SERVICE MANUAL

Models :
HSU-24H03/Z HSU-24C03/Z

l
l l l l

Features

Comfortable:wide-angle airflow Health air purifying Quiet operation Wide variety of functions

Serial Number: 001055 5

Versio n:00.00

Edition: 2005-5-21

Domestic Air Conditioner

Model:

HSU-24H03/Z HSU-24C03/Z

Description of product model coding and series introduction Specifications Curves of performance Description,net dimensions and functions of main component s and accessories 5. Knock-down drawings and part lists 6. Brief introduction to electrical control functions 7. Abnormity diagnose 8. Wiring diagram 9. Circuit diagram 10. Trouble shooting 11. Refrigerating cycle diagram 12. Noise level test chart and air velocity distribution 13 . Installationmanual

1. 2. 3. 4.

Content

Domestic Air Conditioner

Model: HSU-24H03/Z

HSU-24C03/Z

DESCRIPTION OF PRODUCT MODEL CODING & SERIES INTRODUCTION

Domestic Air Conditioner

Model:

HSU-24H03/Z HSU-24C03/Z

A. Description of coding rules of unit model Coding rules and descriptions are as follows: 1 2 3 4 5 6 7 8
9 10 11

Refrigerant type:R1(R407C),R2(R410A) Applicable voltage:3(220~230V),4(240V) Applicable frequency:0(50HZ),1(60HZ) Developing sequence :A,B,C,D... L/C-cooling only Function code R/H-heat pump E-electric aided heating

Nominal cooling capacity (BTU/h)with the first two numbers based on thousand unit The structure code of indoor & outdoor unit: S(wall-mounted),W(window type),P (cabinet type) H-Abbreviation of Haier

Examples: HSU-24H03/Z,It represents wall-mounted split type heat pump air conditioner .The cooling capacity is 24000BTU/h,and the power supply is 220-230V/50Hz,Z means the developing sequence. B.Standard Situation/Conditions
No. 1 2 3 Operating condition Norminal cooling Norminal heating Norminal electrical heating indoor air status DBOC 27 C 20 OC --O

WB C 19 OC 15 OC ---

outdoor air status DBOC WBOC 35 OC 7 OC --24 OC 6C --O

4 3

Domestic Air Conditioner

Model: HSU-24H03/Z

HSU-24C03/Z

C.Series brief introduction


1.High energy efficient The design of inner-grooved copper tube greatly increases the refrigerant contact area and the efficiency of cooling/heating functions.Using the R410A refrigerant and the refrigerating system optimizing design make both the EER and COP reach the B class according to the european energy efficient standard. 2.Comfortable:wide-angle airflow The vertical dual-flap and horizontal wide-angle louvers ensure the cool/warm air reaches every corner of the room. 3.Health air purifying An air purifying filter with deodorizing and disinfecting functions keeps the air clean and users healthy. 4.Quiet operation Fan with random-pitched blades. Random-pitched blades help reduce operating noise while maintaining a high airflow rate. 5.Convenience Auto restart and washable panel: The grille can be removed easily and washed when necessary.Any series have the function then even if the power falls when the unit is operating unit will automatically return to the operating settings in use before the power failure when power is restored. 6.Wide variety of functions 24-Hour Timer: 24-hour timer allows users to select the exact time they would like the air conditioner to turn on and to turn off.Timers on previous models operation based on the number of hours of desired operation. 7.Night-set models When the air conditioner is operating on the timer-off circuit.The preset room temperature gradually rises(going down in heating)before the unit stops as shown below.Users can sleep comfortably without sudden change in temperature. 8.Programdry This function automatically reduces the level of humidity while maintaining the preset indoor temperature.

Domestic Air Conditioner

Model: HSU-24H03/Z

HSU-24C03/Z

SPECIFICATIONS

Domestic Air Conditioner

Model: HSU-24H03/Z

HSU-24C03/Z

Model: HSU-24H03/Z
Cooling capacity(W) Cooling coefficient(W/W) Cooling power input(W) Moiture removal(m3/h)
Operating voltage range(V) Operating temp. range ( C)
O

6800
2.52 2700 2.3X10-3 220-230 ~ -7-43 +1 T1 47/45/43 48/46/44
1155x308x224 1231x372x300 17/20.5

Heating capacity(W)

7600 2.62 2900 50 R22 60


O

Heating coefficient(W/W) Heating power input(W)


Frequency range(Hz) Refrigerant type Air sending angle indoor unit Fan type outdoor unit Class of electric shock Outdoor unit noise( dB(A) ) (cooling) Outdoor unit noise( dB(A) ) (heating) Net dimensions ( mm) (outdoor unit) Packaging dimensions ( mm) (outdoor unit) Net/gross weight (kg) (outdoor unit) Piling layers

Variation of temp. adjust ( C)


O

Cross flow fan Axial flow fan

Climate type: Indoor unit noise( dB(A) ) (cooling) Indoor unit noise ( dB(A) ) (heating) Net dimensions ( mm) (indoor unit) Packaging dimensions ( mm) (indoor unit) Net/gross weight (kg) (indoor unit) Max. mounting height difference(m) Refrigerant charge(g) (R22) Frequency of filter cleaning Compressor model Compressor oil charge (cc) Max . length of connecting pipe (m) Tube type
Fan speed(H/M/L)(r/min) cool

I 58/52 58/52
860x308x730 995x420x815 69/77

5 2300 Once/2 weeks


THU33

indoor unit outdoor unit Current entering side (indoor/outdoor)


Max. refrigerant charge (g) Compressor manufacturer Compressor protector type

8 4 outdoor 2400
SHANGHAIRILI internal

800 15

drain hose

TP2Y
heat
1320/1260/1180 1320/1260/1180 1050

(indoor unit)
Fan speed(r/min)

length(mm) diametre(mm) Type of tube of evaporator and condenser Size of tube of evaporator and condenser(mm)

2000 16 Internal treaded O7&O9.52 plastic metal 2.8

(outdoor unit) Cut-off vavle(inch) two-way three-way Max. operating pressure at warm side(Mpa)

1/4 1/2 2.8

Appearance features of indoor unit Appearance features of outdoor unit Max. operating pressure at cool side(Mpa)

Domestic Air Conditioner

Model: HSU-24H03/Z

HSU-24C03/Z

Model: HSU-24C03/Z
Cooling capacity(W) Cooling coefficient(W/W) Cooling power input(W) Moiture removal(m3/h)
Operating voltage range(V) Operating temp. range ( C)
O

6800
2.52 2700 2.3X10-3 220-230 ~ -7-43 +1 T1 48/44/38 ---1155x308x224 1231x372x300 17/20.5

Heating capacity(W)

-------

Heating coefficient(W/W) Heating power input(W)


Frequency range(Hz) Refrigerant type Air sending angle indoor unit Fan type outdoor unit Class of electric shock Outdoor unit noise( dB(A) ) (cooling) Outdoor unit noise( dB(A) ) (heating) Net dimensions ( mm) (outdoor unit) Packaging dimensions ( mm) (outdoor unit) Net/gross weight (kg) (outdoor unit) Piling layers

50 R22 60
O

Variation of temp. adjust ( C)


O

Cross flow fan Axial flow fan

Climate type: Indoor unit noise( dB(A) ) (cooling) Indoor unit noise ( dB(A) ) (heating) Net dimensions ( mm) (indoor unit) Packaging dimensions ( mm) (indoor unit) Net/gross weight (kg) (indoor unit) Max. mounting height difference(m) Refrigerant charge(g) (R22) Frequency of filter cleaning Compressor model Compressor oil charge (cc) Max . length of connecting pipe (m) Tube type
Fan speed(H/M/L)(r/min) cool

I 58/52 ---860x308x730 995x420x815 69/77

5 2200 Once/2 weeks


THU33

indoor unit outdoor unit Current entering side (indoor/outdoor)


Max. refrigerant charge (g) Compressor manufacturer Compressor protector type

8 4 outdoor 2400
SHANGHAIRILI internal

800 15

drain hose

TP2Y
1320/1260/1180 1050

(indoor unit)
Fan speed(r/min)

heat

length(mm) diametre(mm) Type of tube of evaporator and condenser Size of tube of evaporator and condenser(mm)

2000 16 Internal treaded O7&O9.52 plastic metal 2.8

(outdoor unit) Cut-off vavle(inch) two-way three-way Max. operating pressure at warm side(Mpa)

1/4 1/2 0.65

Appearance features of indoor unit Appearance features of outdoor unit Max. operating pressure at cool side(Mpa)

Domestic Air Conditioner

Model: HSU-24H03/Z

HSU-24C03/Z

CURVES OF PERFORMANCE OF COMPRESSOR

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

PERFORMANCE CURVE
220V-50Hz-1 PHASE SUCTION GAS TEMP.---35 UNDER COOL-----------8.3 AMBIENT TEMP.---------35 RUNNING CAPACITOR--55 F

160 150 140 130 120 110 100 90 80 -5 2600 0 5

FLOW RATE (kg/h)

45 50 55 60

10 60 55 50 45 CONDENSING TEMP. ()

INPUT W

2400 2200 2000 1800 -5 13.0 0 5 10

CURRENT A

12.0 11.0 10.0 9.0 8.0 -5 8500 8000 7500 7000 6500 6000 5500 5000 4500 4000 -5 0 5 EVAPERATING TEMP. ( ) 0 5 10

60 55 50 45

45

CAPACITY W

50 55 60

10

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

DESCRIPTION,DIMENSION AND
FUNCTION OF MAIN COMPONENTS AND ACCESSORIES

10

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

Indoor Unit

Inlet grill

Air filter

Use remote controller to adjust up and down air flow. (Don't adjust it manually.)

Vertical flap

Power indicator
Lights up when unit starts.

Timer mode indicator


Lights up when Timer operation is selected.

Operation mode indicator


Lights up during compressor running .

11

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

KNOCK-DOWN DRAWINGS

12

Domestic Air Conditioner

Model: HSU-24H03/Z

HSU-24C03/Z

13

Domestic Air Conditioner


No. in exploded view Spare parts number Spare parts description in english Model Qty Price list

HSU-24H03/Z Model: HSU-24C03/Z


Edition:2005/05/21 Failure rate(%) The proportion of the spare part Remark stock

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 31 32 33 34 35 36 37 37 38

001A1231360 0010800070 001A2400136 0010802048 0010704157 001A0300060 001A2300098 001A1301857 0010200074 0010200075 001A1301856 001A14311029 001A1231361 001A14311047 001A3900059 0010401745 001A3000273 001A14361036 001A0900011 0010800156 001A14361035 001A14431044 001A14361031 001A1231357 001A1231358 0010200036 001A14361030 001A1741744 001A14311041 0010401531 0010401590 0010401536 001A14311043 0010400576 001A1301858 0010401599 0010401603

Front grillle Front panel assy. Air filter Seperating plate(L) Heat exchanger assy. Bearing Fan Left support Cushion Cushion Mounting plate Fix plate Bottom plate Control box Temperature sensor Displaying panel Swing motor Support plate Drain hose Drain pan assy. Link Bearing support Vane Flap Flap Wnd shield Dew-prevent Heat-insulation tube Seperating plate(R ) PC board PC board Power switch Terminal block Switch Motor cover Motor Right support Remote controller Remote controller Drain hose

HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C03/Z

1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 10 15 1 1 1 1 1 1 1 1 1 1 1 1 1 1

* *

* *

HSU-24H03/Z HSU-24C03/Z
HSU-24H03/Z HSU-24C03/Z HSU-24H03/Z HSU-24C04/Z HSU-24H03/Z HSU-24C05/Z HSU-24H03/Z HSU-24C06/Z HSU-24H03/Z HSU-24C07/Z HSU-24H03/Z HSU-24C08/Z HSU-24H03/Z HSU-24C09/Z HSU-24H03/Z HSU-24C10/Z HSU-24H03/Z HSU-24C11/Z

* *

* * *

14

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

15

Domestic Air Conditioner


No. in exploded view 1 2 3 4 4 5 5 6 7 8 9 10 11 12 13 14 15 16 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 Spare parts number 001A1236199 001A1101106 0010202161 0010402046 0010402157 001A1301427 0010801921 001A5701063 0010704366 001A1231361 001A0100656 001A1436182 001A0100651 001A0100652 001A0100125 001A2500015 0010703916 0010704436 0010702454 0010702420 0010402047 0010702609 001A1762341 0010250255 ---0010806226 001A4000107 001A2500004 001A4000011 001A1301418 0010400334 0010100001 0010401954 001A3600218 001A0100753 001A1101110 Spare parts description in english

Model:
Qty Price list

HSU-24H03/Z HSU-24C03/Z
Edition:2005/03/31 The Failure proport Rem rate(%) ion of ark the

Model

Front grille HSU-24H03/Z HSU-24C03/Z 1 Front panel HSU-24H03/Z HSU-24C03/Z 1 Fan HSU-24H03/Z HSU-24C03/Z 1 Motor HSU-24H03/Z 1 Motor HSU-24C03/Z 1 Motor support assy. HSU-24H03/Z 1 Motor support assy. HSU-24C03/Z 1 Heat exchanger fixing HSU-24H03/Z HSU-24C03/Z 1 Heat exchanger assy. HSU-24H03/Z HSU-24C03/Z 1 Temperature sensor suppHSU-24H03/Z HSU-24C03/Z Back grille HSU-24H03/Z HSU-24C03/Z 1 Side panel (L) assy. HSU-24H03/Z HSU-24C03/Z 1 Handle HSU-24H03/Z HSU-24C03/Z 1 Top panel assy. HSU-24H03/Z HSU-24C03/Z 1 Side panel (R) assy. HSU-24H03/Z HSU-24C03/Z 1 Wiring cover assy. HSU-24H03/Z HSU-24C03/Z 1 Four-way valve HSU-24H03/Z 1 Capillary tube assy. HSU-24H03/Z 1 Capillary tube assy. HSU-24C03/Z 1 Two-way stop valve HSU-24H03/Z HSU-24C03/Z 1 Three-way stop valve HSU-24H03/Z HSU-24C03/Z 1 Wires HSU-24H03/Z HSU-24C03/Z 1 Compressor HSU-24H03/Z HSU-24C03/Z 1 Compressor heating-set HSU-24H03/Z HSU-24C03/Z Cushion HSU-24H03/Z HSU-24C03/Z 1 Wires HSU-24H03/Z HSU-24C03/Z Cushin HSU-24H03/Z HSU-24C03/Z 1 PC board HSU-24H03/Z HSU-24C03/Z 1 Controller box HSU-24H03/Z HSU-24C03/Z 1 Terminal block HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 4-way valve coil Transformer HSU-24H03/Z HSU-24C03/Z Sensor HSU-24H03/Z HSU-24C03/Z Terminal block HSU-24H03/Z HSU-24C03/Z 1 Tube plate(R ) HSU-24H03/Z HSU-24C03/Z 1 AC contactor HSU-24H03/Z HSU-24C03/Z 1 Capacitor clip HSU-24H03/Z HSU-24C03/Z 1 Capacitor for compressor HSU-24H03/Z HSU-24C03/Z 1 Capacitor for motor HSU-24H03/Z HSU-24C03/Z 1 Seperating plate assy. HSU-24H03/Z HSU-24C03/Z 1 Bottom plate assy. HSU-24H03/Z HSU-24C03/Z 1

16

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

REMOTE CONTROLLER FUNCTIONS CONVERTION

17

30

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

Brief introduction to electrical control functions

BRIEF INTRODUCTION TO ELECTRICAL CONTROL FUNCTIONS

1841

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

1. Introduction of electric control function 1.1 Brief introduction of electric control function (1) Auto running (available for cooling and heating type) When Auto running starts for the first time, selection of running mode follows the conditions below: Tr > 23 Select cooling mode Set temperature: 26 Tr23Select heating mode (with temperature compensation) Set temperature: 23 In auto mode, running mode shifts between cooling and heating with the variation of room ambient temperature. (2) Room temperature control Compressor ON Compressor OFF

Heating

16

Set temperature
38

Compressor OFF
38

Compressor ON

Cooling
38

Set temperature

(3) Dry running Compressor, outdoor fan and indoor fan run as follows (Tr, room temperature, Ts, set temperature). When dry mode starts for the first time, compressor, outdoor fan and indoor fan will run following the rules below: Tr>Ts+2 compressor, outdoor fan run successively, indoor fan run at set speed, this working area is defined as area A. Ts2compressor, outdoor fan will run for 10 minutes and stop for 6 minutes, indoor fan will run at low speed, this working area is defined as area B. compressor Tr<Ts, compressor, outdoor fan will stop running, indoor fan will run at low speed, this area is defined as area C. four-way valve In dry mode, system will shift between area A, B and C variation with room ambient temperature. When Tr<Ts+1, system will shift from area A to B; when Tr>Ts, system will shift from area C to B; when Tr>Ts+3, system will shift from B to A; when Tr<Ts-1, system will shift from area A to C. outdoor fan air proof in heating (4) CoolIn heating, every time starts compressor, indoor fan will stop running if room coil temperature is less than 28; indoor fan will run at low speed if room coil temperature is equal to or more than 28and less than 38 ; indoor fan will run at set fan speed if room coil temperature is more than 38or compressor has run more than 4 minutes. (5) Residual heat air discharging in heating In heating, compressor stops, indoor fan stops after a 30-second low running. (6) Defrosting control

19

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

(1)

a. After the state of Tp- Tr<18 is continued for 5 minutes, the accumulated running time of the compressor exceeds 45 minutes, the continuous running time of the compressor exceeds 20 minutes; b. The accumulated running time of the compressor exceeds 3 hours, the continuous running time of the compressor exceeds 20 minutes, indoor unit s Tp <42; c. The continuous running time of the compressor exceeds 20 minutes, the 0 temperature of indoor coil pipe decreases 1 every 6 minutes, which lasts for more than 3 times, indoor unit s Tp <42 ; d. When the indoor unit is in the state of overload protection and the outdoor unit ceases, when the rerunning time of outdoor unit exceeds10 minutes, the accumulated running time of the compressor exceeds 45 minutes, the continuous running time of the compressor is over 20 minutes, and Tp <42. Defrosting will begin if one of the above conditions is met. (2) Defrosting finishing condition: If the defrosting time exceeds 9 minutes, the original heating state will be resumed; Defrosting process is as follows: Indoor fan Outdoor fan 4-way valve

Run on cool air-proof condition

55s 1min

9min 55s 1min

20

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

(7) Temperature compensation. Auto temperature compensation condition: when reach temperature condition, cut-off time of compressor is less than 5 minutes. Temperature compensation rules are as follows: When Ts+4-Tr2when Ts+4- Tr=1 When Ts+4-Tr0 When heating mode starts for the first time, With temperature compensation function, if push temperature increasing and decreasing button on remote controller, ; if push temperature increasing button on remote controller, will maintain previous value. (8) Overcool protection in cooling. In cooling, 9 minutes after the start of compressor, check room coil temperature. when indoor coil temperature is less than 0compressor and outdoor fan will stop running. When the two following conditions are meet, compressor and outdoor fan will restart: Cut-off time is more than 3 minutes; Indoor coil temperature is more than 7 (9) 3-minutes delay When compressor stop running arose from transmitter OFF, ON-OFF or breakdown, compressor will stop for 3- minutes. (10) Overcharging protection in heating Overcharging protection: in HEAT mode, if room coil temperature>56, outdoor fan will stop running and resume when inner coil temperature 53 if room coil temperature>68 and last 10 seconds, compressor and outdoor fan will strop running; compressor and outdoor fan will resume normal operation when room coil temperature<46 Over-current protection: in HEAT mode, outdoor fan will stop running if working current measured with current transformer is continuously more than 14A in 2 seconds; if current is less than 13A, outdoor fan will resume operation; if working current is more than 26A after a 5-minutes running and last 10 seconds, compressor will stop and resume normal operation 3 minutes after; indoor fan will run on cool-air proof condition. If over-current protection occurs twice in 30 minutes, compressor won t restart any more. System will turn into over-current fault alarm. (11) Power failure compensation function. Power failure compensation function will be set by remote controller. To cancel power failure function, push SLEEP button 10 times in 5 seconds, buzzer will sound twice "BEEP"; To set power failure function, push SLEEP button 10 times in 5 seconds, buzzer will sound four times "BEEP". When main panel has power failure compensation function, it will memorize running parameter in the case of sudden power failure (not cut by remote controller), if unit didn t receive remote signal 3 minutes after power resume, it will call automatically memory information and continue to run in previous state. Memory includes operation mode, fan speed, set temperature, air door state, health; timing and sleep mode not included. (12) Emergency switch and forced cooling. Push down emergency ON/OFF button, buzzer will sound once "beep", release it 5 seconds after, unit will perform starting function; if ON/OFF button is pressed continuously for more than 5 seconds, buzzer will sound twice "beep", and unit will perform forced cooling function. Here operational mode is set as cooling, fan speed is set as high; forced cooling will finish 30 minutes after. After having pushed down mode button, fan speed button, temperature increasing and decreasing button, sleep button,

21

Domestic Air Conditioner

Model: HSU-22HC03/R2

WIRING DIAGRAM

22

47

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

CN3

THE WIRING DIAGRAM FOR OUTDOOR UNIT IS ONLY FOR HSU-24H03/Z

THE WIRING DIAGRAM FOR OUTDOOR UNIT IS ONLY FOR HSU-24C03/Z

23

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

CIRCUIT DIAGRAM

2447

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

+12 +12 +12 R27 10K DQ6 9014 R11 10K C35 R26 104 1 0 K R33 1K
DL1 103N

IC2 93C46 5 6 R13 10K +5 8 DQ4 9014 R34 5.1K C22 104 7 GND DO RS DI NC SK VCC CS 4 3 2 1

R31 1 0 K+5 +5
CN5

+12 1 +5

7805 GND Vin Vout 3

+5

R52 C7 10K 104 IC7 LM358

CN6
+5 C9 104

C12

R38 R32 1 M D6 5 1 K 1N4148 C33 104

C8 220UF/16V C20 104

JTP 1236A R14 1 0 KSW1

+12

100UF/16V

+5 +5 R41 10K J19 J C37 104 R51 5.1K DQ5 2N5551

D9 IN4007

JK3 JQ1aP-12V

C29 103 +5

R44 10K

+12V

CN3

100UF/16V C36 C15 104

+12
+5 PS144DP02B-T +12 R35 BUZ 1 0 K XT 2P C6 104 R4 1K R5 100 +12 JK2 G4A-1A-E

R45 5.1K R46 10K +5 R40 5.1K DQ3 9014 DQ2 9014 C34 103 IC1 TMP87PH46N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 P77 VCC P76 P22 P75 P21 P74 P20 P73 P17 P72 P16 P71 P15 P70 P14 P07 P13 P06 P12 P05 P11 P04 P10 P03 P67 P02 P66 P01 P65 P00 P64 TEST P63 RESET P62 XIN P61 XOUT P60 VSS VAREF +5 C25 104
OSC 8MHZ

+5 C11 104

R10 5.1K

DQ7 R47


+12V

5.1K 9014 DQ8 R48 R5.1K 9014 R30 10M DQ9 R49 5.1K 9014 L101 220 R25 L102 L103 220 R24 220 R23 R22 220 R101 +5 R102 C101 R12 10K

42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22

J24 J 1 2 3 4 5 6 7

IC3 ULN2003A A1 Q1 16 15 A2 Q2 A3 Q3 14 13 A4 Q4 A5 Q5 12 11 A6 Q6 A7 Q7 10

+12 C26 104


CN7

8 R59 1K

GND VCC

9 +5

SW2

10K R58 1 KR17 R19 10K


CA1

+5

R42 10K

R43 10K C27

+5 L1 101

JSS 1271

4.7UF/50V


+12
CN2

L2331 R20 20K C28 4.7UF/50V L3 331

VDD


+5 C17 C18

R21 10K

CN8

R15 470UF/100V 470UF/100V 51K

JK1 JQ1aP-12V
IC5 TL431

R18 20K +12 4 1 R8 R37 C16 5102 0 K 104 IC6 LM2575-12 2 Z1 1N6189 L4 331

C19 R53 103 2 K R541 K C23 103

+5

+5 IC8 LM358

R3 1 0 K R551 K C14 R2 5.1K 100UF/16V

+5 R39 5.1K R50 DQ1 10K 9012 R56 3.3K

C31 1000UF/25V

+5

R28 10K

D7 1N4148

R29 1K

D1 UF106

R9 62K


IC4 T600D

C10 330UF/50V

C21 104

C24 4.7UF/50V

C13 R57 D2 471/2KV 100K/2W P6KE200

D4 UF4005

EZ1
N

B1 M1TOP226Y KBJ406 LX1


D

VDD PC3 TLP521-1 D8 1N4148 R36 D5 51K BYW29-200F

F1

C2 0.1UF/275V C1 LX102 NTC 5D-15

C S

R1 10 C30 222/2KV C5 47UF/25V


C4 T1 0.1UF/50V B K - J N 0 2

0.1UF/275V T3.15A 250VAC

C3 100UF/400V

25

AC220V

Domestic Air Conditioner

Model: HSU-22HC03/R2

ABNORMALITY DIAGNOSING

2647

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

For the abnormal phenomenon occurred, please conduct trouble analysis and troubleshooting according to the following table:
No 1 Reason of trouble Phenomena Remarks

The sensor of indoor ambient The compressor indictor temperature is in short circuit or and timing indicator broken circuit extinguish, and the running indicator flickers

The temperature sensor of The compressor indictor indoor coil pipe is in short and timing indicator are circuit or broken circuit on, and the running indicator flickers
The indoor motoris damaged, or the The power indicator and The motor has no signal

computer board is damaged

running indicator of indoor feedback of Hall unit unit flicker twice , the power indicator, running indicator and timing indicator flicker togetherfor 1 second,then repeating the cycle.

27 48

Domestic Air Conditioner

Model: HSU-24H03/Z HSU-24C03/Z

28

49

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

REFRIGERATING CYCLE DIAGRAM

29 50

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

30

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

INSTALLATION MANUAL

31

52

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

26 26

53 32

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

3354

34 55

3556

36

37 58

Flare tool for R410A

Conventional flare tool clutch-type(Rigid-type) Wing-nut type (Imperial-type)

1.Cut pipe

2.Remove burs

Clutch-type

0~0.5mm

1.0~1.5mm

1.5~2.0mm

3.Insert the flare nut

4.Flare pipe

38

Domestic Air Conditioner

Model: HSU-24C03/Z Model: HSU-24H03/Z

39

Sincere Forever

Haier Group