimientos Proporciona lo necesario para la ejecucin de los restablecimientos definidos para el dispositivo y muestra la fecha y la hora a las que se realiz cada funcin de restablecimiento. Los restablecimientos de fecha y hora se muestran solo cuando el dispositivo los admite. Muestra datos de diagnstico que se utilizan para resolver problemas de la red. Esta pgina contiene tambin informacin acerca de la EGX especfica del usuario, incluido el nmero de serie, la fecha de fabricacin y la direccin de control de acceso de medios (MAC). Permite que los usuarios lean datos de registro procedentes de dispositivos locales y remotos conectados a la EGX. Verifica el buen estado de las comunicaciones de todos los dispositivos configurados en la EGX. 51

Diagnsticos Estadsticas 52

Lectura de registros de dispositivo Comprobacin de las comunicaciones Mantenimiento

56

57

Registro de mantenimiento Muestra la fecha, la hora y el usuario que ha realizado el ltimo mantenimiento del equipo y proporciona datos de entrada sobre el mantenimiento realizado.
1

58

Slo el administrador tiene acceso.

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

CONFIGURACIN

Para acceder a los vnculos de la pgina web Configuracin, haga clic en Configuracin en la barra de mens de la EGX.

Configuracin de Ethernet y TCP/IP


Accin Resultado
1. En el men Configuracin, haga clic en Abre la pgina Ethernet y TCP/IP. Ethernet y TCP/IP. 2. Seleccione el formato de trama y el tipo Selecciona el formato de trama y el tipo de medio. de medio. Si no los conoce, pngase en contacto con el administrador de la red. 3. Introduzca su direccin IP, la mscara de subred y la direccin predeterminada de la pasarela asignadas a la EGX por el administrador de la red. Introduce los parmetros de Ethernet para la EGX. NOTA: Si introduce una direccin IP que ya est siendo utilizada por otro dispositivo, se le pedir que seleccione una direccin IP diferente. Consulte Deteccin de direcciones IP duplicadas en la pgina 8. Actualiza la configuracin de Ethernet y TCP/IP de la EGX.

4. Haga clic en Aplicar.

* Consulte la Tabla 2 a continuacin para ver una lista de opciones.

Figura 3:

Pgina Ethernet y TCP/IP

Tabla 2:
Opcin
Formato de trama

Configuracin de Ethernet y TCP/IP de la EGX


Descripcin Valor

Se utiliza para seleccionar el formato en Ethernet II, 802.3 SNAP el que se envan los datos a travs de Predeterminado: Ethernet II una conexin Ethernet. Se utiliza para definir la conexin fsica a Ethernet o el tipo de medio. 10T/100Tx Auto 10BaseT-HD 10BaseT-FD 100BaseTX-HD 100BaseTX-FD

Tipo de medio

Predeterminado: 10T/100Tx Auto Obtener una Se utiliza para obtener automticamente Activado o desactivado direccin IP una direccin IP de un servidor BootP. Predeterminado: Desactivado automticamente NOTA: Requiere apoyo de la administracin de la red. Direccin IP Mscara de subred Pasarela predeterminada Sirve para introducir la direccin IP esttica de la EGX. Se utiliza para introducir la direccin de la mscara de subred de la red. Se utiliza para introducir la direccin IP de la pasarela (router) que se usa para las comunicaciones con la red de rea extendida (WAN). Predeterminado: 169.254.0.10 Predeterminado: 255.255.0.0 Predeterminado: 0.0.0.0

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Configuracin avanzada de Ethernet

AVISO
RENDIMIENTO REDUCIDO DE LA RED Solo los trabajadores cualificados deben cambiar la configuracin avanzada de Ethernet de la EGX. Tales modificaciones deben realizarse solo despus de leer acerca de la configuracin avanzada de Ethernet y comprenderla. El incumplimiento de estas instrucciones puede reducir el rendimiento de la red.

Accin
1. Haga clic en Avanzado en la pgina Ethernet y TCP/IP.

Resultado
Abre la pgina Configuracin avanzada de Ethernet.

2. Configure los parmetros avanzados de Configura los parmetros avanzados de Ethernet (consulte la Tabla 3 en la Ethernet. pgina 7 para ver las opciones disponibles). Haga clic en Predeterminados para asignar los valores predeterminados a todas las opciones. 3. Haga clic en Aplicar. NOTA: Al aplicar los cambios a la pgina Configuracin avanzada de Ethernet, no se guardan los cambios en la pgina Ethernet y TCP/IP. 4. Haga clic en Aceptar para aceptar los cambios y restablecer la EGX. Actualiza la configuracin de Ethernet y TCP/IP de la EGX.

La EGX se reinicia.

Figura 4:

Pgina Configuracin avanzada de Ethernet

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Tabla 3:
Opcin

Configuracin avanzada de Ethernet de la EGX


Descripcin
Identifica el nmero de routers (pasarelas) que puede pasar un paquete TCP.

Valor
1 a 255 saltos Predeterminado: 60 saltos

Perodo de vida

Mantenimiento de conexin TCP

Un temporizador que detecta cundo un 0 a 65.000 segundos dispositivo conectado o una conexin inactiva Predeterminado: pasa a no estar disponible debido a eventos tales 30 segundos como un reinicio o apagado. El valor de 0 deshabilita esta opcin. Se utiliza para especificar durante cunto tiempo 0 a 60 segundos esperar la EGX a que un servidor BootP asigne Predeterminado: sus direcciones IP. (La direccin IP 15 segundos predeterminada se utiliza despus del tiempo de espera si no se ha asignado ninguna direccin IP.) Se utiliza para especificar durante cunto tiempo se mantendrn las entradas de la tabla ARP (Protocolo de resolucin de direcciones). 0 a 65.000 minutos Predeterminado: 15 minutos

Tiempo de espera de BootP

Tiempo de espera de la cach ARP Servidor FTP

Controla si se inicializa el servidor FTP durante el Desactivado o Activado arranque. Predeterminado: Activado Un temporizador que cierra la conexin FTP 30 a 900 segundos despus de una cantidad especfica de tiempo de Predeterminado: inactividad. 120 segundos Un temporizador que cierra la conexin HTTP 0 a 65.000 segundos despus de una cantidad especfica de tiempo de Predeterminado: inactividad. 4 segundos El puerto TCP utilizado para los mensajes HTTP. Los siguientes nmeros de puerto estn reservados para otros protocolos de red y no pueden usarse: 20 y 21 (FTP) y 502 (Modbus TCP/IP). Puerto TCP utilizado para los mensajes HTTPS. La EGX viene con un certificado autofirmado. Para convertir la EGX en un servidor de plena confianza, debe adquirir un certificado a una entidad emisora de certificados (por ejemplo, los servicios de autenticacin VeriSign). Para agregar/instalar un certificado digital, desplcese manualmente a la pgina de actualizacin de certificados empleando la URL http://x.x.x.x./update_certs_shtml, donde x.x.x.x es la direccin IP de la EGX. 0 a 65.000 Predeterminado: 80 0: Desactiva el puerto HTTP. De 1 a 65.000 Predeterminado: 443 0: Desactiva el puerto HTTPS.

Tiempo de inactividad de conexin FTP Tiempo de inactividad de conexin HTTP Nmero de puerto HTTP

Nmero de puerto HTTPS

Mximo de Se utiliza para especificar el nmero mximo de mantenimientos de mantenimientos de conexiones HTTP. conexiones HTTP Conexiones servidor Modbus TCP/IP Difusin Modbus Se utiliza para especificar el nmero de conexiones disponibles del servidor Modbus TCP/IP. Determina cmo se tratan los mensajes TCP/IP Modbus con ID de unidad de 0 en la subred serie. Desactivado = se ignoran todos los mensajes. Activado = se tratan todos los mensajes como difusiones a puertos serie sin que se espere una respuesta. Activado con respuesta = todos los mensajes se tratan como mensajes regulares a puerto serie para los que se espera una respuesta.

0 a 65.000 Predeterminado: 100 16 a 64 Predeterminado: 32 Desactivado, Activado o Activado con respuesta Predeterminado: Desactivado

Proxy MODBUS/TCP

Parmetro que determina si los mensajes Modbus Desactivado o Activado TCP/IP procedentes de clientes remotos se Predeterminado: encaminan a dispositivos remotos Modbus TCP/IP Activado que estn definidos en la EGX.

Tiempo de espera Cantidad de tiempo que la EGX esperar a que un 0,1 a 10 de cliente Modbus dispositivo remoto Modbus TCP/IP responda a Predeterminado: TCP/IP una solicitud Modbus TCP/IP iniciada por la EGX. 5 segundos Tiempo de espera de conexin de cliente Modbus TCP/IP Tiempo de inactividad de conexin de servidor Modbus TCP/IP Cantidad de tiempo que la EGX esperar a que un De 1 a 10 dispositivo remoto Modbus TCP/IP responda a Predeterminado: una solicitud de conexin Modbus TCP/IP iniciada 2 segundos por la EGX. Un temporizador que cierra la conexin Modbus 0 a 32.767 segundos TCP/IP despus de una cantidad especificada de Predeterminado: 0 tiempo de inactividad. El valor de 0 deshabilita esta opcin.

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Deteccin de direcciones IP duplicadas

Mientras est conectada a la red, la EGX publica su direccin IP. Para evitar conflictos de direcciones IP duplicadas, la EGX utiliza el protocolo de resolucin de direcciones (ARP) para ver si algn dispositivo de la red utiliza la misma direccin IP. En la Tabla 4 a continuacin se explica cmo trata la EGX las direcciones duplicadas al detectarlas. Tabla 4: Situaciones de deteccin de IP duplicadas
IP duplicada detectada LED de alimentacin/estado

Situacin
Proceso de inicio/restablecimiento de alimentacin Enlace de Ethernet detectado

Vuelve a la direccin IP, la mscara de Patrn de 4 parpadeos y subred y la direccin de la pasarela pausa predeterminadas de la EGX. Las solicitudes ARP se envan cada 15 segundos hasta que la direccin IP queda disponible. Cuando la direccin IP quede disponible, la EGX la utilizar. La EGX mantiene su direccin IP anterior y muestra un mensaje que indica que otro dispositivo ya la est empleando.

Cambio manual de la direccin

Recibe una solicitud ARP Vuelve a la direccin IP, la mscara de Patrn de 4 parpadeos y subred y la direccin de la pasarela pausa predeterminadas de la EGX si un dispositivo conectado enva cuatro solicitudes ARP de la direccin IP de la EGX. La EGX enviar solicitudes ARP cada 15 segundos hasta que la direccin IP vuelva a quedar disponible. Cuando la direccin IP quede disponible, la EGX la utilizar.

Puerto serie
Accin
1. En el men Configuracin, haga clic en Puerto serie. 2. Seleccione la interfaz fsica, el modo de transmisin, la velocidad en baudios, la paridad y el tiempo de espera de respuesta (consulte la Tabla 5 en la pgina 9). 3. Haga clic en Aplicar.

Resultado
Abre la pgina Puerto serie. Selecciona las opciones del puerto serie.

Actualiza la configuracin del puerto serie de la EGX.

Figura 5:

Pgina Puerto serie

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Tabla 5:
Opcin

Configuracin del puerto serie


Descripcin Valor
RS485 4 hilos, RS485 2 hilos o RS232 Predeterminado: RS485 2 hilos Automtico Modbus ASCII

Interfaz fsica Sirve para seleccionar el modo de cableado fsico del puerto serie de la EGX. Modo de transmisin Se usa para seleccionar el modo de transmitir datos en una conexin serie.

NOTA: El modo Automtico le permite comunicarse con dispositivos esclavos Modbus RTU, Jbus y PowerLogic (SY/MAX) en el mismo bus de comunicaciones serie. Velocidad en Se usa para seleccionar la velocidad de 2400, 4800, 9600, 19200, 38400, baudios transmisin de datos en una conexin 56000* o 57600* serie. Predeterminado: 19200 Paridad Se usa para seleccionar el tipo de Par, Impar o Ninguna paridad con que comprobar la precisin Predeterminado: Par de los datos mediante un bit de paridad. Sirve para seleccionar el tiempo que esperar la EGX a recibir respuesta de un dispositivo serie. 0,1 a 10 segundos Predeterminado: 3 segundos

Tiempo de espera de respuesta

* Slo est disponible si la interfaz fsica y el modo de transmisin son RS232/Modbus ASCII.

Configuracin avanzada del puerto serie

AVISO
RENDIMIENTO REDUCIDO DE LA RED Solo los trabajadores cualificados deben cambiar la configuracin avanzada del puerto serie de la EGX. Tales modificaciones deben realizarse solo despus de leer acerca de la configuracin avanzada del puerto serie y comprenderla. El incumplimiento de estas instrucciones puede reducir el rendimiento de las comunicaciones serie.

Accin
1. Haga clic en Avanzado en la pgina Puerto serie. 2. Configure los parmetros avanzados del puerto serie (para ver las opciones disponibles, consulte la Tabla 6 en la pgina 10 en la pgina 11). Haga clic en Predeterminados para asignar los valores predeterminados a todas las opciones. 3. Haga clic en Aplicar. NOTA: Al aplicar los cambios a la pgina Configuracin avanzada del puerto serie, no se guardan los cambios en la pgina Puerto serie.

Resultado
Abre la pgina Configuracin avanzada del puerto serie. Configura los parmetros avanzados del puerto serie.

Actualiza la configuracin avanzada del puerto serie de la EGX.

Figura 6:

Pgina Configuracin avanzada del puerto serie

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Tabla 6:
Opcin
Retardo entre tramas

Configuracin avanzada del puerto serie


Descripcin Valor

Define el intervalo silencioso mnimo entre 0 a 100 milisegundos el final de la respuesta recibida y el Predeterminado: comienzo de una nueva solicitud en la 50 milisegundos lnea serie. Permite que el intervalo silencioso utilizado 0 a 15 caracteres para marcar el final de un paquete Predeterminado: 6 caracteres ModbusRTU se ample ms all de los 3,5 caracteres definidos por la norma. Indica el cdigo de respuesta de excepcin 0x0A o 0x0B que se devuelve cuando un dispositivo Predeterminado: 0x0B serie conectado a la EGX no responde antes del tiempo de espera del puerto serie. Modbus TCP/IP utiliza 0x0B. Sin embargo, en algunas suites de software anteriores se utilizaba 0x0A.

Extensin de intervalo silencioso Cdigo de excepcin de tiempo de espera Modbus TCP/IP

Conexiones con dispositivos remotos

La EGX permite abrir conexiones para un mximo de 16 dispositivos nicos Modbus TCP/IP definidos por el usuario. Podr introducirlas manualmente o seleccionarlas a partir de una tabla que recoge las conexiones detectadas por la funcin Punto de acceso del sistema (consulte la Figura 7 de la pgina 11). Estas conexiones se ponen a disposicin de la configuracin de la lista de dispositivos para la configuracin de dispositivos remotos.
Accin
1. En el men Configuracin, haga clic en Conexiones con dispositivos remotos.

Resultado
Abre la pgina Conexiones con dispositivos remotos.

2. Para agregar una conexin manualmente, Introduce las direcciones IP de los dispositivos introduzca la direccin IP de los remotos. dispositivos remotos a los que desee conectarse. 3. Para agregar una conexin detectada Introduce la direccin IP correspondiente a la gracias a la funcin Punto de acceso del conexin detectada por la funcin Punto de sistema, haga clic en Aadir (a la derecha acceso del sistema que haya seleccionado. de la conexin que desee en la tabla de conexiones detectadas). 4. Haga clic en Aplicar. Actualiza la configuracin de las conexiones con dispositivos remotos de la EGX.

10

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Figura 7:

Conexiones con dispositivos remotos

2009-2013 Schneider Electric. Reservados todos los derechos.

11

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Lista de dispositivos de la EGX

Antes de comenzar, tenga en cuenta que no debe utilizar las direcciones serie esclavas 1 o 16 en un modo de transmisin Automtico en un bus de comunicaciones serie con protocolos mixtos (por ejemplo, una sola conexin en bus de comunicaciones serie con algunos dispositivos que usen el protocolo PowerLogic y otros que usen el protocolo Modbus RTU/Jbus).

Conexin de dispositivos a una EGX

La Figura 8 y la Figura 9 ilustran la manera en que los dispositivos se conectan a la EGX. Para agregar esos dispositivos a la Lista de dispositivos, siga los pasos que se indican en Configuracin de la lista de dispositivos en la pgina 13. Figura 8: Topologa: Slo dispositivos esclavos en serie

Conexin Ethernet Pginas web de la EGX300 EGX

Conexin RS485

Dispositivos esclavos en serie

Figura 9:

Topologa: Dispositivos esclavos y remotos en serie


Conexin Ethernet

Pginas web de la EGX300 Direccin IP de la EGX100: 169.254.0.28 Direccin IP de la EGX300: 169.254.0.75

Son posibles hasta 16 conexiones IP remotas

Conexin RS485

Conexin RS485

Dispositivos esclavos remotos

Dispositivos esclavos en serie

12

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Configuracin de la lista de dispositivos


Accin
1. En el men Configuracin, haga clic en Lista de dispositivos.

Resultado
Abre la pgina Lista de dispositivos. (Consulte la Figura 10 para conexiones exclusivamente locales, o bien la Figura 11 si hay conexiones remotas disponibles.)

2. Utilice Deteccin para localizar dispositivos Abre la pgina Deteccin de dispositivos para conectados localmente (consulte detectar todos los dispositivos conectados Deteccin de dispositivos en la localmente. pgina 15). Si se requiere configuracin de dispositivos remotos, contine en el paso 3. 3. Consulte la Figura 11 de la pgina 14 y seleccione el nmero de dispositivos visualizables (1 a 64). 4. Seleccione la conexin en la lista desplegable.* 5. Seleccione el tipo de dispositivo en la lista desplegable.* 6. En el cuadro de texto Nombre del dispositivo, escriba el nombre del dispositivo. Selecciona el nmero de ubicaciones visualizables que utilizar para definir los dispositivos conectados a la EGX. Selecciona la conexin. Selecciona el tipo de dispositivo. Introduce el nombre del dispositivo.

7. En el cuadro de texto ID local, escriba la Introduce la direccin local del dispositivo. direccin del dispositivo esclavo serie si est en el puerto serie, o escriba la direccin que desee utilizar para acceder a un dispositivo remoto.* 8. En el cuadro de texto ID remoto, escriba la Introduce la direccin del dispositivo remoto. direccin del dispositivo remoto.* 9. Repita los pasos 4 a 8 hasta introducir todos los dispositivos. 10. Haga clic en Aplicar. Introduce todos los dispositivos conectados. Actualiza los valores de Lista de dispositivos.

* Este parmetro de configuracin slo se puede cambiar si est deshabilitado el registro de datos para el dispositivo que se est actualizando. Consulte Registro de dispositivos en la pgina 17.

Figura 10:

Pgina Lista de dispositivos

2009-2013 Schneider Electric. Reservados todos los derechos.

13

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Figura 11:

Pgina Lista de dispositivos con las conexiones remotas admitidas

Tabla 7:

Configuracin de Lista de dispositivos


Descripcin
Selecciona el nmero de dispositivos que se tienen que mostrar. Selecciona el sitio de la conexin.

Opcin
Nmero de dispositivos visualizables Conexin

Valor
De 1 a 64 Predeterminado: 8 Puerto serie o direccin IP Predeterminado: Puerto serie Gama de dispositivos admitidos

Tipo de dispositivo Nombre del dispositivo ID local ID remoto

Selecciona el tipo de dispositivo que tiene que aparecer en la lista. Le permite asignar nombres a dispositivos individuales. Debe definir el ID local. Debe definir el ID remoto.

14

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Deteccin de dispositivos

La opcin Deteccin de dispositivos permite a la EGX detectar dispositivos Modbus residentes en el puerto serie que no figuran en Lista de dispositivos. Los dispositivos previamente introducidos en Lista de dispositivos se validan independientemente del intervalo de deteccin establecido. Deteccin Cuando inicia una deteccin de dispositivos, la EGX consulta el puerto serie local utilizando un intervalo de direcciones definido por el usuario (consulte la Figura 12 de la pgina 16). Para la deteccin en la conexin en serie, se utiliza el protocolo Modbus ASCII o RTU, dependiendo de la configuracin del puerto serie actual. Si el dispositivo contesta a la consulta, el ID local se establece en la direccin de deteccin actual y se proporciona al dispositivo un nombre de dispositivo predeterminado. La EGX intenta entonces identificar el tipo de dispositivo. Si la EGX reconoce el tipo de dispositivo del dispositivo detectado, la EGX introduce el tipo de dispositivo reconocido en el campo Tipo de dispositivo. Si la EGX no reconoce el tipo de dispositivo, el campo Tipo de dispositivo se establece al valor predeterminado Modbus. Un campo de estado muestra el estado de deteccin. Validacin Todas las entradas de Lista de dispositivos previamente definidas para todas las conexiones (serie y remotas), ya estn aquellas dentro o fuera del intervalo de direcciones de comienzo y fin de deteccin, se validan durante el proceso de deteccin. El protocolo de validacin en la conexin serie se determina en funcin de la configuracin actual del dispositivo en la lista de dispositivos. El protocolo TCP/IP se utiliza para la validacin de dispositivos remotos. La EGX muestra el ID local, el nombre del dispositivo almacenado y el tipo de dispositivo almacenado de Lista de dispositivos, y luego consulta al dispositivo. Se muestra el tipo de dispositivo identificado por la consulta, y luego se compara con lo que se ha definido previamente. El estado mostrar entonces si se ha encontrado una diferencia o si es vlida la configuracin previamente definida. NOTA: Puede editar el nombre del dispositivo y el tipo de dispositivo y seleccionar individualmente los dispositivos que se guardarn en Lista de dispositivos. Sin embargo, si est habilitado el registro para un dispositivo, slo podr modificar su nombre.
Accin Resultado

1. En el men Configuracin, haga clic en Lista Abre la pgina Lista de dispositivos. de dispositivos. 2. Para detectar dispositivos conectados localmente, haga clic en Deteccin. Abre la pgina Deteccin de dispositivos.

3. Introduzca una direccin de comienzo y una Introduce el intervalo de direcciones de direccin de fin. deteccin. NOTA: Se validarn los dispositivos introducidos previamente en la lista de dispositivos con direcciones (ID locales) fuera del intervalo de deteccin. 4. Haga clic en Iniciar deteccin. (Haga clic en Comienza por detectar todos los Detener deteccin para detener el proceso.) dispositivos conectados y definidos. NOTA: La deteccin slo busca dispositivos serie Modbus locales conectados a la EGX. Los dispositivos remotos se tienen que agregar manualmente. Consulte Conexiones con dispositivos remotos en la pgina 10. 5. Introduzca un nombre del dispositivo nuevo en el cuadro de texto Nombre. Cambia el nombre del dispositivo.

6. Marque la casilla de verificacin Guardar Selecciona una entrada de dispositivo que situada junto al dispositivo que desee guardar se tena que guardar o suprimir, o cancela la en Lista de dispositivos. seleccin de esta. 7. Haga clic en Aplicar en la pgina Deteccin de dispositivos. Guarda en la lista de dispositivos la configuracin de todos los dispositivos que se han marcado para ser guardados.

2009-2013 Schneider Electric. Reservados todos los derechos.

15

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Figura 12:

Deteccin de dispositivos

Tabla 8:
Opcin
Direccin de comienzo/fin Guardar Conexin

Opciones de deteccin de dispositivos


Descripcin
Define el intervalo de direcciones Modbus que se utilizar para detectar dispositivos conectados al puerto serie de la EGX. Le permite guardar el dispositivo seleccionado en Lista de dispositivos. Muestra la conexin en la que se ha detectado o validado el dispositivo. Muestra el tipo de dispositivo definido para este dispositivo. Le permite asignar el tipo de dispositivo de la lista desplegable. Le permite introducir un nombre personalizado para el dispositivo. Muestra el ID local del dispositivo. Muestra el ID del dispositivo remoto. Muestra el estado de deteccin o validacin.

Valor
De 1 a 247 Predeterminado: comienzo: 1; fin: 10 Activado o desactivado Predeterminado: Activado Puerto serie o direccin IP (para validacin de dispositivos remotos) Vlido, Desconocido, Error, Encontrado, Detectando o Intentando

Definido Asignado Nombre ID local ID remoto Estado

16

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Registro de dispositivos

El registro de datos est disponible para todos los tipos de dispositivos admitidos por la EGX. La EGX es capaz de registrar a intervalos predefinidos (5, 10, 15, 20, 30 y 60 minutos) datos procedentes de dispositivos conectados tanto local como remotamente. A continuacin se ofrece una explicacin de cmo registra datos la EGX y cmo se configura el registro para un dispositivo. Muchos de los dispositivos de un sistema de supervisin de potencia no poseen la capacidad para registrar datos en una memoria no voltil. La EGX300 proporciona este tipo de registro de datos a intervalos predefinidos para un mximo de 64 dispositivos conectados en serie y remotamente. Almacena los datos registrados en archivos FIFO (Primero en entrar, primero en salir) no voltiles. La capacidad de registro de cada archivo de registro cronolgico de datos es variable y depende del intervalo de registro seleccionado. Dicha capacidad se calcula dividiendo el nmero mximo de intervalos registrados que puede albergar un archivo de registro (171.072) entre el producto del nmero de temas registrados por los intervalos registrados diariamente.
Capacid. archivo de reg. = Intervs. (mx.)/(temas por interv. x intervalos reg. a diario)

Registro de datos de intervalo

Por ejemplo, la capacidad del registro cronolgico de datos de un dispositivo que almacena tres temas cada 10 minutos se calculara de la siguiente manera:
Intervalos registrados diariamente = Minutos del da/intervalo de registro (en min) = 1140/10 = 144 intervalos Capacidad del archivo de registro = Mximo de intervalos posibles/(temas registrados por intervalo x intervalos registrados diariamente) = 171072/(3 x 144) = 396 das

La capacidad de registro se calcula dinmicamente y se muestra en la pgina de seleccin de temas (consulte la Tabla 9 para ver algunos ejemplos). Tabla 9: Intervalos de registro de muestreos
Capacidad de registro (en das) de los intervalos de registro designados Intervalo de 5 min 1 2 3 4 5 6 594 297 198 148 118 99 Intervalo de 10 min 1188 594 396 297 237 198 Intervalo de 15 min 1782 891 594 445 356 297

N. de temas

Configurar registro por intervalos

Cada dispositivo incluido en la lista de dispositivos se puede habilitar independientemente para registro de datos. Los temas que registrar son exclusivos de cada dispositivo. Para ver los registros de datos de intervalo, consulte Registro de dispositivos en la pgina 41. NOTA: Para habilitar la funcin Registro de dispositivos, es necesario seleccionar un valor de tiempo en la ventana desplegable Intervalo de registro. Se recomienda que deshabilite la funcin de registro de dispositivos correspondiente al dispositivo que se est configurando. Para ello consulte la Figura 13 de la pgina 18 y desactive la casilla de verificacin de registro relativa al dispositivo que se va a seleccionar.

2009-2013 Schneider Electric. Reservados todos los derechos.

17

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Accin
1. En el men Configuracin, haga clic en Registro de dispositivos (consulte la Figura 13). 2. Consulte la Figura 13 y marque Registro para los dispositivos que desee registrar. Para seleccionar todos los dispositivos, haga clic en seleccionar todo y, a continuacin, haga clic en Aplicar. Para cancelar la seleccin de todos los dispositivos, haga clic en borrar, y a continuacin, haga clic en Aplicar. 3. Seleccione el intervalo de registro. 4. Haga clic en Aplicar. OPCIONES Si desea personalizar el contenido del registro, habilite el registro de dispositivos y, a continuacin, lleve a cabo lo siguiente: 1. Seleccione un intervalo de registro que no sea cero y desactive la casilla Registro del dispositivo especfico. 2. Bajo Personalizar, haga clic en el vnculo temas correspondiente al dispositivo que desee configurar. 3. Consulte la Figura 14 de la pgina 19 y marque los temas que desee registrar. Para seleccionar todos los temas, haga clic en seleccionar todo y, a continuacin, haga clic en Aplicar. Para cancelar la seleccin de todos los temas, haga clic en borrar, y a continuacin, haga clic en Aplicar. Para seleccionar los temas predeterminados, haga clic en Predeterminados en la parte inferior de la pantalla. Para borrar registros de datos, marque Purgar datos en aquellos que desee borrar. 1. Para seleccionar todos los dispositivos, haga clic en seleccionar todo y, a continuacin, en Aplicar. 2. Para cancelar la seleccin de todos los dispositivos, haga clic en borrar, y a continuacin, haga clic en Aplicar. Para deshabilitar el registro, seleccione el intervalo de registro cero, asegrese de que no haya ninguna seleccin de Registro marcada y, a continuacin, haga clic en Aplicar.

Resultado
Abre la pgina Registro de dispositivos. Selecciona los dispositivos que se tienen que registrar.

Selecciona el intervalo de registro para los dispositivos seleccionados. Actualiza la configuracin del registro de dispositivos de la EGX.

Selecciona los temas de dispositivos que se tienen que registrar y luego vuelve a la pgina principal Registro de dispositivos. NOTA: Si cambia los temas predeterminados registrados relativos a un dispositivo, aparece un asterisco (*) junto a temas en la columna Personalizar correspondiente a ese dispositivo. El cambio de los temas de un registro de dispositivos que ya haya estado activo borrar todos los datos previamente registrados para este dispositivo. Cuando sea necesario, los datos deben recuperarse de la EGX antes de hacer los cambios. Selecciona los registros de datos que se tienen que purgar. NOTA: Para purgar un registro de datos, el dispositivo no debe tener habilitada la casilla de verificacin Registro. Deshabilita la funcin de registro.

Figura 13:

Pgina Registro de dispositivos

Temas que registrar

Es posible seleccionar individualmente los temas que se registrarn por cada dispositivo.
Accin
1. En la pgina Registro de dispositivos, haga clic en el vnculo temas del dispositivo deseado.

Resultado
Abre la pgina de seleccin de temas.

2. Consulte la Figura 14 de la pgina 19 y marque los temas que Selecciona los temas que desee registrar. debern registrarse. Para seleccionar todos los temas, haga clic en seleccionar todo. Para cancelar la seleccin de todos los temas, haga clic en borrar. Para seleccionar los temas predeterminados, haga clic en Predeterminados. 3. Haga clic en Aplicar. Guarda la seleccin de temas que se registrarn.

18

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Figura 14:

Pgina de seleccin de temas

Exportacin del registro de dispositivos

Esta opcin le permite exportar registros de dispositivos de tres maneras: por correo electrnico, por FTP o por HTTP. En las secciones siguientes se describen dichos mtodos. NOTA: Si los servidores de correo electrnico, FTP o HTTP no estn situados en el mismo segmento de red Ethernet que la EGX, asegrese de configurar correctamente la pasarela predeterminada de la EGX. Consulte Configuracin de Ethernet y TCP/IP en la pgina 5.

Exportacin por correo electrnico


Accin Resultado
1. En la pgina Configuracin, haga clic en Exportacin del Abre la pgina Exportacin del registro de dispositivos. registro de dispositivos. 2. Seleccione Correo electrnico como modo de transporte. Abre las opciones de exportacin de registros de dispositivos por correo electrnico. Selecciona slo datos de intervalos nuevos registrados desde la ltima exportacin de datos realizada correctamente.

3. Marque la casilla de verificacin Incremental. NOTA: Si el transporte se programa como Cada hora o como Intervalo de registro, la casilla de verificacin Incremental se seleccionar automticamente. NOTA: Si no se selecciona la casilla de verificacin Incremental, se enviar el archivo de registros completo por correo electrnico en cada intervalo programado. 4. Seleccione Cada hora, Diariamente, Semanalmente, Mensualmente o Intervalo de registro.

Selecciona la frecuencia con la que se envan los registros de datos.

2009-2013 Schneider Electric. Reservados todos los derechos.

19

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Accin
5. Dependiendo de las opciones seleccionadas en el paso anterior, seleccione la hora del da, el da de la semana y/o el da del mes. 6. En el cuadro de texto Desde direccin, escriba la direccin de correo electrnico de la persona que administra el dispositivo. NOTA: Se necesita una direccin de correo electrnico del remitente porque la mayora de los servidores SMTP as lo requieren.

Resultado
Selecciona cundo se envan los registros de datos. Introduce desde qu direccin se ha enviado el correo electrnico.

7. En los cuadros de texto A direcciones, escriba las Introduce las direcciones de direcciones de correo electrnico (cinco como mximo) de correo electrnico de los las personas que van a recibir los registros de datos (una receptores. direccin por cada cuadro de texto). 8. En los cuadros de texto Direccin IP del servidor, introduzca la direccin del servidor de correo saliente (0.0.0.0 a 255.255.255.255). NOTA: Pregunte al administrador de la red en caso de que usted no conozca la direccin del servidor de protocolo sencillo de transferencia de correo (SMTP). 9. En el cuadro de texto Puerto TCP del servidor, introduzca el puerto de entrega del servidor de correo saliente. Introduce la direccin del servidor que entrega los registros de datos de correo electrnico.

Introduce el puerto de entrega del servidor de correo saliente. Predeterminado: 25

10. Si el servidor SMTP requiere informacin de inicio de Le permite introducir sesin, habilite la casilla de verificacin El servidor SMTP informacin de inicio de requiere iniciar sesin. sesin del servidor SMTP. NOTA: La EGX es compatible con autenticacin de acceso Plain, Login, CRAM-MD5 y Digest-MD5. 11. Si ha marcado la casilla de verificacin El servidor SMTP Registra su informacin de requiere iniciar sesin, introduzca su nombre de usuario inicio de sesin del y su contrasea en los cuadros de texto correspondientes. servidor SMTP. 12. Haga clic en Correo electrnico de prueba para enviar Enva un correo electrnico de un correo electrnico de prueba utilizando los parmetros prueba, aplica los valores de establecidos por usted, o haga clic en Aplicar. correo electrnico para exportar registros o realiza ambas NOTA: Al hacer clic en Correo electrnico de prueba, se acciones. aplican los valores de correo electrnico para exportar registros y se enva un correo electrnico de prueba; y al hacer clic en Aplicar, slo se aplican los valores.

Figura 15:

Pgina Exportacin de registros de dispositivos: Correo electrnico

20

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Exportacin por FTP


Accin Resultado
1. En la pgina Configuracin, haga clic en Exportacin Abre la pgina Exportacin del del registro de dispositivos. registro de dispositivos. 2. Seleccione FTP como modo de transporte. 3. Habilite la casilla de verificacin Incremental. Abre las opciones de exportacin de registro de dispositivos por FTP.

Selecciona para su envo slo los nuevos datos registrados desde el NOTA: Si el transporte se programa como Cada hora ltimo intervalo de envo correcto. o como Intervalo de registro, la casilla de verificacin Incremental se seleccionar automticamente. NOTA: Si no se selecciona la casilla de verificacin Incremental, se enviar el archivo de registro completo por FTP en cada intervalo programado.

4. Seleccione Cada hora, Diariamente, Semanalmente, Selecciona la frecuencia con la que Mensualmente o Intervalo de registro. se transportan los registros de datos. 5. Dependiendo de las opciones seleccionadas en el paso anterior, seleccione la hora del da, el da de la semana y/o el da del mes. 6. En los cuadros de texto Direccin IP del servidor, introduzca la direccin del servidor FTP saliente (0.0.0.0 a 255.255.255.255). NOTA: Pregunte al administrador de la red en caso de que usted no conozca la direccin del servidor de protocolo de transferencia de archivos (FTP). 7. En el cuadro de texto Directorio, introduzca el directorio. 8. Introduzca su nombre de usuario y contrasea en los cuadros de texto. 9. Habilite la casilla de verificacin Pasivo. Le permite introducir informacin de directorio correspondiente al servidor remoto. Registra sus datos de inicio de sesin en el servidor. Establece la transferencia pasiva de archivos por FTP. Selecciona cundo se transportan los registros de datos. Introduce la direccin del servidor que transporta los registros de datos.

10. Si est exportando los datos a StruxureWare Energy Aade la direccin MAC para crear Operation, haga clic en la casilla de verificacin Aadir un nombre de archivo exclusivo. la direccin MAC al nombre del archivo. NOTA: Al seleccionar esta casilla de verificacin se impide que los datos se mezclen en el caso de que dos archivos enviados a Energy Operation tengan el mismo nombre. Para ver ms informacin sobre el formato del archivo de registro, consulte Obtencin de registros cronolgicos de datos en la pgina 43. 11. Haga clic en Probar FTP para probar los parmetros del FTP o haga clic en Aplicar. NOTA: Al hacer clic en Probar FTP, se aplican los valores del FTP para exportacin de registros y se transfiere un archivo de prueba; y al hacer clic en Aplicar, slo se aplican los valores. Enva un archivo de prueba al servidor y directorio FTP, aplica los valores del FTP o realiza ambas acciones.

2009-2013 Schneider Electric. Reservados todos los derechos.

21

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Figura 16:

Pgina Exportacin de registro de dispositivos: FTP

NOTA: Si el transporte se programa como Cada hora o como Intervalo de registro, la casilla de verificacin Incremental se seleccionar automticamente.

22

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Exportacin por HTTP


Accin
1. En la pgina Configuracin, haga clic en Exportacin del registro de dispositivos. 2. Seleccione HTTP como modo de transporte. 3. Habilite la casilla de verificacin Incremental. NOTA: Si el transporte se programa como Cada hora o como Intervalo de registro, la casilla de verificacin Incremental se seleccionar automticamente. NOTA: Si no se selecciona la casilla de verificacin Incremental, se enviar el archivo de registro completo por HTTP en cada intervalo programado. 4. Seleccione Cada hora, Diariamente, Semanalmente, Mensualmente o Intervalo de registro. 5. Dependiendo de las opciones seleccionadas en el paso anterior, seleccione la hora del da, el da de la semana y/o el da del mes. 6. En los cuadros de texto Direccin IP del servidor, introduzca la direccin del servidor HTTP. NOTA: Pregunte al administrador de la red en caso de que usted no conozca la direccin del servidor del protocolo de transferencia de hipertexto (HTTP). 7. En el cuadro de texto Puerto TCP del servidor, introduzca el puerto del servidor HTTP. NOTA: Si desea exportar utilizando una capa de sockets seguros (SSL), introduzca el nmero de puerto TCP del servidor HTTPS, que suele ser 443. 8. Si va a utilizar un servidor proxy, Introduce la direccin IP del servidor proxy que introduzca la direccin IP en los cuadros transporta los registros de datos. de texto Direccin IP del servidor proxy. NOTA: Pregunte al administrador de la red en caso de que usted no conozca la direccin del servidor proxy. 9. En el cuadro de texto Puerto TCP del servidor proxy, introduzca el puerto del servidor HTTP. NOTA: Si desea exportar utilizando una capa de sockets seguros (SSL), introduzca el nmero de puerto TCP del servidor HTTPS, que suele ser 443. 10. En el cuadro de texto Ruta, introduzca la Introduce la ruta de secuencia de comandos ruta de acceso a la secuencia de del servidor. comandos del servidor que ser ejecutada por el servidor web cuando la EGX le enve datos. 11. En el cuadro de texto Nombre de campo, Permite a la EGX insertar archivos a una secuencia de comandos existente de servidor introduzca el nombre de archivo que el web. servidor web espera recibir. NOTA: Si no se requiere este dato, utilice el valor predeterminado datafile1. 12. En el cuadro de texto Nombre de host, introduzca el nombre de dominio del host. Identifica un host especfico en el servidor web en el caso de que aloje varios dominios en una sola direccin IP. (Este cuadro est en blanco de manera predeterminada.) Registra sus datos de inicio de sesin en el servidor. Introduce el puerto TCP de entrega saliente. Valor predeterminado: 0 Introduce el puerto TCP de entrega saliente. Predeterminado: 80 Selecciona la frecuencia con la que se transportan los registros de datos. Selecciona cundo se transportan los registros de datos.

Resultado
Abre la pgina Exportacin del registro de dispositivos. Abre las opciones de exportacin de registro de dispositivos por HTTP. Selecciona para su envo slo los nuevos datos registrados desde el ltimo intervalo de envo correcto.

Introduce la direccin IP del servidor que transporta los registros de datos.

13. Introduzca su nombre de usuario y contrasea en los cuadros de texto dispuestos al efecto.

2009-2013 Schneider Electric. Reservados todos los derechos.

23

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Accin
14. Si desea exportar utilizando una capa de sockets seguros, seleccione SSL.

Resultado
Todos los registros de dispositivos que se exportan mediante HTTP, lo harn a travs de una capa de sockets seguros (HTTPS).

15. Si est exportando los datos a Aade la direccin MAC para crear un nombre StruxureWare Energy Operation, haga clic de archivo exclusivo. en la casilla de verificacin Aadir la direccin MAC al nombre del archivo. NOTA: Al seleccionar esta casilla de verificacin se impide que los datos se mezclen en el caso de que dos archivos enviados a Energy Operation tengan el mismo nombre. Para ver ms informacin sobre el formato del archivo de registro, consulte Obtencin de registros cronolgicos de datos en la pgina 43. 16. Haga clic en Probar HTTP para probar los Enva un archivo de prueba al servidor y valores del HTTP o haga clic en Aplicar. directorio HTTP, aplica los valores de HTTP o realiza ambas acciones. NOTA: Al hacer clic en Probar HTTP, se aplican los valores de exportacin de registros por HTTP y se transfiere un archivo de prueba. Si se hace clic en Aplicar, solamente se aplicarn los valores.

Figura 17:

Pgina Exportacin del registro de dispositivos: HTTP

Fecha y hora

La pgina Fecha y hora le permite ajustar la fecha y la hora de la EGX.


Accin
1. En el men Configuracin, haga clic en Fecha y hora. 2. Configure ao, mes, da, hora, minutos y segundos. 3. Seleccione la Desviacin de zona horaria.

Resultado
Abre la pgina Fecha y hora. Establece la fecha y la hora. Ajusta el reloj a la zona horaria seleccionada.

4. Para establecer que el reloj se ajuste Le permite establecer que el reloj se ajuste automticamente al horario de verano, automticamente al horario de verano. habilite la casilla de verificacin Habilitar ajuste automtico del horario de verano. 5. Introduzca nmero, da, mes y hora de comienzo y fin del horario de verano. 6. Haga clic en Aplicar. Establece el comienzo y fin del ajuste del horario de verano. Guarda la configuracin de Fecha y hora.

24

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Figura 18:

Pgina Fecha y hora

Sincronizacin horaria de red

La habilitacin de la sincronizacin de la hora de la red permite ajustar la hora y la fecha del reloj del sistema EGX mediante un servidor de protocolo de hora de la red (NTP). NOTA: Si el servidor NTP no est situado en el mismo segmento de red Ethernet que la EGX, asegrese de configurar correctamente la pasarela predeterminada de la EGX.

Accin

Resultado

1. Seleccione la casilla de verificacin Activar Revela la seccin Parmetros de SNTP y la sincronizacin horaria de red en la pgina ltima sincronizacin horaria realizada Fecha y hora. correctamente. 2. Configure la desviacin de zona horaria, el Configura los parmetros del SNTP. intervalo de adquisicin y las direcciones IP de los servidores principal y secundario NTP (consulte la Tabla 10 en la pgina 26). 3. Haga clic en Aplicar. Guarda la configuracin del SNTP.

Figura 19:

Activar la sincronizacin horaria de red

2009-2013 Schneider Electric. Reservados todos los derechos.

25

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Tabla 10: Configuracin de los parmetros del SNTP


Opcin
Desviacin de zona horaria Habilitar ajuste automtico del horario de verano

Descripcin
La hora se establece sobre la base del valor seleccionado de la hora universal coordinada (UTC).

Valor
UTC12:00 a UTC+13:00 Predeterminado: UTC (GMT)

Permite definir cundo comienza y termina Primer a Quinto o ltimo el horario de verano. Domingo a Sbado Enero a Diciembre 0:00 a 23:00 Predeterminado: Inicio del horario de verano: Segundo Domingo de Marzo a las 2:00. Finalizacin del horario de verano: Segundo Domingo de Noviembre a las 2:00. Controla la frecuencia con la que la EGX se pone en contacto con el NTP para obtener la hora correcta. La direccin IP del servidor principal NTP con la que se pone en contacto la EGX para obtener la hora correcta. La direccin IP del servidor secundario NTP con la que se pone en contacto la EGX para obtener la hora correcta. De 1 hora a 1 semana Predeterminado: 1 semana 0.0.0.0 a 255.255.255.255 Predeterminado: 0.0.0.0 0.0.0.0 a 255.255.255.255 Predeterminado: 0.0.0.0

Intervalo de adquisicin Direccin IP del servidor principal NTP Direccin IP del servidor secundario NTP

Parmetros del SNMP

La EGX es compatible con el SNMP, lo cual permite que un administrador de red acceda de manera remota a una EGX mediante un gestor de SNMP y visualice el estado de la conexin y los diagnsticos de la EGX en formato MIB-II.

Accin
1. En el men Configuracin, haga clic en Parmetros del SNMP.

Resultado
Abre la pgina Parmetros del SNMP.

2. Marque la casilla de verificacin Activar SNMP Activa el SNMP. para habilitar el protocolo simple de administracin de redes. 3. Introduzca el contacto del sistema, el nombre del sistema, su ubicacin, el nombre de la comunidad de slo lectura y el nombre de la comunidad de lectura y escritura. 4. Haga clic en Aplicar. Introduce la informacin del sistema SNMP y los nombres de acceso de las comunidades. Guarda los valores del SNMP.

Figura 20:

Pgina Parmetros del SNMP

26

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Filtrado de Modbus TCP/IP

Esta funcin permite al administrador asignar el nivel de acceso que los clientes Modbus TCP/IP tienen a los dispositivos (locales o remotos) conectados a la EGX. NOTA: Existe una direccin Modbus TCP/IP annima (***.***.***.***) que se puede configurar como Slo lectura o Ninguna. Si la configura como Slo lectura, permitir que cualquier cliente Modbus TCP/IP que no est en la lista de filtrado acceda a los dispositivos esclavos en serie con acceso de slo lectura. Si la configura como Ninguna, bloquear a todos los clientes Modbus TCP/IP que no estn en la lista de filtrado.
Accin Resultado

1. En el men Configuracin, haga clic Abre la pgina Filtrado de Modbus TCP/IP. en Filtrado de Modbus TCP/IP. 2. Marque la casilla de verificacin Activar filtrado. 3. En la columna Direccin IP, introduzca la direccin del cliente Modbus TCP/IP. Activa el filtrado. Introduce la direccin IP de un cliente Modbus TCP/IP que tendr acceso a los dispositivos conectados a la EGX.

4. En la columna Nivel de acceso, Selecciona el nivel de acceso para la correspondiente seleccione Slo lectura o Completo. direccin IP. Cuando se establece como Slo lectura, slo se permiten los siguientes cdigos de funcin Modbus TCP/IP: Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100 Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18, 2B, 64 5. Repita los pasos 3 y 4 para agregar Contina aadiendo direcciones IP para el filtrado. ms direcciones IP. 6. Haga clic en Aplicar. Guarda la lista de filtrado de direcciones Modbus TCP/IP.

Figura 21:

Pgina Filtrado de Modbus TCP/IP

2009-2013 Schneider Electric. Reservados todos los derechos.

27

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Vnculos de documentacin

La EGX admite dos tipos de vnculos de documentacin: 1. acceso a archivo local (documentacin guardada incorporada en la EGX); 2. acceso URL externo. NOTA: Los documentos de archivos locales que desee que aparezcan en la pgina web Documentacin deber colocarlos en la carpeta www/documentation (documentacin) de la EGX utilizando FTP.
Accin
1. En el men Configuracin, haga clic en Vnculos de documentacin. 2. Para acceso a archivo: Marque la casilla de verificacin Activado correspondiente a los vnculos de Nombre de archivo que desee habilitar. Para acceso URL: Marque la casilla de verificacin Activado correspondiente a los vnculos de URL que desee habilitar. 3. Marque Ventana nueva si desea que los Define qu archivos y URL se abrirn en una archivos y URL seleccionados se abran en ventana nueva cuando se haga clic en ellos. una ventana nueva al hacer clic en ellos. 4. Asigne un nombre al ttulo del vnculo de Establece el ttulo del vnculo de documentacin en la casilla de verificacin documentacin que aparecer en la pgina Texto del vnculo. Documentacin. 5. Haga clic en Aplicar. Actualiza los valores de los vnculos de documentacin de la EGX.

Resultado
Abre la pgina Vnculos de documentacin. Define qu archivos y URL aparecen en la pgina Documentacin.

Figura 22:

Pgina Vnculos de documentacin

NOTA: Para obtener informacin sobre la manera de acceder a la documentacin cargada, consulte Documentacin en la pgina 51.

28

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Cuentas de usuario

A los usuarios de la EGX se les asignan nombres de usuario y contraseas. Cada usuario pertenece a un grupo, cuyos derechos de acceso a las pginas web de la EGX los asigna el administrador de la EGX. NOTA: Existen dos cuentas de usuario predeterminadas: Administrator (cuya contrasea predeterminada es Gateway) y Guest (cuya contrasea predeterminada es Guest).
Accin
1. En el men Configuracin, haga clic en Cuentas de usuario. 2. Si desea cambiar el nombre de un grupo, escriba el nuevo nombre en uno de los cuadros de texto Grupos (no se puede cambiar el nombre del grupo Administradores).

Resultado
Abre la pgina Cuentas de usuario. Introduce un nuevo nombre de grupo.

3. En la seccin Usuarios, introduzca un Introduce el nombre y la contrasea de un usuario. nombre (1 a 24 caracteres) y contrasea (0 a 12 caracteres) para el La EGX300 comprueba el grado de la seguridad de nuevo usuario. la contrasea, mostrando una indicacin cromtica y textual de su solidez: NOTA: Los nombres de usuario y las Rojo = Contrasea en blanco/contrasea contraseas respetan maysculas y no segura minsculas y slo pueden contener Amarillo = Contrasea de seguridad media caracteres alfanumricos. Azul = Contrasea segura Verde = Contrasea muy segura 4. Seleccione un grupo y el idioma Selecciona el grupo y el idioma para un usuario. predeterminado para el nuevo usuario. 5. Repita los pasos 3 y 4 por cada usuario adicional que desee agregar. 6. Haga clic en Aplicar. Contina aadiendo usuarios. Guarda toda la configuracin de las cuentas de usuario.

Tabla 11: Cuentas y contraseas de la EGX


Cuenta
Administrator Guest Cuentas definidas por el usuario (hasta 11 cuentas)

Contrasea predeterminada
Gateway Guest Sin valor predeterminado. La contrasea la define el usuario.

Figura 23:

Pgina Cuentas de usuario

2009-2013 Schneider Electric. Reservados todos los derechos.

29

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Acceso a pgina Web


Accin Resultado
1. En el men Configuracin, haga clic en Acceso a Abre la pgina Acceso a pgina Web. pgina Web. 2. Seleccione el nivel de acceso (Ninguna, Slo lectura o Completo) que tiene cada grupo de usuarios para las pginas web. 3. Para permitir el acceso de invitados a la pgina web, seleccione Slo lectura en la columna Guest. NOTA: Si el grupo Guest es de slo lectura, otros grupos se pueden configurar como Slo lectura o Completo. 4. Repita los pasos 2 y 3 para las opciones de cada Selecciona el nivel de acceso para cada seccin. pgina web. 5. Haga clic en Aplicar. Guarda los valores de las contraseas. Consulte la Tabla 12 a continuacin para ver una explicacin de los niveles de acceso correspondientes a cada grupo. Permite que el grupo Guest predeterminado acceda a la pgina web.

Tabla 12: Acceso de grupo


Grupo
Administrator

Acceso
Acceso completo a todas las pginas web. NOTA: Para garantizar la seguridad del sistema, le recomendamos que cambie la contrasea predeterminada del administrador la primera vez que se conecte al sistema. Acceso de slo lectura a las pginas web seleccionadas. Al elegir entre las siguientes opciones, el administrador asigna el acceso a las pginas web para cada grupo. Los niveles de acceso son los siguientes: Ninguna: el grupo no tiene acceso a la pgina web seleccionada. Slo lectura: la contrasea le concede al grupo acceso de slo lectura a la pgina web seleccionada. Completo: el grupo tiene el mismo acceso que el grupo de administradores a la pgina web seleccionada.

Guest Tres grupos definidos por el usuario

Figura 24:

Pgina Acceso a pgina Web

30

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Agregar o quitar pginas web personalizadas

Las pginas web personalizadas y otros tipos de archivos pueden transferirse desde su equipo a la EGX a travs de FTP. Los archivos enviados a travs de FTP a los directorios www/monitoring (supervisin), www/maintenance (mantenimiento) o www/control con extensiones .htm, .html o .shtml se asegurarn automticamente. Cada carpeta cuenta con un vnculo correspondiente en la barra de mens de la interfaz web. Cuando se hace clic en el vnculo de la barra de mens, las pginas web que haya agregado aparecern en el men en la parte izquierda de la ventana del navegador bajo Pginas personalizadas. NOTA: No se pueden crear nuevas carpetas dentro de las carpetas Monitoring, Control o Maintenance. Una vez que se hayan transferido las pginas web personalizadas u otros archivos a la EGX con FTP, se pueden agregar y quitar de la interfaz web sin eliminarlos de la EGX usando la pgina Agregar o quitar pginas Web. Esta pgina se abre desde la pgina Acceso a pgina Web.

Adicin de pginas web mediante FTP


Accin Resultado
1. Inicie el Explorador de Windows, escriba Abre el cuadro de dilogo Iniciar sesin ftp:// y la direccin IP de la EGX (por como. ejemplo, ftp://169.254.0.10) en el cuadro de texto Direccin y luego pulse Intro. 2. Escriba el nombre de usuario Administrator Abre una sesin de FTP con la EGX. y la contrasea de administrador en los cuadros de texto, y luego haga clic en Iniciar sesin. 3. Abra una nueva ventana del Explorador de Copia el archivo en el portapapeles. Windows, ubique la pgina web personalizada que desee enviar a la EGX, haga clic sobre ella con el botn derecho del ratn y despus haga clic en Copiar. 4. Vuelva a la ventana del Explorador de Abre la carpeta donde se almacenar la Windows de la EGX que abri en el paso 1 pgina web en la EGX. y abra la carpeta en la que vaya a copiar la pgina web (por ejemplo, /www/monitoring/). 5. Haga clic con el botn derecho en el panel Copia la pgina web personalizada en la EGX. derecho de la ventana del Explorador de Windows, luego haga clic en Pegar. NOTA: En vez de copiar y pegar el archivo, puede arrastrarlo y soltarlo en el Explorador de Windows. 6. Haga clic en Cerrar en la ventana del Explorador de Windows. Cierra el Explorador de Windows.

Eliminacin de pginas web mediante FTP


Accin Resultado
1. Inicie el Explorador de Windows, escriba Abre el cuadro de dilogo Iniciar sesin ftp:// y la direccin IP de la EGX (por como. ejemplo, ftp://169.254.0.10) en el cuadro de texto Direccin y luego pulse Intro. 2. Escriba el nombre de usuario Administrator Abre una sesin de FTP con la EGX. y la contrasea de administrador en los cuadros de texto, y luego haga clic en Iniciar sesin. 3. Abra la carpeta que contiene la pgina web Abre la carpeta que contiene la pgina web personalizada, haga clic con el botn personalizada y despus borra el archivo. derecho del ratn sobre el archivo que quiera eliminar y despus haga clic en Eliminar. 4. Haga clic en Cerrar en la ventana del Explorador de Windows. Cierra el Explorador de Windows.

2009-2013 Schneider Electric. Reservados todos los derechos.

31

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Agregar o quitar pginas web a o de la interfaz web

Accin
1. En el men Configuracin, haga clic en Acceso a pgina Web. 2. Haga clic en Agregar o quitar pginas Web (consulte la Figura 25).

Resultado
Abre la pgina Acceso a pgina Web. Abre la pgina Agregar o quitar pginas Web.

3. Si ha agregado pginas web Selecciona una pgina web personalizada o personalizadas a cualquiera de las anula la seleccin de esta. carpetas de la EGX, ver una lista de los nombres de archivo debajo del nombre de cada carpeta. Seleccione las pginas web que desee que vean los usuarios. Anule la seleccin de las pginas web que no desee que vean los usuarios. NOTA: Al anular la seleccin de una pgina web, esta no se borra de la EGX. 4. Haga clic en Aplicar. Agrega una pgina web personalizada a la interfaz web de la EGX o la quita de esta.

Figura 25:

Pgina Agregar o quitar pginas Web

32

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Preferencias

Esta opcin permite personalizar individualmente cada EGX.


Accin
1. En el men Configuracin, haga clic en Preferencias.

Resultado
Abre la pgina Preferencias.

2. Introduzca el nombre del equipo, la pgina Establece las preferencias. de inicio predeterminada, la velocidad de muestreo en tiempo real y de velocidad de comprobacin de las comunicaciones. 3. Haga clic en Aplicar. Actualiza la configuracin de Preferencias de la EGX.

Figura 26:

Pgina Preferencias

Tabla 13: Valores de las preferencias


Opcin
Nombre del equipo

Descripcin

Valor

Le permite introducir un nombre Predeterminado: personalizado para la EGX y para el equipo Powerlogic EGX300 asociado. Este nombre se utilizar en el encabezado de la interfaz web. Le permite seleccionar la pgina de inicio predeterminada. Inicio, Resumen de circuito, Resumen de intensidad de carga, Resumen de la demanda de intensidad, Resumen de potencia o Resumen de energa. Predeterminado: Inicio 5 a 60 segundos Predeterminado: 5 segundos Desactivado, 5 a 30 minutos Predeterminado: 15 minutos

Pgina de inicio predeterminada

Velocidad de muestreo Controla la frecuencia con la que se leen en tiempo real los datos procedentes de los dispositivos de las vistas estndar de Tabla de supervisin. Velocidad de comprobacin de las comunicaciones Controla la frecuencia con la que se realiza la comprobacin de las comunicaciones mientras el navegador est mostrando lecturas en tiempo real en las vistas estndar de Tabla de supervisin. Esta funcin intentar poner de nuevo en servicio automticamente cualquier dispositivo que se encuentre fuera de servicio.

2009-2013 Schneider Electric. Reservados todos los derechos.

33

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Tipos de dispositivos visualizables

La pgina Tipos de dispositivos visualizables proporciona una manera de gestionar los tipos de dispositivos disponibles para que el usuario pueda seleccionarlos en la pgina web de configuracin de la lista de dispositivos. Dado que la EGX300 admite muchos tipos diferentes de dispositivos, retirarlos de la lista de tipos de dispositivos disponibles quizs simplifique el ajuste de la pgina web de configuracin de la lista de dispositivos.
Accin Resultado

1. En el men Configuracin, haga clic en Tipos de dispositivos Abre la pgina Tipos de visualizables. dispositivos visualizables. 2. Seleccione los tipos de dispositivos que estarn disponibles para la configuracin de la lista de dispositivos. NOTA: Haga clic en seleccionar todo para habilitar todos los dispositivos y en borrar para deshabilitar todos ellos. NOTA: Es posible que no se pueda cambiar la disponibilidad del tipo de dispositivo de aquellos dispositivos que ya se estn utilizando. 3. Haga clic en Aplicar. Guarda los valores de Tipos de dispositivos visualizables. Selecciona los tipos de dispositivos que estarn disponibles para configurar la lista de dispositivos.

Figura 27:

Pgina Tipos de dispositivos visualizables

Historial de auditora

El historial de auditora consiste en una secuencia de registros o mensajes con una marca horaria. Graba los eventos de cambio de configuracin, error o fallo de autenticacin; tambin identifica al usuario que desencaden el evento. La pgina Historial de auditora permite configurar los cuatro grupos de informes y canales de mensajes. Por cada canal, elija los grupos de informes cuyos mensajes desee ver. Cuando asigne un grupo de informes a un canal, ver todos los mensajes que se generen en ese grupo de informes. Los canales de mensajes son los siguientes:

Archivo de registro de mantenimiento incorporado de la EGX Servidor Syslog remoto (Syslog es un estndar para el registro de mensajes) Correo electrnico

Todos los mensajes llevan una marca de fecha y hora e incluyen informacin de grupo de informes y de identificacin del usuario.
34 2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

La pgina Historial de auditora se divide en tres cuadros que corresponden a los tres canales de mensajes: Registro de mantenimiento, Syslog y Correo electrnico. (Consulte la Figura 28 de la pgina 36.) Es posible configurar de manera independiente los mensajes que se envan a cada canal. En la ventana Configuracin, haga clic en Historial de auditora. Se abre la pgina Historial de auditora. Siga las instrucciones de la tabla siguiente. Tabla 14: Configuracin de Historial de auditora
Opcin
Registro de mantenimiento Controla los tipos de informes cuyos mensajes desea que se visualicen en el registro de mensajes. Syslog Direccin IP del servidor A medida que se generen los mensajes, estos se reenviarn al servidor que indique. Los mensajes de Syslog se enviarn desde este puerto UDP del servidor. Introduzca la direccin IP del servidor remoto al que quiere reenviar los mensajes. Introduzca el nmero de puerto UDP correspondiente a esta direccin IP. Predeterminado = 514. Marque los tipos de informes cuyos mensajes desee reenviar. Elija la categora adecuada. A medida que se generen los mensajes, estos aparecern en el registro de mantenimiento incorporado de la EGX. Marque las opciones de informe que desee incluir. Predeterminado: No hay ninguna opcin marcada

Descripcin

Valor

Puerto UDP del servidor (protocolo de datagramas de usuario) Informe Lista desplegable Instalacin

Lista desplegable Gravedad

Cuatro tipos de informes cuyos mensajes se pueden reenviar. Proporciona una idea aproximada de la ubicacin del sistema donde se gener el mensaje. Aparece en Syslog. Le indica al usuario la importancia Elija la categora adecuada. relativa del mensaje. Debe determinar, para su instalacin, la importancia de cada tipo. Cuando se generan mensajes, la direccin de correo electrnico del emisor aparece en el campo del remitente. El cuerpo del correo electrnico incluir la direccin IP de la EGX, el nombre del grupo de informes, el nombre de usuario, la direccin IP del usuario y el mensaje del grupo de informes. Cuando se generan los mensajes, se envan a las direcciones de correo electrnico de los destinatarios.

Correo electrnico Desde direccin Introduzca la direccin del remitente (emisor) para los correos electrnicos. Mximo de 49 caracteres.

Introduzca las direcciones de los destinatarios (destinatario de todos los correos electrnicos de mensaje). Mximo de 49 caracteres por direccin. Si no introduce una direccin IP Direccin IP del servidor Esta es la direccin IP del de un servidor, no se enviar servidor al que se enviarn los ningn correo electrnico. correos electrnicos. Introduzca el nmero del Puerto TCP del servidor Este es el nmero del puerto TCP de la direccin IP del puerto TCP. El valor predeterminado es 25. servidor. El servidor SMTP requiere Esta casilla de verificacin sirve Marque la casilla para empezar iniciar sesin para activar el inicio de sesin a a aadir datos de inicio de fin de recibir correos electrnicos. sesin. El servidor SMTP requiere que se inicie una sesin. Nombre de usuario Nombre de usuario que utilizar Escriba el nombre de usuario la EGX para iniciar sesin en el que requiera el servidor SMTP (mx. 31 caracteres). servidor SMTP. Contrasea Clave que utilizar la EGX para Escriba la contrasea que requiera el servidor SMTP iniciar sesin en el (mx. 31 caracteres). servidor SMTP. Marque los tipos de informe Informe Se trata de los cuatro tipos de cuyos mensajes desee reenviar. informes cuyos mensajes se pueden reenviar. Se pueden marcar todos los que desee. Predeterminados/Aplicar Haga clic en Aplicar para guardar Haga clic en Aplicar o Predeterminados. las entradas que haya completado. Haga clic en Predeterminados para devolver cada campo a su estado predeterminado. A direcciones

2009-2013 Schneider Electric. Reservados todos los derechos.

35

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

63230-319-216B4_ES 06/2013

Figura 28:

Configuracin de Historial de auditora

Punto de acceso del sistema

El punto de acceso del sistema proporciona un medio de detectar otros dispositivos Schneider Electric conectados a la red y vincularse a estos. Esta funcin est configurada para su ejecucin de manera predeterminada, por lo que no es necesario configurar ningn parmetro adicional. Esta pantalla de configuracin le permitir introducir la direccin IP del grupo y su informacin asociada.

Accin

Resultado

1. En el men Configuracin, haga clic Abre la ventana Punto de acceso del sistema. en Punto de acceso del sistema. 2. Activado Cuando se marca esta casilla, las EGX300 con la misma direccin IP del grupo podrn detectarse entre s. Predeterminado = Activado. Escriba el nmero de puerto (de 1 a 65535) correspondiente al puerto UDP que utiliza la deteccin de la funcin Punto de acceso del sistema. Predeterminado = 59. Escriba la direccin IP del grupo, que admitir direcciones de unidifusin o multidifusin. Predeterminado = 224.0.1.2. Periodo de tiempo transcurrido entre mensajes de bienvenida emitidos por esta EGX300 con que se anuncia su presencia a otros dispositivos de punto de acceso del sistema de Schneider Electric que se encuentren en red. De 1 a 65535 segundos. Predeterminado = 300 segundos.

3. Puerto UDP

4. Direccin IP del grupo

5. Intervalo de introduccin

36

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Configuracin

Accin
6. Tiempo de espera

Resultado
Periodo de tiempo durante el cual los mensajes de bienvenida que emite esta EGX300 deberan ser retenidos por los destinatarios antes de considerar que esta no est disponible. De 2 a 65535 segundos. Predeterminado = 600 segundos. Es posible controlar la amplitud del rea de la red para detectar otros dispositivos. Se controla mediante el nmero de veces que se permite el reenvo de la multidifusin a otros. El intervalo de saltos de router permitidos es de 1 a 255. Predeterminado = 1. Las EGX300 de un grupo pueden dividirse en comunidades. Aquellas pasarelas que tengan la misma direccin IP del grupo y el mismo nmero de comunidad podrn detectarse entre s. Si se configura el nmero de comunidad como 0, ello permitir que una EGX300 detecte todas las EGX300 con la misma direccin IP de grupo independientemente del valor del parmetro de comunidad. Predeterminado = 0.

7. Perodo de vida de multidifusin

8. Comunidad

9. Predeterminados/Aplicar

Haga clic en Aplicar para guardar las entradas; haga clic en Predeterminados para volver a los valores predeterminados que se enumeran.

Figura 29:

Pgina de configuracin Punto de acceso del sistema

2009-2013 Schneider Electric. Reservados todos los derechos.

37

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

63230-319-216B4_ES 06/2013

SUPERVISIN
Datos en tiempo real

La EGX proporciona pantallas en las que muestra datos y tendencias en tiempo real, adems de tendencias histricas de registros de datos. Las pginas Datos en tiempo real proporcionan lecturas bsicas de dispositivos seleccionados en tiempo real as como resmenes de dispositivos. Para ver una tabla de datos en tiempo real, vaya al men Supervisin y seleccione un dispositivo bajo Datos en tiempo real > Pginas de dispositivo nico.

Pginas de dispositivo nico

Configuracin de lecturas bsicas


Accin Resultado
1. En la parte superior de la pantalla, seleccione Selecciona las cantidades que se Intensidad, Potencia, Tensin L-L o Tensin L-N mostrarn en la pantalla grfica de para que aparezcan en la pantalla grfica de indicadores analgicos. indicadores analgicos. NOTA: Los indicadores analgicos no estn disponibles en todos los tipos de dispositivos. 2. De manera predeterminada, los indicadores ajustarn automticamente el rango de visualizacin. Si desea un rango fijo, seleccione Rango. Las instrucciones para configurar el rango de los indicadores analgicos se encuentran en la tabla siguiente. 3. Haga clic en Aplicar. Controla el rango de visualizacin de los indicadores analgicos.

Actualiza la seleccin de rango en la pgina del dispositivo.

Figura 30:

Pgina Lecturas bsicas

38

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

Rango de los indicadores analgicos

Es posible configurar el rango de los indicadores grficos analgicos de la pgina Lecturas bsicas, o bien establecer que se ajuste automticamente (Figura 31).
Accin Resultado

1. En Activar escala automtica, marque los dispositivos en los que Habilita la escala desea que la escala de los indicadores se ajuste automticamente. automtica en los dispositivos NOTA: Haga clic en seleccionar todo para habilitar la escala seleccionados. automtica en todos los dispositivos y en borrar para deshabilitarla en todos ellos. 2. En los dispositivos en los que se haya deshabilitado la escala automtica, introduzca los lmites Mn. y Mx. de cada tipo de indicador. 3. Haga clic en Aplicar. Establece el rango de los indicadores. Actualiza los valores de escala automtica.

Figura 31:

Pgina de configuracin de rangos

Pginas de resumen de dispositivos

Las vistas de tablas Resumen de dispositivos proporcionan resmenes de uno o ms dispositivos seleccionados.
Accin
1. En el men de Supervisin, haga clic en Pginas de resumen de dispositivos. 2. Seleccione la pgina de resumen que desee ver. 3. Seleccione uno o varios dispositivos en la lista Dispositivos disponibles y luego haga clic en Siguiente (consulte la Figura 32). NOTA: Haga clic en >> para seleccionar todos los dispositivos disponibles.

Resultado
Ampla el rbol para posibilidades de seleccin de pginas de resumen. Abre la lista de seleccin de dispositivos. Selecciona uno o varios dispositivos para las opciones de resumen.

Figura 32:

Pgina Seleccin de dispositivo

Figura 33:

Pgina Resumen de circuito

2009-2013 Schneider Electric. Reservados todos los derechos.

39

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

63230-319-216B4_ES 06/2013

Tendencias

Para visualizar una tendencia en tiempo real de varios dispositivos y temas, vaya al men Supervisin y seleccione Datos en tiempo real > Tendencias.
Accin
1. En el men Supervisin, seleccione Datos en tiempo real. 2. Seleccione Tendencias.

Resultado
Ampla el rbol de datos para seleccionar opciones de datos en tiempo real. Ampla el rbol de datos para seleccionar opciones de tiempo real correspondientes a las tendencias. Abre la pgina de configuracin Tendencias en tiempo real. Selecciona los dispositivos cuyas tendencias se mostrarn. Selecciona los temas cuyas tendencias se mostrarn.

3. Seleccione Tendencias en tiempo real. 4. Seleccione hasta cuatro dispositivos de la lista Dispositivos disponibles. 5. Seleccione uno o varios temas en la lista Temas disponibles. NOTA: Solamente estarn disponibles para el clculo de tendencias aquellos temas comunes a todos los dispositivos seleccionados. El nmero mximo de temas cuyas tendencias se calcularn depende del nmero de dispositivos seleccionados. El producto de los dispositivos y los temas seleccionados no podr ser mayor de 8. 6. Haga clic en Siguiente para abrir la pgina de visualizacin Tendencias en tiempo real.

Abre la pagina de visualizacin Tendencias en tiempo real.

7. Para establecer los parmetros relativos a las Permite configurar los tendencias, contine con el procedimiento descrito en la parmetros de las tendencias. tabla que figura a continuacin y consulte la Figura 35 de la pgina 41.

Figura 34:

Seleccionar dispositivos y temas

40

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

Accin
1. Seleccione la tendencia Absoluto o Relativo. NOTA: Absoluto redibuja el eje X del grfico despus de cada muestreo y lo rellena con todos los datos recopilados desde el inicio de la tendencia. Relativo actualiza el grfico con los datos ms recientes despus de cada muestreo y mantiene el eje X constante para mostrar el tiempo general de la tendencia seleccionado. 2. Seleccione un tiempo de tendencia comprendido entre 1 y 15 minutos. Esta ser la duracin de la tendencia. NOTA: Los muestreos de datos se toman lo ms rpido posible, pero el proceso puede requerir ms tiempo dependiendo de la carga de comunicaciones en la subred serie, en los dispositivos remotos o en ambos.

Resultado
Selecciona el modo de grfico.

Selecciona la duracin de la tendencia.

3. Seleccione Iniciar muestreo para iniciar la generacin de Inicia la generacin de tendencias de los temas de los dispositivos tendencias. seleccionados. NOTA: Para detener la generacin de tendencias antes de que transcurra el tiempo de tendencia, haga clic en Detener muestreo. Si pulsa Iniciar muestreo despus de detener el muestreo, se iniciar una nueva tendencia. 4. Pulse Puntos de datos para visualizar un registro de todos los temas muestreados que quedaron registrados durante el tiempo de tendencia. NOTA: Despus de cada intervalo, se aaden a la tabla que aparece bajo el grfico el valor Actual de todos los temas as como los valores Mn., Mx. y Media calculados. 5. Pulse Tema(s) nuevo(s) para volver a seleccionar los dispositivos y los temas cuyas tendencias se deben generar. Muestra un registro de todos los valores de los temas muestreados durante la tendencia.

Le lleva de nuevo a la pgina de configuracin Tendencias en tiempo real.

Figura 35:

Tendencias en tiempo real

Registro de dispositivos

Las pginas de Registro de dispositivos proporcionan representaciones en forma de grficos y tablas de los datos de registro de los dispositivos seleccionados. Para obtener ms detalles acerca de la configuracin del registro de dispositivos, consulte Registro de dispositivos en la pgina 17.

2009-2013 Schneider Electric. Reservados todos los derechos.

41

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

63230-319-216B4_ES 06/2013

Pginas de dispositivo nico

Las pginas de dispositivo nico proporcionan representaciones en forma de grficos y tablas de los datos registrados de un nico dispositivo.
Accin
1. En el men Supervisin, haga clic en Registro de dispositivos. 2. En Registro de dispositivos, haga clic en Pginas de dispositivo nico. 3. Seleccione un dispositivo de la lista Registro de dispositivos.

Resultado
Ampla el rbol para mostrar las opciones disponibles de registro de dispositivos. Ampla el rbol para mostrar los dispositivos disponibles cuyos datos registrados se pueden visualizar. Muestra el registro de dispositivo correspondiente al dispositivo seleccionado.

4. Para ver un rango de datos, seleccinelo Elabora un grfico correspondiente al rango de en la lista desplegable de rangos de datos. datos seleccionado. 5. Mantenga pulsado el botn izquierdo del ratn y arrastre un cuadro de seleccin alrededor de una zona del grfico para ampliarla. 6. Para volver a la vista completa original, escriba Z en el teclado o haga doble clic sobre el grfico. 7. Haga clic en Puntos de datos para visualizar la tabla del registro de datos del intervalo seleccionado (consulte ms adelante la Figura 37). Aumenta la zona del grfico seleccionada.

Se reduce el zoom de la vista.

Abre la tabla del registro de datos del intervalo seleccionado.

8. Para visualizar otros temas, haga clic en Habilita la visualizacin de los temas Tema(s) nuevo(s). Habilite las casillas de seleccionados. verificacin de los temas que desea visualizar y, a continuacin, haga clic en Aplicar.

Los datos registrados de cada dispositivo aparecen en una pgina web en un formato de grfico de tendencia del tiempo. El grfico de tendencia del tiempo est preconfigurado para mostrar los datos del ltimo da completo, la ltima semana completa, el ltimo mes completo o todos los datos. Los parmetros de la energa se registran como valores acumulativos pero se visualizan como valores incrementales por intervalo. Los otros parmetros se registran y visualizan como el valor real registrado. Figura 36: Grfico Registro de datos del intervalo

Figura 37:

Tabla de puntos de datos del registro de datos del intervalo

42

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

Obtencin de registros cronolgicos de datos

Se pueden recuperar registros de datos de intervalo utilizando los mtodos descritos en la Tabla 15. Tabla 15: Mtodos de recuperacin de registros de datos de intervalo y formatos de archivo
Mtodo de recuperacin
FTP Botn Puntos de datos Consulta Web de Microsoft Correo electrnico HTTP

Formato de archivo recuperado


Variable separada por coma (CSV) HTML HTML CSV CSV

Para ver una lista de todos los archivos de registros disponibles, siga los pasos 2 a 4 de la seccin Obtencin de un registro de datos de intervalo mediante FTP en la pgina 44. Los archivos tendrn el siguiente formato: Nombre del dispositivo_ID local.csv, donde Nombre del dispositivo es el nombre dado al dispositivo esclavo, e ID local es el identificador local numrico asignado a este. Por ejemplo, un dispositivo llamado Entrada de servicios del edificio 1 con un identificador local de 3 sera Entrada de servicios del edificio 1_3.csv. Cuando se exportan archivos de registros, la fecha y la hora se aaden al nombre del archivo en el formato siguiente: _AAAAMMDDHHMMSS. Por ejemplo, Entrada de servicios del edificio 1_3_20100218115216.csv. Esto indica que el archivo se export el 18 de febrero de 2010 a las 11:52:16 a. m. Formato de registro Los datos se registran en el siguiente formato (consulte la Figura 38 de la pgina 44): Tabla 16: Formato de registro de datos de intervalo
Fila
1

Datos en formato CSV

Descripcin

Esta fila contiene los encabezamientos (BOM)Nombre de pasarela,N. de serie de de las columnas para la informacin de la pasarela,Direccin de pasarela,Nombre del dispositivo,ID local de dispositivo,Nombre del fila 2. tipo de dispositivo,Intervalo de registro NOTA: (BOM): Los tres primeros bytes del archivo constituyen una marca de orden de bytes (BOM, Byte Order Mark) de 3 caracteres, lo cual indica UTF-8. EGX300SD,23227,157.198.184.116,Entrada de servicios del edificio 1,3,CM4000,15 Esta fila est en blanco. ,,,ID del tema 1,ID del tema 2,ID del tema 3 Esta fila contiene la informacin acerca de la EGX y el dispositivo registrado. Esta fila contiene los encabezamientos de las columnas de los ID de los temas de la fila 5. Un ID de tema es una referencia numrica de la cantidad que se est registrando. El nombre dado a una cantidad puede diferir ligeramente entre dispositivos e idiomas. Los ID de temas se utilizan para identificar la cantidad independientemente del dispositivo y del idioma. Las tres primeras comas se utilizan con fines de disposicin en una aplicacin de hoja de clculo. Esta fila contiene los ID de temas de los valores registrados.

2 3 4

5 6 7

,,,1617,1621,1625 Esta fila est en blanco.

Error,Desviacin de la UTC (Minutos),Indica- Esta fila contiene los encabezamientos de las columnas para los datos dor de hora local,Energa aparente (kVAh), Energa real (kWh),Energa reactiva (kVARh) registrados en las filas 8 y superiores.

Estas filas contienen los datos registrados. 8y superiores 0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15 0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15 0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

Si utiliza una aplicacin de hoja de clculo para ver el archivo CSV, sus datos tendrn un aspecto similar al de la Figura 38 de la pgina 44.
2009-2013 Schneider Electric. Reservados todos los derechos. 43

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

63230-319-216B4_ES 06/2013

Figura 38:

Registro de datos de intervalo abierto en una aplicacin de hoja de clculo

Cdigos de error para los registros cronolgicos de datos

Al resolver problemas en los registros cronolgicos de datos, nos encontraremos con los cdigos de error que aparecen a continuacin (consulte la Figura 36 de la pgina 42 y la Figura 37 de la pgina 42):
Cdigo de error
19

Definicin
Ha ocurrido un error de comunicaciones (por ejemplo: CRC, protocolo o excepcin).

Resultado
Se deja habilitado el registro a menos que se haya perdido el ltimo intervalo.

25

El tiempo de espera se produjo cuando se envi una Se deja habilitado el registro a solicitud sin recibir la respuesta correspondiente menos que se haya perdido el durante el tiempo permitido. ltimo intervalo. Datos no vlidos. Intervalo de tiempo transcurrido antes de que se pudieran registrar los datos Intervalo perdido.

38 100

Pngase en contacto con el soporte tcnico si necesita ayuda para resolver estas u otras condiciones de error.

Obtencin de un registro de datos de intervalo mediante FTP

Puede utilizar FTP para recuperar un archivo de registro de datos conectndose a la EGX a travs de FTP y transfiriendo el archivo .csv, como se indica en los pasos siguientes. NOTA: Si desea que la EGX enve automticamente el archivo de registro de datos a travs de FTP, el parmetro Exportacin del registro de dispositivos tiene que configurarse para FTP (consulte Exportacin por FTP en la pgina 21).
Accin
1. Cree una carpeta en su equipo, como c:egx_logs. 2. Inicie el Explorador de Windows, escriba ftp:// y la direccin IP de la EGX en el cuadro Direccin (por ejemplo, ftp://169.254.0.10), y luego pulse Intro. 3. Escriba el nombre de usuario Administrator y la contrasea de administrador en los cuadros de texto, y luego haga clic en Iniciar sesin. 4. Vaya al directorio /logging/data en la EGX.

Resultado
Crea una carpeta para almacenar el registro de datos de la EGX. Abre el cuadro de dilogo Iniciar sesin como.

Inicia una sesin de FTP con la EGX y muestra los archivos almacenados en la EGX.

Abre el directorio de registro de datos en la EGX.

5. Copie el archivo de registros y luego Copia el registro de datos en la carpeta. pguelo en la carpeta creada en el paso 1.

44

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

Obtencin de un registro de datos de intervalo mediante el botn Puntos de datos

Accin
1. En la pgina web Registro de dispositivos (consulte la Figura 36 de la pgina 42), haga clic en Puntos de datos. 2. Pulse CTRL+A y luego pulse CTRL+C. 3. Inicie Excel y luego pulse CTRL+V.

Resultado
Abre una nueva ventana en la que se muestran los datos registrados. Selecciona todos los datos y luego copia los datos en el portapapeles. Pega los datos en una hoja de clculo de Excel.

Obtencin de un registro de datos de intervalo mediante la funcin de consulta Web de Microsoft

Accin
1. Inicie el explorador web.

Resultado
Abre el explorador web.

2. Verifique que el archivo de registro est Abre la pgina de registros de datos. disponible escribiendo la direccin IP de la EGX300 seguida de /stream/devlog_data.html?device=x, donde x es el ID local del dispositivo. 3. Inicie Excel y haga clic en Datos > Importar datos externos > Nueva consulta Web. NOTA: Esta ruta de acceso es tpica de Microsoft Excel 2003. 4. En el cuadro de dilogo Nueva consulta Web, escriba la direccin del registro introducido en el paso 2 y luego haga clic en Ir. 5. Haga clic en la flecha ms exterior para seleccionar todos los datos y luego haga clic en Importar. 6. Haga clic en Aceptar. Abre el cuadro de dilogo Nueva consulta Web de Excel.

Abre el archivo del registro de datos.

Selecciona los datos y luego abre el cuadro de dilogo Importar datos. Importa los datos.

NOTA: Si desea mostrar los datos ms recientes cada vez que abra la hoja de clculo, haga clic en Propiedades en el cuadro de dilogo Importar datos y seleccione Actualizar al abrir archivo.

Obtencin de un registro de datos de intervalo mediante correo electrnico

La EGX se tiene que configurar para enviar los registros de datos a una direccin de correo electrnico. Para obtener ms informacin, consulte Exportacin por correo electrnico en la pgina 19.

Obtencin de un registro de datos de intervalo mediante HTTP

Es necesario configurar la EGX para que pueda entregar registros cronolgicos de datos a un servidor web. Para obtener ms informacin, consulte Exportacin por HTTP en la pgina 23.

2009-2013 Schneider Electric. Reservados todos los derechos.

45

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

63230-319-216B4_ES 06/2013

Pginas de resumen de dispositivos

Las vistas de Resumen de dispositivos proporcionan resmenes de uno o ms dispositivos seleccionados.


Accin Resultado

1. En el men Supervisin, haga clic en Registro de Ampla el rbol para mostrar las dispositivos. opciones de registro de dispositivos. 2. En Registro de dispositivos, haga clic en Pginas de resumen de dispositivos. 3. En Pginas de resumen de dispositivos, haga clic Abre la pgina de configuracin de la en Varios dispositivos, nico tema. pgina Varios dispositivos, nico tema. 4. Seleccione un dispositivo de la lista Dispositivos Selecciona los dispositivos para las disponibles. opciones de resumen. NOTA: Se pueden seleccionar cuatro dispositivos como mximo. 5. Seleccione un tema de la lista Temas disponibles. NOTA: Solo estarn disponibles aquellos temas que sean comunes a los dispositivos seleccionados. 6. Seleccione Siguiente. 7. Mantenga pulsado el botn izquierdo del ratn y arrastre un cuadro de seleccin alrededor de una zona del grfico para ampliarla. 8. Para volver a la vista completa original, escriba Z en el teclado o haga doble clic sobre el grfico. Abre la pgina de tendencias de Varios dispositivos, nico tema. Aumenta la zona del grfico seleccionada. Se reduce el zoom de la vista. Selecciona el tema que se visualizar para cada dispositivo seleccionado.

El tema registrado de los dispositivos seleccionados se muestra en una pgina web en un formato de grfico de tendencia del tiempo. El grfico de tendencia del tiempo est preconfigurado para mostrar los datos del ltimo da completo, la ltima semana completa, el ltimo mes completo o todos los datos. Los parmetros de la energa se visualizan como valores incrementales por intervalo. Los otros parmetros se registran y visualizan como el valor real registrado.

Figura 39:

Pgina de configuracin de Varios dispositivos, nico tema

46

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

Figura 40:

Pgina de tendencias de Varios dispositivos, nico tema

Panel de instrumentos

La EGX admite cuatro categoras de paneles de instrumentos que muestran la informacin de consumo de energa recopilada a lo largo del tiempo. La Tabla 17 enumera los paneles de instrumentos y sus subconjuntos. Tabla 17: Tipos de paneles de instrumentos
Panel de instrumentos Por horas Subconjunto Da anterior por horas Da actual por horas Da actual con da anterior por horas Por das Semana anterior por das Semana actual por das Semana actual con semana anterior por das Mes anterior por das Mes actual por das Mes actual con mes anterior por das Por semanas Trimestre anterior por semanas Trimestre actual por semanas Trimestre actual con trimestre anterior por semanas 13 semanas anteriores por semanas Por meses Ao anterior por meses Ao actual por meses Ao actual con ao anterior por meses NOTA: Requiere que el archivo de datos de cada dispositivo pueda almacenar dos aos de datos histricos. Consulte Registro de datos de intervalo en la pgina 17 para obtener ms informacin. 12 meses anteriores por meses

2009-2013 Schneider Electric. Reservados todos los derechos.

47

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

63230-319-216B4_ES 06/2013

Visualizacin de un panel de instrumentos


Accin
1. En el men Supervisin, haga clic en Panel de instrumentos. 2. Seleccione un dispositivo en la lista desplegable Dispositivo. NOTA: El panel de instrumentos muestra los datos de un solo dispositivo. 3. Seleccione un tema en la lista desplegable Selecciona los temas que se mostrarn Nombre tema. grficamente. NOTA: Los temas estn limitados a los temas de consumo incremental proporcionados por el dispositivo. 4. Seleccione los parmetros de tiempo en la Selecciona el rango de tiempo de los datos lista desplegable Hora. registrados correspondientes al tema seleccionado. 5. Haga clic en Aplicar. Abre el panel de instrumentos seleccionado.

Resultado
Muestra el men del panel de instrumentos (consulte la Figura 41). Selecciona el dispositivo para mostrar sus datos.

Figura 41:

Men Panel de instrumentos

Los datos de cada panel de instrumentos se muestran en una pgina web en formato de grfico de barras. Al desplazar el puntero del ratn sobre una barra del grfico, se muestra el valor del punto de datos del intervalo seleccionado (Figura 42). Figura 42: Grfico del panel de instrumentos

Figura 43:

Tabla del panel de instrumentos

48

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

Obtencin de los datos del panel de instrumentos mediante el botn Puntos de datos

Los datos de un panel de instrumentos se pueden guardar en una aplicacin de hoja de datos, tal como se muestra en los pasos que se indican a continuacin.
Accin
1. En el panel de instrumentos que contiene los datos deseados, haga clic en Puntos de datos. 2. Pulse CTRL+A y luego pulse CTRL+C. 3. Inicie Excel y luego pulse CTRL+V.

Resultado
Muestra los puntos de datos del panel de instrumentos deseado (Figura 43 de la pgina 48). Selecciona todos los datos y luego los copia en el portapapeles. Pega los datos en una hoja de clculo de Excel.

Guardar un enlace a un panel de instrumentos

Se puede guardar un enlace a un panel de instrumentos para evitar tener que hacer selecciones desde el men principal cada vez que se accede a uno de dichos paneles. La Tabla 18 describe los mtodos para guardar un enlace a un panel de instrumentos. Tabla 18: Guardar un enlace a un panel de instrumentos
Opcin Descripcin Valor Siga las instrucciones para configurar un marcador en el explorador web que utilice. Para configurar el acceso URL, consulte Vnculos de documentacin en la pgina 28. Para que el destinatario del mensaje pueda ver un panel de instrumentos, debe tener una cuenta de usuario de la EGX. Consulte Cuentas de usuario en la pgina 29. Marcador del explorador Permite a los usuarios acceder al web panel de instrumentos guardado desde el equipo donde se cre el marcador. Vnculo de documentacin Permite a los usuarios de la EGX acceder a un panel de instrumentos guardado desde la pgina Documentacin. Permite a los usuarios enviar la URL de un panel de instrumentos en el cuerpo de un mensaje de correo electrnico.

Correo electrnico

Guardar un panel de instrumentos como imagen

Se puede guardar un grfico del panel de instrumentos como imagen siguiendo los pasos que se indican a continuacin.
Accin Resultado

1. Siga los pasos indicados en Visualizacin Muestra el grfico del panel de instrumentos. de un panel de instrumentos en la pgina 48. 2. Haga clic en Mostrar como imagen en la esquina superior derecha de la pgina (Figura 44 de la pgina 50). 3. Haga clic con el botn derecho del ratn sobre la imagen y seleccione Guardar imagen como Abre una nueva ventana con el panel de instrumentos mostrado en forma de imagen. Abre el cuadro de dilogo Guardar como.

4. Escriba un nombre para el archivo, Guarda la imagen. seleccione una ubicacin en la que guardar el archivo y haga clic en Guardar. NOTA: El tipo de archivo predeterminado es de imagen PNG. Para cambiar el tipo de archivo, sustituya .png en el campo del nombre de archivo por la extensin que desee.

NOTA: Esta funcin no est disponible en Internet Explorer versin 8 y anteriores.

2009-2013 Schneider Electric. Reservados todos los derechos.

49

Pasarela Ethernet EGX300 de PowerLogicTM Supervisin

63230-319-216B4_ES 06/2013

Figura 44:

Guardar una imagen del panel de instrumentos

Punto de acceso del sistema

La EGX es capaz de detectar pasarelas EGX300 y otros dispositivos Schneider Electric que estn conectados a la red as como de proporcionar enlaces a estos. Se obtiene as un punto de acceso a un sistema de dispositivos Schneider Electric en red. La pgina Punto de acceso del sistema enumera en forma de hipervnculo todos los dispositivos Schneider Electric detectados. Al desplazar el ratn por encima de cualquier dispositivo de la lista, se ven datos adicionales de este a la izquierda de la lista. Haga clic sobre cualquier dispositivo para ir a su pgina de inicio de sesin.

Figura 45:

Pgina Punto de acceso del sistema: visualizacin de datos de dispositivo

50

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Documentacin

DOCUMENTACIN

La pgina Documentacin le permite acceder a informacin que se ha almacenado como archivos en EGX y como vnculos web URL. Para obtener informacin sobre la carga de vnculos de documentacin, consulte Vnculos de documentacin en la pgina 28. Si desea abrir un vnculo de documentacin, haga clic en el enlace Documentacin, situado en la parte superior de la pgina, y despus seleccione el vnculo que le interese.

Figura 46:

Pgina Documentacin

CONTROL

La EGX tiene la propiedad de poder ejecutar manualmente uno o varios conjuntos de comandos de restablecimiento predefinidos por tipo de dispositivo.
Accin
1. En el men Control, haga clic en Restablecimientos. 2. Seleccione un dispositivo de la lista Restablecimientos que desee ver o restablecer. 3. Seleccione los parmetros del dispositivo que desee restablecer. 4. Haga clic en Restablecer.

Resultado
Abre la pgina Restablecimientos. Selecciona un dispositivo y muestra las opciones de restablecimiento as como la fecha y hora del ltimo restablecimiento. Selecciona la operacin de restablecimiento que se tiene que realizar en el dispositivo seleccionado. Enva un comando (o varios) para los restablecimientos solicitados al dispositivo seleccionado y muestra el estado.

Figura 47:

Restablecimientos

NOTA: La fecha y hora mostradas para el parmetro Fecha/Hora son la fecha y hora actuales en el dispositivo seleccionado. Si se ha seleccionado este parmetro para restablecerlo, se enviar al dispositivo la fecha y hora de la EGX. Se informar de los valores de fecha/hora nicamente si el dispositivo los admite. Por ejemplo, si el dispositivo no admite el valor de Mn./Mx. correspondiente a Fecha/hora ltimo restablecimiento, este valor no aparecer relleno.
2009-2013 Schneider Electric. Reservados todos los derechos. 51

Pasarela Ethernet EGX300 de PowerLogicTM Diagnsticos

63230-319-216B4_ES 06/2013

DIAGNSTICOS

Para acceder a los vnculos de la pgina web Diagnsticos, haga clic en Diagnsticos en la barra de mens de la EGX.

Estadsticas

Esta pgina ilustra las lecturas acumuladas desde la ltima vez que se activ la EGX. Si se interrumpe la alimentacin a la EGX o si se restablece el dispositivo debido a un cambio de configuracin u otro evento, todos los valores acumulativos se ponen a cero.
Accin
1. En la pgina Diagnsticos, haga clic en Estadsticas. 2. Observe los datos. 3. Haga clic en Restablecer.

Resultado
Abre la pgina Estadsticas (consulte ms adelante la Figura 48). Consulte Interpretacin de las estadsticas en la pgina 53. Restablece los datos de diagnstico acumulativos de la EGX a 0.

Figura 48:

Pgina Estadsticas

52

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Diagnsticos

Interpretacin de las estadsticas


Estadstica
Ethernet Estado de conexin Cadena de estado que representa la velocidad y la configuracin bidireccional que se utiliza para comunicarse con el dispositivo conectado. Contador que aumenta cada vez que se enva una trama correctamente. Contador que aumenta cada vez que se reenva una trama debido a deteccin de colisiones. Contador que aumenta cada vez que no se puede enviar una trama porque ha alcanzado el estado de colisin mxima basado en el algoritmo de retroceso exponencial binario truncado. Contador que aumenta cada vez que se recibe una trama correctamente. Contador que aumenta cada vez que se recibe una trama que contiene una suma de verificacin/CRC que no coincide con la calculada. Contador que aumenta cada vez que se recibe una trama que contiene un error de suma de verificacin/CRC y que no termina en un borde de trama de 8 bits. Contador que aumenta cada vez que se recibe una trama que excede el tamao mximo definido en las normas (tramas de ms de 1518 bytes). Contador que aumenta cada vez que se recibe una trama que no alcanza el tamao mnimo definido en las normas (tramas de menos de 64 bytes).

Descripcin

Tramas transmitidas satisfactoriamente Colisiones Colisiones excesivas

Tramas recibidas satisfactoriamente Errores de CRC de tramas

Errores de alineacin

Tramas demasiado largas

Tramas demasiado cortas

Modbus TCP/IP Servidor Tramas enviadas Tramas recibidas Errores de protocolo Conexiones activas1 Contador que aumenta cada vez que se enva una trama. Contador que aumenta cada vez que se recibe una trama. Contador que aumenta cada vez que se recibe un mensaje mal formado. Valor de estado que representa el nmero de conexiones activas en el momento de actualizacin de la pgina de diagnsticos. Se admite un mximo de 64 conexiones. Al hacer clic en Conexiones activas, se abre una ventana nueva con una lista de todas las conexiones clientes activas. Contador que aumenta cada vez que se realiza una conexin a la EGX. Valor de estado que representa el nmero mximo de conexiones que pueden estar activas en un momento dado. Contador que aumenta cada vez que se recibe un mensaje de solicitud de lectura. Contador que aumenta cada vez que se recibe un mensaje de solicitud de escritura. Contador que aumenta cada vez que se enva un mensaje de respuesta.

Conexiones acumuladas Mximo de conexiones

Mensajes entrantes de lectura Mensajes entrantes de escritura Mensajes salientes de respuesta Cliente Tramas enviadas Tramas recibidas Errores de protocolo
1

Contador que aumenta cada vez que se enva una trama. Contador que aumenta cada vez que se recibe una trama. Contador que aumenta cada vez que se recibe un mensaje mal formado.

Haga clic en el vnculo para obtener informacin adicional en detalle.

2009-2013 Schneider Electric. Reservados todos los derechos.

53

Pasarela Ethernet EGX300 de PowerLogicTM Diagnsticos

63230-319-216B4_ES 06/2013

Estadstica
Tiempos de espera

Descripcin
Contador que aumenta cada vez que se enva un mensaje de solicitud sin recibir el mensaje de respuesta correspondiente durante el tiempo permitido. Los tiempos de espera de respuesta suelen ser el resultado de errores de configuracin o un dispositivo que no responde. Contador que aumenta cada vez que se pierde la conexin. Contador que aumenta cada vez que se recibe una excepcin. Contador que aumenta cada vez que se enva un mensaje de solicitud de lectura. Contador que aumenta cada vez que se enva un mensaje de solicitud de escritura. Contador que aumenta cada vez que se recibe un mensaje de respuesta. Tabla detallada que proporcionar estadsticas remotas y serie por dispositivo.

Tiempos de espera de conexin Recibidas excepciones Mensajes salientes de lectura Mensajes salientes de escritura Mensajes entrantes de respuesta Detalles1 Puerto serie Tramas enviadas Tramas recibidas Errores de CRC de tramas

Contador que aumenta cada vez que se enva una trama. Contador que aumenta cada vez que se recibe una trama. Contador que aumenta cada vez que se recibe un mensaje que contiene una CRC que no coincide con la calculada. Suele ser el resultado de problemas de cableado. Contador que aumenta cada vez que se recibe un mensaje mal formado. Contador que aumenta cada vez que se enva un mensaje de solicitud sin recibir el mensaje de respuesta correspondiente durante el tiempo permitido. Los tiempos de espera de respuesta suelen ser el resultado de errores de configuracin o un dispositivo que no responde. Contador que aumenta cada vez que se recibe una excepcin. Contador que aumenta cada vez que se enva un mensaje de solicitud de lectura. Contador que aumenta cada vez que se enva un mensaje de solicitud de escritura. Contador que aumenta cada vez que se recibe un mensaje de solicitud de lectura. Contador que aumenta cada vez que se recibe un mensaje de solicitud de escritura. Tabla detallada que proporcionar estadsticas remotas y serie por dispositivo.

Errores de protocolo Tiempos de espera

Recibidas excepciones Mensajes salientes de lectura Mensajes salientes de escritura Mensajes entrantes de lectura Mensajes entrantes de escritura Detalles1 Servidor HTTP Tramas enviadas Tramas recibidas Conexiones activas1

Contador que aumenta cada vez que se enva una trama. Contador que aumenta cada vez que se recibe una trama. Valor de estado que representa el nmero de conexiones activas en el momento de actualizacin de la pgina de diagnsticos. Se admite un mximo de 20 conexiones. Haga clic en Conexiones activas para abrir una ventana nueva con una lista de todas las conexiones clientes activas. Contador que aumenta cada vez que se realiza una conexin a la EGX. Valor de estado que representa el nmero mximo de conexiones que pueden estar activas en un momento dado.

Conexiones acumulativas1 Mximo de conexiones

Haga clic en el vnculo para obtener informacin adicional en detalle.

54

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Diagnsticos

Estadstica
Informacin de pasarela Versin del firmware Tiempo de inactividad del sistema Direccin MAC Nmero de serie Nmero de modelo Versin del hardware Fecha de fabricacin Cliente HTTP Envo correcto Error de conexin Error de autenticacin

Descripcin

Versin del firmware que est instalada en la EGX. Porcentaje del 0% al 100% que indica el tiempo medio de procesador que no se utiliza. Direccin exclusiva del hardware Ethernet de una EGX. Nmero de serie de la EGX. Nmero de modelo de la EGX. Versin del hardware de la EGX. Fecha de fabricacin de la EGX.

Contador que aumenta cada vez que se enva un archivo correctamente al servidor HTTP. Contador que aumenta cada vez que la EGX no puede conectarse al servidor HTTP. Contador que aumenta cada vez que el servidor HTTP no puede autenticar las credenciales del usuario o contrasea. Contador que aumenta cada vez que no se puede transferir un archivo al servidor HTTP. Contador que aumenta cada vez que no se puede transferir un archivo debido a la incapacidad de la EGX para originar la transaccin.

Error de envo Error general

Cliente FTP Envo correcto Error de conexin Error de autenticacin Contador que aumenta despus de cada transferencia con xito a un servidor FTP. Contador que aumenta cada vez que la EGX no puede conectarse al servidor FTP. Contador que aumenta cada vez que al servidor FTP no puede autenticar las credenciales del usuario o contrasea. Contador que aumenta cada vez que el servidor FTP no puede localizar el directorio solicitado. Contador que aumenta cada vez que no se puede transferir un archivo al servidor FTP. Contador que aumenta cada vez que no se puede transferir un archivo debido a la incapacidad de la EGX para originar la transaccin.

Error de directorio Error de envo Error general

Cliente SMTP Envo correcto Error de conexin Error de autenticacin Contador que aumenta cada vez que se enva un correo electrnico con xito al servidor SMTP. Contador que aumenta cada vez que la EGX no puede conectarse al servidor SMTP. Contador que aumenta cada vez que el servidor SMTP no puede autenticar las credenciales del usuario o contrasea. Contador que aumenta cada vez que no se puede enviar un correo electrnico al servidor SMTP. Contador que aumenta cada vez que no se puede enviar un correo electrnico debido a la incapacidad de la EGX para crear el correo electrnico.

Error de envo Error general

Sistema de archivos Espacio total Espacio libre


1

La cantidad total de espacio de disco de la EGX en kilobytes. La cantidad total de espacio de disco no utilizado en el disco de la EGX en kilobytes.

Haga clic en el vnculo para obtener informacin adicional en detalle.

2009-2013 Schneider Electric. Reservados todos los derechos.

55

Pasarela Ethernet EGX300 de PowerLogicTM Diagnsticos

63230-319-216B4_ES 06/2013

Lectura de registros de dispositivo

Esta opcin permite a la EGX leer desde sus dispositivos locales o remotos. Figura 49: Pgina Lectura de registros de dispositivo

Accin
1. En el men Diagnsticos, haga clic en Lectura de registros de dispositivo.

Resultado
Abre la pgina Lectura de registros de dispositivo.

2. Introduzca el ID local del dispositivo (o Introduce los registros que se deben leer eljalo en la lista de dispositivos definidos), desde el dispositivo especificado. la direccin datos de comienzo y el nmero de registros que se deben leer. 3. Seleccione un tipo de datos. Selecciona el tipo de datos apropiado. 4. Para modificar la visualizacin de los datos Selecciona el modo de visualizacin de los de la columna Valor, seleccione Decimal, valores de los datos. Hexadecimal, Binario o ASCII. 5. Haga clic en Lectura. Lee los registros del dispositivo segn la configuracin seleccionada.

Tabla 19: Parmetros de lectura de registros de dispositivo de la EGX


Opcin
Nombre del dispositivo

Descripcin
Selecciona un dispositivo que leer de la lista de dispositivos aadidos previamente. Para leer un dispositivo no definido en la lista de dispositivos, introduzca el ID local de este. La direccin del dispositivo que se tiene que leer. El primer registro para leer. El nmero de registros para leer (1 a 125). Muestra una lista con los nmeros de los registros. Muestra una lista de los datos almacenados en un registro. Los valores recuperados dependen del dispositivo conectado a la EGX. Consulte la documentacin correspondiente al dispositivo conectado para obtener ms informacin acerca de los valores de los registros almacenados. Seleccione Registros de retencin, Registros de entrada, Bobinas de salida, Bobinas de entrada o ID de dispositivo. Seleccione una opcin para especificar el modo de visualizacin de los datos de la columna Valor.

Predet.

ID local Registro de inicio Nmero de registros Columna Registro Columna Valor

1 1000 10

Tipo de datos

Registros de retencin Decimal

Opciones Decimal, Hexadecimal, Binario o ASCII

56

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Diagnsticos

Comprobacin de las comunicaciones


Comprobacin de comunicaciones automatizada Cuando se examinan las vistas Datos en tiempo real, la EGX tiene una comprobacin de comunicaciones automatizada que se ejecuta de forma predeterminada cada 15 minutos. (Para cambiar la frecuencia, consulte Preferencias en la pgina 33.) Esta comprobacin verificar el buen estado de las comunicaciones de todos los dispositivos configurados en la EGX e intentar restablecer la comunicacin con cualquier dispositivo marcado como Fuera de servicio dentro de la sesin actual del navegador.

Comprobacin de comunicaciones manual

En ciertos casos, es posible que no quiera esperar el tiempo necesario para comprobar las comunicaciones de forma automatizada y necesite forzar la comprobacin en ejecucin manual.
Accin
1. En la pgina Diagnsticos, haga clic en Comprobacin de las comunicaciones. 2. Haga clic en Comprobar estado del dispositivo.

Resultado
Abre la pgina Comprobacin de las comunicaciones. Ejecuta una comprobacin de las comunicaciones. Los dispositivos en comunicacin muestran Aprobado en la columna Comunicaciones y En servicio en la columna Estado. Un dispositivo que no est comunicando mostrar Error en la columna Comunicaciones y Fuera de servicio en la columna Estado, si ha fallado varias veces.

Figura 50:

Pgina Comprobacin de las comunicaciones

2009-2013 Schneider Electric. Reservados todos los derechos.

57

Pasarela Ethernet EGX300 de PowerLogicTM Mantenimiento

63230-319-216B4_ES 06/2013

MANTENIMIENTO

El registro de mantenimiento le proporciona una manera de documentar el mantenimiento realizado en la EGX, los equipos conectados o el sistema del cual la EGX forma parte. Cada entrada se registra con la fecha y hora en la que se hizo la entrada y el nombre del usuario que la hizo. Este registro tambin enumerar automticamente la actividad del sistema, como las funciones de activacin o desactivacin. No tendr que aadir entradas para estos elementos. Por ltimo, este registro enumerar todas las actividades que se especifican para el registro de mantenimiento en la pgina de configuracin Historial de auditora (consulte Historial de auditora en la pgina 34).
Accin
1. En el men Mantenimiento, haga clic en Registro de mantenimiento. 2. Seleccione la casilla de verificacin Eliminar situada junto a la entrada que desee eliminar y luego haga clic en Eliminar entradas.

Resultado
Abre la pgina Registro de mantenimiento. Elimina la entrada seleccionada.

3. Haga clic en Eliminar registro para borrar Borra el registro de mantenimiento. todas las entradas del registro de mantenimiento. 4. Para agregar una nueva entrada de registro, haga clic en Aadir entrada de registro y luego introduzca el texto de mantenimiento en el cuadro de texto Detalle de entrada (consulte ms adelante la Figura 52). Abre la pgina Aadir entrada de registro y permite al usuario introducir los detalles de mantenimiento.

Figura 51:

Registro de mantenimiento

Figura 52:

Aadir entrada de registro

FIRMWARE

El firmware de la EGX se puede actualizar utilizando el protocolo de transferencia de archivos (FTP). Consulte con el sitio www.schneider-electric.com o con su distribuidor local para obtener la ltima actualizacin del firmware.

Identificacin de la versin del firmware

La EGX consta de dos componentes de firmware: el componente binario ejecutable y el componente de imagen de disco.

58

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Firmware

Versin del firmware del componente binario ejecutable

Accin

Resultado

1. Abra el explorador web e inicie una sesin Abre la pgina de inicio de la EGX. en la EGX. 2. Localice la versin del firmware en la parte Seala la versin del firmware de la EGX. inferior izquierda de la pgina. NOTA: Si ha actualizado el firmware recientemente, pulse F5 para actualizar la pgina web y actualizar el nmero de firmware que aparece en ella. 3. Tambin puede seleccionar Diagnsticos Tambin seala la versin del firmware de > Estadsticas para ver la versin del la EGX. firmware en la seccin Informacin de pasarela.

Versin de imagen de disco


Accin Resultado
1. Abra el explorador web e inicie una sesin Abre la pgina de inicio de la EGX. en la EGX. 2. Localice la versin del firmware en la parte Determina la versin del firmware de la imagen inferior izquierda de la pgina. de disco de la EGX. NOTA: Si ha actualizado el firmware recientemente, pulse F5 para actualizar la pgina web y actualizar el nmero de firmware que aparece en ella. 3. Tambin puede seleccionar la EGX mediante FTP, localizar el archivo version.txt y hacer doble clic en l para abrirlo. Determina la versin del firmware de la imagen de disco de la EGX.

Obtencin de firmware nuevo


Accin
1. Inicie el explorador web, escriba www.powerlogic.com en la barra de direcciones y luego pulse Intro.

Resultado
Abre el sitio web de PowerLogic.

2. Seleccione su pas y luego haga clic en Go Abre el sitio web PowerLogic de su pas. (Ir). NOTA: Si ha seleccionado Estados Unidos, vaya al paso 3. De lo contrario, siga la navegacin del sitio web especfico del pas para obtener el firmware de la EGX. 3. Haga clic en Support > Downloads (Asistencia > Descargas). Abre la pgina de descargas.

4. Haga clic en el vnculo EGX300 Firmware Abre la pgina Firmware de la EGX300. (Firmware de la EGX300). 5. Haga clic en el vnculo del archivo de firmware (egxxxx.bin, donde xxxx es el nmero de la versin del firmware), luego haga clic en Guardar. Abre el cuadro de dilogo Descarga de archivos y, a continuacin, el cuadro de dilogo Guardar como.

6. En el cuadro de dilogo Guardar como, Guarda el archivo de firmware en el directorio o seleccione o cree un directorio o carpeta la carpeta indicados. local en el que se almacenar el archivo de firmware y haga clic en Guardar. 7. Haga clic en el vnculo egxxxx.upd (donde Abre el cuadro de dilogo Descarga de xxxx es el nmero del firmware), luego archivos y, a continuacin, el cuadro de dilogo haga clic en Guardar. Guardar como. 8. En el cuadro de dilogo Guardar como, Guarda el archivo de firmware con la extensin seleccione o cree un directorio o carpeta .upd en el directorio o la carpeta indicados. local en el que se almacenar el archivo de firmware y haga clic en Guardar.

2009-2013 Schneider Electric. Reservados todos los derechos.

59

Pasarela Ethernet EGX300 de PowerLogicTM Firmware

63230-319-216B4_ES 06/2013

Actualizacin del firmware

No corte la alimentacin elctrica a la EGX mientras se est descargando firmware. Si se corta la alimentacin elctrica durante el proceso de programacin, la EGX dejar de funcionar. Estando en curso la programacin, el indicador LED de estado parpadear rpidamente. Cuando cesa el parpadeo, la programacin est terminada.
Accin
1. Inicie el Explorador de Windows, escriba ftp:// y la direccin IP de la EGX en el cuadro Direccin (por ejemplo, ftp://169.254.0.10), y luego pulse Intro. 2. Escriba el nombre de usuario Administrator y la contrasea de administrador en los cuadros de texto, y luego haga clic en Iniciar sesin.

Resultado
Abre el cuadro de dilogo Iniciar sesin como.

Abre una sesin de FTP con la EGX.

3. Localice el directorio o la carpeta del Copia el archivo de firmware en el equipo donde se ha guardado el archivo portapapeles. de firmware (egxxxxx.bin), haga clic con el botn derecho en el archivo y, a continuacin, haga clic en Copiar. 4. Haga clic con el botn derecho en la ventana del Explorador de Windows y luego haga clic en Pegar. NOTA: En vez de copiar y pegar el archivo del firmware, puede arrastrarlo y soltarlo en el Explorador de Windows. Copia el firmware en la EGX y luego se reinicia la EGX. NOTA: La luz de alimentacin/estado parpadear rpidamente mientras se est transfiriendo y programando el archivo a la EGX. Una vez terminada la programacin, se restablecer la EGX. El tiempo necesario para la programacin est comprendido entre 1,5 y 2 minutos. Copia el archivo de actualizacin del disco en el portapapeles.

5. Localice el archivo de actualizacin del disco guardado en su equipo (egxxxxx.upd), haga clic con el botn derecho en el nombre del archivo y, a continuacin, haga clic en Copiar. 6. Haga clic con el botn derecho en la ventana del Explorador de Windows y luego haga clic en Pegar. NOTA: En vez de copiar y pegar el archivo del firmware, puede arrastrarlo y soltarlo en el Explorador de Windows.

Copia el archivo en la EGX y luego se reinicia la EGX.

7. Para verificar que se ha actualizado Verifica la versin actualizada del firmware. correctamente la versin del firmware, siga los pasos de Identificacin de la versin del firmware en la pgina 58. 8. Haga clic en Cerrar en la ventana del Explorador de Windows. Cierra el Explorador de Windows y termina la conexin FTP con la EGX.

60

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Apndice A: Protocolos Ethernet compatibles

APNDICE A: PROTOCOLOS ETHERNET COMPATIBLES

La EGX acepta los siguientes protocolos Ethernet:

Modbus TCP/IP: Modbus TCP/IP es una combinacin del protocolo Modbus, que proporciona comunicacin maestro-esclavo entre dispositivos, y TCP/IP, que proporciona comunicacin a travs de una conexin Ethernet. Se utiliza Modbus TCP/IP para intercambiar datos entre la EGX y otros dispositivos compatibles con Modbus TCP/IP a travs del puerto TCP 502. Protocolo de transferencia de hipertexto (HTTP): HTTP es un protocolo de red que realiza los envos de archivos y datos en Internet. Proporciona funcionalidad de servidor web a travs del puerto TCP 80. Protocolo de transferencia de hipertexto seguro (HTTPS): HTTPS es un protocolo de red que realiza los envos cifrados de archivos y datos en Internet mediante SSL. Proporciona funcionalidad de servidor web a travs del puerto TCP 443. Protocolo de transferencia de archivos (FTP): FTP es un protocolo de redes que ofrece la capacidad de transferir archivos por Internet de un ordenador a otro. Se admiten los modos FTP activo y pasivo, principalmente a travs del puerto TCP 21. Protocolo simple de administracin de redes (SNMP): SNMP se basa en el formato MIB2 y proporciona la capacidad de almacenar y enviar informacin de identificacin y diagnstico utilizada en la red por razones de administracin por medio del puerto UDP 161. Protocolo de resolucin de direccin (ARP): ARP se utiliza para convertir las direcciones IP en direcciones Ethernet. Las solicitudes de ARP se envan a travs de la EGX para determinar si su direccin es el duplicado de una direccin IP (consulte Deteccin de direcciones IP duplicadas en la pgina 8). Protocolo simple de hora de la red (SNTP): SNTP es un protocolo que se usa para sincronizar los relojes de los dispositivos en red utilizando un servidor NTP por medio del puerto UDP 123.

Equipo fsico
Puerto Ethernet RJ45 Alimentacin

LED para Ethernet y comunicaciones en serie

LED de alimentacin y estado

Puerto serie RS485

Interruptores de puentes para polaridad, resistencia de final de lnea y 2 hilos/4 hilos Botn de restablecim. Puerto serie RS232 (conector RJ45)

2009-2013 Schneider Electric. Reservados todos los derechos.

61

Pasarela Ethernet EGX300 de PowerLogicTM Apndice B: Tipos de dispositivos admitidos

63230-319-216B4_ES 06/2013

APNDICE B: TIPOS DE DISPOSITIVOS ADMITIDOS

La EGX acepta los siguientes tipos de dispositivos: La presente lista de dispositivos compatibles es exacta a fecha de publicacin de este documento. Para obtener actualizaciones, visite el sitio web www.schneider-electric.com. Tabla 20: Tipos de dispositivos admitidos por la EGX300
Grupo de dispositivos Filtro de harmnicos activos Interruptores Dispositivos Accusine Compact NSX-A Compact NSX-E PowerPact - A PowerPact - E CM100/200 CM2000 CM3000 CM4000 ION7500 ION7550 ION7600 ION7650 DM6000 DM6300 Modelo 98 ATV61 ATV71 Energy Meter Enercept E5600 EM1200 EM1210 EM1250 EM1251 EM26-96 EM3550 EM3555 EM4800 EM6400 EM6433 EM6436 EM6436DUAL EM6438 EM7230 EM7280 iEM3150 iEM3155 iEM3250 iEM3255 ION8600 Vigilohm IM20 Vigilohm IM20-H TeSys T BCPM tipo A BCPM tipo B BCPM tipo C BCM50A BCM100A MCM MotorLogic Plus MotorLogic Plus II Varlogic

Circuit Monitors

Medidores digitales Controladores digitales de temperatura Variadores Medidores de energa

Dispositivos de supervisin de aislamiento Administracin de motores Multi-Circuit Monitors

Rels de sobrecarga (SSOLR) Controlador de factor de potencia

62

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM Apndice B: Tipos de dispositivos admitidos

Tabla 20: Tipos de dispositivos admitidos por la EGX300


Grupo de dispositivos Centrales de medida Dispositivos PM9c PM200 PM300 PM500 PM600 PM700 PM800 PM1000 PM3250 PM5100 PM5300 PM5350 PM5350BW PM5560 ION6200 (Standard y Mega) ION7300 Sepam 2000 Sepam Serie 10 Sepam Serie 20 Sepam Serie 40 Sepam Serie 80 SIM10Z SIM10M SIM6BZ ATS48 MVSS/RVSS ZED-THL-M Micrologic A Micrologic E Micrologic H Micrologic P Acti9 SmartLink Inversores Conext TL

Rels protectores

Mdulos de interfaz inteligentes

Arranques suaves Sensores de temperatura/humedad/luz Unidades de control

Otros

2009-2013 Schneider Electric. Reservados todos los derechos.

63

Pasarela Ethernet EGX300 de PowerLogicTM Apndice B: Tipos de dispositivos admitidos

63230-319-216B4_ES 06/2013

64

2009-2013 Schneider Electric. Reservados todos los derechos.

63230-319-216B4_ES 06/2013

Pasarela Ethernet EGX300 de PowerLogicTM ndice alfabtico

ndice alfabtico
A
acceso a la EGX a travs de una red 2 ARP (protocolo de resolucin de direcciones) 8

F
fecha y hora configuracin 24 filtrado de Modbus TCP/IP configuracin 27 firmware actualizacin 60 actualizacin mediante FTP 58 obtencin de nuevo 59 formato de registro de datos 43 FTP exportacin del registro de dispositivos 21 para aadir pginas web 31 para eliminar pginas web 31 para recuperar registros cronolgicos de datos 44

B
botn Puntos de datos registro de datos de intervalo 45

paneles de instrumentos 47 parmetros del SNMP configuracin 26 preferencias personalizacin de la EGX 33 protocolos Ethernet compatibles 61 punto de acceso del sistema configuracin 36 enlaces a otras EGX300 50

R
rango de los indicadores analgicos 39 red acceso a travs de una 2 registro 17, 41 cronolgico de datos cdigos de error 44 recuperacin 43 recuperacin mediante FTP 44 de datos de intervalo mediante botn Puntos de datos 45 mediante correo electrnico 45 mediante FTP 44 mediante funcin de consulta Web de Microsoft 45 mediante HTTP 45 de dispositivos 17, 41 de mantenimiento 58 historial de auditora 35 formato de datos 43 temas 18 registros de dispositivo lectura 56

C
certificado de confianza nmero de puerto HTTPS 7 cdigos de error registro cronolgico de datos 44 comprobacin de las comunicaciones 57 automatizada 57 manual 57 conexin de dispositivos 12 conexiones con dispositivos remotos 10 configuracin de Ethernet avanzada 6 de Ethernet y TCP/IP 5 de lecturas bsicas 38 de los puertos serie 8 del puerto serie avanzada 9 EGX 5 lista de dispositivos 13 consulta Web de Microsoft registro de datos de intervalo 45 control 51 correo electrnico exportacin del registro de dispositivos 19 registro de datos de intervalo 45 cuentas de usuario configuracin 29

H
hardware 61 historial de auditora 34 cuadro Syslog 35 registro de mantenimiento 35 HTTP exportacin registro de dispositivos 23 nmero de puerto configuracin 7 recuperacin de registros de datos de intervalo 45 HTTPS nmero de puerto configuracin 7

I
inicio de sesin en la EGX 2 interfaz de usuario EGX 3 intervalos de registro 17 introduccin 1

S
seguridad de la contrasea indicacin cromtica 29 sincronizacin horaria de red configuracin 25 supervisin 38 Syslog historiales de auditora 35

D
datos en tiempo real 38 deteccin de direcciones IP duplicadas 8 deteccin de dispositivos 15 diagnsticos 52 dispositivos Modbus deteccin 15

L
lectura de registros de dispositivo 56 lista de dispositivos EGX 12

T
tendencias 40 tipos de dispositivos admitidos 62 tipos de dispositivos visualizables 34

N
niveles de acceso a la EGX 27

V
versin del firmware del componente binario ejecutable 59 versin del firmware del componente de imagen de archivo 59 vnculos de documentacin configuracin 28 visualizacin de datos y tendencias en tiempo real 38

E
EGX inicio de sesin 2 interfaz de usuario 3 lista de dispositivos 12 estadsticas 52 interpretacin 53 exportacin del registro de dispositivos 19 configuracin 19

O
otros recursos 1

P
pgina de documentacin 51 pginas de dispositivo nico 38, 42 de resumen de dispositivos 39, 46 web adicin a/eliminacin de la interfaz web 32 configuracin 30 personalizadas configuracin 31

2009-2013 Schneider Electric. Reservados todos los derechos.

65

Pasarela Ethernet EGX300 de PowerLogicTM ndice alfabtico

63230-319-216B4_ES 06/2013

66

2009-2013 Schneider Electric. Reservados todos los derechos.

Pasarela Ethernet EGX300 de PowerLogicTM Manual del usuario

PowerLogic es una marca comercial o una marca comercial registrada de Schneider Electric en Francia, EE. UU. y otros pases. Todas las dems marcas comerciales utilizadas son propiedad de sus respectivos propietarios. Este producto se deber instalar, conectar y utilizar de conformidad con las normas y/o los reglamentos de instalacin vigentes. Debido a la evolucin constante de las normas y del material, deber solicitar siempre confirmacin previa de las caractersticas y dimensiones. 63230-319-216B4_ES 06/2013 Sustituye a 63230-319-216B3_ES 03/2013 2009-2013 Schneider Electric. Reservados todos los derechos.

Schneider Electric
35, rue Joseph Monier CS 30323 F - 92506 Rueil-Malmaison Cedex www.schneider-electric.com

Passerelle Ethernet PowerLogicTM EGX300


Manuel dutilisation
63230-319-216B4_FR 06/2013

Informations de scurit
Informations importantes
Lisez attentivement lensemble de ces instructions et examinez le matriel pour vous familiariser avec lui avant toute installation, utilisation, rparation ou intervention de maintenance. Les messages spciaux qui suivent peuvent apparatre dans ce document ou sur lappareillage. Ils vous avertissent de dangers potentiels ou attirent votre attention sur des renseignements pouvant claircir ou simplifier une procdure. Lajout dun de ces symboles une tiquette de scurit Danger ou Avertissement indique quil existe un danger lectrique qui peut entraner des blessures si les instructions ne sont pas respectes. Ceci est le symbole dalerte de scurit. Il sert vous avertir dun danger potentiel de blessures corporelles. Respectez toutes les consignes de scurit accompagnant ce symbole pour viter tout risque potentiel de blessure ou de mort.

DANGER
DANGER indique une situation de danger imminent qui, si elle nest pas vite, entranera la mort ou des blessures graves.

AVERTISSEMENT
AVERTISSEMENT indique un danger potentiel qui, sil nest pas vit, peut entraner la mort ou des blessures graves.

ATTENTION
ATTENTION indique un danger potentiel qui, sil nest pas vit, peut entraner des blessures lgres ou de gravit moyenne.

NOTE
NOTE concerne des questions non lies des blessures corporelles. Le symbole dalerte de scurit ne doit pas tre utilis avec cette mention.

Veuillez noter
Seul un personnel qualifi doit effectuer linstallation, lutilisation, lentretien et la maintenance du matriel lectrique. Schneider Electric nassume aucune responsabilit des consquences ventuelles dcoulant de lutilisation de cette documentation. Par personne qualifie, on entend un technicien comptent en matire de construction, dinstallation et dutilisation des quipements lectriques et form aux procdures de scurit, donc capable de dtecter et dviter les risques associs.

Avis
Avis FCC section 15
Cet appareil a subi des essais et a t reconnu conforme aux limites imposes aux appareils numriques de classe A, selon le paragraphe 15 de la rglementation FCC (Commission fdrale des communications des tats-Unis). Ces limites sont conues pour fournir une protection raisonnable contre les interfrences nuisibles lorsquun appareil est employ dans un environnement commercial. Cet appareil produit, utilise et peut mettre de lnergie radiofrquence et, sil nest pas install ou utilis conformment au mode demploi, il peut provoquer des interfrences nuisibles aux communications radio. Le fonctionnement de cet appareil dans une zone rsidentielle est susceptible de provoquer des interfrences nuisibles, auquel cas lutilisateur devra corriger les interfrences ses propres frais. La puissance dalimentation de sonnerie (REN, Ringer Equivalence Number) du modem interne en option de lappareil est de 0,6. Le raccordement du modem interne de lappareil doit tre effectu avec un cordon tlphonique conforme la section 68 de la rglementation FCC (non fourni). Lappareil ne peut pas tre utilis avec un service tlphonique public payant ou avec un service ligne partage. Cet appareil numrique appartient la Classe A et est conforme la norme ICES-003 du Canada.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Table des matires

Table des matires


Introduction ............................................................................................... 1 Ressources supplmentaires ...................................................................... 1 Accs la passerelle EGX via un rseau ............................................... 2 Connexion la passerelle EGX .................................................................. 2 Prsentation de linterface utilisateur EGX ............................................ 3 Configuration ............................................................................................. 5 Paramtres Ethernet et TCP/IP .................................................................. 5 Paramtres Ethernet avancs ............................................................... 6 Dtection des adresses IP identiques ................................................... 8 Port srie ..................................................................................................... 8 Paramtres avancs du port srie......................................................... 9 Connexions dappareils distants ............................................................... 10 Liste des appareils EGX ............................................................................ 12 Connexion dappareils une passerelle EGX ..................................... 12 Configuration de la liste des appareils................................................. 13 Dtection des appareils ....................................................................... 15 Journaux dappareil ................................................................................... 17 Enregistrement des donnes par intervalle ......................................... 17 Configuration de lintervalle denregistrement ..................................... 17 Grandeurs consigner ........................................................................ 18 Exporter le journal de lappareil ................................................................. 19 Exportation par courrier lectronique .................................................. 19 Exportation par FTP ............................................................................ 21 Exportation par HTTP.......................................................................... 22 Date et heure ............................................................................................ 24 Synchronisation de lheure rseau ...................................................... 25 Paramtres SNMP .................................................................................... 26 Filtrage Modbus TCP/IP ............................................................................ 27 Liens vers la documentation ..................................................................... 28 Comptes utilisateur ................................................................................... 29 Accs aux pages Web .............................................................................. 30 Ajout/Suppression de pages Web personnalises .............................. 31 Ajout de pages Web personnalises par FTP ..................................... 31 Suppression de pages Web personnalises par FTP ......................... 31 Ajout/Suppression de pages Web personnalises laide de linterface Web................................................................................ 32 Prfrences ............................................................................................... 33 Types dappareil affichables ...................................................................... 34 Piste daudit ............................................................................................... 34 Point daccs systme .............................................................................. 36 Surveillance ............................................................................................. 38 Donnes en temps rel ............................................................................. 38 Pages dappareil unique ...................................................................... 38 Paramtres des mesures de base....................................................... 38 Plage des cadrans analogiques .......................................................... 39 Pages rcapitulatives appareils........................................................... 39 Calcul de tendance.............................................................................. 40 Journaux dappareil ................................................................................... 41 Pages dappareil unique ...................................................................... 42 Obtention dun journal de donnes...................................................... 43 Format des journaux............................................................................ 43 Codes derreur des journaux de donnes ........................................... 44 Obtention dun journal de donnes dintervalle via FTP ...................... 44
2009-2013 Schneider Electric. Tous droits rservs. i

Passerelle Ethernet PowerLogicTM EGX300 Table des matires

63230-319-216B4_FR 06/2013

Obtention dun journal de donnes dintervalle par le biais du bouton Accs aux donnes ............................................................ 45 Obtention dun journal de donnes dintervalle par le biais dune requte Web Microsoft............................................................... 45 Obtention dun journal de donnes dintervalle par courrier lectronique ......................................................................................... 45 Obtention dun journal de donnes dintervalle par HTTP................... 45 Pages rcapitulatives appareils........................................................... 46 Tableaux de bord ...................................................................................... 47 Affichage dun tableau de bord............................................................ 48 Accs aux donnes de tableau de bord par le biais du bouton Accs aux donnes ............................................................................. 49 Enregistrement dun lien de tableau de bord....................................... 49 Enregistrement dun tableau de bord sous forme dimage .................. 49 Point daccs systme .............................................................................. 50 Documentation ........................................................................................ 51 Commande ............................................................................................... 51 Diagnostics .............................................................................................. 52 Statistiques ................................................................................................ 52 Interprtation des statistiques.............................................................. 53 Lecture de registres dappareils ................................................................ 56 Vrification des communications ............................................................... 57 Vrification automatique des communications .................................... 57 Vrification manuelle des communications ......................................... 57 Maintenance ............................................................................................ 58 Logiciel embarqu (firmware) ................................................................ 58 Recherche de la version du logiciel embarqu ......................................... 58 Version du composant binaire excutable du logiciel embarqu ........ 59 Version de limage disque ................................................................... 59 Obtention du dernier logiciel embarqu .................................................... 59 Mise jour du logiciel embarqu (firmware) ............................................. 60 Annexe A Protocoles Ethernet pris en charge .................................. 61 Matriel ..................................................................................................... 61 Annexe B Types dappareil pris en charge ........................................ 62

ii

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Introduction

INTRODUCTION

LEGX300 est un composant Ethernet qui constitue une interface transparente entre les rseaux Ethernet et les appareils situs sur le terrain : compteurs, appareils de mesure, relais de protection, automates programmables, units de contrle, commandes de moteur et autres appareils qui communiquent au moyen des protocoles Modbus, Jbus ou PowerLogic. La passerelle EGX300 utilise le protocole Modbus TCP/IP pour accder aux informations des appareils sur site via un rseau local (LAN) ou un rseau tendu (WAN). Cette fonctionnalit permet dutiliser un logiciel de surveillance qui accde aux informations des appareils et ralise les fonctions de collecte de donnes, courbes de tendances, gestion dalarmes/vnements, analyses et autres. LEGX300 prend en charge la communication des donnes en temps rel de nombreux types dappareil courants et offre plusieurs fonctionnalits spcifiques. Les rapports disponibles prsentent par exemple des pages de rcapitulatifs internes sur lappareil et le circuit, des calculs de tendances en temps rel ou des journaux de donnes internes. Figure 1 : Prsentation de lEGX300
Affichage en temps rel Affichage des donnes dappareil laide dun simple navigateur pas de logiciel spcial Pages Web de lEGX300 Tendances en temps rel

Rinitialisation des commandes

Tendances des journaux de donnes

EGX300

Affiche sous forme de pages Web les informations dautres passerelles PowerLogic et dinterfaces Modbus TCP/IP comme les modules ECC21 et PM8ECC.

EGX100

ION6200

PM800

Micrologic

Sepam

Ressources supplmentaires

Sur le site www.schneider-electric.com, saisissez EGX300 dans le champ de recherche. Naviguez jusquaux documents et tlchargements EGX.

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300 Accs la passerelle EGX via un rseau

63230-319-216B4_FR 06/2013

ACCS LA PASSERELLE EGX VIA UN RSEAU

Aprs avoir configur les paramtres Ethernet de la passerelle EGX (voir le manuel dinstallation EGX), vous pouvez accder la passerelle EGX sur un rseau local Ethernet au moyen dun navigateur Web standard.

Connexion la passerelle EGX


Action
1. Lancez le navigateur Web.

Rsultat
Ouvre le navigateur Web.

2. Dans la barre dadresses, tapez ladresse Ouvre la bote de dialogue de connexion. IP de la passerelle EGX (169.254.0.10 par dfaut) et appuyez sur Entre. 3. Tapez votre nom dutilisateur (Administrator par dfaut) et votre mot de passe (Gateway par dfaut) dans les zones appropries, puis cliquez sur OK. REMARQUE : Le nom dutilisateur et le mot de passe doivent respecter les majuscules/minuscules. 4. Cliquez sur llment appropri dans la barre de menus. Ouvre llment de menu slectionn. Saisit le nom dutilisateur et le mot de passe, puis ouvre la page daccueil EGX.

Figure 2 :

Page daccueil EGX

Barre de menus

Nous vous recommandons de vous dconnecter ds que vous navez plus besoin daccder la passerelle EGX. Pour fermer la session EGX, cliquez sur Dconnexion ou fermez le navigateur.

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Prsentation de linterface utilisateur EGX

PRSENTATION DE LINTERFACE UTILISATEUR EGX

Linterface utilisateur EGX comporte plusieurs pages Web destines la surveillance et la commande dappareils, ainsi qu la configuration et au diagnostic de la passerelle EGX. Voir le Tableau 1 pour la description de chaque page. Tableau 1 : Pages EGX
Page Web EGX
Configuration Ethernet et TCP/IP Port srie Connexions dappareils distants Liste des appareils Configure les paramtres des communications Ethernet et TCP/IP. Configure les paramtres de communication srie. Configure les connexions dappareils Modbus TCP/IP distants. Configure, identifie ou vrifie les appareils srie locaux raccords la guirlande. Les appareils distants peuvent uniquement tre configurs et vrifis. Configure les paramtres denregistrement des journaux dappareil. Configure les options dexportation des journaux denregistrement. Permet de dfinir la date et lheure manuellement ou par le biais de paramtres SNTP. Configure le protocole SNMP (Simple Network Management Protocol). Configure les adresses IP qui peuvent accder la passerelle EGX via le protocole Modbus TCP/IP. 5 8 10 12

Description

Voir page

Journaux dappareil Exporter le journal de lappareil Date et heure1 Paramtres SNMP1 Filtrage Modbus TCP/IP1

17 19 24 26 27 28 29 30 33 34 34

Liens vers la documentation Configure les fichiers et liens de documentation. Comptes utilisateur1 Accs aux pages Web1 Prfrences Permet de crer ou modifier les noms de groupe. Configure les droits daccs aux pages Web pour chaque groupe dutilisateurs. Configure les prfrences de la passerelle EGX.

Types dappareil affichables Configure les types dappareil compatibles qui peuvent tre affichs dans la page Liste des appareils EGX. Piste daudit1 Configure la communication des messages systme par lEGX : via le journal de maintenance, par courrier lectronique ou via le serveur Syslog distant. Active et configure ladresse IP de groupe pour plusieurs passerelles EGX300, ce qui leur permet de se dtecter entre elles et daccder mutuellement aux informations.

Point daccs systme1

36

Surveillance Donnes en temps rel Les Pages dappareil unique affichent les mesures de base provenant dune slection dappareils sous forme de tableaux. Les Pages rcapitulatives appareils affichent le rcapitulatif dun ou de plusieurs appareils slectionns sous forme de tableaux. La page Calcul de tendance offre une vue en temps rel de grandeurs communes pour plusieurs appareils, sous forme de graphiques ou de tableaux. Les Pages dappareil unique fournissent des tendances, sous forme de graphiques et de tableaux, des valeurs slectionnes par lutilisateur pour les appareils choisis. Les Pages rcapitulatives appareils fournissent des tendances pour plusieurs appareils et une grandeur commune, sous forme de graphiques. Les tableaux de bord offrent des reprsentations graphiques et tabulaires des donnes de consommation dnergie agrges sur la priode considre et pour tous les appareils o lenregistrement des donnes est activ. La page Point daccs systme affiche les EGX300 et autres appareils systmes en rseau accessibles depuis cette EGX300. Chaque ligne comporte un hyperlien vers la page de connexion EGX300. 38

Journaux dappareil

41

Tableaux de bord

47

Point daccs systme

50

Uniquement accessible par un administrateur

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300 Prsentation de linterface utilisateur EGX

63230-319-216B4_FR 06/2013

Tableau 1 : Pages EGX


Page Web EGX
Documentation Documentation Commande Rinitialisations Prvoit lexcution des rinitialisations dfinies pour lappareil et affiche la date et lheure laquelle chaque opration a t excute. Les rinitialisations de date et heure napparaissent que si lappareil offre cette fonction. Affiche les donnes de diagnostic utilises pour rechercher des problmes sur le rseau. Cette page contient galement des informations sur votre passerelle EGX, notamment le numro de srie, la date de fabrication et ladresse MAC (Media Access Control contrle daccs au support). Permet aux utilisateurs de lire les donnes de registres des appareils connects la passerelle EGX localement et distance. Effectue une vrification des communications de tous les appareils configurs sur la passerelle EGX. Affiche la date et lheure de la dernire maintenance ralise sur lquipement, lutilisateur qui la effectue ainsi que des dtails concernant lobjet de cette maintenance. 51 Permet daccder la documentation EGX pertinente et aux liens de documentation utilisateur. 51

Description

Voir page

Diagnostics Statistiques 52

Lecture de registres dappareils Vrification des communications Maintenance Journal de maintenance

56

57

58

Uniquement accessible par un administrateur

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

CONFIGURATION

Pour accder aux liens de la page Configuration, cliquez sur Configuration dans la barre de menus de la passerelle EGX.

Paramtres Ethernet et TCP/IP


Action
1. Dans le menu Configuration, cliquez sur Ethernet et TCP/IP. 2. Slectionnez le format de trame et le type de support. Contactez votre administrateur rseau si vous ne connaissez pas ces informations. 3. Entrez ladresse IP, le masque de sous-rseau et ladresse de passerelle attribus la passerelle EGX par votre administrateur rseau.

Rsultat
Ouvre la page Ethernet et TCP/IP. Slectionne le format de trame et le type de support.

Configure les paramtres Ethernet de la passerelle EGX. REMARQUE : Si vous saisissez une adresse IP dj utilise par un autre appareil, le systme vous demande den saisir une autre. Voir Dtection des adresses IP identiques , page 8. Met jour les paramtres Ethernet et TCP/IP de la passerelle EGX.

4. Cliquez sur Appliquer.

* Voir le Tableau 2 ci-dessous pour la liste des options.

Figure 3 :

Page Ethernet et TCP/IP

Tableau 2 : Paramtres Ethernet et TCP/IP de la passerelle EGX


Option
Format de trame

Description
Slection du format des donnes envoyes travers une connexion Ethernet. Dfinition de la connexion Ethernet physique ou du type de support.

Valeur
Ethernet II, 802.3 SNAP Par dfaut : Ethernet II 10T/100Tx Auto 10BaseT-HD 10BaseT-FD 100BaseTx-HD 100BaseTx-FD

Type de support

Par dfaut : 10T/100Tx Auto Obtenir une adresse IP automatiquement Adresse IP Masque de sousrseau Passerelle par dfaut Obtention automatique dune adresse IP Option active ou dsactive partir dun serveur BootP. Par dfaut : Dsactiv REMARQUE : Impose la prise en charge de ladministration rseau. Saisie de ladresse IP statique de la passerelle EGX. Par dfaut : 169.254.0.10

Saisie de ladresse IP Ethernet du masque Par dfaut : 255.255.0.0 de sous-rseau. Saisie de ladresse IP de la passerelle (routeur) utilise pour les communications sur rseau tendu. Par dfaut : 0.0.0.0

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Paramtres Ethernet avancs

NOTE
MAUVAISES PERFORMANCES DU RSEAU Les paramtres Ethernet avancs de la passerelle EGX ne doivent tre modifis que par des techniciens qualifis qui ont lu et assimil la documentation relative ces paramtres. Le non-respect de ces instructions pourrait entraner une baisse des performances du rseau.

Action

Rsultat

1. Cliquez sur Avanc la page Ethernet et Ouvre la page des paramtres Ethernet TCP/IP. avancs. 2. Configurez les paramtres Ethernet Dfinit les paramtres Ethernet avancs. avancs (voir le Tableau 3, page 7 pour les options disponibles). Cliquez sur Valeurs par dfaut pour slectionner les valeurs par dfaut pour toutes les options. 3. Cliquez sur Appliquer. REMARQUE : La modification des donnes de la page Paramtres Ethernet avancs ne valide aucune des modifications apportes la page Ethernet et TCP/IP. 4. Cliquez sur OK pour valider les modifications et rinitialiser la passerelle EGX. Met jour les paramtres Ethernet et TCP/IP de la passerelle EGX.

La passerelle EGX redmarre.

Figure 4 :

Page Paramtres Ethernet avancs

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Tableau 3 : Paramtres Ethernet avancs de la passerelle EGX


Option
Dure de vie

Description
Dtermine le nombre de routeurs par lesquels un paquet TCP peut passer.

Valeur
1 255 sauts Par dfaut : 60 sauts

Maintien de la connexion TCP

Dcompte permettant de dtecter lorsquun appareil 0 65 000 s sur une connexion inactive devient indisponible du Par dfaut : fait dun redmarrage, dune mise hors tension, etc. 30 secondes Entrez la valeur 0 pour dsactiver cette fonction. Permet de spcifier le temps pendant lequel la passerelle EGX doit attendre lassignation de son adresse IP par un serveur BootP (ladresse IP par dfaut est utilise si aucune adresse IP nest attribue aprs le dlai dattente). 0 60 s Par dfaut : 15 secondes

Dlai dattente BootP

Dlai dattente du cache ARP Serveur FTP Dlai dinactivit de la connexion FTP Dlai dinactivit de la connexion HTTP Numro de port HTTP

Permet de spcifier le temps pendant lequel les 0 65 000 minutes entres sont conserves dans la table ARP (Address Par dfaut : Resolution Protocol). 15 minutes Dtermine si le serveur FTP sinitialise pendant le dmarrage. Dsactiv ou Activ Par dfaut : Activ

Dcompte permettant de fermer une connexion FTP 30 900 s aprs le temps dinactivit dfini. Par dfaut : 120 secondes Dcompte permettant de fermer une connexion HTTP aprs le temps dinactivit dfini. Port TCP utilis pour les messages HTTP. Les numros de port suivants sont rservs dautres protocoles rseau et ne sont donc pas disponibles : 20 et 21 (FTP) et 502 (Modbus TCP/IP). Port TCP utilis pour les messages HTTPS. La passerelle EGX est fournie avec un certificat autosign. Pour authentifier lEGX comme serveur, vous devez obtenir un certificat dune autorit de certification (par exemple VeriSign Authentication Services). Pour ajouter ou installer un certificat numrique, ouvrez la page de mise jour du certificat, ladresse http://x.x.x.x./update_certs_shtml (o x.x.x.x correspond ladresse IP de lEGX). 0 65 000 s Par dfaut : 4 secondes 0 65 000 Par dfaut : 80 0 dsactive le port HTTP 1 65 000 Par dfaut : 443 0 dsactive le port HTTPS

Numro de port HTTPS

Tentatives de maintien de la connexion HTTP

Permet de spcifier le nombre maximal de tentatives 0 65 000 de maintien de la connexion HTTP. Par dfaut : 100 16 64 Par dfaut : 32 Dsactiv, Activ ou Activ avec rponse Par dfaut : Dsactiv

Connexions serveur Permet de spcifier le nombre de connexions Modbus TCP/IP serveur Modbus TCP/IP disponibles. Diffusion Modbus Dtermine le traitement par le sous-rseau srie des messages Modbus TCP/IP de type Unit ID = 0. Dsactiv = tous les messages sont ignors. Activ = tous les messages sont traits comme des messages diffusion gnrale en direction des ports srie nappelant pas de rponse. Activ avec rponse = tous les messages sont traits comme des messages ordinaires en direction des ports srie avec rponse attendue.

Proxy Modbus/TCP Dtermine si les messages Modbus TCP/IP provenant de clients distants seront achemins aux appareils Modbus TCP/IP distants dfinis dans la passerelle EGX. Dlai dattente du client Modbus TCP/IP

Dsactiv ou Activ Par dfaut : Activ

Temps que doit attendre la passerelle EGX pour 0,1 10 quun appareil Modbus TCP/IP distant rponde une Par dfaut : demande Modbus TCP/IP lance par la passerelle 5 secondes EGX.

Dlai dattente de la Temps que doit attendre la passerelle EGX pour 1 10 connexion client quun appareil Modbus TCP/IP distant rponde une Par dfaut : Modbus TCP/IP demande de connexion Modbus TCP/IP lance par 2 secondes la passerelle EGX. Dlai dinactivit de la connexion serveur Modbus TCP/IP Dcompte permettant de fermer une connexion Modbus TCP/IP aprs le temps dinactivit dfini. Entrez la valeur 0 pour dsactiver cette fonction. 0 32 767 s Par dfaut : 0

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Dtection des adresses IP identiques

Lorsquelle est connecte au rseau, la passerelle EGX publie son adresse IP. Pour viter les conflits dadresses, la passerelle EGX utilise le protocole ARP (Address Resolution Protocol) pour vrifier si un autre appareil du rseau utilise la mme adresse IP. Le Tableau 4 ci-dessous dcrit comment la passerelle EGX ragit en cas de dtection dune adresse IP identique. Tableau 4 : Scnarios de dtection des adresses IP identiques
Scnario
Redmarrage / Rtablissement de lalimentation

Adresse IP en double dtecte

Voyant LED dalimentation / tat

Rtablit ladresse IP, le masque de Quatre clignotements, sous-rseau et ladresse par dfaut de pause la passerelle EGX. Les demandes ARP sont envoyes toutes les 15 secondes Liaison Ethernet dtecte jusqu ce que ladresse IP soit disponible. Lorsque ladresse est disponible, la passerelle EGX lutilise. Modification manuelle des adresses La passerelle EGX conserve son adresse IP prcdente et affiche un message qui indique que ladresse IP est dj utilise par un autre appareil.

Rception dune demande ARP

Rtablit ladresse IP, le masque de Quatre clignotements, sous-rseau et ladresse par dfaut de pause la passerelle EGX si un appareil connect envoie quatre demandes ARP pour ladresse IP de la passerelle EGX. La passerelle EGX envoie des demandes ARP toutes les 15 secondes jusqu ce que ladresse IP soit nouveau disponible. Lorsque ladresse est disponible, la passerelle EGX lutilise.

Port srie
Action
1. Dans le menu Configuration, cliquez sur Port srie.

Rsultat
Ouvre la page Port srie.

2. Slectionnez linterface physique, le mode Slectionne les options de port srie. de transmission, la vitesse, la parit et le dlai de rponse (voir le Tableau 5, page 9). 3. Cliquez sur Appliquer. Met jour les paramtres du port srie de la passerelle EGX.

Figure 5 :

Page Port srie

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Tableau 5 : Paramtres de port srie


Option
Interface physique Mode de transmission

Description
Permet de slectionner le cblage physique du port srie de la passerelle EGX. Permet de dterminer comment les donnes sont transmises travers une connexion srie.

Valeur
RS-485 4 fils, RS-485 2 fils ou RS-232 Par dfaut : RS-485 2 fils Automatique Modbus ASCII

REMARQUE : Le mode automatique permet simultanment de communiquer avec les appareils esclaves Modbus RTU, PowerLogic (SY/MAX) et Jbus sur la mme guirlande. Vitesse de transmission Parit Permet de slectionner la vitesse de transmission travers une connexion srie. 2400, 4800, 9600, 19200, 38400, 56000* ou 57600* Par dfaut : 19200

Permet de slectionner le type de parit Paire, Impaire ou Aucune Par dfaut : Paire requise pour vrifier lexactitude des donnes laide dun bit de parit. 0,1 10 s Permet de slectionner le temps pendant lequel la passerelle EGX attend Par dfaut : 3 secondes une rponse dun appareil srie.

Dlai dattente de rponse

* Disponible uniquement si linterface physique et le mode de transmission sont RS-232/Modbus ASCII.

Paramtres avancs du port srie

NOTE
MAUVAISES PERFORMANCES DU RSEAU Les paramtres Ethernet avancs de la passerelle EGX ne doivent tre modifis que par des techniciens qualifis qui ont lu et assimil la documentation relative ces paramtres. Le non-respect de ces instructions pourrait entraner une baisse des performances de linterface srie.

Action
1. Cliquez sur Avanc dans la page Port srie. 2. Configurez les paramtres de port srie avancs (voir le Tableau 6, page 10 pour les options disponibles). Cliquez sur Valeurs par dfaut pour slectionner les valeurs par dfaut pour toutes les options. 3. Cliquez sur Appliquer. REMARQUE : La modification des donnes de la page Paramtres avancs du port srie ne valide aucune des modifications apportes la page Port srie.

Rsultat
Ouvre la page des paramtres avancs du port srie. Permet de dfinir les paramtres avancs du port srie. Met jour les paramtres avancs du port srie de la passerelle EGX.

Figure 6 :

Page des paramtres avancs du port srie

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Tableau 6 : Paramtres avancs du port srie


Option
Dlai dattente entre trames Extension de lintervalle de silence Code derreur de dlai dattente Modbus TCP/IP

Description

Valeur

Dfinit lintervalle de silence minimal entre 0 100 millisecondes la fin de la rponse reue et le dbut dune Par dfaut : 50 millisecondes nouvelle requte sur la ligne srie. Permet dtendre au-del des 3,5 caractres normaux lintervalle de silence charg de marquer la fin dun paquet Modbus RTU. 0 15 caractres Par dfaut : 6 caractres

Indique le code derreur renvoy lorsquun 0x0A ou 0x0B appareil srie connect la passerelle Par dfaut : 0x0B EGX ne rpond pas dans le dlai prvu pour le port srie. Pour Modbus TCP/IP, ce code est 0x0B. Dans certaines suites logicielles plus anciennes, le code tait 0x0A.

Connexions dappareils distants

LEGX peut tablir des connexions pour un maximum de 16 appareils Modbus TCP/IP distants uniques dfinis par lutilisateur. Vous pouvez entrer les connexions manuellement ou les slectionner dans le tableau des connexions dtectes par le Point daccs systme (voir Figure 7, page 11). Ces connexions seront ajoutes la configuration de la liste des appareils pour la configuration dappareils distants.
Action
1. Dans le menu Configuration, cliquez sur Connexions dappareils distants.

Rsultat
Ouvre la page Connexions dappareils distants.

2. Pour ajouter manuellement une connexion, Configure les adresses IP des appareils entrez les adresses IP des appareils distants. distants auxquels vous souhaitez vous connecter. 3. Pour ajouter une connexion dtecte par le Entre ladresse IP de la connexion slectionne Point daccs systme, cliquez sur Ajouter parmi les connexions dtectes par le Point ( droite de la connexion souhaite dans le daccs systme. tableau des connexions dtectes). 4. Cliquez sur Appliquer. Met jour les paramtres de connexions dappareils distants de la passerelle EGX.

10

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Figure 7 :

Connexions dappareils distants

2009-2013 Schneider Electric. Tous droits rservs.

11

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Liste des appareils EGX

Avant de commencer, gardez lesprit que vous ne devez pas utiliser les adresses esclaves srie 1 16 en mode de transmission automatique sur une guirlande utilisant plusieurs protocoles (par exemple, une guirlande qui comporte des appareils utilisant le protocole PowerLogic et dautres utilisant le protocole Modbus RTU/Jbus).

Connexion dappareils une passerelle EGX

La Figure 8 et la Figure 9 montrent les possibilits de connexion des appareils la passerelle EGX. Pour ajouter ces appareils la liste des appareils, suivez la procdure dcrite la section Configuration de la liste des appareils , page 13. Figure 8 : Topologie Appareils esclaves srie uniquement

Connexion Ethernet Pages Web de lEGX300 EGX

Connexion RS-485

Appareils esclaves srie

Figure 9 :

Topologie Appareils esclaves srie et appareils distants


Connexion Ethernet

Pages Web de lEGX300 EGX100 Adresse IP : 169.254.0.28 EGX300 Adresse IP : 169.254.0.75

16 connexions IP distantes sont possibles

Connexion RS-485

Connexion RS-485

Appareils esclaves distants

Appareils esclaves srie

12

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Configuration de la liste des appareils


Action
1. Dans le menu Configuration, cliquez sur Liste des appareils.

Rsultat
Ouvre la page Liste des appareils. (Voir Figure 10 pour les connexions locales uniquement ; Figure 11 si des connexions distantes sont disponibles.)

2. Vous pouvez utiliser la dtection des Ouvre la page Dtection des appareils pour appareils pour dtecter les appareils dtecter tous les appareils connects connects localement (voir Dtection des localement. appareils , page 15) puis passer ltape 3 pour configurer les appareils distants si ncessaire. 3. Reportez-vous la Figure 11, page 14 et slectionnez le nombre dappareils affichables (1 64). 4. Slectionnez la Connexion dans la liste droulante.* 5. Slectionnez le Type dappareil dans la liste droulante.* 6. Dans la zone de texte Nom dappareil, tapez le nom de lappareil. Slectionne le nombre demplacements affichables qui peuvent servir dfinir des appareils connects la passerelle EGX. Slectionne la connexion. Slectionne le type dappareil. Saisit le nom de lappareil.

7. Dans la zone de texte Identification Configure ladresse locale de lappareil. locale, tapez ladresse de lappareil esclave srie sil est raccord au port srie ou saisissez ladresse que vous voulez utiliser pour accder un appareil distant.* 8. Dans la zone de texte Identification distante, tapez ladresse de lappareil distant.* Configure ladresse de lappareil distant.

9. Recommencez les tapes 4 8 jusqu ce Saisit tous les appareils connects. que tous les appareils soient configurs. 10. Cliquez sur Appliquer. Actualise la liste des appareils.

* Ce paramtre de configuration peut tre modifi uniquement si lenregistrement des donnes est dsactiv pour lappareil mis jour. Voir Journaux dappareil , page 17.

Figure 10 : Page Liste des appareils

2009-2013 Schneider Electric. Tous droits rservs.

13

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Figure 11 : Page Liste des appareils avec connexions distantes prises en charge

Tableau 7 : Paramtres de la liste des appareils


Option
Nombre dappareils afficher Connexion Type dappareil Nom dappareil Identification locale Identification distante

Description
Slectionne le nombre dappareils afficher. Slectionne le site de connexion.

Valeur
1 64 Par dfaut : 8 Port srie ou adresse IP Par dfaut : Port srie

Slectionne le type dappareil apparaissant Ensemble des appareils pris dans la liste. en charge Permet dattribuer un nom chaque appareil. Vous devez dfinir lidentification locale. Vous devez dfinir lidentification distante.

14

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Dtection des appareils

Loption Dtection des appareils permet la passerelle EGX de dtecter les appareils Modbus connects au port srie qui ne sont pas dans la liste des appareils. Les appareils saisis prcdemment dans la liste sont valids quelle que soit la plage de dtection configure. Dtection Lorsque vous lancez la dtection des appareils, la passerelle EGX interroge le port srie local sur une plage dadresses dfinie par lutilisateur (voir la Figure 12, page 16). La dtection sur la connexion srie utilise le protocole Modbus ASCII ou RTU, selon la configuration active du port srie. Si lappareil rpond la requte, lidentification locale prend ladresse dtecte et lappareil reoit un nom par dfaut. La passerelle EGX essaie alors didentifier le type dappareil. Si la passerelle EGX reconnat le type de lappareil dtect, elle indique le nom correspondant dans la zone Type dappareil. Si la passerelle EGX ne reconnat pas le type dappareil, la zone Type dappareil prend la valeur par dfaut Modbus . Une zone dtat affiche ltat de la dtection. Validation Toutes les entres dfinies prcdemment dans la liste des appareils pour lensemble des connexions (srie et distantes), quelles soient ou non comprises dans la plage dadresses de la dtection, sont valides pendant le processus de dtection. Sur la connexion srie, le protocole de validation est dtermin par la configuration actuelle de lappareil dans la liste des appareils. Le protocole Modbus TCP/IP est utilis pour la validation des appareils distants. La passerelle EGX affiche lidentification locale, le nom dappareil et le type dappareil mmoriss partir de la liste des appareils, puis elle interroge lappareil. Elle affiche alors le type dappareil identifi par cette requte, puis le compare au type dfini prcdemment. Ltat indique alors sil existe une diffrence ou si la configuration dfinie prcdemment est valide. REMARQUE : Vous pouvez modifier le nom et le type de lappareil, et slectionner individuellement les appareils stocker dans la liste des appareils. Nanmoins, si lenregistrement de journaux est activ pour un appareil, vous ne pouvez modifier que son nom.

Action
1. Dans le menu Configuration, cliquez sur Liste des appareils. 2. Pour dtecter les appareils connects localement, cliquez sur Dtection.

Rsultat
Ouvre la page Liste des appareils. Ouvre la page Dtection des appareils.

3. Saisissez ladresse de dbut et ladresse Dfinit la plage dadresses de dtection. de fin. REMARQUE : Les appareils saisis prcdemment dans la liste des appareils et dont les adresses (identifications locales) se trouvent en dehors de la plage de dtection seront valids. 4. Cliquez sur Lancer la dtection. (Cliquez Dbute la dtection de tous les appareils sur Arrter la dtection pour arrter le connects et dfinis. processus.) REMARQUE : La dtection ne dtecte que les appareils Modbus srie connects localement la passerelle EGX. Les appareils distants doivent tre ajouts manuellement. Voir Connexions dappareils distants , page 10. 5. Saisissez un nouveau nom dappareil dans Renomme lappareil. la zone de texte Nom.

2009-2013 Schneider Electric. Tous droits rservs.

15

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Action

Rsultat

6. Slectionnez la case cocher Enregistrer Slectionne ou dslectionne une entre en regard de lappareil que vous souhaitez dappareil enregistrer ou renommer. enregistrer dans la liste des appareils. 7. Cliquez sur le bouton Appliquer de la page Dtection des appareils. Enregistre dans la liste des appareils la configuration de tous les appareils slectionns.

Figure 12 : Dtection des appareils

Tableau 8 : Options de dtection des appareils


Option
Adresse dbut/fin

Description

Valeur

Dfinit la plage dadresses Modbus utilise 1 247 pour dtecter des appareils sur le port srie Par dfaut : dbut, 1 ; fin, 10 de lEGX. Permet denregistrer lappareil slectionn dans la liste des appareils. Affiche la connexion sur laquelle lappareil a t dtect ou valid. Affiche le type dappareil dfini pour cet appareil. Permet de slectionner le type dappareil dans la liste droulante. Permet de personnaliser le nom de lappareil. Affiche lidentification locale. Affiche lidentification distante. Affiche ltat de la dtection ou de la validation. Activ ou Dsactiv Par dfaut : Activ Port srie ou adresse IP (pour la validation des appareils distants) Valide, Inconnu, chec, Dtect, Dtection ou Essai

Enregistrer Connexion

Dfini Attribu Nom Identification locale Identification distante tat

16

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Journaux dappareil

Lenregistrement des journaux est disponible pour tous les types dappareils pris en charge par la passerelle EGX. La passerelle EGX peut enregistrer dans un journal, des intervalles prdfinis (5, 10, 15, 20, 30 et 60 minutes), les donnes transmises par des appareils connects localement et distance. Cette section dcrit comment la passerelle EGX enregistre les donnes dans les journaux et comment configurer lenregistrement des journaux pour un appareil. Dans un systme de surveillance de lnergie, de nombreux appareils ne peuvent pas conserver les donnes dans une mmoire non volatile. La passerelle EGX300 peut enregistrer des donnes des intervalles prdfinis en provenance de 64 appareils connects en srie et distance. La passerelle EGX enregistre les donnes dans des fichiers FIFO (premier entr, premier sorti) non volatiles. La capacit de chaque fichier journal varie selon lintervalle denregistrement slectionn. Pour calculer la capacit denregistrement dun fichier journal, il faut diviser le nombre maximum possible dintervalles enregistrs que peut contenir le fichier (171 072) par le produit du nombre de grandeurs enregistres et des intervalles enregistrs en un jour.
Capacit du journal = intervalles (max) / (grandeurs par intervalle * intervalles enregistrs en un jour)

Enregistrement des donnes par intervalle

Par exemple, la capacit denregistrement dun fichier qui enregistre trois grandeurs toutes les 10 minutes serait calcule comme suit :
Intervalles enregistrs par jour = minutes par jour / intervalle denregistrement (en minutes) = 1440 / 10 = 144 intervalles Capacit du journal = maximum intervalles possibles / (grandeurs par intervalle * intervalles enregistrs en un jour) = 171072 / (3 * 144) = 396 jours

La capacit denregistrement est calcule de faon dynamique et affiche dans la page Slection de grandeur (voir les exemples du Tableau 9). Tableau 9 : Exemples dintervalles denregistrement
Nombre de grandeurs Capacit du journal (en jours) pour les intervalles indiqus Intervalle 5 min 1 2 3 4 5 6 594 297 198 148 118 99 Intervalle 10 min 1188 594 396 297 237 198 Intervalle 15 min 1782 891 594 445 356 297

Configuration de lintervalle denregistrement

Lenregistrement peut tre activ individuellement sur chaque appareil de la liste. Les grandeurs consigner sont spcifiques chaque appareil. Pour afficher les journaux de donnes dintervalle, voir Journaux dappareil , page 41. REMARQUE : Pour activer la fonction Journaux dappareil, vous devez slectionner une valeur dans la fentre Intervalle denregistrement. Nous vous recommandons de dsactiver la fonction denregistrement sur lappareil que vous configurez. Il suffit pour cela de dcocher loption correspondante pour lappareil slectionn (voir Figure 13, page 18).
17

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Action
1. Dans le menu Configuration, cliquez sur Journaux dappareil (voir Figure 13). 2. Reportez-vous la Figure 13 et cochez loption Enregistrement du ou des appareils dont vous voulez enregistrer les donnes. Pour slectionner tous les appareils, cliquez sur slectionner tout, puis sur Appliquer. Pour dslectionner tous les appareils, cliquez sur effacer, puis sur Appliquer. 3. Slectionnez lintervalle denregistrement. 4. Cliquez sur Appliquer.

Rsultat
Ouvre la page Journaux dappareil. Slectionne les appareils dont les donnes doivent tre enregistres.

Dfinit lintervalle denregistrement pour les appareils slectionns. Met jour les paramtres denregistrement des journaux dappareil de la passerelle EGX.

OPTIONS Pour personnaliser le contenu enregistr, activez Slectionne les grandeurs dappareils enregistrer, puis revient la page lenregistrement puis procdez comme suit : Journaux dappareil principale. 1. Slectionnez un intervalle denregistrement non nul REMARQUE : Si vous modifiez puis dcochez loption denregistrement pour les grandeurs par dfaut lappareil en question. enregistres pour un appareil, un 2. Cliquez sur grandeurs sous Personnaliser pour astrisque (*) apparat ct des lappareil que vous souhaitez configurer. grandeurs dans la colonne 3. Reportez-vous la Figure 14, page 19 et cochez les Personnaliser pour chaque grandeurs que vous souhaitez enregistrer. appareil. La modification des Pour slectionner toutes les grandeurs, cliquez grandeurs dun journal dappareil dj activ a pour consquence sur slectionner tout, puis cliquez sur deffacer toutes les donnes Appliquer. prcdemment enregistres pour Pour dslectionner toutes les grandeurs, cliquez cet appareil. Si ncessaire, il sur effacer, puis cliquez sur Appliquer. convient de rcuprer les Pour slectionner les grandeurs par dfaut, donnes de lEGX avant les cliquez sur Valeurs par dfaut en bas de lcran. modifications. Slectionne les journaux de donnes Pour supprimer un journal de donnes, cochez loption purger. Purge donnes du ou des journaux en question. 1. Pour slectionner tous les appareils, cliquez sur slectionner tout, puis sur Appliquer. 2. Pour dslectionner tous les appareils, cliquez sur effacer, puis sur Appliquer. Pour dsactiver lenregistrement, slectionnez un intervalle denregistrement nul, assurez-vous que les options denregistrement sont dcoches, puis cliquez sur Appliquer. REMARQUE : Pour purger un journal de donnes, il est impratif que loption Enregistrement de journaux soit dsactive. Dsactive la fonction denregistrement.

Figure 13 : Page Journaux dappareil

Grandeurs consigner

Vous pouvez slectionner individuellement les grandeurs consigner pour chaque appareil.
Action Rsultat
1. la page Journaux dappareil, cliquez sur le lien grandeurs pour Ouvre la page de lappareil en question. slection des grandeurs. 2. Reportez-vous la Figure 14, page 19 et cochez les grandeurs Permet de slectionner que vous souhaitez enregistrer. les grandeurs enregistrer. Pour slectionner toutes les grandeurs, cliquez sur slectionner tout. Pour dslectionner toutes les grandeurs, cliquez sur effacer. Pour slectionner les grandeurs par dfaut, cliquez sur Valeurs par dfaut. 3. Cliquez sur Appliquer. Enregistre dans le journal les grandeurs slectionnes.

18

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Figure 14 : Page de slection des grandeurs

Exporter le journal de lappareil

Cette fonction permet dexporter les journaux dappareils de trois faons : par courrier lectronique, FTP ou HTTP. Chaque mthode est dcrite dans les sections suivantes. REMARQUE : Si les serveurs de courrier lectronique, FTP ou HTTP ne se trouvent pas sur le mme segment de rseau Ethernet que la passerelle EGX, assurez-vous que les paramtres de passerelle EGX par dfaut sont correctement configurs. Voir Paramtres Ethernet et TCP/IP , page 5.

Exportation par courrier lectronique


Action
1. Dans la page Configuration, cliquez sur Exporter le journal de lappareil. 2. Slectionnez Courrier lectronique comme mode dacheminement. 3. Cochez loption Incrmentale.

Rsultat
Ouvre la page Exporter le journal de lappareil. Affiche les options dexportation des journaux dappareil par courrier lectronique.

Slectionne uniquement les nouvelles donnes enregistres REMARQUE : Si lacheminement est rgl sur les options depuis la dernire exportation de Horaire ou Intervalle denregistrement , la case donnes russie. cocher Incrmentale est automatiquement slectionne. REMARQUE : Si loption Incrmentale est dsactive, la totalit du fichier journal est envoye en fichier joint chaque intervalle dfini.

4. Slectionnez Horaire, Quotidien, Hebdomadaire, Mensuel ou Intervalle denregistrement.

Slectionne la frquence denvoi des journaux de donnes.

2009-2013 Schneider Electric. Tous droits rservs.

19

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Action

Rsultat

5. Selon les options spcifies ltape prcdente, Spcifie quel moment les slectionnez lheure, le jour de la semaine et/ou le jour du journaux de donnes sont mois. envoys. 6. Dans la zone de texte De ladresse, tapez ladresse lectronique de la personne responsable de lappareil. REMARQUE : Ladresse lectronique de lexpditeur est indispensable car la plupart des serveurs SMTP la demandent. 7. Dans les zones de texte Aux adresses, tapez les adresses lectroniques (5 maximum) des destinataires des journaux de donnes (une adresse par zone). 8. Dans les zones de texte Adresse IP du serveur, saisissez ladresse du serveur de courrier sortant (de 0.0.0.0 255.255.255.255). REMARQUE : Contactez votre administrateur rseau si vous ne connaissez pas ladresse du serveur SMTP (Simple Mail Transfer Protocol). 9. Dans la zone de texte Port TCP du serveur, saisissez le Dfinit le port dexpdition du port dexpdition du serveur de courrier sortant. serveur de courrier sortant. Par dfaut : 25 10. Si le serveur SMTP exige une authentification, activez loption Connexion au serveur SMTP via authentification. REMARQUE : La passerelle EGX prend en charge les types dauthentification Plain, Login, CRAM-MD5 et Digest-MD5. 11. Si vous avez coch loption Connexion au serveur SMTP via authentification, saisissez votre nom dutilisateur et votre mot de passe dans les zones de texte. Mmorise vos identifiants de connexion au serveur SMTP. Permet de saisir les identifiants de connexion au serveur SMTP. Dfinit les adresses lectroniques des destinataires. Dfinit ladresse du serveur qui envoie les journaux. Dfinit lexpditeur du courrier lectronique.

12. Cliquez sur Courrier lectronique de test pour envoyer Envoie un courrier lectronique un message test avec les paramtres que vous avez de test et/ou applique les dfinis ou cliquez sur Appliquer. paramtres dexportation du journal par courrier lectronique. REMARQUE : Le bouton Courrier lectronique de test valide les paramtres dexportation du journal par courrier lectronique et envoie un courrier de test ; le bouton Appliquer valide uniquement les paramtres.

Figure 15 : Page Exporter le journal de lappareil par courrier lectronique

20

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Exportation par FTP


Action
1. Dans la page Configuration, cliquez sur Exporter le journal de lappareil. 2. Slectionnez FTP comme mode dacheminement. 3. Activez loption Incrmentale. REMARQUE : Si lacheminement est rgl sur les options Horaire ou Intervalle denregistrement , la case cocher Incrmentale est automatiquement slectionne. REMARQUE : Si loption Incrmentale est dsactive, la totalit du fichier journal est envoye par FTP chaque intervalle dfini. 4. Slectionnez Horaire, Quotidien, Hebdomadaire, Mensuel ou Intervalle denregistrement.

Rsultat
Ouvre la page Exporter le journal de lappareil. Affiche les options dexportation des journaux dappareil par FTP. Permet de slectionner uniquement les nouvelles donnes enregistres depuis la dernire exportation de donnes russie.

Permet de slectionner la frquence dacheminement des journaux de donnes.

5. Selon les options spcifies ltape prcdente, Spcifie quel moment les slectionnez lheure, le jour de la semaine et/ou le jour du journaux de donnes sont mois. achemins. 6. Dans les zones de texte Adresse IP du serveur, saisissez ladresse du serveur FTP sortant (de 0.0.0.0 255.255.255.255). REMARQUE : Contactez votre administrateur rseau si vous ne connaissez pas ladresse du serveur FTP (File Transfer Protocol). 7. Saisissez le rpertoire dans la zone de texte Rpertoire. Dfinit ladresse du serveur acheminant les journaux de donnes.

Permet de saisir les informations relatives au rpertoire du serveur distant. Mmorise vos identifiants de connexion au serveur. Permet de slectionner le mode passif pour le transfert FTP.

8. Saisissez votre nom dutilisateur et votre mot de passe dans les zones de texte. 9. Activez loption Passif.

10. Si vous exportez des donnes vers StruxureWare Energy Ajoute ladresse MAC pour crer Operation, slectionnez loption Ajouter ladresse MAC un nom de fichier unique. au nom de fichier. REMARQUE : Cette option empche la fusion des donnes au cas o deux fichiers du mme nom seraient envoys Energy Operation. Voir Obtention dun journal de donnes, page 43, pour en savoir plus sur le format du journal. 11. Cliquez sur Test FTP pour effectuer un test des paramtres Envoie un fichier de test au FTP que vous avez dfinis ou cliquez sur Appliquer. serveur et rpertoire FTP et/ou REMARQUE : Le bouton Test FTP valide les paramtres applique les paramtres FTP. dexportation du journal par FTP et transfre un fichier de test ; le bouton Appliquer valide uniquement les paramtres.

2009-2013 Schneider Electric. Tous droits rservs.

21

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Figure 16 : Page Exporter le journal de lappareil par FTP

REMARQUE : Si lacheminement est rgl sur les options Horaire ou Intervalle denregistrement , la case cocher Incrmentale est automatiquement slectionne.

Exportation par HTTP


Action
1. Dans la page Configuration, cliquez sur Exporter le journal de lappareil. 2. Slectionnez HTTP comme mode dacheminement. 3. Cochez loption Incrmentale.

Rsultat
Ouvre la page Exporter le journal de lappareil. Affiche les options dexportation des journaux dappareil par HTTP.

Permet de slectionner uniquement les nouvelles donnes enregistres depuis la REMARQUE : Si lacheminement est rgl sur les options Horaire ou Intervalle dernire exportation de donnes russie. denregistrement , la case cocher Incrmentale est automatiquement slectionne. REMARQUE : Si loption Incrmentale est dsactive, la totalit du fichier journal est envoye par HTTP chaque intervalle dfini.

4. Slectionnez Horaire, Quotidien, Hebdomadaire, Mensuel ou Intervalle denregistrement.

Permet de slectionner la frquence dacheminement des journaux de donnes.

5. Selon les options spcifies ltape Spcifie quel moment les journaux de prcdente, slectionnez lheure, le jour de donnes sont achemins. la semaine et/ou le jour du mois. 6. Dans les zones de texte Adresse IP du serveur, saisissez ladresse du serveur HTTP. REMARQUE : Contactez votre administrateur rseau si vous ne connaissez pas ladresse du serveur HTTP. 7. Dans la zone de texte Port TCP du serveur, saisissez le port du serveur HTTP. REMARQUE : Si vous souhaitez utiliser une connexion SSL pour lexportation, entrez le numro de port TCP du serveur HTTPS (habituellement 443). Dfinit le port TCP dexpdition. Par dfaut : 80 Dfinit ladresse IP du serveur acheminant les journaux de donnes.

22

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Action

Rsultat

8. Si vous utilisez un serveur proxy, saisissez Dfinit ladresse IP du serveur proxy son adresse IP dans les zones de texte acheminant les journaux de donnes. Adresse IP du serveur proxy. REMARQUE : Consultez ladministrateur du rseau si vous ne connaissez pas ladresse du serveur proxy. 9. Dans la zone de texte Port TCP du serveur proxy, saisissez le port du serveur HTTP. REMARQUE : Si vous souhaitez utiliser une connexion SSL pour lexportation, entrez le numro de port TCP du serveur HTTPS (habituellement 443). 10. Dans la zone de texte Chemin, saisissez le chemin du script serveur que le serveur Web doit excuter lorsque la passerelle EGX lui transmet des donnes. Insre le chemin du script serveur. Dfinit le port TCP dexpdition. Par dfaut : 0

11. Dans le champ Nom de champ, saisissez Permet la passerelle EGX de passer des le nom sous lequel le serveur Web doit fichiers un script de serveur Web existant. attendre le nom de fichier. REMARQUE : Si ce critre est sans objet, utilisez la valeur par dfaut datafile1 . 12. Dans le champ Nom dhte, saisissez le nom de domaine de lhte. 13. Saisissez votre nom dutilisateur et votre mot de passe dans les zones de texte. 14. Si vous souhaitez utiliser une connexion SSL pour lexportation, cochez cette option. 15. Si vous exportez des donnes vers StruxureWare Energy Operation, slectionnez loption Ajouter ladresse MAC au nom de fichier. REMARQUE : Cette option empche la fusion des donnes au cas o deux fichiers du mme nom seraient envoys Energy Operation. Voir Obtention dun journal de donnes, page 43, pour en savoir plus sur le format du journal. 16. Cliquez sur Test HTTP pour effectuer un test des paramtres HTTP que vous avez dfinis ou cliquez sur Appliquer. REMARQUE : Lorsque vous cliquez sur Test HTTP, les paramtres dexportation du journal par HTTP sont appliqus et un fichier de test est transfr. Lorsque vous cliquez sur Appliquer, les paramtres sont simplement appliqus. Envoie un fichier de test au serveur et rpertoire HTTP et/ou applique les paramtres HTTP. Identifie un hte spcifique sur le serveur Web si ce serveur hberge plusieurs domaines pour une mme adresse IP. (Vide par dfaut.) Mmorise vos identifiants de connexion au serveur. Tous les journaux dappareil exports via HTTP seront dsormais exports via SSL (HTTPS). Ajoute ladresse MAC pour crer un nom de fichier unique.

2009-2013 Schneider Electric. Tous droits rservs.

23

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Figure 17 : Page Exporter le journal de lappareil par HTTP

Date et heure

La page Date et heure permet de rgler la date et lheure de la passerelle EGX.


Action
1. Dans le menu Configuration, cliquez sur Date et heure.

Rsultat
Ouvre la page Date et heure.

2. Rglez lanne, le mois, le jour, lheure, les Rgle la date et lheure. minutes et les secondes. 3. Slectionnez le dcalage horaire. Rgle lhorloge sur le fuseau horaire slectionn.

4. Pour que lhorloge passe automatiquement Permet lhorloge de passer automatiquement lheure dt, slectionnez la case lheure dt. cocher Activer le rglage automatique de lheure dt. 5. Saisissez lordinal, le jour de la semaine, le Dfinit le dbut et la fin de lheure dt. mois et lheure de dbut et de fin de lheure dt. 6. Cliquez sur Appliquer. Enregistre les paramtres de date et dheure.

24

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Figure 18 : Page Date et heure

Synchronisation de lheure rseau

La synchronisation de lheure rseau permet de rgler la date et lheure de lhorloge du systme EGX laide dun serveur NTP (Network Time Protocol). REMARQUE : Si le serveur NTP ne se trouve pas sur le mme segment de rseau Ethernet que la passerelle EGX, assurez-vous que les paramtres de passerelle EGX par dfaut sont correctement configurs.

Action
1. Slectionnez la case cocher Activer synchronisation de lheure rseau de la page Date et heure. 2. Configurez le dcalage horaire, la priode de scrutation et ladresse IP des serveurs NTP primaire et secondaire (voir le Tableau 10, page 26). 3. Cliquez sur Appliquer.

Rsultat
Affiche les paramtres SNTP ainsi que la dernire synchronisation horaire russie. Rgle les paramtres SNTP.

Enregistre la configuration SNTP.

Figure 19 : Activation de la synchronisation de lheure rseau

2009-2013 Schneider Electric. Tous droits rservs.

25

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Tableau 10 : Paramtres SNTP


Option
Dcalage horaire

Description

Valeur

Lheure est dfinie en fonction de la valeur UTC12:00 UTC+13:00 de temps universel coordonn (UTC Par dfaut : UTC (GMT) Universal Time Coordinated) slectionne. Permet de dfinir le dbut et la fin de lheure dt. Premier Cinquime ou Dernier, Dimanche Samedi, Janvier Dcembre, 0:00 23:00 Par dfaut : Dbute le deuxime dimanche de mars 2:00. Termine le deuxime dimanche de novembre 2:00. 1 heure 1 semaine Par dfaut : 1 semaine 0.0.0.0 255.255.255.255 Par dfaut : 0.0.0.0 0.0.0.0 255.255.255.255 Par dfaut : 0.0.0.0

Activer le rglage automatique de lheure dt

Priode de scrutation Contrle la frquence laquelle la passerelle EGX contacte le serveur NTP pour obtenir lheure correcte. Adresse IP du Adresse IP du serveur NTP primaire que serveur NTP primaire la passerelle EGX contacte pour obtenir lheure correcte. Adresse IP du serveur NTP secondaire Adresse IP du serveur NTP secondaire que la passerelle EGX contacte pour obtenir lheure correcte.

Paramtres SNMP

La passerelle EGX prend en charge le protocole SNMP qui permet un administrateur rseau daccder distance la passerelle EGX au moyen dun gestionnaire SNMP et dafficher le statut rseau et les diagnostics de la passerelle au format MIBII.
Action
1. Dans le menu Configuration, cliquez sur Paramtres SNMP. 2. Slectionnez loption Activer SNMP pour activer le protocole SNMP. 3. Saisissez le contact systme, le nom et lemplacement du systme, le nom de la communaut en lecture seule et le nom de la communaut en lecture/criture. 4. Cliquez sur Appliquer.

Rsultat
Ouvre la page Paramtres SNMP. Active le protocole SNMP. Saisit les informations SNMP du systme et les noms daccs des communauts.

Enregistre la configuration SNMP.

Figure 20 : Page Paramtres SNMP

26

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Filtrage Modbus TCP/IP

Cette fonction permet ladministrateur de dfinir le niveau daccs des clients Modbus TCP/IP aux appareils (locaux ou distants) connects la passerelle EGX. REMARQUE : Il existe une adresse anonyme Modbus TCP/IP (***.***.***.***) quil est possible de configurer en lecture seule ou sans droit daccs. La configuration en Lecture seule permet nimporte quel client Modbus TCP/IP ne figurant pas dans la liste filtre daccder en lecture seule aux appareils srie esclave. La configuration sans droit daccs (Aucun) bloque tous les clients Modbus TCP/IP qui ne figurent pas dans la liste filtre.
Action
1. Dans le menu Configuration, cliquez sur Filtrage Modbus TCP/IP. 2. Slectionnez loption Activer le filtrage. 3. Dans la colonne Adresse IP, saisissez ladresse client Modbus TCP/IP. 4. Dans la colonne Niveau daccs, slectionnez Lecture seule ou Complet.

Rsultat
Ouvre la page Filtrage Modbus TCP/IP. Active le filtrage. Saisit ladresse IP dun client Modbus TCP/IP qui accdera aux appareils srie connects la passerelle EGX. Slectionne le niveau daccs pour chaque adresse IP correspondante. En Lecture seule, les codes de fonctions Modbus TCP/IP suivants sont autoriss : Dcimal : 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100 Hexadcimal : 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18, 2B, 64 Ajoute dautres adresses IP filtrer. Enregistre la liste de filtrage des adresses Modbus TCP/IP.

5. Recommencez les tapes 3 et 4 pour ajouter dautres adresses IP. 6. Cliquez sur Appliquer.

Figure 21 : Page Filtrage Modbus TCP/IP

2009-2013 Schneider Electric. Tous droits rservs.

27

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Liens vers la documentation

La passerelle EGX prend en charge deux types de liens vers la documentation : 1. Accs aux fichiers locaux (documentation stocke en interne sur la passerelle EGX). 2. Accs des URL externes. REMARQUE : Les documents locaux que vous voulez faire apparatre sur la page Web Documentation doivent tre placs dans le dossier EGX www/documentation par FTP.
Action
1. Dans le menu Configuration, cliquez sur Liens vers la documentation.

Rsultat
Affiche la page Liens vers la documentation.

2. Pour laccs aux fichiers : slectionnez la Dfinit quels fichiers et URL apparaissent la case cocher Activ du ou des liens vers page Documentation. les noms de fichiers que vous voulez activer. Pour laccs aux URL : slectionnez la case cocher Activ du ou des liens URL que vous voulez activer. 3. Activez loption Nouvelle fentre si vous Dfinit quels fichiers et URL souvrent dans une voulez que les fichiers et URL slectionns nouvelle fentre lorsquils sont cliqus. souvrent dans une nouvelle fentre lorsque lutilisateur clique dessus. 4. Dfinit le titre du lien vers la documentation Dfinit le titre du lien vers la documentation qui dans la zone de texte Texte du lien. apparat sur la page Documentation. 5. Cliquez sur Appliquer. Met jour les paramtres des liens vers la documentation EGX.

Figure 22 : Page Liens vers la documentation

REMARQUE : Pour des informations sur la documentation charge, voir Documentation , page 51.

28

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Comptes utilisateur

Les utilisateurs de la passerelle EGX reoivent un nom dutilisateur et un mot de passe. Chaque utilisateur appartient un groupe et chaque groupe a des droits daccs aux pages Web EGX qui lui sont attribus par ladministrateur EGX. REMARQUE : Il existe deux comptes utilisateur par dfaut : Administrator (administrateur, mot de passe : Gateway) et Guest (invit, mot de passe : Guest).
Action
1. Dans le menu Configuration, cliquez sur Comptes utilisateur. 2. Si vous voulez modifier le nom dun groupe, tapez le nouveau nom dans lune des zones de texte de la zone Groupes (vous ne pouvez pas modifier le nom du groupe Administrator). 3. Dans la zone Utilisateurs, saisissez le nom (1 24 caractres) et le mot de passe (0 12 caractres) du nouvel utilisateur. REMARQUE : Les noms et les mots de passe des utilisateurs distinguent les majuscules et les minuscules ; ils peuvent contenir uniquement des caractres alphanumriques.

Rsultat
Ouvre la page Comptes utilisateur. Entrez le nom du nouveau groupe.

Dfinit le nom et le mot de passe dun utilisateur. LEGX300 indique par une couleur et une mention textuelle le niveau de scurit du mot de passe : Rouge = Mot de passe vide / Mot de passe faible Jaune = Mot de passe moyen Bleu = Mot de passe fort Vert = Mot de passe trs fort Slectionne le nom et la langue de lutilisateur. Ajoute dautres utilisateurs. Enregistre tous les paramtres dun compte utilisateur.

4. Slectionnez le groupe ainsi que la langue par dfaut du nouvel utilisateur. 5. Recommencez les oprations 3 et 4 pour chaque utilisateur que vous voulez ajouter. 6. Cliquez sur Appliquer.

Tableau 11 : Comptes et mots de passe EGX


Compte
Administrator Guest Comptes personnaliss (jusqu 11 comptes) Gateway Guest Aucune valeur par dfaut Le mot de passe personnalis est dfini par lutilisateur.

Mot de passe par dfaut

Figure 23 : Page Comptes utilisateur

2009-2013 Schneider Electric. Tous droits rservs.

29

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Accs aux pages Web


Action
1. Dans le menu Configuration, cliquez sur Accs aux pages Web. 2. Slectionnez le niveau daccs aux pages Web (Aucun, Lecture seule ou Complet) de chaque groupe dutilisateurs.

Rsultat
Ouvre la page Accs aux pages Web. Voir le Tableau 12 pour une explication des niveaux daccs de chaque groupe.

3. Pour autoriser le compte Guest accder la page Web, Permet au groupe par dfaut slectionnez Lecture seule sous la colonne Guest. Guest daccder la page Web. REMARQUE : Si le groupe Guest est en lecture seule, les autres groupes peuvent tre configurs uniquement en lecture seule ou en accs complet. 4. Recommencez les tapes 2 et 3 pour rgler les options de chaque section. 5. Cliquez sur Appliquer. Slectionne le niveau daccs chaque page Web. Enregistre la configuration des mots de passe.

Tableau 12 : Accs des groupes


Groupe
Administrator

Accs
Accs complet toutes les pages Web. REMARQUE : Il est recommand de changer le mot de passe par dfaut du compte Administrateur lors de la premire connexion. Accs en lecture seule aux pages Web slectionnes. En choisissant parmi les options ci-dessous, ladministrateur attribue des niveaux daccs aux pages Web pour chaque groupe. Les niveaux daccs sont les suivants : Aucun : le groupe ne peut pas accder la page Web slectionne. Lecture seule : le mot de passe autorise laccs en lecture seule du groupe la page Web slectionne. Complet : le groupe a le mme droit daccs que le groupe Administrator la page Web slectionne.

Guest Trois groupes personnaliss dfinis par lutilisateur

Figure 24 : Page Accs aux pages Web

30

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Ajout/Suppression de pages Web personnalises

Les pages Web personnalises et autres fichiers peuvent tre transfrs de votre ordinateur vers la passerelle EGX par FTP. Les fichiers placs via FTP dans les rpertoires www/monitoring (surveillance), www/maintenance ou www/control (commande), sils sont dots de lextension .htm, .html ou .shtml, sont automatiquement scuriss. La barre de menus de linterface Web comporte un lien vers chacun de ces dossiers. Lorsque vous cliquez sur lun de ces liens, les pages personnalises que vous ajoutez apparaissent dans le menu, dans la partie gauche de la fentre du navigateur, sous Pages personnalises. REMARQUE : Vous ne pouvez pas crer de nouveaux dossiers dans les dossiers prdfinis Monitoring, Control et Maintenance. Une fois les pages Web personnalises ou autres fichiers transfrs vers la passerelle EGX par FTP, il est possible de les ajouter ou de les retirer de linterface Web, sans avoir les supprimer de la passerelle EGX, par le biais de la page Ajouter/supprimer des pages Web. Cette page est accessible depuis la page Accs aux pages Web.

Ajout de pages Web personnalises par FTP


Action
1. Lancez lExplorateur Windows, tapez ftp:// suivi de ladresse IP de la passerelle EGX (ex. ftp://169.254.0.10) dans la barre dadresses, puis appuyez sur Entre. 2. Tapez le nom dutilisateur Administrator et le mot de passe correspondant dans les zones de texte appropries, puis cliquez sur Connexion.

Rsultat
Ouvre la bote de dialogue Connexion en tant que.

Ouvre une session FTP avec la passerelle EGX.

3. Ouvrez une autre fentre de lExplorateur Copie le fichier dans le Presse-papiers. Windows, localisez la page Web personnalise que vous souhaitez envoyer la passerelle EGX, cliquez dessus avec le bouton droit, puis choisissez Copier. 4. Revenez lExplorateur Windows de lEGX Ouvre le dossier dans lequel la page sera (fentre affiche ltape 1), puis ouvrez le stocke sur la passerelle EGX. dossier dans lequel la page doit tre copie ( /www/monitoring/ , par exemple). 5. Cliquez avec le bouton droit dans le volet Copie la page personnalise sur la passerelle droit de la fentre de lExplorateur Windows EGX. et cliquez sur Coller. REMARQUE : Au lieu de copier-coller le fichier, vous pouvez le faire glisser vers lExplorateur Windows. 6. Cliquez sur le bouton Fermer de la fentre Ferme la fentre de lExplorateur Windows. de lExplorateur Windows.

Suppression de pages Web personnalises par FTP

Action
1. Lancez lExplorateur Windows, tapez ftp:// suivi de ladresse IP de la passerelle EGX (ex. ftp://169.254.0.10) dans la barre dadresses, puis appuyez sur Entre. 2. Tapez le nom dutilisateur Administrator et le mot de passe correspondant dans les zones de texte appropries, puis cliquez sur Connexion.

Rsultat
Ouvre la bote de dialogue Connexion en tant que.

Ouvre une session FTP avec la passerelle EGX.

3. Ouvrez le dossier dans lequel la page Web Ouvre le dossier contenant la page Web est stocke, cliquez avec le bouton droit sur personnalise, puis supprime le fichier. le fichier supprimer, puis choisissez Supprimer. 4. Cliquez sur le bouton Fermer de la fentre Ferme la fentre de lExplorateur Windows. de lExplorateur Windows.

2009-2013 Schneider Electric. Tous droits rservs.

31

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Ajout/Suppression de pages Web personnalises laide de linterface Web

Action
1. Dans le menu Configuration, cliquez sur Accs aux pages Web.

Rsultat
Ouvre la page Accs aux pages Web.

2. Cliquez sur Ajouter/supprimer des pages Ouvre la page Ajouter/supprimer des pages Web (voir la Figure 25). Web. 3. Si vous avez ajout des pages Web Slectionne ou dslectionne une page Web personnalises aux dossiers EGX, la liste personnalise. de ces fichiers apparat sous chaque nom de dossier. Slectionnez les pages Web que vous souhaitez rendre disponibles pour les utilisateurs. Dslectionnez les pages qui ne doivent pas tre visibles. REMARQUE : Lorsque vous dslectionnez une page Web, elle nest pas supprime de la passerelle EGX. 4. Cliquez sur Appliquer. Ajoute ou supprime une page personnalise de linterface Web EGX.

Figure 25 : Page Ajouter/Supprimer des pages Web

32

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Prfrences

Cette option permet de personnaliser les passerelles EGX individuellement.


Action
1. Dans le menu Configuration, cliquez sur Prfrences.

Rsultat
Ouvre la page Prfrences.

2. Saisissez le nom de lquipement, la page Dfinit les prfrences. daccueil par dfaut, la frquence dchantillonnage en temps rel, ainsi que la frquence de vrification des communications. 3. Cliquez sur Appliquer. Met jour les paramtres de prfrences de la passerelle EGX.

Figure 26 : Page Prfrences

Tableau 13 : Paramtres de prfrences


Option
Nom de lquipement

Description

Valeur

Permet de personnaliser le nom de lEGX et Par dfaut : Powerlogic de lquipement associ. Ce nom sera EGX300 utilis dans la bannire de linterface Web. Permet de slectionner la page daccueil par dfaut. Accueil, Rcapitulatif circuit, Rsum du courant de charge, Rcapitulatif des val. moyennes du courant, Rcapitulatif puissance ou Rcapitulatif nergie. Par dfaut : Accueil

Page daccueil par dfaut

Frquence dchantillonnage en temps rel Frquence de vrification des communications

Dfinit la frquence de lecture des donnes 5 60 s du ou des appareils dans laffichage Par dfaut : 5 secondes standard des tableaux de surveillance. Dfinit la frquence laquelle les Dsactiv, 5 30 minutes communications sont vrifies lorsque le Par dfaut : 15 minutes navigateur affiche des mesures en temps rel dans laffichage standard des tableaux de surveillance. Cette fonction essaie de remettre automatiquement en service tout appareil hors service.

2009-2013 Schneider Electric. Tous droits rservs.

33

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Types dappareil affichables

La page Types dappareil affichables permet de grer les types dappareil slectionnables par lutilisateur dans la page Liste des appareils. tant donn le nombre de types dappareil pris en charge par la passerelle EGX300, le fait de supprimer certaines entres de la liste des types disponibles permet de simplifier la configuration dans la page Liste des appareils.
Action
1. Dans le menu Configuration, cliquez sur Types dappareil affichables. 2. Slectionnez les types dappareil qui doivent tre disponibles dans la liste de configuration. REMARQUE : Cliquez sur slectionner tout pour activer tous les appareils et sur effacer pour dsactiver tous les appareils. REMARQUE : Vous ne pouvez changer la disponibilit des types dappareil correspondant des appareils en cours dutilisation. 3. Cliquez sur Appliquer. Enregistre les paramtres de Types dappareil affichables.

Rsultat
Ouvre la page Types dappareil affichables. Permet de slectionner les types dappareil qui doivent tre disponibles dans la liste de configuration.

Figure 27 : Page Types dappareil affichables

Piste daudit

La piste daudit est une squence horodate denregistrements ou de messages. Elle consigne les changements de configuration, les erreurs et les checs dauthentification, et indique lutilisateur lorigine de chaque vnement. Utilisez la page Piste daudit pour configurer les groupes de rapports et canaux de messages. Pour chaque canal, vous choisissez le ou les groupes de rapports qui pourront afficher les messages. Lorsque vous slectionnez un groupe de rapports pour un canal, vous voyez safficher les messages gnrs dans ce groupe de rapports. Les canaux de messages sont les suivants :

Fichier journal de maintenance interne de lEGX Serveur Syslog distant (Syslog est un protocole pour les messages de journalisation) Courrier lectronique

Tous les messages sont horodats et identifient le groupe de rapports et lutilisateur.


34 2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

La page Piste daudit est divise en trois sections correspondant aux trois canaux de messages : Journal de maintenance, Syslog, Courrier lectronique. (Voir Figure 28, page 36.) Vous pouvez configurer sparment les messages envoys sur chaque canal. Dans la fentre Configuration, cliquez sur Piste daudit. La page Piste daudit saffiche. Suivez les instructions du tableau ci-dessous. Tableau 14 : Configuration de la piste daudit
Option
Journal de maintenance Contrle les types de Les messages gnrs apparaissent rapport pour lesquels dans le journal de maintenance vous souhaitez voir interne de lEGX. apparatre des messages dans le journal des messages. Syslog Adresse IP du serveur. Les messages gnrs sont rexpdis au serveur que vous spcifiez. Les messages Syslog seront envoys depuis ce port UDP du serveur. Les quatre types de rapport pour lesquels des messages peuvent tre rexpdis. Donne une indication approximative de lorigine du message au sein du systme. Cette information apparatra dans le journal Syslog. Indique lutilisateur limportance relative du message. Vous devez dterminer limportance de chaque type pour votre site. Entrez ladresse IP du serveur distant auquel vous souhaitez rexpdier les messages. Entrez le numro de port UDP pour cette adresse IP. Par dfaut = 514. Cochez les types de rapport pour lesquels vous souhaitez rexpdier des messages. Slectionnez la catgorie approprie. Cochez les options de rapport que vous souhaitez inclure. Par dfaut, aucune option nest coche.

Description

Valeur

Port UDP (User Datagram Protocol) du serveur Rapport

Liste droulante Installation

Liste droulante Gravit

Slectionnez la catgorie approprie.

Courrier lectronique De ladresse Ladresse lectronique de lexpditeur apparatra dans le champ De des messages gnrs. Le corps du message contiendra les informations suivantes : adresse IP de lEGX, nom du groupe de rapports, nom de lutilisateur, adresse IP de lutilisateur et message du groupe de rapports. Les messages gnrs seront envoys la ou aux adresses destinataires spcifies. Spcifiez ladresse de lexpditeur des courriers lectroniques dans le champ prvu cet effet. Maximum = 49 caractres.

Aux adresses

Adresse IP du serveur

Port TCP du serveur

Connexion au serveur SMTP via authentification

Nom dutilisateur

Mot de passe

Spcifiez ladresse de lexpditeur des courriers lectroniques dans le champ prvu cet effet. Maximum = 49 caractres par adresse. Adresse IP du serveur o les Si vous ne spcifiez pas courriers lectroniques seront ladresse IP du serveur, aucun envoys. courrier lectronique ne sera envoy. Numro de port TCP pour ladresse Saisissez le numro de port TCP. La valeur par dfaut est IP du serveur. 25. Cochez cette case pour activer la Cochez cette option pour connexion pour la rception des entrer les informations de courriers lectroniques. La connexion connexion. au serveur SMTP exige une authentification. Nom dutilisateur que lEGX utilisera Tapez le nom dutilisateur pour accder au serveur SMTP. exig par le serveur SMTP (maximum 31 caractres). Mot de passe que lEGX utilisera Tapez le mot de passe exig pour accder au serveur SMTP. par le serveur SMTP (maximum 31 caractres).

2009-2013 Schneider Electric. Tous droits rservs.

35

Passerelle Ethernet PowerLogicTM EGX300 Configuration

63230-319-216B4_FR 06/2013

Option
Rapport

Description
Types de rapport pour lesquels des messages peuvent tre rexpdis. Vous pouvez en cocher autant que vous le souhaitez. Cliquez sur Appliquer pour enregistrer vos slections. Cliquez sur Valeurs par dfaut pour rtablir la valeur initiale dun champ.

Valeur
Cochez les types de rapport pour lesquels vous souhaitez envoyer des messages. Cliquez sur Appliquer ou Valeurs par dfaut.

Valeurs par dfaut / Appliquer

Figure 28 : Configuration de la piste daudit

Point daccs systme

Le Point daccs systme sert dtecter et relier la passerelle les autres appareils Schneider Electric connects au rseau. Cette fonction est active par dfaut et ne ncessite pas dautre configuration. Utilisez cet cran de configuration pour entrer ladresse IP de groupe et dautres informations connexes.

Action
1. Dans le menu Configuration, cliquez sur Point daccs systme. 2. Activ

Rsultat
Affiche la fentre Point daccs systme. Lorsque cette option est coche, les passerelles EGX300 affectes la mme adresse IP pourront se dtecter entre elles. Valeur par dfaut = Activ. Entrez le numro (entre 1 et 65535) du port UDP utilis pour la dtection par Point daccs systme. Valeur par dfaut = 59.

3. Port UDP

36

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Configuration

Action
4. Adresse IP de groupe

Rsultat
Tapez ladresse IP du groupe. Il peut sagir dune adresse pour multidiffusion ou monodiffusion. Valeur par dfaut = 224.0.1.2. Intervalle entre deux messages Hello envoys par cette passerelle EGX300 pour annoncer sa prsence aux autres appareils Schneider Electric dtects par le Point daccs systme sur le rseau. Plage = 1-65535 secondes. Valeur par dfaut = 300 secondes. Dlai dattente maximum aprs le dernier message Hello envoy par cette EGX300 avant que les autres appareils ne la considrent comme indisponible. Plage = 2-65535 secondes. Valeur par dfaut = 600 secondes. Vous pouvez spcifier la portion du rseau sur laquelle portera la dtection des autres appareils. Cette valeur est dtermine par le nombre de fois que la multidiffusion peut tre rexpdie aux autres appareils. Plage = 1-255 sauts de routeur. Valeur par dfaut = 1. Les passerelles EGX300 dun groupe peuvent tre rparties en communauts. Les passerelles EGX300 affectes la mme adresse IP et au mme numro de communaut pourront se dtecter entre elles. Si vous rglez le numro de communaut sur 0, la passerelle pourra dtecter toutes les autres passerelles EGX300 ayant la mme adresse IP, quel que soit le paramtre de communaut. Valeur par dfaut = 0.

5. Intervalle Hello

6. Temps de retenue

7. Dure de vie pour multidiffusion

8. Communaut

9. Valeurs par dfaut / Appliquer

Cliquez sur Appliquer pour enregistrer vos slections. Cliquez sur Valeurs par dfaut pour rtablir les valeurs initiales.

Figure 29 : Page de configuration du Point daccs systme

2009-2013 Schneider Electric. Tous droits rservs.

37

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

63230-319-216B4_FR 06/2013

SURVEILLANCE
Donnes en temps rel
Pages dappareil unique

La passerelle EGX permet dafficher des donnes et tendances en temps rel ainsi que des tendances historiques. Les pages de donnes en temps rel affichent les mesures de base des appareils slectionns en temps rel ainsi que les rsums des appareils. Pour afficher les donnes en temps rel dans un tableau, accdez au menu Surveillance et slectionnez un appareil sous Donnes en temps rel > Pages dappareil unique.

Paramtres des mesures de base


Action
1. En haut de lcran, slectionnez Courant de charge, Puissance, Tension L-L ou Tension L-N pour afficher la grandeur en question sur le graphique cadran analogique.

Rsultat
Permet de slectionner les grandeurs afficher sur le graphique cadran analogique. REMARQUE : Les cadrans analogiques ne sont pas disponibles pour tous les types dappareil.

2. Par dfaut, les cadrans ajustent automatiquement la Permet de contrler la plage affiche plage affiche. Pour utiliser une plage fixe, par les cadrans analogiques. slectionnez Plage. Le tableau ci-dessous explique comment configurer la plage des cadrans analogiques. 3. Cliquez sur Appliquer. Met jour la slection des cadrans pour la page de lappareil.

Figure 30 : Page Mesures de base

38

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

Plage des cadrans analogiques

La plage affiche sur les cadrans analogiques de la page Mesures de base peut tre configure ou mise lchelle automatiquement (voir Figure 31).
Action
1. Sous Activer la mise lchelle automatique , cochez les appareils dont les cadrans doivent tre rgls automatiquement. REMARQUE : Cliquez sur slectionner tout pour activer la mise lchelle automatique pour tous les appareils et sur effacer pour la dsactiver pour tous les appareils. 2. Pour les appareils sans mise lchelle automatique, entrez les limites Min et Max de chaque type de cadran. 3. Cliquez sur Appliquer. Spcifie la plage du cadran. Met jour les paramtres Mise lchelle automatique.

Rsultat
Active la mise lchelle automatique pour les appareils slectionns.

Figure 31 : Page de configuration de plage

Pages rcapitulatives appareils

Les vues Pages rcapitulatives appareils affichent des tableaux rcapitulatifs concernant un appareil ou une slection dappareils.
Action
1. Dans le menu Surveillance, cliquez sur Pages rcapitulatives appareils. 2. Slectionnez la page de rcapitulatif afficher.

Rsultat
Dveloppe larborescence permettant de slectionner les pages de rcapitulatif. Ouvre la liste de slection dappareil.

3. Slectionnez un ou plusieurs appareils dans la liste Slectionne un ou plusieurs appareils des appareils disponibles, puis cliquez sur Suivant en vue de laffichage des rcapitulatifs. (voir la Figure 32). REMARQUE : Cliquez sur >> pour slectionner tous les appareils disponibles.

Figure 32 : Page Slection des appareils

2009-2013 Schneider Electric. Tous droits rservs.

39

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

63230-319-216B4_FR 06/2013

Figure 33 : Page Rcapitulatif circuit

Calcul de tendance

Pour afficher une tendance en temps rel pour plusieurs appareils et plusieurs grandeurs, allez dans le menu Surveillance et slectionnez Donnes en temps rel > Calcul de tendance.
Action
1. Dans le menu Surveillance, slectionnez Donnes en temps rel. 2. Slectionnez Calcul de tendance.

Rsultat
Dveloppe larborescence des options de donnes en temps rel. Dveloppe larborescence des options de tendance en temps rel. Ouvre la page de configuration Calcul de tendance en temps rel. Permet de slectionner les appareils pour le calcul de tendance. Permet de slectionner les grandeurs pour le calcul de tendance.

3. Slectionnez Calcul de tendance en temps rel.

4. Slectionnez jusqu quatre appareils dans la liste Appareils disponibles. 5. Slectionnez une ou plusieurs grandeurs dans la liste des grandeurs disponibles. REMARQUE : Seules les grandeurs communes tous les appareils slectionns sont disponibles pour le calcul de tendance. Le nombre maximum de grandeurs prendre en compte dpend du nombre dappareils slectionns. Le produit des appareils et grandeurs slectionns doit tre gal ou infrieur 8. 6. Cliquez sur Suivant pour ouvrir la page daffichage Calcul de tendance en temps rel.

La page daffichage Calcul de tendance en temps rel souvre.

7. Pour configurer les paramtres de tendance, poursuivez Permet de dfinir les paramtres la procdure du tableau suivant en vous reportant la de calcul de tendance. Figure 35, page 41.

Figure 34 : Slectionner les appareils et les grandeurs

40

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

Action
1. Slectionnez le type de tendance : Absolue ou Relative. REMARQUE : En mode Absolue, laxe des abscisses est gnr nouveau aprs chaque chantillon et comporte toutes les donnes recueillies depuis le dbut de la tendance. En mode Relative, le graphique est mis jour avec les donnes les plus rcentes aprs chaque chantillon tandis que laxe des abscisses reste constant et affiche toute la priode de tendance slectionne.

Rsultat
Permet de slectionner le mode du graphique.

2. Slectionnez la dure de la tendance, de 1 15 minutes. Il Permet de slectionner la sagit de la dure de la tendance. priode considre pour le calcul de tendance. REMARQUE : Les donnes sont chantillonnes aussi vite que possible mais la vitesse de transmission dpend de la charge de communication sur le sous-rseau srie et/ou sur les appareils distants. 3. Slectionnez Commencer lchantillonnage pour lancer Permet de lancer le calcul de le calcul de tendance sur les grandeurs et appareils tendance. slectionns. REMARQUE : Pour arrter le calcul de tendance avant la fin de la priode, cliquez sur Arrter lchantillonnage. Si vous arrtez lopration puis cliquez nouveau sur Commencer lchantillonnage, un nouveau calcul de tendance commence. 4. Cliquez sur Accs aux donnes pour afficher le journal de toutes les grandeurs chantillonnes enregistres au cours du calcul de tendance. REMARQUE : Aprs chaque intervalle, la valeur actuelle de chaque grandeur ainsi que les valeurs Min, Max et Moyenne calcules sont insres dans le tableau sous le graphique. 5. Cliquez sur Nouvelle(s) grandeur(s) pour slectionner dautres appareils et grandeurs pour le calcul de tendance. Permet dafficher le journal de toutes les valeurs chantillonnes au cours du calcul de tendance.

Rouvre la page de configuration Calcul de tendance en temps rel.

Figure 35 : Calcul de tendance en temps rel

Journaux dappareil

Les pages Journaux dappareil fournissent des reprsentations graphiques et tabulaires des donnes enregistres pour lappareil slectionn. Pour plus de dtails sur la configuration de lenregistrement des journaux dappareil, voir Journaux dappareil , page 17.

2009-2013 Schneider Electric. Tous droits rservs.

41

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

63230-319-216B4_FR 06/2013

Pages dappareil unique

Les Pages dappareil unique fournissent des reprsentations graphiques et tabulaires des donnes enregistres pour un seul appareil.
Action
1. Dans le menu Surveillance, cliquez sur Journaux dappareil. 2. Sous Journaux dappareil, cliquez sur Pages dappareil unique. 3. Slectionnez un appareil dans la liste Journaux dappareil. 4. Slectionnez la plage de donnes afficher dans la liste droulante. 5. Maintenez le bouton gauche de la souris enfonc et tracez une zone de slection sur la partie du graphique agrandir. 6. Pour revenir laffichage dorigine, appuyez sur la touche Z du clavier ou double-cliquez sur le graphique. 7. Cliquez sur Accs aux donnes pour afficher le journal de donnes dintervalle slectionn (voir la Figure 37 ci-dessous).

Rsultat
Dveloppe larborescence des options Journaux dappareil disponibles. Dveloppe larborescence pour afficher les appareils dont les journaux de donnes peuvent tre consults. Affiche le journal de lappareil slectionn. Permet de slectionner la plage de donnes tracer. Agrandit la partie du graphique slectionne.

Laffichage rtrcit.

Ouvre le tableau du Journal de donnes dintervalle slectionn.

8. Pour afficher dautres grandeurs, cliquez Permet dafficher les grandeurs slectionnes. sur Nouvelle(s) grandeur(s). Cochez les valeurs afficher puis cliquez sur le bouton Appliquer.

Les donnes enregistres pour chaque appareil saffichent dans une page Web sous forme dun graphique temporel. Ce graphique est prconfigur pour afficher les donnes de la dernire journe complte, de la dernire semaine complte, du dernier mois complet ou toutes les donnes. Les paramtres dnergie sont enregistrs comme valeurs cumules mais affichs sous forme de valeurs incrmentales par intervalle. Tous les autres paramtres sont enregistrs et affichs comme la valeur relle enregistre. Figure 36 : Graphique du journal de donnes dintervalle

Figure 37 : Tableau des accs aux donnes du journal dintervalle

42

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

Obtention dun journal de donnes

Vous pouvez rcuprer un journal de donnes dintervalle laide des mthodes indiques dans le Tableau 15 : Tableau 15 : Mthodes de rcupration des journaux de donnes par intervalle Formats des fichiers
Mthode de rcupration
FTP Bouton Accs aux donnes Requte Web Microsoft Courrier lectronique HTTP HTML HTML CSV CSV

Format du fichier rcupr


CSV (valeurs spares par des virgules)

Pour afficher la liste des journaux disponibles, effectuez la procdure dcrite aux tapes 2 4 de la section Obtention dun journal de donnes dintervalle via FTP , page 44. Les fichiers seront dnomms ainsi : Nom dappareil_Identification locale.csv o Nom dappareil correspond au nom donn lappareil esclave et Identification locale lidentification numrique locale qui lui est attribue. Par exemple, un appareil appel Arrive services Btiment et dot de lidentification locale 3 donnera le fichier Arrive services Btiment_3.csv . En cas dexportation des journaux de donnes, la date et lheure sont ajoutes au nom du fichier sous la forme : _AAAAMMJJHHMMSS Par exemple : Arrive services Btiment 1_3_20100218115216.csv . Ce nom indique que le fichier a t export le 18 fvrier 2010 11:52:16. Format des journaux Les donnes sont enregistres au format suivant (voir Figure 38, page 44) : Tableau 16 : Format des journaux de donnes dintervalle
Ligne
1

Donnes au format CSV


(BOM)Nom passerelle,N srie passerelle,Adresse passerelle,Nom appareil,ID appareil local,Nom type appareil,Intervalle enregistrement REMARQUE : (BOM) Les trois premiers octets du fichier forment une marque dordre des octets (Byte Order Mark) dnotant le format UTF-8. EGX300SD,23227,157.198.184.116, Arrive services Btiment 1,3, CM4000,15 Cette ligne est vide. ,,,Identification grandeur 1,Identification grandeur 2,Identification grandeur 3

Description
Cette ligne contient les en-ttes de colonne des informations affiches la ligne 2.

Cette ligne contient les informations relatives la passerelle EGX et lappareil enregistr. Cette ligne contient les en-ttes de colonne des identifications de grandeurs affiches la ligne 5. Lidentification dune grandeur est une rfrence numrique la grandeur sur laquelle porte lenregistrement. Le nom attribu une grandeur peut diffrer selon les appareils et la langue. Les identifications de grandeurs permettent didentifier les grandeurs, indpendamment de lappareil ou de la langue. Les trois premires virgules servent la mise en page dans un tableur. Cette ligne contient les identifications de grandeurs des valeurs consignes. Cette ligne contient les en-ttes de colonne des donnes enregistres prsentes ligne 8 et suivantes.

3 4

5 6 7

,,,1617,1621,1625 Cette ligne est vide. Erreur,Dcalage par rapport temps universel UTC (minutes),Horodatage local,nergie apparente (kVAh),nergie active (kWh),nergie ractive (kVArh)

partir Ces lignes contiennent les donnes enregistres. de la ligne 8 0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15 0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15 0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

Si vous affichez le fichier CSV dans un tableur, la prsentation des donnes devrait ressembler celle de la Figure 38, page 44.
2009-2013 Schneider Electric. Tous droits rservs. 43

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

63230-319-216B4_FR 06/2013

Figure 38 : Journal de donnes dintervalle ouvert dans un tableur

Codes derreur des journaux de donnes

Les codes derreur ci-dessous peuvent apparatre lorsque vous diagnostiquez les journaux de donnes (voir Figure 36, page 42 et Figure 37, page 42) :
Code derreur
19

Dfinition
Erreur de communication (par exemple : CRC [contrle par redondance cyclique], protocole ou exception).

Rsultat
Lenregistrement reste activ moins que le dernier intervalle ait t manqu.

25

Expiration du dlai dattente en cas de non-rponse Lenregistrement reste activ une requte dans le temps imparti. moins que le dernier intervalle nait t manqu. Donnes incorrectes. Expiration de la priode de scrutation avant que les donnes puissent tre enregistres. Intervalle manqu.

38 100

Contactez le support technique pour obtenir de laide dans la rsolution de ces problmes ou dautres erreurs.

Obtention dun journal de donnes dintervalle via FTP

Vous pouvez utiliser le protocole FTP pour rcuprer un journal de donnes en vous connectant la passerelle EGX par FTP et en transfrant le fichier CSV suivant les instructions ci-aprs. REMARQUE : Si vous souhaitez que la passerelle EGX envoie automatiquement le journal de donnes par FTP, les options dexportation du journal de lappareil doivent tre configures pour FTP (voir Exportation par FTP , page 21).
Action
1. Crez un dossier sur votre ordinateur, par exemple c:\journaux_egx.

Rsultat
Cre un dossier pour conserver les journaux de donnes de la passerelle EGX.

2. Lancez lExplorateur Windows, tapez ftp:// Ouvre la bote de dialogue Connexion en tant et ladresse IP de la passerelle EGX dans la que. barre dadresses (ex. : ftp://169.254.0.10), puis appuyez sur Entre. 3. Tapez le nom dutilisateur Administrator et Ouvre une session FTP avec la passerelle le mot de passe correspondant dans les EGX et affiche les fichiers enregistrs dans la zones de texte appropries, puis cliquez sur passerelle. Connexion. 4. Ouvrez le rpertoire /logging/data de la passerelle EGX. Ouvre le rpertoire des journaux de donnes sur la passerelle EGX.

5. Copiez le journal et collez-le dans le dossier Copie le journal dans votre dossier. cr ltape 1.

44

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

Obtention dun journal de donnes dintervalle par le biais du bouton Accs aux donnes

Action
1. Dans la page Web Journaux dappareil (voir la Figure 36, page 42), cliquez sur bouton Accs aux donnes. 2. Appuyez sur CTRL+A, puis sur CTRL+C. 3. Ouvrez Excel et appuyez sur CTRL+V.

Rsultat
Une nouvelle fentre affiche les donnes enregistres. Slectionne toutes les donnes, puis les copie dans le Presse-papiers. Colle les donnes dans une feuille de calcul Excel.

Obtention dun journal de donnes dintervalle par le biais dune requte Web Microsoft

Action
1. Lancez votre navigateur Web.

Rsultat
Ouvre le navigateur Web.

2. Vrifiez que le journal est disponible en Ouvre la page des journaux de donnes. tapant ladresse IP de la passerelle EGX300 suivie de /stream/devlog_data.html?device=x (o x correspond lidentification locale de lappareil). 3. Lancez Excel et cliquez sur Donnes > Donnes externes > Nouvelle requte sur le Web. REMARQUE : Le chemin daccs indiqu correspond Microsoft Excel 2003. 4. Dans la bote de dialogue Nouvelle requte sur le Web, tapez ladresse du journal que vous avez saisie ltape 2, puis validez. Ouvre la bote de dialogue Nouvelle requte sur le Web de Microsoft Excel.

Ouvre le journal des donnes.

5. Cliquez sur la flche la plus lextrieur Slectionne les donnes, puis ouvre la bote de pour slectionner toutes les donnes, puis dialogue Importer des donnes. cliquez sur le bouton Importer. 6. Cliquez sur OK. Importe les donnes.

REMARQUE : Si vous voulez afficher les donnes les plus rcentes chaque fois que vous ouvrez la feuille de calcul, cliquez sur le bouton Proprits dans la bote de dialogue Importer des donnes, puis slectionnez Actualiser louverture du fichier .

Obtention dun journal de donnes dintervalle par courrier lectronique

La passerelle EGX doit tre configure de manire envoyer des journaux une adresse lectronique. Pour plus dinformations, voir Exportation par courrier lectronique , page 19.

Obtention dun journal de donnes dintervalle par HTTP

La passerelle EGX doit tre configure de manire envoyer des journaux un serveur Web. Pour plus dinformations, voir Exportation par HTTP , page 22.

2009-2013 Schneider Electric. Tous droits rservs.

45

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

63230-319-216B4_FR 06/2013

Pages rcapitulatives appareils

Les vues Pages rcapitulatives appareils affichent des rcapitulatifs concernant un appareil ou une slection dappareils.
Action
1. Dans le menu Surveillance, cliquez sur Journaux dappareil. 2. Sous Journaux dappareil, cliquez sur Pages rcapitulatives appareils. 3. Sous Pages rcapitulatives appareils, cliquez sur Plusieurs appareils, une seule grandeur. 4. Slectionnez un appareil dans la liste Appareils disponibles. REMARQUE : Vous pouvez slectionner jusqu 4 appareils. 5. Slectionnez une grandeur dans la liste Grandeurs disponibles. REMARQUE : Seules les grandeurs communes tous les appareils slectionns sont disponibles. 6. Slectionnez Suivant. 7. Maintenez le bouton gauche de la souris enfonc et tracez une zone de slection sur la partie du graphique agrandir. 8. Pour revenir laffichage dorigine, appuyez sur la touche Z du clavier ou double-cliquez sur le graphique. Ouvre la page de calcul de tendance Plusieurs appareils, une seule grandeur. Agrandit la partie du graphique slectionne. Permet de slectionner la grandeur afficher pour chaque priphrique slectionn. Ouvre la page de configuration Plusieurs appareils, une seule grandeur. Permet de slectionner les appareils pour les options de rcapitulatif.

Rsultat
Dveloppe larborescence des options Journaux dappareil disponibles.

Laffichage rtrcit.

La grandeur enregistre pour les appareils slectionns saffiche dans une page Web sous forme de graphique temporel. Ce graphique est prconfigur pour afficher les donnes de la dernire journe complte, de la dernire semaine complte, du dernier mois complet ou toutes les donnes. Les paramtres dnergie sont affichs sous forme de valeurs incrmentales par intervalle. Tous les autres paramtres sont enregistrs et affichs comme la valeur relle enregistre.

Figure 39 : Page de configuration Plusieurs appareils, une seule grandeur

46

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

Figure 40 : Page de calcul de tendance Plusieurs appareils, une seule grandeur

Tableaux de bord

La passerelle EGX prend en charge quatre catgories de tableau de bord affichant des informations de consommation dnergie agrges sur la priode. Le Tableau 17 liste les tableaux de bord disponibles et leurs sousensembles. Tableau 17 : Types de tableau de bord
Tableau de bord Par heure Sous-ensemble Jour prcdent, par heure Jour courant, par heure Jour courant sur jour prcdent, par heure Par jour Semaine prcdente, par jour Semaine courante, par jour Semaine courante sur semaine prcdente, par jour Mois prcdent, par jour Mois courant, par jour Mois courant sur mois prcdent, par jour Par semaine Trimestre prcdent, par semaine Trimestre courant, par semaine Trimestre courant sur trimestre prcdent, par semaine 13 dernires semaines, par semaine Par mois Anne prcdente, par mois Anne courante, par mois Anne courante sur anne prcdente, par mois REMARQUE : Le fichier journal de chaque appareil doit pouvoir contenir deux ans de donnes historiques. Voir Enregistrement des donnes par intervalle , page 17 pour plus dinformations. 12 derniers mois, par mois

2009-2013 Schneider Electric. Tous droits rservs.

47

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

63230-319-216B4_FR 06/2013

Affichage dun tableau de bord


Action
1. Depuis le menu Surveillance, cliquez sur Tableaux de bord. 2. Slectionnez un appareil dans la liste droulante Appareil. REMARQUE : Chaque tableau de bord affiche les donnes dun mme appareil. 3. Slectionnez une grandeur dans la liste droulante Nom de grandeur. REMARQUE : Seules les grandeurs de consommation incrmentales fournies par lappareil sont concernes ici. 4. Slectionnez les paramtres temporels dans la liste droulante Heure. 5. Cliquez sur Appliquer. Slectionne la priode de donnes enregistres pour la grandeur slectionne. Ouvre le tableau de bord slectionn. Slectionne les grandeurs tracer.

Rsultat
Affiche le menu de tableau de bord (voir Figure 41). Slectionne le priphrique dont les donnes seront affiches.

Figure 41 : Menu de tableau de bord

Les donnes de chaque tableau de bord saffichent sur une page Web sous la forme dun graphique barres. Lorsque vous survolez lune des barres du graphique avec la souris, la valeur du point de donnes saffiche pour lintervalle slectionn (Figure 42). Figure 42 : Graphique de tableau de bord

Figure 43 : Tableau de tableau de bord

48

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

Accs aux donnes de tableau de bord par le biais du bouton Accs aux donnes

Procdez comme suit pour exporter les donnes dun tableau de bord sous la forme dune feuille de calcul.
Action Rsultat

1. Depuis le tableau de bord contenant les Affiche les points de donnes pour le tableau donnes, cliquez sur Accs aux donnes. de bord slectionn (Figure 43, page 48). 2. Appuyez sur CTRL+A, puis sur CTRL+C. 3. Ouvrez Excel et appuyez sur CTRL+V. Slectionne toutes les donnes, puis les copie dans le Presse-papiers. Colle les donnes dans une feuille de calcul Excel.

Enregistrement dun lien de tableau de bord

Si vous souhaitez viter de passer par le menu principal chaque fois que vous accdez un tableau de bord, vous pouvez enregistrer un lien vers le tableau de bord selon lune des mthodes dcrites dans le Tableau 18. Tableau 18 : Enregistrement dun lien de tableau de bord
Option Favori de navigateur Description Valeur Permet aux utilisateurs daccder Suivez les instructions pour au tableau de bord enregistr sur crer un favori dans le lordinateur sur lequel le favori a t navigateur de votre choix. cr. Permet tous les utilisateurs EGX daccder un tableau de bord enregistr depuis la page Documentation. Permet aux utilisateurs denvoyer lURL dun tableau de bord dans le corps dun message lectronique. Voir Liens vers la documentation , page 28 pour configurer laccs par URL. Chaque destinataire du message lectronique doit disposer dun compte utilisateur EGX pour afficher le tableau de bord. Voir Comptes utilisateur , page 29.

Lien vers la documentation

Courrier lectronique

Enregistrement dun tableau de bord sous forme dimage

La procdure suivante permet denregistrer un graphique de tableau de bord sous forme dimage.
Action
1. Suivez les tapes de la section Affichage dun tableau de bord, page 48. 2. Cliquez sur Afficher sous forme dimage en haut droite de la page (Figure 44, page 50). 3. Cliquez avec le bouton sur limage et choisissez Enregistrer limage sous.

Rsultat
Affiche le graphique de tableau de bord. Affiche le tableau de bord sous forme dimage dans une nouvelle fentre. Ouvre la bote de dialogue Enregistrer sous.

4. Saisissez le nom du fichier, slectionnez un Enregistre limage. emplacement pour lenregistrer, puis cliquez sur Enregistrer. REMARQUE : Le type de fichier par dfaut est le format dimage PNG. Pour changer le type de fichier, remplacez .png par lextension voulue dans le champ Nom de fichier.

REMARQUE : Cette fonction nest pas disponible avec Internet Explorer version 8 ou antrieure.

2009-2013 Schneider Electric. Tous droits rservs.

49

Passerelle Ethernet PowerLogicTM EGX300 Surveillance

63230-319-216B4_FR 06/2013

Figure 44 : Enregistrement dune image de tableau de bord

Point daccs systme

LEGX peut dtecter et fournir des liens vers les passerelles EGX300 et autres appareils Schneider Electric connects au rseau. Le Point daccs systme ainsi cr permet daccder aux appareils Schneider Electric mis en rseau. La page Point daccs systme fournit un hyperlien vers chaque appareil Schneider Electric dtect. Lorsque vous survolez un hyperlien avec la souris, des informations supplmentaires sur lappareil saffichent gauche de la liste. Cliquez sur un appareil pour afficher la page de connexion cet appareil.

Figure 45 : Page Point daccs systme, avec dtails de lappareil

50

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Documentation

DOCUMENTATION

La page Documentation permet daccder aux informations qui ont t stockes sous forme de fichiers sur la passerelle EGX et de liens Web. Pour des informations sur le chargement de liens vers la documentation, voir Liens vers la documentation , page 28. Pour ouvrir un lment de documentation, cliquez sur le lien Documentation en haut de la page puis slectionnez le lien qui vous intresse.

Figure 46 : Page Documentation

COMMANDE

La passerelle EGX peut excuter manuellement une ou plusieurs commandes de rinitialisation prdfinies pour chaque type dappareil.
Action
1. Depuis le menu Commande, cliquez sur Rinitialisations. 2. Slectionnez lappareil afficher ou rinitialiser dans la liste Rinitialisations. 3. Slectionnez les paramtres de lappareil que vous voulez rinitialiser. 4. Cliquez sur Rinitialiser.

Rsultat
Ouvre la page Rinitialisations. Slectionne lappareil et affiche les options de rinitialisation correspondantes, avec la date et lheure de la dernire rinitialisation. Slectionne la rinitialisation effectuer sur lappareil slectionn. Envoie lappareil slectionn une ou plusieurs commandes de rinitialisation pour la ou les oprations souhaites et en affiche ltat.

Figure 47 : Rinitialisations

REMARQUE : Le paramtre Date/Heure indique la date et lheure actuelles de lappareil slectionn. Si vous choisissez de rinitialiser ce paramtre, la date et lheure de la passerelle EGX seront envoyes lappareil. Les valeurs de date et dheure ne sont rapportes que si lappareil offre cette fonction. Par exemple, si le priphrique ne prend pas en charge la valeur Min/Max pour Date/heure de la dernire rinitialisation , la valeur Min/Max napparat pas ici.

2009-2013 Schneider Electric. Tous droits rservs.

51

Passerelle Ethernet PowerLogicTM EGX300 Diagnostics

63230-319-216B4_FR 06/2013

DIAGNOSTICS

Pour accder aux liens de la page Web Diagnostics, cliquez sur Diagnostics dans la barre de menus EGX.

Statistiques

Cette page affiche les mesures cumules depuis la dernire activation de la passerelle EGX. En cas de perte de lalimentation de la passerelle EGX, de rinitialisation de lappareil suite une modification de la configuration ou autre vnement, toutes les valeurs cumules sont remises zro.
Action
1. Dans le menu Diagnostics, cliquez sur Statistiques. 2. Affichez les donnes. 3. Cliquez sur Rinitialiser.

Rsultat
Ouvre la page Statistiques (voir Figure 48 cidessous). Voir Interprtation des statistiques , page 53 ci-dessous. Remet zro les donnes de diagnostic de la passerelle EGX.

Figure 48 : Page Statistiques

52

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Diagnostics

Interprtation des statistiques


Statistiques
Ethernet tat de liaison Chane de caractres qui reprsente la vitesse de transmission et le paramtre duplex utiliss pour communiquer avec un autre appareil. Compteur qui augmente dune unit chaque fois quune trame est envoye sans problme. Compteur qui augmente dune unit chaque fois quune trame est retransmise cause de la dtection dune collision. Compteur qui augmente dune unit chaque fois quil est impossible denvoyer une trame car le nombre maximal de collisions bas sur lalgorithme de repli exponentiel binaire par troncature est atteint. Compteur qui augmente dune unit chaque fois quune trame est reue sans problme. Compteur qui augmente dune unit chaque rception dune trame dont la somme de contrle / CRC (contrle par redondance cyclique) ne correspond pas la valeur calcule. Compteur qui augmente dune unit chaque rception dune trame dont la somme de contrle / CRC (contrle par redondance cyclique) est errone et qui ne se termine pas sur une limite sur 8 bits. Compteur qui augmente dune unit chaque rception dune trame suprieure la taille maximale autorise dfinie dans les normes (trames suprieures 1518 octets). Compteur qui augmente dune unit chaque rception dune trame infrieure la taille minimale autorise dfinie dans les normes (trames infrieures 64 octets).

Description

Trames transmises avec succs Collisions

Excs de collisions

Trames reues avec succs Erreurs CRC

Erreurs dalignement

Longueur de trame excessive

Longueur de trame insuffisante

Modbus TCP/IP Serveur Trames envoyes Trames reues Erreurs de protocole Connexions actives1 Compteur qui augmente dune unit chaque envoi dune trame. Compteur qui augmente dune unit chaque rception dune trame. Compteur qui augmente dune unit chaque rception dun message de format incorrect. Valeur qui indique le nombre de connexions actives lors de la mise jour de la page de diagnostics. Prise en charge de 64 connexions maximum. Cliquez sur Connexions actives pour ouvrir une nouvelle fentre qui affiche la liste de toutes les connexions client actives. Compteur qui augmente dune unit chaque connexion tablie avec la passerelle EGX. Valeur qui indique le nombre maximal de connexions qui taient actives un instant donn. Compteur qui augmente dune unit chaque rception dun message de demande de lecture. Compteur qui augmente dune unit chaque rception dun message de demande dcriture. Compteur qui augmente dune unit chaque envoi dun message de rponse. Compteur qui augmente dune unit chaque envoi dune trame. Compteur qui augmente dune unit chaque rception dune trame. Compteur qui augmente dune unit chaque rception dun message de format incorrect.

Connexions cumules Nombre maximal de connexions Messages de lecture en arrive Messages dcriture en arrive Messages de rponse en partance Client Trames envoyes Trames reues Erreurs de protocole
1

Cliquez sur le lien pour plus dinformations.

2009-2013 Schneider Electric. Tous droits rservs.

53

Passerelle Ethernet PowerLogicTM EGX300 Diagnostics

63230-319-216B4_FR 06/2013

Statistiques
Dlais dattente

Description
Compteur qui augmente dune unit chaque fois quun message ne reoit aucune rponse dans le temps imparti. Il sagit en gnral de la consquence derreurs de configuration ou dun appareil dfaillant. Compteur qui augmente dune unit chaque fois que la connexion a t perdue. Compteur qui augmente dune unit chaque rception dune exception. Compteur qui augmente dune unit chaque envoi dun message de demande de lecture. Compteur qui augmente dune unit chaque envoi dun message de demande dcriture. Compteur qui augmente dune unit chaque rception dun message de rponse. Tableau dtaill prsentant des statistiques srie et distantes par appareil.

Dlai dattente connexion Exceptions reues Messages de lecture en partance Messages dcriture en partance Messages de rponse en arrive Dtails1 Port srie Trames envoyes Trames reues Erreurs CRC

Compteur qui augmente dune unit chaque envoi dune trame. Compteur qui augmente dune unit chaque rception dune trame. Compteur qui augmente dune unit chaque rception dun message dont le contrle par redondance cyclique (CRC) ne correspond pas la valeur calcule. Indique gnralement des problmes de cblage. Compteur qui augmente dune unit chaque rception dun message de format incorrect. Compteur qui augmente dune unit chaque fois quun message ne reoit aucune rponse dans le temps imparti. Il sagit en gnral de la consquence derreurs de configuration ou dun appareil dfaillant. Compteur qui augmente dune unit chaque rception dune exception. Compteur qui augmente dune unit chaque envoi dun message de demande de lecture. Compteur qui augmente dune unit chaque envoi dun message de demande dcriture. Compteur qui augmente dune unit chaque rception dun message de demande de lecture. Compteur qui augmente dune unit chaque rception dun message de demande dcriture. Tableau dtaill prsentant des statistiques srie et distantes par appareil.

Erreurs de protocole Dlais dattente

Exceptions reues Messages de lecture en partance Messages dcriture en partance Messages de lecture en arrive Messages dcriture en arrive Dtails1 Serveur HTTP Trames envoyes Trames reues Connexions actives1

Compteur qui augmente dune unit chaque envoi dune trame. Compteur qui augmente dune unit chaque rception dune trame. Valeur qui indique le nombre de connexions actives lors de la mise jour de la page de diagnostics. Prise en charge de 20 connexions maximum. Cliquez sur Connexions actives pour ouvrir une nouvelle fentre qui affiche la liste de toutes les connexions client actives. Compteur qui augmente dune unit chaque connexion tablie avec la passerelle EGX. Valeur qui indique le nombre maximal de connexions qui taient actives un instant donn.

Connexions cumules1 Nombre maximal de connexions


1Cliquez

sur le lien pour plus dinformations.

54

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Diagnostics

Statistiques
Informations sur la passerelle Version du logiciel embarqu Dlai dinactivit du systme Adresse MAC Numro de srie Numro de modle Version de matriel Date de fabrication Client HTTP Envoi : OK Erreur de connexion

Description

Version du logiciel embarqu install sur la passerelle EGX. Priode moyenne dinactivit du processeur exprime en pourcentage (0 100 %). Adresse matrielle Ethernet dune passerelle EGX. Numro de srie de la passerelle EGX. Numro du modle de la passerelle EGX. Version matrielle de la passerelle EGX. Date de fabrication de la passerelle EGX.

Compteur qui augmente dune unit chaque fois quun fichier est envoy sans problme au serveur HTTP. Compteur qui augmente dune unit chaque fois que la passerelle EGX ne parvient pas tablir la connexion avec le serveur HTTP. Compteur qui augmente dune unit chaque fois que le serveur HTTP ne parvient pas authentifier les identifiants Utilisateur / Mot de passe. Compteur qui augmente dune unit chaque chec de transfert dun fichier vers le serveur HTTP. Compteur qui augmente dune unit chaque fois quun fichier ne peut tre envoy parce que la passerelle EGX ne parvient pas mettre la transaction.

Erreur dauthentification

Envoi : erreur Erreur gnrale

Client FTP Envoi : OK Erreur de connexion Compteur qui augmente dune unit aprs chaque transfert russi vers un serveur FTP. Compteur qui augmente dune unit chaque fois que la passerelle EGX ne parvient pas tablir la connexion avec le serveur FTP. Compteur qui augmente dune unit chaque fois que le serveur FTP ne parvient pas authentifier les identifiants Utilisateur / Mot de passe. Compteur qui augmente dune unit chaque fois que le serveur FTP ne parvient pas localiser le rpertoire demand. Compteur qui augmente dune unit chaque chec de transfert dun fichier vers le serveur FTP. Compteur qui augmente dune unit chaque fois quun fichier ne peut tre envoy parce que la passerelle EGX ne parvient pas mettre la transaction.

Erreur dauthentification

Erreur de rpertoire

Envoi : erreur Erreur gnrale

Client SMTP Envoi : OK Compteur qui augmente dune unit chaque fois quun courrier lectronique est envoy sans problme au serveur SMTP. Compteur qui augmente dune unit chaque fois que la passerelle EGX ne parvient pas tablir la connexion avec le serveur SMTP. Compteur qui augmente dune unit chaque fois que le serveur SMTP ne parvient pas authentifier les identifiants Utilisateur / Mot de passe. Compteur qui augmente dune unit chaque fois quun courrier lectronique ne peut pas tre envoy au serveur SMTP. Compteur qui augmente dune unit chaque fois quun courrier lectronique ne peut tre envoy parce que la passerelle EGX ne parvient pas crer le message.

Erreur de connexion

Erreur dauthentification

Envoi : erreur

Erreur gnrale

Systme de fichiers Espace total Espace libre


1

Espace disque total de lEGX en kilo-octets. Volume total despace libre sur le disque de lEGX en kilo-octets.

Cliquez sur le lien pour plus dinformations.

2009-2013 Schneider Electric. Tous droits rservs.

55

Passerelle Ethernet PowerLogicTM EGX300 Diagnostics

63230-319-216B4_FR 06/2013

Lecture de registres dappareils

Cette option permet la passerelle EGX de lire les donnes en provenance de appareils locaux ou distants qui lui sont connects. Figure 49 : Page Lecture de registres dappareils

Action
1. Dans le menu Diagnostics, cliquez sur Lecture de registres dappareils.

Rsultat
Ouvre la page Lecture de registres dappareils.

2. Saisissez lidentification locale de lappareil Permet dentrer les registres lire sur lappareil (ou effectuez une slection dans la liste spcifi. des appareils dfinis), ladresse de dpart et le nombre de registres lire. 3. Slectionnez un type de donnes. Slectionne le type de donnes appropri.

4. Pour modifier laffichage des donnes Slectionne le mode daffichage des valeurs. dans la colonne Valeur, slectionnez Dcimal, Hexadcimal, Binaire ou ASCII. 5. Cliquez sur Lire. Lit les registres dappareils en fonction de la configuration slectionne.

Tableau 19 : Paramtres de lecture de registres dappareils EGX


Option
Nom dappareil

Description
Slectionne un appareil lire dans la liste des appareils ajouts prcdemment. Pour lire un appareil non dfini dans la liste des appareils, entrez son numro didentification locale. Adresse (identification locale) de lappareil lire. Premier registre lire. Nombre de registres lire (1 125). Liste des numros de registres. Liste des donnes enregistres dans un registre. Les valeurs rcupres dpendent de lappareil connect la passerelle EGX. Reportez-vous la documentation de lappareil connect pour plus dinformations sur les valeurs stockes dans un registre. Permet de slectionner les registres de maintien, les registres dentre, les bobines de sortie, les bobines dentre ou lidentification dappareil.

Valeur par dfaut

Identification de lappareil Registre de dpart Nombre de registres Colonne Registre Colonne Valeur

1 1000 10

Type de donnes

Registres de maintien Dcimal

Options Dcimal, Slection dune option pour spcifier laffichage des Hexadcimal, Binaire donnes de la colonne Valeur. ou ASCII

56

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Diagnostics

Vrification des communications


Vrification automatique des communications Lorsque vous parcourez les affichages de donnes en temps rel, la passerelle EGX effectue une vrification automatique des communications toutes les 15 minutes par dfaut. (Pour changer la frquence, voir Prfrences , page 33.) Cette opration vrifie ltat des communications de tous les appareils configurs sur la passerelle EGX et essaie de rtablir la communication avec tous les appareils marqus hors service dans la session de navigation actuelle.

Vrification manuelle des communications

Dans certains cas, il peut savrer prfrable de ne pas attendre lintervalle de vrification automatique des communications et dexcuter la vrification manuellement.
Action
1. Dans le menu Diagnostics, cliquez sur Vrification des communications. 2. Cliquez sur Vrification de ltat des appareils.

Rsultat
Ouvre la page Vrification des communications. Effectue une vrification des communications. Pour les appareils communicants, les valeurs Russite et En service saffichent dans les colonnes Communications et tat, respectivement. Pour les appareils qui ne communiquent pas, ces colonnes indiquent respectivement chec et Hors service si lchec se reproduit plusieurs fois.

Figure 50 : Page Vrification des communications

2009-2013 Schneider Electric. Tous droits rservs.

57

Passerelle Ethernet PowerLogicTM EGX300 Maintenance

63230-319-216B4_FR 06/2013

MAINTENANCE

Le journal de maintenance permet de consigner les oprations de maintenance effectues sur la passerelle EGX, les quipements qui y sont connects ou le systme dont elle fait partie. Chaque entre est enregistre avec la date et lheure de consignation, ainsi que le nom de lutilisateur qui la ralise. Ce journal indique galement lactivit systme, par exemple les activations et dsactivations de fonctions. Vous navez pas besoin dajouter des entres pour ces lments. Enfin, le journal liste aussi les activits spcifies pour le Journal de maintenance dans la page de configuration Piste daudit (voir Piste daudit , page 34).
Action
1. Dans le menu Maintenance, cliquez sur Journal de maintenance. 2. Slectionnez la case cocher Supprimer en regard de lentre supprimer, puis cliquez sur Supprimer des entres. 3. Cliquez sur Effacer le journal pour supprimer toutes les entres contenues dans le journal de maintenance.

Rsultat
Ouvre la page Journal de maintenance. Supprime lentre slectionne.

Efface le journal de maintenance.

4. Pour ajouter une nouvelle entre au Ouvre la page Ajouter une entre de journal et journal, cliquez sur Ajouter une entre de permet lutilisateur de saisir les dtails de la journal, puis saisissez le texte de maintenance. maintenance dans la zone de texte Dtail entre (voir Figure 52 ci-dessous).

Figure 51 : Journal de maintenance

Figure 52 : Ajouter une entre de journal

LOGICIEL EMBARQU (FIRMWARE)

Vous pouvez mettre niveau le logiciel embarqu (firmware) de la passerelle EGX au moyen du protocole FTP (File Transfer Protocol). Rendez-vous sur le site www.schneider-electric.com ou consultez votre reprsentant local pour obtenir la dernire mise jour du logiciel embarqu.

Recherche de la version du logiciel embarqu

LEGX comprend deux composants de logiciel embarqu : le composant binaire excutable et le composant image disque.

58

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Logiciel embarqu (firmware)

Version du composant binaire excutable du logiciel embarqu

Action
1. Ouvrez le navigateur Internet et connectez-vous la passerelle EGX.

Rsultat
Ouvre la page daccueil EGX.

2. Recherchez la version du logiciel Dtermine la version du logiciel embarqu de la embarqu dans le coin infrieur gauche de passerelle EGX. la page. REMARQUE : Si vous avez rcemment mis jour le logiciel embarqu, appuyez sur la touche F5 pour actualiser la page et afficher le nouveau numro de version. 3. Vous pouvez galement slectionner Dtermine galement la version du logiciel Diagnostics > Statistiques pour embarqu de la passerelle EGX. rechercher la version du logiciel embarqu dans la section Informations sur la passerelle.

Version de limage disque


Action
1. Ouvrez le navigateur Internet et connectez-vous la passerelle EGX. 2. Recherchez la version du logiciel embarqu en bas gauche de la page. REMARQUE : Si vous avez rcemment mis jour le logiciel embarqu, appuyez sur la touche F5 pour actualiser la page et afficher le nouveau numro de version. 3. Vous pouvez galement accder lEGX via FTP, localiser le fichier version.txt , puis double-cliquer dessus pour louvrir.

Rsultat
Ouvre la page daccueil EGX. Dtermine la version du composant image disque du logiciel embarqu de la passerelle EGX.

Dtermine la version du composant image disque du logiciel embarqu de la passerelle EGX.

Obtention du dernier logiciel embarqu

Action
1. Lancez le navigateur Web. Dans la barre dadresses tapez www.powerlogic.com et appuyez sur Entre. 2. Slectionnez votre pays, puis cliquez sur Go (atteindre). REMARQUE : Si vous slectionnez les tats-Unis, allez ltape 3. Dans le cas contraire, suivez les tapes spcifiques chaque pays pour obtenir le logiciel embarqu de la passerelle EGX. 3. Cliquez sur Support > Downloads (support > tlchargements). 4. Cliquez sur le lien EGX300 Firmware (logiciel embarqu EGX300).

Rsultat
Ouvre le site Web de PowerLogic.

Affiche le site PowerLogic de votre pays.

Ouvre la page de tlchargement. Affiche la page du logiciel embarqu de lEGX300.

5. Cliquez sur le lien menant au fichier du Ouvre la bote de dialogue de tlchargement, logiciel embarqu (egxxxxx.bin, o xxxx puis la bote de dialogue Enregistrer sous. correspond au numro de la version), puis cliquez sur Enregistrer. 6. Dans la bote de dialogue Enregistrer Sous, slectionnez ou crez le rpertoire local dans lequel le fichier doit tre enregistr, puis cliquez sur Enregistrer. Enregistre le fichier du logiciel embarqu dans le rpertoire slectionn.

7. Cliquez sur le lien menant au fichier du Ouvre la bote de dialogue de tlchargement, logiciel embarqu (egxxxxx.upd, o xxxx puis la bote de dialogue Enregistrer sous. correspond au numro de la version), puis cliquez sur Enregistrer. 8. Dans la bote de dialogue Enregistrer Sous, slectionnez ou crez le rpertoire local dans lequel le fichier doit tre enregistr, puis cliquez sur Enregistrer. Enregistre le fichier UPD du logiciel embarqu dans le rpertoire slectionn.

2009-2013 Schneider Electric. Tous droits rservs.

59

Passerelle Ethernet PowerLogicTM EGX300 Logiciel embarqu (firmware)

63230-319-216B4_FR 06/2013

Mise jour du logiciel embarqu (firmware)

Ne coupez pas lalimentation de la passerelle EGX pendant le tlchargement du logiciel embarqu. Si lalimentation est coupe pendant le processus de programmation, la passerelle EGX ne fonctionnera plus. Le voyant LED dtat clignote rapidement pendant la programmation. Lorsque le voyant se fige, la programmation est acheve.
Action Rsultat

1. Lancez lExplorateur Windows, tapez ftp:// Ouvre la bote de dialogue Connexion en tant et ladresse IP de la passerelle EGX dans la que. barre dadresses (ex. : ftp://169.254.0.10), puis appuyez sur Entre. 2. Tapez le nom dutilisateur Administrator et Ouvre une session FTP avec la le mot de passe correspondant dans les passerelle EGX. zones de texte appropries, puis cliquez sur Connexion. 3. Localisez le rpertoire du fichier de logiciel Copie le fichier dans le Presse-papiers. embarqu sur votre ordinateur (egxxxxx.bin), cliquez avec le bouton droit sur le fichier, puis cliquez sur Copier. 4. Cliquez avec le bouton droit de la souris dans la fentre de lExplorateur Windows, puis cliquez sur Coller. REMARQUE : Au lieu de copier-coller le fichier, vous pouvez le faire glisser vers lExplorateur Windows. Copie le logiciel embarqu dans la passerelle EGX, qui redmarre. REMARQUE : Le voyant Alimentation/tat clignote rapidement pendant que le fichier est transfr et programm sur la passerelle EGX. la fin de la programmation, lEGX redmarre. Le temps ncessaire la programmation est de 1,5 2 minutes.

5. Localisez le fichier de mise jour Copie le fichier de mise jour dans le Presse(egxxxxx.upd) sur votre ordinateur, cliquez papiers. avec le bouton droit sur le fichier, puis choisissez Copier. 6. Cliquez avec le bouton droit de la souris dans la fentre de lExplorateur Windows, puis cliquez sur Coller. REMARQUE : Au lieu de copier-coller le fichier, vous pouvez le faire glisser vers lExplorateur Windows. 7. Pour vrifier que la mise jour a russi, suivez la procdure dcrite la section Recherche de la version du logiciel embarqu , page 58. Vrifie la mise jour du logiciel embarqu. Copie le fichier sur la passerelle EGX, qui redmarre.

8. Cliquez sur le bouton Fermer de la fentre Ferme lExplorateur Windows et met fin la de lExplorateur Windows. connexion FTP avec la passerelle EGX.

60

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Annexe A Protocoles Ethernet pris en charge

ANNEXE A PROTOCOLES ETHERNET PRIS EN CHARGE

La passerelle EGX prend en charge les protocoles Ethernet suivants :

Modbus TCP/IP : Modbus TCP/IP est une combinaison du protocole Modbus qui permet les communications matre/esclave entre des appareils et de TCP/IP qui permet de communiquer par le biais dune connexion Ethernet. Modbus TCP/IP permet dchanger des donnes entre la passerelle EGX et dautres appareils compatibles Modbus TCP/IP via le port TCP 502. Hypertext Transfer Protocol (HTTP) : HTTP est un protocole rseau qui gre la remise de fichiers et de donnes sur le Web. La fonctionnalit de service Web est assure via le port TCP 80. HTTP scuris (HTTPS) : HTTPS est un protocole rseau qui gre le transfert crypt de fichiers et de donnes sur le Web via la technologie SSL. La fonctionnalit de service Web scuris est assure via le port TCP 443. File Transfer Protocol (FTP) : FTP est un protocole rseau qui permet de transfrer des fichiers dun ordinateur un autre sur Internet. Les modes FTP actif et passif sont pris en charge, principalement via le port TCP 21. Simple Network Management Protocol (SNMP) : Bas sur le format MIB2, SNMP permet denregistrer et didentifier des informations de diagnostic utilises pour la gestion du rseau via le port UDP 161. ARP (Address Resolution Protocol) : ARP convertit des adresses IP en adresses Ethernet. La passerelle EGX envoie des requtes ARP pour vrifier si son adresse IP est dj utilise (voir Dtection des adresses IP identiques , page 8). Simple Network Time Protocol (SNTP) : Le protocole SNTP permet de synchroniser les horloges des appareils en rseau laide dun serveur SNTP, via le port UDP 123.

Matriel
Port Ethernet RJ-45 Alimentation

Voyant LED dalimentation et dtat Port srie RS-485 Voyant LED pour les communications Ethernet et srie

Cavaliers de polarit, de terminaison et 2/4 fils Bouton de rinitialisation Port srie RS-232 (connecteur RJ-45)

2009-2013 Schneider Electric. Tous droits rservs.

61

Passerelle Ethernet PowerLogicTM EGX300 Annexe B Types dappareil pris en charge

63230-319-216B4_FR 06/2013

ANNEXE B TYPES DAPPAREIL PRIS EN CHARGE

La passerelle EGX prend en charge les types dappareil suivants. La liste des appareils pris en charge tait exacte au moment de la publication de ce document. Reportez-vous au site www.schneider-electric.com pour les mises jour. Tableau 20 : EGX300 Types dappareil pris en charge
Groupe dappareils Filtre dharmoniques actif Disjoncteurs Appareils Accusine Compact NSX-A Compact NSX-E PowerPact A PowerPact E Circuit Monitors CM100/200 CM2000 CM3000 CM4000 ION7500 ION7550 ION7600 ION7650 Appareils de mesure logiques DM6000 DM6300 Rgulateur de temprature numrique Modle 98 Variateurs ATV61 ATV71 Appareils de mesure dnergie Energy Meter Enercept E5600 EM1200 EM1210 EM1250 EM1251 EM26-96 EM3550 EM3555 EM4800 EM6400 EM6433 EM6436 EM6436DUAL EM6438 EM7230 EM7280 iEM3150 iEM3155 iEM3250 iEM3255 ION8600 Appareils de surveillance disolement Vigilohm IM20 Vigilohm IM20-H Gestion de moteur TeSys T MCM (Multi-Circuit Monitors) BCPM modle A BCPM modle B BCPM modle C BCM50A BCM100A MCM Relais de surcharge (SSOLR) MotorLogic Plus MotorLogic Plus II Contrleur de facteur de puissance Varlogic

62

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Annexe B Types dappareil pris en charge

Tableau 20 : EGX300 Types dappareil pris en charge


Groupe dappareils Power Meters Appareils PM9c PM200 PM300 PM500 PM600 PM700 PM800 PM1000 PM3250 PM5100 PM5300 PM5350 PM5350BW PM5560 ION6200 (Standard et Mega) ION7300 Sepam 2000 Sepam srie 10 Sepam srie 20 Sepam srie 40 Sepam srie 80 SIM10Z SIM10M SIM6BZ ATS48 MVSS/RVSS ZED-THL-M Micrologic A Micrologic E Micrologic H Micrologic P Acti9 SmartLink Onduleurs Conext TL

Relais de protection

Modules dinterface intelligents

Dispositifs de dmarrage en douceur Capteurs de temprature, dhumidit ou de lumire Units de contrle

Autre

2009-2013 Schneider Electric. Tous droits rservs.

63

Passerelle Ethernet PowerLogicTM EGX300 Annexe B Types dappareil pris en charge

63230-319-216B4_FR 06/2013

64

2009-2013 Schneider Electric. Tous droits rservs.

63230-319-216B4_FR 06/2013

Passerelle Ethernet PowerLogicTM EGX300 Index ftp exporter le journal de lappareil 21 pour ajouter des pages Web 31 pour obtenir un journal de donnes 44 pour supprimer des pages Web 31 pages Web ajout/suppression dans linterface Web 32 configuration 30 personnalisation 31 paramtres de port srie avancs 9 des mesures de base 38 Ethernet avancs 6 Ethernet et TCP/IP 5 SNMP configuration 26 TCP/IP 5 piste daudit 34 journal de maintenance 35 section Syslog 35 plage des cadrans analogiques 39 point daccs systme configuration 36 liens dautres passerelles EGX300 50 prfrences personnalisation de lEGX 33 prise en charge des types dappareil 62 protocoles Ethernet 61 pris en charge 61

Index
A
accs la passerelle EGX via un rseau 2 adresse IP dtection des adresses identiques 8 affichage des donnes et tendances en temps rel 38 appareils Modbus dtection 15 ARP (Address Resolution Protocol) 8

H
HTTP exporter journal de lappareil 22 numro de port configuration 7 obtention dun journal de donnes dintervalle 45 HTTPS numro de port configuration 7

B
bouton Accs aux donnes journal de donnes dintervalle 45

C
calcul de tendance 40 certificat dauthentification numro de port HTTPS 7 codes derreur journal de donnes 44 commande 51 comptes utilisateurs configuration 29 configuration EGX 5 liste des appareils 13 ports srie 8 synchronisation de lheure rseau 25 connexion lEGX 2 connexions dappareils 12 dappareils distants 10 courrier lectronique exporter le journal de lappareil 19 journal de donnes dintervalle 45

I
interface utilisateur EGX 3 intervalles denregistrement 17 introduction 1

J
journal de donnes codes derreur 44 obtenir via ftp 44 obtention 43 journal de donnes dintervalle laide dune requte Web Microsoft 45 par courrier lectronique 45 via ftp 44 via HTTP 45 via le bouton daccs aux donnes 45 journal de maintenance 58 piste daudit 35 journaux dappareil 17, 41

R
registres dappareils lecture 56 requte Web Microsoft journal de donnes dintervalle 45 rseau accs via 2 ressources supplmentaires 1

S
scurit du mot de passe indication couleur 29 statistiques 52 interprtation 53 surveillance 38 synchronisation de lheure rseau 25 Syslog pistes daudit 35

D
date et heure configuration 24 dtection des adresses IP identiques 8 dtection des appareils 15 diagnostics 52 donnes en temps rel 38

L
lecture de registres dappareils 56 liens vers la documentation configuration 28 liste des appareils EGX 12 logiciel embarqu (firmware) mise jour 60 mise jour par ftp 58 obtention de la dernire version 59

E
EGX connexion 2 interface utilisateur 3 liste des appareils 12 enregistrement 17, 41 format de donnes 43 grandeurs 18 intervalles 17 exportation du journal de lappareil 19 configuration 19

T
tableaux de bord 47 types dappareils affichables 34 pris en charge 62

M
matriel 61

V
vrification des communications 57 automatique 57 manuel 57 version du composant binaire excutable du logiciel embarqu 59 version du composant image de fichier de logiciel embarqu 59

N
niveaux daccs lEGX 27

P
page Documentation 51 pages dappareil unique 38, 42 pages rcapitulatives appareils 39, 46

F
filtrage Modbus TCP/IP configuration 27 format des journaux de donnes 43

2009-2013 Schneider Electric. Tous droits rservs.

65

Passerelle Ethernet PowerLogicTM EGX300 Index

63230-319-216B4_FR 06/2013

66

2009-2013 Schneider Electric. Tous droits rservs.

Passerelle Ethernet PowerLogicTM EGX300 Manuel dutilisation

PowerLogic est une marque commerciale ou une marque dpose de Schneider Electric aux tats-Unis, en France et dans dautres pays. Les autres marques commerciales sont la proprit de leurs dtenteurs respectifs. Ce produit doit tre install, raccord et utilis conformment aux normes et/ou aux rglements dinstallation en vigueur. En raison de lvolution des normes et du matriel, les caractristiques indiques par le texte et les images de ce document ne nous engagent quaprs confirmation par nos services. 63230-319-216B4_FR, 06/2013 Remplace 63230-319-216B3_FR, 03/2013 2009-2013 Schneider Electric. Tous droits rservs.

Schneider Electric
35, rue Joseph Monier CS 30323 92500 Rueil-Malmaison, France www.schneider-electric.com

PowerLogicTM Ethernet Gateway EGX300


Benutzerhandbuch
63230-319-216B4_DE 06/2013

Sicherheitshinweise
Wichtige Informationen
Lesen Sie die Anweisungen sorgfltig durch und sehen Sie sich die Ausrstung genau an, um sich mit dem Gert vor der Installation, dem Betrieb oder der Wartung vertraut zu machen. In dieser Publikation oder auf dem Gert knnen sich folgende Hinweise befinden, die vor potenziellen Gefahren warnen oder die Aufmerksamkeit auf Informationen lenken, die eine Prozedur erklren oder vereinfachen. Der Zusatz eines Symbols zu den Sicherheitshinweisen Gefahr oder Warnung deutet auf eine elektrische Gefahr hin, die zu schweren Verletzungen fhren kann, wenn die Anweisungen nicht befolgt werden. Dieses Symbol steht fr eine Sicherheitswarnung. Es macht auf die potenzielle Gefahr eines Personenschadens aufmerksam. Beachten Sie alle Sicherheitshinweise mit diesem Symbol, um schwere Verletzungen oder Todesflle zu vermeiden.

GEFAHR
GEFAHR weist auf eine unmittelbar gefhrliche Situation hin, die bei Nichtbeachtung zu schweren Verletzungen oder Todesfllen fhrt.

WARNUNG
WARNUNG weist auf eine potenziell gefhrliche Situation hin, die bei Nichtbeachtung zu schweren Verletzungen oder Todesfllen fhren kann.

ACHTUNG
ACHTUNG weist auf eine potenziell gefhrliche Situation hin, die bei Nichtbeachtung zu leichten Verletzungen fhren kann.

HINWEIS
HINWEIS wird verwendet, um Verfahren zu beschreiben, die nicht mit einer Verletzungsgefahr verbunden sind. Das Warnsymbol darf nicht mit diesem Signalwort verwendet werden.

Bitte beachten
Elektrisches Gert sollte stets von qualifiziertem Personal installiert, betrieben und gewartet werden. Schneider Electric bernimmt keine Verantwortung fr jegliche Konsequenzen, die sich aus der Verwendung dieser Publikation ergeben knnen. Eine qualifizierte Person ist jemand, der Fertigkeiten und Wissen im Zusammenhang mit dem Aufbau, der Installation und der Bedienung von elektrischen Gerten und eine entsprechende Schulung zur Erkennung und Vermeidung der damit verbundenen Gefahren absolviert hat.

Hinweise
Hinweis zum Teil 15 der FCC-Bestimmungen
Dieses Gert wurde getestet und erfllt die Anforderungen fr digitale Gerte der Klasse A gem Teil 15 der FCC-Bestimmungen. Diese Bestimmungen sollen bei der gewerblichen Nutzung des Gerts einen angemessenen Schutz gegen schdliche Funkstrungen sicherstellen. Dieses Gert erzeugt und nutzt Energie im Funkfrequenzspektrum und kann solche auch abstrahlen. Wird es nicht der Anleitung entsprechend installiert, kann es schdliche Funkstrungen verursachen. Die Verwendung dieses Gerts in einem Wohngebiet kann schdliche Funkstrungen verursachen. In diesem Fall ist der Benutzer dafr verantwortlich, die Strungen auf eigene Kosten zu beseitigen. Die RENNummer (Ringer Equivalence Number) fr das optionale interne Modem des Gerts lautet 0.6. Der Anschluss am internen Modem des Gerts muss ber ein Telefonkabel gem FCC Teil 68 erfolgen (nicht im Lieferumfang enthalten). Das Gert kann nicht in Verbindung mit ffentlichen Mnztelefonen oder Gemeinschaftsanschlssen eingesetzt werden. Dieses digitale Gert der Klasse A erfllt die Anforderungen der kanadischen Norm ICES-003 (Interference-Causing Equipment Standard).

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Inhaltsverzeichnis

Inhaltsverzeichnis
Einfhrung ................................................................................................. 1 Zustzliche Ressourcen .............................................................................. 1 Zugang zum EGX ber ein Netzwerk ....................................................... 2 Anmelden beim EGX ................................................................................... 2 EGX-Benutzeroberflche berblick ..................................................... 3 Setup .......................................................................................................... 5 Ethernet- und TCP/IP-Einstellungen ........................................................... 5 Erweiterte Ethernet-Einstellungen ......................................................... 6 Erkennung identischer IP-Adressen ...................................................... 8 Serielle Schnittstelle .................................................................................... 8 Erweiterte Einstellungen der seriellen Schnittstelle............................... 9 Verbindungen zu entfernten Gerten ........................................................ 10 EGX-Gerteliste ........................................................................................ 12 Anschluss von Gerten an ein EGX .................................................... 12 Gerteliste einrichten........................................................................... 13 Gerteerkennung................................................................................. 15 Gerteaufzeichnung .................................................................................. 17 Intervalldatenaufzeichnung.................................................................. 17 Intervallaufzeichnung einrichten .......................................................... 17 Aufzuzeichnende Gren.................................................................... 18 Gerteprotokollexport ................................................................................ 19 E-Mail-Export....................................................................................... 19 FTP-Export .......................................................................................... 21 HTTP-Export........................................................................................ 23 Datum und Uhrzeit .................................................................................... 24 Netzwerkzeitsynchronisation ............................................................... 25 SNMP-Parameter ...................................................................................... 26 Modbus-TCP/IP-Filter ............................................................................... 27 Unterlagenlinks ......................................................................................... 28 Benutzerkonten ......................................................................................... 29 Webseitenzugriff ....................................................................................... 30 Benutzerdefinierte Webseiten hinzufgen/entfernen........................... 31 Hinzufgen von Webseiten mit FTP .................................................... 31 Lschen von Webseiten mit FTP......................................................... 31 Webseiten zur Webschnittstelle hinzufgen oder aus ihr entfernen.... 32 Prferenzen ............................................................................................... 32 Anzeigbare Gertetypen ........................................................................... 33 Prfpfad ..................................................................................................... 34 Systemzugangspunkt ................................................................................ 36 berwachung .......................................................................................... 38 Echtzeitdaten ............................................................................................ 38 Einzelgerteseiten ............................................................................... 38 Grundmesswerteinstellungen .............................................................. 38 Analogmessgertbereich..................................................................... 39 bersichtsgerteseiten........................................................................ 39 Trendverfolgung .................................................................................. 40

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300 Inhaltsverzeichnis

63230-319-216B4_DE 06/2013

Gerteaufzeichnung .................................................................................. 41 Einzelgerteseiten ............................................................................... 42 Abrufen eines Datenprotokolls ............................................................ 43 Protokollformat .................................................................................... 43 Fehlercodes fr Datenprotokolle ......................................................... 44 Abrufen eines Intervalldatenprotokolls mit FTP................................... 44 Abrufen eines Intervalldatenprotokolls mit der Schaltflche Datenpunkte ................................................................. 45 Abrufen eines Intervalldatenprotokolls mit Microsoft WebQuery......... 45 Abrufen eines Intervalldatenprotokolls ber E-Mail ............................. 45 Abrufen eines Intervalldatenprotokolls ber HTTP.............................. 45 bersichtsgerteseiten........................................................................ 46 Instrumententafeln .................................................................................... 47 Anzeigen einer Instrumententafel........................................................ 48 Abrufen von Instrumententafeldaten mit der Schaltflche Datenpunkte ................................................................. 49 Speichern eines Instrumententafel-Links ............................................ 49 Speichern einer Instrumententafel als ein Bild .................................... 49 Systemzugangspunkt ................................................................................ 50 Unterlagen ............................................................................................... 51 Steuerung ................................................................................................ 51 Diagnose .................................................................................................. 52 Statistik ...................................................................................................... 52 Statistik auswerten .............................................................................. 53 Gerteregister lesen .................................................................................. 56 Kommunikationsprfung ........................................................................... 57 Automatische Kommunikationsprfung ............................................... 57 Manuelle Kommunikationsprfung ...................................................... 57 Wartung .................................................................................................... 58 Firmware .................................................................................................. 58 Firmwareversion feststellen ...................................................................... 58 Firmwareversion der ausfhrbaren Binrkomponente ........................ 59 Datentrgerabbildkomponente ............................................................ 59 Neue Firmware herunterladen .................................................................. 59 Firmware aktualisieren .............................................................................. 60 Anhang A Untersttzte Ethernet-Protokolle ...................................... 61 Hardware ................................................................................................... 61 Anhang B Untersttzte Gertetypen .................................................. 62

ii

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Einfhrung

EINFHRUNG

Das EGX300 ist ein Ethernet-basiertes Gert, welches eine transparente Schnittstelle zwischen Ethernet-Netzen und Feldgerten bereitstellt. Zu den Feldgerten gehren Mess- und berwachungsgerte, Schutzrelais, SPSEinheiten, Auslsesysteme, Motorsteuerungen und andere Gerte, die mit Modbus-, Jbus- oder PowerLogic-Protokollen kommunizieren. Das EGX300 benutzt das Modbus-TCP/IP-Protokoll fr den Zugriff auf Feldgertedaten in einem LAN- oder WAN-Netz. Diese Fhigkeit ermglicht den Einsatz von berwachungssoftware fr den Zugriff auf Gertedaten fr Datenerfassung, Trendverfolgung, Alarm- und Ereignisverwaltung, Analyse und andere Funktionen. Das EGX300 untersttzt die Echtzeitdatenanzeige fr viele gebruchliche Gertetypen und stellt verschiedene gertespezifische Funktionen bereit. Es stehen z. B. Onboard-Gerte- und Schaltkreisbersichtsseiten sowie Onboard-Datenaufzeichnung und Echtzeit-Trendverfolgung zur Verfgung. Abbildung 1: berblick ber das EGX300
Betrachten von Gertedaten mit einem einfachen Browser ohne zustzliche Software EGX300-Webseiten Echtzeitansichten

EchtzeitTrendkurven

Steuerungsrcksetzungen

DatenprotokollTrendkurven

EGX300

Auslesen von Daten von anderen PowerLogicGateways und ModbusTCP/IP-Schnittstellen, z. B. ECC21- und PM8ECCGerte, in Webseiten.

EGX100

ION6200

PM800

Micrologic

Sepam

Zustzliche Ressourcen

Rufen Sie die Website www.schneider-electric.com auf und geben Sie EGX300 in das Suchfeld ein. Navigieren Sie zu EGX Documents & Downloads (EGX-Unterlagen und Downloads).

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300 Zugang zum EGX ber ein Netzwerk

63230-319-216B4_DE 06/2013

ZUGANG ZUM EGX BER EIN NETZWERK

Nachdem Sie die EGX-Ethernet-Parameter eingerichtet haben (siehe EGXInstallationshandbuch), knnen Sie ber ein Ethernet-LAN mit jedem gngigen Webbrowser auf das EGX zugreifen.

Anmelden beim EGX


Manahme
1. Starten Sie den Webbrowser. 2. Geben Sie in die Adressenleiste die Adresse Ihres EGX ein (169.254.0.10 ist die Werkeinstellung) und drcken Sie die Eingabetaste. 3. Geben Sie in die Textfelder Ihren Benutzernamen (Werkeinstellung: Administrator) und das Kennwort (Werkeinstellung: Gateway) ein und klicken Sie auf OK. HINWEIS: Beim Benutzernamen und Kennwort wird zwischen Gro- und Kleinschreibung unterschieden. 4. Klicken Sie auf den entsprechenden Menpunkt in der Menleiste. Einblendung des ausgewhlten Menpunkts.

Ergebnis
Einblendung des Webbrowsers. Einblendung des Anmelde-Dialogfeldes.

Eingabe des Benutzernamens und des Kennwortes und Einblendung der EGXStartseite.

Abbildung 2: EGX-Startseite

Menleiste

Wir empfehlen, dass Sie sich immer dann abmelden, wenn Sie keinen Zugang zum EGX bentigen. Klicken Sie auf Logout oder schlieen Sie einfach Ihren Browser, um sich von der EGX-Sitzung abzumelden.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 EGX-Benutzeroberflche berblick

EGX-BENUTZEROBERFLCHE BERBLICK

Die EGX-Benutzeroberflche besteht aus mehreren Webseiten, die fr die Gerteberwachung und -steuerung sowie fr die EGX-Diagnose und -Einrichtung benutzt werden. Tabelle 1 enthlt eine Beschreibung jeder Webseite. Tabelle 1: EGX-Seiten
EGX-Webseite
Setup Ethernet & TCP/IP Serielle Schnittstelle Konfiguration der Ethernet- und TCP/IP-Einstellungen. Konfiguration der Parameter fr die serielle Kommunikation. 5 8 10 12

Beschreibung

Siehe Seite

Verbindungen zu entfernten Konfiguration der Modbus-TCP/IP-Verbindungen zu Gerten entfernten Gerten. Gerteliste Konfiguration, Erkennung oder berprfung von lokalen seriellen Gerten in der Gertekette. Entfernte Gerte knnen nur konfiguriert oder berprft werden. Konfiguration der Parameter fr die Gerteaufzeichnung. Konfiguration der Optionen fr den Gerteprotokollexport. Einstellung des Datums und der Uhrzeit entweder manuell oder mit SNTP-Parametern. Konfiguration des Simple Network Management Protocol (SNMP). Festlegung der IP-Adressen, die auf das EGX ber Modbus-TCP/IP zugreifen knnen. Konfiguration der Datei- und URL-Links der Unterlagen. Erstellung und Bearbeitung von Gruppen und Benutzern. Konfiguration der Webseiten-Zugriffsrechte fr jede Benutzergruppe. Konfiguration der EGX-Prferenzen. Konfiguration der untersttzten Gertetypen, die auf der Webseite EGX-Gerteliste anzeigbar sind. Konfiguration der Weiterleitung von Systemmeldungen durch das EGX: ber das Wartungsprotokoll, per E-Mail oder ber den entfernten Syslog-Server. Aktivierung und Konfiguration der Gruppen-IP-Adresse fr mehrere EGX300-Gerte, damit sie sich gegenseitig erkennen und ihre Daten lesen knnen.

Gerteaufzeichnung Gerteprotokollexport Datum und Uhrzeit1 SNMP-Parameter1 Modbus-TCP/IP-Filter1 Unterlagenlinks Benutzerkonten1 Webseitenzugriff1 Prferenzen Anzeigbare Gertetypen Prfpfad1

17 19 24 26 27 28 29 30 32 33 34

Systemzugangspunkt1

36

berwachung Echtzeitdaten Die Tabellenansicht Einzelgerteseiten zeigt Grundmesswerte der ausgewhlten Gerte an. Die Tabellenansicht bersichtsgerteseiten zeigt bersichten ber ein oder mehrere ausgewhlte Gerte an. Die Ansicht Trendverfolgungsseite zeigt grafisch und tabellarisch die Echtzeit-Trendverfolgung von Gren an, die mehrere Gerte gemeinsam haben. Die Einzelgerteseiten zeigen grafische und tabellarische Trendaufzeichnungen in benutzerdefinierbaren Gren fr ausgewhlte Gerte an. Die bersichtsgerteseiten zeigen grafische Trendaufzeichnungen mehrerer Gerte mit einer gemeinsamen Gre an. Die Instrumententafeln enthalten grafische und tabellarische Darstellungen von zeitlich summierten Energieverbrauchsdaten aller Gerte, fr die die Datenaufzeichnung aktiviert ist. Die Seite Systemzugangspunkt zeigt EGX300-Gerte und andere Systemgerte im Netzwerk an, auf die vom jeweiligen EGX300 zugegriffen werden kann. Jede Zeile ist ein Hyperlink zur EGX300-Anmeldeseite. 38

Gerteaufzeichnung

41

Instrumententafeln

47

Systemzugangspunkt

50

Nur fr den Administrator zugnglich

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300 EGX-Benutzeroberflche berblick

63230-319-216B4_DE 06/2013

Tabelle 1: EGX-Seiten
EGX-Webseite
Unterlagen Unterlagen Steuerung Resets Sorgt fr die Ausfhrung von Rckstellungen, die fr das Gert festgelegt sind, und zeigt das Datum und die Uhrzeit der Durchfhrung jeder Rcksetzfunktion an. Die Datums- und Uhrzeit-Rckstellungen werden nur angezeigt, wenn das Gert diese Funktionen untersttzt. Anzeige von Diagnosedaten zur Fehlersuche und behebung bei Netzwerkproblemen. Diese Seite enthlt ebenfalls spezifische Informationen ber Ihr EGX, einschlielich Seriennummer, Herstellungsdatum und MAC-Adresse. Damit knnen Benutzer Registerdaten von lokalen und entfernten Gerten, die an das EGX angeschlossen sind, lesen. berprfung der strungsfreien Kommunikation mit allen im EGX konfigurierten Gerten. Anzeige des Datums, der Uhrzeit und des Benutzers, der zuletzt Wartungsarbeiten am Gert durchgefhrt hat, sowie der Eintrge ber die durchgefhrte Wartung. 51 Zugriff auf relevante EGX-Unterlagen und vom Benutzer konfigurierte Unterlagenlinks. 51

Beschreibung

Siehe Seite

Diagnose Statistik 52

Gerteregister lesen

56

Kommunikationsprfung Wartung Wartungsprotokoll

57

58

Nur fr den Administrator zugnglich

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

SETUP

Fr den Zugang zu den Links der Setup-Webseiten klicken Sie auf Setup in der EGX-Menleiste.

Ethernet- und TCP/IP-Einstellungen


Manahme Ergebnis
1. Klicken Sie im Setup-Men auf Ethernet & Einblendung der Ethernet & TCP/IP-Seite. TCP/IP. 2. Whlen Sie Ihr Rahmenformat und das bertragungsmedium aus. Falls Sie diese Informationen nicht kennen, wenden Sie sich an Ihren Netzwerkadministrator. 3. Geben Sie Ihre IP-Adresse, die Subnetzmaske und die dem EGX durch Ihren Netzwerkadministrator zugewiesene Standard-Gateway-Adresse ein. Auswahl von Rahmenformat und bertragungsmedium.

Eingabe der Ethernet-Parameter fr das EGX. HINWEIS: Wenn Sie eine IP-Adresse eingeben, die bereits in Verwendung ist, werden Sie zur Auswahl einer anderen IPAdresse aufgefordert. Siehe Erkennung identischer IP-Adressen auf Seite 8. Aktualisierung der Ethernet- und TCP/IPEinstellungen fr das EGX.

4. Klicken Sie auf bernehmen. * Tabelle 2 enthlt eine Liste der Optionen.

Abbildung 3: Ethernet & TCP/IP-Seite

Tabelle 2: EGX-Ethernet- und TCP/IP-Einstellungen


Option Beschreibung Einstellung

Rahmenformat Auswahl des Formats, in dem Daten ber eine Ethernet II, 802.3 SNAP Ethernet-Verbindung gesendet werden. Werkeinstellung: Ethernet II bertragungs- Festlegung der physikalischen medium Ethernet-Verbindung oder des bertragungsmediums. 10T/100Tx Auto 10BaseT-HD 10BaseT-FD 100BaseTX-HD 100BaseTX-FD

Werkeinstellung: 10T/100Tx Auto IP-Adresse automatisch erhalten IP-Adresse Fr den automatischen Abruf einer IP-Adresse Aktiviert oder Deaktiviert von einem BootP-Server. Werkeinstellung: Deaktiviert HINWEIS: Erfordert die Untersttzung der Netzwerkadministration. Eingabe der statischen IP-Adresse des EGX. Werkeinstellung: 169.254.0.10 Werkeinstellung: 255.255.0.0

Subnetzmaske Eingabe der Ethernet-IP-Subnetzmaskenadresse Ihres Netzwerks. StandardGateway

Eingabe der Gateway-IP-Adresse (Router) fr Werkeinstellung: 0.0.0.0 WAN-Kommunikation.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Erweiterte Ethernet-Einstellungen

HINWEIS
BEEINTRCHTIGTE LEISTUNGSFHIGKEIT DES NETZWERKS Die erweiterten Ethernet-Einstellungen des EGX drfen nur von qualifiziertem Personal vorgenommen werden. Diese nderungen drfen grundstzlich erst vorgenommen werden, wenn die Informationen ber die erweiterten Einstellungen vollstndig gelesen und verstanden wurden. Durch Nichtbeachtung dieser Anweisungen kann die Leistungsfhigkeit des Netzwerks beeintrchtigen.

Manahme
1. Klicken Sie auf der Seite Ethernet & TCP/IP auf Erweitert.

Ergebnis
Einblendung der Seite Erweiterte EthernetEinstellungen.

2. Konfigurieren Sie die erweiterten Ethernet- Einrichtung der erweiterten EthernetEinstellungen (Tabelle 3 auf Seite 7 enthlt Einstellungen. die verfgbaren Optionen). Klicken Sie auf Standardwerte, um die Standardwerte fr alle Optionen auszuwhlen. 3. Klicken Sie auf bernehmen. HINWEIS: Beim bernehmen von nderungen auf die Seite Erweiterte Ethernet-Einstellungen werden diese nderungen nicht auf der Seite Ethernet & TCP/IP gespeichert. Aktualisierung der Ethernet- und TCP/IPEinstellungen fr das EGX.

4. Klicken Sie auf OK, um die nderungen zu Das EGX startet neu. besttigen und das EGX zurckzusetzen.

Abbildung 4: Seite Erweiterte Ethernet-Einstellungen

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Tabelle 3: Erweiterte Ethernet-Einstellungen des EGX


Option
Gltigkeitsdauer

Beschreibung
Legt die Anzahl der Router fest, die ein TCPPaket durchlaufen kann.

Einstellung
1 bis 255 Hops Werkeinstellung: 60 Hops

TCP Keep-Alive

0 bis 65.000 Sekunden Ein Timer, der feststellt, wenn ein ber eine Werkeinstellung: unbelegte Verbindung angeschlossenes Gert 30 Sekunden aufgrund von Ereignissen wie Neustart oder Ausschalten nicht mehr verfgbar ist. Der Wert 0 deaktiviert diese Einstellung. Legt fest, wie lange das EGX auf die Zuweisung seiner IP-Adresse durch einen BootP-Server wartet. (Wenn nach Ablauf der Zeit keine IPAdresse zugewiesen wurde, wird die voreingestellte IP-Adresse verwendet.) Legt fest, wie lange Eintrge in der ARP-Tabelle (Address Resolution Protocol) verbleiben. Steuert die Aktivierung der Initialisierung des FTP-Servers beim Start. 0 bis 60 Sekunden Werkeinstellung: 15 Sekunden

BootPZeitberschreitung

ARP-CacheTimeout FTP-Server

0 bis 65.000 Minuten Werkeinstellung: 15 Minuten Deaktiviert oder Aktiviert Werkeinstellung: Aktiviert 30 bis 900 Sekunden Werkeinstellung: 120 Sekunden

FTP-Verbindungsleerlaufzeit

Ein Timer, der eine FTP-Verbindung nach einer festgelegten Leerlaufzeit schliet.

HTTP-Verbindungs- Ein Timer, der eine HTTP-Verbindung nach einer 0 bis 65.000 Sekunden leerlaufzeit festgelegten Leerlaufzeit schliet. Werkeinstellung: 4 Sekunden HTTP-Port-Nr. Der fr HTTP-Meldungen verwendete TCP-Port. Die folgenden Portnummern sind fr andere Netzwerkprotokolle reserviert und knnen nicht verwendet werden: 20 und 21 (FTP) und 502 (Modbus TCP/IP). Der fr HTTPS-Meldungen verwendete TCP-Port. Das EGX wird mit einem selbstsignierten Zertifikat ausgeliefert. Damit aus dem EGX ein vertrauenswrdiger Server wird, mssen Sie ein Zertifikat von einer Zertifizierungsstelle erwerben (z. B. VeriSign Authentication Services). Um ein digitales Zertifikat hinzuzufgen bzw. zu installieren, rufen Sie manuell mit der URL http://x.x.x.x./update_certs_shtml (wobei x.x.x.x fr die IP-Adresse des EGX steht) die Zertifikataktualisierungsseite auf. Max. Anzahl der HTTP-Keep-AliveVersuche Modbus-TCP/IPSerververbindungen Modbus-Broadcast Legt die maximale Anzahl der HTTP-Keep-Alive- 0 bis 65.000 Versuche fest. Werkeinstellung: 100 Legt die verfgbare Anzahl an Modbus-TCP/IPServer-Verbindungen fest. Legt fest, wie Modbus-TCP/IP-Meldungen mit Unit-ID = 0 im seriellen Subnetzwerk behandelt werden. Deaktiviert = alle Meldungen werden ignoriert. Aktiviert = alle Meldungen werden als Broadcasts an serielle Schnittstellen behandelt, fr die keine Antwort erwartet wird. Aktiviert mit Rckmeldung = alle Meldungen werden als normale Meldungen an serielle Schnittstellen behandelt, fr die eine Antwort erwartet wird. Diese Einstellung legt fest, ob Modbus-TCP/IPMeldungen von entfernten Clients an entfernte Modbus-TCP/IP-Gerte, die im EGX definiert sind, weitergeleitet werden. 16 bis 64 Werkeinstellung: 32 Deaktiviert, Aktiviert oder Aktiviert mit Rckmeldung Werkeinstellung: Deaktiviert 0 bis 65.000 Werkeinstellung: 80 0 HTTP-Port deaktiviert 1 bis 65.000 Werkeinstellung: 443 0 HTTPS-Port deaktiviert

HTTPS-Port-Nr.

Modbus TCPProxyserver

Deaktiviert oder Aktiviert Werkeinstellung: Aktiviert

Timeout ModbusTCP/IP-Client

0,1 bis 10 Die Zeit, whrend der das EGX auf die Antwort eines entfernten Modbus-TCP/IP-Gerts auf eine Werkeinstellung: 5 Sekunden durch das EGX eingeleitete Modbus-TCP/IPAnforderung wartet. 1 bis 10 Die Zeit, whrend der das EGX auf die Antwort eines entfernten Modbus-TCP/IP-Gerts auf eine Werkeinstellung: 2 Sekunden durch das EGX eingeleitete Modbus-TCP/IPVerbindungsanforderung wartet.

Timeout ModbusTCP/IP-ClientVerbindung

Modbus-TCP/IPEin Timer, der eine Modbus-TCP/IP-Verbindung 0 bis 32.767 Sekunden Server-Verbindung nach einer festgelegten Leerlaufzeit schliet. Der Werkeinstellung: 0 Leerlaufzeit Wert 0 deaktiviert diese Einstellung.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Erkennung identischer IP-Adressen

Whrend das EGX an Ihr Netzwerk angeschlossen ist, verffentlicht es seine IP-Adresse. Zur Vermeidung von Konflikten aufgrund doppelt vergebener IP-Adressen wird vom EGX das ARP-Protokoll (Address Resolution Protocol) benutzt. Damit wird festgestellt, ob ein anderes Gert in Ihrem Netzwerk die gleiche IP-Adresse verwendet. In der nachstehenden Tabelle 4 wird erlutert, wie das EGX mit einer doppelt vergebenen IPAdresse umgeht, sobald es sie erkannt hat. Tabelle 4: Szenarien der Erkennung doppelter IP-Adressen
Szenario
Boot-Prozess/Wiederherstellung der Spannungsversorgung Ethernet-Verbindung erkannt

Doppelte IP-Adresse erkannt

Spannungsversorgungs/Status-LED

Das EGX kehrt zur voreingestellten Muster aus vier Blinkzeichen IP-Adresse, Subnetzmaske und und einer Pause Gateway-Adresse zurck. ARPAnfragen werden alle 15 Sekunden gesendet, bis die IP-Adresse verfgbar ist. Sobald die IPAdresse verfgbar ist, wird sie vom EGX verwendet. Das EGX behlt seine vorherige IP-Adresse und zeigt eine Meldung an, die darauf hinweist, dass die IPAdresse bereits von einem anderen Gert verwendet wird.

Manuelle Adressennderung

Erhalt einer ARP-Anfrage

Rckkehr zur im EGX Muster aus vier Blinkzeichen voreingestellten IP-Adresse, und einer Pause Subnetzmaske und GatewayAdresse, wenn ein angeschlossenes Gert vier ARPAnfragen bezglich der IP-Adresse des EGX sendet. Das EGX sendet alle 15 Sekunden ARP-Anfragen, bis die IP-Adresse wieder verfgbar ist. Sobald die IPAdresse verfgbar ist, wird sie vom EGX verwendet.

Serielle Schnittstelle
Manahme
1. Klicken Sie im Setup-Men auf Serielle Schnittstelle.

Ergebnis
Einblendung der Seite Serielle Schnittstelle.

2. Whlen Sie die physische Schnittstelle, Auswahl der Optionen fr die serielle den bertragungsmodus, die Baudrate, die Schnittstelle. Paritt und die Antwort-Zeitberschreitung aus (siehe Tabelle 5 auf Seite 9). 3. Klicken Sie auf bernehmen. Aktualisierung der Einstellungen fr die serielle EGX-Schnittstelle.

Abbildung 5: Seite Serielle Schnittstelle

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Tabelle 5: Einstellungen der seriellen Schnittstelle


Option
Physische Schnittstelle

Beschreibung
Auswahl der physischen Verdrahtung der seriellen EGX-Schnittstelle.

Einstellung
RS485 4-Leiter, RS485 2-Leiter oder RS232 Werkeinstellung: RS485 2-Leiter Automatisch Modbus ASCII

bertragungsmodus

Hier wird festgelegt, wie Daten ber die serielle Verbindung bertragen werden.

HINWEIS: Im Automatikmodus kann das Gert mit Modbus RTU-, Jbus- und PowerLogic (SY/MAX)-Slave-Gerten in der gleichen Gertekette kommunizieren. Baudrate Hier wird die Geschwindigkeit der Datenbertragung ber die serielle Verbindung festgelegt. 2400, 4800, 9600, 19200, 38400, 56000* oder 57600* Werkeinstellung: 19200

Paritt

Hier wird die Art der Paritt festgelegt, die Gerade, Ungerade oder Keine fr die berprfung der Richtigkeit der Werkeinstellung: Gerade Daten mit einem Paritts-Bit erforderlich ist. 0,1 bis 10 Sekunden Werkeinstellung: 3 Sekunden

AntwortDieser Parameter legt fest, wie lange das Zeitberschreitung EGX auf den Empfang einer Antwort von einem seriellen Gert wartet.

* Nur verfgbar, wenn die physische Schnittstelle bzw. der bertragungsmodus auf RS232/Modbus ASCII eingestellt ist.

Erweiterte Einstellungen der seriellen Schnittstelle

HINWEIS
BEEINTRCHTIGTE LEISTUNGSFHIGKEIT DES NETZWERKS Die erweiterten Einstellungen der seriellen Schnittstelle des EGX drfen nur von qualifiziertem Personal vorgenommen werden. Diese nderungen drfen grundstzlich erst vorgenommen werden, wenn die Informationen ber die erweiterten Einstellungen der seriellen Schnittstelle vollstndig gelesen und verstanden wurden. Durch Nichtbeachtung dieser Anweisungen kann die Leistungsfhigkeit der seriellen Kommunikation beeintrchtigen.
Manahme
1. Klicken Sie auf der Seite Serielle Schnittstelle auf Erweitert.

Ergebnis
Einblendung der Seite Erweiterte Einstellungen der seriellen Schnittstelle.

Einrichtung der erweiterten 2. Konfigurieren Sie die erweiterten Einstellungen der seriellen Schnittstelle (Tabelle 6 auf Seite 10 enthlt die Einstellungen der seriellen verfgbaren Optionen). Klicken Sie auf Standardwerte, Schnittstelle. um die Standardwerte fr alle Optionen auszuwhlen. 3. Klicken Sie auf bernehmen. Aktualisierung der erweiterten Einstellungen der seriellen HINWEIS: Beim bernehmen von nderungen auf der Schnittstelle fr das EGX. Seite Erweiterte Einstellungen der seriellen Schnittstelle werden diese nderungen nicht auf der Seite Serielle Schnittstelle gespeichert.

Abbildung 6: Seite Erweiterte Einstellungen der seriellen Schnittstelle

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Tabelle 6: Erweiterte Einstellungen der seriellen Schnittstelle


Option Beschreibung Einstellung
0 bis 100 Millisekunden Werkeinstellung: 50 Millisekunden

Verzgerung Hier wird das Mindeststilleintervall zwischen Rahmen zwischen dem Ende einer empfangenen Antwort und dem Beginn einer neuen Anfrage auf der seriellen Leitung festgelegt. Verlngerung des Stilleintervalls

Erlaubt die Verlngerung des 0 bis 15 Zeichen Stilleintervalls zur Kennzeichnung des Werkeinstellung: 6 Zeichen Endes eines Modbus RTU-Pakets ber die standardmig festgelegten 3,5 Zeichen hinaus. Hier wird der Ausnahmefehlercode 0x0A oder 0x0B festgelegt, der zurckgesendet wird, wenn Werkeinstellung: 0x0B ein an das EGX angeschlossenes serielles Gert nicht vor der Zeitberschreitung der seriellen Schnittstelle antwortet. Modbus TCP/IP verwendet 0x0B. Allerdings wurde bei einigen lteren Software-Suites 0x0A verwendet.

Ausnahmefehlercode ModbusTCP/IP-Timeout

Verbindungen zu entfernten Gerten

Das EGX kann Verbindungen fr bis zu 16 eindeutige, benutzerdefinierte entfernte Modbus-TCP/IP-Gerte herstellen. Verbindungen knnen manuell eingegeben oder aus einer Tabelle mit vom Systemzugangspunkt erkannten Verbindungen ausgewhlt werden (siehe Abbildung 7 auf Seite 11). Diese Verbindungen werden auf der Seite zum Einrichten der Gerteliste fr die Konfiguration entfernter Gerte zur Verfgung gestellt.
Manahme
1. Klicken Sie im Setup-Men auf Verbindungen zu entfernten Gerten. 2. Manuelles Hinzufgen einer Verbindung: Geben Sie die IP-Adressen fr die entfernten Gerte ein, mit denen Sie eine Verbindung herstellen mchten. 3. Hinzufgen einer vom Systemzugangspunkt erkannten Verbindung: Klicken Sie auf Hinzufgen (rechts neben der gewnschten Verbindung in der Tabelle der erkannten Verbindungen). 4. Klicken Sie auf bernehmen.

Ergebnis
Anzeige der Seite Verbindungen zu entfernten Gerten. Eingabe der IP-Adressen der entfernten Gerte.

Eingabe der IP-Adresse der ausgewhlten, vom Systemzugangspunkt erkannten Verbindung.

Aktualisierung der EGX-Einstellungen fr Verbindungen zu entfernten Gerten.

10

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Abbildung 7: Verbindungen zu entfernten Gerten

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

11

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

EGX-Gerteliste

Bedenken Sie vor Beginn, dass Sie die seriellen Slave-Adressen 1 bzw. 16 nicht im automatischen bertragungsmodus in einer Gertekette mit gemischten Protokollen benutzen drfen (beispielsweise bei einer Gertekette mit Gerten, von denen einige das PowerLogic-Protokoll und andere ein Modbus RTU/Jbus-Protokoll verwenden).

Anschluss von Gerten an ein EGX

Abbildung 8 und Abbildung 9 zeigen, wie Gerte an das EGX angeschlossen werden knnen. Um diese Gerte zur Gerteliste hinzuzufgen, fhren Sie die unter Gerteliste einrichten auf Seite 13 beschriebenen Schritte aus. Abbildung 8: Topologie nur serielle Slave-Gerte

EthernetVerbindung EGX

EGX300-Webseiten

RS485-Verbindung

Serielle Slave-Gerte

Abbildung 9: Topologie serielle Slave- und entfernte Gerte


EthernetVerbindung

EGX300-Webseiten IP-Adresse des EGX100: 169.254.0.28 IP-Adresse des EGX300: 169.254.0.75

Es sind bis zu 16 IPFernverbindungen mglich.

RS485Verbindung

RS485-Verbindung

Entfernte Slave-Gerte

Serielle Slave-Gerte

12

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Gerteliste einrichten
Manahme
1. Klicken Sie im Setup-Men auf Gerteliste.

Ergebnis
Einblendung der Seite Gerteliste. (Abbildung 10 zeigt lokale Verbindungen und Abbildung 11 zeigt entfernte Verbindungen sofern verfgbar.)

2. Fr die Suche nach lokal angeschlossenen Einblendung der Seite Gerteerkennung fr Gerten knnen Sie Erkennung die Erkennung aller lokal angeschlossenen verwenden (siehe Gerteerkennung auf Gerte. Seite 15). Wenn die Konfiguration entfernter Gerte erforderlich ist, fahren Sie mit Schritt 3 fort. 3. Beachten Sie Abbildung 11 auf Seite 14 und whlen Sie die Anzahl der anzeigbaren Gerte aus (1 bis 64). 4. Whlen Sie die Verbindung aus der Dropdown-Liste aus.* 5. Whlen Sie den Gertetyp aus der Dropdown-Liste aus.* 6. Geben Sie in das Textfeld Gertebezeichnung den Namen des Gerts ein. Auswahl der Anzahl sichtbarer Standorte, die zur Definition der an das EGX angeschlossenen Gerte benutzt werden knnen. Auswahl der Verbindung. Auswahl des Gertetyps. Eingabe der Gertebezeichnung.

7. Geben Sie in das Textfeld Lokale ID die Eingabe der lokalen Adresse des Gerts. Adresse des seriellen Slave-Gertes ein, wenn es am seriellen Port angeschlossen ist, bzw. die Adresse, die Sie fr den Zugriff auf ein entferntes Gert verwenden mchten.* 8. Geben Sie in das Textfeld Fern-ID die Adresse des entfernten Gerts ein.* 9. Wiederholen Sie die Schritte 4 bis 8, bis alle Gerte eingegeben sind. 10. Klicken Sie auf bernehmen. Eingabe der Adresse des entfernten Gerts. Eingabe aller angeschlossenen Gerte. Aktualisierung der Einstellungen in der Gerteliste.

* Dieser Konfigurationsparameter kann nur verndert werden, wenn die Datenaufzeichnung fr das zu aktualisierende Gert deaktiviert ist. Siehe Gerteaufzeichnung auf Seite 17.

Abbildung 10: Seite Gerteliste

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

13

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Abbildung 11: Seite Gerteliste mit untersttzten Fernverbindungen

Tabelle 7: Gertelisteneinstellungen
Option
Anzahl anzuzeigende Gerte Verbindung

Beschreibung

Einstellung

Auswahl der Anzahl anzuzeigender Gerte. 1 bis 64 Werkeinstellung: 8 Auswahl des Verbindungsstandortes. Serielle Schnittstelle oder IPAdresse Werkeinstellung: Serielle Schnittstelle Bereich untersttzter Gerte

Gertetyp

Auswahl des Gertetyps, der in der Liste erscheinen soll.

Gertebezeichnung Ermglicht die Bezeichnung einzelner Gerte. Lokale ID Fern-ID Sie mssen die Lokale ID festlegen. Sie mssen die Fern-ID festlegen.

14

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Gerteerkennung

Mit der Option Gerteerkennung kann das EGX an der seriellen Schnittstelle angeschlossene Modbus-Gerte erkennen, die nicht in der Gerteliste enthalten sind. Gerte, die vorher in die Gerteliste eingetragen wurden, werden unabhngig vom eingestellten Erkennungsbereich berprft. Erkennung Zu Beginn der Gerteerkennung fragt das EGX den lokalen seriellen Port mit einem benutzerdefinierten Adressenbereich ab (siehe Abbildung 12 auf Seite 16). Fr die Erkennung an der seriellen Schnittstelle wird je nach deren aktueller Konfiguration das Modbus ASCII- oder das RTU-Protokoll benutzt. Wenn das Gert auf die Anfrage antwortet, wird die lokale ID auf die aktuelle Erkennungsadresse gesetzt und dem Gert wird ein voreingestellter Gertename zugewiesen. Das EGX versucht dann, den Gertetyp zu erkennen. Wenn das EGX den Typ des erkannten Gerts identifiziert, wird die Bezeichnung des erkannten Gertetyps in das Feld Gertetyp eingetragen. Kann das EGX den Gertetyp nicht identifizieren, wird das Feld Gertetyp auf die Werkeinstellung Modbus gesetzt. Ein Statusfeld zeigt den Erkennungsstatus an. berprfung Whrend des Erkennungsvorgangs werden alle vorher definierten Eintrge in der Gerteliste fr alle Verbindungen (serielle und Fernverbindungen innerhalb und auerhalb des Erkennungsbereichs zwischen Start- und Endadresse) berprft. Das berprfungsprotokoll der seriellen Verbindung wird durch die aktuelle Konfiguration des Gerts in der Gerteliste bestimmt. Fr die berprfung entfernter Gerte wird das Modbus-TCP/IPProtokoll benutzt. Das EGX zeigt die lokale ID, die gespeicherte Gertebezeichnung sowie den gespeicherten Gertetyp aus der Gerteliste an und fragt danach das Gert ab. Der durch die Abfrage erkannte Gertetyp wird angezeigt und danach mit der vorangegangenen Definition verglichen. Der Status zeigt dann an, ob eine Abweichung erkannt wurde oder ob die vorher definierte Konfiguration gltig ist. HINWEIS: Sie knnen die Gertebezeichnung und den Gertetyp bearbeiten und einzeln auswhlen, welche Gerte in der Gerteliste gespeichert werden sollen. Wenn allerdings die Aufzeichnung fr ein Gert aktiviert ist, knnen Sie nur die Bezeichnung ndern.
Manahme
1. Klicken Sie im Setup-Men auf Gerteliste.

Ergebnis
Einblendung der Seite Gerteliste.

2. Klicken Sie fr die Erkennung lokal angeschlossener Einblendung der Seite Gerte auf Erkennung. Gerteerkennung. 3. Geben Sie eine Startadresse und eine Endadresse Eingabe des Adressenbereichs fr ein. die Erkennung. HINWEIS: Gerte, die zuvor in die Gerteliste mit Adressen (lokale IDs) auerhalb des Erkennungsbereichs eingetragen wurden, werden berprft. 4. Klicken Sie auf Erkennung starten (um den Prozess Beginn der Erkennung aller anzuhalten, klicken Sie auf Erkennung anhalten). angeschlossenen und definierten Gerte. HINWEIS: Mit der Erkennungsfunktion werden nur lokale, serielle Modbus-Gerte, die an das EGX angeschlossen sind, gefunden. Entfernte Gerte mssen manuell hinzugefgt werden. Siehe Verbindungen zu entfernten Gerten auf Seite 10. 5. Geben Sie eine neue Gertebezeichnung in das Textfeld Name ein. 6. Aktivieren Sie das Kontrollkstchen Speichern neben dem Gert, das Sie in der Gerteliste speichern mchten. 7. Klicken Sie auf der Seite Gerteerkennung auf bernehmen. Damit wird das Gert umbenannt. Auswahl der zu speichernden oder zu entfernenden Gerteeintrge bzw. Aufheben dieser Auswahl. Damit wird die Gertekonfiguration aller fr die Speicherung markierten Gerte in der Gerteliste gespeichert.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

15

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Abbildung 12: Gerteerkennung

Tabelle 8: Optionen der Gerteerkennung


Option Beschreibung Einstellung
1 bis 247 Werkeinstellung: Start: 1 Ende: 10 Aktiviert oder Deaktiviert Werkeinstellung: Aktiviert

Start-/Endadresse Legt den Modbus-Adressenbereich fest, der fr die Erkennung von Gerten am seriellen Port des EGX benutzt wird. Speichern Verbindung Damit knnen Sie das ausgewhlte Gert in der Gerteliste speichern.

Anzeige der Verbindung, auf der das Gert Serielle Schnittstelle oder IPerkannt oder berprft wurde. Adresse (fr die berprfung entfernter Gerte). Anzeige des Gertetyps, der fr das entsprechende Gert festgelegt wurde. Damit knnen Sie den Gertetyp aus einer Dropdown-Liste zuweisen. Hier knnen Sie einen benutzerdefinierten Namen fr das Gert eingeben. Anzeige der lokalen ID. Anzeige der Fern-ID. Anzeige des Erkennungs- oder berprfungsstatus. Gltig, Unbekannt, Fehlgeschlagen, Gefunden, Erkennung oder Versuch

Definiert Zugewiesen Name Lokale ID Fern-ID Status

16

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Gerteaufzeichnung

Die Aufzeichnung ist fr jeden durch das EGX untersttzten Gertetyp verfgbar. Das EGX kann Daten aufzeichnen, die von angeschlossenen lokalen und entfernten Gerten in vordefinierten Intervallen (5, 10, 15, 20, 30 und 60 Minuten) empfangen werden. Nachfolgend wird erlutert, wie das EGX Daten aufzeichnet und wie die Aufzeichnung fr ein Gert eingerichtet wird. Viele Gerte in einem Leistungsberwachungssystem knnen keine Daten in einem nichtflchtigen Speicher ablegen. Das EGX300 bietet Datenaufzeichnung fr bis zu 64 seriell und entfernt angeschlossenen Gerten in vordefinierten Intervallen. Das EGX legt die aufgezeichneten Daten in nichtflchtigen FIFO-Dateien (First In First Out) ab. Die Aufzeichnungskapazitt jeder Datenprotokolldatei ist unterschiedlich und hngt vom ausgewhlten Aufzeichnungsintervall ab. Die Aufzeichnungskapazitt jeder Datenprotokolldatei kann durch Division der maximal mglichen Anzahl von Aufzeichnungsintervallen, die eine Datenprotokolldatei enthalten kann (171.072), durch das Produkt aus der Anzahl der aufgezeichneten Gren und den pro Tag aufgezeichneten Intervallen berechnet werden.
Protokolldateikapazitt = Intervalle (max.) / (Gren pro Intervall * pro Tag aufgezeichnete Intervalle)

Intervalldatenaufzeichnung

Beispiel: Die Aufzeichnungskapazitt fr ein Gertedatenprotokoll mit Aufzeichnung von drei Gren alle 10 Minuten wrde wie folgt bestimmt:
Pro Tag aufgezeichnete Intervalle = Minuten pro Tag / Aufzeichnungsintervalle (in Minuten) = 1440 / 10 = 144 Intervalle Protokolldateikapazitt = maximal mgliche Intervalle / (aufgezeichnete Gren pro Intervall * pro Tag aufgezeichnete Intervalle) = 171072 / (3 * 144) = 396 Tage

Die Aufzeichnungskapazitt wird dynamisch berechnet und auf der Grenauswahlseite (fr Beispiele siehe Tabelle 9) angezeigt. Tabelle 9: Beispiele fr Aufzeichnungsintervalle
Anzahl der Gren Aufzeichnungskapazitt (in Tagen) fr bestimmte Aufzeichnungsintervalle 5-Minuten-Intervall 10-Minuten-Intervall 15-Minuten-Intervall 1 2 3 4 5 6 594 297 198 148 118 99 1188 594 396 297 237 198 1782 891 594 445 356 297

Intervallaufzeichnung einrichten

Fr jedes Gert in der Gerteliste kann die Aufzeichnung separat aktiviert werden. Die aufzuzeichnenden Gren sind fr jedes Gert eindeutig. Informationen ber die Anzeige der Intervalldatenprotokolle finden Sie unter Gerteaufzeichnung auf Seite 41. HINWEIS: Fr die Aktivierung der Gerteaufzeichnung muss im DropdownFenster Aufzeichnungsintervall ein Zeitwert ausgewhlt werden. Es wird empfohlen, die Aufzeichnungsfunktion whrend der Konfiguration eines Gerts zu deaktivieren. Beachten Sie dazu Abbildung 13 auf Seite 18 und deaktivieren Sie das Kontrollkstchen Protokollierung fr das ausgewhlte Gert.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

17

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Manahme
1. Klicken Sie im Setup-Men auf Gerteaufzeichnung (siehe Abbildung 13).

Ergebnis
Einblendung der Seite fr die Gerteaufzeichnung.

2. Beachten Sie Abbildung 13 und aktivieren Sie die Auswahl der zu protokollierenden Gerte. Option Protokollierung bei den Gerten, die Sie protokollieren mchten: Um alle Gerte auszuwhlen, klicken Sie auf Alle auswhlen und anschlieend auf bernehmen. Um die Auswahl aller Gerte aufzuheben, klicken Sie auf Lschen und anschlieend auf bernehmen. 3. Whlen Sie das Aufzeichnungsintervall aus. 4. Klicken Sie auf bernehmen. Auswahl des Aufzeichnungsintervalls fr die ausgewhlten Gerte. Aktualisierung der EGX-Einstellungen fr die Gerteaufzeichnung.

OPTIONEN Um den Aufzeichnungsinhalt anzupassen, aktivieren Sie die Gerteaufzeichnung und fhren Sie anschlieend folgende Schritte aus: 1. Whlen Sie ein Aufzeichnungsintervall ungleich null aus und deaktivieren Sie das jeweilige Kontrollkstchen Gerteaufzeichnung des Gerts. 2. Klicken Sie fr das Gert, das Sie konfigurieren mchten, unter Anpassen auf Gren. 3. Beachten Sie Abbildung 14 auf Seite 19 und aktivieren Sie die Gren, die Sie aufzeichnen mchten: Um alle Gren auszuwhlen, klicken Sie auf Alle auswhlen und anschlieend auf bernehmen. Um die Auswahl aller Gren aufzuheben, klicken Sie auf Lschen und anschlieend auf bernehmen. Um die Standardgren auszuwhlen, klicken Sie auf Standardwerte unten im Bildschirm. Damit werden die aufzuzeichnenden Gertegren ausgewhlt. Danach erfolgt die Rckkehr zur Seite Gerteaufzeichnung. HINWEIS: Wenn Sie die Standardgren ndern, die fr ein Gert aufgezeichnet werden, erscheint neben Gren in der Spalte Anpassen fr dieses Gert ein Sternchen (*). Durch die Vernderung der Gren eines bereits aktiven Gerteprotokolls werden alle vorher aufgezeichneten Daten fr dieses Gert gelscht. Bei Bedarf sollten die Daten vor den nderungen aus dem EGX abgerufen werden.

Um ein Datenprotokoll zu lschen, aktivieren Sie Daten Auswahl der zu lschenden lschen fr die Datenprotokolle, die Sie lschen mchten: Datenprotokolle. HINWEIS: Damit ein 1. Um alle Gerte auszuwhlen, klicken Sie auf Alle Datenprotokoll gelscht werden auswhlen und anschlieend auf bernehmen. kann, darf das Kontrollkstchen 2. Um die Auswahl aller Gerte aufzuheben, klicken Sie Protokollierung des Gerts nicht auf Lschen und anschlieend auf bernehmen. aktiviert sein. Um die Aufzeichnung zu deaktivieren, whlen Sie ein Damit wird die Aufzeichnungsfunktion ausgeschaltet. Aufzeichnungsintervall gleich null aus. Die Aufzeichnungsoptionen mssen deaktiviert sein. Klicken Sie anschlieend auf bernehmen.

Abbildung 13: Seite Gerteaufzeichnung

Aufzuzeichnende Gren

Gren fr die Aufzeichnung knnen fr jedes Gert einzeln ausgewhlt werden.


Manahme Ergebnis
1. Klicken Sie auf der Seite Gerteaufzeichnung auf den Link Anzeige der Grenauswahlseite. Gren fr das gewnschte Gert. 2. Beachten Sie Abbildung 14 auf Seite 19 und aktivieren Sie die Gre(n), die Sie aufzeichnen mchten: Um alle Gren auszuwhlen, klicken Sie auf Alle auswhlen. Um die Auswahl aller Gren aufzuheben, klicken Sie auf Lschen. Um die voreingestellten Gren auszuwhlen, klicken Sie auf Standardwerte. 3. Klicken Sie auf bernehmen. Auswahl der zu protokollierenden Gren.

Speicherung der Auswahl der zu protokollierenden Gren.

18

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Abbildung 14: Grenauswahlseite

Gerteprotokollexport

Mit dieser Option knnen Sie Gerteprotokolle auf dreierlei Art exportieren: ber E-Mail, FTP oder HTTP. In den folgenden Abschnitten werden beide Methoden beschrieben. HINWEIS: Wenn sich die E-Mail-, FTP- oder HTTP-Server nicht auf demselben Ethernet-Netzsegment wie das EGX befinden, muss das EGXStandard-Gateway ordnungsgem konfiguriert sein. Siehe Ethernet- und TCP/IP-Einstellungen auf Seite 5.

E-Mail-Export
Manahme
1. Klicken Sie auf der Setup-Seite auf Gerteprotokollexport. 2. Whlen Sie E-Mail als bertragungsart. 3. Aktivieren Sie das Kontrollkstchen Inkrementell.

Ergebnis
Einblendung der Seite fr den Gerteprotokollexport. Anzeige der Exportoptionen fr das Gerteprotokoll ber E-Mail.

Hiermit werden nur neue, seit dem letzten erfolgreichen Datenexport HINWEIS: Wenn die bertragung Stndlich oder zum aufgezeichnete Intervalldaten Aufzeichnungsintervall geplant ist, wird das ausgewhlt. Kontrollkstchen Inkrementell automatisch aktiviert.

HINWEIS: Wenn das Kontrollkstchen Inkrementell nicht aktiviert ist, wird die gesamte Protokolldatei in jedem geplanten Intervall ber einen E-Mail-Anhang bertragen. 4. Whlen Sie Stndlich, Tglich, Wchentlich, Monatlich oder Aufzeichnungsintervall aus. Festlegung, wie oft Datenprotokolle bertragen werden sollen.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

19

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Manahme
5. Whlen Sie je nach Auswahl der Optionen im vorangegangenen Schritt die Tageszeit, den Wochentag und/oder den Tag des Monats. 6. Geben Sie in das Textfeld Von Adresse die E-MailAdresse der Person ein, die das Gert verwaltet. HINWEIS: Eine Absenderadresse ist notwendig, weil die meisten SMTP-Server sie verlangen. 7. Geben Sie in die Textfelder Zu Adresse die E-MailAdressen (max. 5) der Empfnger der Datenprotokolle ein (eine Adresse pro Textfeld). 8. Geben Sie in die Textfelder Server-IP-Adresse die Adresse des Ausgangs-E-Mail-Servers (0.0.0.0 bis 255.255.255.255) ein. HINWEIS: Wenden Sie sich an Ihren Netzwerkadministrator, wenn Sie die Adresse des SMTP-Servers nicht kennen.

Ergebnis
Festlegung, wann Datenprotokolle bertragen werden sollen. Eingabe des Absenders der E-Mail.

Eingabe der E-Mail-Adressen der Empfnger. Eintrag der Adresse des Servers, der Datenprotokolle ber E-Mail versendet.

9. Geben Sie im Textfeld Server-TCP-Port die Eintrag der Sendeschnittstelle des Sendeschnittstelle fr den Ausgangs-E-Mail-Server ein. Ausgangs-E-Mail-Servers. Werkeinstellung: 25 10. Wenn der SMTP-Server Anmeldedaten erfordert, aktivieren Sie das Kontrollkstchen SMTP-Server erfordert Anmeldung. HINWEIS: Das EGX untersttzt die Zugangsauthentifizierungen Plain, Login, CRAMMD5 und Digest-MD5. 11. Wenn Sie das Kontrollkstchen SMTP-Server erfordert Aufzeichnung Ihrer Anmeldedaten Anmeldung aktiviert haben, geben Sie den fr den SMTP-Server. Benutzernamen und das Kennwort in die Textfelder ein. 12. Klicken Sie auf Test-E-Mail, um eine Test-E-Mail mit den von Ihnen eingestellten Parametern zu versenden, oder klicken Sie auf bernehmen. HINWEIS: Durch das Anklicken von Test-E-Mail werden die E-Mail-Einstellungen fr den Export des Protokolls bernommen und eine Test-E-Mail gesendet. Wird bernehmen angeklickt, werden nur die Einstellungen bernommen. Senden einer Test-E-Mail und/oder bernehmen der E-MailEinstellungen fr den Protokollexport. Ermglicht die Eingabe von Anmeldedaten fr den SMTPServer.

Abbildung 15: Seite Gerteprotokollexport E-Mail

20

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

FTP-Export
Manahme
1. Klicken Sie auf der Setup-Seite auf Gerteprotokollexport. 2. Whlen Sie FTP als bertragungsart. 3. Aktivieren Sie das Kontrollkstchen Inkrementell. HINWEIS: Wenn die bertragung Stndlich oder zum Aufzeichnungsintervall geplant ist, wird das Kontrollkstchen Inkrementell automatisch aktiviert. HINWEIS: Wenn das Kontrollkstchen Inkrementell nicht aktiviert ist, wird die gesamte Protokolldatei in jedem geplanten Intervall ber FTP bertragen. 4. Whlen Sie Stndlich, Tglich, Wchentlich, Monatlich oder Aufzeichnungsintervall aus. 5. Whlen Sie je nach Auswahl der Optionen im vorangegangenen Schritt die Tageszeit, den Wochentag und/oder den Tag des Monats.

Ergebnis
Einblendung der Seite fr den Gerteprotokollexport. Einblendung der Optionen fr den Export des Gerteprotokolls ber FTP. Hiermit werden nur neue, seit dem letzten erfolgreichen Datenexport aufgezeichnete Daten fr das Senden ausgewhlt.

Festlegung, wie oft Datenprotokolle bertragen werden sollen. Festlegung, wann Datenprotokolle bertragen werden sollen.

Eintrag der Adresse des Servers, der 6. Geben Sie in die Textfelder Server-IP-Adresse die Adresse des Ausgangs-FTP-Servers (0.0.0.0 die Datenprotokolle bertrgt. bis 255.255.255.255) ein. HINWEIS: Wenden Sie sich an Ihren Netzwerkadministrator, wenn Sie die Adresse des FTP-Servers nicht kennen. 7. Geben Sie im Textfeld Verzeichnis das Verzeichnis ein. Eingabe von Verzeichnisinformationen fr den entfernten Server.

8. Geben Sie in die Textfelder Ihren Benutzernamen Aufzeichnung Ihrer Serverund das Kennwort ein. Anmeldedaten. 9. Aktivieren Sie das Kontrollkstchen Passiv. 10. Wenn Sie Daten zur StruxureWare Energy Operation exportieren, aktivieren Sie das Kontrollkstchen MAC-Adresse an Dateinamen anhngen. HINWEIS: Die Aktivierung dieses Kontrollkstchens verhindert das Zusammenfhren von Daten, wenn zwei Dateien mit dem gleichen Namen an die Energy Operation gesendet werden. Fr Einzelheiten zum Protokolldateiformat siehe Abrufen eines Datenprotokolls auf Seite 43. 11. Klicken Sie auf FTP prfen, um die von Ihnen eingestellten FTP-Parameter zu berprfen, oder klicken Sie auf bernehmen. HINWEIS: Durch das Anklicken von FTP prfen werden die FTP-Einstellungen fr den Export des Protokolls bernommen und eine Testdatei bertragen. Wird bernehmen angeklickt, werden nur die Einstellungen bernommen. bertragung einer Testdatei an den FTP-Server und das Verzeichnis und/oder bernehmen der FTPEinstellungen. Passiveinstellung des FTPDateibertragungsmodus. Hinzufgung der MAC-Adresse fr die Erstellung eines unverwechselbaren Dateinamens.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

21

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Abbildung 16: Seite Gerteprotokollexport FTP

HINWEIS: Wenn die bertragung Stndlich oder zum Aufzeichnungsintervall geplant ist, wird das Kontrollkstchen Inkrementell automatisch aktiviert.

22

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

HTTP-Export
Manahme
1. Klicken Sie auf der Setup-Seite auf Gerteprotokollexport. 2. Whlen Sie HTTP als bertragungsart. 3. Aktivieren Sie das Kontrollkstchen Inkrementell. HINWEIS: Wenn die bertragung Stndlich oder zum Aufzeichnungsintervall geplant ist, wird das Kontrollkstchen Inkrementell automatisch aktiviert. HINWEIS: Wenn das Kontrollkstchen Inkrementell nicht aktiviert ist, wird die gesamte Protokolldatei in jedem geplanten Intervall ber HTTP bertragen. 4. Whlen Sie Stndlich, Tglich, Wchentlich, Monatlich oder Aufzeichnungsintervall aus. Festlegung, wie oft Datenprotokolle bertragen werden sollen.

Ergebnis
Einblendung der Seite fr den Gerteprotokollexport. Einblendung der Optionen fr den Export des Gerteprotokolls ber HTTP. Hiermit werden nur neue, seit dem letzten erfolgreichen Datenexport aufgezeichnete Daten fr das Senden ausgewhlt.

5. Whlen Sie je nach Auswahl der Optionen Festlegung, wann Datenprotokolle bertragen im vorangegangenen Schritt die Tageszeit, werden sollen. den Wochentag und/oder den Tag des Monats. 6. Geben Sie in die Textfelder Server-IPAdresse die Adresse des HTTP-Servers ein. HINWEIS: Wenden Sie sich an Ihren Netzwerkadministrator, wenn Sie die Adresse des HTTP-Servers nicht kennen. 7. Geben Sie im Textfeld Server-TCP-Port die HTTP-Server-Schnittstelle ein. HINWEIS: Wenn Sie mit SSLVerschlsselung exportieren mchten, geben Sie die TCP-Port-Nummer des HTTPS-Servers ein, die normalerweise 443 lautet. 8. Wenn Sie einen Proxyserver verwenden, Eintrag der IP-Adresse des Proxyservers, der geben Sie die IP-Adresse in die Textfelder die Datenprotokolle bertrgt. fr die IP-Adresse des Proxyservers ein. HINWEIS: Wenden Sie sich an Ihren Netzwerkadministrator, wenn Sie die Adresse Ihres Proxyservers nicht kennen. 9. Geben Sie im Textfeld Proxyserver-TCP- Eingabe des Ausgangs-TCP-Ports. Port die HTTP-Server-Schnittstelle ein. Werkeinstellung: 0 HINWEIS: Wenn Sie mit SSLVerschlsselung exportieren mchten, geben Sie die TCP-Port-Nummer des HTTPS-Servers ein, die normalerweise 443 lautet. 10. Geben Sie im Textfeld Pfad den Pfad zu Eingabe des Server-Script-Pfads. dem Server-Script ein, das der Webserver ausfhrt, nachdem das EGX Daten an ihn gesendet hat. 11. Geben Sie in das Feld Feldname den Mglichkeit der bertragung von Dateien vom Namen ein, unter dem der Webserver den EGX an ein vorhandenes WWW-Server-Script. Dateinamen erwartet. HINWEIS: Ist das nicht erforderlich, verwenden Sie den Standardwert datafile1. 12. Geben Sie in das Feld Hostname den Domnennamen des Hosts ein. Erkennung eines bestimmten Hosts auf dem WWW-Server, wenn er mehrere Domnen unter einer einzigen IP-Adresse aufnimmt (Voreinstellung ist leer). Aufzeichnung Ihrer Server-Anmeldedaten. Eingabe des Ausgangs-TCP-Ports. Werkeinstellung: 80 Eintrag der IP-Adresse des Servers, der die Datenprotokolle bertrgt.

13. Geben Sie in die Textfelder Ihren Benutzernamen und das Kennwort ein.

14. Wenn Sie mit SSL-Verschlsselung Alle Gerteprotokolle, die ber HTTP exportiert exportieren mchten, aktivieren Sie SSL. werden, verwenden dann die SSLVerschlsselung (HTTPS).

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

23

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Manahme

Ergebnis

15. Wenn Sie Daten zur StruxureWare Energy Hinzufgung der MAC-Adresse fr die Operation exportieren, aktivieren Sie das Erstellung eines unverwechselbaren Kontrollkstchen MAC-Adresse an Dateinamens. Dateinamen anhngen. HINWEIS: Die Aktivierung dieses Kontrollkstchens verhindert das Zusammenfhren von Daten, wenn zwei Dateien mit dem gleichen Namen an die Energy Operation gesendet werden. Fr Einzelheiten zum Protokolldateiformat siehe Abrufen eines Datenprotokolls auf Seite 43. 16. Klicken Sie auf HTTP prfen, um die von Ihnen eingestellten HTTP-Parameter zu berprfen, oder klicken Sie auf bernehmen. HINWEIS: Durch Anklicken von HTTP prfen werden die HTTP-Einstellungen fr den Protokollexport bernommen und es wird eine Testdatei bertragen. Mit dem Klicken auf bernehmen werden nur die Einstellungen bernommen. bertragung einer Testdatei an den HTTPServer und das Verzeichnis und/oder bernehmen der HTTP-Einstellungen.

Abbildung 17: Seite Gerteprotokollexport HTTP

Datum und Uhrzeit

Mit der Seite Datum und Uhrzeit knnen Sie das Datum und die Uhrzeit fr das EGX einstellen.
Manahme Ergebnis

1. Klicken Sie im Setup-Men auf Datum und Einblendung der Seite Datum und Uhrzeit. Uhrzeit. 2. Konfigurieren Sie Jahr, Monat, Tag, Stunden, Minuten und Sekunden. 3. Whlen Sie den Zeitzonenausgleich. 4. Damit sich die Uhr automatisch auf die Sommerzeit umstellt, aktivieren Sie das Kontrollkstchen Automatische Sommerzeiteinstellung aktivieren. Einstellung des Datums und der Uhrzeit des Systems. Einstellung der Uhr auf die gewhlte Zeitzone. Einstellung der Uhr auf automatische Umstellung auf Sommerzeit.

5. Geben Sie den Tag im Monat, den Einstellung des Beginns und Endes der Wochentag, den Monat und die Stunde fr Sommerzeitumstellung. Beginn und Ende der Sommerzeit ein. 6. Klicken Sie auf bernehmen. Speicherung der Datums- und Uhrzeiteinstellungen.

24

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Abbildung 18: Seite Datum und Uhrzeit

Netzwerkzeitsynchronisation

Mit der Aktivierung der Netzwerkzeitsynchronisation kann die Uhrzeit und das Datum der EGX-Systemuhr durch einen NTP-Server (Network Time Protocol) eingestellt werden. HINWEIS: Wenn sich der NTP-Server nicht auf demselben EthernetNetzsegment wie das EGX befindet, achten Sie auf die richtige Konfiguration des EGX-Standard-Gateway.

Manahme
1. Markieren Sie das Kontrollkstchen Netzwerkzeitsynchronisation aktivieren auf der Seite Datum und Uhrzeit.

Ergebnis
Einblendung des SNTPParameterabschnitts und der letzten erfolgreichen Zeitsynchronisation.

2. Konfigurieren Sie die Zeitzonenabweichung, das Einstellung der SNTP-Parameter. Aufrufintervall und die IP-Adresse des primren und sekundren NTP-Servers (siehe Abbildung 10 auf Seite 26). 3. Klicken Sie auf bernehmen. Speicherung der SNTP-Einstellungen.

Abbildung 19: Netzwerkzeitsynchronisation aktivieren

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

25

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Tabelle 10: Einstellung der SNTP-Parameter


Option
Zeitzonenausgleich

Beschreibung
Zeiteinstellung auf der Basis des gewhlten Werts der Coordinated Universal Time (UTC). Damit knnen Sie den Beginn und das Ende der Sommerzeit festlegen.

Einstellung
UTC12:00 bis UTC+13:00 Werkeinstellung: UTC (GMT) Erster bis Fnfter oder letzter, Sonntag bis Samstag, Januar bis Dezember, 0:00 bis 23:00 Werkeinstellung: Beginn am zweiten Sonntag im Mrz um 2:00 Uhr Ende am zweiten Sonntag im November um 2:00 Uhr 1 Stunde bis 1 Woche Werkeinstellung: 1 Woche 0.0.0.0 bis 255.255.255.255 Werkeinstellung: 0.0.0.0 0.0.0.0 bis 255.255.255.255 Werkeinstellung: 0.0.0.0

Automatische Sommerzeiteinstellung aktivieren

Abrufintervall

Steuerung, wie oft das EGX den NTPServer wegen der richtigen Uhrzeit kontaktiert. Die IP-Adresse des primren NTPServers, den das EGX nach der richtigen Uhrzeit fragt. Die IP-Adresse des sekundren NTPServers, den das EGX nach der richtigen Uhrzeit fragt.

IP-Adresse des primren NTPServers IP-Adresse des sekundren NTPServers

SNMP-Parameter

Das EGX untersttzt das Protokoll SNMP, mit dem der Netzwerkadministrator mit einem SNMP-Manager auf ein entferntes EGX zugreifen und den Netzwerkstatus sowie die Diagnosedaten des EGX im MIB-II-Format anzeigen kann.
Manahme Ergebnis

1. Klicken Sie im Setup-Men auf SNMP-Parameter. Einblendung der SNMPParameterseite. 2. Markieren Sie SNMP aktivieren, um das Simple Network Management Protocol einzuschalten. Aktivierung von SNMP.

3. Geben Sie den Systemverantwortlichen, die Eingabe der SNMPSystembezeichnung, den Systemstandort, den Systeminformationen und der Community-Namen mit schreibgeschtztem Zugriff Community-Zugriffsnamen. und den Community-Namen mit Lese- und Schreibzugriff ein. 4. Klicken Sie auf bernehmen. Speicherung der SNMP-Einstellungen.

Abbildung 20: Seite SNMP-Parameter

26

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Modbus-TCP/IP-Filter

Mit dieser Funktion kann der Administrator die Zugangsstufe zuweisen, die Modbus-TCP/IP-Clients auf die an das EGX angeschlossenen Gerte (lokal oder entfernt) haben. HINWEIS: Der anonymen Modbus-TCP/IP-Adresse (***.***.***.***) knnen die Zugriffsberechtigungen Schreibgeschtzt oder Keine zugewiesen werden. Die Einstellung Schreibgeschtzt erlaubt jedem Modbus-TCP/IPClient, der nicht in der Filterliste enthalten ist, den Zugriff auf serielle SlaveGerte mit der Zugriffsberechtigung Schreibgeschtzt. Die Einstellung Keine blockiert alle Modbus-TCP/IP-Clients, die nicht in der Filterliste enthalten sind.
Manahme
1. Klicken Sie im Setup-Men auf ModbusTCP/IP-Filter. 2. Markieren Sie Filter aktivieren. 3. Geben Sie in der Spalte IP-Adresse die Modbus-TCP/IP-Client-Adresse ein.

Ergebnis
Einblendung der Seite Modbus-TCP/IP-Filter. Aktivierung der Filterung. Eingabe einer IP-Adresse fr einen ModbusTCP/IP-Client, der Zugriff auf die an das EGX angeschlossenen Gerte haben soll.

4. Whlen Sie in der Spalte Auswahl der Zugriffsberechtigung fr die Zugriffsberechtigung entweder entsprechende IP-Adresse. Fr die Einstellung Schreibgeschtzt oder Vollstndig aus. Schreibgeschtzt sind die folgenden ModbusTCP/IP-Funktionen erlaubt: Dezimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100 Hexadezimal: 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18, 2B, 64 5. Wiederholen Sie die Schritte 3 und 4, um weitere IP-Adressen hinzuzufgen. 6. Klicken Sie auf bernehmen. Hinzufgen weiterer IP-Adressen fr den Filter. Speicherung der Modbus-TCP/IP-AdressenFilterliste.

Abbildung 21: Seite Modbus-TCP/IP-Filter

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

27

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Unterlagenlinks

Das EGX untersttzt zwei Arten von Unterlagenlinks: 1. Zugriff auf lokale Dateien (im EGX gespeicherte Onboard-Unterlagen) 2. Zugriff auf externe URLs HINWEIS: Lokale Dateiunterlagen, die auf der Unterlagenwebseite erscheinen sollen, mssen mit FTP in den EGX-Ordner www/documentation (Unterlagen) bertragen werden.
Manahme
1. Klicken Sie im Setup-Men auf Unterlagenlinks. 2. Fr Dateizugriff: Aktivieren Sie das Kontrollkstchen Aktiviert fr die Dateinamenlinks, die Sie aktivieren mchten. Fr URL-Zugriff: Aktivieren Sie das Kontrollkstchen Aktiviert fr die URLLinks, die Sie aktivieren mchten. 3. Aktivieren Sie das Kontrollkstchen Neues Aktivierung derjenigen Dateien und URLs, die Fenster, wenn die ausgewhlten Dateien nach dem Anklicken in einem neuen Fenster und URLs nach dem Anklicken in einem angezeigt werden sollen. neuen Fenster angezeigt werden sollen. 4. Geben Sie in das Textfeld Link-Text einen Einstellung des Unterlagenlinktitels, der auf der Titel des Unterlagenlinks ein. Unterlagenseite erscheinen soll. 5. Klicken Sie auf bernehmen. Aktualisierung der Einstellungen fr die EGXUnterlagenlinks.

Ergebnis
Einblendung der Seite Unterlagenlinks. Aktivierung der Dateien und URLs, die auf der Unterlagenseite erscheinen sollen.

Abbildung 22: Seite Unterlagenlinks

HINWEIS: Informationen ber den Zugriff auf die geladenen Unterlagen finden Sie unter Unterlagen auf Seite 51.

28

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Benutzerkonten

EGX-Benutzern werden Benutzernamen und Kennwrter zugewiesen. Jeder Benutzer gehrt zu einer Gruppe, und jede Gruppe besitzt Zugriffsrechte auf die EGX-Webseiten, die vom EGX-Administrator zugewiesen wurden. HINWEIS: Zwei Benutzerkonten sind voreingestellt: Administrator (voreingestelltes Kennwort: Gateway) und Guest (Gast, voreingestelltes Kennwort: Guest).
Manahme
1. Klicken Sie im Setup-Men auf Benutzerkonten. 2. Wenn Sie einen Gruppennamen ndern wollen, geben Sie den neuen Namen in eines der Textfelder Gruppen ein (der AdministratorGruppenname kann nicht gendert werden). 3. Geben Sie im Bereich Benutzer einen Namen (1 bis 24 Zeichen) und ein Kennwort (0 bis 12 Zeichen) fr einen neuen Benutzer ein.

Ergebnis
Einblendung der Seite Benutzerkonten. Eingabe eines neuen Gruppennamens.

Eingabe des Namens und des Kennwortes fr einen Benutzer. Das EGX300 berprft die Sicherheit des Kennworts und zeigt diese durch einen HINWEIS: Benutzernamen und Kennwrter bercksichtigen Gro- und Kleinschreibung und Farb- sowie einen Textcode an: = kein Kennwort/Kennwort mit knnen nur alphanumerische Zeichen enthalten. Rot niedriger Sicherheit Gelb = Kennwort mit mittlerer Sicherheit Blau = Kennwort mit hoher Sicherheit Grn = Kennwort mit sehr hoher Sicherheit Auswahl der Gruppe und der Sprache fr einen Benutzer. Hinzufgen weiterer Benutzer.

4. Whlen Sie eine Gruppe und die Standardsprache fr den neuen Benutzer aus. 5. Wiederholen Sie die Schritte 3 und 4 fr jeden zustzlichen Benutzer, den Sie hinzufgen wollen. 6. Klicken Sie auf bernehmen.

Sicherung aller Benutzerkonteneinstellungen.

Tabelle 11: EGX-Konten und -Kennwrter


Konto
Administrator Guest

Werkeingestelltes Kennwort
Gateway Guest

Benutzerdefinierte Konten (bis zu 11 Konten mglich) Keine Werkeinstellung Kennwort ist benutzerdefiniert

Abbildung 23: Seite Benutzerkonten

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

29

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Webseitenzugriff
Manahme
1. Klicken Sie im Setup-Men auf Webseitenzugriff. 2. Whlen Sie die Zugriffsberechtigung (Keine, Schreibgeschtzt oder Vollstndig) aus, die jede Benutzergruppe auf die Webseiten haben soll.

Ergebnis
Einblendung der Seite Webseitenzugriff. Fr eine Erluterung der Zugriffsberechtigungen fr jede Gruppe siehe die nachstehende Tabelle 12.

3. Um einem Gast den Zugriff auf die Webseite zu Erlaubt der werkeingestellten Gruppe ermglichen, whlen Sie in der Spalte Guest die Guest den Zugriff auf die Webseite. Zugriffsberechtigung Schreibgeschtzt aus. HINWEIS: Wenn fr die Gruppe Guest die Zugriffsberechtigung Schreibgeschtzt eingestellt ist, kann als Zugriffsberechtigung fr die anderen Gruppen nur Schreibgeschtzt oder Vollstndig ausgewhlt werden. 4. Wiederholen Sie die Schritte 2 und 3 fr die Optionen in jedem Abschnitt. 5. Klicken Sie auf bernehmen. Auswahl der Zugriffsberechtigung fr jede Webseite. Speicherung der Kennworteinstellungen.

Tabelle 12: Gruppenzugriff


Gruppe
Administrator

Zugriff
Vollstndiger Zugriff auf alle Webseiten. HINWEIS: Aus Systemsicherheitsgrnden wird empfohlen, das werkeingestellte Administratorkennwort nach der ersten Anmeldung zu ndern. Schreibgeschtzter Zugriff auf ausgewhlte Webseiten.

Guest

Drei benutzerdefi- Durch Auswahl aus folgenden Optionen weist der Administrator jeder nierte Gruppen Gruppe bestimmte Webseiten-Zugriffsrechte zu. Es gibt folgende Zugriffsberechtigungen: Keine: eine Gruppe hat keinen Zugriff auf die ausgewhlte Webseite Schreibgeschtzt: das Kennwort gewhrt einer Gruppe nur Lesezugriff auf die ausgewhlte Webseite Vollstndig: eine Gruppe hat den gleichen Zugriff wie die AdministratorGruppe auf die ausgewhlte Webseite

Abbildung 24: Seite Webseitenzugriff

30

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Benutzerdefinierte Webseiten hinzufgen/entfernen

Benutzerdefinierte Webseiten und andere Dateien knnen von Ihrem Computer ber FTP auf das EGX bertragen werden. ber FTP in die Verzeichnisse www/monitoring (berwachung), www/maintenance (Wartung) oder www/control (Steuerung) bertragene Dateien mit den Erweiterungen .htm, .html oder .shtml werden automatisch gesichert. Fr jeden Ordner ist auf der Menleiste der Webschnittstelle ein entsprechender Link vorhanden. Wenn in der Menleiste der Link angeklickt wird, erscheinen die von Ihnen hinzugefgten Webseiten auf der linken Seite des Browserfensters unter Benutzerdefinierte Seiten. HINWEIS: In den Ordnern berwachung, Steuerung oder Wartung knnen keine neuen Ordner erstellt werden. Nach der bertragung von benutzerdefinierten Webseiten oder anderen Dateien ber FTP in das EGX knnen die Webseiten und Dateien mithilfe der Seite Webseiten hinzufgen/entfernen zur Webschnittstelle hinzugefgt werden bzw. von der Webschnittstelle entfernt werden, ohne sie im EGX zu lschen. Diese Seite wird von der Seite Webseitenzugriff aus geffnet.

Hinzufgen von Webseiten mit FTP


Manahme Ergebnis
1. Starten Sie Windows Explorer, geben Sie ftp:// und die Einblendung des Dialogfelds IP-Adresse des EGX (zum Beispiel ftp://169.254.0.10) in Anmelden als. das Adressentextfeld ein und drcken Sie die Eingabetaste. 2. Geben Sie in die Textfelder den Benutzernamen Administrator und das Administratorkennwort ein und klicken Sie auf Anmelden. Erffnung einer FTP-Sitzung mit dem EGX.

3. ffnen Sie ein neues Fenster in Windows Explorer, Kopiert die Datei in die gehen Sie zur benutzerdefinierten Webseite, die Sie an Zwischenablage. das EGX senden mchten, klicken Sie mit der rechten Maustaste darauf und klicken Sie anschlieend auf Kopieren. 4. Wechseln Sie zum EGX-Fenster in Windows Explorer, das Sie in Schritt 1 geffnet haben, und ffnen Sie anschlieend den Ordner, in den die Webseite kopiert werden soll (z. B. /www/monitoring/). 5. Klicken Sie mit der rechten Maustaste in das rechte Fenster in Windows Explorer und anschlieend auf Einfgen. HINWEIS: Anstelle von Kopieren und Einfgen knnen Sie die Datei auch per Drag-and-Drop in Windows Explorer bertragen. 6. Klicken Sie im Windows-Explorer-Fenster auf Schlieen. Schlieen von Windows Explorer. ffnet den Ordner, in dem die Webseite auf dem EGX gespeichert wird. Kopiert die benutzerdefinierte Webseite in das EGX.

Lschen von Webseiten mit FTP


Manahme Ergebnis
1. Starten Sie Windows Explorer, geben Sie ftp:// und die Einblendung des Dialogfelds IP-Adresse des EGX (zum Beispiel ftp://169.254.0.10) in Anmelden als. das Adressentextfeld ein und bettigen Sie anschlieend die Eingabetaste. 2. Geben Sie in die Textfelder den Benutzernamen Administrator und das Administratorkennwort ein und klicken Sie auf Anmelden. Erffnung einer FTP-Sitzung mit dem EGX.

3. ffnen Sie den Ordner, in dem die benutzerdefinierte ffnet den Ordner, in dem sich die Webseite gespeichert ist, klicken Sie mit der rechten benutzerdefinierte Webseite Maustaste auf die zu lschende Datei und anschlieend befindet, und lscht die Datei. auf Lschen. 4. Klicken Sie im Windows-Explorer-Fenster auf Schlieen. Schlieen von Windows Explorer.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

31

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Webseiten zur Webschnittstelle hinzufgen oder aus ihr entfernen

Manahme
1. Klicken Sie im Setup-Men auf Webseitenzugriff. 2. Klicken Sie auf Webseiten hinzufgen/entfernen (siehe Abbildung 25).

Ergebnis
Einblendung der Seite Webseitenzugriff. Einblendung der Seite Webseiten hinzufgen/entfernen.

3. Wenn Sie benutzerdefinierte Webseiten zu Auswahl oder Deaktivierung einer einem EGX-Ordner hinzugefgt haben, benutzerdefinierten Webseite. sehen Sie unter der jeweiligen Ordnerbezeichnung eine Liste mit den entsprechenden Dateinamen. Whlen Sie die Webseiten aus, die die Benutzer sehen sollen. Deaktivieren Sie die Webseiten, die Sie Ihren Benutzern nicht zeigen mchten. HINWEIS: Das Deaktivieren einer Webseite lscht diese nicht aus dem EGX. 4. Klicken Sie auf bernehmen. Hinzufgen einer benutzerdefinierten Webseite zur EGX-Webschnittstelle oder Entfernen einer benutzerdefinierten Webseite von der EGX-Webschnittstelle.

Abbildung 25: Seite Webseiten hinzufgen/entfernen

Prferenzen

Mit dieser Option kann jedes EGX einzeln angepasst werden.


Manahme
1. Klicken Sie im Setup-Men auf Prferenzen. 2. Geben Sie den Gertenamen, die voreingestellte Startseite, die EchtzeitAbtastrate und die Hufigkeit der Kommunikationsprfung ein. 3. Klicken Sie auf bernehmen.

Ergebnis
Einblendung der Seite Prferenzen. Einstellung der Prferenzen.

Aktualisierung der EGXPrferenzeinstellungen.

Abbildung 26: Seite Prferenzen

32

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Tabelle 13: Prferenzeinstellungen


Option
Gertename

Beschreibung
Hier knnen Sie einen benutzerdefinierten Namen fr das EGX und dazugehrige Gerte eingeben. Dieser Name wird im Banner der Webschnittstelle benutzt. Mglichkeit der Auswahl einer voreingestellten Startseite.

Einstellung
Werkeinstellung: Powerlogic EGX300

Voreingestellte Startseite

Startseite, Schaltkreisbersicht, Laststrombersicht, Strommittelwertbersicht, Leistungsbersicht oder Energiebersicht Werkeinstellung: Startseite 5 bis 60 Sekunden Werkeinstellung: 5 Sekunden Deaktiviert, 5 bis 30 Minuten Werkeinstellung: 15 Minuten

Echtzeit-Abtastrate

Steuert die Hufigkeit, mit der Daten aus den Gerten in die normalen berwachungstabellenansichten ausgelesen werden.

Hufigkeit der Kommu- Steuert, wie oft eine Kommunikationsnikationsprfung prfung durchgefhrt wird, whrend der Browser Echtzeitmesswerte in den normalen berwachungstabellenansichten anzeigt. Mit dieser Funktion wird versucht, alle auer Betrieb befindlichen Gerte automatisch wieder in Betrieb zu setzen.

Anzeigbare Gertetypen

Auf der Seite Anzeigbare Gertetypen knnen die Gertetypen verwaltet werden, die fr den Benutzer auf der Setup-Webseite Gerteliste zur Auswahl stehen. Da das EGX300 viele verschiedene Gertetypen untersttzt, kann das Entfernen von Gertetypen aus der Liste Verfgbare Gerte u. U. die Konfiguration der Setup-Webseite Gerteliste vereinfachen.
Manahme
1. Klicken Sie im Setup-Men auf Anzeigbare Gertetypen.

Ergebnis
Einblendung der Seite Anzeigbare Gertetypen.

2. Whlen Sie die Gertetypen aus, die fr die Konfiguration Auswahl von Gertetypen, die fr der Gerteliste verfgbar sein sollen. die Konfiguration der Gerteliste verfgbar sein sollen. HINWEIS: Klicken Sie auf Alle auswhlen, um alle Gerte zu aktivieren, bzw. auf Lschen, um alle Gerte zu deaktivieren. HINWEIS: Die Verfgbarkeit des Gertetyps kann bei gerade verwendeten Gerten nicht gendert werden. 3. Klicken Sie auf bernehmen. Speichern der Einstellungen fr Anzeigbare Gertetypen.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

33

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Abbildung 27: Seite Anzeigbare Gertetypen

Prfpfad

Der Prfpfad besteht aus einer Folge von Aufzeichnungen oder Meldungen mit Zeitstempel. Er zeichnet Konfigurationsnderungen, Fehler und fehlgeschlagene Authentifizierungen auf. Auerdem identifiziert er den Benutzer, der das Ereignis ausgelst hat. Verwenden Sie die Seite Prfpfad, um die vier Berichtsgruppen und die Meldungskanle einzurichten. Fr jeden Kanal sind die Berichtsgruppen auszuwhlen, fr die Meldungen angezeigt werden sollen. Wenn Sie eine Berichtsgruppe fr einen Kanal auswhlen, sehen Sie alle Meldungen, die in dieser Berichtsgruppe generiert werden. Folgende Meldungskanle stehen zur Verfgung:

Onboard-Wartungsprotokolldatei fr das EGX Entfernter Syslog-Server (Syslog ist ein Standard fr die Protokollierung von Meldungen) E-Mail

Alle Meldungen werden mit einem Zeitstempel versehen und enthalten die Berichtsgruppe sowie die Benutzeridentifikation. Die Seite Prfpfad ist in drei Bereiche unterteilt, die den drei Meldungskanlen entsprechen: Wartungsprotokoll, Syslog und E-Mail. (Siehe Abbildung 28 auf Seite 36.) Sie knnen die auf jedem Kanal bertragenen Meldungen separat konfigurieren. Klicken Sie im Fenster Setup auf Prfpfad. Die Seite Prfpfad wird angezeigt. Befolgen Sie die Anweisungen in der nachstehenden Tabelle.

34

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Tabelle 14: Prfpfadeinrichtung


Option
Wartungsprotokoll Steuerung der Meldungen werden im OnboardBerichtstypen, fr Wartungsprotokoll des EGX angezeigt, die Meldungen im sobald sie generiert werden. Meldungsprotokoll angezeigt werden sollen. Syslog Server-IP-Adresse Meldungen werden zu dem hier angegebenen Server weitergeleitet, sobald sie generiert werden. Server-UDP-Port (User Datagram Protocol) Bericht Geben Sie die IP-Adresse fr den entfernten Server ein, zu dem die Meldungen weitergeleitet werden sollen. Syslog-Meldungen werden ber diesen Geben Sie die UDP-PortServer-UDP-Port bertragen. Nummer fr diese IP-Adresse ein. Werkeinstellung = 514 Hier werden die vier Berichtstypen, fr die Aktivieren Sie die Berichtstypen, Meldungen weitergeleitet werden knnen, fr die Meldungen weitergeleitet werden sollen. ausgewhlt. Liefert einen groben Anhaltspunkt zum Whlen Sie die entsprechende Standort der Anlage, die die Meldung Kategorie aus. generiert hat. Diese Information wird im Syslog angezeigt. Informiert den Benutzer ber die Wichtigkeit Whlen Sie die entsprechende der Meldung. Sie mssen fr Ihre Anlage Kategorie aus. die Wichtigkeit jedes Typs bestimmen. Wenn Meldungen generiert werden, wird die E-Mail-Adresse des Absenders im Feld Von angezeigt. Der Hauptteil der E-Mail enthlt folgende Informationen: IP-Adresse des EGX, Berichtsgruppenname, Benutzername, IPAdresse des Benutzers und die Meldung von der Berichtsgruppe. Wenn Meldungen generiert werden, werden sie an die E-Mail-Adresse(n) des Empfngers bertragen. Geben Sie unter Von Adresse die E-Mail-Adresse des Absenders fr E-Mails ein. Es drfen maximal 49 Zeichen verwendet werden. Aktivieren Sie die Optionen, die im Bericht enthalten sein sollen. Werkeinstellung: keine Optionen aktiviert

Beschreibung

Einstellung

Dropdown-Liste Anlage

Dropdown-Liste Schwere E-Mail Von Adresse

Geben Sie unter Zu Adresse die E-Mail-Adresse des Empfngers aller Meldungs-EMails ein. Pro Adresse drfen maximal 49 Zeichen verwendet werden. Server-IP-Adresse Das ist die IP-Adresse des Servers, an Wenn keine Server-IP-Adresse den die E-Mails bertragen werden. eingegeben wird, werden keine E-Mails gesendet. Server-TCP-Port Das ist die TCP-Port-Nummer fr die Geben Sie die TCP-PortServer-IP-Adresse. Nummer ein. Die Werkeinstellung lautet 25. Markieren Sie das SMTP-Server Aktivieren Sie dieses Kontrollkstchen, erfordert um die Anmeldung fr den Empfang von Kontrollkstchen, um mit dem Anmeldung E-Mails zu aktivieren. Der SMTP-Server Hinzufgen von Anmeldedaten erfordert eine Anmeldung. zu beginnen. Benutzername Das ist der Benutzername, den das EGX Geben Sie den fr den SMTPverwendet, um sich beim SMTP-Server Server erforderlichen Benutzeranzumelden. namen ein (max. 31 Zeichen). Kennwort Das ist das Kennwort, welches vom EGX Geben Sie das fr den SMTPverwendet wird, um sich beim SMTPServer erforderliche Kennwort Server anzumelden. ein (max. 31 Zeichen). Bericht Das sind die Berichtstypen, fr die Aktivieren Sie die Meldungen weitergeleitet werden knnen. Berichtstypen, fr die Sie Sie knnen beliebig viele auswhlen. Meldungen haben mchten. Standardwerte/ Klicken Sie auf bernehmen, um die von Klicken Sie auf bernehmen bernehmen Ihnen vorgenommenen Eintrge zu oder auf Standardwerte. speichern. Klicken Sie auf Standardwerte, um jedes Feld auf seine Werkeinstellung zurckzusetzen.

Zu Adresse

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

35

PowerLogicTM Ethernet Gateway EGX300 Setup

63230-319-216B4_DE 06/2013

Abbildung 28: Prfpfadeinrichtung

Systemzugangspunkt

Mit dem Systemzugangspunkt knnen andere, an das Netzwerk angeschlossene Schneider Electric-Gerte erkannt und Verbindungen zu ihnen hergestellt werden. Diese Funktion ist so konfiguriert, dass sie standardmig ausgefhrt wird und keine weitere Konfiguration bentigt. Verwenden Sie diesen Setup-Bildschirm fr die Eingabe der Gruppen-IPAdresse und zugehriger Informationen.

Manahme
1. Klicken Sie im Setup-Men auf Systemzugangspunkt. 2. Aktiviert

Ergebnis
Das Fenster Systemzugangspunkt wird angezeigt. Ist dieses Kontrollkstchen aktiviert, knnen sich EGX300-Gerte mit denselben GruppenIP-Adressen untereinander erkennen. Werkeinstellung = Aktiviert Geben Sie die Port-Nummer (von 1 bis 65535) des UDP-Ports ein, der fr die Erkennung ber den Systemzugangspunkt verwendet wird. Werkeinstellung = 59 Geben Sie die Gruppen-IP-Adresse ein, die Multicast- oder Unicast-Adressen untersttzt. Werkeinstellung = 224.0.1.2 Das ist die Zeit zwischen den HalloMeldungen, die vom EGX300 ausgegeben werden, um anderen Systemzugangsgerten von Schneider Electric seine Anwesenheit im Netzwerk mitzuteilen. 165535 Sekunden, Werkeinstellung = 300 Sekunden

3. UDP-Port

4. Gruppen-IP-Adresse

5. Meldungsintervall

36

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Setup

Manahme
6. Haltezeit

Ergebnis
Das ist die Zeit, fr die vom jeweiligen EGX300 gesendete Hallo-Meldungen von Empfngern gehalten werden mssen, bevor dieses EGX300 als nicht verfgbar angesehen wird. Von 2 bis 65535 Sekunden, Werkeinstellung = 600 Sekunden Sie knnen die Gre des Netzwerkbereichs festlegen, der zur Erkennung von anderen Gerte verwendet wird. Das wird durch die zulssige Anzahl der Multicast-Weiterleitungen an andere Gerte geregelt. Der Bereich der zulssigen Router-Sprnge betrgt 1255. Werkeinstellung = 1 EGX300-Gerte in einer Gruppe knnen in Gemeinschaften unterteilt werden. EGX300Gerte mit derselben Gruppen-IP-Adresse und Gemeinschaftsnummer knnen sich untereinander erkennen. Durch Einstellung der Gemeinschaftsnummer auf 0 kann ein EGX300 alle EGX300-Gerte mit derselben Gruppen-IP-Adresse ohne Bercksichtigung der Gemeinschaftseinstellung erkennen. Werkeinstellung: 0

7. Multicast-Gltigkeitsdauer

8. Gemeinschaft

9. Standardwerte/bernehmen

Klicken Sie auf bernehmen, um Ihre Eintrge zu speichern bzw. auf Standardwerte, um zu den aufgelisteten Werkeinstellungen zurckzukehren.

Abbildung 29: Setup-Seite fr den Systemzugangspunkt

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

37

PowerLogicTM Ethernet Gateway EGX300 berwachung

63230-319-216B4_DE 06/2013

BERWACHUNG
Echtzeitdaten
Einzelgerteseiten

Das EGX bietet Bildschirmanzeigen fr die Anzeige von Echtzeitdaten und -Trendkurven zusammen mit historischen Datenprotokoll-Trendkurven. Die Seite Echtzeitdaten stellt grundlegende Messwerte ausgewhlter Gerte in Echtzeit sowie Gertebersichten bereit. Um eine Tabelle mit Echtzeitdaten zu betrachten, wechseln Sie in das berwachungsmen und whlen Sie ein Gert unter Echtzeitdaten > Einzelgerteseiten aus.

Grundmesswerteinstellungen
Manahme
1. Whlen Sie oben auf der Anzeige entweder Laststrom, Leistung, L-L-Spannung oder L-NSpannung fr die Anzeige in der grafischen Darstellung des Analogmessgerts aus.

Ergebnis
Auswahl der Gren, die in der grafischen Darstellung des Analogmessgerts angezeigt werden sollen. HINWEIS: Analogmessgertdarstellungen stehen nicht fr alle Gertetypen zur Verfgung.

2. Standardmig passen die Messgerte ihren Anzeigebereich automatisch an. Whlen Sie Bereich aus, wenn ein fester Bereich gewnscht wird. Anweisungen fr die Konfiguration des Bereichs der Analogmessgerte sind in der nachstehenden Tabelle aufgefhrt. 3. Klicken Sie auf bernehmen.

Steuerung des Anzeigebereichs der Analogmessgerte.

Aktualisierung der Messgertauswahl fr die Seite Gert.

Abbildung 30: Seite Grundmesswerte

38

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 berwachung

Analogmessgertbereich

Der Bereich der grafischen Analogmessgerte auf der Seite Grundmesswerte kann konfiguriert oder auf automatische Skalierung eingestellt werden (siehe Abbildung 31).
Manahme
1. Aktivieren Sie unter Automatische Skalierung aktivieren die Gerte, die automatisch skaliert werden sollen. HINWEIS: Klicken Sie auf Alle auswhlen, um die automatische Skalierung fr alle Gerte zu aktivieren, bzw. auf Lschen, um die automatische Skalierung fr alle Gerte zu deaktivieren. 2. Geben Sie fr Gerte mit deaktivierter automatischer Festlegung des Messgertbereichs. Skalierung die unteren und oberen Grenzwerte fr jeden Messgerttyp ein. 3. Klicken Sie auf bernehmen. Aktualisierung der Einstellungen fr die automatische Skalierung.

Ergebnis
Aktivierung der automatischen Skalierung fr ausgewhlte Gerte.

Abbildung 31: Setup-Seite Bereich

bersichtsgerteseiten

Auf den bersichtsgerteseiten befinden sich tabellarische bersichten ber ein oder mehrere ausgewhlte Gerte.
Manahme
1. Klicken Sie im berwachungsmen auf bersichtsgerteseiten. 2. Whlen Sie die bersichtsseite aus, die Sie betrachten mchten.

Ergebnis
Erweiterung der Baumdarstellung fr die Auswahl der bersichtsseiten. Einblendung der Gerteauswahlliste.

3. Whlen Sie Gerte aus der Liste Verfgbare Gerte Auswahl von Gerten fr die aus und klicken Sie auf Weiter (siehe Abbildung 32). bersichtsoptionen. HINWEIS: Klicken Sie auf >>, um alle verfgbaren Gerte auszuwhlen.

Abbildung 32: Seite Gerteauswahl

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

39

PowerLogicTM Ethernet Gateway EGX300 berwachung

63230-319-216B4_DE 06/2013

Abbildung 33: Seite Schaltkreisbersicht

Trendverfolgung

Um eine Echtzeit-Trenddarstellung mehrerer Gerte anzuzeigen, rufen Sie das berwachungsmen auf und whlen Sie Echtzeitdaten > Trendverfolgung aus.
Manahme
1. Whlen Sie im berwachungsmen Echtzeitdaten aus.

Ergebnis
Erweiterung der Datenbaumansicht fr die Auswahl der Echtzeit-Datenoptionen. Erweiterung der Datenbaumansicht fr die Auswahl der EchtzeitTrendverfolgungsoptionen. Einblendung der Setup-Seite fr die Echtzeit-Trendverfolgung. Auswahl von Gerten fr die Trendverfolgung. Auswahl von Gren fr die Trendverfolgung.

2. Whlen Sie Trendverfolgung aus.

3. Whlen Sie Echtzeit-Trendverfolgung aus. 4. Whlen Sie bis zu vier Gerte aus der Liste Verfgbare Gerte aus. 5. Whlen Sie ein oder mehrere Gren aus der Liste Verfgbare Gren aus. HINWEIS: Es stehen nur die Gren zur Trendverfolgung zur Verfgung, die alle ausgewhlten Gerte gemeinsam haben. Die maximale Anzahl der Gren fr die Trendverfolgung hngt von der Anzahl der ausgewhlten Gerte ab. Das Produkt aus der Anzahl der ausgewhlten Gerte und Gren muss kleiner als oder gleich 8 sein. 6. Klicken Sie auf Weiter, um die Anzeigeseite EchtzeitTrendverfolgung einzublenden.

Einblendung der Anzeigeseite Echtzeit-Trendverfolgung.

7. Um die Trendverfolgungsparameter festzulegen, fahren Mglichkeit zur Einstellung der Sie mit dem Verfahren in der nachstehenden Tabelle fort Parameter fr die und beachten Sie dazu Abbildung 35 auf Seite 41. Trendverfolgung.

Abbildung 34: Auswahl von Gerten und Gren

40

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 berwachung

Manahme

Ergebnis

1. Whlen Sie die Trendverfolgungsoption Absolutwert oder Auswahl des Diagrammmodus. Relativwert aus. HINWEIS: Mit der Option Absolutwert wird die X-Achse des Diagramms nach jeder Abtastung neu gezeichnet und das Diagramm wird mit allen Daten gefllt, die seit dem Start der Trendkurve erfasst wurden. Mit der Option Relativwert wird das Diagramm nach jeder Abtastung mit den neuesten Daten aktualisiert, wobei die X-Achse konstant bleibt, um die ausgewhlte Gesamttrendzeit anzuzeigen. 2. Whlen Sie eine Trendzeit zwischen 1 und 15 Minuten aus. Das ist die Dauer der Trenddarstellung. HINWEIS: Datenabtastungen werden so schnell wie mglich vorgenommen, knnen aber je nach Kommunikationslast im seriellen Subnetz und/oder auf den entfernten Gerten lnger dauern. 3. Whlen Sie Abtastung starten aus, um die Trendverfolgung der ausgewhlten Gertegren zu starten. HINWEIS: Die Trendverfolgung kann vor dem Ablauf der Trendzeit durch Klicken auf Abtastung anhalten angehalten werden. Wenn nach dem Anhalten der Abtastung Abtastung starten angeklickt wird, wird eine neue Trendkurve gestartet. 4. Klicken Sie auf Datenpunkte, um ein Protokoll aller abgetasteten Gren anzuzeigen, die whrend der Trendzeit aufgezeichnet wurden. HINWEIS: Nach jedem Intervall werden die Angaben Aktueller Wert fr alle Gren sowie die berechneten Werte Min., Max. und Mittelwert in die Tabelle unter dem Diagramm eingetragen. 5. Klicken Sie auf Neue Gre(n), um Gerte und Gren fr die Trendverfolgung neu auszuwhlen. Anzeige eines Protokolls aller Grenwerte, die whrend der Trendverfolgung abgetastet wurden. Start der Trendverfolgung. Auswahl der Dauer der Trenddarstellung.

Navigation zurck zur SetupSeite EchtzeitTrendverfolgung.

Abbildung 35: Echtzeit-Trendverfolgung

Gerteaufzeichnung

Die Seiten Gerteaufzeichnung enthalten grafische und tabellarische Darstellungen der ausgewhlten Gerteaufzeichnungsdaten. Weitere Details zur Konfiguration der Gerteaufzeichnung finden Sie unter Gerteaufzeichnung auf Seite 17.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

41

PowerLogicTM Ethernet Gateway EGX300 berwachung

63230-319-216B4_DE 06/2013

Einzelgerteseiten

Einzelgerteseiten enthalten grafische und tabellarische Darstellungen der Daten, die von einem einzelnen Gert aufgezeichnet wurden.
Manahme
1. Klicken Sie im berwachungsmen auf Gerteaufzeichnung. 2. Klicken Sie unter Gerteaufzeichnung auf Einzelgerteseiten. 3. Whlen Sie ein Gert aus der Liste Gerteaufzeichnung aus.

Ergebnis
Erweiterung der Baumansicht fr die Anzeige der verfgbaren Auswahlmglichkeiten fr die Gerteaufzeichnung. Erweiterung der Baumansicht zur Anzeige der verfgbaren Gerte, die Daten fr die Betrachtung aufgezeichnet haben. Anzeige des Gerteprotokolls fr das ausgewhlte Gert.

4. Um einen Datenbereich anzuzeigen, whlen Sie Auftragung des ausgewhlten den Bereich aus der Dropdown-Liste Datenbereichs. Datenbereich aus. 5. Halten Sie die linke Maustaste gedrckt und ziehen Sie einen Auswahlrahmen um den Diagrammbereich, der vergrert dargestellt werden soll. 6. Um zur ursprnglichen Vollansicht zurckzukehren, geben Sie Z auf Ihrer Tastatur ein oder doppelklicken Sie auf das Diagramm. 7. Klicken Sie auf Datenpunkte, um die Tabelle fr das ausgewhlte Intervalldatenprotokoll anzuzeigen (siehe nachstehende Abbildung 37). 8. Um andere Gren anzuzeigen, klicken Sie auf Neue Gre(n). Aktivieren Sie die Kontrollkstchen der Gren, die Sie anzeigen mchten, und klicken Sie auf bernehmen. Vergrerte Darstellung des ausgewhlten Diagrammbereichs.

Die Ansicht wird verkleinert.

Einblendung der Tabelle fr das ausgewhlte Intervalldatenprotokoll. Aktivierung der Anzeige ausgewhlter Gren.

Die von jedem Gert aufgezeichneten Daten werden auf einer Webseite in einem Zeitgang-Diagrammformat dargestellt. Das Zeitgang-Diagramm ist fr die Anzeige der Daten vom letzten vollstndigen Tag, von der letzten vollstndigen Woche, vom letzten vollstndigen Monat oder aller Daten vorkonfiguriert. Energieparameter werden als kumulierte Werte aufgezeichnet, aber als inkrementelle Werte auf der Basis von Intervallen angezeigt. Alle anderen Parameter werden als aufgezeichneter Istwert protokolliert und angezeigt. Abbildung 36: Diagramm des Intervalldatenprotokolls

Abbildung 37: Datenpunkttabelle des Intervalldatenprotokolls

42

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 berwachung

Abrufen eines Datenprotokolls

Intervalldatenprotokolle knnen mit den Methoden in Tabelle 15 abgerufen werden: Tabelle 15: Methoden zum Abrufen von Intervalldatenprotokollen und Dateiformate
Abrufmethode
FTP Schaltflche Datenpunkte Microsoft WebQuery E-Mail HTTP HTML HTML CSV CSV

Abgerufenes Dateiformat
CSV-Format (Variablen durch Komma getrennt)

Um eine Liste aller vorhandenen Protokolldateien anzuzeigen, fhren Sie die Schritte 2 bis 4 im Abschnitt Abrufen eines Intervalldatenprotokolls mit FTP auf Seite 44 aus. Die Dateien haben das Format Gertename_Lokale ID.csv, wobei Gertename der dem Slave-Gert zugewiesene Name und Lokale ID die ihm zugewiesene lokale IDNummer ist. Beispielsweise wrde ein Gert mit der Bezeichnung Building 1 Utility Entrance mit der lokalen ID 3 eine Datei mit dem Namen Building 1 Utility Entrance_3.csv erzeugen. Werden Protokolldateien exportiert, werden das Datum und die Uhrzeit im folgenden Format an den Dateinamen angehngt: _JJJJMMTTSSMMSS. Beispiel: Building 1 Utility Entrance_3_20100218115216.csv. Damit wird angezeigt, dass die Datei am 18. Februar 2010 um 11:52:16 Uhr exportiert wurde. Protokollformat Die Daten werden in folgendem Format aufgezeichnet (siehe Abbildung 38 auf Seite 44): Tabelle 16: Intervalldaten-Protokollformat
Zeile
1

Daten im CSV-Format

Beschreibung

(BOM)Gateway-Bezeichnung, Diese Zeile enthlt die Spaltenberschriften fr Gateway SN,Gateway-Adresse, die Daten in Zeile 2. Gertebezeichnung,lokale Gerte-ID, Gertetypbezeichnung,Aufzeichnungsintervall HINWEIS: (BOM) Die ersten drei Bytes der Datei sind von einer 3-Zeichen-BOM (Byte Order Mark) belegt (UTF-8-Codierung). EGX300SD,23227,157.198.184.116, Diese Zeile enthlt die Daten ber das EGX und Building 1 Utility Entrance,3, das protokollierte Gert. CM4000,15 Diese Zeile ist leer. ,,,Gren-ID 1,Gren-ID 2, Gren-ID 3 Diese Zeile enthlt die Spaltenberschriften fr die Gren-IDs in Zeile 5. Eine Gren-ID ist die numerische Bezeichnung der aufzuzeichnenden Gre. Der einer Gre zugewiesene Name kann sich zwischen Gerten und Sprachen geringfgig unterscheiden. Gren-IDs werden fr die Identifizierung der Gre unabhngig von Gert oder Sprache benutzt. Die ersten drei Kommas dienen Layoutzwecken in einer Tabellenkalkulations-anwendung. Diese Zeile enthlt die Gren-IDs der aufgezeichneten Werte.

3 4

5 6 7

,,,1617,1621,1625 Diese Zeile ist leer.

Fehler,UTC-Abweichung (Minuten), Diese Zeile enthlt die Spaltenberschriften der lokale Uhrzeit,Scheinenergie (kVAh), aufgezeichneten Daten in Zeile 8 und darber. Wirkenergie (kWh),Blindenergie (kVArh)

8 und Diese Zeilen enthalten die aufgezeichneten Daten. darber 0,-300,2008-10-09 14:15:00,1400738.219,1201962.707,647069.906,15 0,-300,2008-10-09 14:20:00,1400758.260,1201980.725,647078.602,15 0,-300,2008-10-09 14:25:00,1400778.198,1201998.661,647087.233,15

Wenn Sie eine Tabellenkalkulationsanwendung fr die Betrachtung der CSV-Datei benutzen, sollten die Daten wie in Abbildung 38 auf Seite 44 dargestellt werden.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

43

PowerLogicTM Ethernet Gateway EGX300 berwachung

63230-319-216B4_DE 06/2013

Abbildung 38: Intervalldatenprotokoll geffnet in einer Tabellenkalkulationsanwendung

Fehlercodes fr Datenprotokolle

Die nachstehenden Fehlercodes sind u. U. bei der Fehlerbehebung von Datenprotokollen zu sehen (siehe Abbildung 36 auf Seite 42 und Abbildung 37 auf Seite 42):
Fehlercode
19

Definition
Ein Kommunikationsfehler ist aufgetreten (z. B.: CRC-Fehler, Protokollfehler oder Ausnahme). Zeitberschreitung; nach Sendung einer Anfrage wurde innerhalb der zulssigen Zeit keine entsprechende Antwort empfangen. Ungltige Daten. Die Intervallzeit ist abgelaufen, bevor Daten aufgezeichnet werden konnten.

Ergebnis
Die Aufzeichnung bleibt eingeschaltet, sofern das letzte Intervall nicht fehlt. Die Aufzeichnung bleibt eingeschaltet, sofern das letzte Intervall nicht fehlt. Intervall fehlt.

25

38 100

Wenden Sie sich an die technische Untersttzung, wenn Sie bei der Lsung dieser oder anderer Fehlerbedingungen Hilfe brauchen.

Abrufen eines Intervalldatenprotokolls mit FTP

Sie knnen FTP fr das Abrufen einer Datenprotokolldatei benutzen, indem Sie ber FTP eine Verbindung mit dem EGX herstellen und die CSV-Datei bertragen, wie es in den nachfolgenden Schritten dargestellt wird. HINWEIS: Wenn Sie mchten, dass das EGX die Datenprotokolldatei automatisch ber FTP bertrgt, muss der Gerteprotokollexport fr FTP konfiguriert werden (siehe FTP-Export auf Seite 21).
Manahme
1. Erstellen Sie auf Ihrem Computer einen Ordner, z. B. c:\egx_logs. 2. Starten Sie Windows Explorer, geben Sie ftp:// und die IP-Adresse des EGX in die Adressenleiste ein (z. B. ftp://169.254.0.10) und drcken Sie die Eingabetaste. 3. Geben Sie in die Textfelder den Benutzernamen Administrator und das Administratorkennwort ein und klicken Sie auf Anmelden. 4. Navigieren Sie zum Verzeichnis /logging/data im EGX. 5. Kopieren Sie die Protokolldatei und fgen Sie diese dann in den im Schritt 1 erstellten Ordner ein.

Ergebnis
Erstellung eines Ordners zum Ablegen des EGX-Datenprotokolls. Einblendung des Dialogfelds Anmelden als.

Erffnung einer FTP-Sitzung mit dem EGX und Einblendung der im EGX gespeicherten Dateien. Einblendung des Datenprotokollverzeichnisses im EGX. Kopieren des Datenprotokolls in Ihren Ordner.

44

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 berwachung

Abrufen eines Intervalldatenprotokolls mit der Schaltflche Datenpunkte

Manahme

Ergebnis

1. Klicken Sie auf der Webseite Einblendung eines neues Fensters mit Anzeige Gerteaufzeichnung (siehe Abbildung 36 der aufgezeichneten Daten. auf Seite 42) auf die Schaltflche Datenpunkte. 2. Fhren Sie die Tastenkombinationen STRG+A und danach STRG+C aus. 3. ffnen Sie Excel und fhren Sie dann die Tastenkombination STRG+V aus. Auswahl aller Daten und Kopieren der Daten in die Zwischenablage. Einfgen der Daten in eine Excel-Tabelle.

Abrufen eines Intervalldatenprotokolls mit Microsoft WebQuery

Manahme
1. Starten Sie den Webbrowser. 2. berprfen Sie, ob die Protokolldatei verfgbar ist. Geben Sie dazu die IPAdresse des EGX300 gefolgt von /stream/devlog_data.html?device=x ein, wobei x fr die lokale ID des Gerts steht.

Ergebnis
Einblendung des Webbrowsers. Einblendung der Datenprotokoll-Seite.

3. Starten Sie Excel und klicken Sie auf Einblendung des Excel-Dialogfeldes Daten > Externe Daten importieren > Neue Webabfrage. Neue Webabfrage. HINWEIS: Der dargestellte Pfad ist typisch fr Microsoft Excel 2003. 4. Geben Sie im Dialogfeld Neue ffnen der Datenprotokoll-Datei. Webabfrage die in Schritt 2 eingegebene Adresse des Protokolls ein und klicken Sie auf Start. 5. Klicken Sie auf den uersten Pfeil, um alle Daten zu markieren, und klicken Sie dann auf Importieren. 6. Klicken Sie auf OK. Auswahl der Daten und Einblendung des Dialogfelds Daten importieren. Import der Daten.

HINWEIS: Wenn Sie jedes Mal beim ffnen der Excel-Tabelle die neuesten Daten anzeigen mchten, klicken Sie auf Eigenschaften im Dialogfeld Daten importieren und whlen Sie Aktualisieren beim ffnen der Datei aus.

Abrufen eines Intervalldatenprotokolls ber E-Mail

Das EGX muss fr die Sendung von Datenprotokollen an eine E-MailAdresse konfiguriert sein. Fr weitere Informationen hierzu siehe E-MailExport auf Seite 19.

Abrufen eines Intervalldatenprotokolls ber HTTP

Das EGX muss so konfiguriert werden, dass es Datenprotokolle an einen Webserver bertrgt. Fr weitere Informationen hierzu siehe HTTP-Export auf Seite 23.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

45

PowerLogicTM Ethernet Gateway EGX300 berwachung

63230-319-216B4_DE 06/2013

bersichtsgerteseiten

Auf den bersichtsgerteseiten befinden sich bersichten ber ein oder mehrere ausgewhlte Gerte.
Manahme
1. Klicken Sie im berwachungsmen auf Gerteaufzeichnung. 2. Klicken Sie unter Gerteaufzeichnung auf bersichtsgerteseiten. 3. Klicken Sie unter bersichtsgerteseiten Einblendung der Setup-Seite fr Mehrere auf Mehrere Gerte, Einzelgre. Gerte, Einzelgre. 4. Whlen Sie ein Gert aus der Liste Verfgbare Gerte aus. HINWEIS: Es knnen maximal vier Gerte ausgewhlt werden. 5. Whlen Sie eine Gre aus der Liste Verfgbare Gren aus. HINWEIS: Es sind nur Gren verfgbar, die alle ausgewhlten Gerte gemeinsam haben. 6. Klicken Sie auf Weiter. 7. Halten Sie die linke Maustaste gedrckt und ziehen Sie einen Auswahlrahmen um den Diagrammbereich, der vergrert dargestellt werden soll. Einblendung der Trendseite Mehrere Gerte, Einzelgre. Vergrerte Darstellung des ausgewhlten Diagrammbereichs. Auswahl der anzuzeigenden Gre fr jedes ausgewhlte Gert. Auswahl der Gerte fr die bersichtsoptionen.

Ergebnis
Erweiterung der Baumansicht fr die Auswahlmglichkeiten der Gerteaufzeichnung.

8. Um zur ursprnglichen Vollansicht Die Ansicht wird verkleinert. zurckzukehren, geben Sie Z auf Ihrer Tastatur ein oder doppelklicken Sie auf das Diagramm.

Die von den ausgewhlten Gerten aufgezeichnete Gre wird auf einer Webseite in einem Zeitgang-Diagrammformat dargestellt. Das ZeitgangDiagramm ist fr die Anzeige der Daten vom letzten vollstndigen Tag, von der letzten vollstndigen Woche, vom letzten vollstndigen Monat oder aller Daten vorkonfiguriert. Energieparameter werden als inkrementelle Werte auf der Basis von Intervallen angezeigt. Alle anderen Parameter werden als aufgezeichneter Istwert protokolliert und angezeigt. Abbildung 39: Setup-Seite Mehrere Gerte, Einzelgre

46

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 berwachung

Abbildung 40: Trendseite Mehrere Gerte, Einzelgre

Instrumententafeln

Das EGX untersttzt vier Kategorien von Instrumententafeln, die zeitlich summierte Energieverbrauchsdaten anzeigen. Die Instrumententafeln und ihre Teilstze sind in Tabelle 17 aufgelistet. Tabelle 17: Instrumententafelarten
Instrumententafel Nach Stunden Vortag nach Stunden Aktueller Tag nach Stunden Aktueller Tag ber Vortag nach Stunden Nach Tagen Vorwoche nach Tagen Aktuelle Woche nach Tagen Aktuelle Woche ber Vorwoche nach Tagen Vormonat nach Tagen Aktueller Monat nach Tagen Aktueller Monat ber Vormonat nach Tagen Nach Wochen Vorquartal nach Wochen Aktuelles Quartal nach Wochen Aktuelles Quartal ber Vorquartal nach Wochen Zurckliegende 13 Wochen nach Wochen Nach Monaten Vorjahr nach Monaten Aktuelles Jahr nach Monaten Aktuelles Jahr ber Vorjahr nach Monaten HINWEIS: Bei dieser Option muss jede Gertedatenprotokolldatei gengend Kapazitt fr die Verlaufsdaten von zwei Jahren haben. Fr weitere Informationen siehe Intervalldatenaufzeichnung auf Seite 17. Zurckliegende 12 Monate nach Monat Teilsatz

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

47

PowerLogicTM Ethernet Gateway EGX300 berwachung

63230-319-216B4_DE 06/2013

Anzeigen einer Instrumententafel


Manahme
1. Klicken Sie im berwachungsmen auf Instrumententafeln. 2. Whlen Sie ein Gert aus der DropdownListe Gert aus. HINWEIS: Die Instrumententafel zeigt Daten eines Einzelgerts an. 3. Whlen Sie eine Gre aus der Dropdown- Auswahl der grafisch darzustellenden Gre. Liste Grenbezeichnung aus. HINWEIS: Die Grenauswahl ist auf inkrementelle Verbrauchsgren des Gerts beschrnkt. 4. Whlen Sie die Zeitparameter aus der Dropdown-Liste Uhrzeit aus. 5. Klicken Sie auf bernehmen. Auswahl des Zeitbereichs der aufgezeichneten Daten fr die ausgewhlte Gre. Anzeige der ausgewhlten Instrumententafel.

Ergebnis
Anzeige des Instrumententafelmens (siehe Abbildung 41). Auswahl des Gerts zur Anzeige von Daten.

Abbildung 41: Men Instrumententafeln

Die Daten jeder Instrumententafel werden als Balkendiagramme auf einer Webseite angezeigt. Wenn Sie mit dem Mauszeiger ber einen Balken im Diagramm gehen, wird der Datenpunktwert fr das ausgewhlte Intervall angezeigt (Abbildung 42). Abbildung 42: Instrumententafeldiagramm

Abbildung 43: Instrumententafeltabelle

48

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 berwachung

Abrufen von Instrumententafeldaten mit der Schaltflche Datenpunkte

Sie knnen Daten einer Instrumententafel wie nachstehend beschrieben in einer Tabellenkalkulationsanwendung speichern.
Manahme Ergebnis

1. Klicken Sie in der Instrumententafel mit Anzeige der Datenpunkte fr die ausgewhlte den gewnschten Daten auf Datenpunkte. Instrumententafel (Abbildung 43 auf Seite 48). 2. Drcken Sie STRG+A und dann STRG+C. Auswahl aller Daten und Kopieren der Daten in die Zwischenablage. 3. ffnen Sie Excel und drcken Sie dann STRG+V. Einfgen der Daten in eine Excel-Tabelle.

Speichern eines Instrumententafel-Links

Sie knnen einen Link zu einer Instrumententafel speichern, um diese nicht jedesmal vom Hauptmen aus aufrufen zu mssen. Tabelle 18 beschreibt die Methoden fr die Speicherung eines Instrumententafel-Links.

Tabelle 18: Speichern eines Instrumententafel-Links


Option Browser-Lesezeichen Beschreibung Damit knnen Benutzer ber den Computer auf die gespeicherte Instrumententafel zugreifen, auf dem das Lesezeichen erstellt wurde. Damit knnen EGX-Benutzer ber die Unterlagenseite auf eine gespeicherte Instrumententafel zugreifen. Einstellung Befolgen Sie die Anweisungen zum Erstellen eines Lesezeichens in Ihrem bevorzugten Browser. Fr das Erstellen eines URLZugriffs siehe Unterlagenlinks auf Seite 28.

Unterlagenlink

E-Mail

Damit knnen Benutzer eine Der E-Mail-Empfnger muss Instrumententafel-URL im Hauptteil zum Anzeigen einer einer E-Mail versenden. Instrumententafel ein EGXBenutzerkonto haben. Siehe Benutzerkonten auf Seite 29.

Speichern einer Instrumententafel als ein Bild

Mit den folgenden Schritten knnen Sie ein Instrumententafeldiagramm als ein Bild speichern.
Manahme
1. Befolgen Sie die Schritte unter Anzeigen einer Instrumententafel auf Seite 48. 2. Klicken Sie auf Als Bild anzeigen... in der rechten oberen Ecke der Seite (Abbildung 44 auf Seite 50). 3. Rechtsklicken Sie auf das Bild und whlen Sie Bild speichern unter... aus. 4. Geben Sie einen Dateinamen ein, whlen Sie einen Speicherort aus und klicken Sie auf Speichern. HINWEIS: PNG-Bild ist der voreingestellte Dateityp. Um den Dateityp zu ndern, ersetzen Sie .png im Dateinamenfeld durch Ihre bevorzugte Erweiterung.

Ergebnis
Anzeige des Instrumententafeldiagramms. ffnen eines neuen Fensters, in dem die Instrumententafel als Bild angezeigt wird. ffnen des Dialogfeldes Speichern unter. Speicherung des Bildes.

HINWEIS: Diese Funktion ist bei Internet Explorer, Version 8 und frheren Versionen nicht verfgbar.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

49

PowerLogicTM Ethernet Gateway EGX300 berwachung

63230-319-216B4_DE 06/2013

Abbildung 44: Speichern eines Instrumententafelbildes

Systemzugangspunkt

Das EGX kann andere EGX300-Gerte und andere Schneider ElectricGerte, die am Netzwerk angeschlossen sind, erkennen und entsprechende Links zur Verfgung stellen. Damit wird ein Zugangspunkt fr ein System vernetzter Schneider Electric-Gerte bereitgestellt. Die Seite Systemzugangspunkt listet jedes erkannte Schneider ElectricGert in Form eines Hyperlinks auf. Wenn Sie mit dem Mauszeiger ber ein Gert in der Liste gehen, werden links neben der Liste zustzliche Details zum Gert angezeigt. Klicken Sie auf ein Gert, um die Anmeldeseite fr dieses Gert aufzurufen.

Abbildung 45: Seite Systemzugangspunkt mit Detailanzeige

50

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Unterlagen

UNTERLAGEN

ber die Unterlagen-Seite knnen Sie auf Informationen zugreifen, die in Form von Dateien und URL-Links im EGX gespeichert sind. Informationen ber das Laden von Unterlagenlinks finden Sie unter Unterlagenlinks auf Seite 28. Um einen Unterlagenlink zu ffnen, klicken Sie auf den Link Unterlagen oben auf der Seite und whlen Sie danach den gewnschten Link aus.

Abbildung 46: Unterlagenseite

STEUERUNG

Das EGX kann manuell eine oder mehrere Gruppen vordefinierter Rckstellbefehle pro Gertetyp ausfhren.
Manahme
1. Klicken Sie im Men Steuerung auf Resets.

Ergebnis
Einblendung der Seite Resets.

2. Whlen Sie in der Liste unter Resets das Auswahl eines Gerts und Anzeige seiner Gert aus, das Sie betrachten oder Rckstelloptionen sowie des Datums und der zurckstellen mchten. Uhrzeit der letzten Rckstellung. 3. Whlen Sie die Gerteparameter aus, die Sie zurckstellen mchten. 4. Klicken Sie auf Rcksetzen. Festlegung des am ausgewhlten Gert durchzufhrenden Rckstellvorgangs. Senden der Rcksetzbefehle fr die geforderten Rckstellvorgnge an das ausgewhlte Gert und Anzeige des Status.

Abbildung 47: Resets

HINWEIS: Das Datum und die Uhrzeit, die fr den Parameter Datum/Uhrzeit angezeigt werden, entsprechen dem Datum und der Uhrzeit im ausgewhlten Gert. Wenn dieser Parameter fr eine Rckstellung ausgewhlt ist, werden das Datum und die Uhrzeit des EGX an das Gert bertragen. Die Werte fr Datum/Uhrzeit werden nur dann gemeldet, wenn das Gert sie untersttzt. Wenn beispielsweise das Gert den Min/Max-Wert fr Datum/Uhrzeit letzter Reset nicht untersttzt, wird hier kein Eintrag fr den Wert Min/Max angezeigt.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

51

PowerLogicTM Ethernet Gateway EGX300 Diagnose

63230-319-216B4_DE 06/2013

DIAGNOSE

Fr den Zugang auf die Diagnose-Webseiten-Links klicken Sie auf Diagnose in der EGX-Menleiste.

Statistik

Diese Seite zeigt seit der letzten Aktivierung des EGX kumulierte Werte an. Wenn die Stromversorgung des EGX ausfllt, oder das Gert wegen einer Konfigurationsnderung oder eines anderen Ereignisses zurckgestellt wird, werden alle kumulierten Werte auf null zurckgestellt.
Manahme
1. Klicken Sie im Diagnose-Men auf Statistik. 2. Zeigen Sie die Daten an.

Ergebnis
Einblendung der Statistikseite (siehe nachstehende Abbildung 48). Weitere Informationen hierzu finden Sie nachstehend unter Statistik auswerten auf Seite 53. Rcksetzung der kumulativen Diagnosedaten des EGX auf 0.

3. Klicken Sie auf Rcksetzen.

Abbildung 48: Seite Statistik

52

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Diagnose

Statistik auswerten
Statistik
Ethernet Verbindungsstatus Status-Zeichenkette, die die Geschwindigkeit und die Duplex-Einstellung darstellt, die zur Kommunikation mit dem Verbindungspartner benutzt werden. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen erfolgreich gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen aufgrund der Erkennung einer Kollision neu bertragen wird. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen aufgrund der Erreichung des maximalen Kollisionsstatus auf der Basis des Truncated Binary Exponential Backoff-Algorithmus nicht gesendet werden kann. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen erfolgreich empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird, dessen Prfsumme/CRC nicht mit dem berechneten Wert bereinstimmt. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird, dessen Prfsumme/CRC nicht mit einer 8-Bit-Rahmenbegrenzung endet. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird, der die in den Standardeinstellungen festgelegte maximale Lnge berschreitet (Rahmen lnger als 1518 Byte). Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird, der die in den Standardeinstellungen festgelegte minimale Lnge unterschreitet (Rahmen krzer als 64 Byte).

Beschreibung

Rahmen ohne Fehler gesendet Kollisionen

Zu hohe Anzahl an Kollisionen

Rahmen ohne Fehler empfangen CRC-Fehler

Synchronisierfehler

Rahmen zu lang

Rahmen zu kurz

Modbus-TCP/IP Server Rahmen gesendet Rahmen empfangen Protokollfehler Aktive Verbindungen1 Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Nachricht mit einem falschen Format empfangen wird. Statuswert, der die Anzahl der Verbindungen darstellt, die zum Zeitpunkt der Aktualisierung der Diagnoseseite aktiv sind. Es werden maximal 64 Verbindungen untersttzt. Durch Klicken auf Aktive Verbindungen wird ein neues Fenster mit einer Liste aller aktiven Client-Verbindungen geffnet. Zhler, der sich jedes Mal um eins erhht, wenn eine Verbindung zum EGX aufgebaut wird. Statuswert, der die maximale Anzahl von Verbindungen darstellt, die aufgebaut werden. Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Antwortnachricht gesendet wird.

Summe der Verbindungen Maximale Anzahl Verbindungen Eingegangene Lesenachrichten Eingegangene Schreibnachrichten Abgegangene Antwortnachrichten Client Rahmen gesendet Rahmen empfangen Protokollfehler
1

Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Nachricht mit einem falschen Format empfangen wird.

Klicken Sie fr weitere ausfhrliche Informationen auf den Link.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

53

PowerLogicTM Ethernet Gateway EGX300 Diagnose

63230-319-216B4_DE 06/2013

Statistik
Zeitberschreitungen

Beschreibung
Zhler, der sich jedes Mal um eins erhht, wenn eine Anforderungsnachricht gesendet wird, ohne dass eine entsprechende Antwortnachricht innerhalb der zulssigen Zeit empfangen wird. Zeitberschreitungen sind normalerweise das Ergebnis von Konfigurationsfehlern oder einer fehlenden Reaktion des Gerts. Zhler, der sich bei jedem Verbindungsausfall um eins erhht. Zhler, der sich jedes Mal um eins erhht, wenn eine Ausnahme empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht gesendet wird. Zhler, der sich jedesmal um eins erhht, wenn eine Antwortnachricht empfangen wird. Ausfhrliche Tabelle mit Fern- und seriellen Statistiken pro Gert.

Verbindungszeitberschreitungen Ausnahmen empfangen Abgegangene Lesenachrichten Abgegangene Schreibnachrichten Eingegangene Antwortnachrichten Details1 Serielle Schnittstelle Rahmen gesendet Rahmen empfangen CRC-Fehler

Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Nachricht empfangen wird, deren CRC nicht mit dem berechneten Wert bereinstimmt. Dies ist normalerweise die Folge von Verdrahtungsproblemen. Zhler, der sich jedes Mal um eins erhht, wenn eine Nachricht mit einem falschen Format empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Anforderungsnachricht gesendet wird, ohne dass eine entsprechende Antwortnachricht innerhalb der zulssigen Zeit empfangen wird. Zeitberschreitungen sind normalerweise das Ergebnis von Konfigurationsfehlern oder einer fehlenden Reaktion des Gerts. Zhler, der sich jedes Mal um eins erhht, wenn eine Ausnahme empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht empfangen wird. Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht empfangen wird. Ausfhrliche Tabelle mit Fern- und seriellen Statistiken pro Gert.

Protokollfehler Zeitberschreitungen

Ausnahmen empfangen Abgegangene Lesenachrichten Abgegangene Schreibnachrichten Eingegangene Lesenachrichten Eingegangene Schreibnachrichten Details1 HTTP-Server Rahmen gesendet Rahmen empfangen Aktive Verbindungen1

Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird. Statuswert, der die Anzahl der Verbindungen darstellt, die zum Zeitpunkt der Aktualisierung der Diagnoseseite aktiv sind. Es werden maximal 20 Verbindungen untersttzt. Klicken Sie auf Aktive Verbindungen, um ein neues Fenster mit einer Liste aller aktiven Client-Verbindungen zu ffnen. Zhler, der sich jedes Mal um eins erhht, wenn eine Verbindung zum EGX aufgebaut wird. Statuswert, der die maximale Anzahl von Verbindungen darstellt, die aufgebaut werden.

Summe der Verbindungen1 Maximale Anzahl Verbindungen


1

Klicken Sie fr weitere ausfhrliche Informationen auf den Link.

54

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Diagnose

Statistik
Gateway-Informationen Firmwareversion System-Leerlaufzeit MAC-Adresse Seriennummer Modellnummer Hardwareversion Herstellungsdatum HTTP-Client Senden OK Verbindungsfehler Authentifizierungsfehler

Beschreibung

Das ist die Firmwareversion, die im EGX installiert ist. Prozentsatz von 0 % bis 100 %, der die durchschnittliche ungenutzte Prozessorzeit anzeigt. Unverwechselbare Ethernet-Hardware-Adresse eines EGX Seriennummer des EGX Modellnummer des EGX EGX-Hardwareversion Datum, an dem das EGX hergestellt wurde.

Zhler, der sich jedes Mal um eins erhht, wenn eine Datei erfolgreich an den HTTP-Server gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn das EGX keine Verbindung zum HTTP-Server herstellen kann. Zhler, der sich jedes Mal um eins erhht, wenn der HTTPServer den Benutzernamen bzw. das Kennwort nicht authentifizieren kann. Zhler, der sich jedes Mal um eins erhht, wenn eine Datei nicht zum HTTP-Server gesendet werden kann. Zhler, der sich jedes Mal um eins erhht, wenn eine Datei nicht gesendet werden kann, weil das EGX den Vorgang nicht einleiten kann.

Sendefehler Allgemeiner Fehler

FTP-Client Senden OK Verbindungsfehler Authentifizierungsfehler Zhler, der sich nach jeder erfolgreichen bertragung an einen FTP-Server um eins erhht. Zhler, der sich jedes Mal um eins erhht, wenn das EGX keine Verbindung zum FTP-Server herstellen kann. Zhler, der sich jedes Mal um eins erhht, wenn der FTPServer den Benutzernamen bzw. das Kennwort nicht authentifizieren kann. Zhler, der sich jedes Mal um eins erhht, wenn der FTPServer das angeforderte Verzeichnis nicht lokalisieren kann. Zhler, der sich jedes Mal um eins erhht, wenn eine Datei nicht zum FTP-Server gesendet werden kann. Zhler, der sich jedes Mal um eins erhht, wenn eine Datei nicht gesendet werden kann, weil das EGX den Vorgang nicht einleiten kann.

Verzeichnisfehler

Sendefehler Allgemeiner Fehler

SMTP-Client Senden OK Verbindungsfehler Authentifizierungsfehler Zhler, der sich jedes Mal um eins erhht, wenn eine E-Mail erfolgreich an den SMTP-Server gesendet wird. Zhler, der sich jedes Mal um eins erhht, wenn das EGX keine Verbindung zum SMTP-Server herstellen kann. Zhler, der sich jedes Mal um eins erhht, wenn der SMTP-Server den Benutzernamen bzw. das Kennwort nicht authentifizieren kann. Zhler, der sich jedes Mal um eins erhht, wenn eine E-Mail nicht an den SMTP-Server gesendet werden kann. Zhler, der sich jedes Mal um eins erhht, wenn das Erstellen einer E-Mail durch das EGX fehlschlgt und die E-Mail nicht gesendet werden kann.

Sendefehler Allgemeiner Fehler

Dateisystem Kapazitt insgesamt Freie Kapazitt


1Klicken

Gesamtkapazitt des EGX-Speichers in Kilobyte. Gesamter ungenutzter Speicherplatz im EGX in Kilobyte.

Sie fr weitere ausfhrliche Informationen auf den Link.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

55

PowerLogicTM Ethernet Gateway EGX300 Diagnose

63230-319-216B4_DE 06/2013

Gerteregister lesen

Diese Option ermglicht es, angeschlossene lokale und entfernte Gerte mit dem EGX auszulesen. Abbildung 49: Seite Gerteregister lesen

Manahme
1. Klicken Sie im Diagnose-Men auf Gerteregister lesen. 2. Geben Sie die lokale Gerte-ID ein (oder whlen Sie sie aus der definierten Gerteliste aus). Geben Sie die Startdatenadresse und die Anzahl der zu lesenden Register ein. 3. Whlen Sie einen Datentyp aus.

Ergebnis
Einblendung der Seite Gerteregister lesen. Eingabe der vom angegebenen Gert zu lesenden Register.

Auswahl des entsprechenden Datentyps.

4. Um die Art der Datenanzeige in der Spalte Auswahl der Art der Datenanzeige. Wert zu ndern, whlen Sie Dezimal, Hexadezimal, Binr oder ASCII aus. 5. Klicken Sie auf Lesen. Lesen der Gerteregister gem der ausgewhlten Konfiguration.

Tabelle 19: Einstellungen des EGX zum Lesen von Gerteregistern


Option Beschreibung Werkeinstellung

Gertebezeichnung Damit wird ein zu lesendes Gert aus der Liste vorher hinzugefgter Gerte ausgewhlt. Ein Gert, das nicht in der Gerteliste definiert ist, kann durch Eingabe seiner lokalen ID gelesen werden. Gerte-ID Startregister Anzahl Register Spalte Register Spalte Wert Adresse (lokale ID) des auszulesenden Gerts. Erstes zu lesendes Register. Anzahl der zu lesenden Register (1 bis 125). Auflistung der Registernummern. Auflistung der fr ein Register gespeicherten Daten. Die abgerufenen Werte hngen vom Gert ab, das mit dem EGX verbunden ist. Weitere Informationen ber gespeicherte Registerwerte finden Sie in den Unterlagen des verbundenen Gerts. Auswahl von Halteregister, Eingangsregister, Ausgangsspulen, Eingangsspulen bzw. Gerte-ID. 1 1000 10

Datentyp

Halteregister Dezimal

Optionen Dezimal, Legt fest, wie Daten in der Spalte Wert angezeigt Hexadezimal, Binr werden sollen. bzw. ASCII

56

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Diagnose

Kommunikationsprfung
Automatische Kommunikationsprfung Whrend der Anzeige der Echtzeitdatenansichten fhrt das EGX standardmig alle 15 Minuten eine automatische Kommunikationsprfung aus. (Um die Zeitsteuerung zu verndern, siehe Prferenzen auf Seite 32.) Damit wird die Strungsfreiheit der Kommunikation mit allen Gerten berprft, die im EGX konfiguriert sind, und innerhalb der Browsersitzung der Wiederaufbau der Kommunikation zu jedem Gert versucht, das mit Auer Betrieb gekennzeichnet ist.

Manuelle Kommunikationsprfung

In bestimmten Fllen mchten Sie mglicherweise nicht auf die automatische Kommunikationsprfung warten und mssen die Ausfhrung der Prfung manuell erzwingen.
Manahme
1. Klicken Sie im Diagnose-Men auf Kommunikationsprfung.

Ergebnis
Einblendung der Seite Kommunikationsprfung.

2. Klicken Sie auf Gertestatus berprfen. Damit wird eine Kommunikationsprfung ausgefhrt. Gerte, mit denen eine Kommunikation mglich ist, zeigen Bestanden in der Spalte Kommunikation und In Betrieb in der Spalte Status an. Gerte, mit denen keine Kommunikation mglich ist, zeigen Fehlgeschlagen in der Spalte Kommunikation und Auer Betrieb in der Spalte Status an, wenn die Verbindungsaufnahme mehrmals fehlgeschlagen ist.

Abbildung 50: Seite Kommunikationsprfung

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

57

PowerLogicTM Ethernet Gateway EGX300 Wartung

63230-319-216B4_DE 06/2013

WARTUNG

Mit dem Wartungsprotokoll knnen die Wartungsarbeiten dokumentiert werden, die am EGX, an den angeschlossenen Gerten oder an der Anlage, zu der das EGX gehrt, durchgefhrt werden. Jeder Eintrag wird mit Datum und Uhrzeit und dem Namen des betreffenden Benutzers protokolliert. Dieses Protokoll listet auch automatisch Systemaktivitten auf, zum Beispiel die Aktivierung bzw. Deaktivierung von Funktionen. Sie mssen dafr keine Eintrge vornehmen. Zudem listet dieses Protokoll alle Aktivitten auf, die fr das Wartungsprotokoll auf der Setup-Seite Prfpfad festgelegt wurden (siehe Prfpfad auf Seite 34).
Manahme
1. Klicken Sie im Wartungsmen auf Wartungsprotokoll. 2. Aktivieren Sie das Kontrollkstchen Lschen neben dem Eintrag, den Sie lschen mchten. Klicken Sie danach auf Eintrge lschen.

Ergebnis
Einblendung der Seite Wartungsprotokoll. Lschen des ausgewhlten Eintrags.

3. Klicken Sie auf Protokoll lschen, um alle Lschen des Wartungsprotokolls. Eintrge im Wartungsprotokoll zu lschen. 4. Klicken Sie auf Protokolleintrag hinzufgen und geben Sie den Wartungstext in das Textfeld Eingabedetail ein (siehe nachstehende Abbildung 52), um einen neuen Protokolleintrag hinzuzufgen. Einblendung der Seite Protokolleintrag hinzufgen, in die der Benutzer Wartungsdetails eingeben kann.

Abbildung 51: Wartungsprotokoll

Abbildung 52: Protokolleintrag hinzufgen

FIRMWARE

Die Firmware der EGX-Gerte kann mit FTP (File Transfer Protocol) aktualisiert werden. Das neueste Firmware-Update finden Sie unter www.schneider-electric.com, oder fragen Sie Ihren zustndigen Vertriebsmitarbeiter danach.

Firmwareversion feststellen

Das EGX enthlt zwei Firmware-Komponenten: die ausfhrbare Binrkomponente und die Datentrgerabbildkomponente.

58

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Firmware

Firmwareversion der ausfhrbaren Binrkomponente

Manahme
1. ffnen Sie den Webbrowser und melden Sie sich beim EGX an. 2. Suchen Sie die Firmwareversion in der unteren linken Ecke der Seite. HINWEIS: Wenn Sie die Firmware krzlich aktualisiert haben, drcken Sie F5, um die Webseite und die angezeigte Firmwarenummer zu aktualisieren. 3. Alternativ knnen Sie auf Diagnose > Statistik klicken, um die Firmwareversion im Abschnitt Gateway-Informationen zu finden.

Ergebnis
Einblendung der EGX-Startseite. Feststellung der Firmware-Version des EGX.

Alternative Feststellung der Firmwareversion des EGX.

Datentrgerabbildkomponente
Manahme
1. ffnen Sie den Webbrowser und melden Sie sich beim EGX an. 2. Suchen Sie die Firmwareversion in der unteren linken Ecke der Seite. HINWEIS: Wenn Sie die Firmware krzlich aktualisiert haben, drcken Sie F5, um die Webseite und die angezeigte Firmwarenummer zu aktualisieren. 3. Alternativ knnen Sie ber FTP auf das EGX zugreifen. Suchen Sie die Datei version.txt und doppelklicken Sie anschlieend auf die Datei, um sie zu ffnen. Feststellung der DatentrgerabbildFirmware-Version des EGX.

Ergebnis
Einblendung der EGX-Startseite. Feststellung der DatentrgerabbildFirmware-Version des EGX.

Neue Firmware herunterladen


Manahme
1. Starten Sie den Webbrowser, geben Sie www.powerlogic.com in das Adressentextfeld ein und drcken Sie die Eingabetaste. 2. Whlen Sie Ihr Land aus und klicken Sie auf Go (Start). HINWEIS: Wenn Sie United States ausgewhlt haben, fahren Sie mit Schritt 3 fort. Anderenfalls folgen Sie der lnderspezifischen Navigation, um die EGXFirmware zu erhalten. 3. Klicken Sie auf Support > Downloads. 4. Klicken Sie auf den Link EGX300 Firmware. 5. Klicken Sie auf den Link mit der FirmwareDatei (egxxxxx.bin, wobei xxxx die FirmwareVersionsnummer ist) und dann auf Speichern. 6. Whlen Sie im Dialogfeld Speichern unter das lokale Verzeichnis bzw. den Dateiordner aus, in dem die Firmwaredatei gespeichert werden soll, oder erstellen Sie ein lokale Verzeichnis bzw. einen Dateiordner, und klicken Sie auf Speichern. 7. Klicken Sie auf den Link egxxxxx.upd (wobei xxxx die Firmware-Nummer ist) und dann auf Speichern. 8. Whlen Sie im Dialogfeld Speichern unter das lokale Verzeichnis bzw. den Dateiordner aus, in dem die Firmwaredatei gespeichert werden soll, oder erstellen Sie ein lokale Verzeichnis bzw. einen Dateiordner, und klicken Sie auf Speichern. Einblendung der Download-Seite. Einblendung der Seite EGX300 Firmware. Einblendung des Dialogfelds fr den DateiDownload und dann des Dialogfeldes Speichern unter. Speicherung der Firmwaredatei im angegebenen Verzeichnis bzw. Ordner.

Ergebnis
Einblendung der PowerLogic-Website.

Einblendung der PowerLogic-Website fr Ihr Land.

Einblendung des Dialogfelds fr den DateiDownload und dann des Dialogfeldes Speichern unter. Speicherung der Firmwaredatei (.upd) im angegebenen Verzeichnis bzw. Ordner.

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

59

PowerLogicTM Ethernet Gateway EGX300 Firmware

63230-319-216B4_DE 06/2013

Firmware aktualisieren

Whrend die Firmware heruntergeladen wird, darf die Stromversorgung des EGX nicht unterbrochen werden. Wenn whrend des Programmiervorgangs die Stromversorgung unterbrochen wird, funktioniert das EGX nicht mehr. Die Status-LED blinkt whrend des Programmiervorgangs schnell. Wenn das Blinken aufhrt, ist die Programmierung abgeschlossen.
Manahme
1. Starten Sie Windows Explorer, geben Sie ftp:// und die IP-Adresse des EGX in das Adressentextfeld ein (z. B. ftp://169.254.0.10) und drcken Sie die Eingabetaste. 2. Geben Sie in die Textfelder den Benutzernamen Administrator und das Administratorkennwort ein und klicken Sie auf Anmelden. 3. Suchen Sie das Verzeichnis bzw. den Ordner, in dem die Firmwaredatei (egxxxxx.bin) auf Ihrem Computer gespeichert ist, rechtsklicken Sie auf die Datei und klicken Sie dann auf Kopieren. 4. Rechtsklicken Sie in das WindowsExplorer-Fenster und klicken Sie anschlieend auf Einfgen. HINWEIS: Anstelle von Kopieren und Einfgen knnen Sie die Datei auch per Drag-and-Drop in Windows Explorer bertragen.

Ergebnis
Einblendung des Dialogfelds Anmelden als.

Erffnung einer FTP-Sitzung mit dem EGX.

Kopieren der Firmware-Datei in die Zwischenablage.

Kopieren der Firmware auf das EGX und Neustart des EGX. HINWEIS: Die LED Spannungsversorgung/Status blinkt schnell, whrend die Datei auf das EGX bertragen und programmiert wird. Nach Beendigung der Programmierung wird das EGX zurckgestellt. Die Programmierung dauert zwischen 1,5 und 2 Minuten.

5. Suchen Sie die gespeicherte Kopiert die Aktualisierungsdatei in die Aktualisierungsdatei (egxxxxx.upd) auf Zwischenablage. Ihrem Computer, rechtsklicken Sie auf den Dateinamen und klicken Sie dann auf Kopieren. 6. Rechtsklicken Sie in das WindowsExplorer-Fenster und klicken Sie anschlieend auf Einfgen. HINWEIS: Anstelle von Kopieren und Einfgen knnen Sie die Datei auch per Drag-and-Drop in Windows Explorer bertragen. 7. Um zu kontrollieren, ob die Firmwareversion erfolgreich aktualisiert wurde, fhren Sie die Schritte unter Firmwareversion feststellen auf Seite 58 aus. 8. Klicken Sie im Windows-Explorer-Fenster auf Schlieen. berprfung der aktualisierten Firmwareversion. Kopieren der Datei in das EGX und Neustart des EGX.

Schlieen von Windows Explorer und Beenden der FTP-Verbindung zum EGX.

60

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Anhang A Untersttzte Ethernet-Protokolle

ANHANG A UNTERSTTZTE ETHERNET-PROTOKOLLE

Das EGX untersttzt folgende Ethernet-Protokolle:

Modbus-TCP/IP: Modbus TCP/IP ist eine Kombination aus dem Modbus-Protokoll, das die Master-Slave-Kommunikation zwischen Gerten ermglicht, und TCP/IP, das fr die Kommunikation ber eine Ethernet-Verbindung sorgt. Modbus TCP/IP wird fr den Datenaustausch zwischen dem EGX und anderen kompatiblen ModbusTCP/IP-Gerten ber TCP-Port 502 verwendet. Hypertext Transfer Protocol (HTTP): HTTP ist ein Netzwerkprotokoll, das die bertragung von Dateien und Daten im Internet abwickelt. Es stellt Webserver-Funktionen ber den TCP-Port 80 zur Verfgung. Hypertext Transfer Protocol Secure (HTTPS): HTTPS ist ein Netzwerkprotokoll, das die verschlsselte bertragung von Dateien und Daten mithilfe von SSL abwickelt Es stellt sichere WebserverFunktionen ber den TCP-Port 443 zur Verfgung. File Transfer Protocol (FTP): FTP ist ein Netzwerkprotokoll, mit dem Dateien ber das Internet von einem Computer zum anderen bertragen werden knnen. Sowohl der aktive als auch der passive FTP-Modus werden untersttzt hauptschlich ber TCP-Port 21. Simple Network Management Protocol (SNMP): SNMP basiert auf dem MIB-II-Format und ermglicht das Speichern und bertragen von Identifikations- und Diagnosedaten, die fr Netzwerkverwaltungszwecke ber den UDP-Port 161 benutzt werden. Address Resolution Protocol (ARP): ARP wird zur Konvertierung von IP-Adressen in Ethernet-Adressen verwendet. ARP-Anfragen werden vom EGX gesendet, um festzustellen, ob seine IP-Adresse bereits benutzt wird (siehe Erkennung identischer IP-Adressen auf Seite 8). Simple Network Time Protocol (SNTP): SNTP ist ein Protokoll, mit dem die Uhrzeit von Netzwerkgerten mithilfe eines NTP-Servers ber UDP-Port 123 synchronisiert werden kann.

Hardware
Ethernet-RJ45-Anschluss Steuerspannung

LEDs fr Ethernet und serielle Kommunikationsschnittstelle

Spannungsversorgungs-/ Status-LED

Serielle RS485Schnittstelle

DIP-Schalter zur Konfiguration von Vorspannung, Leitungsabschluss und 2-/4-LeiterVerbindung Serielle RS232-Schnittstelle (RJ45-Anschluss)

Rcksetztaste

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

61

PowerLogicTM Ethernet Gateway EGX300 Anhang B Untersttzte Gertetypen

63230-319-216B4_DE 06/2013

ANHANG B UNTERSTTZTE GERTETYPEN

Das EGX untersttzt folgende Gertetypen: Die Auflistung der untersttzten Gerte entspricht dem aktuellen Stand zum Zeitpunkt der Verffentlichung dieses Dokuments. Fr Aktualisierungen siehe www.schneider-electric.com. Tabelle 20: Vom EGX untersttzte Gertetypen
Gertegruppe Oberwellenaktivfilter Leistungsschalter Gerte Accusine Compact NSX-A Compact NSX-E PowerPact A PowerPact E Circuit Monitore CM100/200 CM2000 CM3000 CM4000 ION7500 ION7550 ION7600 ION7650 Digitalmessgerte Digitaler Temperaturregler Antriebe Energiemessgerte DM6000 DM6300 Modell 98 ATV61 ATV71 Energy Meter Enercept E5600 EM1200 EM1210 EM1250 EM1251 EM26-96 EM3550 EM3555 EM4800 EM6400 EM6433 EM6436 EM6436DUAL EM6438 EM7230 EM7280 iEM3150 iEM3155 iEM3250 iEM3255 ION8600 Isolationsberwachungsgerte Motorsteuerung Multi-Circuit Monitore (MCM) Vigilohm IM20 Vigilohm IM20-H TeSys T BCPM-Modell A BCPM-Modell B BCPM-Modell C BCM50A BCM100A MCM berlastrelais (SSOLR) Leistungsfaktorregler MotorLogic Plus MotorLogic Plus II Varlogic

62

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Anhang B Untersttzte Gertetypen

Tabelle 20: Vom EGX untersttzte Gertetypen


Gertegruppe Power Meter Gerte PM9c PM200 PM300 PM500 PM600 PM700 PM800 PM1000 PM3250 PM5100 PM5300 PM5350 PM5350BW PM5560 ION6200 (Standard und Mega) ION7300 Schutzrelais Sepam 2000 Sepam Serie 10 Sepam Serie 20 Sepam Serie 40 Sepam Serie 80 Intelligente Schnittstellenmodule SIM10Z SIM10M SIM6BZ Sanftanlasser Temperatur-/Feuchte- und Lichtsensoren Auslsesysteme ATS48 MVSS/RVSS ZED-THL-M Micrologic A Micrologic E Micrologic H Micrologic P Sonstiges Acti9 SmartLink Conext TL Wechselrichter

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63

PowerLogicTM Ethernet Gateway EGX300 Anhang B Untersttzte Gertetypen

63230-319-216B4_DE 06/2013

64

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

63230-319-216B4_DE 06/2013

PowerLogicTM Ethernet Gateway EGX300 Index Firmwareversion Ausfhrbaren Binrkomponente 59 Datei-Image-Komponente 59 FTP Datenprotokollabruf 44 Gerteprotokollexport 21 Hinzufgen von Webseiten 31 Lschen von Webseiten 31

Index
A
Analogmessgertbereich 39 Anmelden beim EGX 2 Anschluss von Gerten 12 Anzeigbare Gertetypen 33 Anzeige von Echtzeitdaten und Trendkurven 38 ARP (Address Resolution Protocol) 8 Aufzeichnung 17, 41 Datenformat 43 Gren 18 Aufzeichnungsintervalle 17

N
Netzwerk Zugang ber 2 Netzwerkzeitsynchronisation Einrichten 25

P
Prferenzen Anpassen des EGX 32 Prfpfad 34 Syslog-Feld 35 Wartungsprotokoll 35 Prfung 52

G
Gerteaufzeichnung 17, 41 Gerteerkennung 15 Gerteliste EGX 12 Gerteprotokollexport Einrichten 19 Gerteregister Lesen 56 Gertetypen, untersttzt 62 Grundmesswerteinstellungen 38

S
Schaltflche Datenpunkte Intervalldatenprotokoll 45 Serielle Schnittstelle einrichten 8 SNMP-Parameter Einrichten 26 Statistik 52 Auswerten 53 Steuerung 51 Syslog Prfpfade 35 Systemzugangspunkt Einrichten 36 Links zu anderen EGX300-Gerten 50

B
Benutzerdefinierte Webseiten Einrichten 31 Benutzerkonten Einrichten 29 Benutzeroberflche EGX 3

H
Hardware 61 HTTP Abrufen eines Intervalldatenprotokolls 45 Export Gerteprotokoll 23 Port-Nummer Einrichten 7 HTTPS Port-Nummer Einrichten 7

D
Datenprotokoll Abrufen 43 Fehlercodes 44 FTP-Abruf 44 Datenprotokollformat 43 Datum und Uhrzeit Einrichten 24

T
TCP/IP-Einstellungen 5 Trendverfolgung 40

E
Echtzeitdaten 38 EGX Anmeldung 2 Benutzeroberflche 3 Gerteliste 12 Einfhrung 1 Einrichten EGX 5 Gerteliste 13 Einstellungen der seriellen Schnittstelle Erweitert 9 Einzelgerteseiten 38, 42 E-Mail Gerteprotokollexport 19 Intervalldatenprotokoll 45 Erkennung identischer IP-Adressen 8 Ethernet- und TCP/IP-Einstellungen 5 Ethernet-Einstellungen Erweitert 6 Ethernet-Protokolle 61 Exportieren des Gerteprotokolls 19

I
Instrumententafeln 47 Intervalldatenprotokoll E-Mail 45 FTP 44 HTTP 45 Microsoft Web Query 45 Schaltflche Datenpunkte 45 Intervalle Aufzeichnung 17 IP-Adresse Erkennung identischer Adressen 8

U
bersichtsgerteseiten 39, 46 berwachung 38 Unterlagenlinks Einrichten 28 Unterlagenseite 51 Untersttzte Ethernet-Protokolle 61 Untersttzte Gertetypen 62

V
Verbindungen zu entfernten Gerten 10 Vertrauenswrdiges Zertifikat HTTPS-Port-Nr. 7

K
Kennwortsicherheit Farbcode 29 Kommunikationsprfung 57 Automatisch 57 Manuell 57

W
Wartungsprotokoll 58 Prfpfad 35 Webseiten Einrichten 30 Benutzerdefiniert 31 Hinzufgen zur/Entfernen aus Webschnittstelle 32

L
Lesen Gerteregister 56

F
Fehlercodes Datenprotokoll 44 Firmware Aktualisieren 60 Aktualisieren ber FTP 58 Neu herunterladen 59

M
Microsoft Web Query Intervalldatenprotokoll 45 Modbus-Gerte Erkennung 15 Modbus-TCP/IP-Filter Einrichten 27

Z
Zeitsynchronisation Netzwerk 25 Zugang zum EGX ber ein Netzwerk 2 Zugriffsberechtigungen fr das EGX 27 Zustzliche Ressourcen 1

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

65

PowerLogicTM Ethernet Gateway EGX300 Index

63230-319-216B4_DE 06/2013

66

2009-2013 Schneider Electric. Alle Rechte vorbehalten.

PowerLogicTM Ethernet Gateway EGX300 Benutzerhandbuch

PowerLogic ist eine Marke oder eingetragene Marke von Schneider Electric in Frankreich, den USA und anderen Lndern. Alle anderen verwendeten Marken sind das Eigentum ihrer jeweiligen Inhaber. Installierung, Anschluss und Verwendung dieses Produkts mssen unter Einhaltung der gltigen Normen und Montagevorschriften erfolgen. Aufgrund der stndigen Weiterentwicklung der Normen, Richtlinien und Materialien sind die technischen Daten und Angaben in dieser Publikation erst nach Besttigung durch unsere technischen Abteilungen verbindlich. 63230-319-216B4_DE, 06/2013 Ersetzt 63230-319-216B3_DE 03/2013 2009-2013 Schneider Electric. Alle Rechte vorbehalten.

Schneider Electric
35, rue Joseph Monier CS 30323 F - 92506 Rueil-Malmaison Cedex www.schneider-electric.com

You might also like