You are on page 1of 55

Technical Study Report

Energy Efficient
Transformers
This report was produced under the project entitled “Supporting Action
on Climate Change through a Network of National Climate Change Focal
Points in South-east Asia” (SEAN-CC) implemented by UNEP and funded by
Ministry of Foreign Affairs of the Government of Finland.

Dec 2011

Energy Efficient Transformers


Contents
Section 1: Introduction 2
1.1 Type of Transformers 2
1.2 Substation Transformers 2
1.3 Distribution Transformers 7
1.4 Energy Savings Outlook 8

Section 2: Describe the Proposed Technology 11


2.1 Transformer Efficiency 12
2.2 Transformer Losses 12
2.3 Traditional Technologies 13
2.4 Cost Economics 16

Section 3: Requirements of the Technology 20


Intervention
3.1 New Technology Awareness and Acceptance 21
3.2 Contribution to Energy Efficiency and Global Warming Goals 22
3.3 Characterization of the Utility Market 22
3.4 National/International Policies and Initiatives 23
3.5 Potential Mechanisms for Change 24
3.6 International Perspective 24

Section 4: Analysis, Recommendations and 31


Action Plans
4.1 Use of High-efficiency Transformers 32
4.2 Amorphous Transformers 37
4.3 Running Cool for Lower Energy Costs 42
4.4 Projected Energy Savings Using Metglas AMDTs 42
4.5 Superconducting Transformers 43

Section 5: Follow-up to the Technology 45

5.1 Research & Development 46


5.2 Energy Efficient Distribution Transformers Trends 47
5.3 Some of the Short Term and Long Term Measures Taken by BEE 53
5.4 Policies & Regulations 52

Energy Efficient Transformers


Section 1

Energy Efficient Transformers 1


Section 1

Introduction
Before invention of transformers, in initial days of electrical industry, power was distributed as direct
current at low voltage. The voltage drop in lines limited the use of electricity to only urban areas where
consumers were served with distribution circuits of small length. All the electrical equipment had to be
designed for the same voltage. Development of the first transformer around 1885 dramatically changed
transmission and distribution systems. The alternating current (AC) power generated at a low voltage
could be stepped up for the transmission purpose to higher voltage and lower current, reducing voltage
drops and transmission losses. Use of transformers made it possible to transmit the power economically
hundreds of kilometers away from the generating station. Step-down transformers then reduced the
voltage at the receiving stations for distribution of power at various standardized voltage levels for its
use by the consumers. Transformers have made AC systems quite flexible because the various parts and
equipment of the power system can be operated at economical voltage levels by use of transformers
with suitable voltage rating. The voltage levels are different in different countries depending upon their
system design. Transformers can be broadly classified, depending upon their application as given below.

1.1 Types of Transformers


1.1.1 Power Transformers

ANSI/IEEE defines a transformer as a static


electrical device, involving no continuously
moving parts, used in electric power systems to
transfer power between circuits through the use
of electromagnetic induction. The term power
transformer is used to refer to those transformers
used between the generator and the distribution
circuits, and these are usually rated at 500 KVA
and above. Power systems typically consist of a
large number of generation locations, distribution Fig. 1.1.1 Power Transformer

points, and interconnections within the system or


with nearby systems, such as a neighboring utility.
The complexity of the system leads to a variety
of transmission and distribution voltages. Power
transformers must be used at each of these points
where there is a transition between voltage levels.

Energy Efficient Transformers 2


Section 1

1.1.2 Distribution Transformers 1.1.3 Phase-Shifting Transformers


In 1886, George Westinghouse built the first The necessity to control the power flow rose
long-distance alternating-current electric lighting early in the history of the development of
system in Great Barrington, MA. The power electrical power systems. When high-voltage
source was a 25-hp steam engine driving an grids were superimposed on local systems,
alternator with an output of 500 V and 12 A. In parallel-connected systems or transmission lines
the middle of town, 4000 ft away, transformers of different voltage levels became standard.
were used to reduce the voltage to serve light Nowadays large high-voltage power grids are
bulbs located in nearby stores and offices (Powel, connected to increase the reliability of the
1997). electrical power supply and to allow exchange
of electrical power over large distances.
Any transformer that takes voltage from a Complications, attributed to several factors such
primary distribution circuit and “steps down” as variation in power generation output and/or
or reduces it to a secondary distribution circuit power demand, can arise and have to be dealt
or a consumer’s service circuit is a distribution with to avoid potentially catastrophic system
transformer. Although many industry standards disturbances. Additional tools in the form of
tend to limit this definition by KVA rating (e.g., phase-shifting transformers (PSTs) are available
5 to 500 KVA), distribution transformers can to control the power flow to stabilize the grids.
have lower ratings and can have ratings of 5000 These may be justified to maintain the required
KVA or even higher, so the use of KVA ratings quality of the electrical power supply.
to define transformer types is being discouraged
(IEEE, 2002b). 1.1.4 Rectifier Transformers
Power electronic circuits can convert alternating
current (ac) to direct current (dc). These are called
rectifier circuits. Power electronic circuits can also
convert direct current to alternating current. These
are called inverter circuits. Both of these circuits
are considered to be converters. A transformer that
has one of its windings connected to one of these
circuits, as a dedicated transformer, is a converter
Fig. 1.1.2 Three-Phase Distribution Transformer transformer, or rectifier transformer. IEC
standards refer to these transformers as converter
transformers, while IEEE standards refer to these
transformers as rectifier transformers. Because
it is IEEE practice to refer to these transformers
as rectifier transformers, that same term is
used throughout this discussion. Transformers
connected to circuits with a variety of loads,
but which may contain some electronic circuits
that produce harmonics, are not considered to
be rectifier transformers. However, they may
have harmonic heating effects similar to rectifier
Fig. 1.1.3 Quadrature booster set (300 MVA, 50 Hz,
400􀁳12*1.25%/115􀁳12*1.45˚ kV). transformers. Those transformers are covered
under IEEE.

Energy Efficient Transformers 3


Section 1

Many perceptions of dry-type transformers


Recommended Practice for Establishing are associated with the class of design by
Transformer Capability when Supplying Non- virtue of the range of ratings or end-use
Sinusoidal Load Currents, ANSI/IEEE C57.110. applications commonly associated with
that form of construction Of course, the
fundamental principles are no different from
those encountered in liquid-immersed designs,
as discussed in other chapters. Considerations
involving harmonics are especially notable in this
regard.

Consequently, this chapter is brief, expounding


only on those topics that are particularly relevant
for a transformer because it is “dry.”

Fig. 1.1.4 A 12-pulse Circuit 31 5450-kVA, 4160-V delta primary to 1.1.6 Instrument Transformers
2080-V delta and wye secondaries, cast coil transformer in case.
Instrument transformers are primarily used to
1.1.5 Dry-Type Transformers provide isolation between the main primary
A dry-type transformer is one in which the circuit and the secondary control and measuring
insulating medium surrounding the winding devices. This isolation is achieved by magnetically
assembly is a gas or dry compound. Basically, any coupling the two circuits. In addition to isolation,
transformer can be constructed as “dry” as long as levels in magnitude are reduced to safer levels.
the ratings, most especially the voltage and KVA,
Instrument transformers are divided into two
can be economically accommodated without the
categories: voltage transformers (VT) and current
use of insulating oil or other liquid media. This
transformers (CT). The primary winding of the
section covers single- and three-phase, ventilated,
VT is connected in parallel with the monitored
non-ventilated, and sealed dry type transformers
circuit, while the primary winding of the CT
with voltage in excess of 600 V in the highest-
is connected in series. The secondary windings
voltage winding.
proportionally transform the primary levels to
typical values of 120 V and 5 A. Monitoring
devices such as watt-meters, power-factor meters,
voltmeters, ammeters, and relays are often
connected to the secondary circuits.

Fig. 1.1.5 Cast Resin Dry Type Transformer

Energy Efficient Transformers 4


Section 1

(a) (b)

Fig. 1.1.6 (a) 69-kV single-bushing VT,(b) High-voltage wound-type CT in combination steel tank, oil, and porcelain construction.

Energy Efficient Transformers 5


Section 1

1.1.7 Step-Voltage Regulators 1.1.8 Constant-Voltage Transformers


Distribution systems must be designed in such Constant-voltage transformers (CVT) have
a way that voltage magnitudes always remain been used for many years, primarily as a noise-
within a specified range as required by standards. isolation device. Recently, they have found value
This is accomplished through the use of voltage- when applied as a voltage-sag protection device
control equipment and effective system design. for industrial and commercial facilities. The
Regulating power transformers (load-tap- industrial use of constant-voltage transformers
changing transformers, or LTCs), three-phase (also called CVTs and ferroresonant transformers)
step-voltage regulators, single-phase step-voltage goes back to the early 1940s. Joseph G. Sola,
regulators, and Auto-Boosters are typical a German-born engineer, discovered the CVT
transformer-type equipment used to improve the technology [1,2] based on a single transformer
voltage “profile” of a power system. rather than an arrangement of transformers,
separate filters, and capacitors. This innovation
provides several important advantages: its
inherent robustness (CVT consists of just three
or four windings and a high-reliability capacitor),
its imperviousness to continuous short circuits
(whether it is turned on into a short circuit or
from full load), and its capability to maintain
output-voltage stabilization on a cycle-to-cycle
basis for significantly large overvoltages and
undervoltages.

Primary
Section of
the Core
Primary
Winding
Magnetic
Shunt
Air Gap
Secondary
Fig. 1.1.7 Single Phase Auto Booster Four-Step Voltage
Winding
Regulator Resonating
Resonant
Winding
Capacitor
Single-phase step-voltage regulators maintain a Secondary
constant voltage by on-load voltage regulation Section of
the Core
wherever the voltage magnitude is beyond
Fig. 1.1.8 Components of a typical constant-voltage transformer.
specified upper and lower limits. A common
practice among utilities is to stay within preferred
voltage levels and ranges of variation as set forth
by ANSI 84.1, Voltage Rating for Electric Power
Systems and Equipment.

Energy Efficient Transformers 6


Section 1

Industrial Agricultural

Resident
Substation Transformer

Distribution
Transformer
Commercial

Fig. 1.2 Electrical Distribution System

1.2 Substation Transformers 1.3 Distribution Transformers


A substation is a high-voltage electric facility. It is Distribution transformers: Using distribution
used to switch generators, equipment and circuits transformers, the primary feeder voltage is
or lines in and out of system. A Substation is also reduced to actual utilization voltage (~415 or 460
used to change AC voltages from one level to V) for domestic/ industrial use. A great variety of
another, or change alternating current to direct transformers fall into this category due to many
current or direct current to alternating current. different arrangements and connections. Load
There are small substations and large one. The on these transformers varies widely, and they are
small substation are little more than a transformer often overloaded. A lower value of no-load loss is
and relate switches, while the large one has desirable to improve all-day efficiency. Hence, the
several transformers an dozens of switches and no-load loss is usually capitalized with a high rate
equipment. at the tendering stage. Since very little supervision
is possible, users expect the least maintenance
There are generally four types of substation, but on these transformers. The cost of supplying
some substations there are a combination of two losses and reactive power is highest for these
or more types. transformers.

Substation Transformer Types


• Step-Up Transmission Substations
• Step-Down Transmission Substation
• Distribution Substation
• Underground Distribution Substation

Energy Efficient Transformers 7


Section 1

1.4 Energy Savings Outlook benefits. Taking the full life cycle cost into
account, selecting high efficiency transformers
Transformers typically can be expected to operate
is normally an economically sound investment
20-30 years or more, so buying a unit based only
decision despite their higher purchase price. As
on its initial cost is uneconomical and foolish.
a result, high efficiency transformers yield a net
Transformer life-cycle cost (also called “total
economic gain for global society. A reduction
cost of ownership”) takes into account not only
of energy consumption is also an important
the initial transformer cost but also the cost to
advantage for the world’s environment { not least
operate and maintain the transformer over its
because of the resulting reduction in greenhouse
life. This requires that the total owning cost
gas emissions.
(TCO) be calculated over the life span of the
transformer. With this method, it is now possible With this savings potential available, seven of
to calculate the real economic choice between the largest economies in the world have been
competing models. (This same method can be taking actions to improve transformer efficiency:
used to calculate the most economical total cost Australia, China, Europe, Japan, Canada and the
of ownership of any long-lived device and to USA. They have set up programs { mandatory
compare competing models on the same basis.) or voluntary { based on minimum standards or
The TCO method not only includes the value of efficiency labels. Up to now, the programs in
purchase price and future losses but also allows Australia, China, India and Japan are the most
the user to adjust for tax rates, cost of borrowing advanced.
money, different energy rates, etc.
1.4.2 Network Losses
Losses of the electricity network world-wide
1.4.1 Why focus on distribution
can be estimated at 1 279 TWh, or 9.2% of
transformers?
electricity use. While some level of losses is
Energy losses throughout the world’s electrical inevitable, tables 1.4.1 and 1.4.2 show a variation
distribution networks amount to 1 279 TWh. in losses from less than 4% to more than 20%.
They vary from country to country between This variation cannot be explained alone by
3.7% and 26.7% of the electricity use, size of country, size of the electricity system or
which implies that there is a large potential population.
for improvement. After lines, distribution
transformers are the second largest loss- Network losses in certain countries have
making component in electricity networks. decreased steadily over the past decades. The data
Transformers are relatively easy to replace, shows that there remains a large potential for
certainly in comparison with lines or cables, improvement. Network losses are important for
and their efficiency can fairly easily be classified, several reasons. They represent a global economic
labeled and standardized. Moreover, modern loss of US$ 61 billion, adding unnecessarily to
technology exists to reduce losses by up to 80%. the cost of electricity. Especially in developing
The worldwide electricity savings potential of countries, losses use scarce generating capacity.
switching to high efficiency transformers is
estimated to be at least 200 TWh, equivalent to Over 700 million tons of greenhouse gas
the Benelux electricity consumption. This savings emissions can be associated with these losses.
potential is not only technically advantageous, Table 1.4.3 shows an indicative breakdown of
but also brings economic and environmental transmission and distribution losses, based on a
limited number of case studies:

Energy Efficient Transformers 8


Section 1

Typically, a third of losses occur in transformers, • Distribution transformers represent the 2nd
and two thirds in the rest of the system. largest loss component in the network
• Replacing transformers is easier than changing
Approximately 70% of losses occur in the cables or lines
distribution system. There is a very high potential • Transformers have a large potential for loss
for high efficiency distribution transformers, as a reduction. Technologies exist to reduce losses
technology to improve network losses. There are by up to 80%.
several good reasons for such a focus:

Country Electricity use Network losses Network losses


(TWh) (TWh) (%)
Europe 3 046 222
Western Europe 2 540 185 7.3
Former Soviet Union 1135 133 11.7
North America 4 293 305 7.1
Latin America 721 131
18.3
Brazil 336 61
Asia 3 913 381
Japan 964 98 9.1
Aus, NZ 219 21 9.5
China 1 312 94 7.2
India 497 133 26.7
Africa / ME 826 83 10.0
Total 13 934 1 279 9.2
Table 1.4.1: Estimated network losses in the world
* Leonardo Energy Transformers – Leonardo-energy.org

Energy Efficient Transformers 9


Section 1

Country 1980 1990 1999 2000


Finland 6.2 4.8 3.6 3.7
Netherlands 4.7 4.2 4.2 4.2
Belgium 6.5 6.0 5.5 4.8
Germany 5.3 5.2 5.0 5.1
Italy 10.4 7.5 7.1 7.0
Denmark 9.3 8.8 5.9 7.1
United States 10.5 10.5 7.1 7.1
Switzerland 9.1 7.0 7.5 7.4
France 6.9 9.0 8.0 7.8
Austria 7.9 6.9 7.9 7.8
Sweden 9.8 7.6 8.4 9.1
Australia 11.6 8.4 9.2 9.1
United Kingdom 9.2 8.9 9.2 9.4
Portugal 13.3 9.8 10.0 9.4
Norway 9.5 7.1 8.2 9.8
Ireland 12.8 10.9 9.6 9.9
Canada 10.6 8.2 9.2 9.9
Spain 11.1 11.1 11.2 10.6
New Zealand 14.4 13.3 13.1 11.5
Average 9.5 9.1 7.5 7.5
European Union 7.9 7.3 7.3 7.3
Table 1.4.2: Transmission and distribution losses in selected countries
* Leonardo Energy Transformers – Leonardo-energy.org

% of total Trans former Lin es Other


Case T D T D
USA - example 1 4.0 16.2 32.3 10.5 2.0
USA - example 2 2.2 36.5 45.5 43.0 7.8
Australia - example 2.0 40.0 20.0 38.0

UK - example 1 8.0 24.0 21.0 15.0


UK - example 2 10.0 32.0 45.0 43.0 2.0
Market assessment 10.0 35.0 15.0 19.0 2
Average 6.0 30.6 35.0 41.6 2.8
Table 1.4.3: Breakdown of Transmission (T) & Distribution (D) losses
* Leonardo Energy Transformers – Leonardo-energy.org

Energy Efficient Transformers 10


Section 2

Energy Efficient Transformers 11


Section 2

DESCRIBE THE PROPOSED TECHNOLOGY


2.1 Transformer Efficiency 2.2 Transformer Losses
The efficiency of a transformer, like any other There are three different types of losses:
device, is defined as the ratio of useful output
• No-load loss (also called iron loss or core loss):
power to input power.
Caused by the hysteresis and eddy currents in
the core. It is present whenever the transformer
The percentage efficiency of a transformer is is connected, and independent of the load. It
in the range of 95 to 99%. For large power represents a constant, and therefore significant,
transformers with low loss designs, the efficiency energy drain.
can be as high as 99.7%. • Load loss (or copper loss or short circuit loss):
Caused by the resistive losses in the windings
There is a possibility of error if the efficiency is and leads, and by eddy currents in the
determined from the measured values of output structural steelwork and the windings. It varies
and input powers, as the wattmeter readings may with the square of the load current.
have an error of about 1%. Hence, it is a more • Cooling loss (only in transformers with fan
accurate approach if the efficiency is determined cooling): Caused by the energy consumption
using the measured values of losses by the open of a fan. The bigger the other losses, the more
circuit and short circuit tests. cooling is needed and the higher the cooling
loss. These losses can be avoided if operational
Although the load power factor has some effect temperature is kept low by different loss
on the mutual flux and hence the core loss, the reduction measures.
effect is insignificant, allowing us to assume that
the core loss is constant at all the load conditions. 2.2.1. Transformer Losses Standards
Although the efficiency of a transformer is given There are European specifications for power
by the ratio of output power to input power, systems transformers, which set standards for
there are some specific applications of transformer performance, including power losses. These have
in which its performance cannot be judged only consolidated earlier national standards, and are
by this efficiency. Distribution transformers, for compatible with International Electrotechnical
example, supply a load which varies over a wide Commission (IEC) world standards. They have
range throughout the day. For such transformers, been developed by the European Committee for
the parameter all-day efficiency is of more Electrotechnical Standardisation (CENELEC), in
relevance. The output and losses are computed consultation with UNIPEDE.
for a period of 24 hours using the load cycle.
No-load losses are constant (independent of The distribution transformer standards applicable
load); hence it is important to design distribution within EU are all documented. Non-utility
transformers with a lower value of no-load losses outdoor distribution transformers are superficially
so that a higher value of all day energy efficiency very similar to utility transformers, but the
is achieved. specifications and sizes may be different. For
example, many European railways are supplied
at 15kV, 162/3Hz, single phase. Mining
transformers are often flameproof.

Energy Efficient Transformers 12


Section 2

Distribution transformers with conventional lower core loss steels, or by reducing flux
oil cooling and installed on indoor sites, for density in a specific core by increasing the
example the basement of a large commercial core size
building, are considered to pose a possible • current density in the copper windings.
fire risk. They are required by the building Increasing conductor cross-section reduces
regulations in many EU countries either to use the current density. This will improve energy
non-flammable coolants, or to be dry-type, efficiency, but also result in higher cost.
without coolants. Polychlorinated biphenyls Because copper losses are dependent on the
(PCBs), the principal coolant used in the past, loading of the transformer, it is necessary to
have been linked with the production of highly consider how the unit is to be installed and
toxic chlorine compounds, mainly dioxins, at used in practice
high temperatures. Non-toxic coolants are now • iron/copper balance. The balance between
available, and cast resin clad transformers offer an the relative quantities of iron and copper
alternative to dry-type construction. Reliability in the core and windings. A “copper-rich”
is reported to be the main factor influencing the unit has a high efficiency across a wide range
way in which distribution transformers are chosen of load currents. An “iron-rich” unit has a
by consulting engineers and non-utility sector lower initial cost price, and may be more
customers. Their installations are relatively small economical when transformers are expected to
in scale, and unlike utility networks may have be lightly loaded.
only limited back-up in the case of transformer
failure. These basic considerations must then be
combined with a wide range of other factors,
2.3 Traditional Technologies to enable a competitive tender to be submitted
to the customer. Copper and iron prices are
2.3.1 Distribution Transformer
Technology continually changing, and this can affect the
balance between the two materials.
1) Design Concepts
Transformer design is extremely specialized, and A variety of proprietary steels are available for
requires a capable and experienced design team. building the core, and the techniques to be used
Transformers are manufactured against specific for the construction of the transformer core,
customer invitations to tender, taking into windings, insulation and housing need to be
account the following basic parameters: decided. Alternative materials, such as aluminum
coils or pre-formed copper windings, could be
• flux density (or induction), a measure of considered. The energy efficiency of a distribution
the loading of the iron core. Each magnetic transformer, in terms of losses, is usually specified
steel has its typical inherent core loss, directly by the customer.
related to its flux density. Once above the
saturation induction of the steel, the flux a) Transformer Steels
will leave the core and no-load losses are no The energy efficiency of distribution
longer under control. Maximum flux density transformers is fundamentally dependent
should therefore be limited to well below on the type of steel used for building the
this saturation point. Energy-efficiency can transformer core. Please see Fig 9. More
be improved by selecting better performing, specialized steels, particularly suitable for

Energy Efficient Transformers 13


Section 2

distribution and larger transformers, have b) Grain-oriented Steels


developed in a number of stages. Conventional grain-orientated (CGO) steels
are rolled from silicon- iron slabstock, and
Thin hot-rolled steel sheet, with a silicon coated on both sides with a thin layer of
content of about 3%, became the basic oxide insulating material to reduce eddy-
material for fabricating electromagnetic currents. They are supplied in Europe in
cores in about 1900. Individual sheets were about 10 standard thickness. The European
separated by insulating layers to combine low standard, EN10107, reflects the international
hysteresis losses with high resistivity. Cold IEC 60404 standard, and describes a range
rolling and more sophisticated insulation of gauges from 0.23-0.50mm (previously
techniques were progressively developed. M3-M7, a nomenclature which is recognized
Grain-oriented silicon steels, in which the world-wide). CGO steels remain the standard
magnetic properties of transformer steels are raw material for distribution transformer
improved by rolling and annealing, to align manufacture in Europe. They are estimated
the orientation of the grains, became available to account for over 70% of the total steel
in the mid-1950s. Various processing and consumption in distribution transformer
coating techniques, combined with a reduced production, estimated at about 100,000 tons
silicon content, were incorporated into high per year. Demand is still very much skewed
permeability grain-oriented steels, about 10 to the thicker gauges. Thinner gauge CGO
years later. During the 1980s, techniques were and other more sophisticated raw materials are
introduced for domain refinement, reducing considerably more expensive, reflecting higher
domain width by mechanical processes, capital investment and technology levels,
principally laser-etching. as well as additional processing steps. Core
production costs are also higher.

Energy Efficient Transformers 14


Section 2

High permeability steels are manufactured are labor-intensive, and require skilled workers.
to the same European Standard as CGO, Again the performance and energy efficiency of
and are available in about five gauges ranging a distribution transformer greatly depends on
from 0.23-0.30mm. They account for about these steps. Mechanized winding, under operator
20% of total consumption in transformer control, is increasingly used for producing
manufacture. coils based upon copper wire, wide strip and
aluminum foil.
c) Conductor
The conductor materials for winding the coils The main types of coil which are now used in
of distribution transformers are supplied in distribution transformers are:
the form of wire, narrow strip or sheet. They • spiral sheet windings, using wide copper
have not experienced the same significant step strip or aluminum foil. A relatively recent
changes in recent years as core steels. The main development, used in place of helical coils for
developments have been: the availability of the LV windings of distribution transformers,
copper and aluminum wire-rod produced by particularly where there are only a small
continuous casting and rolling (CCR) processes, number of turns required in the coil
combined with mechanized handling techniques. • multilayer coils for HV windings. The
This has enabled semi-fabricators to offer wire complete winding is a single unit, wound in
and strip in much longer lengths than was wire, consisting of several layers and a number
previously possible, increasing transformer of turns per layer.
reliability. The welded or brazed joints in strip, • disc coils, particularly for the HV windings of
which were inevitable in rod produced from dry-type transformers. A number of radially
wire-bar, created weak points in the finished coils wound discs produced from a single length
l both copper and aluminum are now available in of conductor, separated from one another by
wide sheet and foil form with high dimensional insulating spacers.
tolerances. Sheet has extensively replaced strip for
the LV windings of distribution transformers. 2.4 Cost Economics
2.4.1 Distribution Transformer
Standards
d) Other Materials
Most of the characteristics of distribution
Developments have also taken place in the other
transformers are specified in national or
components used in distribution transformer
international product standards. The application
manufacture. The most significant are the
of standards can be legally required, or by specific
development of flame-proof coolants to replace
reference in the purchase contract.
PCBs, and the use of cast resin encapsulation
as an alternative to dry construction in non- Generally, the purpose of standards is to facilitate
liquid cooled transformers. More sophisticated the exchange of products in both home and
insulating papers and boards, including synthetic overseas markets, and to improve product quality,
and self-bonding papers, are also available. health, safety and the environment. International
standards are also of importance in reducing trade
barriers. For distribution transformers purchased
2) Coil Winding and Assembly
in the European Union, three levels of standards
The processes of winding the conductor coils are applicable:
and then fitting them onto the assembled core

Energy Efficient Transformers 15


Section 2

• world-wide standards (ISO, IEC, ANSI) Among the many international standards for
• European standards and regulations (EN, HD) distribution transformers, two main European
• national standards (e.g. BSI, NF, DIN, NEN, Harmonization Documents specify energy
UNE, OTEL). efficiency levels:

European Harmonization Documents are • HD428: Three-phase oil-immersed


initiated if there is a need for a European distribution transformers 50Hz, from 50 to
standard. The draft HD is a compilation of the 2,500kVA with highest voltage for equipment
different national standards on the subject. The not exceeding 36kV
HD is finalized by eliminating as many national • HD538: Three-phase dry-type distribution
differences as possible. transformers 50Hz, from 100 to 2,500kVA,
with highest voltage for equipment not
When a harmonization document (HD) has exceeding 36 kV.
been issued, conflicting national standards have
to be withdrawn within a specified period of A separate HD is under consideration for pole-
time, or modified to be compatible with the HD. mounted transformers. In the next Section, the
Usually, the HD is the predecessor of an European efficiency limits defined in these standards are
standard (EN), which must be adopted as a discussed. The standards however leave considerable
national standard in the EU member countries. freedom for local deviations in energy efficiency,
Thus, purchase orders which refer to national which implies that energy loss levels may (and do)
standards are compatible with European standards still vary across European countries and even in
(EN) and/or harmonization documents (HD). other countries. (Please see Table 2.4.1)

Country /Region Standard Subject


USA • Guide for Determining Energy Efficiency Efficiency standards and TOC
for Distribution Transformers (TP1- formula
1996). National Electrical Manufacturers
Association. 1996.
• Standard Test Method for Measuring the
Energy Consumption of Distribution
Transformers (TP2-1998).
• National Electrical Manufacturers
Association. 1998.
• Power transformers - Application guide,
60076-8, IEC:1997
International Design, calculation aspects
including measurement of
losses
Europe Cenelec 1992, Harmonization documents Efficiency standards and
HD 428, HD538 oil and dry type cost capitalization formula
transformers
Variety of country standards defining efficiency levels; MEPS in Australia, Canada,
China, Japan, Mexico, proposed in India and New Zealand, non mandatory in Europe
Table 2.4.1: Main transformer efficiency standards
* Leonardo Energy Transformers – Leonardo-energy.org

Energy Efficient Transformers 16


Section 2

2.4.2 Life-cycle Costing In which:


Most company structures separate the purchasing • P0 is the no-load loss [kW]
function from operations. This results in a • Pk is the load loss [kW]
situation where the purchase of a transformer is • I is the rms-average load of the transformer2
often based on the delivery price only. In most • 8760 is the number of hours in a year
cases however, transformers with the lowest
purchase price are also the ones with the highest TCCloss = Eloss * C * (1 + r)n - 1 / r * (1 + r)n
losses. Since transformers have a long life span,
these extra losses can add up to a considerable While the load profile over time and the future
amount, exceeding the initial price by several price evolution of energy is not known exactly,
times. the use of trend line values can give good
estimates of the total cost of the losses.
When comparing two different types of
transformers, one should take into account the 2.4.3 Economic analysis of loss
total cost during the lifespan of the transformer, reduction
in other words, the ‘Total Cost of Ownership’ The energy efficiencies of distribution
(TCO). transformers range from around 94% for a small
A-A’ transformer, to more than 99% for an
TCO consists of several components: purchase amorphous-core distribution transformer with
price, installation cost, value of the energy HD 428 C-level losses (‘C-AMDT’), the most
losses and maintenance costs over its life, efficient type available.
and decommissioning costs. Except for PCB
cooled transformers, the last two elements are On average, the loss in a distribution transformer
relatively insensitive to the type and design of the is around 1.5 { 2.0% of the energy transferred.
transformer, and are consequently seldom taken Considering that transformers are working
into account. Purchase price and energy losses are continuously, significant losses can build up. By
the two key factors. When different technologies choosing the right technology, these losses can be
are compared, e.g. dry-type or oil-immersed, reduced by up to 80%.
installation costs can be considerably different,
and should be taken into account. As the tables below show, the pay-back period for
investing in high efficiency transformers is relatively
To evaluate the total cost of losses, their Net short, certainly regarding their long life span (25 -
Present Value at the moment of purchase needs 30 years). Please see Table 2.4.1 and 2.4.2.
to be calculated, to put them into the same
perspective as the purchase price. This is done 1. Changing an industrial 1600 KVA transformer
by calculating the Total Capitalized Cost of the from a A-A’ type to a C-C’ type will pay back in
losses, TCCloss, calculated from the estimated 1.4 years. The Internal Rate of Return (IRR) for
average cost per kWh (C), the cost of capital (r) investments in efficient transformers is consistently
and the life time of the transformer in years (n), above 10% and sometimes as high as 70%.
where Eloss was defined.
2. Considering the low risk of the investment, this
Eloss[kW] = (P0 + Pk * I2 ) * 8760 should make efficient transformers attractive to
both industrial companies and grid operators. But

Energy Efficient Transformers 17


Section 2

in the case of grid operators, there is at present no only factor, as they have to be covered by the grid
incentive to invest. Loss reduction then remains the operators, as is the case in most countries.

Energy saved IRR (% -25


Efficiency class Efficiency (%) Payback
(kWh / year) years)
A-A’ 94.71 996 - -
C-C’ 96.46 2 277 5.0 20
A-AMDT 98.71 2 310 7.7 12
C-AMDT 98.77 - 8.6 11
Table 2.4.2: Energy saving & return for a high efficiency 100 kVA transformer
* Leonardo Energy Transformers – Leonardo-energy.org

Energy saved IRR (% -25


Efficiency class Efficiency (%) Payback
(kWh / year) years)
A-A’ 98.04 3 143 - -
C-C’ 98.64 6 833 2.8 36
A-AMDT 99.35 7 085 5.7 17
C-AMDT 99.40 - 6.6 15
Table 2.4.3: Energy saving & return for a high efficiency 1600 kVA transformer
* Leonardo Energy Transformers – Leonardo-energy.org

2.4.4 Externalities
mix can be estimated at 5 US Cents / kWh3. A
As shown in the previous section, a higher
saving of 200 TWh/year represents, in monetary
efficiency benefits the owner of the transformer,
equivalent, a reduction of 10 billion US$ in
reducing TCO. On a larger scale, those cost
environmental cost.
savings are beneficial for the whole economy,
enabling the lower cost of production to result in
2.4.5 Non-technical losses
lower tariffs to customers.
Distribution losses are calculated as the difference
Each kWh also has an external cost, i.e. the between electricity paid by clients and energy
environmental and health costs to society that supplied by a medium voltage transformer to the
are not fully reflected in the price of electricity. distribution network. Losses can be technical, or
These externalities originate from the various non-technical. Non-technical losses can be:
types of emissions resulting from the combustion
of fossil fuel. Apart from CO2, the main • Electricity theft
offenders are SO2 and NOx which contribute • Invoicing errors
to the acidification of the environment. These • Bankruptcies of clients
pollutants have long range transborder effects • Measurement errors
and have therefore become a major concern for
most European countries. From table 2.4.3, the Electricity theft is a social problem, and hard
average external cost for the world’s generation to solve, since it addresses a large portion of

Energy Efficient Transformers 18


Section 2

the population in certain countries. It is not care should be taken in interpreting loss figures to
the subject of this paper, which addresses distinguish between technical and non-technical
technological solutions to increase efficiency. But losses.

External Cost Part of generation Contribution


Fuel
US$ / kWh % US$ / kWh
Coal 8.3 39 3.2
Oil 11.6 8 0.9
Gas 3.8 17 0.6
Nuclear 1.0 17 0.2
Hydro 0.3 17 0.1
Renewable 0.3 – 2.9 2 0.0
Total 100 5.0

Table 2.4.4: The external cost of electricity for the world generation mix, based on 63 studies
* Leonardo Energy Transformers – Leonardo-energy.org

Energy Efficient Transformers 19


Section 3

Energy Efficient Transformers 20


Section 3

Requirements of the Technology


Intervention
3.1 New Technology Awareness 3.1.2. Future Developments
and Acceptance Research and development on magnetic steels
3.1.1 New Developments in is vigorously pursued world-wide. The licensing
Transformer Materials of new processes has been extremely prevalent
in this sector for many years. Distribution
1) Domain Refined Steels transformers appear to represent a poor return
A further reduction of losses is achieved by on recent development effort, with the possible
domain limitation. Domain refined steels are exception of amorphous iron, because of the
produced mainly by proprietary laser etching competitive nature of the market. However new
processes. Together with grain-oriented steel, magnetic steel developments also benefit from
they offer material with specific losses ranging other applications, notably electric motors and
from about 0.85-1.75W/kg at 1.7T/50Hz for small transformers.
distribution transformer manufacture.
Future emphasis on energy efficiency and
Commercially available domain-refined steel environmental impact could change this picture.
is typically 0.23mm thick. Together with Among areas of interest are:
amorphous iron, see below, it has a market share • the ending of certain patents on amorphous
in Europe for transformer manufacture of about iron processes, which could encourage other
10%. producers to enter the market
• the adoption of the design of amorphous iron
2) Amorphous Iron transformers to European practice (i.e. use
Distribution transformers built with amorphous a three legged Evans-core design for Dy-
iron cores can have more than 70% reduction in connected transformers, resulting in reduced
no-load losses compared to the best conventional length, cost and noise)
designs. There is only one known producer • mechanical or thermal processes other than
world-wide of amorphous iron material suitable laser etching for domain limitation
for distribution transformer manufacture. • the use of thinner steels. Magnetic steels with
Amorphous iron became commercially available gauges as low as 0.05mm are being offered
in the early 1980s. It is reported to have been in narrow strip for small transformers and
used in the construction of several hundred coils. For larger transformers 0.18mm steel
thousand distribution transformers in the US, is available, but both raw material and core
Japan, India and China. European experience of fabrication costs rise very rapidly as the gauge
manufacturing and installing amorphous iron is reduced.
distribution transformers in the EU has been
very limited. This is partly due to network design 3.1.3 Superconducting Transformers
characteristics which differ from US and Japanese A number of superconducting distribution
practice. However a very large (1,600kVA) transformers have been built. One company
amorphous iron three-phase distribution has developed a nitrogen-cooled 630kVA high
transformer has recently been built and installed temperature superconductor (HTS) transformer,
in the EU. which was installed in the Swiss electricity

Energy Efficient Transformers 21


Section 3

supply network in 1997. This is a single-phase Emissions data suggested by the International
transformer, and considerable engineering Institute for Energy Conservation (IIEC) for
problems are reported in producing three-phase Europe is 0.4kg CO2/kWh. Electrical energy
versions. savings of 22.3TWh will provide emissions
savings of 8.9 million tons of CO2. The
It is widely agreed that superconductivity will
European Union is committed to a reduction of
always remain much more expensive for power
8 per cent on 1990 levels (266 million tons) by
distribution transformers than conventional
2008-2012.
technology. The most promising areas appear
to be in specialist applications, particularly
traction transformers, where increasingly large The potential savings from energy-efficient
transformers are required for train motors in distrubution transformers could reach 7.3 TWh.
railway networks. This is approximately over 1% of the European
commitment.
3.1.4 Technology Sources
Power systems transformers are very specialized To put the overall potential saving of 22.3TWh
products, and R&D activities outside the major into perspective, this is equivalent to the annual
transformer manufacturing companies are energy use of over 5.1 million homes or the
limited. Even here most effort is centered on electricity produced by three of the largest coal
practical product development, together with the burning power stations in Europe.
testing and evaluation of new materials. Only
a few distribution transformer manufacturers Distribution transformers have not yet been the
in Europe have significant fundamental R&D focus of energy saving measures and could, if
capabilities dedicated to transformer research. developed, contribute significantly to European
targets for reduction.
Much of the recent work on the steels used
in distribution transformers has originated 3.3 Characterization of the Utility
from Japan and the United States, although Market
European companies have a world reputation
Utility markets account for approximately
for the steels and non-ferrous alloys used in
half the installed transformer capacity in
smaller transformers. Some of the technology for
Europe. Throughout Europe, the purchasing of
adding value to conductors and coils, such as the
transformers seems to be reasonably standardized,
continuous cold rolling of narrow strip, has also
with the utilities having open tender practices
been imported. However there are a number of
in line with European Purchasing Directives.
centers of excellence in Europe, with a capability
In almost all cases, losses (iron and copper) are
for R&D and demonstration of distribution
factored into the specification, with minimum
transformers or component materials. Many
standards in line with internationally accepted
European universities have a capability in
standards. However, the specifications in
magnetic materials within their electrical
each country differ in relation to the load
engineering or materials departments.
characteristics (rural/urban), the network being
served or the requirements for low noise emission
3.2 Contribution to Energy
(e.g. in German urban areas).
Efficiency and Global Warming
Goals

Energy Efficient Transformers 22


Section 3

of transformer efficiency across Europe, the


Selection of the supplier is usually made on the
specification would have to be formally adopted
“first cost” principle, i.e. the supplier providing
by CENELEC as a standard and compliance (via
the lowest cost offer that meets the specification
the provisions of any national standard) would
wins the business. Few exceptions are made where
have to be compulsory.
a supplier offers a more efficient transformer
(i.e. lower life-time cost), but at a slightly higher
price. The one exception to this is the Nordic Despite this apparent standardization, national
countries, where the efficiency of the transformer standards can vary significantly. Each country
in specific applications is given a high priority, has its own specific issues related to distribution
with the specification giving the efficiency of the system strength, capacity considerations, etc.
transformer a very high rating. Other differences result from variations in
particular circumstances within countries. In
In almost all EU countries, first cost is the driving France, the majority of generation is by nuclear
principle. Where the utility is state owned, power station. The marginal cost of generation is
limitations on capital expenditure are paramount therefore very low and the environmental impact
to assist in meeting the ever tightening is negligible because emissions are minimal.
budgets brought about by the strict monetary French utilities are therefore under no pressure to
requirements associated with the Û. Where the purchase energy-efficient transformers and lowest
utility is in private ownership, the availability of first cost transformers are specified as standard.
capital for efficient transformer purchases always In Germany, where many transformers are based
competes against more attractive (i.e. quicker in the centre of residential areas, there are very
payback) investments that can be made by the stringent noise regulations. There are also often
utility in other areas. In both cases, the lack of size restrictions.
interest in efficient transformers is compounded
by the electricity suppliers’ inability to pass the Harmonizing the East/West supply systems and
cost of any losses on to the consumer, hence standardizing the equipment are also causing
removing any incentive to overall system, and problems.
consequentially transformer, performance.
The situation is further confused with the
3.4 National/International Policies regulators in each country setting varying goals
and Initiatives for the utility companies. In almost all cases,
continuity of supply is the key factor. However,
Across Europe, transformers are manufactured to
variations on other priorities are profuse and
individual national standards. These are broadly
cover cost of electricity to the customer, voltage
compatible with the European specification,
tolerances, safety, noise, overall environmental
Harmonization Document 428. This in turn
impact of the system, etc.
is based on the International Electro-technical
Commission World Standard IEC60076.
There appears to be little overall attempt
Through this harmonization of standards, a
to encourage the uptake of energy-efficient
mechanism is in place for communicating and
transformers by any national government or
enforcing more rigorous requirements for energy
regulator. In the UK, the regulator includes an
efficiency. However at present, compliance with
efficiency incentive in the pricing formula for
HD428 is purely voluntary. For this mechanism
supply, but this is marginal compared with other
to be effective in increasing the overall level

Energy Efficient Transformers 23


Section 3

considerations. The following example describes Harmonizing the East/West supply systems and
how one electricity supply company assessed the standardizing the equipment are also causing
value of fitting amorphous core transformers into problems.
its network.
The situation is further confused with the
3.5 National/International Policies regulators in each country setting varying goals
and Initiatives for the utility companies. In almost all cases,
continuity of supply is the key factor. However,
Across Europe, transformers are manufactured to
variations on other priorities are profuse and
individual national standards. These are broadly
cover cost of electricity to the customer, voltage
compatible with the European specification,
tolerances, safety, noise, overall environmental
Harmonization Document 428. This in turn
impact of the system, etc.
is based on the International Electro-technical
Commission World Standard IEC60076.
There appears to be little overall attempt
Through this harmonization of standards, a
to encourage the uptake of energy-efficient
mechanism is in place for communicating and
transformers by any national government or
enforcing more rigorous requirements for energy
regulator. In the UK, the regulator includes an
efficiency. However at present, compliance with
efficiency incentive in the pricing formula for
HD428 is purely voluntary. For this mechanism
supply, but this is marginal compared with other
to be effective in increasing the overall level
considerations.
of transformer efficiency across Europe, the
specification would have to be formally adopted
3.6 Potential Mechanisms for Change
by CENELEC as a standard and compliance (via
the provisions of any national standard) would There appears to be several potential mechanisms
have to be compulsory. that could change the buying behavior of
transformer purchasers. Each potential
Despite this apparent standardization, national
mechanism is briefly examined below.
standards can vary significantly. Each country
has its own specific issues related to distribution 3.6.1 No Change Scenario
system strength, capacity considerations, etc. It is possible that no action at the EU level will be
Other differences result from variations in required, as national governments begin to realize
particular circumstances within countries. In the implications of international commitments
France, the majority of generation is by nuclear on CO2 and act at national level to improve the
power station. The marginal cost of generation is efficiency of transformers purchased. However,
therefore very low and the environmental impact realistically this is unlikely to occur, due to the
is negligible because emissions are minimal. long term nature of savings from transformers
French utilities are therefore under no pressure to and the complex nature of specification and the
purchase energy-efficient transformers and lowest purchasing cycle. National governments are much
first cost transformers are specified as standard. more likely to concentrate on simpler targets, e.g.
In Germany, where many transformers are based improvements in the performance of domestic
in the centre of residential areas, there are very appliances, etc.
stringent noise regulations. There are also often
size restrictions.

Energy Efficient Transformers 24


Section 3

3.6.2 Enforceable Minimum Standards transformers is the requirement of many


Discussions have already taken place between purchasers for the lowest first cost. If some
EC DGXVII, COTREL and EURELECTRIC financial mechanism could be introduced,
to discuss the possibility of voluntary agreements that would make the purchase of efficient
or a European Directive to initiate reduced transformers more attractive, it is likely to have a
losses from distribution transformers through a major impact on the marketplace. Such financial
minimum standard. incentives appear to fall into three categories:
If a mechanism was in place to define efficient
transformers (e.g. transformer labels described
A minimum standard of sorts already exists in
below), it would be possible to offer rebates
the Harmonization Document 428 (standard
on purchases of higher efficiency units, hence
for three-phase oil immersed distribution
lowering the purchase cost differential between
transformers, 50 Hz, from 50kVA to 2500 kVA
the more and less efficient units.
with highest voltage for equipment not exceeding
36kVA). This standard could be made more Unfortunately, the rebate would be extremely
prescriptive and specify improved minimum expensive, given the number of transformers
losses for all types of transformer. purchased across the EU annually. Further, such a
scheme could only be sustained for a short period
Such a standard could then be made mandatory and following withdrawal, the marketplace would
through an EU Directive. almost certainly revert to the original situation
with no lasting market transformation.
Unfortunately, such an approach is likely to be
strongly resisted at national level, due to the Changing national taxation systems to make
specific needs of each national distribution system the capitalization of transformers more
and local political considerations. Further, the attractive, e.g. shortening the allowable assets
imposition of overall standards for efficiency write- off period, is likely to have a major
higher than those already in force would cause impact on the purchases made by utility buyers
problem s, due to the variations in demand (other buyers are unlikely to purchase enough
profiles from the various end use applications, e.g. transformers for this to have any significant
rural/urban uses. impact relative to other considerations). However,
this would have to be made a national issue,
An alternative approach would be for the EU as the EU is specifically excluded from direct
to place obligatory requirements on national interference with national taxation issues. As
regulators to include efficiency as one of their such, it is unlikely that individual member states
key elements when forming regulatory policy. It would adopt such a policy, due to the complex
is unlikely that such an approach would work as, requirements in drafting the required legislation
without specific guidelines, regulators are likely and policing claims under the system. Increasing
to simply pay lip-service to the issue. Further, the responsibility for cost of losses. Obviously,
preparation of specific guidelines may impose financial costs associated with losses from
on the principles of subsidiarity and would be transformers owned by end users are already
difficult to draft in any case. borne by the end user. However, losses accruing
from transformers owned by utilities are currently
3.6.3 Financial Incentives almost universally transferred to the end user as
The major cause of purchases of “less efficient” part of the cost of electricity.

Energy Efficient Transformers 25


Section 3

This situation is difficult to change where the cost reduction from the investment are shared
utility is state owned. However, where the utility with the consumers.
is privatized, there is an opportunity to use this • Allow some carryover of measurable
“cost of losses” as an incentive to improve the efficiency gains, so that investing in energy
system. At present, if the utility improves the efficiency becomes more attractive for the
efficiency of the system, then the amount of “cost network companies.
of losses” is adjusted accordingly, hence the utility
makes little improvement in profit. 2. Capital-intensive investments are very sensitive
to future changes, e.g. in the regulatory regime.
A realignment of the pricing structure , to allow This discourages investments in efficiency
a fixed amount of “cost for losses” to be passed improvements.
to the consumer, with the savings from any • Give special incentives to promote capital-
reduction in losses split between the consumer intensive energy efficiency measures. Create
and the utility (say on a 50:50 basis), would a stable, long term system of regulation.
improve the business case for examining lifetime
costing. Such a system would allow investments 3. The regulatory framework tends to concentrate
in efficient transformers to be more competitive on cost savings in the short term.
against other demands on the capital budgets
of the utilities. However, this is again a national These do not encourage companies to take the
issue, with the individual pricing regimes coming life cycle costs of equipment into
under the control of the national regulators. account.

3.6.4 Liberalization 4. Energy losses are calculated without


The costs and profits of network companies consideration of external costs.
in a liberalized electricity market are in most • Take the true cost of network losses into
countries limited by regulation or regulated account.
tariffs. This may inhibit investments in energy
efficiency measures, for instance high efficiency 3.6.5 Labelling system
transformers. The risk is that companies are more Lack of knowledge is a significant barrier to the
focused on short term cost savings and fail to purchase of energy- efficient transformers. This is
invest in systems that would save more in the particularly true of large energy users, where there
long run. is a desire to use efficient transformers, but not
the technical ability to specify them effectively.
If the correct regulatory framework is developed,
investments in improving the efficiency of a A labeling system that indicated the efficiency of
network can also be stimulated under market transformers under specific load profiles would
regulation. The following is a short description of assist this group considerably, and is likely to
the 4 main barriers and possible remedies. cause a significant movement in the market.
While there are obvious difficulties in creating
1. Most models of regulation rely on a partial a labeling system for transformers, given the
redistribution of savings to consumers. variability of losses depending upon application,
This discourages companies from making it is possible to develop a labeling system that
investments for efficiency improvements, since provides the user with appropriate guidance in

Energy Efficient Transformers 26


Section 3

most instances. Such a system is currently under level and reviewing them is less diffcult
development for electric motors, a product with and less time consuming. Consequently, it is a
similar difficulties in efficiency definition. much more °exible system.

The introduction of a labeling system also The main difficulty to overcome in voluntary
provides a framework from which future programs is reaching a reasonable degree of
minimum standards may be derived (if deemed participation often taking a few years.
appropriate). The framework could also be used
for financial incentives, should they be required at The goal of a voluntary program should be to
a national level. make the incentives and the image so important
that it becomes difficult for companies to ignore.
3.6.5 Labelling system High image value, a meaningful brand presence,
Lack of knowledge is a significant barrier to the and a strong policy context for instance make the
purchase of energy- efficient transformers. This is Japanese ‘Toprunner’ program a good example of
particularly true of large energy users, where there an effective scheme.
is a desire to use efficient transformers, but not
the technical ability to specify them effectively. 3.7 International Perspective
3.7.1 US and Canada
A labeling system that indicated the efficiency of
The US DOE is in the process of implementing
transformers under specific load profiles would
a test standard for distribution transformers,
assist this group considerably, and is likely to
following a report from Oak Ridge that
cause a significant movement in the market.
supports a DOE determination that minimum
While there are obvious difficulties in creating
performance requirements for distribution
a labeling system for transformers, given the
transformers can be justified.
variability of losses depending upon application,
it is possible to develop a labeling system that
provides the user with appropriate guidance in Following on from the test standard, formal analysis
most instances. Such a system is currently under and legislation will be implemented. The standard
development for electric motors, a product with is not expected to be issued until after 2000.
similar difficulties in efficiency definition.
The transformer industry opposes the prospect
The introduction of a labeling system also of a mandatory minimum and would prefer a
provides a framework from which future voluntary standard (NEMA TP1).
minimum standards may be derived (if deemed
appropriate). The framework could also be used The Oak Ridge study concluded that the TP1
for financial incentives, should they be required at levels of energy efficiency do not meet the DOE
a national level. criteria. A US ‘Energy Star’ program which
provides energy efficiency labeling, currently
3.6.6 Voluntary schemes promotes the TP1 levels of energy efficiency.
Voluntary schemes do not have the disadvantages Canada is in the midst of consultation to
of a mandatory minimum standard. implement mandatory levels equivalent to
TP1, with a view to revising them once the US
The targets can often be set at a more ambitious legislation has been implemented.

Energy Efficient Transformers 27


Section 3

3.7.2 China
transformers which do not meet minimum
Shanghai Zhixin Electrical Industry Co Ltd. efficiency levels. The standards are defined for
have been developing a relationship with GE oil-filled distribution transformers between 10
under a license agreement to produce amorphous and 2 500 KVA and for dry-type distribution
core transformers since June 1997. The contract transformers between 15 and 2 500 KVA, both
was signed in February 1998. Currently they at 50% load. The MEPS are mandated by
are importing most of the components and legislation, effective 1 October 2004. Under the
assembling them in Shanghai. A core winding stimulus of the National Greenhouse Strategy
machine has been purchased, to be installed in and thanks to the strong will of the parties
mid-July 1999. involved, the creation of the MEPS passed
smoothly. The field study to define the scope was
Average transformer size is 400kVA. Shanghai started in 2000, with the minimum standards
Urban Power Distribution Bureau have installed written in 2002.
116 sets of amorphous core transformers, saved
770,000kWh power per year, worth about The second track, currently under development,
27,900,000 RMB (Û3.2 million). is the creation of further energy efficiency
performance standards resulting in a scheme for
Information from the company identifies the voluntary ‘high efficiency’ labeling.
no load losses as 20% of those in a conventional
transformer. The incremental cost is 30% over New Zealand follows the Australian regulation
that of a conventional transformer. They have for distribution transformers.
a target to reduce this to 20% when more
components are manufactured in China. 3.7.4 Europe
Currently the estimated payback is 2.5 years. CENELEC has defined efficiency standards for
distribution transformers in the range from 50
Transformer sales in China are estimated to be to 2500 KVA. HD428 stipulates A, B and C
350,000 per year. categories for load and no-load losses. HD538
advises a maximum for the load and no-load
The company has a production target of 2,000/ losses of dry type transformers. The efficiency
year, which will rise to 3,000/year, and can see ranges defined by these standards are relatively
no technical barriers to more transformers being wide. The minimum efficiency in the highest
manufactured in China if the market can be category (CC’) is still far below the efficiency
stimulated. The main barrier to uptake is the of the best in class and far below the ‘5-star’
increased cost over the conventional product. transformer defined by the Indian Bureau of
Energy Efficiency. CENELEC is currently
3.7.3 Australia and New Zealand defining new efficiency categories with lower
The Australian program for energy efficiency in losses.
distribution transformers, executed by the National
Appliance and Equipment Energy Efficiency In 1999, a Thermie project of the European
Committee (NAEEEC), works on two levels. Union assessed the total energy losses in
distribution transformers. The savings potential
First, there is the Minimum Energy Performance in the 15 countries of the EU was estimated to be
Standard (MEPS), a regulation that bans 22 TWh.

Energy Efficient Transformers 28


Section 3

A mandatory minimum efficiency standard The minimum standard is not based on the
for distribution transformers is not expected average efficiency level of products currently
to be introduced in the near future. This is available, but on the highest efficiency level
disappointing, given the availability of world- achievable. However, the program does not
class transformer technology in Europe. impose this level immediately, but sets a target
date by which this efficiency level must be
3.7.5 India reached. A manufacturer’s product range must,
In India, the Bureau of Energy Efficiency (BEE) on average, meet the requirement. It is not
has developed a 5-star classification scheme for applied to individual products.
distribution transformers in the range from
25 to 200 KVA. The scheme is a co-operative 3.7.7 Mexico
venture between public and private organizations
As in Australia, the Mexican standard includes
that issues rules and recommendations under
voluntary and mandatory elements. The Normas
the statutory powers vested with it. The 5-star
Oficiales Mexicanas (NOM) define minimum
program stipulates a lower and a higher limit for
efficiency performance standards for transformers
the total losses in transformers, at 50% load. The
in the range from 5 to 500 KVA, and a
scheme recommends replacing transformers with
compulsory test procedure for determining this
higher star rated units. The 5-star unit represents
performance. For each power category, maximum
world class technology, while 3-stars is recom-
load and no-load losses are imposed.
mended as a minimum, and already followed by
many utilities. India historically has a rather poor
performance in transformer energy efficiency, but
this 5-star program could become an important
driver for change.

3.7.6 Japan
In Japan, transformers are a part of the
‘Toprunner Program’ which either defines the
efficiency for various categories of a product
type, or uses a formula to calculate minimum
efficiency. This program, which covers 18
different categories of appliances, has some
major differences compared to other minimum
efficiency performance programs.

Energy Efficient Transformers 29


Section 4

Energy Efficient Transformers 30


Section 4

Analysis, Recommendations, and


Action Plans
4.1 Use of High-efficiency An alternative way of defining “energy-efficient
Transformers transformers” would be to by considering the
energy-efficiency levels of the transformers
4.1.1 Achievable Loss Levels
sold on the market. This is be analogous to the
The HD428 C-C’ loss level for oil-filled concept of the US “energy star” transformer
distribution transformers may, as mentioned program.
before, be regarded as providing a high practical
standard of energy efficiency for a distribution Here transformers with energy efficiency equal
transformer. to or above that of the most efficient 35% being
currently sold meet the requirement for Energy
There is no internationally agreed definition of Star rating.
an “energy-efficient” transformer. It is proposed
to use the term “energy-efficient” transformer for Another way to define “energy-efficient
the following transformers: transformers” would be the application of special
windings, advanced steels or amorphous iron. An
l oil-filled transformers: range C-C’ (HD428.1) argument against this definition is that there are
and D-E’ (HD428.3) a number of practical considerations involved in
deciding on the optimum choice of transformer
l dry-type transformers up to and including for installation into a network.
24kV: 20% lower than specified in HD538.1.
HD538 mentions one list of preferred values, Moreover, the energy loss level is the key
but explicitly allows the possibility for national performance indicator of each transformer design
standards to specify a second series with load with respect to energy efficiency and would
and/or no-load losses at least 15% lower. Some consequently the fairest benchmark.
transformer manufacturers offer dry-type
transformers in normal and low-loss versions As expected, the loss level of “energy-efficient
l dry-type transformers 36kV: 20% better than transformers” as defined above does not represent
specified in HD538.2, analogous to the previous the maximum efficiency which is technically
category. possible. Both load and no-load losses may be
reduced significantly.
An important reason for choosing the values
suggested above is the fact that these levels are Load losses may be reduced beyond the levels
entirely feasible within the current “state of the mentioned above by following technical design
art” of nearly all transformer manufacturers. In measures:
the remainder of this report, the class of energy-
efficient transformers is often referred to as C-C’, • increasing the conductor section of the
as the oil-filled transformers form the majority of transformer windings, which reduces
the transformers, and, among these, units up to conductor resistance and thus load losses. To
24kV are the most numerous. a lesser extent, the application of ribbon or
sheet conductors also contributes to reducing
load losses. The disadvantage of increasing the

Energy Efficient Transformers 31


Section 4

conductor section is the higher investment sound but uneconomic. The number of
cost. Another disadvantage is the larger size extremely energy-efficient transformers (beyond
of the transformer, which may exceed the the C-C’ level) operating in Europe is quite low,
maximum sizes specified by the purchaser. compared with the United States. We estimate
This is partially offset by the reduction of heat that about 200 amorphous distribution iron
production in the transformer, which lowers transformers have so far been installed, many
the need for cooling. of which are very small, and probably a slightly
• application of superconductor material for larger number using laser-etched domain-refined
the windings, eliminating load losses. This steel. The amorphous iron installations we have
technology is not yet mature and still very identified are as follows:
expensive. The main application will lie in • yearly peak load: the highest load of the
larger transformers. transformer as a percentage of its rated power.
This load is only present for a small part of the
Another drawback of superconducting year.
transformers is the inability to withstand short- • running time: the ratio of energy transmitted
circuit currents of the level that are common during a year [kWh] and the yearly peak load
in medium-voltage networks. These problems [kW] - physically, this figure indicates how
need to be solved before the superconducting much time it would take to transmit the yearly
transformer will become a viable option. energy at a power equal to the yearly peak
No-load losses may be reduced beyond the levels load. A low value indicates strong fluctuations
mentioned above by following technical design of the load, a high value a relatively constant
measures: load. The average transformer load is the yearly
• increasing the core section, which reduces the peak load, multiplied by the running time over
magnetic field in the transformer core and thus 8760 hours.
the no-load losses. However, this results in • loss time: the ratio of the yearly energy loss
higher investment cost. Another disadvantage [kWh] and the maximum losses occurring in
is the larger size of the transformer, which may a year [kW] - this figure indicates how much
exceed the maximum sizes specified by the time it would take for the transformer to lose
purchaser. the yearly energy loss when loaded at the
• application of high-grade modern transformer maximum load occurring in the year.
core steel. It should be noted that the C-C’
level can be reached without applying laser- The data above result into the following data for
etched transformer steel, the latter being an A-A’ and a CC’ transformer with an “average”
regularly used in large transformers. load profile as indicated above:
• reduction of the thickness of the core
laminations. The no-load (iron) losses account for 95% of the
• application of amorphous core material. The yearly losses in the case of a 100kVA transformer,
saving potential with respect to no-load losses and 66% of the no-load losses in a 1,600kVA
is high, as shown in the table below, where the transformer.
amorphous transformer is compared to the
conventional types according to HD428. For very lightly loaded transformers, the
efficiency falls rapidly. There are several reasons
Energy-efficient transformers are generally why some transformers are so lightly loaded.
regarded by European customers as technically Often a limited number of transformer types

Energy Efficient Transformers 32


Section 4

used by a utility (advantages of lower stock) is the electrical distance to the feeding point and the
the cause, or allowing for a load increase. Usually, load situation. A special case is the gradual change
the distribution network is dimensioned with (between 1989 and 2004) of the network voltage
certain expectations of load growth, in order to within Europe from 220V or 240V to 230V as
postpone upgrading of the infrastructure as long defined in IEC60038. In some cases, the increase
as possible. A final factor is the usual technical from 220V to 230V is realized by increasing the
practice to apply safety margins to electrical voltage level in the medium-voltage network,
equipment. This is good for the load losses, but which leads to increased losses in the distribution
increases the no-load losses. transformers.

The extremely low loads encountered at some On the other hand, the decrease from 240V to
transformers seem to suggest the need for smaller 230V may be achieved by decreasing the voltage
distribution transformer sizes, or cores with level in the medium-voltage network, which leads
extremely low losses. to lower losses in the distribution transformers

Although the figures used are based on empirical • Operating temperature of the transformer.
rules validated by measurements, there is a wide Conductor losses slightly increase with the
spread in the average transformer loading and the operating temperature of the transformer.
running time. Although some utilities keep track • The loss levels of individual transformers
of the maximum loads of transformers, there are are, therefore, always specified for a defined
no representative transformer load data available operating temperature
for the European Union. • Production deviations of the transformer.
This is a quality assurance aspect, which will
4.1.2 Deviations from the standard loss normally not yield large deviations from the
values contracted loss values
Apart from the efficiency class and the load • Ageing of the transformer. Older transformers
profile, many other factors may influence trans- may deteriorate in several modes, one of
former losses: which is a loss increase. Normally, this effect is
neglected. There are, however, some concerns
• medium-voltage (MV) network voltage - about ageing of amorphous cores
the core (iron) losses are dependent on the - Poor power quality. The presence of non-linear
network voltage. A higher network voltage loads in the network will lead to harmonic
leads to higher core (iron) losses. For instance, current components in the transformer.
5% increase of the network voltage may cause These harmonic currents tend to heat the
10-20% higher core losses, depending on the transformer, but normally the transformer design
type of core material and the design of the allows for some harmonic contents of the load
transformer. current. Normally, this effect is not taken into
account, except in industrial or comparable
The loss levels of individual transformers are, installations with many distorting loads.
therefore, always specified for a defined network
voltage. For an individual transformer the effect Accounting for these factors for a network
can easily be measured. In an electrical network, would require a detailed knowledge of operating
the voltage at each substation varies according to conditions, Usually, efficiency class and

Energy Efficient Transformers 33


Section 4

transformer loading are the two dominant factors, For the specified load loss of a transformer, the
the other factors are not taken into account when purchaser can assign a cost figure per kW of loss
assessing transformer losses. representing the capitalized value (net present
value) of the load losses over the lifetime of the
4.1.3 Loss Evaluation transformer or a shorter time scale e.g. 5 or 10
A transformer purchaser aims to buy the cheapest years. This cost figure is based on the expected
transformer, i.e. with the lowest total cost of transformer load over time, the average cost
Ownership, which complies with the require- per kWh and the interest rate chosen by the
ments for a given application. The total cost of purchaser.
ownership of a transformer consists of several
components, including purchase price, the value Similarly, for the no-load loss of a transformer,
of energy losses, maintenance and repair costs the purchaser can assign a cost figure per kW of
over the lifetime, and decommissioning cost. no-load loss representing the capitalized value of
the no-load losses. This cost figure is also based
The purchase price and the energy losses are the on the average cost per kWh and the interest rate
two key factors for comparison of the different chosen by the purchaser.
transformers. Installation, maintenance, repair
and decommission costs are seldom taken into As nearly all transformers are connected to the
account for choosing between transformers as grid for 100% of the time, and the no-load losses
they are relatively insensitive to transformer are independent on the load, the load curve is not
design. relevant. The average cost per kWh will tend to
be lower than for the load losses, as the latter will
In cases where transformers of different tend to coincide with peak loads, at which time
technologies are compared, e.g. dry-type and oil- energy is very expensive.
immersed, installation costs (e.g. fire protection,
oil containment provisions) will be considerably Since different transformer users have different
different and do need to be taken into account. operating costs and cost of capital assumptions,
When comparing two transformers with different the Total Cost of Ownership (TCO), mentioned
purchase prices and/or different losses, one must section 2.4.2, is distinct for every user. Thus,
take into account that the purchase price is paid TCO of a transformer can be further simplified
at the moment of purchase, while the cost of and expressed as the sum of the purchase price
losses come into effect during the lifetime of the (Ct), the cost of no-load losses and the cost of the
transformer. load losses, or as a formula:
TCO = Ct + A x Po + B x Pk
Usually the costs are converted to the moment
of purchase by assigning capital values. When where A represents the assigned cost of no-load
transformers are compared with respect to energy losses per watt, Po the value of the no-load losses
losses, the process is called loss evaluation. per watt, B the assigned cost of load losses per
In the basic process of loss evaluation, three watt and Pk the value of the load losses per watt.
transformer figures are needed: This formula can also be found in the HD428
• purchase price and HD538.
• load loss
• no-load loss It is obvious that there is a significant discrepancy

Energy Efficient Transformers 34


Section 4

between the cheapest transformer at purchase and evaluation values. It is then usual to select one
the cheapest transformer in the long term. Even category e.g. C-C’ as the most appropriate, and
the expensive amorphous transformer may be the omit the tedious evaluation process by purchasing
cheapest option. the cheapest C-C’ compliant transformer.

The formula is simple, but the choice of the It can be concluded that the efficiency of
factors A and B is very complicated. Medium- transformers purchased is, directly or indirectly,
size and large utilities use standard values for loss controlled by the choice of loss evaluation figures:
evaluation, based on average values for energy - if high loss evaluation figures A and B are used,
cost and loads. energy-efficient transformers tend to be favored.

Usually, the loss evaluation figures A and B are A and/or B will be higher if a value is assigned
submitted to the transformer manufacturers in to energy saving, an allowance is made for taxes
the request for quotation. They can in turn start on usage of natural resources. A low interest rate
the complicated process of transformer design, to will yield high A and B values, by valuing future
obtain a transformer design which performs best energy savings to a greater extent
using the same formula. The result of this open • low loss evaluation figures A and B, the result
process should be the cheapest transformer, i.e. of a high rate of return required, lead to cheap
with the lowest total owning cost, optimized for a but relatively inefficient transformers
given application. • merely evaluating the purchase price will lead
to the cheapest transformers being chosen,
Drawbacks of this process are its extreme which may be very inefficient. This policy
complexity and the uncertainty of the purchaser corresponds to A and B equal to zero, and
with the exact load profiles of the transformers is regularly found with turn-key contracting
and energy prices in the future. Tariff structures firms or the project departments of utilities
are very complex. that are concerned only with direct project
costs. The chosen values for A and B are
For large transformers, above a few MVA, the also the key factor in the application of new
cost of losses are so high, that transformers are technologies.
custom-built, tailored to the loss evaluation
figures specified in the request for quotation for a
specific project.

For distribution transformers, often bought


by large batches, the process is undertaken
infrequently, e.g. once every 5 years. This yields
an optimum transformer design, which is then
kept for several years until energy prices or load
profiles have changed dramatically.

In fact, the loss levels established in HD428,


HD538 and national standards reflect established
practice of preferred designs with respect to loss

Energy Efficient Transformers 35


Section 4

4.2 Amorphous Transformers In 1975, Allied Signal developed the planar-flow


More than ever, electric utilities and industries casting method for the production of amorphous
today are searching for technologies that will alloy ribbon in continuous lengths. In this
reduce their operating costs and improve propriety manufacturing process, molten alloy is
energy savings throughout their systems. cooled at a rate of 1,000,000 deg C per second.
New transmission and distribution (T&D) This rapid solidification enables the finished alloy
technologies are now available to help utilities to retain is amorphous atomic structure.
meet these goals.
4.2.1 Amorphous Core Transformers -
With a new generation of Metglas amorphous History
metal distribution transformers (AMDTs) -- with 1967 – Produced the first amorphous metal
up to 80% lower core loss than conventional suitable for transformer application as a magnetic
transformers -- Metglas, Inc. is helping utilities material.
worldwide to achieve their efficiency objectives.
When you consider that 10% of all electricity 1975 – Allied Signal (USA) developed the
generated by utilities is lost in the transmission planar-flow casting method for the production
& distribution process, the potential savings of amorphous metal ribbons in commercial
through reductions in core loss can be significant. quantities.
Ultra-efficient transformer cores made with 1980 – First amorphous metal core transformer
Metglas amorphous metal alloy make lower core was produced.
losses possible. Amorphous metal distribution
transformers are key to improving utility 1985 – 1000 units of 25 kva pole-type and 25
economics and enhancing energy conservation units of 25 kva padmounted transformers were
efforts worldwide. installed in the United States.

1998 – Over 1.3 million amorphous core


transformers have been installed worldwide.

Melting Furnace
Reservoir

In-line In-line
Winding
Process
Nozzle Control

Casting Roll

* Hitachi Metals Website

Energy Efficient Transformers 36


Section 4

4.2.2 Amorphous Core Transformers-


TOC = Initial Purchase Price + Cost of Future
Characteristics
Energy Losses This chart illustrates that despite
• 60 to 70 percent lower No-Load Losses a higher initial cost, the use of AMDTs results
compared to silicon steel transformers in overall financial savings for utilities over the
• Approximately 60% lower exciting current life of the transformer, compared with the use of
conventional silicon steel core transformers.
4.2.3 Application is exactly the same as
Silicon steel core DT’s 4.2.5 Setting the Standard for Low
• Extreme load variation Cost Solutions
• Low load factor Amorphous Metal Distribution Transformers often
• High harmonic content loads provide the lowest price method for distribution
• Protection of the environment under the new United States Department of Energy
efficiency regulation.
4.2.4 Amorphous Metal Transformer
Purchases on a Total Owning Cost Basis Department of Energy Title 10 CFR Part 431
One method of illustrating how Amorphous Energy Conservation Program for Commercial
Metal Distribution Transformers (AMDTs) Equipment: Distribution Transformers Energy
provide economic savings is by evaluating Conservation Standards: Final Rule
on a Total Owning Cost (TOC) basis. TOC
encompasses both the initial cost of the CRGO Metglas
transformer, plus the future cost of the energy 1.00
AMDT vs. CRGO
Cost Savings of

losses over the life of the equipment. The essence 0.95


Transformer

of transformer loss evaluation is to recognize


0.90
that there is a cost of losses associated with the
distribution transformer purchase decision that 0.85
is just as important as the initial price. A user
0.80
who saves on the initial purchase price of the 50 kVA 1Ø 300 kVA 1Ø
transformer may in fact be losing money by not
properly considering the value of the energy losses Department of Energy assumes 50% transformer
over the transformer’s active life. load factor. At lower load factors, AMDT’s are
also more efficient.
CRGO Cost from DOE Core Steel Analysis
2005 - App 3A

Price Price
No load Load loss
loss cost cost

Load loss
cost
No load TOC
loss cost benefit

SiFe DTs AMDTs

Energy Efficient Transformers 37


Section 4

4.2.6 Evaluating Industrial Transformer TYPICAL TRANSFORMER CORE


Efficiency CONFIGURATIONS

Industrial Transformer Purchases on a Simple


Payback Basis Industrial and commercial
customers who own their transformers and
pay for electricity on a per unit basis can easily
calculate the operating cost of their transformers
and thus, determine how long it takes to recover
the price premium associated with the purchase
of higher-efficiency transformers. Since the Typical Single Phase-core Type
payback period for AMDTs is relatively short,
the simple payback method provides a good
approximation.

Transformer Price Premium


Payback (years)=
Annual Energy Cost Savings

Annual Energy Cost Savings=


[No Load Loss (W) + Load Loss (Averge Load)2]x8760 Typical Single Phase-shell Type
1000

5
Payback Period (Years)

US$ 0.10 k/Wh


US$ 0.075 k/WH
4

1 Typical Three Phase-5 Leg


0 10 20 30 40
AMDT Price Premium (% Base Cost)

* Data from Hitachi Metals website

A simple payback calculation demonstrates that


for a wide range of price premiums - the energy
savings result in a relatively short payback period
for AMDTs.

Energy Efficient Transformers 38


Section 4

DESIGN REQUIREMENTS

Standard Ribbon width (nominal)


3 sizes available (call for custom widths): 142 mm 170 mm 213 mm

A = Window heigh 180 mm* A * 600 mm


(in 10 mm increments
B = Window width 80 mm * B * 250 mm
(in 5 mm increments)
C = Build C = 25 mm
D = Ribbon width plus
4 mm edge cover
E = Joint build E = C*1.25 (nominal)
R = Corner radius R = 6.4 ± 1.5 mm
Weight Limits Minimum: 30 kg
Maxiumm: 225 kg
Outer Circumference < 2.5 m
Limit

SAMPLE CORE DESIGN & CALCULATIONS

Joint laps are illustrative only.


Number and spacing of joints will vary.

Energy Efficient Transformers 39


Section 4

GUARANTEED PROPERTIES
mm Inches
Ribbon Width 142 5.6
A = Window Height 203 + 3/-0 7.99 + 0.13/-0
B = Window Width 102 + 3/-0 4.02 + 0.13/-0
C = Core Build 76.0 Maximum 2.99 Maximum
D = Core + Cover Width 146.0 Maximum 5.75 Maximum
R = Window Radius 6.4 ±1.5 0.25 ±0.6
Maximum Build at Joint 95.0 mm 3.74 inches
Minimum Core Net Area 90.7 cm2 14.05 in2
TEST CONDITIONS
Frequency 50 Hz 60 Hz
Test Voltage per Turn 2.62 3.14
Maximum Core Loss 11 Watts 13 Watts
Maximum Exciting Power 112 VA 129 VA
Measurements taken without oil impregnation at nominal 1.3 Tesla and ambient temperature.
TYPICAL PROPERTIES
Invoice Weight 56 kg 123 lbs
Material: Metglas® transformer core alloy SA1
SAMPLE CALCULATIONS FOR ESTIMATING CORE WEIGHT
Density in g/cc: 7.20
Lamination factor: 84%
A B C
D (-4 mm) cm
cm cm cm
Sample Core Dimension 20.3 10.2 7.6 14.2
Core Weight (estimated) = (Lam. factor) x (Density) x [(2 x A x C x D) + (2 x B x C x D) + (3.14 x C2
x D)]/1000 = 55 kg.
*Use this formula only for checking weight to ensure your design is within weight limits.
(30 kg min., 225 kg max.). Also, be sure to check that outer perimeter is below 2.5 m.
* Data from Hitachi Metals Website

Energy Efficient Transformers 40


Section 4

4.3 Running Cool for Lower Energy accommodate longterm growth in demand for
Costs power.

Today, hundreds of utilities are benefiting from


the use of Amorphous Metal Distribution 4.4 Projected Energy Savings Using
Transformers(AMDT’s) in their power Metglas AMDTs
distribution systems. Many more utilities can In the year 2004, it was estimated that total
benefit from a strategic program of replacing energy savings for the regions listed would
conventional distribution transformers with amount to 81(TWh) of core loss reduction per
AMDT’s. This could result in annual energy year, or the equivalent of US $6.1 billion dollars
savings of approximately 27 terawatt-hours annually. The reduction in the production of
(TWh) of core losses in the U.S.A. alone. CO2, a major contributor to global warming,
These savings enable utilities to cost-effectively would be 51 million tons yearly.

Region/ Electricity Distribution Distribution Potential Potential


Country Consumption Transformer Transformer Annual Annual
2004 Core Losses Core Losses Savings Savings
(TWh)1 2004 Year 2000 with with
(TWh)2 (TWh) AMDTs AMDTs**
Year 2004 Year 2004
(TWh)3 (in millions,
US$)
USA 3974 33.8 27.0 2027 16.6
EU25 2982 25.3 20.3 1521 10.5
China 2080 17.7 14.1 1061 12.3
Japan 974 8.3 6.6 497 3.5
Russia 882 7.5 6.0 450 4.2
India 631 5.4 4.3 322 3.8
Brazil 381 3.2 2.6 194 0.2
1
EnergyInformation Agency-International Energy Outlook 2004
2
SEEDT Report EIE-05-056 and Metglas estimates
3
Based on Metglas experience
4
$0.075/kwhr Energy costs
5
Based on percentage and efficiency of thermal generation

“... new transformer core designs are emerging that use amorphous metal instead of
the traditional silicon steel. These amorphous core transformers … offer up to 80
percent lower core losses than conventional transformers”.

~ The Office of Energy Efficiency Natural Resources Canada

* Data from Hitachi Metals Website

Energy Efficient Transformers 41


Section 4

4.5 Superconducting Transformers with the consequence that I2R losses become
4.5.1 Overview essentially zero, thereby creating the potential
Transformers represent one of the oldest and for a dramatic reduction in overall losses. In
most mature elements in a power transmission ac operation, the superconductor in an HTS
and distribution network. From the point of transformer experiences a type of eddy current
electricity generation at a power plant, where loss: both the heat produced by this loss
extremely high voltages are needed to “push” large (although extremely small in comparison to the
amounts of power into the grid, to the end user energy lost in conventional materials) and heat
of electricity in a home or office, where typical conducted into the lower temperature regions
appliances operate at much lower voltages (100- of the superconducting transformer need to be
200 volts), transformers are needed to effect volt- removed through refrigeration. Even with the
age conversions. At each conversion point, energy added cost of refrigeration, HTS transformers in
is lost, primarily in the form of wasted heat from the 10 MVA and higher range are projected to
changing electrical and magnetic fields in the be substantially more efficient and less expensive
copper (coil), iron (core), tank, and supporting than their conventional counterparts.
structure. Even when the transformer is “idling,”
so-called “no-load losses” (NLL) are generated Motivation for developing superconducting
in the core. Research over the last 50 years has transformers is not based solely on economic
succeeded in reducing NLL by a factor of three considerations of lowering total owning costs
while increasing core costs by a factor of two. (initial capital cost + capitalized cost of load and
Recent substitution in distribution transformers no-load losses over the transformer’s effective
(ratings below about 100 kVA) of amorphous life). With limited new siting availability in
metals for silicon iron core material has reduced urban areas, the anticipated 2% annual growth
NLL further, but this material has not been used in power demand means that existing sites
in the cores of power transformers (ratings greater must be uprated with higher power capabilities.
than 500 kVA). When a transformer is under a Many existing sites are indoors or adjacent
loaded condition, Joule heating (I2R losses) of to buildings, which restricts the use of most
the copper coil adds considerably to the amount oil-filled transformers. The inherent dangers
of lost energy. In spite of the fact that today’s of oil-filled devices are totally eliminated by
utility power transformer loses less than 1% of application of superconducting technology where
its total rating in wasted energy, any energy saved the only coolant required is benign (nitrogen as
within this one percent represents a tremendous opposed to oil). Consequently, superconducting
potential savings over the expected lifetime of the transformers operating either with a refrigerated
transformer. coil or one cooled with liquid nitrogen pose no
fire hazards and no threat to the environment
In a conventional power transformer, load losses comparable to that posed by leaks of flammable
(LL) represent approximately 80% of total oils and toxic chemicals such as PCBs.
losses. Of this load loss, 80% are I2R losses.
The remaining 20% consists of stray and eddy Serious interest in superconducting transformers
current losses. To date, efforts to reduce load began in the early 1960s as reliable low
losses have been directed toward the latter. temperature superconductors based on Nb-Ti
Unlike copper and aluminum, superconductors and Nb3Sn became available. Analysis of the
present no resistance to the flow of dc electricity, feasibility of such LTS transformers concluded

Energy Efficient Transformers 42


Section 4

that the high refrigeration loads required to resistivity Cu-Ni matrix materials have assisted
keep the LTS materials at 4.2 K made the LTS in the reduction of ac losses. Feasibility of weight
transformers uneconomical. A major reduction reduction and higher efficiencies has been
in refrigeration costs and/or the discovery of demonstrated on smaller devices with ratings
materials that superconduct at much higher smaller than 100 kVA: single-phase 80 kVA
temperatures would be required to improve the (Alsthom), 30 kVA (Toshiba), and a three-phase
economic attractiveness of these electric power 40 kVA (Osaka University). Larger units have
applications. In the mid-1970s Westinghouse also been constructed and tested successfully. A
conducted an exhaustive design study of a single-phase 330 kVA transformer built by ABB
1,000 MVA, 550/22 kV generator step-up included provisions for fault-current limiting
unit; it found that current transfer, overcurrent and quench protection. Kansai Electric Power
operation, and protection remained persistent Company reported the development of an
problems. LTS transformer utilizing Nb3Sn conductor.
One phase of this three-phase 2,000 kVA unit
Since 1980, development of LTS transformers operated at 1,379 kVA without quenching and
has been conducted primarily by ABB and transferred fault current to parallel coils under
GEC-Alsthom in Europe and by various quench condition.
utilities, industries, and universities in Japan.
Advances in production of long-length ultrafine
multifilamentary Nb-Ti conductor and high

Energy Efficient Transformers 43


Section 5

Energy Efficient Transformers 44


Section 5

Follow-up to the technology


5.1 Research & Development reduced in some cases if conventional electrical
5.1.1 Modern Transformer Design steel can be replaced with amorphous metal.
Transformers are at the heart of electrical
5.1.3 Types of Transformer Design
transmission and distribution systems, and as
competition increases within the energy sector, so Transformer life expectancy is based on a number
does the pressure on transformer manufacturing of factors, the most important being the quality
industry to improve reliability and reduce costs of of its insulation system. Two things that damage
transformers. transformer insulation are moisture and excessive
heat. Addressing these two factors, modern
The power transformer concept was conceived transformer designs are developed to preserve
and developed in the late 1800s and since then, overall insulation quality of the transformer.
the basic concept of transformer has remained Some of these designs include open style, sealed
the same. However, design and construction tank, conservator style, and automatic gas
techniques have improved to increase both - pressure.
the overall efficiency and cost effectiveness of
manufactured units. • Open Style Design
• Sealed Tank Design
5.1.2 Why Modern Transformer Design • Conservator Type Design
With superior expertise in designing coupled • Automatic Gas Pressure Design
with extensive R&D efforts, modern transform-
ers are much smaller in size, lower in cost, and are 5.1.4 Trends in Modern Transformer
able to promise a remarkable increase in efficiency Design
and reduce lost energy. With the cost of energy increasing and pres-
sure mounting to reduce transformer losses,
Especially for countries like the US, modern attention is on modern transformer design that
transformer design can play a significant role in incorporates technology to lower energy losses
reduction of energy loss. The U.S. has only 4% in transformers. Most transformers are inher-
of the worlds population but produces 25% of ently efficient when they function at 100% load.
its greenhouse gases. The country has over 9,200 However, 100% load is an ideal situation, and
electricity generating units much of them old, many transformers need to function at far lower
needing replacement and thus largely inefficient. loading. As transformer loading changes so does
Since 1982, growth in peak demand for electricity its efficiency. Low loss transformers with modern
in the U.S. has exceeded transmission growth by designs are said to be 30-50% more energy ef-
almost 25% each year, even while a majority of ficient and their losses are designed to be 30%
the energy transformers in the country continue less at 35% loading.
to waste away large amounts of energy.
Modern transformer design is governed by
Better transformer design and the use of superior industry trends that make these transformers
grade electrical steel can drastically reduce no-load stand out for their numerous energy and cost
loss, one of the prime components of loss in an saving advantages.
energy transformer. No-load loss can be further

Energy Efficient Transformers 45


Section 5

5.1.5 Incorporating air bag in 5.1.8 Non-Linear (K-Factor)


expansion tank Distribution Transformers
Newer transformer designs with conservator tanks The use of electronic equipment has continued to
incorporate an air bag in the expansion tank, grow in both offices and industrial plants. Offices
which virtually eliminates moisture egress from now include computers, fax machines, copier,
oil contact with the outside atmosphere. printers, cash registers, UPS’s and solid-state
ballasts. They all contribute to the distortion
5.1.6 Artificial Intelligence techniques of the current waveform and the generation
in transformer design of Harmonics. The K-Factor transformer are
Numerous transformer design tools have been designed to tolerate the harmonic distortion
developed also such as artificial intelligence (AI) associated with these loads.
techniques in combination with finite element
method (FEM). Today, AI is widely used for 5.1.9 Benefits of Modern Transformer
modeling nonlinear and large-scale systems, Design
especially when explicit mathematical models are There is a gradual and increasing preference
difficult to obtain or completely lacking. Moreo- towards modern transformer design not just due
ver, AI is computationally efficient in solving hard to legal requirement but simply because these
optimization problems. On the other hand, FEM transformers have a higher energy efficiency and
is particularly capable of dealing with complex soon pay for themselves. Benefits of modern
geometries, and also yields stable and accurate transformer design include:
solutions.
• Longer transformer life
• Reduced cost of energy due to reduced wastage
5.1.7 Innovative insulation material
• Reduced Greenhouse Gas emissions
Thermal deterioration of transformer insulation • More efficient use of energy; higher
material reduces dielectric strength and reduces production with lower energy use
its ability to withstand short-circuit events.
Innovative hybrid high-temperature insulation 5.2 Energy Efficient Distribution
however can improve insulation temperature Transformer Trends
tolerance, improve winding mechanical strength,
and reduce costs of maintaining and replacing Electricity is one of the most vital infrastructure
transformers. Hybrid insulation consists of inputs for economic development of a country.
using layers of aramid papers and cellulose The demand for electricity in India is enormous
papers. Additional global design modifications and is growing steadily. This growth has been
include reducing the number of cooling ducts slower than country’s economic growth. To
between layers and reinforcing the frame of the balance this demand and supply of electricity, it
transformer to improve short-circuit withstand is the time for electric utilities to go for energy
strength. Higher reliability and longer life efficient electrical equipment for huge savings as
anticipated by hybrid-insulation manufactured this would be utilized for future needs.
transformers results in cost savings to the utility. The Ministry of Power has outlined its mission
for 11th Five Year Plan – “Power For All: 2012”.
In the next 5 years, India will require 66,000
MW of new generation capacity with matching

Energy Efficient Transformers 46


Section 5

investments in transmission and distribution The 10th Five Year Plan originally envisaged
networks. For every 1 MW of new capacity 41,100 MW, re-revised finally to about
that comes up, about 7 – 8 MVA transformers 30,500 MW and has ended at 23,450 MW.
(approximately) are used across Generation, Simultaneously, with the worsening power
Transmission and Distribution segments. scenario and acute power shortage, the Indian
This implies a demand of about 5,00,000 Economy cannot sustain the growth momentum
MVA of transformers unfolding over next 5 but has to look for aggressively augmenting
years, resulting in an annual demand of about power supply.
100,000 MVA, which would mean that there
would be approximately a demand for 2.25 The strategy developed to make power available
Million Transformer units (approx. 30% for to all by 2012 includes promotion of energy
distribution) of average rating of 63 kVA. Besides efficient products and its conservation in the
fresh demand, some replacement demand of country, which is found to be the least cost
15,000MVA (approximately) will also be coming option to augment the gap between demand and
up, as transformers usually have a life of 20 – 30 supply.
years.

Case: Typical loss Ordinary Energy Efficient Transformer


comparison of a 63kVA Conventional
Distribution Transformer Transformer
63KVA – Distribution
Transformer
3 star 5 star
Max. Total Losses at 50%
490 380 280
loading (watts)
Max. Total Losses at 100%
1415 1250 1100
loading (watts)
Difference in power 1415 – 1250 = 165 (3 star)
savings at 100% loading 1415 – 1100 = 315 (5 star)
(watts)
* Board of Energy Efficiency - India

Energy Efficient Transformers 47


Section 5

Nearly 185 to 354 MW (considering 50% of in the network, and the way in which they are
2.25 Million transformers) of capacity creation loaded, can also increase savings. Transformers
through energy efficiency in the distribution are at maximum efficiency when approximately
sector alone is required in our country and this 50% loaded.
can be achieved only through employing Energy
Efficient Distribution Transformers by our In India, T & D losses are high, in the range of
Electrical Utilities as transformer is the heart of 20-23 percent. The Ministry of Power says that
any electrical distribution system. aggregate technical and commercial (AT & C)
losses are around 50% - and losses are even higher
The Distribution Reforms were identified as than this in some of the states.
the key area to bring about the efficiency and
improve financial health of the power sector. The main reason for exceptional high losses in
the Indian network lies at the distribution levels.
Power utilities improve efficiency of their Hence, the use of energy efficient equipments for
distribution systems by reducing losses. Industrial the utilities is very much essential for reduction
and commercial users of electricity also improve of losses, which implies for savings in electrical
the efficiency of their electrical distribution energy for its growing demand.
systems by reducing losses. The distribution
transformer supplies power to all the power Over many years there has been a lack of
consuming items and remains energized for 24 investment in essential improvements to
hours. Being supply equipment, it does not, by the electricity system, with only lowest cost
itself, consume any power. But the process of incremental investments being undertaken.
transformation involves certain inherent losses With this kind of purchasing system, especially
especially in the core, having to run continuously for transformer at distribution sectors of
for all the 24 hours of the day and 365 days of State Electricity Boards in India, it would be
the year. Hence, the need to turn the attention to unmanageable for them to meet the electricity
low loss designs and latest technologies in quality demand of the economic growth.
of core material to promote energy efficiency. In
this context “amorphous metal core” material Many electrical utilities have obligations to
offers great advantage, as no load losses are less. ‘operate an economic and efficient system’, but
The scope for improving the efficiency of therein lies a conflict. ‘Economic’ suggests low
distribution transformers can arise in a number capital cost transformers, which are not the most
of ways. Higher performance raw materials, efficient, whereas ‘Efficient’ transformers come at
particularly special steels for building transformer higher prices.
cores, are continually being developed.
Transformer manufacturers are aware of the
Advancement in the core material, amorphous commercial pressures on customers not to apply
iron, produced by cooling molten metal alloy loss capitalization strictly and have to respond
very rapidly, has become available and is getting to these, particularly in a competitive market. A
wide acceptance in many utilities in India and common ploy is to tempt the customer with a
across the globe. Losses in the core are less than low cost / high loss alternative offer. Total Cost
30% as compared to those of conventional steel of Ownership (TCO)(see Section 4.1.3), takes
cores. The size of the transformers being installed into account not only the initial transformer

Energy Efficient Transformers 48


Section 5

cost but also the cost to operate and maintain Energy – efficiency labels are informative labels
the transformer over its life. This requires that fixed to manufactured products, which describe
the TCO be calculated over the life span of the the product’s energy performance (usually in
transformer. With this method, it is now possible the form of energy use, efficiency, or energy
to calculate the real economic choice between cost) and rate the product on a comparative
competing models. scale so that consumers can make appropriate
decisions while purchasing electrical equipments.
Thus TCO method provides the Electrical Energy-efficiency Standards are procedures and
utilities an effective way to evaluate various regulations that prescribe minimum efficiency
transformer initial purchase prices and cost of performance standards of the manufactured
losses. The goal is to choose a transformer that products.
meets specifications and simultaneously has the
lowest TCO. BEE has taken lead role to network with and
ensure participation of stakeholders such
Even though the more-efficient transformer as industry associations, R&D institutions,
costs more initially, its lower operating cost saves manufacturers, Bureau of Indian Standards, etc.
money over its life. at all stages in the entire process.
• Facilitate and assist manufacturers to
Considering the vast potential of energy savings develop testing procedures and protocols
and benefits of energy efficiency, the Bureau for determining energy performance, label
of Energy Efficiency (BEE), has come up with setting, fixing of standards, and enforcement
reasonable solutions for strengthening and mechanisms.
up gradation of the transformers used in the • Encourage manufacturers to improve energy
distribution system. efficiency of equipments and appliances at
the manufacturing stage. Promote integration
5.3 Some of the Short Term and of efficient technology in manufacturing of
Long Term Measures Taken by BEE equipment and appliances.
• Stimulate market transformation and promote
• Bureau of Energy Efficiency(BEE) energy efficient equipment and appliances.
operationalized complete pilot phase
of programme for energy efficiency in The benefits of the approach and activities would
government building and prepare action plan be the following:
for wider dissemination and implementation. • Manufacture of energy efficient equipments
• Standards and Labeling (S&L) Programme and appliances.
has been identified as one of the key activities • Enabling consumers to exercise considered
for energy efficiency improvements. The S&L choice based on energy consumption at the
program ensures that only energy efficient time of purchase.
equipment would be available for purchasers. • Reduction of energy consumption in
Some of the electrical products to be covered equipments and appliances of common use.
under S&L program are: Agricultural pump
sets, Distribution Transformers, Motors, With this, some of the electrical equipment
Lighting products, refrigerators, etc. manufacturers are fixing tie – up with
distribution utilities to penetrate into the pool of

Energy Efficient Transformers 49


Section 5

promoting energy efficient equipments. The existing IS 1180 (part 1) specification losses
To exemplify the above statement, there has been are the base case with star 1.
a tie-up between CFL maker and distribution This demonstrates that the Centre is encouraging
utility which entail distribution to domestic the electrical equipment manufacturers to come
consumers for using less energy than other up with energy efficient products for their fullest
ordinary products (such as incandescent bulbs), utilization in energy savings.
saving their money on utility bills and helps in
protecting the environment over the life of each 5.3.1 Selection of better material for
CFL and draw carbon credits. energy efficient transformer
In selecting the material for core, we say that
BEE has recently approved the ‘star labeling’ amorphous metal core outflanks in reducing
for Distribution Transformers – The highest the no-load losses. This can summate immense
loss segment is defined as star 1 and lowest loss economic savings to the electric utilities since
segment is defined as star 5. they are one of the highest energy efficient
transformers rated so far.

A typical comparison is shown below which


depicts the decrease by installation of energy CRGO (in AMDT (in Reduction in
efficient low loss amorphous metal core watts) watts) Losses
transformers. Rating (Three Phase)
25 kVA 100 32 68%
50 kVA 160 58 64%
100 kVA 260 85 67%
200 kVA 470 115 75%
* Board of Energy Efficiency - India

Energy Efficient Transformers 50


Section 5

5.4 Policies and Regulations 5.4.2 Energy Star Transformer Program


5.4.1 NEMA Standards TP1 Program 5.4.2.1 What Is The Energy Star
The NEMA Premium Efficiency Transformer Transformer Program?
Program will help utilities, commercial buildings,
and industrial plants incorporate super high- The ENERGY STAR Transformer Program is
efficiency electrical transformers into their a voluntary, EPA-sponsored effort to recognize
operations. NEMA originally set the standard electric utilities that make a commitment
for the efficiency of various types of distribution to purchasing high-efficiency distribution
transformers with the publication of NEMA TP transformers. The program requirements for
1-2002 Guide for Determining Energy Efficiency utility members are simple.
for Distribution Transformers, which was later
adopted by the U.S. Department of Energy PARTNERS AGREE TO:
(DOE) as the national energy-efficiency rule for Perform economic analysis of total transformer-
low-voltage dry-type distribution transformers. owning costs — including the purchase price
The new NEMA Premium Efficiency and the cost of energy losses — using a standard
Transformer designation requires 30 percent industry methodology; and Buy transformers
fewer losses than existing DOE regulations (10 that meet EPA’s ENERGY STAR guidelines only
CFR 431) for low-voltage dry-type distribution when they are cost-effective.
transformers.
WHY ENERGY STAR TRANSFORMERS?
The transformers covered under the new program Distribution transformers are one of the most
are typically used in commercial and industrial widely used elements of America’s electric
applications. However, some electric utilities distribution systems. Transformers convert
are considering the NEMA program for their electricity from the high voltage levels on utility
commercial and industrial energy-efficiency transmission systems to voltages that can be
rebate programs. The adoption of this program used in businesses and homes. Over 40 million
will not only reduce energy consumption, but distribution transformers are currently in service
will also significantly reduce carbon dioxide on electric utility distribution systems, and
emissions. The new transformers, built to utilities nationwide purchase more than one
NEMA premium standards, have the potential million new units annually. Transformers are a
to eliminate the need for a new coal power plant crucial link in the utility industry’s efforts to bring
over the next five years. Actual efficiencies for American consumers safe, reliable, and cost-
these new premium transformers range from 98 effective electricity.
percent to more than 99 percent, depending on
the size of the transformer. One of the most striking features of transformers
is their dependability and long service lives. On
For the complete publication of NEMA average, transformers remain in service for over
TP1 – 2002, Guide for Energy Efficiency of 30 years, during which time they perform their
Distribution Transformers, please see attachment. vital function reliably and with little degradation
in service quality. Amazingly enough, many
transformers operate at efficiency levels that often
exceed 98 percent.

Energy Efficient Transformers 51


Section 5

JOIN THE ENERGY STAR TRANSFORMER 5.4.2.2 Energy Star Transformer Program
PROGRAM Benefits
As a Partner in the ENERGY STAR Transformer
The ENERGY STAR Transformer Program is Program, your company will have access to
a voluntary energy efficiency program designed valuable communication, public recognition, and
to encourage utilities to purchase and install technical resources provided by EPA.
high-efficiency, cost-effective transformers
on their distribution systems. The Program 5.4.2.3 Public Recognition
promotes the best practices in the utility industry A critical element of EPA’s voluntary pollution
and recognizes those utilities that have made a prevention program is the highly visible
commitment to high efficiency transformers. recognition of our Partners’ environmental
efforts. As part of the ENERGY STAR
The ENERGY STAR Transformer Program Transformer Program commitment, your
is one of the action steps in the U.S. Climate company can use the ENERGY STAR
Change Action Plan (CCAP). The CCAP calls Transformer logo SM in reports and press
for voluntary, profitable actions that will help the releases to inform your customers about your
United States reduce its greenhouse gas emissions environmental success. In addition, EPA is
to 1990 levels by the year 2000. committed to developing prototype materials
designed to recognize participants’ commitments
Like other programs in the Action Plan, the to the environment and to build public and
ENERGY STAR Transformer Program relies on regulatory support for their efforts.
the ingenuity and technical know-how of U.S.
industries to both improve the economy and 5.4.2.4 Technical Tools
protect the environment. A second critical component of the ENERGY
STAR Transformer Program is the technical
In addition, the ENERGY STAR Transformer assistance and resources provided to Partners to
Program is listed as one of the options in the increase the profitability of their high-efficiency
Climate Challenge Program. Climate Challenge transformer purchases. The following represent a
is a joint effort of the Department of Energy sampling of tools available from EPA.
(DOE) and the U.S. electric utility industry to For a complete copy of the Energy Star Program
reduce greenhouse gas emissions. Hundreds of Brochure, please see attachment.
utilities have joined the Program and are actively
developing plans to cost-effectively achieve their
emission reductions.

* Sources of Information

1. Leonardo Energy Transformers – Leonardo-energy.org


2. Hitachi Metals Website
3. Energy Efficiency in Transmission & Distribution – European Commission
4. Electric Power Transformer Engineering by James Harlow

Energy Efficient Transformers 52

You might also like