KEC is one of the oldest players in the industry and global leader in the Infrastructure Engineering, Procurement and Construction
space. Established in 1945, KEC has a signicant presence in the segments of Power Transmission & Distribution, Cabling, Railway,
Telecom and Water Resource management. KECs strengths lie in Engineering, Design, Manufacture and Testing, supply of
transmission towers, telecom towers, cables and Construction of turnkey infrastructure projects. KECs focused approach towards
project management enables the creation of world class products, innovative solutions, customized to overcome extreme terrain
and climate. With proven technical prowess in handling mega projects and superior project management expertise, KEC has made
an indelible mark on the world map by constantly and consistently reengineering itself to retain its position of leadership in the
areas of quality, technology, capacity and capability.

RPG
ENTERPRISES
RPG Enterprises is one of Indias largest business conglomerates. Since its inception in 1979, RPG Enterprises has been one
of the fastest growing business houses in India. RPG Enterprises has diverse businesses under its fold ranging from Power,
Tyres, Infrastructure, IT to Pharma. The Groups management comprises individuals extensively qualied and experienced in
their domain areas. RPGs wide ranging business invite growing returns and high esteem in the eyes of all its stakeholders. The
Group lives by values of keen entrepreneurial skills, performance and excellence.

COMPANY
PROFILE

Silvassa Plant

Mysore Plant

Thane Plant

RPG Cables, a division of KEC International Limited has established itself as


one of the leading manufacturers of Power, Control & Telecommunication
cables in India. One of the oldest cable manufacturing company (1958), we
have been serving the industries with quality cables for over 5 decades. The
state-of-the art manufacturing plants are located at Thane for HT cables
upto 33 kV and EHV cables upto 132 kV and Silvassa for LT cables upto 1.1
kV (power and control). The manufacturing facility at Mysore manufactures
LT Power and Control Cables, apart from Telecom Cables (Fiber Optic & Jelly
Filled), Instrumentation, Fire Survival and Signaling Cables. RPG Cables also
offers expertise in Turnkey contracts involving cable laying, jointing, testing
and commissioning. To keep pace with the changing needs of the customers
and requirement of cables for voltage grades above 132 kV, the company is
coming up with a new manufacturing unit near Halol, Gujarat with capability
to manufacture cables up to 400 kV. The brand name Asian is synonymous
with stringent norms in quality, environment and safety management. The
plants have been ISO 9000 and ISO 14000 certied.
RPG cables has been making major export thrust in keeping with its global
aspirations. We match international quality standards and cables can be
designed to comply with required international standards. The division
has also been given recognition by the Govt. of Maharashtra for achieving
excellence in Exports.

TECHNICAL CATALOGUE

HV CABLES

ELEMENTS IN
HV CABLES
TYPICAL CROSS-SECTIONAL SKETCHES
CONDUCTOR
Aluminium/Copper

CONDUCTOR SCREEN
INSULATION
NON METALLIC INSULATION SCREEN
METALLIC INSULATION SCREEN
PVC INNER SHEATH
GALVANISED STEEL ARMOUR
PVC OUTER SHEATH
FILLERS

CABLE CONSTRUCTION
Conductor

Insulation

Stranded compacted circular conductors are composed of


Electrolytic grade high conductivity Aluminium wires or Copper,
Circular, stranded with high compactness.

The insulation is of natural, chemically cross linked polyethylene


with high di-electric strength is extruded over semiconducting
conductor screening. Thickness of insulation is as per the
relevant tables.

Conductor Screening / Shielding


Conductors for cables rated above 3.3 kV are screened with an
extruded layer of semiconducting compound . This eliminates
the chance of electrical discharge at the interface between
conductor and insulation.

Insulation screening
Cables rated above 3.3 kV will have a screening consisting
of non metallic part, in combination with a metallic part over
the insulation. The non-metallic part of the screening consists

of either a semiconducting tape applied helically or a layer of


extruded semi-conducting compound or both. The conductor
screening, XLPE insulation and the non-metallic part of
insulation screening are all extruded in one operation by
TRIPLE EXTRUSION which eliminates the formation of micro
voids during the extrusion and curing resulting in longer life
of cables.
Over this layer a bare annealed copper tape / copper wire
is applied.

Laying up
Insulated conductors of three cores are laid up together,
interstices lled up with non hygroscopic llers to make the
cable circular.
The phase identication of three core cable is done either
by coloured / numbered strips applied on the cores or by the
numerals printed on the cores.

Inner Sheath
The cable cores are provided with a common covering of
wrapped plastic tapes or by an extruded PVC sheath or
pressure extruded PVC sheath, as per the requirement of the
customer.

Armouring
GI Round wire / Flat strip / Double steel tape armouring is
applied over the inner sheath in case of three core cables. The
direction of lay of armouring is opposite to that of cores.
For single core cables non magnetic Aluminium armouring is
applied over non metallic part of insulation screening or over
the inner sheath.

Outer sheath
The cables are provided with an extruded PVC / PE TYPE
ST7 / LSZH outer sheath over the armour. For Single core
unarmoured cables the outer sheath is extruded over the non
magnetic metallic part of insulation screening. Outer sheath
is generally of Black colour, but any colour as per customer
requirement can be provided.

TECHNICAL CATALOGUE

HV CABLES

ELEMENTS IN
HV CABLES
Construction of HT Cables
Elements

Material

Standards

Conductor

Compacted stranded - Class 2 , Annealed


Plain Copper / Aluminium

IS:8130 / IEC: 60228 / BS 6360

Conductor Screen

Extruded Semiconducting Compound

IS:7098 part 2, IEC: 60502 part 2,


BS:6622, BS:7835

Insulation

XLPE

IS:7098 part 2, IEC: 60502 part 2,


BS:6622, BS:7835

Insulation Non - Metallic Screen

Extruded Semiconducting Compound

IS:7098 part 2, IEC: 60502 part 2,


BS:6622, BS:7835

Insulation metallic Screen

Copper Wire / Tape

Fillers

Non Hygroscopic PVC / Polypropylene


Fiber

Inner Sheath / Bedding

PVC ST2/ Polyethylene ST 7

IS:7098 part 2, IEC:60502 part 2,


BS:6622, BS:7835

Armour

GI / Aluminium Round wire / Flat strip /


Double steel tape

IS:7098 part 2, IS:3975 IEC:60502 part 2,


BS:6622, BS:7835

Outer Sheath

PVC ST2 / FR PVC / FRLS PVC /


Polyethylene ST 7/ LSZH

IS:7098 part 2, IEC:60502 part 2,


BS:6622, BS:7835

QUALITY ASSURANCE AND TESTING


Asian brand cables of RPG Cables division of KEC international
Ltd. are manufactured with latest state of the art machinery
and testing facilities. The experienced technical staff ensures
high quality standards at all the levels of processing of the
cables from Raw material stage till nal testing.

IS:7098 part 2, IEC: 60502 part 2,


BS:6622, BS:7835

The cables are tested in accordance with IS:7098


(Part 2) -1985 / IEC / BS / Customer Specications and internal
Company Standards .
Following Routine test are carried out on each of the cable
before offering cables for inspection
i.

Conductor Resistance Test

ii.

Partial Discharge Test

iii.

High Voltage Test

The cables are subjected to following Type Tests as per


IS 7098 (Part 2) -1985 / IEC / BS / Customer Specications.
i.
ii.
iii.

Electrical Type tests


Non Electrical Type Tests
Special Tests

At RPG Cables our testing labs are of the highest standards,


well equipped with latest equipments for accurate results and
quality controls. Following In house tests can be carried out

Guide lines for Cable Laying


Minimum Bending Radii of HT XLPE Cables
1 core cable

Multicore Cable

6.6 kV to 11 kV -

15 x D

15 x D

Above 11 kV -

20 x D

15 x D

Where D is Overall diameter of Cable

1. Oxygen Index and Temperature Index tests as per


ASTM-D-2863 / IS -10810, part-58
2. Flammability Characteristics of cable as per
IEC-332(Part-I), IEC-332(part-III) and IEEE-383/IS -10810,
part-53
3. Flammability Characteristics of Cable as per Swedish
standard SS4241475 Class F3
4. Determination of amount of halogen acid gas
evolved during combustion of outer sheath as per
IEC-754(Part-I) / IS-10810, part-59
5. Determination of smoke generation of outer sheath under
re as per ASTM-D-2843

HV CABLES

TECHNICAL CATALOGUE

15

15

30

30

30

53

53

53

53

53

150

185

240

300

400

500

630

800

1000

15

95

120

12

70

35

50

(Nos.)

0.0291

0.0367

0.0469

0.0605

0.0778

0.1000

0.1250

0.1640

0.2060

0.2530

0.3200

0.4430

0.6410

0.8680

(Ohm/km)

D.C. Resistance

Aluminium Conductor

Minimum No.
of wires

(sq.mm)

Nominal Area
of Conductor

94.00

75.20

59.22

47.00

37.60

28.20

22.60

17.40

14.10

11.30

8.93

6.58

4.70

3.29

(kA/sec.)

Short ckt
rating

TABLE 1 : COMMON PARAMETERS

53

53

53

53

53

34

34

30

18

18

15

12

(Nos.)

Minimum No.
of wires

0.0176

0.0221

0.0283

0.0366

0.0470

0.0601

0.0754

0.0991

0.1240

0.1530

0.1930

0.2680

0.3870

0.5240

(Ohm/km)

D.C. Resistance

Copper Conductor

143.00

114.40

90.09

71.50

57.20

42.90

34.32

26.46

21.45

17.16

13.59

10.01

7.15

5.01

(kA/sec.)

Short ckt
rating

3.5

3.3

3.0

2.8

2.6

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

Single Core
armoured
cable (mm)

3.0

2.8

2.6

2.4

2.2

2.2

2.2

2.2

2.2

2.2

2.2

2.2

2.2

2.2

Single Core
unarmoured
and 3 core
cable (mm)

1.9/3.3 and 3.3/3.3 kV

3.6

3.5

3.5

3.5

3.3

3.0

2.8

2.8

2.8

2.8

2.8

2.8

2.8

(mm)

3.8/6.6 kV

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

3.6

(mm)

6.35/11 kV

5.5

5.5

5.5

5.5

5.5

5.5

5.5

5.5

5.5

5.5

5.5

5.5

5.5

(mm)

11/11 kV

Nominal Thickness of Insulation

6.0

6.0

6.0

6.0

6.0

6.0

6.0

6.0

6.0

6.0

6.0

6.0

6.0

(mm)

12.7/22 kV

8.8

8.8

8.8

8.8

8.8

8.8

8.8

8.8

8.8

8.8

8.8

(mm)

19/33 kV

mm

mm

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight of
cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium (A2XY)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight of
cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Copper (2XY)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C

Amps.

In Air at
40 C

Continuous Current Rating

1.8

1.8

2.0

2.0

2.0

2.0

2.0

2.0

2.2

2.2

2.2

2.4

2.6

50

70

95

120

150

185

240

300

400

500

630

800

1000

50

45

40

37

33

29

28

25

24

22

21

19

17

16

3540

2840

2250

1810

1460

1160

970

800

680

580

500

390

310

260

0.0440

0.0526

0.0646

0.0810

0.1024

0.1302

0.1618

0.2114

0.2650

0.3251

0.4108

0.5684

0.8221

1.1131

0.0768

0.0776

0.0783

0.0796

0.0810

0.0836

0.0856

0.0883

0.0918

0.0944

0.0973

0.1005

0.1091

0.1140

0.943

0.901

0.858

0.831

0.803

0.695

0.637

0.569

0.515

0.470

0.429

0.375

0.320

0.285

580

530

470

420

370

325

285

250

220

200

175

145

120

100

680

610

540

480

420

370

330

285

250

225

195

165

135

115

1060

930

800

690

580

495

425

360

310

275

235

190

150

125

41

37

33

30

28

26

24

23

21

19

17

16

6220

4870

3840

3030

2420

1930

1580

1320

1080

810

600

480

0.0428

0.0520

0.0641

0.0799

0.0987

0.1282

0.1595

0.1962

0.2469

0.3423

0.4938

0.6684

0.0782

0.0795

0.0810

0.0831

0.0853

0.0880

0.0915

0.0938

0.0973

0.1005

0.1087

0.1140

0.866

0.834

0.806

0.713

0.643

0.575

0.519

0.480

0.429

0.375

0.323

0.285

580

520

465

410

370

320

285

255

225

190

155

130

670

600

530

470

420

365

320

290

255

215

175

150

980

860

740

630

550

460

400

350

300

245

195

160

45

49

2.0

2.0

2.0

2.0

2.2

2.2

2.2

2.4

2.4

2.6

2.8

95

120

150

185

240

300

400

500

630

800

1000

54

42

37

33

31

28

27

25

24

22

2.0

70

21

2.0

50

3947

3226

2624

2177

1723

1391

1177

958

826

726

636

532

442

0.0433

0.0520

0.0639

0.0804

0.1020

0.1299

0.1616

0.2112

0.2648

0.3250

0.4107

0.5683

0.8221

0.0821

0.0834

0.0860

0.0889

0.0888

0.0919

0.0941

0.0957

0.1013

0.1030

0.1072

0.1118

0.1236

0.830

0.769

0.689

0.620

0.578

0.550

0.539

0.485

0.443

0.408

0.375

0.332

0.290

590

530

475

420

370

325

285

250

220

195

175

145

120

690

620

550

485

425

370

330

285

250

225

200

165

135

1070

940

810

700

600

510

440

370

320

285

245

200

160

45

42

37

34

31

29

27

26

24

22

21

6593

5239

4108

3271

2625

2091

1733

1465

1216

950

733

0.0418

0.0511

0.0635

0.0793

0.0983

0.1279

0.1593

0.1960

0.2468

0.3422

0.4937

0.0854

0.0886

0.0885

0.0921

0.0934

0.0971

0.1007

0.1040

0.1072

0.1118

0.1228

0.695

0.622

0.580

0.563

0.544

0.490

0.447

0.415

0.375

0.332

0.292

590

520

465

415

370

320

285

255

225

190

155

680

610

540

475

420

365

325

290

255

215

175

1010

880

760

650

560

480

415

365

315

260

205

TABLE 3 : 3.8/6.6 kV, SINGLE CORE, XLPE INSULATED AND PVC SHEATHED, SCREENED, UNARMOURED CABLES. (A2XY / 2XY)

1.8

35

TABLE 2 : 3.3 kV, SINGLE CORE, XLPE INSULATED AND PVC SHEATHED, UNSCREENED UNARMOURED CABLES. (A2XY / 2XY)

Nominal
Thickness
of
O/Sheath

Nominal
Area of
Conductor

HV CABLES

TECHNICAL CATALOGUE

mm

mm

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight of
cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium (A2XY)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight of
cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Copper (2XY)

Amps.

In Duct at
30 C

Amps.

In Ground
at 30 C

Amps.

In Air at
40 C

Continuous Current Rating

26

45

50

2.0

2.0

2.0

2.2

2.2

2.2

2.2

2.4

2.4

2.6

2.8

95

120

150

185

240

300

400

500

630

800

1000

3947

3240

2638

2189

1757

1453

1255

1058

894

791

697

590

496

0.0433

0.0518

0.0639

0.0804

0.1019

0.1298

0.1615

0.2112

0.2648

0.3249

0.4107

0.5683

0.8221

0.0821

0.0847

0.0860

0.0889

0.0904

0.0938

0.0961

0.1000

0.1036

0.1079

0.1122

0.1172

0.1265

0.830

0.749

0.672

0.605

0.535

0.469

0.433

0.391

0.358

0.331

0.305

0.272

0.238

590

530

475

420

370

325

285

250

220

195

175

145

120

690

620

550

485

425

370

330

285

250

225

200

165

135

1070

940

810

700

600

510

440

370

320

285

245

200

160

46

42

38

35

33

31

28

27

26

24

22

788

6606

5252

4142

3334

2704

2192

1801

1531

1278

1008

0.4937

0.0417

0.0511

0.0634

0.0792

0.0981

0.1278

0.1592

0.1959

0.2467

0.3421

0.1257

0.0868

0.0886

0.0902

0.0939

0.0974

0.1013

0.1030

0.1064

0.1122

0.1172

0.240

0.678

0.607

0.537

0.480

0.437

0.395

0.361

0.337

0.305

0.272

155

590

520

465

415

370

320

285

255

225

190

175

680

610

540

475

420

365

325

290

255

215

205

1010

880

760

650

560

480

415

365

315

260

29

49

54

2.0

2.2

2.2

2.2

2.2

2.2

2.4

2.4

2.6

2.8

2.8

95

120

150

185

240

300

400

500

630

800

1000

58

46

42

38

36

34

32

31

28

2.0

70

26

2.0

50

4265

3584

2952

2439

2024

1662

1454

1246

1100

988

859

743

640

0.0428

0.0514

0.0635

0.0801

0.1017

0.1296

0.1614

0.2111

0.2647

0.3249

0.4107

0.5683

0.8221

0.0866

0.0895

0.0914

0.0946

0.0967

0.1008

0.1035

0.1079

0.1120

0.1165

0.1191

0.1269

0.1370

0.566

0.513

0.462

0.418

0.372

0.328

0.305

0.277

0.255

0.237

0.220

0.198

0.175

590

530

475

420

370

325

285

250

220

195

175

145

120

690

620

550

485

425

370

330

285

250

225

200

165

135

1070

940

810

700

600

510

440

370

320

285

245

200

160

50

46

42

39

36

34

33

31

29

28

26

6923

5502

4410

3546

2904

2381

2008

1729

1439

1160

931

0.0411

0.0506

0.0630

0.0789

0.0979

0.1276

0.1591

0.1958

0.2466

0.3421

0.4937

0.0920

0.0944

0.0965

0.1007

0.1028

0.1071

0.1133

0.1151

0.1191

0.1269

0.1362

0.466

0.419

0.373

0.336

0.307

0.280

0.257

0.241

0.220

0.198

0.177

590

520

465

415

370

320

285

255

225

190

155

680

610

540

475

420

365

325

290

255

215

175

1010

880

760

650

560

480

415

365

315

260

205

TABLE 5 : 11/11 kV, SINGLE CORE, XLPE INSULATED AND PVC SHEATHED, SCREENED, UNARMOURED CABLES. (A2XY / 2XY)

54

42

38

34

32

30

28

27

24

2.0

70

22

2.0

50

TABLE 4 : 6.35/11 kV, SINGLE CORE, XLPE INSULATED AND PVC SHEATHED, SCREENED, UNARMOURED CABLES. (A2XY / 2XY)

Nominal
Thickness
of
O/Sheath

Nominal
Area of
Conductor

mm

mm

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight of
cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium (A2XY)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight of
cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Copper (2XY)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C

Amps.

In Air at
40 C

Continuous Current Rating

31

2.2

2.2

2.2

2.2

2.2

2.2

2.4

2.6

2.6

2.8

3.0

95

120

150

185

240

300

400

500

630

800

1000

4409

3665

3027

2553

2088

1721

1510

1298

1150

1036

933

786

681

0.0427

0.0513

0.0634

0.0800

0.1016

0.1296

0.1613

0.2110

0.2647

0.3248

0.4106

0.5683

0.8221

0.0877

0.0907

0.0926

0.0959

0.0982

0.1024

0.1052

0.1097

0.1139

0.1185

0.1233

0.1291

0.1394

0.524

0.475

0.429

0.388

0.346

0.306

0.284

0.259

0.239

0.222

0.206

0.186

0.165

580

520

470

410

360

320

280

245

215

195

170

145

120

680

610

550

480

420

370

325

280

250

225

195

165

135

1080

950

820

710

610

520

450

380

330

295

255

210

170

51

47

43

40

37

35

34

32

31

29

27

973

6998

5616

4474

3605

2960

2434

2058

1778

1513

1204

0.4937

0.0410

0.0505

0.0629

0.0789

0.0979

0.1276

0.1590

0.1958

0.2466

0.3421

0.1386

0.0932

0.0957

0.0979

0.1023

0.1045

0.1089

0.1152

0.1171

0.1233

0.1291

0.166

0.432

0.389

0.347

0.313

0.287

0.261

0.240

0.226

0.206

0.186

150

580

520

460

410

365

315

280

250

220

185

175

680

600

530

470

420

360

320

290

255

210

215

1020

890

770

660

580

490

430

380

330

270

2.2

2.2

2.2

2.4

2.4

2.6

2.6

2.8

2.8

3.0

3.2

95

120

150

185

240

300

400

500

630

800

1000

65

61

56

53

49

46

43

41

39

38

36

4990

4204

3525

3020

2519

2158

1889

1658

1458

1334

1220

0.0421

0.0508

0.0630

0.0797

0.1014

0.1294

0.1612

0.2109

0.2646

0.3248

0.4106

0.0938

0.0972

0.0998

0.1035

0.1064

0.1128

0.1147

0.1197

0.1244

0.1293

0.1327

0.377

0.344

0.312

0.284

0.255

0.227

0.212

0.195

0.181

0.169

0.158

580

520

470

410

360

320

280

245

215

195

170

680

610

550

480

420

370

325

280

250

225

195

1080

950

820

710

610

520

450

380

330

295

255

57

53

49

46

44

41

39

38

36

7499

6084

4906

4048

3341

2795

2367

2078

1800

0.0404

0.0501

0.0625

0.0786

0.0976

0.1274

0.1589

0.1957

0.2466

0.1002

0.1033

0.1061

0.1111

0.1154

0.1189

0.1238

0.1279

0.1327

0.314

0.285

0.256

0.232

0.214

0.196

0.182

0.171

0.158

580

520

460

410

365

315

280

250

220

680

600

530

470

420

360

320

290

255

1020

890

770

660

580

490

430

380

330

TABLE 7 : 19/33 kV, SINGLE CORE, XLPE INSULATED AND PVC SHEATHED, SCREENED, UNARMOURED CABLES. (A2XY / 2XY)

59

55

50

47

43

39

37

35

33

32

29

2.0

70

27

2.0

50

TABLE 6 : 12.7/22 kV, SINGLE CORE, XLPE INSULATED AND PVC SHEATHED, SCREENED, UNARMOURED CABLES. (A2XY / 2XY)

Nominal
Thickness
of
O/Sheath

Nominal
Area of
Conductor

HV CABLES

TECHNICAL CATALOGUE

10

mm

mm

mm

Minimum
Thickness
of O/
Sheath

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight
of cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium (A2XWaY)

Amps.

In Duct
at
30 C
Amps.

In
Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight
of cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro
Farad/km

Approx.
Capacitace
per phase

Copper (2XWaY)

Amps.

In Duct at
30 C

Amps.

In Ground at
30 C

Amps.

In Air at
40 C

Continuous Current Rating

1.4
1.4
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2
2
2
2
2.5

1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.88
2.04

18
20
22
24
25
27
28
31
33
37
40
45
50
56

390
460
580
690
790
890
1030
1250
1460
1860
2250
2790
3440
4380

1.1131
0.8221
0.5683
0.4107
0.3250
0.2649
0.2113
0.1616
0.1300
0.1021
0.0806
0.0641
0.0520
0.0432

0.1229
0.1182
0.1104
0.1051
0.1011
0.0985
0.0945
0.0921
0.0895
0.0875
0.0853
0.0840
0.0828
0.0827

0.258
0.292
0.337
0.385
0.430
0.465
0.514
0.574
0.631
0.695
0.727
0.762
0.783
0.825

105
120
150
175
200
220
250
285
320
360
400
445
485
510

115
140
170
200
225
250
285
325
365
410
465
520
560
600

135
160
200
245
285
325
375
440
500
590
680
780
880
970

18
20
22
24
25
27
28
31
33
37
40
45
53
58

600
750
1000
1270
1520
1800
2160
2740
3330
4240
5310
6750
8447
10367

0.6683
0.4937
0.3422
0.2468
0.1960
0.1593
0.1280
0.0983
0.0795
0.0636
0.0514
0.0420
0.0346
0.0299

0.1229
0.1182
0.1104
0.1051
0.1011
0.0985
0.0945
0.0921
0.0893
0.0875
0.0853
0.0840
0.0876
0.0859

0.258
0.292
0.337
0.385
0.430
0.465
0.514
0.574
0.635
0 .695
0.727
0.762
0.818
0.858

135
155
190
225
255
285
315
360
400
445
485
530
570
580

150
175
215
255
290
325
360
415
460
510
560
610
660
680

170
205
260
315
365
415
475
560
640
730
840
940
1040
1100

50
70
95
120
150
185
240
300
400
500
630
800
1000

1.6
1.6
1.6
1.6
1.6
1.6
2
2
2
2
2
2.5
2.5

1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20

22
24
26
27
29
30
33
36
40
44
48
53
58

550
660
770
870
1000
1150
1430
1670
2070
2510
3030
3830
4600

CABLES-(A2XWaY / 2XWaY)

0.8221
0.5683
0.4107
0.3249
0.2648
0.2112
0.1615
0.1297
0.1018
0.0802
0.0636
0.0515
0.0428

0.1265
0.1172
0.1122
0.1079
0.1058
0.1000
0.0980
0.0974
0.0937
0.0918
0.0901
0.0883
0.0866

0.290
0.332
0.375
0.408
0.443
0.485
0.539
0.550
0.578
0.620
0.689
0.769
0.830

120
145
175
195
220
245
280
315
355
395
435
470
500

140
170
200
225
250
285
325
365
410
455
510
550
590

165
210
255
295
330
380
450
510
590
680
780
870
960

22
24
26
27
29
31
34
36
40
44
48
54
59

850
1070
1350
1610
1910
2280
2880
3550
4450
5580
7000
8477
10383

0.4937
0.3421
0.2467
0.1959
0.1592
0.1278
0.0980
0.0792
0.0632
0.0508
0.0414
0.0300
0.0298

0.1257
0.1172
0.1122
0.1064
0.1052
0.1013
0.0992
0.0957
0.0934
0.0916
0.0894
0.0881
0.0861

0.292
0.332
0.375
0.415
0.447
0.490
0.544
0.563
0.580
0.622
0.695
0.775
0.836

155
190
225
250
280
315
355
395
435
475
520
540
570

175
215
255
290
320
360
410
455
510
550
600
640
670

215
270
325
375
425
485
570
640
730
830
930
1010
1090

TABLE 9 : 3.8/6.6 kV, SINGLE CORE, XLPE INSULATED, ALUMINIUM ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED

35
50
70
95
120
150
185
240
300
400
500
630
800
1000

CABLES- (A2XWaY / 2XWaY)

TABLE 8 : 3.3 kV, SINGLE CORE, XLPE INSULATED, ALUMINIUM ROUND WIRE ARMOUREDAND PVC SHEATHED, UNSCREENED

Nominal
Dia. Of
Armour
Wire

Nominal
Area of
Conductor

11

mm

Nominal
Area of
Conductor

mm

mm

Minimum
Thickness
of O/
Sheath

mm

dia. of
cable

Approx.
overall

kg/km

Approx.
weight
of cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium (A2XWaY)

Amps.

Amps.

Amps.

mm

overall
dia. of
cable

In Air at
40 C

Approx.

In
Ground
at 30 C

Continuous Current Rating


In Duct
at
30 C
kg/km

Approx.
weight
of cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro
Farad/km

Approx.
Capacitace
per phase

Copper (2XWaY)

Amps.

In Duct at
30 C
Amps.

In Ground at
30 C

1.6

1.6

1.6

1.6

2.5

2.5

70

95

120

150

185

240

300

400

500

630

800

1000

2.20

2.04

1.88

1.72

1.72

1.56

1.56

1.56

1.56

1.56

1.40

1.40

1.40

58

53

48

44

41

37

35

33

30

29

27

26

24

4600

3840

3050

2540

2100

1740

1520

1310

1080

970

840

730

620

0.0428

0.0515

0.0636

0.0802

0.1017

0.1297

0.1614

0.2111

0.2648

0.3249

0.4107

0.5683

0.8221

0.0866

0.0883

0.0901

0.0918

0.0952

0.0991

0.1017

0.1060

0.1080

0.1123

0.1146

0.1223

0.1320

0.830

0.749

0.672

0.605

0.535

0.469

0.433

0.391

0.358

0.331

0.305

0.272

0.238

500

470

435

395

355

315

280

245

220

195

175

145

120

590

550

510

455

410

365

325

285

250

225

200

170

140

960

870

780

680

590

510

450

380

330

295

255

210

165

59

54

48

44

41

37

35

33

31

29

27

26

24

910

10383

8504

7020

5600

4490

3620

2970

2440

1990

1710

1420

1140

0.0298

0.0345

0.0414

0.0508

0.0631

0.0791

0.0980

0.1277

0.1591

0.1959

0.2467

0.3421

0.4937

0.0861

0.0884

0.0894

0.0916

0.0949

0.0974

0.1011

0.1052

0.1094

0.1109

0.1146

0.1223

0.1312

0.836

0.755

0.678

0.607

0.537

0.480

0.437

0.395

0.361

0.337

0.305

0.272

0.240

570

540

520

475

435

395

355

315

280

250

225

190

155

670

640

600

550

510

455

410

360

320

290

255

215

175

1090

1010

930

830

730

640

570

485

425

375

325

270

215

400

2.5

300

1000

240

2.5

185

800

150

120

2.5

1.6

95

630

1.6

70

500

1.6

50

2.20

2.20

2.04

1.88

1.88

1.72

1.72

1.56

1.56

1.56

1.56

1.56

1.56

62

57

53

48

45

41

39

37

35

34

31

30

28

4960

4230

3560

2850

2400

2010

1780

1530

1370

1240

1060

930

810

CABLES- (A2XWaY / 2XWaY)

0.0423

0.0511

0.0632

0.0800

0.1015

0.1295

0.1613

0.2110

0.2647

0.3248

0.4106

0.5683

0.8221

0.0908

0.0929

0.0963

0.0973

0.1011

0.1056

0.1085

0.1132

0.1176

0.1223

0.1233

0.1313

0.1417

0.566

0.513

0.462

0.418

0.372

0.328

0.305

0.277

0.255

0.237

0.220

0.198

0.175

500

470

435

395

355

315

280

245

220

195

175

145

120

590

550

510

455

410

365

325

285

250

225

200

170

140

960

870

780

680

590

510

450

380

330

295

255

210

165

62

58

53

48

45

42

39

37

35

34

31

30

28

10760

8888

7530

5910

4790

3910

3240

2670

2280

1980

1640

1340

1100

0.0293

0.0340

0.0408

0.0504

0.0628

0.0788

0.0978

0.1275

0.1590

0.1958

0.2466

0.3421

0.4937

0.0901

0.0930

0.0957

0.0970

0.1008

0.1054

0.1079

0.1124

0.1170

0.1209

0.1233

0.1313

0.1409

0.570

0.516

0.466

0.419

0.373

0.336

0.307

0.280

0.257

0.241

0.220

0.198

0.177

570

540

520

475

435

395

355

315

280

250

225

190

155

670

640

600

550

510

455

410

360

320

290

255

215

175

1090

1010

930

830

730

640

570

485

425

375

325

270

215

TABLE 11: 11/11 kV, SINGLE CORE, XLPE INSULATED, ALUMINIUM ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED

1.6

50

SCREENED CABLES- (A2XWaY / 2XWaY)

Amps.

In Air at
40 C

Continuous Current Rating

TABLE 10 : 6.35/11 kV, SINGLE CORE, XLPE INSULATED, ALUMINIUM ROUND WIRE ARMOURED AND PVC SHEATHED,

Nominal
Dia. Of
Armour
Wire

HV CABLES

TECHNICAL CATALOGUE

12

Thickness
of O/
Sheath

Dia. Of
Armour
Wire

mm

Area of
Conductor

mm

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight
of cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium (A2XWaY)

Amps.

In Duct
at
30 C
Amps.

In
Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight
of cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro
Farad/km

Approx.
Capacitace
per phase

Copper (2XWaY)

Amps.

In Duct at
30 C

Amps.

In Ground at
30 C

1.6

2.5

2.5

2.5

2.5

70

95

120

150

185

240

300

400

500

630

800

1000

2.36

2.20

2.04

2.04

1.88

1.72

1.72

1.56

1.56

1.56

1.56

1.56

1.56

63

58

54

51

46

42

40

38

36

35

33

31

29

5110

4320

3640

3120

2470

2080

1850

1590

1420

1300

1180

970

860

0.0422

0.0510

0.0631

0.0798

0.1015

0.1295

0.1613

0.2110

0.2647

0.3248

0.4106

0.5682

0.8221

0.0918

0.0940

0.0975

0.1011

0.1024

0.1071

0.1101

0.1149

0.1194

0.1242

0.1272

0.1333

0.1439

0.524

0.475

0.429

0.388

0.346

0.306

0.284

0.259

0.239

0.222

0.206

0.186

0.165

490

460

420

380

345

305

275

240

215

195

170

145

120

570

540

495

445

400

355

320

280

250

225

195

165

135

950

870

770

680

600

510

450

385

340

300

260

215

170

64

59

54

51

46

43

40

38

36

35

33

31

29

10908

8981

7610

6180

4870

3970

3300

2730

2330

2050

1760

1390

1150

0.0292

0.0339

0.0407

0.0502

0.0627

0.0787

0.0977

0.1275

0.1590

0.1958

0.2466

0.3421

0.4937

0.0915

0.0941

0.0968

0.1008

0.1022

0.1068

0.1094

0.1141

0.1187

0.1227

0.1272

0.1333

0.1431

0.528

0.479

0.432

0.389

0.347

0.313

0.287

0.261

0.240

0.226

0.206

0.186

0.166

550

530

500

460

425

380

350

305

275

245

220

185

150

650

630

580

540

495

445

400

355

315

285

250

215

175

1080

1020

920

830

740

650

570

490

430

385

335

275

220

2.20

2.36

2.5

2.5

2.5

2.5

2.5

3.15

150

185

240

300

400

500

630

800

1000

2.52

2.20

2.04

2.04

1.88

1.72

1.72

1.72

1.72

95

120

70

64

60

57

53

49

46

44

42

41

39

6030

4930

4200

3650

3110

2710

2280

2000

1820

1680

1550

CABLES- (A2XWaY / 2XWaY)

0.0417

0.0506

0.0628

0.0796

0.1013

0.1293

0.1611

0.2109

0.2646

0.3248

0.4106

0.0984

0.1002

0.1041

0.1081

0.1113

0.1168

0.1189

0.1241

0.1291

0.1341

0.1377

0.377

0.344

0.312

0.284

0.255

0.227

0.212

0.195

0.181

0.169

0.158

490

460

420

380

345

305

275

240

215

195

170

570

540

495

445

400

355

320

280

250

225

195

950

870

770

680

600

510

450

385

340

300

260

71

65

60

57

53

50

46

44

42

41

39

11823

9594

8190

6710

5500

4610

3730

3140

2730

2430

2130

0.0285

0.0333

0.0402

0.0498

0.0624

0.0784

0.0976

0.1274

0.1589

0.1957

0.2465

0.0983

0.1002

0.1035

0.1078

0.1111

0.1163

0.1182

0.1233

0.1284

0.1326

0.1377

0.380

0.346

0.314

0.285

0.256

0.232

0.214

0.196

0.182

0.171

0.158

550

530

500

460

425

380

350

305

275

245

220

650

630

580

540

495

445

400

355

315

285

250

1080

1020

920

830

740

650

570

490

430

385

335

TABLE 13 : 19/33 kV, SINGLE CORE, XLPE INSULATED, ALUMINIUM ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED

1.6

50

SCREENED CABLES- (A2XWaY / 2XWaY)

Amps.

In Air at
40 C

Continuous Current Rating

TABLE 12 : 12.7/22 kV, SINGLE CORE, XLPE INSULATED, ALUMINIUM ROUND WIRE ARMOURED AND PVC SHEATHED,

mm

Minimum

Nominal

Nominal

13

mm

mm

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight of
cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium - A2XFY(P)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight of
cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Copper - 2XFY(P)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C

Amps.

In Air at
40 C

Continuous Current Rating

1.56

1.56

1.72

1.72

1.88

2.04

2.20

2.20

2.52

50

70

95

120

150

185

240

300

400

63

57

53

48

45

42

40

36

33

31

5445

4475

3827

3119

2664

2306

2008

1628

1349

1179

0.1023

0.1302

0.1618

0.2114

0.2650

0.3251

0.4108

0.5684

0.8222

1.1132

0.0719

0.0736

0.0750

0.0768

0.0792

0.0808

0.0829

0.0859

0.0926

0.0965

0.704

0.635

0.574

0.512

0.466

0.427

0.389

0.341

0.296

0.263

350

305

270

235

210

185

165

140

110

94

410

360

320

280

245

220

195

165

135

115

535

460

400

340

295

255

225

185

145

120

63

57

53

48

45

42

40

36

33

31

12500

10004

8229

6463

5340

4474

3726

2864

2205

1811

0.0640

0.0798

0.0986

0.1282

0.1595

0.1962

0.2469

0.3423

0.4938

0.6684

0.0719

0.0736

0.0750

0.0768

0.0792

0.0808

0.0829

0.0859

0.0926

0.0965

0.704

0.635

0.574

0.512

0.466

0.427

0.389

0.341

0.296

0.263

440

390

350

300

270

240

210

175

145

120

520

460

410

355

315

285

250

210

170

145

670

590

510

435

375

330

290

235

190

155

50

1.88

2.04

2.20

2.20

2.36

2.52

2.84

95

120

150

185

240

300

400

80

70

65

60

56

53

46

1.88

70

42

1.72

50

(A2XFY(P) / 2XFY(P))

7950

6330

5380

4490

3930

3420

3030

2570

2140

0.1025

0.1303

0.1619

0.2115

0.2650

0.3251

0.4108

0.5684

0.8221

0.0812

0.0833

0.0841

0.0867

0.0900

0.0924

0.0951

0.0994

0.1079

0.578

0.550

0.539

0.485

0.443

0.408

0.375

0.332

0.290

350

310

275

240

210

190

165

140

115

400

355

315

275

245

220

190

160

130

520

450

395

335

295

260

230

190

150

80

71

66

60

56

53

50

46

42

15200

12120

9860

7930

6710

5770

4790

3840

3020

0.0643

0.0800

0.0988

0.1283

0.1596

0.1962

0.2470

0.3423

0.4938

0.0812

0.0827

0.0839

0.0864

0.0897

0.0918

0.0951

0.0994

0.1075

0.580

0.563

0.544

0.490

0.447

0.415

0.375

0.332

0.292

440

390

350

305

270

240

215

180

150

500

445

400

350

310

280

250

210

170

650

570

500

430

380

335

295

240

195

TABLE 15 : 3.8/6.6 KV, THREE CORE, XLPE INSULATED, FLAT STRIP ARMOURED AND PVC SHEATHED, SCREENED CABLES.

1.56

35

(A2XFY(P) / 2XFY(P))

TABLE 14 : 3.3 KV, THREE CORE, XLPE INSULATED, FLAT STRIP ARMOURED AND PVC SHEATHED, UNSCREENED CABLES.

Nominal
Thickness
of
O/Sheath

Nominal
Area of
Conductor

HV CABLES

TECHNICAL CATALOGUE

14

mm

mm

mm

dia. of
cable

Approx.
overall

kg/km

Approx.
weight of
cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium - A2XFY(P)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight of
cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Copper - 2XFY(P)

Amps.

In Duct at
30 C

Amps.

In Ground
at 30 C

Amps.

In Air at
40 C

Continuous Current Rating

53

2.04

2.20

2.20

2.36

2.52

2.68

2.84

95

120

150

185

240

300

400

8140

6780

5890

5020

4290

3850

3430

2890

2460

0.1024

0.1302

0.1618

0.2114

0.2650

0.3250

0.4108

0.5684

0.8221

0.0824

0.0859

0.0880

0.0909

0.0945

0.0972

0.1002

0.1050

0.1140

0.535

0.469

0.433

0.391

0.358

0.331

0.305

0.272

0.238

350

310

275

240

210

190

165

140

115

400

355

315

275

245

220

190

160

130

520

450

395

335

295

260

230

190

150

81

74

69

64

60

57

53

49

46

15390

12500

10290

8460

7050

6100

5200

4160

3340

0.0642

0.0798

0.0986

0.1282

0.1595

0.1961

0.2469

0.3422

0.4938

0.0824

0.0854

0.0878

0.0906

0.0942

0.0966

0.1002

0.1050

0.1136

0.537

0.480

0.437

0.395

0.361

0.337

0.305

0.272

0.240

440

390

350

305

270

240

215

180

150

500

445

400

350

310

280

250

210

170

2.20

2.20

2.36

2.36

2.52

2.68

2.84

3.00

3.00

50

70

95

120

150

185

240

300

400

90

82

78

73

69

65

62

58

55

(A2XFY(P) / 2XFY(P))

9480

7970

7070

6030

5420

4830

4300

3810

3300

0.1020

0.1299

0.1616

0.2112

0.2648

0.3249

0.4107

0.5683

0.8221

0.0895

0.0938

0.0963

0.0999

0.1041

0.1074

0.1109

0.1166

0.1267

0.372

0.328

0.305

0.277

0.255

0.237

0.220

0.198

0.175

350

310

275

240

210

190

165

140

115

400

355

315

275

245

220

190

160

130

520

450

395

335

295

260

230

190

150

90

84

78

73

69

66

62

58

55

16730

13840

11500

9600

8180

7130

6070

5080

4190

0.0636

0.0794

0.0982

0.1279

0.1592

0.1960

0.2467

0.3421

0.4937

0.0894

0.0931

0.0960

0.0995

0.1038

0.1066

0.1109

0.1166

0.1262

0.373

0.336

0.307

0.280

0.257

0.241

0.220

0.198

0.177

440

390

350

305

270

240

215

180

150

500

445

400

350

310

280

250

210

170

TABLE 17 : 11/11 kV, THREE CORE, XLPE INSULATED, FLAT STRIP ARMOURED AND PVC SHEATHED, SCREENED CABLES

81

73

69

64

60

56

49

1.88

70

46

1.88

50

(A2XFY(P) / 2XFY(P))

650

570

500

430

380

335

295

240

195

650

570

500

430

380

335

295

240

195

TABLE 16 : 6.35/11 kV, THREE CORE, XLPE INSULATED, FLAT STRIP ARMOURED AND PVC SHEATHED, SCREENED CABLES

Nominal
Thickness
of
O/Sheath

Nominal
Area of
Conductor

15

mm

mm

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight of
cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium - A2XFY(P)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight of
cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Copper - 2XFY(P)

Amps.

In Duct at
30 C
Amps.

In Ground
at 30 C

Amps.

In Air at
40 C

Continuous Current Rating

2.36

2.36

2.52

2.68

2.68

2.84

3.00

3.00

70

95

120

150

185

240

300

400

92

85

80

75

71

68

65

61

57

9870

8320

7300

6340

5700

5110

4640

4060

3510

0.1020

0.1298

0.1615

0.2112

0.2648

0.3249

0.4107

0.5683

0.8221

0.0912

0.0957

0.0984

0.1021

0.1064

0.1098

0.1135

0.1193

0.1296

0.346

0.306

0.284

0.259

0.239

0.222

0.206

0.186

0.165

355

310

275

240

215

190

170

140

115

395

350

310

270

240

215

190

160

130

530

455

400

340

300

265

230

190

155

92

86

80

75

72

69

65

61

57

17120

14120

11770

9850

8460

7480

6410

5320

4400

0.0635

0.0793

0.0982

0.1278

0.1592

0.1959

0.2467

0.3421

0.4937

0.0911

0.0950

0.0980

0.1017

0.1061

0.1090

0.1135

0.1193

0.1291

0.347

0.313

0.287

0.261

0.240

0.226

0.206

0.186

0.166

440

390

350

305

275

245

215

180

150

495

440

395

345

305

275

245

205

170

2.84

2.84

3.00

3.00

3.00

3.00

3.00

95

120

150

185

240

300

400

104

97

93

88

84

81

78

(A2XFY(P) / 2XFY(P))

11790

10250

9260

8280

7530

6820

6360

0.1016

0.1296

0.1613

0.2110

0.2647

0.3248

0.4106

0.1002

0.1055

0.1086

0.1130

0.1180

0.1219

0.1262

0.255

0.227

0.212

0.195

0.181

0.169

0.158

355

310

275

240

215

190

170

395

350

310

270

240

215

190

530

455

400

340

300

265

230

104

98

93

88

85

81

78

19040

16020

13700

11730

10290

9110

8120

0.0629

0.0789

0.0978

0.1276

0.1590

0.1958

0.2466

0.1001

0.1046

0.1083

0.1126

0.1176

0.1210

0.1262

0.256

0.232

0.214

0.196

0.182

0.171

0.158

440

390

350

305

275

245

215

495

440

395

345

305

275

245

TABLE 19 : 19/33 kV, THREE CORE, XLPE INSULATED, FLAT STRIP ARMOURED AND PVC SHEATHED, SCREENED CABLES.

2.20

50

(A2XFY(P) / 2XFY(P))

660

580

510

435

385

340

300

660

580

510

435

385

340

300

245

200

TABLE 18 : 12.7/22 kV, THREE CORE, XLPE INSULATED, FLAT STRIP ARMOURED AND PVC SHEATHED, SCREENED CABLES.

Nominal
Thickness
of
O/Sheath

Nominal
Area of
Conductor

HV CABLES

TECHNICAL CATALOGUE

16

Thickness
of O/
Sheath

Dia. Of
Armour
Wire

mm

Area of
Conductor

mm

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight
of cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium - A2XWY(P)

Amps.

In Duct
at
30 C
Amps.

In
Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

Approx.
overall
dia. of
cable
kg/km

Approx.
weight
of cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro
Farad/km

Approx.
Capacitace
per phase

Copper - 2XWY(P)

Amps.

In Duct at
30 C

Amps.

In Ground at
30 C

Amps.

In Air at
40 C

Continuous Current Rating

2.5

2.5

2.5

2.5

3.15

50

70

95

120

150

185

240

300

400

2.68

2.36

2.20

2.04

2.04

1.88

1.72

1.56

1.56

1.56

68

61

56

51

48

44

42

38

35

32

8000

6130

5300

4450

3920

3150

2760

2320

1980

1540

0.1028

0.1305

0.1620

0.2116

0.2651

0.3252

0.4109

0.5684

0.8222

1.1132

0.0719

0.0736

0.0750

0.0768

0.0792

0.0808

0.0829

0.0859

0.0926

0.0965

0.704

0.635

0.574

0.512

0.466

0.427

0.389

0.341

0.296

0.263

350

305

270

235

210

185

165

140

110

94

410

360

320

280

245

220

195

165

135

115

535

460

400

340

295

255

225

185

145

120

68

61

56

51

48

44

42

38

35

32

15060

11660

9700

7800

6600

5320

4480

3560

2840

2170

0.0657

0.0811

0.0996

0.1289

0.1600

0.1966

0.2471

0.3424

0.4939

0.6684

0.0574

0.0595

0.0612

0.0634

0.0662

0.0682

0.0728

0.0764

0.0837

0.0881

0.704

0.635

0.574

0.512

0.466

0.427

0.389

0.341

0.296

0.263

440

390

350

300

270

240

210

175

145

120

520

460

410

355

315

285

250

210

170

145

670

590

510

435

375

330

290

235

190

155

2.04

2.5

2.5

2.5

2.5

3.15

3.15

95

120

150

185

240

300

400

3.00

2.68

2.52

2.36

2.20

2.20

1.88

70

1.88

50

86

75

70

63

59

56

53

48

44

(A2XWY(P) / 2XWY(P))

12290

9100

7920

6170

5470

4920

4410

3420

2960

0.1025

0.1303

0.1619

0.2115

0.2650

0.3251

0.4108

0.5684

0.8221

0.0812

0.0833

0.0841

0.0867

0.0900

0.0924

0.0951

0.0994

0.1079

0.578

0.550

0.539

0.485

0.443

0.408

0.375

0.332

0.290

350

310

275

240

210

190

165

140

115

400

355

315

275

245

220

190

160

130

520

450

395

335

295

260

230

190

150

86

76

70

63

59

57

53

48

44

19540

14930

12430

9650

8220

7240

6170

4690

3840

0.0643

0.0800

0.0988

0.1283

0.1596

0.1962

0.2470

0.3423

0.4938

0.0812

0.0827

0.0839

0.0864

0.0897

0.0918

0.0951

0.0994

0.1075

0.580

0.563

0.544

0.490

0.447

0.415

0.375

0.332

0.292

440

390

350

305

270

240

215

180

150

500

445

400

350

310

280

250

210

170

650

570

500

430

380

335

295

240

195

TABLE 21 : 3.8/6.6 kV, THREE CORE, XLPE INSULATED, ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED CABLES.

1.6

35

(A2XWY(P) / 2XWY(P))

TABLE 20 : 3.3 kV, THREE CORE, XLPE INSULATED, ROUND WIRE ARMOURED AND PVC SHEATHED, UNSCREENED CABLES.

mm

Minimum

Nominal

Nominal

17

mm

Nominal
Area of
Conductor

mm

mm

Minimum
Thickness
of O/
Sheath

mm

dia. of
cable

Approx.
overall

kg/km

Approx.
weight
of cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium - A2XWY(P)

Amps.

Amps.

Amps.

mm

overall
dia. of
cable

In Air at
40 C

Approx.

In
Ground
at 30 C

Continuous Current Rating


In Duct
at
30 C
kg/km

Approx.
weight
of cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro
Farad/km

Approx.
Capacitace
per phase

Copper - 2XWY(P)

Amps.

In Duct at
30 C
Amps.

In Ground at
30 C

Amps.

In Air at
40 C

Continuous Current Rating

2.5

2.5

2.5

2.5

3.15

3.15

3.15

70

95

120

150

185

240

300

400

3.00

2.84

2.68

2.52

2.36

2.20

2.20

2.04

2.04

88

78

74

69

63

59

57

53

49

12570

9650

8620

7490

5970

5400

4910

4270

3720

0.1024

0.1302

0.1618

0.2114

0.2650

0.3250

0.4108

0.5684

0.8221

0.0824

0.0859

0.0880

0.0909

0.0945

0.0972

0.1002

0.1050

0.1140

0.535

0.469

0.433

0.391

0.358

0.331

0.305

0.272

0.238

350

310

275

240

210

190

165

140

115

400

355

315

275

245

220

190

160

130

520

450

395

335

295

260

230

190

150

88

79

74

69

63

60

57

53

49

19820

15430

13020

11000

8730

7650

6680

5540

4610

0.0642

0.0798

0.0986

0.1282

0.1595

0.1961

0.2469

0.3422

0.4938

0.0824

0.0854

0.0878

0.0906

0.0942

0.0966

0.1002

0.1050

0.1136

0.537

0.480

0.437

0.395

0.361

0.337

0.305

0.272

0.240

440

390

350

305

270

240

215

180

150

500

445

400

350

310

280

250

210

170

650

570

500

430

380

335

295

240

195

2.5

2.5

3.15

3.15

3.15

3.15

3.15

50

70

95

120

150

185

240

300

400

3.00

3.00

3.00

2.84

2.68

2.52

2.52

2.36

2.20

96

88

83

77

73

70

67

62

58

(A2XWY(P) / 2XWY(P))

14300

12280

10210

8910

8080

7410

6750

5470

4780

0.1020

0.1299

0.1616

0.2112

0.2648

0.3249

0.4107

0.5683

0.8221

0.0895

0.0938

0.0963

0.0999

0.1041

0.1074

0.1109

0.1166

0.1267

0.372

0.328

0.305

0.277

0.255

0.237

0.220

0.198

0.175

350

310

275

240

210

190

165

140

115

400

355

315

275

245

220

190

160

130

520

450

395

335

295

260

230

190

150

96

90

83

78

74

71

67

62

58

21550

18240

14680

12470

10910

9710

8520

6740

5700

0.0636

0.0794

0.0982

0.1279

0.1592

0.1960

0.2467

0.3421

0.4937

0.0894

0.0931

0.0960

0.0995

0.1038

0.1066

0.1109

0.1166

0.1262

0.373

0.336

0.307

0.280

0.257

0.241

0.220

0.198

0.177

440

390

350

305

270

240

215

180

150

500

445

400

350

310

280

250

210

170

650

570

500

430

380

335

295

240

195

TABLE 23 : 11/11 kV, THREE CORE, XLPE INSULATED, ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED CABLES.

2.5

50

(A2XWY(P) / 2XWY(P))

TABLE 22 : 6.35/11 kV, THREE CORE, XLPE INSULATED, ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED CABLES.

Nominal
Dia. Of
Armour
Wire

HV CABLES

TECHNICAL CATALOGUE

18

mm

mm

mm

Minimum
Thickness
of O/
Sheath

mm

Approx.
overall
dia. of
cable

kg/km

Approx.
weight
of cable

ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro Farad/
km

Approx.
Capacitance
per phase

Aluminium - A2XWY(P)

Amps.

at
30 C

In Duct

Amps.

In
Ground
at 30 C
Amps.

In Air at
40 C

Continuous Current Rating

mm

dia. of
cable

Approx.
overall

kg/km

Approx.
weight
of cable
ohm/km

Approx.
A.C.
Resistance
at 90C
ohm/km

Approx.
Reactance
at 50 Hz
Micro
Farad/km

Approx.
Capacitace
per phase

Copper - 2XWY(P)

Amps.

In Duct at
30 C

Amps.

In Ground at
30 C

Amps.

In Air at
40 C

Continuous Current Rating

3.15

3.15

3.15

95

120

150

185

240

300

400

3.00

3.00

3.00

2.84

2.68

2.68

2.52

2.36

2.36

98

91

87

80

76

73

69

64

60

14750

12800

11650

9310

8420

7790

7180

5730

5110

0.1020

0.1298

0.1615

0.2112

0.2648

0.3249

0.4107

0.5683

0.8221

0.0912

0.0957

0.0984

0.1021

0.1064

0.1098

0.1135

0.1193

0.1296

0.346

0.306

0.284

0.259

0.239

0.222

0.206

0.186

0.165

355

310

275

240

215

190

170

140

115

395

350

310

270

240

215

190

160

130

530

455

400

340

300

265

230

190

155

98

92

87

80

76

73

69

64

60

22000

18700

16120

12820

11250

10150

8940

7000

6000

0.0635

0.0793

0.0982

0.1278

0.1592

0.1959

0.2467

0.3421

0.4937

0.0911

0.0950

0.0980

0.1017

0.1061

0.1090

0.1135

0.1193

0.1291

0.347

0.313

0.287

0.261

0.240

0.226

0.206

0.186

0.166

440

390

350

305

275

245

215

180

150

495

440

395

345

305

275

245

205

170

660

580

510

435

385

340

300

245

200

3.15

95

120

150

185

240

300

400

3.00

3.00

3.00

3.00

3.00

3.00

3.00

110

103

99

94

90

87

83

(A2XWY(P) / 2XWY(P))

17420

15480

14250

13010

12000

11280

9500

0.1016

0.1296

0.1613

0.2110

0.2647

0.3248

0.4106

0.1002

0.1055

0.1086

0.1130

0.1180

0.1219

0.1262

0.255

0.227

0.212

0.195

0.181

0.169

0.158

355

310

275

240

215

190

170

395

350

310

270

240

215

190

530

455

400

340

300

265

230

110

104

99

94

91

88

83

24680

21330

18660

16470

14760

13540

11260

0.0629

0.0789

0.0978

0.1276

0.1590

0.1958

0.2466

0.1001

0.1046

0.1083

0.1126

0.1176

0.1210

0.1262

0.256

0.232

0.214

0.196

0.182

0.171

0.158

440

390

350

305

275

245

215

495

440

395

345

305

275

245

660

580

510

435

385

340

300

TABLE 25 : 19/33 kV, THREE CORE, XLPE INSULATED, ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED CABLES.

2.5

3.15

70

2.5

50

(A2XWY(P) / 2XWY(P))

TABLE 24 : 12.7/22 kV, THREE CORE, XLPE INSULATED, ROUND WIRE ARMOURED AND PVC SHEATHED, SCREENED CABLES.

Nominal
Dia. Of
Armour
Wire

Nominal
Area of
Conductor

1) Continuous current carrying capacity is an important


factor for the selection of the optimum size of conductor
in a cable. The current ratings given in Tables 2 to 25 are
on the following standard installation conditions:
1.

1.5 K.m/W

3. Ground Temprature

30C

4. Ambient Air Temprature

40C

6.

A = nominal area of conductor ( mm )


t = duration of short circuit (sec)

Depth of Laying - to the highest point of cables


laid direct or to top surface of ducts, is taken to be
as follows:
a) 3.3, 6.6 and 11 kV cables

900 mm

b) 22 and 33 kV cables

1050 mm

Method of Installation :
a) Single core cables:

Three core cables


in trefoil touching

b) Three core cables

Installed single

The conductor size in a cable for an installation is also


governed by its ability to carry short circuit current of
the system.
Short circuit rating are based on the assumption that the
duration of short circuit is so small and apparently there
is no transmission of heat, produced during short circuit,
through the insulation and the whole of it is absorbed by
the conductor.
The short circuit current ratings (r.m.s. values) of XLPE
insulated cables with aluminium / copper conductors for
one second duration are given in table 1. These ratings
have been calculated on the following assumptions.
Parametres

Aluminium

Copper

1. Conductor temprature
prior to short circuit

90C

90C

2. Maximum permissible
conductor temprature
during short circuit

250C

250C

3. Specic gravity of
2.703
aluminium
4. Resistivity of aluminium 28.264
at 20 C (ohm/km/mm)
5. Temprature coefcient
of resistance at 20

8.89
17.24

0.00403/C 0.0039/C

With the above assumptions, the maximum short circuit


current is calculated with the following formula.
kxA
t

3) Combinations of duct and cable dimensions


assumed are shown below.
Duct Dimesions corresponding to cable diametre

2) Short Circuir Rating

Ish

k = a constant (Aluminium-0.094, Copper-0.143)

Maximum Conductor Temprature 90C

2. Thermal Resistivity of Soil

5.

Where Ish = r.m.s. value of short circuit current (kA)

Overall Cable Diameter

Inside Duct
Diameter

Outside
Duct
Diameter

mm

mm

mm

Up to and including 65

100

130

Above 65 and including 90

125

160

Above 90 and including 115

150

190

4) Rating Factors
In actual practice, conditions of installation may be
different from the standard installation conditions given
above. Hence to determine the continuous current rating
for the actual conditions, the tabulated current ratings
should be multiplied by the appropriate ratings factors or
factors given in Tables 26 to 40-c.
a) Cable Laid Direct in the Ground
i)

For Depth of laying

Refer
Table No.
26

ii)

For variation in ground


27
temprature
iii) For variation in thermal resistivity 28 and 29
of soil
iv) For group rating factors
30 and 31
b) Cables Installed in Ducts
i)

For depth of laying

Refer
Table No.
32

ii)

For variation in ground


33
temprature
iii) For variation in thermal resistivity 34 and 35
of Soil
iv) For group rating factors
36 and 37
c) Cables Installed in Air
i)

For variation in ambient air


temprature

d) Group Rating
i)

Group Rating factors for cables


laid in Trays/ Racks
(1core & 3 core)

Refer
Table No.
38
Refer
Table No.
39-A to
40-c

(kA)

19

HV CABLES

TECHNICAL CATALOGUE

20

1.12

15
1.08

20
1.04

25
1.00

30
0.96

35

1.17

1.18

1.19

1.19

1.19

1.19

1.19

1.19

1.2

1.2

1.2

1.2

1.21

1.21

1.21

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

1.11

1.11

1.11

1.11

1.11

1.11

1.11

1.1

1.1

1.1

1.1

1.1

1.1

1.1

1.09

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

0.87

0.87

0.87

0.87

0.87

0.87

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

Rating factors for variation in thermal resistivity of soil for three single core cables laid direct in the ground
Nominal Area of
Value of Thermal Resistivity of Soil K.m / W
Conductor mm2
1.0
1.20
1.50
2.00

TABLE 28

Rating Factor
(maximum conductor temperature 90 Deg.C)

Ground Temperature Deg.C

Rating factors for variation in ground temperature for cables laid direct in the ground

TABLE 27

Rating factors for depth of laying of cables laid direct in the ground
Depth of Laying (mm)
3.3,6.6 And 11 kV Cables
900
1.00
1050
0.99
1200
0.97
1500
0.95
1800
0.94
2000
0.93
2500
0.91
3000 or More
0.9

TABLE 26

0.78

0.78

0.78

0.79

0.79

0.79

0.79

0.79

0.79

0.79

0.79

0.8

0.8

0.8

0.8

2.50

0.91

40
0.87

45

22 And 33 kV Cables
1.00
0.99
0.97
0.95
0.94
0.92
0.91

3.0

0.72

0.72

0.72

0.72

0.72

0.72

0.72

0.72

0.73

0.73

0.73

0.73

0.73

0.74

0.74

0.82

50

21

1.09

1.16

1.16

1.16

1.16

1.16

1.17

1.17

1.17

1.17

70

95

120

150

185

240

300

400

500

1.09

1.09

1.09

1.09

1.09

1.09

1.09

1.08

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.50

0.5

0.45
0.43
0.42
0.41
0.40

10

11

12

0.53

0.47

0.58

0.64

0.76

TOUCHING

Number of Cables In Group

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.82

2.50

0.52

0.53

0.54

0.55

0.56

0.58

0.6

0.63

0.67

0.72

0.83

200

0.63

0.64

0.64

0.65

0.66

0.67

0.69

0.71

0.75

0.79

0.87

400

0.73

0.73

0.74

0.76

0.77

0.8

0.83

0.9

600

Spacing Between Trefoil Group Centres , mm

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.9

0.9

2.00

Value of Thermal Resistivity of Soil K.m / W

Group rating factors for circuits of three single - core cables in trefoil laid direct in the ground

TABLE 30

1.09

1.16

50

1.08

1.16

1.08

1.16

1.20

35

1.0

25

Nominal Area of Conductor mm2

Rating factors for variation in thermal resistivity of soil for three core cables laid direct in the ground

TABLE 29

0.79

0.8

0.81

0.84

0.86

0.92

800

0.74

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

3.0

HV CABLES

TECHNICAL CATALOGUE

22

0.67

0.61

0.56

0.53

0.5

0.48

0.46

0.44

0.43

0.42

10

11

12

200

0.57

0.58

0.59

0.6

0.61

0.63

0.65

0.68

0.72

0.77

0.86

0.98
0.96
0.95
0.94
0.93
0.92

1200

1500

1800

2000

2500

3000 or More

15

1.12

Ground Temperature
Deg.C

Rating Factor
(maximum conductor
temperature 90
Deg.C)

1.08

20

1.04

25

Rating factors for variation in ground temperature for cables in ducts

1.00

0.96

35

0.99

1050

30

1.00

900

TABLE 33

3.3,6.6 And 11 kV Cables

Depth of Laying (mm)

0.68

0.69

0.69

0.70

0.71

0.72

0.74

0.76

0.79

0.82

0.90

400

0.91

40

0.87

45

Spacing Between Trefoil Group Centres, mm

Rating factors for depth of laying single or three core cables in single way ducts.

TABLE 32

0.79

TOUCHING

Number of Cables In Group

Group rating factors for three core cables in horizontal formation laid direct in the ground.

TABLE 31
600

0.82

50

0.93

0.94

0.95

0.96

0.98

0.99

1.00

0.76

55

22 And 33 kV Cables

0.77

0.78

0.78

0.8

0.81

0.83

0.86

0.92

800

0.83

0.84

0.85

0.87

0.89

0.94

0.71

60

23

1.11

1.12

1.12

1.12

1.12

1.12

1.13

1.13

1.13

1.14

1.14

1.14

1.15

1.15

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

1.08

1.08

1.08

1.08

1.08

1.07

1.07

1.07

1.07

1.07

1.07

1.06

1.06

1.06

1.05

1.20

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.50

1.07

1.07

1.07

1.08

1.08

1.09

1.09

1.09

1.09

1.09

1.1

1.1

35

50

70

95

120

150

185

240

300

400

500

1.0

25

Nominal area of conductor mm2

1.06

1.06

1.05

1.05

1.05

1.05

1.05

1.05

1.04

1.04

1.04

1.04

1.20

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.50

0.92

0.92

0.92

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

2.00

Value of Thermal Resistivity of Soil K.m / W

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.91

0.91

0.91

0.91

0.92

0.92

0.92

0.92

2.00

Value of Thermal Resistivity of Soil K.m / W

Rating factors for variation in thermal resistivity of soil for three core cables in single way ducts

TABLE 35

1.11

1.0

25

Nominal area of conductor mm2

Rating factors for variation in thermal resistivity of soil for three single core cables in ducts

TABLE 34

0.86

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.88

0.88

0.88

0.89

2.50

0.82

0.82

0.82

0.83

0.83

0.83

0.83

0.84

0.84

0.84

0.84

0.85

0.85

0.85

0.85

2.50

0.81

0.82

0.82

0.82

0.82

0.83

0.83

0.83

0.83

0.83

0.83

0.84

3.0

0.76

0.76

0.76

0.77

0.77

0.77

0.78

0.78

0.78

0.79

0.79

0.79

0.79

0.8

0.8

3.0

HV CABLES

TECHNICAL CATALOGUE

24
0.49
0.48

10

0.54

0.55

0.56

0.6

0.63

0.65

0.69

0.85
0.75
0.7
0.65
0.62
0.59
0.57
0.55
0.54
0.52
0.51

10

11

12

TOUCHING

Number of Cables In Group

400

0.66

0.66

0.67

0.68

0.69

0.70

0.72

0.74

0.77

0.81

0.89

600

0.75

0.76

0.77

0.78

0.79

0.82

0.84

0.91

0.62

0.63

0.64

0.65

0.67

0.68

0.7

0.73

0.76

0.81

0.89

200

0.73

0.74

0.74

0.75

0.76

0.77

0.78

0.80

0.83

0.86

0.92

400

0.81

0.82

0.82

0.84

0.85

0.87

0.89

0.94

600

Spacing Between Trefoil Group Centres , mm

Group rating factors for circuits of three - core cables in single-way ducts in horizontal formation.

TABLE 37

0.51

0.46

0.53

0.47

0.56

12

0.57

0.59

11

0.59

0.64

0.75

0.69

200
0.85

0.81

TOUCHING

Spacing Between Trefoil Group Centres , mm

No. of cables in Group

Group rating factors for circuits of single - core cables in single-way ducts in trefoil

TABLE 36
800

0.86

0.87

0.88

0.89

0.91

0.95

800

0.81

0.82

0.83

0.85

0.87

0.93

25

1.16

Rating Factor
(Maximum Conductor Temperature 90
Deg.C)
1.11

30
1.06

35
1.00

40
0.94

45
0.88

50
0.81

55
0.74

60
0.71

65
0.63

70

0.9

0.88

0.86

0.81

0.83

0.85

0.9

0.79

0.81

0.83

0.88

No. of Cables

Number of Cables Trays


In Tier

0.93

0.94

0.95

0.98

0.90

0.92

0.93

0.96

No. of Cables

Group rating factors for single core cables laid on racks/trays in open air trench without covers where air circulation is not restricted, trefoils are seperated by two cable
dia horizontally and the trays are in tiers with 30 cm. Gap between them.

TABLE 39-B

0.95

In Tier

Number of Cables Trays

Group rating factors for single core cables laid on racks/trays in covered trench with removable covers where air circulation is restricted, trefoils are seperated by two cable
dia horizontally and the trays are in tiers with 30 cm. Gap between them.

TABLE 39-A

25

Air Temperature Deg.C

Rating factors for variation in ambient air temperature.

TABLE 38

HV CABLES

TECHNICAL CATALOGUE

26

0.9

0.88

0.86

0.81

0.83

0.85

0.9

0.79

0.81

0.83

0.88

No. of Cables

0.77

0.79

0.81

0.85

0.76

0.78

0.8

0.84

0.93

0.94

0.95

0.98

0.90

0.92

0.93

0.96

No. of Cables

0.87

0.89

0.9

0.93

0.86

0.88

0.89

0.92

Number of Cables Trays In Tier

0.76

0.78

0.8

0.84

0.72

0.74

0.76

0.80

No. of Cables

0.68

0.7

0.71

0.75

0.66

0.68

0.69

0.73

Group rating factors for three - core cables laid on cable trays exposed to air, the cables touching and trays in tiers by 300 mm. The clearance between the wall and the
cable 25 mm

TABLE 40-C

Number of Cables Trays In Tier

Group rating factors for three - core cables laid on cable trays exposed to air, the cable spaced by one cable diameter and trays in tiers by 300 mm. The clearance
betweenthe wall and the cable 25 mm

TABLE 40-B

0.95

Number of Cables Trays In Tier

Group rating factors for three - core cables laid inside concrete trench with removable covers, on cable trays where air circulation is restricted. The cable spaced by one
cable diameter and trays in tiers by 300 mm. The clearance between the wall and the cable 25 mm

TABLE 40-A

PROCESS FLOW
CHART
MATERIAL USED
1

ALUMINIUM

MANUFACTURING OPERATIONS
WIRE DRAWING

CONDUCTOR STRANDING

SEMICONDUCTING CROSS - LINKED POLYETHYLENE

CROSS LINKED POLYETHYLENE

SEMICONDUCTING CROSS - LINKED POLYETHYLENE

INSULATION SHIELDING (EXTRUSION AND VULCANIZING)

ANNEALED COPPER TAPE

METALLIC SHIELDING

PLASTIC FILLERS

LAYING-UP OF CORES WITH PLASTIC FILLERS

THERMOPLASTIC TAPES OR EXTRUDED


PVC/POLYTHYLENE

INNER SHEATHING

GALVANISED FLAT STEEL STRIPS OR


GALVANISED ROUND STEEL WIRES

PVC / POLYETHYLENE

CONDUCTOR SHIELDING (EXTRUSION AND VULCANIZING)

CROSS LINKED POLYETHYLENE INSULATION (EXTRUSION AND VULCANIZING)

ARMOURING

OUTER SHEATHING
(EXTRUSION)

TESTING

PACKING

NOTE: For 3 Core 3.3 kV grade unscreened cables, activities 2,4,5 will not be applicable

27

TECHNICAL CATALOGUE

HV CABLES

DRUM
HANDLING
In order to prevent damage to cable drums during
transportation, observe the following six instructions:

1. Always stand upright


Otherwise the cable might be damaged or the cable
layers tangled making it impossible to pull out and use
the cable.

2. Crane handling
Always use yoke to avoid damage to the drum anges and cable.
Always use lifting bar to avoid damage to the centre hole

3. Fork lift truck handling


The forks must cover the drum entirely. Otherwise the
lagging will be destroyed and the cable will get damaged.

28

DRUM
HANDLING
4. Lower gently on to a
level surface

5. Use blocks during unloading


Nail the blocks to the oor

6. Leave space between drums


during unloading
Enough space should be left to prevent damage to cable end and drum ange

CORPORATE OFFICE
6th Floor, RPG House, 463. Dr. Annie Besant Road, Worli, Mumbai - 400 030. India
Tel. +91-22-66670300, 24937244 | Fax No. +91-22-24930206
email: powercables@kecrpg.com | telecomcables@kecrpg.com | exportcables@kecrpg.com

SALES OFFICES
Delhi

Mumbai

Pune

Chennai

N-83,1st Floor,(Above PNB )


Pratap Building, Connaught Place,
New Delhi - 110 001. India

6th Floor, RPG House, 463.


Dr. Annie Besant Road, Worli,
Mumbai - 400 030. India

Flat No.9, KSHITIJ ,1st Floor, 769/6,


Lane No.7, Prabhat Road, Deccan
Gymkhana, Pune - 411 004. India

Bhavani Mansion No.3, 4th Lane,


Nungambakkam High Road,
Chennai - 600 034. India

Tel. +91-11-66098598, 599


Fax No. +91-11-66098597

Tel. +91-22-66670300, 24937244


Fax No. +91-22-24930206

Tel. +91-20-64706061, 6065


Fax No. +91-20-25650414

Tel. +91-44-28332920, 28332918


Fax No. +91-44-28332917

Kolkata

Vadodara

Hyderabad

Bangalore

Halwasiya Mansion, Ground Floor,


6/2, Moira Street,
Kolkata - 700 017. India

421, Center Point,


R. C. Dutt Road, Alkapuri,
Vadodara - 390 007. India

406 & 407, Maheshwari Chambers,


Erramanzil, Somajiguda,
Hyderabad - 500 082. India

C/o. CEAT Limited, Jasmine Mansion,


4th Floor, 19, J. C. Road,
Bangalore - 560 002. India

Tel. +91-33-64590654
Fax No. +91-33-22906720

Tel. +91-265-3015454
Fax No. +91-265-3015454

Tel. +91-40-30901642
Fax No. +91-40-30901642

Tel. +91-80-22124444