General
Manufacturer Name Job No. LOI No. Equipment No. Location Height above MSL Design ambient temperature Design relative humidity Plant atmospheric condition

2 3

N/A Outdoor 1000m o 50 C % 90 Corrosive, Contaminated with vapour traces, CO2, NH3, Balance Data to be filled by theHydrocarbon Vendor D1(3C X 240 SQ.MM) Requisition Data Sheet No.

Major Parameters
E2 (XLPE/PVC/GSS/FRLS-PVC) HV Power Cable IS:7098P-II/85 6.6 kV (UE) 40 kA for 3 secs (System Fault Level) Resistance Earthed No Yes 40 0.25 (For 3 Core Combined) 29 at 27 2 oC Yes Yes (By Printing) Yes (PVC end Cap) Yes

3.1 Type 3.2 Application 3.3 Standard applicable 3.4 Voltage grade 3.5 Fault level 3.6 System Earthing 3.7 Suitable for system a) Earthed b) Unearthed c) Short circuit current for 0.25 sec d) Earth fault current for 1 sec 3.8 Value of oxygen index 3.9 Chemical added to protect cable against rodent and termite attack 3.10 Sequential embossing of length provided on outer sheath at every one meter 3.11 PVC rubber end caps provided 3.12 End of cable sealed with caps to avoid ingress of water during transportation and storage

kA kA
o

4.1 Material 4.2 Number of wires 4.3 Shape 4.4 Standard applicable 4.5 Conductor Temparature i) Rated ii) During Short Circuit

Aluminium 37 Circular IS:8130/84


0 0

C C

90 250 IS:5831 ST-2 PVC Yes As per IS:7098P-II Black Extruded Cross Linked Polyethylene RED, YELLOW, BLUE colour strip shall be Applied over core 3.6(nom.) IS:7098P-II/85 Yes Conductor Screen: Extruded Semiconducting Compound

5
5.1 5.2 5.3 5.4 5.5 5.6

Inner sheath
Standard applicable Type Material Extruded Minimum thickness Colour scheme for identification

mm

6
6.1 6.2 6.3 6.4 6.5 6.6 6.7

Insulation
Type Material Colour scheme for identification Insulation thickness Standard applicable Screening Type of Screening

mm

7
7.1 7.2 7.3 7.4

Armouring
Type of material Nominal diameter of wire Thickness of strips Standard applicable mm

Galvanised steel Strips N/A 4.0 X 0.8 IS:3975 FRLS ST2(with anti-rodent & anti-termite property) as per IS: 5831/84 Black PVC

Outer sheath

8.1 Type 8.2 Colour 8.3 Material 8.4 Thickness a) Nominal b) Minimum

mm mm

N/A 2.52

8.5

Extruded

Yes mm mm mm mm 71.1 61.2 65.1 62.8 Extruded Semiconducting Compound Extruded Semiconducting Compound followed by a Copper Tape

9
9.1 9.2 9.3 9.4

Dimension
Nominal overall diameter of cable Calculated diameter under armour Nominal diameter under outer sheath Calculated diameter under outer sheath

10
10.1 10.2

Screening /shielding
Over conductor Over insulation

11

Technical parameters
W W Amp Amp Amp W

11.1 Resistance of each conductor per 1000 meters length of complete cable a) Maximum DC resistance at 20 oC b) A.C. resistance at 70 oC 11.2 Continuous AC current rating of cable a) When laid direct in ground b) When laid in ducts c) When laid in air 11.3 Equivalent star reactance per 1000 meter length of cable at 50 Hz. 11.4 Minimum volume resistivity of insulation 11.5 Maximum permissible short circuit current for duration of one second 11.6 Voltage drop per 1000 meter/amp length of cable a) When laid direct in ground b) When laid in ducts c) When laid in air 11.7 Approximate net weight per 1000 meter length of cable 11.8 Standard length of cable 11.9 Maximum tolerance on total length of cable of each type 11.10 Maximum tolerance on individual drum

0.125 0.16 315 275 395 0.085 1x104 at 270C & 1x10 at 900C 22.6 kA (For Conductor)

Volt Volt Volt kg m % % MW/km

98 86 123 6300 As per Drum Schedule +/-5% +/-5% Volume Resistivity of Each Core 1 X 1014 (Ohm-cm) at 270C & 1 X 1012 (Ohm-cm) at

12
12.1

Insulation resistance
Core to core

12.2

Core to screen

MW/km mm kg mm mm kgf kgf

Volume Resistivity of Each Core 1 X 1014 (Ohm-cm) at 270C & 1 X 1012 (Ohm-cm) at 2100 3700 Refer S.No. 13.1 above 15 Times of the cable OD. 30N/MM 9 X D2 17 kV for 5 Minutes 75 Not Applicable

13
13.1 13.2 13.3 13.4

Drum dimensions
Approximate overall height of drum Approximate gross weight of drum Approximate outer diameter of drum Minimum bending radius for laying of cables

14
14.1 14.2

Recommended pulling force


When conductor pulled by pulling eye When cable pulled with stocking

15 High Voltage Withstand Test Values 15.1 Power Frequency Withstand Voltage 15.2 Impulse Withstand Voltage 15.3 DC Withstand Voltage 16 Additional Informations 16.1 FRLS Tests a) Min. Oxygen Index test as per ASTM-D-2863 b) Min. Temp. index as per ASTM-D-2863 c) Max. Smoke density rating as per ASTM-D-2843 d) Max. Halogen acid gas evolution as per IEC-754-I e) Flammability test 16.2 Marking on outer sheath kV kV V

deg.C deg.C % %

29 at 27 + 2 0C 250 60 20 by weight IEC 332-3 Cat-C & SS-424-1475 (Cl.F3) as Applicable Manufacturer's name, Year of manufacture, Voltage grade, Size of cable,