On-Site Test Reports

SF6 Gas insulated Switchgear


Type EXK-0

ABB Calor Emag Hochspannung GmbH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

Table of Contents
Cover Page...............................................................................................................3
General Data ............................................................................................................4
Circuit Diagrams .......................................................................................................5
Primary Drawings .....................................................................................................6
Moisture Contents ....................................................................................................7
Gas Density Relay....................................................................................................9
WIKA Gas Density Sensor .....................................................................................14
TRAFAG Gas Density Sensor ................................................................................21
Protocol for SF6 Inventory ......................................................................................28
Gas Tightness.........................................................................................................29
High Voltage Test of the Main Circuits ...................................................................30
Voltage Drop...........................................................................................................32
Local Control Cubicle .............................................................................................33
Circuit Breaker General ..........................................................................................35
Circuit Breaker Single Pole.....................................................................................37
Disconnector...........................................................................................................43
Disconnector / Earthing Switch...............................................................................44
Earthing Switch with Short Circuit Making Capacity...............................................45
Current Transformer ...............................................................................................46
Voltage Transformer...............................................................................................47
Surge Arrester ........................................................................................................48
Earthing / Transversal Erection Module .................................................................49
Capacitive Voltage Indicator...................................................................................50
High Voltage Detection System..............................................................................51
Remarks .................................................................................................................52
Sealing of GIS Equipment ......................................................................................53

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

Cover Page
Customer

Project

Project-Nr.

Substation

Location

Country

ABB-Order No.

ABB-Installation Supervisor

ABB-Commissioning Supervisor :

Note

Hand-over on

Customers Representative

Department

Consultants Representative

Remarks

Remarks

Remarks

The commissioning protocol as part of the on-site tests is sufficiently validated by one
signature (either customers or consultants).

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

General Data
Customer:
Substation:
GIS type

No. of bays:

Layout diagram

Revision :

Standard

IEC

VDE

ANSI

BS

Installation acc. to Installation Instructions :


Filling acc. to Filling Pressure Diagram

Ratings
Voltage

kV

Control Voltage

Frequency

Hz

Auxiliary Voltage

Lightning Impulse Withstand Voltage:

kV

Auxiliary Voltage 3phase

Power Frequency Withstand Voltage:

kV

Heater Voltage

Breaking Current

kA

Voltage Drive Motor

Current Busbar

Voltage Hydraulic Pump

Current Feeder

Crane?

Yes

Current Coupler

Lifting Capacity

Commissioning finished on

Hand-over to Customer on

Energization on

Remarks

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

No

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

Circuit Diagrams
Table 1: Circuit Diagrams
Bay No.

Drawing Set No.

Rev.

Revision on

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

by

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

Primary Drawings
Table 1: Primary Drawings
Drawing No.

Rev.

Revision on

by

Circuit Diagrams
Building Plan
GIS Plan
Earthing
Gas Schematics
Sections -Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay
-Bay

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

Moisture Contents
Measuring Instrument Type

DP19

Inventory No.

Conversion (Pressure)

: 100 kPa = 1 bar

Table 1: Measurement of Moisture Contents


Bay

SF6-Gas
Compartment

Filling
Pressure
kPa

Date of
Filling

Dew Point at
Filling Pressure
(C)

Ambient Temperature (C)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

Date of
Measurement

Signature

Remarks

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

Measurement of Moisture Contents


Maximum permissible Dewpoint (measured at rated pressure): Refer to Figure 1.
10

Dewpoint Temperature

-2

-4

-6

-8

-10
0

10

15

20

25

Ambient Temperature C
Figure 1: Dewpoint

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

30

35

40

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

of

53

Gas Density Relay


Measuring Instrument Type:

DILO SK 509

Inventory No.:
Ambient Temperature:
SF6-Pressure (measured actual value):

refer to Table 1

SF6-Filling Pressure (default value):

refer to Figure 1

Table 1: SF6-Pressures
SF6-Filling Pressures
Bay

Gas Density Relay

Contact /
Signal Level

Default

Actual

Remarks

at Ambient Temperature
kPa (100 kPa = 1 bar)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

10

of

53

Gas Density Relay


Table 2: Pressure in the Gas Compartments (default values at 20 C)
Pressures at 20C

Diagram

max. kV*

Filling
Pressure

Warning
Contact

Alarm
Contact

Circuit Breaker

Figure 1

145

700 kPa

620 kPa

600 kPa

Separate Current Transformer

Figure 1

145

700 kPa

620 kPa

600 kPa

Surge Arrester AZ 41

Figure 2

500 kPa

440 kPa

420 kPa

All other Gas Compartments

Figure 3

145

600 kPa

540 kPa

520 kPa

* Rated Voltage

SF6-Filling Pressure (default value):

refer to Figure 1 to Figure 3

840
820
800

F illin g P r e s s u re

Pabs [kPa]

780
760
740
720

S ig n a l C o n ta c t 1

700

S ig n a l C o n ta c t 2
(C B B lo c k in g )

680
660
640
620
600
580
560
540
520
500
480
460
440
420
400
380

T o le r a n c e s :
F illin g P r e s s u re :
S w itc h in g P o in t:

360
340

+ 10 kPa
+ 10 kPa

320
300
-3 0

-2 0

-1 0

10

20

30

40

50

60

T
Figure 1: SF6-Filling pressure circuit breaker and separate current transformer

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

11

of

840

Pabs [kPa]

820
800
780
760
740
720
700
680
660
640
620
600
580

Filling Pressure

560
540
520
500

Signal Contact 1

480

Signal Contact 2

460
440
420
400
380

Tolerances:
Filling Pressure:
Switching Point:

360
340

+ 10 kPa
+ 10 kPa

320
300
-30

-20

-10

10

20

30

40

50

60

T
Figure 2: SF6-Filling pressure surge arrester AZ 41

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

12

of

840

Pabs [kPa]

820
800
780
760
740
720
700

Filling Pressure

680
660
640

Signal Contact 1

620
600

Signal Contact 2

580
560
540
520
500
480
460
440
420
400

Tolerances:
Filling Pressure:
Switching Point:

380
360

+ 10 kPa
+ 10 kPa

340
320
300
-30

-20

-10

10

20

30

40

50

T
Figure 3: SF6-Filling pressure for all other gas compartments

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

60

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

13

of

53

Gas Density Relay


Formula for pressure calculation in relation to the temperature
Note

The following formula are only valid for the gaseous state, not for partial liquification!
Calculation of gas pressures for ambient temperatures other than 20 C:

273 +
273 + 20

= P20

pressure at temperature

actual gas temperature in C

P20

pressure at 20C

Example:
Circuit breaker, pressure at 40C:

P40 = 700 kPa

1HDG 918 790 C en

273 + 40
= 748 kPa
273 + 20

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

14

of

53

WIKA Gas Density Sensor


Measuring Instrument Type:

Inventory No.:
SF6-Pressure (measured actual value):

refer to Table 1

SF6-Filling Pressure (default value):

refer to Table 3 and Table 4

Bay

Gas Density Sensor

Measuring point

Table 1: SF6-Pressures
SF6-Filling Pressure
TU

Measured
value with
manometer
at TU

Measured values
standardized to
20C (calculate with
equation b))

PISA sensor
value
(at 20C)

kPa

kPa

kPa

Remarks
(Permissible deviation
between measured
value from equation b)
and sensor
value 10 kPa)

1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
TU = ambient temperature (indoor installation), temperature of enclosure (outdoor installation)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

15

of

53

WIKA Gas Density Sensor


Table 2: Pressure in the Gas Compartments (default values at 20 C)
Pressures at 20C

Diagram

max. kV*

Filling
Pressure

Warning
Contact

Alarm
Contact

Circuit Breaker

Figure 1

145

700 kPa

620 kPa

600 kPa

Separate Current Transformer

Figure 1

145

700 kPa

620 kPa

600 kPa

Surge Arrester AZ 41

Figure 2

500 kPa

440 kPa

420 kPa

All other Gas Compartments

Figure 3

145

600 kPa

540 kPa

520 kPa

* Rated Voltage

SF6-Filling Pressure (default value):

refer to Figure 1 to Figure 3

840
820
800

F illin g P re s s u re

Pabs [kPa]

780
760
740
720

S ig n a l C o n ta c t 1

700

S ig n a l C o n ta c t 2
(C B B lo c k in g )

680
660
640
620
600
580
560
540
520
500
480
460
440
420
400
380

T o le r a n c e s :
F illin g P re s s u re :
S w itc h in g P o in t:

360
340

+ 10 kP a
+ 10 kP a

320
300
-3 0

-2 0

-1 0

10

20

30

40

50

60

T
Figure 1: SF6-Filling pressure circuit breaker and separate current transformer

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

16

of

840

Pabs [kPa]

820
800
780
760
740
720
700
680
660
640
620
600
580

Filling Pressure

560
540
520
500

Signal Contact 1

480

Signal Contact 2

460
440
420
400
380

Tolerances:
Filling Pressure:
Switching Point:

360
340

+ 10 kPa
+ 10 kPa

320
300
-30

-20

-10

10

20

30

40

50

60

T
Figure 2: SF6-Filling pressure surge arrester AZ 41

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

17

of

840

Pabs [kPa]

820
800
780
760
740
720
700

Filling Pressure

680
660
640

Signal Contact 1

620
600

Signal Contact 2

580
560
540
520
500
480
460
440
420
400

Tolerances:
Filling Pressure:
Switching Point:

380
360

+ 10 kPa
+ 10 kPa

340
320
300
-30

-20

-10

10

20

30

40

50

T
Figure 3: SF6-Filling pressure for all other gas compartments

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

60

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

18

of

53

WIKA Gas Density Sensor


Formula for pressure calculation in relation to the temperature
Note

The following formula are only valid for the gaseous state, not for partial liquification!
a) Calculation of gas pressures for ambient temperatures other than 20 C:
273 +
273 + 20

= P20

pressure at temperature

actual gas temperature in C = ambient temperature in C

P20 =

pressure at 20C

Example:
Circuit breaker, pressure at 40C:
P40 = 700 kPa

273 + 40
= 748 kPa
273 + 20

b) Equation for calculating the standardized gas pressure at 20 C:


P20 = P

273 + 20
273 +

pressure at temperature

actual gas temperature in C

P20 =

pressure at 20C

Example:
Gas compartment with 515 kPa at 25C:
P20 = 515 kPa

1HDG 918 790 C en

273 + 20
= 506.36 kPa
273 + 25

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Note

Page

19

of

1 kg / m3 = 1 g / l

Table 3: Conversion SF6 density into SF6 pressure for entire range 0... to 60 kg / m3 at 20C
D [kg/m3]

I [mA]

P [kPa]

D [kg/m3]

I [mA]

P [kPa]

D [kg/m3]

I [mA]

P [kPa]

0.0

4.00

000

20.0

9.33

321

40.0

14.67

616

0.5

4.13

008

20.5

9.47

328

40.5

14.80

623

1.0

4.27

017

21.0

9.60

336

41.0

14.93

630

1.5

4.40

025

21.5

9.73

344

41.5

15.07

637

2.0

4.53

033

22.0

9.87

351

42.0

15.20

644

2.5

4.67

042

22.5

10.00

359

42.5

15.33

651

3.0

4.80

050

23.0

10.13

367

43.0

15.47

658

3.5

4.93

058

23.5

10.27

374

43.5

15.60

665

4.0

5.07

066

24.0

10.40

382

44.0

15.73

672

4.5

5.20

074

24.5

10.53

389

44.5

15.87

679

5.0

5.33

083

25.0

10.67

397

45.0

16.00

686

5.5

5.47

091

25.5

10.80

404

45.5

16.13

693

6.0

5.60

099

26.0

10.93

412

46.0

16.27

700

6.5

5.73

107

26.5

11.07

419

46.5

16.40

707

7.0

5.87

115

27.0

11.20

427

47.0

16.53

713

7.5

6.00

123

27.5

11.33

434

47.5

16.67

720

8.0

6.13

131

28.0

11.47

442

48.0

16.80

727

8.5

6.27

139

28.5

11.60

449

48.5

16.93

734

9.0

6.40

148

29.0

11.73

457

49.0

17.07

741

9.5

6.53

156

29.5

11.87

464

49.5

17.20

748

10.0

6.67

164

30.0

12.00

472

50.0

17.33

754

10.5

6.80

172

30.5

12.13

479

50.5

17.47

761

11.0

6.93

180

31.0

12.27

486

51.0

17.60

768

11.5

7.07

188

31.5

12.40

494

51.5

17.73

775

12.0

7.20

196

32.0

12.53

501

52.0

17.87

781

12.5

7.33

203

32.5

12.67

508

52.5

18.00

788

13.0

7.47

211

33.0

12.80

516

53.0

18.13

795

13.5

7.60

219

33.5

12.93

523

53.5

18.27

801

14.0

7.73

227

34.0

13.07

530

54.0

18.40

808

14.5

7.87

235

34.5

13.20

537

54.5

18.53

815

15.0

8.00

243

35.0

13.33

545

55.0

18.67

821

15.5

8.13

251

35.5

13.47

552

55.5

18.80

828

16.0

8.27

259

36.0

13.60

559

56.0

18.93

834

16.5

8.40

266

36.5

13.73

566

56.5

19.07

841

17.0

8.53

274

37.0

13.87

573

57.0

19.20

848

17.5

8.67

282

37.5

14.00

580

57.5

19.33

854

18.0

8.80

290

38.0

14.13

588

58.0

19.47

861

18.5

8.93

298

38.5

14.27

595

58.5

19.60

867

19.0

9.07

305

39.0

14.40

602

59.0

19.73

874

19.5

9.20

313

39.5

14.53

609

59.5

19.87

880

60.0

20.00

887

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Note

Page

20

of

1 kg / m3 = 1 g / l

Table 4: Conversion SF6 density into SF6 pressure for partial range 25... to 48.8 kg / m3 at 20C
D [kg/m3]

I [mA]

P [kPa]

D [kg/m3]

I [mA]

P [kPa]

D [kg/m3]

I [mA]

P [kPa]

25.0

10.67

397

33.0

12.80

516

41.0

14.93

630

25.2

10.72

400

33.2

12.85

518

41.2

14.99

633

25.4

10.77

403

33.4

12.91

521

41.4

15.04

636

25.6

10.83

406

33.6

12.96

524

41.6

15.09

639

25.8

10.88

409

33.8

13.01

527

41.8

15.15

641

26.0

10.93

412

34.0

13.07

530

42.0

15.20

644

26.2

10.99

415

34.2

13.12

533

42.2

15.25

647

26.4

11.04

418

34.4

13.17

536

42.4

15.31

650

26.6

11.09

421

34.6

13.23

539

42.6

15.36

653

26.8

11.15

424

34.8

13.28

542

42.8

15.41

655

27.0

11.20

427

35.0

13.33

545

43.0

15.47

658

27.2

11.25

430

35.2

13.39

547

43.2

15.52

661

27.4

11.31

433

35.4

13.44

550

43.4

15.57

664

27.6

11.36

436

35.6

13.49

553

43.6

15.63

667

27.8

11.41

439

35.8

13.55

556

43.8

15.68

669

28.0

11.47

442

36.0

13.60

559

44.0

15.73

672

28.2

11.52

445

36.2

13.65

562

44.2

15.79

675

28.4

11.57

448

36.4

13.71

565

44.4

15.84

678

28.6

11.63

451

36.6

13.76

568

44.6

15.89

680

28.8

11.68

454

36.8

13.81

570

44.8

15.95

683

29.0

11.73

457

37.0

13.87

573

45.0

16.00

686

29.2

11.79

460

37.2

13.92

576

45.2

16.05

689

29.4

11.84

463

37.4

13.97

579

45.4

16.11

691

29.6

11.89

466

37.6

14.03

582

45.6

16.16

694

29.8

11.95

469

37.8

14.08

585

45.8

16.21

697

30.0

12.00

472

38.0

14.13

588

46.0

16.27

700

30.2

12.05

474

38.2

14.19

590

46.2

16.32

703

30.4

12.11

477

38.4

14.24

593

46.4

16.37

705

30.6

12.16

480

38.6

14.29

596

46.6

16.43

708

30.8

12.21

483

38.8

14.35

599

46.8

16.48

711

31.0

12.27

486

39.0

14.40

602

47.0

16.53

713

31.2

12.32

489

39.2

14.45

605

47.2

16.59

716

31.4

12.37

492

39.4

14.51

608

47.4

16.64

719

31.6

12.43

495

39.6

14.56

610

47.6

16.69

722

31.8

12.48

498

39.8

14.61

613

47.8

16.75

724

32.0

12.53

501

40.0

14.67

616

48.0

16.80

727

32.2

12.59

504

40.2

14.72

619

48.2

16.85

730

32.4

12.64

507

40.4

14.77

622

48.4

16.91

733

32.6

12.69

510

40.6

14.83

625

48.6

16.96

735

32.8

12.75

513

40.8

14.88

627

48.8

17.01

738

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

21

of

53

TRAFAG Gas Density Sensor


Measuring Instrument Type:
Inventory No.:
SF6-Pressure (measured actual value):

refer to Table 1

SF6-Filling Pressure (default value):

refer to Table 3 and Table 4

Bay

Gas Density Sensor

Measuring point

Table 1: SF6-Pressures
SF6-Filling Pressure
TU

Measured
value with
manometer
at TU

Measured values
standardized to
20C (calculate with
equation b))

Sensor value
(at 20C)

kPa

kPa

kPa

Remarks
(Permissible deviation
between measured
value from equation b)
and sensor
value 10 kPa)

1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
TU = ambient temperature (indoor installation), temperature of enclosure (outdoor installation)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

22

of

53

TRAFAG Gas Density Sensor


Table 2: Pressure in the Gas Compartments (default values at 20 C)
Pressures at 20C

Diagram

max. kV*

Filling
Pressure

Warning
Contact

Alarm
Contact

Circuit Breaker

Figure 1

145

700 kPa

620 kPa

600 kPa

Separate Current Transformer

Figure 1

145

700 kPa

620 kPa

600 kPa

Surge Arrester AZ 41

Figure 2

500 kPa

440 kPa

420 kPa

All other Gas Compartments

Figure 3

145

600 kPa

540 kPa

520 kPa

* Rated Voltage

SF6-Filling Pressure (default value):

refer to Figure 1 to Figure 3

840
820
800

F illin g P re s s u re

Pabs [kPa]

780
760
740
720

S ig n a l C o n ta c t 1

700

S ig n a l C o n ta c t 2
(C B B lo c k in g )

680
660
640
620
600
580
560
540
520
500
480
460
440
420
400
380

T o le r a n c e s :
F illin g P re s s u re :
S w itc h in g P o in t:

360
340

+ 10 kP a
+ 10 kP a

320
300
-3 0

-2 0

-1 0

10

20

30

40

50

60

T
Figure 1: SF6-Filling pressure circuit breaker and separate current transformer

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

23

of

840

Pabs [kPa]

820
800
780
760
740
720
700
680
660
640
620
600
580

Filling Pressure

560
540
520
500

Signal Contact 1

480

Signal Contact 2

460
440
420
400
380

Tolerances:
Filling Pressure:
Switching Point:

360
340

+ 10 kPa
+ 10 kPa

320
300
-30

-20

-10

10

20

30

40

50

60

T
Figure 2: SF6-Filling pressure surge arrester AZ 41

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

24

of

840

Pabs [kPa]

820
800
780
760
740
720
700

Filling Pressure

680
660
640

Signal Contact 1

620
600

Signal Contact 2

580
560
540
520
500
480
460
440
420
400

Tolerances:
Filling Pressure:
Switching Point:

380
360

+ 10 kPa
+ 10 kPa

340
320
300
-30

-20

-10

10

20

30

40

50

T
Figure 3: SF6-Filling pressure for all other gas compartments

1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

60

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

25

of

53

TRAFAG Gas Density Sensor


Formula for pressure calculation in relation to the temperature
Note

The following formula are only valid for the gaseous state, not for partial liquification!
a) Calculation of gas pressures for ambient temperatures other than 20 C:
273 +
273 + 20

= P20

pressure at temperature

actual gas temperature in C = ambient temperature in C

P20 =

pressure at 20C

Example:
Circuit breaker, pressure at 40C:
P40 = 700 kPa

273 + 40
= 748 kPa
273 + 20

b) Equation for calculating the standardized gas pressure at 20 C:


P20 = P

273 + 20
273 +

pressure at temperature

actual gas temperature in C

P20 =

pressure at 20C

Example:
Gas compartment with 515 kPa at 25C:
P20 = 515 kPa

1HDG 918 790 C en

273 + 20
= 506.36 kPa
273 + 25

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Note

Page

26

of

1 kg / m3 = 1 g / l

Table 3: Conversion SF6 density into SF6 pressure for entire range 0... to 60 kg / m3 at 20C

D [kg/m3]

f [Hz]

P [kPa]

D [kg/m3]

0.0

10.00

000

20.0

113.23

321

40.0

206.71

616

0.5

14.80

008

20.5

115.60

328

40.5

209.02

623

1.0

18.06

017

21.0

117.97

336

41.0

211.33

630

1.5

21.06

025

21.5

120.34

344

41.5

213.64

637

2.0

23.93

033

22.0

122.70

351

42.0

215.95

644

2.5

26.71

042

22.5

125.07

359

42.5

218.26

651

3.0

29.44

050

23.0

127.43

367

43.0

220.56

658

3.5

32.12

058

23.5

129.78

374

43.5

222.87

665

4.0

34.77

066

24.0

132.14

382

44.0

225.18

672

4.5

37.38

074

24.5

134.49

389

44.5

227.48

679

5.0

39.97

083

25.0

136.84

397

45.0

229.78

686

5.5

42.54

091

25.5

139.19

404

45.5

232.09

693

6.0

45.10

099

26.0

141.54

412

46.0

234.39

700

6.5

47.63

107

26.5

143.89

419

46.5

236.69

707

7.0

50.16

115

27.0

146.23

427

47.0

238.99

713

7.5

52.67

123

27.5

148.57

434

47.5

241.29

720

8.0

55.17

131

28.0

150.92

442

48.0

243.59

727

8.5

57.65

139

28.5

153.26

449

48.5

245.89

734

9.0

60.13

148

29.0

155.59

457

49.0

248.19

741

9.5

62.60

156

29.5

157.93

464

49.5

250.48

748

10.0

65.07

164

30.0

160.27

472

50.0

252.78

754

10.5

67.52

172

30.5

162.60

479

50.5

255.08

761

11.0

69.97

180

31.0

164.93

486

51.0

257.37

768

11.5

72.41

188

31.5

167.26

494

51.5

259.66

775

12.0

74.85

196

32.0

169.59

501

52.0

261.96

781

12.5

77.28

203

32.5

171.92

508

52.5

264.25

788

13.0

79.70

211

33.0

174.25

516

53.0

266.54

795

13.5

82.12

219

33.5

176.57

523

53.5

268.84

801

14.0

84.54

227

34.0

178.90

530

54.0

271.13

808

14.5

86.95

235

34.5

181.22

537

54.5

273.42

815

15.0

89.36

243

35.0

183.54

545

55.0

275.71

821

15.5

91.76

251

35.5

185.87

552

55.5

278.00

828

16.0

94.16

259

36.0

188.19

559

56.0

280.29

834

16.5

96.56

266

36.5

190.50

566

56.5

282.58

841

f [Hz]

P [kPa]

D [kg/m3]

f [Hz]

P [kPa]

17.0

98.95

274

37.0

192.82

573

57.0

284.86

848

17.5

101.34

282

37.5

195.14

580

57.5

287.15

854

18.0

103.72

290

38.0

197.46

588

58.0

289.44

861

18.5

106.10

298

38.5

199.77

595

58.5

291.73

867

19.0

108.48

305

39.0

202.08

602

59.0

294.01

874

19.5

110.86

313

39.5

204.40

609

59.5

296.30

880

60.0
1HDG 918 790 C en

01.06.2005 EXTMEHA

01.06.2005 CHSVOTH

887

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Note

Page

27

of

1 kg / m3 = 1 g / l

Table 4: Conversion SF6 density into SF6 pressure for partial range 25... to 48.8 kg / m3 at 20C

D [kg/m3]

f [Hz]

P [kPa]

25.0

136.84

397

33.0

174.25

516

41.0

211.33

630

25.2

137.78

400

33.2

175.18

518

41.2

212.26

633

25.4

138.72

403

33.4

176.11

521

41.4

213.18

636

25.6

139.66

406

33.6

177.04

524

41.6

214.10

639

25.8

140.60

409

33.8

177.97

527

41.8

215.03

641

26.0

141.54

412

34.0

178.90

530

42.0

215.95

644

26.2

142.48

415

34.2

179.83

533

42.2

216.87

647

26.4

143.42

418

34.4

180.76

536

42.4

217.80

650

26.6

144.36

421

34.6

181.69

539

42.6

218.72

653

26.8

145.29

424

34.8

182.62

542

42.8

219.64

655

27.0

146.23

427

35.0

183.54

545

43.0

220.56

658

27.2

147.17

430

35.2

184.47

547

43.2

221.49

661

27.4

148.11

433

35.4

185.40

550

43.4

222.41

664

27.6

149.04

436

35.6

186.33

553

43.6

223.33

667

27.8

149.98

439

35.8

187.26

556

43.8

224.25

669

28.0

150.92

442

36.0

188.19

559

44.0

225.18

672

28.2

151.85

445

36.2

189.11

562

44.2

226.10

675

28.4

152.79

448

36.4

190.04

565

44.4

227.02

678

28.6

153.72

451

36.6

190.97

568

44.6

227.94

680

28.8

154.66

454

36.8

191.90

570

44.8

228.86

683

29.0

155.59

457

37.0

192.82

573

45.0

229.78

686

29.2

156.53

460

37.2

193.75

576

45.2

230.70

689

29.4

157.46

463

37.4

194.68

579

45.4

231.63

691

29.6

158.40

466

37.6

195.60

582

45.6

232.55

694

29.8

159.33

469

37.8

196.53

585

45.8

233.47

697

30.0

160.27

472

38.0

197.46

588

46.0

234.39

700

30.2

161.20

474

38.2

198.38

590

46.2

235.31

703

30.4

162.13

477

38.4

199.31

593

46.4

236.23

705

30.6

163.07

480

38.6

200.23

596

46.6

237.15

708

30.8

164.00

483

38.8

201.16

599

46.8

238.07

711

31.0

164.93

486

39.0

202.08

602

47.0

238.99

713

31.2

165.86

489

39.2

203.01

605

47.2

239.91

716

31.4

166.80

492

39.4

203.94

608

47.4

240.83

719

31.6

167.73

495

39.6

204.86

610

47.6

241.75

722

31.8

168.66

498

39.8

205.79

613

47.8

242.67

724

32.0

169.59

501

40.0

206.71

616

48.0

243.59

727

32.2

170.52

504

40.2

207.63

619

48.2

244.51

730

32.4

171.46

507

40.4

208.56

622

48.4

245.43

733

32.6

172.39

510

40.6

209.48

625

48.6

246.35

735

32.8

173.32

513

40.8

210.41

627

48.8

247.27

738

1HDG 918 790 C en

D [kg/m3]

01.06.2005 EXTMEHA

f [Hz]

P [kPa]

D [kg/m3]

f [Hz]

01.06.2005 CHSVOTH

P [kPa]

53

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

28

of

53

Protocol for SF6 Inventory


Customer:
Designation of substation:
No. of bays:

Delivery amount of SF6


Amount of SF6 in bay gas compartments:

kg

Amount of SF6 in gas bottles:

Pieces

Total delivered amount of SF6:

kg
kg

Mounting of the GIS


Amount of SF6 filled in substation:

kg

Remaining SF6 in gas bottles:

Pieces

kg

Amount of remaining rest of SF6


Amount of SF6 bottles delivered to customer:

Pieces

Total amount of SF6 delivered to customer:

kg

Recipient at customer site:


Name:
Department:
Amount of SF6 bottles returning to WGA:

Pieces

Total amount of SF6 returning to WGA:

kg

Recipient in WGA:
Name:
Department:

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

29

of

53

Gas Tightness
Measurement Instrument Type:

L-780 a

Inventory No.:
Table 1: Test for Gas Tightness
Gas Compartment-Identification through:
Bay

Electrical Designation of
Gas Density Relay

o.k.

Remarks

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

30

of

53

High Voltage Test of the Main Circuits


Resonance Test Set

Step Transformator No.

Test Transformator No.

Peak Voltage Test Device No.

Test Adapter No.

Power of Test Transformer

Test Voltages Up

: refer to Table 1

kVA

Table 1: Test Voltages


Rated Voltage

BIL

Test Duration

Test Voltage Up

kV

kV

min

kV

72.5

325

120

123

550

200

145

650

235

Gas Pressure for High Voltage Test of the Main Circuits


Table 2: Pressure in the Gas Compartment (default values at 20 C)
Pressures at 20 / 293 Kelvin

Max. Rated Voltage [kV]

Filling Pressure

Circuit Breaker

145

700 kPa

Separate Current Transformer

145

700 kPa

Surge Arrester AZ 41

145

500 kPa

All other Gas Compartments

145

600 kPa

Note

All the procedures associated with carrying out the high voltage test of the main circuits
are described in detail in the product manual in chapter Commissioning in document
1HDG 918 742 High Voltage Test of the Main Circuits.

Note

The filling pressures for other ambient temperatures are listed in this document in section
Gas Density Relay.

Note

All works associated with the handling of SF6 are described in detail in the product
manual in chapter Gas Insulated Switchgear in document 1HDG 518 012 Sulphur
Hexafluoride.
For the test values please refer to Table 3

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

31

of

53

High Voltage Test of the Main Circuits


Test Unit mounted on

Circuit Diagram No.

Test Voltage Up

Revision

(default value) :

kV

: I2 (mA ) =

Calculation formula

I1 (A) U1 (V )
U p (kV )

Table 3: Test Values


Bay

Device Designation

Phase

Primary Voltage U1

Primary Current I1

Test Voltage Up

kV

L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

32

of

53

Voltage Drop
Measuring Instrument Type

: Micro Ohmmeter 600 A

Inventory No.:

Conversion Formula

: U (mV ) =

I ( A)xR( Ohm )
1000

(adjusted current range: 200 A DC)


Note

The procedures associated with the measurement of the voltage drop and the related
default values for the individual components are listed in the product manual in chapter
Commissioning in document 1HDG 918 740 Tests Prior to Commissioning.

A. Phasing checked acc. to primary drawings

B. Values of voltage drop measured (s. Table 1)

Table 1: Measurement of Voltage Drop


Designation of Measuring Point
in accordance with the Circuit
Diagram

Phase

Actual Value (measured)


mV

Ohm

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

Remarks

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

33

of

53

Local Control Cubicle


Bay

Customer Designation

O.K. at Commissioning
A. Visual Check for external Damages

B. Bay Interlocking

C. Station Interlocking

D. Antipumping Circuit Breaker

E. All Messages checked acc. to Signal List

F. Circuit Breaker Blocking (Operating Mechanism)


AR

CLOSE

OPEN I

OPEN II

G. Protection Trip on Relay or Terminal Block

H. Electrical Plug-Connections (Plugs) secured with Screws

I. Check of Position Indicators


Circuit Breaker

Disconnector / Earthing Switch

Disconnector

Earthing Switch

Earthing Switch with Short Circuit Making Capacity

J. Check of Control Circuits acc. to Function Chart

K. Functional Check of Anti-Condensation Heaters

L. Adjustment of Timing Relays acc. to Operating Schematics

For Test Values please refer to Table 1

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

34

of

53

Local Control Cubicle


Table 1: Test Values
Device Designation

Default Value

Actual Value (measured)

Timing Relay K210

60 s

Timing Relay K301

20 s

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

35

of

53

Circuit Breaker General

CAUTION

Bay

Customer Designation

Device Designation

Component No.

CB-Chamber Type

Measuring Instrument Type

TM 1600
TM 16______

The Circuit Breaker may only be operated when filled with SF6 (min. 600 kPa)!

O.K. at Commissioning
A. Visual Inspection for external Damages

B. Check Counter for Operating Hours

C. Check that the locking varnish on the throttle screw for setting
the operating mechanism speed is undamaged

D. Functional Check of Anti-Condensation Heater (if provided)

E. Check the carbon brushes (minimum height 11 mm)

F. Check if the stored operating sequence is enabled from control cubicle without blocking

G. Visual Check of Operating Mechanism Elements: Rotary Bushing on the Operating Mechanism

H. Visual Check of Operating Mechanism Elements: Auxiliary Switches, Position Indicator

I. Check of the Electrical Plug-Connections for secure Contacting

J. Check the Numbers of Operations and Pump Starts

Operations:
_________ Date:_______________
Pump Starts:
_________ Date:_______________
K. Functional Test acc. to Circuit Diagram (Engineering Document)
L. Charging Time of Hydraulic Operating Mechanism from 0 to Operating Pressure _______________s
M. Setting time relays:
k_________________ Actual value: ____________________ Specified value: ___________________
k_________________ Actual value: ____________________ Specified value: ___________________
k_________________ Actual value: ____________________ Specified value: ___________________
k_________________ Actual value: ____________________ Specified value: ___________________

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

36

of

53

Circuit Breaker General


O.K. at Commissioning
N. Check for simultaneity of contact separation: 3 ms

O. Functional check of circuit breaker (Table 1)

Table 1: Functional check of circuit breaker

Functional Check

OPEN I *

OPEN II *

OPEN III *

OPEN IV *

CLOSE I *

CLOSE II *

tOPEN = From opening impulse until contact separation,


tCLOSE = From closing impulse until contact touch,
The measured values shall not exceed a deviation of 3 ms compared with
the factory routine-tests.**

Phase L1 (ms)
factory / on site
Phase L2 (ms)
factory / on site
Phase L3 (ms)
factory / on site
t (ms) O.K.
[YES/NO]

Measurements to be performed with fully charged operating mechanism and 100% supply voltage.

**

The switching cycle times are described in detail in the product documentation in chapter
Equipment and Functional Descriptions in document 1HDG 918 750 Circuit Breaker.

Protocol strips of time measurement -> please refer to the following page(s)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

37

of

53

Circuit Breaker Single Pole


Additional tests required for circuit breaker with single pole operating mechanism
(Table 2):
O.K. at Commissioning
P. Check for simultaneity of contact making: 3 ms

Q. Check for simultaneity of contact separation during CO switching: 5 ms

Table 2: Additional tests required for Circuit Breaker with single pole operating mechanism
CLOSE I OPEN II *

CLOSE I OPEN II *

Functional Check

Test of switching time for CO operation with shortest close-open time:


From closing impulse to contact separation at CO switching = 60 ms - 100 ms

Phase L1 (ms)
factory / on site
Phase L2 (ms)
factory / on site
Phase L3 (ms)
factory / on site
t (ms) O.K.
[YES/NO]

* Measurements to be performed with fully charged operating mechanism and 100% supply voltage.

Protocol strips of time measurement -> please refer to the following page(s)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

38

of

53

Circuit Breaker
Protocol Strip of Time Measurement: OPEN I (Figure 1)

Figure 1: Protocol Strip of Time Measurement: OPEN I

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

39

of

53

Circuit Breaker
Protocol Strip of Time Measurement: OPEN II (Figure 2)

Figure 2: Protocol Strip of Time Measurement: OPEN II

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

40

of

53

Circuit Breaker
Protocol Strip of Time Measurement: CLOSE I (Figure 3)

Figure 3: Protocol Strip of Time Measurement: CLOSE I

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

41

of

53

Circuit Breaker
Protocol Strip of Time Measurement: OPEN I CLOSE I (Figure 4)

Figure 4: Protocol Strip of Time Measurement: OPEN I CLOSE I

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

42

of

53

Circuit Breaker
Protocol Strip of Time Measurement: OPEN II CLOSE I (Figure 5)

Figure 5: Protocol Strip of Time Measurement: OPEN II CLOSE I

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

43

of

53

Disconnector
Bay

Customer Designation

Device Designation

Component No.

Type

Location

BB1

BB2

BB3

Feeder

O.K. at Commissioning
A. Visual Inspection for external Damages

B. Visual Inspection of Operating Mechanism Elements

C. Functional Check of Operating Mechanism mechanical (with Handcrank) CLOSE / OPEN

D. Functional Check of Signalling Devices:

Limit Switch, Interlocking Switch (Hand crank), Position Indicator, Auxiliary Switches
E. Check Interlocking of Handcrank

F. Check Key-Interlocking

G. Functional Check of Operating Mechanism electrical CLOSE / OPEN

H. Performance Check:

Measurement of Motor Current at Auxiliary Voltage: __________ V


Motor Current:

CLOSE: __________ A

OPEN: __________ A

I. Electrical Plug-Connections (Plugs) secured with Screws

J. Functional Check of Anti-Condensation Heater (if applicable)

K. Visual Inspection of electrical Connections

L. Functional Check acc. to Circuit Diagrams (planning standard)

Note

All default values for the disconnector are listed in chapter Equipment Descriptions in
document Disconnector / Earthing Switch 1HDG 918 754.

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

44

of

53

Disconnector / Earthing Switch


Bay

Customer Designation

Device Designation

Device No.

Type

Location

BB1

BB2

BB3

Feeder

O.K. at Commissioning
A. Visual Inspection for external Damages

B. Visual Inspection of Operating Mechanism Elements

C. Functional Check of Operating Mechanism mechanical (Handcrank) CLOSE / OPEN

D. Functional Check of Signalling Devices:

Limit Switches, Interlocking Switch (Hand crank), Position Indicators, Auxiliary Switches
E. Check the Handcrank Interlocking

F. Check the Key-Interlocking

G. Functional Check of the Operating Mechanism electrical CLOSE / OPEN

H. Performance Check:

Measurement of Motor Current at Auxiliary Voltage:


Disconnector:
Motor Current CLOSE: _________ A OPEN: _________ A
Earthing Switch: Motor Current CLOSE: _________ A OPEN: _________ A
I. Electrical Plug-Connections (Plugs) secured with Screws

J. Functional Check of Anti-Condensation Heater (if applicable)

K. Visual Inspection of electrical Connections

L. Functional Check acc. to Circuit Diagrams (planning standard)

Note

All default values for the disconnector / earthing switch are listed in the product manual
in chapter Equipment and Functional Descriptions in document Disconnector /
Earthing Switch 1HDG 918 754.

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

45

of

53

Earthing Switch with Short Circuit Making Capacity

Note

Bay

Customer Designation

Device Designation

Device No.

Type

Location

BB1

BB2

BB3

Feeder

The default values for the earthing switch with short circuit making capacity are listed in
the product manual in chapter Equipment and Functional Descriptions in document
Earthing Switch with Short Circuit Making Capacity 1HDG 918 756.

O.K. at Commissioning
A. Visual Inspection for external Damages

B. Visual Inspection of Operating Mechanism Elements

C. Functional Check of Operating Mechanism mechanical (Handcrank) CLOSE / OPEN

D. Functional Check of Signalling Devices:


Limit Switches, Interlocking Switch (Hand crank), Position Indicator, Auxiliary Switches
E. Check of Handcrank Interlocking
F. Check of Key-Interlocking
G. Functional Check of the Operating Mechanism electrical CLOSE / OPEN
H. Performance Check:
Measurement of Motor Current at Auxiliary Voltage: __________ V
Motor Current: CLOSE: __________ A
OPEN: __________ A
I. Electrical Plug-Connections (Plugs) secured with Screws
J. Functional Check of Anti-Condensation Heaters (if applicable)
K. Visual Inspection of electrical Connections
L. Inspection of Contact Bands: Phase - Enclosure
Phase L1
Phase L2
Phase L3
M. Functional Check acc. to Circuit Diagrams (planning standard)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

46

of

53

Current Transformer
Bay

Customer Designation

Current Transformer Type

Location

Manufacturer

Manufacturer Type

Fabrication No.

Current Transformer Ratings:

please refer to Table 1

Table 1: Current Transformer Ratings


Core I

Core II

Core III

Core IV

Core V

Ratio
Burden
Accuracy

O.K. at Commissioning
A. Inspection of Connections and Earthing through ABB

B. Inspection of Connections and Earthing through:_________________________

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

47

of

53

Voltage Transformer
Bay

Customer Designation

Voltage Transformer Type

Location

Manufacturer

Manufacturer Type

Fabrication No.

Voltage Transformer Ratings:

please refer to Table 1

Table 1: Voltage Transformer Ratings


Winding I

Winding II

Winding III

Winding IV

Ratio
Burden
Accuracy

O.K. at Commissioning
A. Visual Inspection for external Damages

B. Visual Inspection of the Shock Indicators

C. Inspection of Connections and Earthing through ABB

D. Inspection of Connections and Earthing through:

E. Inspection of Fuses
F

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

48

of

53

Surge Arrester
Bay

Customer Designation

Type

Location

Manufacturer

Manufacturer Type

Fabrication No.

Max. perm. cont. Operating Voltage

kV [RMS]

O.K. at Commissioning
A. Visual Inspection for external Damages

B. Visual Inspection of Shock Indicator

C. Inspection of Connections

D. Earthing

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

49

of

53

Earthing / Transversal Erection Module


Bay

Customer Designation

Earthing acc. to Drawing No.

Revision

O.K. at Commissioning
A. Inspection of bolted and pressed Connections

B. Cable Trays earthed

C. SF6-Air Bushings earthed

D. Surge Arrestors earthed

E. Local Control Cabinets earthed

F. Base Frame earthed (if applicable)

G. HV Cables earthed (Arrestor or Spark Gap)

H. Circuit Breaker earthed

I. Transversal Erection Module: Bolts of Compensation Unit loosened and secured

J. Transversal Erection Module: Bolts of Shorting Bridge tightened

K. Outdoor Flange Connections greased

L. REC 580 earthed (SMART-GIS only)

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

50

of

53

Capacitive Voltage Indicator


Bay

Customer Designation

Equipment Designation

Component No.

Type

O.K. at Commissioning
A. Visual Inspection for external and internal Damages

B. Electrical Plug and Socket Connections (plug) screwed-in

C. System-Check

D. Electrical functional check


Voltage at MP1~0,65 V RMS

by earthing switchgear

green LED

by current voltage

red LED

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

51

of

53

High Voltage Detection System


Bay

Customer Designation

Equipment Designation

Component No.

Type

O.K. at Commissioning
A. Visual Inspection for external Damages

B. Electrical Plug and Socket Connections (plug) screwed-in

C. Function check at earthed arrangement


Lightning symbols not indicated

LED indication as shown in Figure 1

D. Function check at rated voltage


LED indication as shown in Figure 2

O
H

V
H

ff
Er
ro
r
Po
w
er

Lightning symbols completely displayed

Er
ro
r
Po
w
er

V
H

ff

Figure 1: LED display at earthed arrangement

Figure 2: LED display at rated voltage

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

52

of

53

Remarks

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH

Product Documentation GIS Type EXK-0


On-Site Test

Commissioning Protocol

Page

53

of

53

Sealing of GIS Equipment


Customer

Project

Project No.

DECES Commission Supervisor

Date of sealing

Equipment and Seal No.

: refer to Table 1

Table 1: Equipment and Seal No.


Feeder

Note

Equipment

Seal No.

Seals are not allowed to be removed by unauthorised personnel, any broken seal must
be reported immediately to DECES.

Tested:

Approved:

________________________________
Date, ABB

_______________________________
Date, Customer

1HDG 918 790 C en

01.06.2005 EXTMEHA

_____________________________
Date, Consultant

01.06.2005 CHSVOTH