Permissible Current Density at Earth Electrode (Id) Permissible Earth Resistance of System Detail of Plate Earthing: Plate Width Plate Height Surface Area of both sides of plate(S) Max.Current Dessipated by One Electrode Single Earth Plate Resistance
119
Parallel Traingle 8
Nos
1 Meter
2.467 Yes
12 2200 200 52.8 0.00 0.1601
Results
No of Plate Earthing Arrangement of Plate Earthing Earthing Strip / Wire For Earthing Buried in Ground Overlall Resistance of Earthing Plate Resistance of Earthing Strip/Wire Total Earth Resistance of Plate Earthing & Earth Strip
119
Parallel Yes 2.4666 0.1601
0.1503
:Calculation: Earthing Strip Size A=(IscXt)/K Current Density permissible at an Earth Electrode Id=(7.57*1000)/(xt) Amps/Sqmeter No of Plates required N=Isc/Id/S Plate R=(/S)*(/S) Ohm Pipe or Rod R= (100/2L)*log(4L/d)ohms Stip or Conductor R=(100/2L)*log(2L/wt) ohms
Permissible Current Density at Earth Electrode (Id) Permissible Earth Resistance of System Detail of Pipe Earthing: Diameter of Pipe(d) Radius of GI Pipe(R.) length of Pipe(L) Surface Area(S) Max.Current Dessipated by One Electrode Single Cast Iron Pipe Resistance
60
Parallel Hollow Sqare 8
Nos
1 Meter
0.514 Yes
12 2200 200 52.8 46961.35 0.1160
Results
No of Pipe Earthing Arrangement of Pipe Earthing Earthing Strip / Wire For Earthing Buried in Ground Overlall Resistance of Earthing Pipe/Rod Resistance of Earthing Strip/Wire Total Earth Resistance of Pipe Earthing & Earth Strip
60
Parallel Yes 0.5135 0.1160
0.0946
Normal Short Circuit Value 440KV 40 KA for 1 to 3 Sec 220KV 40 KA for 1 to 3 Sec 132KV 35 KA for 1 to 3 Sec 66KV 25 KA for 1 to 3 Sec 11KV(Urban) 35 KA for 1 to 3 Sec 11KV(Rural) 25 KA for 1 to 3 Sec 415V 10 KA for 1 to 3 Sec 220V 6 KA for 1 to 3 Sec Typical soil resistivity (IEEE 142 / BS 7430) Soil Type Avg. Resistivity (m) Wellgraded gravel 600 1000 Poorly graded gravel 1000 2500 Clayey gravel 200 400 Silty sand 100 800 Clayey sands Silty or clayey sand Fine sandy soil Gravelly clays Inorganic clays Surface Soils Clay Sandy clay Moist gravel Dry gravel Limestone Porous limestone Quartz, limestone Sandstone Granites 50 200 30 80 80 300 20 60 10 55 1 50 2 100 100 150 50 700 700 1200 5 10000 30 100 100 1000 20 2000 900 1100
Volumetric haet capacity of conductor material (Qc) Reciprocal of Tmp.coeff of Resistivity at 0 deg.Centrigade (B) Electrical resisitivity of conductorat 20 deg.Centrigade(20) Final Temprature of conductor(t) Initial Temprature of conductor(i) Value of k Constant for 1sec Allowance for Corrosion in Earth Strip Number of Year before replacement say Safety Factor Calculated Min.Earth Strip Size
Copper Aluminium 0.0345 0.025 234.5 228 0.0001724 0.0002826 395 325 40 40 205.60 126.05 0% Per Year 0 Year 1
Earthing Strip Size (Copper): Earthing Strip Size (Aluminium): Earthing Strip Size (Lead): Earthing Strip Size (GI):
No 1 1 2 1
Earthing Conductor Size for XLPE Conductor (Al.) Earthing Conductor Size for XLPE Conductor (Cu.) Earthing Conductor Size for PVC Conductor (Al.) Earthing Conductor Size for PVC Conductor (Cu.)
360.43
235.28 451.73 294.61
trip
Jignesh.N.Parmar www.electricalnotes.wordpress.com, jiguparmar@yahoo.com Normal Short Circuit Value 440KV 40 KA for 1 to 3 Sec 220KV 40 KA for 1 to 3 Sec 132KV 35 KA for 1 to 3 Sec 66KV 25 KA for 1 to 3 Sec 11KV(Urban) 35 KA for 1 to 3 Sec 11KV(Rural) 25 KA for 1 to 3 Sec 415V 10 KA for 1 to 3 Sec 220V 6 KA for 1 to 3 Sec
Actual Earth Strip Size Width(mm) Thickness(mm) Status O.K 10 20 O.K 10 30 O.K 60 10 Increase No or Size of Strip 10 20
Typical soil resistivity (IEEE 142 / BS 7430) Soil Type Avg. Resistivity (m) Wellgraded gravel 600 1000 Poorly graded gravel 1000 2500 Clayey gravel 200 400 Silty sand 100 800 Clayey sands 50 200 Silty or clayey sand 30 80 Fine sandy soil 80 300 Gravelly clays 20 60 Inorganic clays 10 55 Surface Soils 1 50 Clay 2 100 Sandy clay 100 150 Moist gravel Dry gravel Limestone Porous limestone Quartz, limestone Sandstone Granites Concrete 50 700 700 1200 5 10000 30 100 100 1000 20 2000 900 1100 300 500