MODEL TECHNICAL SPECIFICATION

SECTION-GTR (GENERAL TECHNICAL REQUIREMENT) [Rev.No.12]

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR)

CONTENTS CLAUSE NO. 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 PARTICULARS Foreword General Requirement Standards Services to be performed by the Equipment being furnished Engineering Data and Drawings Material/Workmanship Design Improvements/Coordination Quality Assurance Programme Type Testing, Inspection & Inspection Certificate Tests Packaging & Protection Finishing of Metal Surfaces Handling, Storing & Installation Tools and Tackles Auxiliary Supply Support Structure Clamps and Connectors including Terminal Connectors Control Cabinets, Junction Boxes, Terminal Boxes & Marshalling Boxes for Outdoor Equipment Auxiliary Switches Terminal Blocks and Wiring Lamps and Sockets 30 30 32 29 23 23 24 26 27 27 28 28 14 16 19 20 20 PAGE NO. 1 1 1 2

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR)

CLAUSE NO. 22.0 23.0 24.0 Annexure-A Annexure-B Annexure-C Annexure-D Annexure-E

PARTICULARS Bushings, Hollow Column Insulators, Support Insulators Motors Technical Requirement of Equipments Corona and Radio Interference Voltage (RIV) Test Seismic Withstand Test Procedure List of Specifications List of Drawings/Documents List of the makes for which type test reports not required to be submitted

PAGE NO. 32 33 34 47 50 51 73 74

--------------

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 1.0 1.1 FOREWORD The provisions under this section are intended to supplement general requirements for the materials, equipments and services covered under other sections of tender documents and is not exclusive. GENERAL REQUIREMENT The contractor shall furnish catalogues, engineering data, technical information, design documents, drawings etc., fully in conformity with the technical specification during detailed engineering. It is recognised that the Contractor may have standardised on the use of certain components, materials, processes or procedures different from those specified herein. Alternate proposals offering similar equipment based on the manufacturers standard practice will also be considered provided such proposals meet the specified designs, standard and performance requirements and are acceptable to Purchaser. Wherever a material or article is specified or defined by the name of a particular brand, Manufacturer or Vendor, the specific name mentioned shall be understood as establishing type, function and quality and not as limiting competition. For lighting fixtures, makes shall be as defined in Section- Lighting System. Equipment furnished shall be complete in every respect with all mountings, fittings, fixtures and standard accessories normally provided with such equipment and/or needed for erection, completion and safe operation of the equipment as required by applicable codes though they may not have been specifically detailed in the Technical Specifications unless included in the list of exclusions. Materials and components not specifically stated in the specification and bid price schedule but which are necessary for commissioning and satisfactory operation of the switchyard/substation unless specifically excluded shall be deemed to be included in the scope of the specification and shall be supplied without any extra cost. All similar standard components/parts of similar standard equipment provided, shall be inter-changeable with one another. STANDARDS The works covered by the specification shall be designed, engineered, manufactured, built, tested and commissioned in accordance with the Acts, Rules, Laws and Regulations of India. The equipment to be furnished under this specification shall conform to latest issue with all amendments (as on the date of bid opening) of standard specified under Annexure-C of this section, unless specifically mentioned in the specification. The Bidder shall note that standards mentioned in the specification are not mutually exclusive or complete in themselves, but intended to compliment each other. The Contractor shall also note that list of standards presented in this specification is not complete. Whenever necessary the list of standards shall be considered in conjunction with specific IS/IEC. When the specific requirements stipulated in the specifications exceed or differ than those required by the applicable standards, the stipulation of the specification shall take precedence. Other internationally accepted standards which ensure equivalent or better performance than that specified in the standards specified under Annexure-C / Page1of74

2.0 2.1

2.2

2.3

2.4

3.0 3.1

3.2

3.3

3.4

3.5

3.6

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) individual sections for various equipments shall also, be accepted, however the salient points of difference shall be clearly brought out in the Additional information schedule of the bid along with English language version of such standard. The equipment conforming to standards other than specified under Annexure-C/ individual sections for various equipments shall be subject to Purchasers approval. 4.0 4.1 SERVICES TO BE PERFORMED BY THE EQUIPMENT BEING FURNISHED The 800kV and 420kV system is being designed to limit the switching surge over voltage of 1.9 p.u. and 2.5 p.u., respectively and the power frequency over voltage of 1.4 p.u. and 1.5 p.u., respectively. In case of the 420kV system, the initial value of the temporary overvoltages could be 2.0 p.u. for 1 - 2 cycles. The equipment furnished under this specification shall perform all its functions and operate satisfactorily without showing undue strain, restrike etc under such over voltage conditions. All equipments shall also perform satisfactorily under various other electrical, electromechanical and meteorological conditions of the site of installation. All equipment shall be able to withstand all external and internal mechanical, thermal and electromechanical forces due to various factors like wind load, temperature variation, ice & snow, (wherever applicable) short circuit etc for the equipment. The bidder shall design terminal connectors of the equipment taking into account various forces that are required to withstand. The equipment shall also comply to the following: a) b) To facilitate erection of equipment, all items to be assembled at site shall be match marked. All piping, if any between equipment control cabinet/ operating mechanism to marshalling box of the equipment, shall bear proper identification to facilitate the connection at site.

4.2 4.3

4.4 4.5

4.6 4.6.1

Equipments and system shall be designed to meet the following major technical parameters as brought out hereunder. System Parameter 765kV, 400kV & 220kV System SL No 1. 2. 3. 4. 5. i) ii) Description of parameters System operating voltage Maximum operating voltage of the system(rms) Rated frequency No. of phase Rated Insulation levels Full wave impulse withstand voltage (1.2/50 microsec.) Switching impulse withstand voltage (250/2500 micro sec.) 765kV System 765kV 800kV 50HZ 3 2100kVp 1550kVp 400 kV System 400kV 420kV 50Hz 3 1550kVp 1050kVp 220 kV System 220kV 245kV 50Hz 3 1050 kVp -

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page2of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) SL No iii) Description of parameters dry and wet One minute power frequency dry withstand voltage (rms) One minute power frequency dry and wet withstand voltage (rms) Corona extinction voltage Max. radio interference voltage for frequency between 0.5 MHz and 2 MHz at 508 kV rms for 765kV, 266kV rms for 400kV system and 156kV rms for 220kV system Minimum creepage distance (25mm/kV) Min. clearances Phase to phase 765kV System 830kV 400 kV System 630kV 220 kV System -

iv) 6. 7.

508 kV 2500 micro-volts

320kV 1000 microvolt

460kV 156kV 1000 microvolt

8. 9. i.

20000 mm 7600mm (for conductorconductor configuration) 9400mm (for rod-conductor configuration) 4900mm (for conductorstructure) 6400mm (for rod- structure) 10300 mm 40kA/50kA (as applicable) Effectively earthed

10500 mm

6125 mm

ii.

Phase to earth

4000mm (for 2100 mm conductorconductor configuration) 4200mm (for rod conductor configuration) 3500 mm 2100 mm

iii) 10. 11.

Sectional clearances Rated short circuit current for 1 sec. duration System neutral earthing

6500 mm 40kA/50kA/ 63 kA (as applicable) Effectively earthed

5000 mm 40kA/ 50kA(as applicable) Effectively earthed

132kV, 66kV, 33kV & 11kV System SL No 1. 2. Description of parameters System operating voltage Maximum operating voltage of the 132 kV System 132kV 145kV 66kV System 66kV 72.5kV 33 kV System 33kV 36kV 11kV System 11kV 12kV

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page3of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) SL No 3. 4. 5. i) ii) 6. 7. Description of parameters system(rms) Rated frequency No. of phase Rated Insulation levels Full wave impulse withstand voltage (1.2/50 microsec.) One minute power frequency dry and wet withstand voltage (rms) Corona extinction voltage Max. radio interference voltage for frequency between 0.5 MHz and 2 MHz at 92KV rms for 132KV system Minimum creepage distance (25mm/kV) Min. clearances Phase to phase Phase to earth Sectional clearances Rated short circuit current for 1 sec. duration System neutral earthing 132 kV System 50Hz 3 650 kVp 275kV 105kV 500 microvolt 3625 mm 1300 mm 1300 mm 4000 mm 31.5 kA
Effectively earthed

66kV System 50Hz 3 325 kVp 140kV -

33 kV System 50Hz 3 170 kVp 70kV -

11kV System 50Hz 3 75 kVp 28kV -

8. 9. i. ii. iii) 10. 11. Note :

1813 mm 750 mm 630 mm 3000 mm 31.5 kA


Effectively earthed

900 mm 320 mm 320 mm 3000 mm 25 kA


Effectively earthed

300 mm 280 mm 140 mm 3000 mm 25 kA


Effectively earthed

1. The above parameters are applicable for installations up to an altitude of 1000m above mean sea level. For altitude exceeding 1000m, necessary altitude correction factor shall be applicable. 2. The insulation and RIV levels of the equipments shall be as per values given in the respective chapter of the equipments. 4.6.2 Major technical parameters of bushings / hollow column / support insulators are given below: 765kV, 400kV & 220kV System S.N. (a) (b) (c) Parameters Max. System voltage Um(kV) Impulse withstand voltage (dry & wet) (kVp) Switching surge withstand voltage (dry & wet) (kVp) 765 kV 800 + 2100 + 1550 400 kV 420 + 1425 + 1050 220 kV 245 + 1050 -

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page4of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) (d) (e) (f) Power frequency withstand voltage (dry and wet) (kV rms) Total creepage distance (min) (mm) 830 20000 630 10500 460 6125

Insulator shall also meet requirement of IEC- 60815 for 800 kV, 420 kV and 245 kV systems, as applicable having alternate long & short sheds.

132kV, 66kV, 33kV & 11kV System S.N. (a) (b) (c) (d) Parameters Max. System voltage Um(kV) Impulse withstand voltage (dry & wet) (kVp) Power frequency withstand voltage (dry and wet) (kV rms) Total creepage distance (min) (mm) 132 kV 145 + 650 275 3625 66 kV 72.5 + 325 140 1813 33kV 36 + 170 75 900 11kV 12 + 75 28 300

4.6.3

Major Technical Parameters The major technical parameters of the equipments are given below. For other parameters and features respective technical sections should be referred.

4.6.3.1

(A)

For (765/3)/(400/3)/33 kV Single Phase Auto Transformer Voltage ratio (kV) Rated frequency (Hz) Max. Design Ambient Temp. (C) Windings (i) (ii) (iii) System Fault level (KA) 1.2/50 micro sec. impulse withstand voltage kVp 20/200/500 micro second switching surge withstand voltage kVp One minute power frequency voltage kV (rms) Winding connection Neutral Insulation (765/3)/(400/3)/33 50 50 HV 40 1950 1550 IV 40/50/63 (As applicable) 1300 1050 250 LV 25

(iv)

95

(v) (vi) (vii)

Star

Star

delta

- Solidly grounded - Solidly grounded -

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page5of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) (viii) Vector Group (B) For 765/3 KV Shunt Reactor Shunt Reactor Rated Voltage (KV) System fault level (KA) (a) Lightning impulse 1.2/50 micro seconds withstand voltage (kVp) Switching surge impulse 20/200/500 micro seconds voltage (kVp) Impulse withstand voltage (kVp) Power frequency voltage (rms) 765/3 kV 40 1950 - YN a0 d11

(b)

1550

Insulation level of neutral (a) (b) (C) 550 230

Neutral Grounding Reactor Rated voltage from insulation strength considerations Rated frequency No. of phases Type Insulation Max. continuous current (rms) Rated short time current (rms) (60secs.) 145kV 50Hz One Dry type air core for outdoor application Graded/uniform 20 A 240A (however the NGR shall be designed for a current rating of 600A (rms) short time current to ensure mechanical robustness.

Rated impedance at rated short time and continuous current Connection Insulation level for winding

As per section - project Between neutral of shunt reactor and ground Line side Ground side 95

(i)

Lighting impulse (1.2/50 microsec )withstand voltage (kVp)

550

(ii)

One minute power frequency withstand

230

38

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page6of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) voltage (kVrms) Method of grounding Solidly connected between neutral of shunt reactor and earth. Mounting of NGR a) Type b) Minimum Creepage c) 1 min. Power frequency withstand voltage d) Lighting impulse (1.2/50 microsec) withstand voltage (kVp) (ii) Mounting structure (D) Rated voltage (kV, rms) Rated frequency (Hz) No. of poles Design ambient temperature (C) Rated Insulation levels : 1) Full wave impulse withstand voltage (1.2/50 microsec.) between line terminals and ground between terminals with circuit breaker/ Isolator open 2100 kV peak 2100 kVp impulse on one terminal and 455 kVp power frequency voltage of opposite polarity on other terminal Non magnetic material 800 50 3 50 For 800 kV Circuit Breaker and Isolator 110 kVp Pedestal insulator Porcelain/ silicon rubber 438 mm 38 kV rms

2)

Switching impulse withstand voltage (250/2500 micro-second) dry and wet between line terminals and ground between terminals with circuit breaker/ Isolator open 1550 kV peak 1175 kVp impulse on one terminal and 650 kVp power frequency voltage of opposite polarity on other terminal

3)

One minute power frequency dry withstand voltage between line terminals and ground 830 kV rms

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page7of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) between terminals with circuit breaker/ Isolator open 1150 kV rms

Corona extinction voltage with Circuit Breaker/Isolator in all positions Max. radio interference voltage (micro volts) for frequency between 0.5 MHz and 2 MHz at 508 kV rms. in all positions Minimum Creepage distance:i) ii) Phase to ground (mm)

508 KV rms (min)

2500

20000 18000 0.3g horizontal 10 A at 220 V DC 2 A DC with circuit time constant not less than 20 ms. Effectively Earthed

Between CB Terminals (mm)

Seismic acceleration Thermal Rating of Auxiliary Contacts Breaking Capacity of auxiliary contacts System neutral earthing

Auxiliary switch shall also comply with other clauses of this chapter. (E) FOR 800 kV CT/CVT/SA Max. System voltage (kV, rms) Rated frequency (Hz) Design ambient temperature (C) Rated Insulation levels : 1) Full Insulation levels : between line terminals and ground for CT and CVT For arrester housing 2100 kV peak 800 50 50

2)

As per IEC 60099-4

Switching impulse withstand voltage (250/2500 micro second) dry and wet between line terminals and ground for CT and CVT For arrester housing between line terminals and ground for CT and CVT 975 kV rms. 1150 kV peak

3) -

As per IEC 60099-4

One minute power frequency dry withstand voltage

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page8of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) Corona extinction voltage for CT/CVT. Max. radio interference voltage for frequency between 0.5 MHz and 2 MHz at 508 KV rms (Micro volts) Min. Creepage distance :Seismic acceleration Partial discharge :for arrester at 1.05 COV for CT/CVT Less than or equal to 10pc As per IEC Effectively earthed 20000 mm 0.3g horizontal 2500 for CT/CVT 508 KV rms (min)

System neutral earthing (F) For 400/220/33 kV Auto Transformer Voltage ratio (kV) Rated frequency (Hz) Max. Design Ambient Temp. (C) Windings (i) (ii) (iii) System Fault level (KA) 1.2/50 micro sec. impulse withstand voltage kVp 20/200/500 micro second switching surge withstand voltage kVp One minute power frequency voltage kV (rms) Winding connection Neutral Insulation

400/220/33 50 50 HV 40/50/63 (As applicable) 1300 1050 950 250 IV 40 LV 25

(iv)

95

(v) (vi) (vii) (G)

Star

Star

delta

- Solidly grounded - Solidly grounded - YN a0 d11

(viii) Vector Group For 400 KV Shunt Reactor & NGR Shunt Reactor Rated Voltage (KV) System fault level (KA) (a) Lightning impulse 1.2/50 micro seconds withstand voltage (kVp)

420 (1.0 pu) 40/50/63 (As applicable) 1300

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page9of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) (b) Switching surge impulse 20/200/500 micro seconds voltage (kVp) Impulse withstand voltage (kVp) Power frequency voltage (rms) 1050

Insulation level of neutral (a) (b) 550 230

Neutral Grounding Reactor Rated voltage from insulation strength considerations (KV) Rated frequency (Hz) No. of Phases Insulation level for winding (i) Lightning impulse (1.2/ 50 micro seconds) withstand voltage (kVp) One minute power frequency withstand voltage (kV rms) 145 50 One Line Side 550 Ground Side 95

(ii) (H)

230

38

For 420 kV Circuit Breaker and Isolator Rated voltage (kV, rms) Rated frequency (Hz) No. of poles Design ambient temperature (C) Rated Insulation levels : 1) Full wave impulse withstand voltage (1.2/50 microsec.) between line terminals and ground between terminals with circuit breaker/ Isolator open 1425 kV peak 1425 kVp impulse on one terminal and 240 kVp power frequency voltage of opposite polarity on other terminal 420 50 3 50

2)

Switching impulse withstand voltage (250/2500 micro-second) dry and wet between line terminals and ground between terminals with circuit breaker/ Isolator open 1050 kV peak 900 kVp impulse on one terminal and 345 kVp power frequency voltage of opposite polarity on other terminal Page10of74

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 3) One minute power frequency dry withstand voltage between line terminals and ground between terminals with circuit breaker/ Isolator open 520 kV rms 610 kV rms

Corona extinction voltage (kV rms) with Circuit Breaker/Isolator in all positions Max. radio interference voltage (micro volts) for frequency between 0.5 MHz and 2 MHz at 266 kV rms. in all positions Minimum Creepage distance:i) ii) Phase to ground (mm) Between CB Terminals (mm)

320 (min)

1000

10500 10500 6000/7000 mm (as applicable) 0.3g horizontal 10 A at 220 V DC 2 A DC with circuit time constant not less than 20 ms. Effectively Earthed

Phase to phase spacing Seismic acceleration Thermal Rating of Auxiliary Contacts Breaking Capacity of auxiliary contacts System neutral earthing (I) FOR 420 kV CT/CVT/SA Rated voltage (kV, rms) Rated frequency (Hz) No. of poles Design ambient temperature (C) Rated Insulation levels : 1) Full Insulation levels : between line terminals and ground for CT and CVT For arrester housing

Auxiliary switch shall also comply with other clauses of this chapter. 420 50 1 50

1425 kV peak

2)

1425 kV peak

Switching impulse withstand voltage (250/2500 micro second) dry and wet

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page11of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) between line terminals and ground for CT and CVT For arrester housing between line terminals and ground for CT and CVT For arrester housing Corona extinction voltage (kV rms) for CT/CVT. Max. radio interference voltage for frequency between 0.5 MHz and 2 MHz at 266 kV rms (Micro volts) Min. Creepage distance :Phase to ground (mm) Seismic acceleration Partial discharge :(J) for arrester at 1.05 COV for CT/CVT Not exceeding 50 pc. Not exceeding 10 pC. Effectively earthed 245 50 3 50 145 50 3 50 10500 0.3g horizontal 630 kV rms. (dry) 630 kV rms (dry & wet) 320 (min) 1000 for CT/CVT 500 for SA 1050 kVp peak

3) -

1050 kV peak

One minute power frequency withstand voltage

System neutral earthing Rated voltage kV (rms) Rated frequency (Hz) No. of Poles Design ambinet temperature (C) Rated insulation levels : 1) 2) -

For 245 kV & 145 kV Circuit Breaker and Isolator

Full wave impulse withstand voltage (1.2/50 micro sec.) between line terminals and ground between terminals with circuit breaker open between terminals with isolator open between line terminals and ground between terminals with circuit breaker open 1050 kVp 1050 kVp 1200 kVp 650 kVp 650 kVp 750 kVp

One minute power frequency dry and wet withstand voltage 460 kV (rms) 460 kV (rms) 275 kV (rms) 275 kV (rms)

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page12of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) between terminals with Isolator open 530 kV (rms) 1000 (at 156 kV rms) 315kV (rms) 500 (at 92 kV rms)

Max. radio interference voltage (microvolts) for frequency between 0.5 MHz and 2 MHz in all positions of the equipments. Minimum creepage distance :Phase to ground (mm) Between CB Terminals (mm) System neutral earthing Seismic acceleration Rating of Auxiliary Contacts Breaking capacity of Auxiliary Contacts Phase to phase spacing (mm) (K) FOR 245 kV & 145 kV CT/CVT/SA Rated voltage kV (rms) Rated frequency (Hz) No. of poles Design ambient temperature (C) Rated insulation levels : 1) 2) -

6125 6125 Effectively earthed

3625 3625 Effectively earthed

- 0.3g horizontal 10 A at 220/110 V DC (as applicable) 2 A DC with circuit time constant of not less than 20ms. 4500 or 4000 3000 or 2700

Auxiliary Switch shall also comply with other clauses of this chapter. 245 50 1 50 145 50 1 50

Full wave impulse withstand voltage (1.2/50 micro sec.) between line terminals and ground for CT and CVT for arrester housing between line terminals and ground for CT and CVT for arrester housing 1050 kVp 1050 kV peak 460 kV rms 460 kV rms 1000 for CT/CVT 500 for SA (at 156 kV rms) 650 kVp 650 kVp 275 kV rms 275kV rms 500 (at 92 kV rms)

One minute power frequency dry and wet withstand voltage

Max. radio interference voltage (microvolts) for frequency between 0.5 MHz and 2 MHz in all positions of the equipment. Minimum creepage distance :Phase to ground (mm) System neutral earthing TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

6125

3625

- Effectively earthed Page13of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) Seismic acceleration Partial discharge for :(L) Surge arrester at 1.05 COV for CT/CVT - Not exceeding 50 pc. - Not exceeding 10 pc. 72.5 50 3 50 36 50 3 3 - 0.3g horizontal -

For 72.5 kV AND 36 kV EQUIPMENTS Rated Voltage KV (rms) Rated frequency (Hz) No. of Poles Design ambient temperature (C) Rated insulation levels : 1) 2) Full wave impulse withstand voltage (1.2/50 micro sec.) between line terminals and ground between terminals with Isolator open voltage between line terminals and ground between terminals with Isolator open 140 kV (rms) 160 kV (rms) 70 kV (rms) 80 kV (rms) 325 kVp 375 kVp 170 kVp 180 kVp

One minute power frequency dry and wet withstand

Minimum creepage distance :Phase to ground (mm) Seismic acceleration Rating of Auxiliary Contacts Breaking capacity of Auxiliary Contacts Phase to phase spacing (mm) 5.0 5.1 ENGINEERING DATA AND DRAWINGS The list of drawings/documents which are to be submitted to the Purchaser shall be discussed and finalised by the Purchaser at the time of award. The Contractor shall necessarily submit all the drawings/ documents unless anything is waived. 5.2 The Contractor shall submit 4 (four) sets of drawings/ design documents /data / detailed bill of quantity and 1 (one) set of test reports for the approval of the Purchaser. The contractor shall also submit the softcopy of the above documents in addition to hardcopy. Drawings Page14of74 1813 900 -- 0.3g horizontal -10A at 220/110V DC (As applicable) 2 A DC with circuit time constant of not less than 20 ms. 2000 1500

Auxiliary Switch shall also comply with other clauses of this chapter.

5.3

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 5.3.1 All drawings submitted by the Contractor shall be in sufficient detail to indicate the type, size, arrangement, material description, Bill of Materials, weight of each component, break-up for packing and shipment, dimensions, internal & the external connections, fixing arrangement required and any other information specifically requested in the specifications. Drawings submitted by the Contractor shall be clearly marked with the name of the Purchaser, the unit designation, the specifications title, the specification number and the name of the Project. POWERGRID has standardized a large number of drawings/documents of various make including type test reports which can be used for all projects having similar requirements and in such cases no project specific approval (except for list of applicable drawings alongwith type test reports) is required. However, distribution copies of standard drawings/documents shall be submitted as per provision of the contract. All titles, noting, markings and writings on the drawing shall be in English. All the dimensions should be in SI units. The review of these data by the Purchaser will cover only general conformance of the data to the specifications and documents, interfaces with the equipment provided under the specifications, external connections and of the dimensions which might affect substation layout. This review by the Purchaser may not indicate a thorough review of all dimensions, quantities and details of the equipment, materials, any devices or items indicated or the accuracy of the information submitted. This review and/or approval by the Purchaser shall not be considered by the Contractor, as limiting any of his responsibilities and liabilities for mistakes and deviations from the requirements, specified under these specifications and documents. All manufacturing and fabrication work in connection with the equipment prior to the approval of the drawings shall be at the Contractors risk. The Contractor may make any changes in the design which are necessary to make the equipment conform to the provisions and intent of the Contract and such changes will again be subject to approval by the Purchaser. Approval of Contractors drawing or work by the Purchaser shall not relieve the contractor of any of his responsibilities and liabilities under the Contract. All engineering data submitted by the Contractor after final process including review and approval by the Purchaser shall form part of the Contract Document and the entire works performed under these specifications shall be performed in strict conformity, unless otherwise expressly requested by the Purchaser in Writing. Approval Procedure The scheduled dates for the submission of the drawings as well as for, any data/information to be furnished by the Purchaser would be discussed and finalised at the time of award. The following schedule shall be followed generally for approval and for providing final documentation. i) Approval/comments/ by Purchaser on initial submission Resubmission (whenever required) Approval or comments As per agreed schedule Within 3 (three) weeks from date of comments Within 3 (three) weeks of receipt of resubmission.

5.3.2

5.3.3

5.5

5.6

5.7

ii)

iii)

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page15of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) iv) Furnishing of distribution copies (5 hard copies per substation and one scanned copy (pdf format) for Corporate Centre) Furnishing of distribution copies of test reports (a) Type test reports (one scanned softcopy in pdf format per substation plus one for corporate centre & one hardcopy per substation) (b) Routine Test Reports (one copy for each substation) vi) Furnishing of instruction/ operation manuals (2 copies per substation and one softcopy (pdf format) for corporate centre & per substation) 2 weeks from the date of final approval 2 weeks from the date of approval

v)

-do-

As per agreed schedule

(vii) As built drawings (two sets of hardcopy per substation & one softcopy (pdf format) for corporate centre& per substation) NOTE : (1)

On completion of entire works

The contractor may please note that all resubmissions must incorporate all comments given in the earlier submission by the Purchaser or adequate justification for not incorporating the same must be submitted failing which the submission of documents is likely to be returned. All drawings should be submitted in softcopy form, however substation design drawings like SLD, GA, all layouts etc. shall also be submitted in AutoCAD Version. SLD, GA & layout drawings shall be submitted for the entire substation in case of substation extension also. The instruction Manuals shall contain full details of drawings of all equipment being supplied under this contract, their exploded diagrams with complete instructions for storage, handling, erection, commissioning, testing, operation, trouble shooting, servicing and overhauling procedures. If after the commissioning and initial operation of the substation, the instruction manuals require any modifications/ additions/changes, the same shall be incorporated and the updated final instruction manuals shall be submitted by the Contractor to the Purchaser. The Contractor shall furnish to the Purchaser catalogues of spare parts. All As-built drawings/documents shall be certified by site indicating the changes before final submission.

(2)

(3)

(4)

(5) (6) 5.8 6.0 6.1

The list of major drawings and General Technical Parameters to qualify for second advance as per Section SCC shall be as per Annexure D. MATERIAL/ WORKMANSHIP General Requirement Page16of74

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 6.1.1 Where the specification does not contain references to workmanship, equipment, materials and components of the covered equipment, it is essential that the same must be new, of highest grade of the best quality of their kind, conforming to best engineering practice and suitable for the purpose for which they are intended. Incase where the equipment, materials or components are indicated in the specification as similar to any special standard, the Purchaser shall decide upon the question of similarity. When required by the specification or when required by the Purchaser the Contractor shall submit, for approval, all the information concerning the materials or components to be used in manufacture. Machinery, equipment, materials and components supplied, installed or used without such approval shall run the risk of subsequent rejection, it being understood that the cost as well as the time delay associated with the rejection shall be borne by the Contractor. The design of the Works shall be such that installation, future expansions, replacements and general maintenance may be undertaken with a minimum of time and expenses. Each component shall be designed to be consistent with its duty and suitable factors of safety, subject to mutual agreements. All joints and fastenings shall be devised, constructed and documented so that the component parts shall be accurately positioned and restrained to fulfill their required function. In general, screw threads shall be standard metric threads. The use of other thread forms will only be permitted when prior approval has been obtained from the Purchaser. Whenever possible, all similar part of the Works shall be made to gauge and shall also be made interchangeable with similar parts. All spare parts shall also be interchangeable and shall be made of the same materials and workmanship as the corresponding parts of the Equipment supplied under the Specification. Where feasible, common component units shall be employed in different pieces of equipment in order to minimize spare parts stocking requirements. All equipment of the same type and rating shall be physically and electrically interchangeable. All materials and equipment shall be installed in strict accordance with the manufacturers recommendation(s). Only first-class work in accordance with the best modern practices will be accepted. Installation shall be considered as being the erection of equipment at its permanent location. This, unless otherwise specified, shall include unpacking, cleaning and lifting into position, grouting, levelling, aligning, coupling of or bolting down to previously installed equipment bases/foundations, performing the alignment check and final adjustment prior to initial operation, testing and commissioning in accordance with the manufacturers tolerances, instructions and the Specification. All factory assembled rotating machinery shall be checked for alignment and adjustments made as necessary to re-establish the manufacturers limits suitable guards shall be provided for the protection of personnel on all exposed rotating and / or moving machine parts and shall be designed for easy installation and removal for maintenance purposes. The spare equipment(s) shall be installed at designated locations and tested for healthiness. The Contractor shall apply oil and grease of the proper specification to suit the machinery, as is necessary for the installation of the equipment. Lubricants used for installation purposes shall be drained out and the system flushed through where necessary for applying the lubricant required for operation. The Contractor shall apply all operational lubricants to the equipment installed by him. All oil, grease and other consumables used in the Works/ Equipment shall be purchased in India unless the Contractor has any special requirement for the specific application of a type of oil or grease not available in India. In such is the Page17of74

6.1.2

6.1.3

6.1.4

6.1.5

6.1.6

6.1.7

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) case he shall declare in the proposal, where such oil or grease is available. He shall help Purchaser in establishing equivalent Indian make and Indian Contractor. The same shall be applicable to other consumables too. 6.1.8 Corona and radio interference voltage test and seismic withstand test (for 132kV and above voltage level) procedures for equipments shall be in line with the procedure given at Annexure-A and B respectively. Provisions For Exposure to Hot and Humid climate Outdoor equipment supplied under the specification shall be suitable for service and storage under tropical conditions of high temperature, high humidity, heavy rainfall and environment favourable to the growth of fungi and mildew. The indoor equipments located in non-air conditioned areas shall also be of same type. 6.2.1 6.2.1.1 6.2.1.2 Space Heaters The heaters shall be suitable for continuous operation at 240V as supply voltage. On-off switch and fuse shall be provided. One or more adequately rated thermostatically connected heaters shall be supplied to prevent condensation in any compartment. The heaters shall be installed in the compartment and electrical connections shall be made sufficiently away from below the heaters to minimize deterioration of supply wire insulation. The heaters shall be suitable to maintain the compartment temperature to prevent condensation. Suitable anti condensation heaters with the provision of thermostat shall be provided. FUNGI STATIC VARNISH Besides the space heaters, special moisture and fungus resistant varnish shall be applied on parts which may be subjected or predisposed to the formation of fungi due to the presence or deposit of nutrient substances. The varnish shall not be applied to any surface of part where the treatment will interfere with the operation or performance of the equipment. Such surfaces or parts shall be protected against the application of the varnish. 6.2.3 Ventilation opening Wherever ventilation is provided, the compartments shall have ventilation openings with fine wire mesh of brass to prevent the entry of insects and to reduce to a minimum the entry of dirt and dust. Outdoor compartment openings shall be provided with shutter type blinds and suitable provision shall be made so as to avoid any communication of air / dust with any part in the enclosures of the Control Cabinets, Junction boxes and Marshalling Boxes, panels etc. 6.2.4 Degree of Protection The enclosures of the Control Cabinets, Junction boxes and Marshalling Boxes, panels etc. to be installed shall provide degree of protection as detailed here under: a) b) c) d) e) Installed out door: IP- 55 Installed indoor in air conditioned area: IP-31 Installed in covered area: IP-52 Installed indoor in non air conditioned area where possibility of entry of water is limited: IP-41. For LT Switchgear (AC & DC distribution Boards) : IP-52 Page18of74

6.2

6.2.1.3 6.2.2

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) The degree of protection shall be in accordance with IS:13947 (Part-I) / IEC-60947 (Part-I) / IS 12063 / IEC-60529. Type test report for degree of protection test, shall be submitted for approval. 6.3 6.3.1 RATING PLATES, NAME PLATES AND LABELS Each main and auxiliary item of substation is to have permanently attached to it in a conspicuous position a rating plate of non-corrosive material upon which is to be engraved manufacturers name, year of manufacture, equipment name, type or serial number together with details of the loading conditions under which the item of substation in question has been designed to operate, and such diagram plates as may be required by the Purchaser. The rating plate of each equipment shall be according to IEC requirement. All such nameplates, instruction plates, rating plates of transformers, reactors, CB, CT, CVT, SA, Isolators, C & R panels and PLCC equipments shall be bilingual with Hindi inscription first followed by English. Alternatively two separate plates one with Hindi and the other with English inscriptions may be provided. FIRST FILL OF CONSUMABLES, OIL AND LUBRICANTS All the first fill of consumables such as oils, lubricants, filling compounds, touch up paints, soldering/brazing material for all copper piping of circuit breakers and essential chemicals etc. which will be required to put the equipment covered under the scope of the specifications, into successful Operation, shall be furnished by the Contractor unless specifically excluded under the exclusions in these specifications and documents. 7.0 7.1 DESIGN IMPROVEMENTS / COORDINATION The bidder shall note that the equipment offered by him in the bid only shall be accepted for supply. However, the Purchaser or the Contractor may propose changes in the specification of the equipment or quality thereof and if the Purchaser & contractor agree upon any such changes, the specification shall be modified accordingly. If any such agreed upon change is such that it affects the price and schedule of completion, the parties shall agree in writing as to the extent of any change in the price and/or schedule of completion before the Contractor proceeds with the change. Following such agreement, the provision thereof, shall be deemed to have been amended accordingly. The Contractor shall be responsible for the selection and design of appropriate equipments to provide the best co-ordinated performance of the entire system. The basic design requirements are detailed out in this Specification. The design of various components, sub-assemblies and assemblies shall be so done that it facilitates easy field assembly and maintenance. The Contractor has to coordinate designs and terminations with the agencies (if any) who are Consultants/Contractor for the Purchaser. The names of agencies shall be intimated to the successful bidders. The Contractor will be called upon to attend design co-ordination meetings with the Engineer, other Contractors and the Consultants of the Purchaser (if any) during the period of Contract. The Contractor shall attend such meetings at his own cost at POWERGRID Corporate Centre, Gurgaon (Haryana) or at mutually agreed venue as and when required and fully cooperate with such persons and agencies involved during those discussions.

6.3.2

6.4

7.2

7.3

7.4

7.5

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page19of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 8.0 8.1 QUALITY ASSURANCE PROGRAMME To ensure that the equipment and services under the scope of this Contract whether manufactured or performed within the Contractors Works or at his Subcontractors premises or at the Purchasers site or at any other place of Work are in accordance with the specifications, the Contractor shall adopt suitable quality assurance programme to control such activities at all points necessary. Such programme shall be broadly outlined by the contractor and finalised after discussions before the award of contract. The detailed programme shall be submitted by the contractor after the award for reference. A quality assurance programme of the contractor shall generally cover the following: (a) (b) (c) (d) His organisation structure for the management and implementation of the proposed quality assurance programme: Documentation control system; Qualification data for bidders key personnel; The procedure for purchases of materials, parts components and selection of sub-Contractors services including vendor analysis, source inspection, incoming raw material inspection, verification of material purchases etc. System for shop manufacturing and site erection controls including process controls and fabrication and assembly control; Control of non-conforming items and system for corrective actions; Inspection and test procedure both for manufacture and field activities. Control of calibration and testing of measuring instruments and field activities; System for indication and appraisal of inspection status; System for quality audits; System for authorising release of manufactured product to the Purcahser. System for maintenance of records; System for handling storage and delivery; and A quality plan detailing out the specific quality control measures and procedures adopted for controlling the quality characteristics relevant to each item of equipment furnished and/or services rendered.

(e) (f) (g) (h) (i) (j) (k) (l) (m) (n)

The Purchaser or his duly authorised representative reserves the right to carry out quality audit and quality surveillance of the system and procedure of the Contractor/his vendors quality management and control activities. 8.2 Quality Assurance Documents The contractor would be required to submit all the Quality Assurance Documents as stipulated in the Quality Plan at the time of purchasers inspection of equipment/material 9.0 9.1 TYPE TESTING, INSPECTION, TESTING & INSPECTION CERTIFICATE All equipment being supplied shall conform to type tests as per technical specification and shall be subject to routine tests in accordance with requirements stipulated under respective sections. The reports for all type tests as per technical specification shall be furnished by the Contractor alongwith equipment / material drawings. However, type test reports of similar equipments/ material already accepted in POWERGRID shall be Page20of74

9.2

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) applicable for all project with similar requirement. The type tests conducted earlier should have either been conducted in accredited laboratory (accredited based on ISO / IEC Guide 25 / 17025 or EN 45001 by the national accreditation body of the country where laboratory is located) or witnessed by POWERGRID or representative authorized by POWERGRID or Utility or representative of accredited test lab or reputed consultant. The test reports submitted shall be of the tests conducted within last 10 (ten) years prior to the date of bid opening. In case the test reports are of the test conducted earlier than 10 (ten) years prior to the date of bid opening, the contractor shall repeat these test(s) at no extra cost to the purchaser. However, in case of instrument transformers, the following type tests should have been conducted within 5 (five) years prior to the date of bid opening. i) ii) iii) iv) Lightning Impulse Test Switching Impulse Test Multiple Chopped Impulse Test (For CT) Chopped Impulse Test (For CVT )

In case the test reports are of these tests (for instrument transformers) as mentioned above are conducted earlier than 5 (five) years prior to the date of bid opening, the contractor shall repeat these test(s) at no extra cost to the purchaser. Further, in the event of any discrepancy in the test reports i.e. any test report not acceptable due to any design/manufacturing changes (including substitution of components) or due to non-compliance with the requirement stipulated in the Technical Specification or any/all type tests not carried out, same shall be carried out without any additional cost implication to the Purchaser. The Contractor shall intimate the Purchaser the detailed program about the tests atleast two (2) weeks in advance in case of domestic supplies & six (6) weeks in advance in case of foreign supplies. Further, in case type tests are required to be conducted/repeated and the deputation of Inspector/Purchaser's representative is required, then all the expenses shall be borne by the contractor. 9.3 The Purchaser intends to repeat the type tests on Power Transformer and Shunt Reactor except Dynamic short circuit tests on transformers, for which test charges shall be payable as per provision of contract. The price of conducting type tests shall be included in Bid price and break up of these shall be given in the relevant schedule of Bid Proposal Sheets. These Type test charges would be considered in bid evaluation. In case Bidder does not indicate charges for any of the type tests or does not mention the name of any test in the price schedules, it will be presumed that the particular test has been offered free of charge. Further, in case any Bidder indicates that he shall not carry out a particular test, his offer shall be considered incomplete and shall be liable to be rejected. The Purchaser reserves the right to witness any or all the type tests. The Purchaser also reserves the right to waive the repeating of type tests partly or fully and in case of waival, test charges for the same shall not be payable. The Purchaser shall bear all expenses for deputation of purchasers representative(s) for witnessing the type tests under this clause except in the case of re-deputation if any, necessitated due to no fault of the purchaser. For outdoor receptacles, trefoil clamps, diesel engine, alternator, motors, cable glands, lighting fixtures, ACSR/AAC conductor, IPS aluminum tube and junction TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page21of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) boxes, type test reports are not required to be submitted for the makes indicated at Annexure-E / POWERGRID approved list of subvendors. For the new makes (other than those indicated at Annexure-E / POWERGRID approved list of subvendors), type test reports as per relevant standard shall be submitted for purchasers approval. 9.4 The Purchaser, his duly authorised representative and/or outside inspection agency acting on behalf of the Purchaser shall have at all reasonable times free access to the Contractors/sub-vendors premises or Works and shall have the power at all reasonable times to inspect and examine the materials and workmanship of the Works during its manufacture or erection if part of the Works is being manufactured or assembled at other premises or works, the Contractor shall obtain for the Engineer and for his duly authorised representative permission to inspect as if the works were manufactured or assembled on the Contractors own premises or works. Inspection may be made at any stage of manufacture, despatch or at site at the option of the Purchaser and the equipment if found unsatisfactory due to bad workmanship or quality, material is liable to be rejected. The Contractor shall give the Purchaser /Inspector fifteen (15) days written notice for on-shore and six (6) weeks notice for off-shore material being ready for joint testing including contractor and POWERGRID. Such tests shall be to the Contractors account except for the expenses of the Inspector. The Purchaser /inspector, unless witnessing of the tests is virtually waived, will attend such tests within fifteen (15) days of the date of which the equipment is notified as being ready for test/inspection, failing which the Contractor may proceed alone with the test which shall be deemed to have been made in the Inspectors presence and he shall forthwith forward to the Inspector duly certified copies of tests in triplicate. The Purchaser or Inspector shall, within fifteen (15) days from the date of inspection as defined herein give notice in writing to the Contractor, of any objection to any drawings and all or any equipment and workmanship which in his opinion is not in accordance with the Contract. The Contractor shall give due consideration to such objections and shall either make the modifications that may be necessary to meet the said objections or shall confirm in writing to the Purchaser /Inspector giving reasons therein, that no modifications are necessary to comply with the Contract. When the factory tests have been completed at the Contractors or SubContractors works, the Purchaser/inspector shall issue a certificate to this effect within fifteen (15) days after completion of tests but if the tests are not witnessed by the Purchaser /Inspector, the certificate shall be issued within fifteen (15) days of receipt of the Contractors Test certificate by the Engineer/Inspector. Failure of the Purchaser /Inspector to issue such a certificate shall not prevent the Contractor from proceeding with the Works. The completion of these tests or the issue of the certificate shall not bind the Purchaser to accept the equipment should, it, on further tests after erection, be found not to comply with the Contract. The equipment shall be dispatched to site only after approval of test reports and issuance of CIP by the Purchaser. In all cases where the Contract provides for tests whether at the premises or at the works of the Contractor or of any Sub-Contractor, the Contractor except where otherwise specified shall provide free of charge such items as labour, materials, electricity, fuel, water, stores, apparatus and instruments as may be reasonably demanded by the Purchaser /Inspector or his authorised representative to carry out effectively such tests of the equipment in accordance with the Contract and shall give facilities to the Purchaser /Inspector or to his authorised representative to accomplish testing. Page22of74

9.5

9.6

9.7

9.8

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 9.9 The inspection by Purchaser and issue of Inspection Certificate thereon shall in no way limit the liabilities and responsibilities of the Contractor in respect of the agreed quality assurance programme forming a part of the Contract. The Purchaser will have the right of having at his own expenses any other test(s) of reasonable nature carried out at Contractors premises or at site or in any other place in addition of aforesaid type and routine tests, to satisfy that the material comply with the specification. The Purchaser reserves the right for getting any field tests not specified in respective sections of the technical specification conducted on the completely assembled equipment at site. The testing equipments for these tests shall be provided by the Purchaser. TESTS Pre-commissioning Tests On completion of erection of the equipment and before charging, each item of the equipment shall be thoroughly cleaned and then inspected jointly by the Purchaser and the Contractor for correctness and completeness of installation and acceptability for charging, leading to initial pre-commissioning tests at Site. The list of pre-commissioning tests to be performed are given in respective chapters and shall be included in the Contractors quality assurance programme. 10.2 10.2.1 Commissioning Tests The available instrumentation and control equipment will to be used during such tests and the Purchaser will calibrate, all such measuring equipment and devices as far as practicable. Any special equipment, tools and tackles required for the successful completion of the Commissioning Tests shall be provided by the Contractor, free of cost. The specific tests requirement on equipment have been brought out in the respective chapters of the technical specification. The Contractor shall be responsible for obtaining statutory clearances from the concerned authorities for commissioning the equipment and the switchyard. However necessary fee shall be reimbursed by POWERGRID on production of requisite documents. PACKAGING & PROTECTION All the equipments shall be suitably protected, coated, covered or boxed and crated to prevent damage or deterioration during transit, handling and storage at Site till the time of erection. On request of the Purchaser, the Contractor shall also submit packing details/associated drawing for any equipment/material under his scope of supply, to facilitate the Purchaser to repack any equipment/material at a later date, in case the need arises. While packing all the materials, the limitation from the point of view of availability of Railway wagon sizes in India should be taken into account. The Contractor shall be responsible for any loss or damage during transportation, handling and storage due to improper packing. Any demurrage, wharfage and other such charges claimed by the transporters, railways etc. shall be to the account of the Contractor. Purchaser takes no responsibility of the availability of the wagons. All coated surfaces shall be protected against abrasion, impact, discolouration and any other damages. All exposed threaded portions shall be suitably protected with either a metallic or a non-metallic protecting device. All ends of all valves and

9.10

9.11

10.0 10.1

10.2.2 10.2.3 10.3

11.0 11.1

11.2

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page23of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) pipings and conduit equipment connections shall be properly sealed with suitable devices to protect them from damage. 12.0 12.1 FINISHING OF METAL SURFACES All metal surfaces shall be subjected to treatment for anti-corrosion protection. All ferrous surfaces for external use unless otherwise stated elsewhere in the specification or specifically agreed, shall be hot-dip galvanized after fabrication. High tensile steel nuts & bolts and spring washers shall be electro galvanized to service condition 4. All steel conductors including those used for earthing/grounding (above ground level) shall also be galvanized according to IS: 2629. HOT DIP GALVANISING The minimum weight of the zinc coating shall be 610 gm/sq.m and minimum average thickness of coating shall be 86 microns for all items having thickness 6mm and above. For items lower than 6mm thickness requirement of coating thickness shall be as per relevant ASTM. For surface which shall be embedded in concrete, the zinc coating shall be 610 gm/sq. m minimum. The galvanized surfaces shall consist of a continuous and uniform thick coating of zinc, firmly adhering to the surface of steel. The finished surface shall be clean and smooth and shall be free from defects like discoloured patches, bare spots, unevenness of coating, spelter which is loosely attached to the steel globules, spiky deposits, blistered surface, flaking or peeling off, etc. The presence of any of these defects noticed on visual or microscopic inspection shall render the material liable to rejection. After galvanizing. no drilling or welding shall be performed on the galvanized parts of the equipment excepting that nuts may be threaded after galvanizing. Sodium dichromate treatment shall be provided to avoid formation of white rust after hot dip galvanization. The galvanized steel shall be subjected to six one minute dips in copper sulphate solution as per IS-2633. Sharp edges with radii less than 2.5 mm shall be able to withstand four immersions of the Standard Preece test. All other coatings shall withstand six immersions. The following galvanizing tests should essentially be performed as per relevant Indian Standards. 12.2.6 Coating thickness Uniformity of zinc Adhesion test Mass of zinc coating

12.2 12.2.1

12.2.2

12.2.3

12.2.4 12.2.5

Galvanised material must be transported properly to ensure that galvanised surfaces are not damaged during transit. Application of zinc rich paint at site shall not be allowed.

12.3
12.3.1

PAINTING
All sheet steel work shall be degreased, pickled, phosphated in accordance with the IS-6005 Code of practice for phosphating iron and sheet. All surfaces, which will not be easily accessible after shop assembly, shall beforehand be treated and protected for the life of the equipment. The surfaces, which are to be finished painted after installation or require corrosion protection until installation, shall be shop painted with at least two coats of primer. Oil, grease, dirt and swaf shall be thoroughly removed by emulsion cleaning. Rust and scale shall be removed by Page24of74

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) pickling with dilute acid followed by washing with running water, rinsing with slightly alkaline hot water and drying. 12.3.2 After phosphating, thorough rinsing shall be carried out with clean water followed by final rinsing with dilute dichromate solution and oven drying. The phosphate coating shall be sealed with application of two coats of ready mixed, stoving type zinc chromate primer. The first coat may be flash dried while the second coat shall be stoved. After application of the primer, two coats of finishing synthetic enamel paint shall be applied, each coat followed by stoving. The second finishing coat shall be applied after inspection of first coat of painting. The exterior and interior colour of the paint in case of new substations shall preferably be RAL 7032 for all equipment, marshalling boxes, junction boxes, control cabinets, panels etc. unless specifically mentioned under respective sections of the equipments. Glossy white colour inside the equipments /boards /panels/junction boxes is also acceptable. The exterior colour for panels shall be matching with the existing panels in case of extension of a substation. Each coat of primer and finishing paint shall be of slightly different shade to enable inspection of the painting. A small quantity of finishing paint shall be supplied for minor touching up required at site after installation of the equipments. In case the Bidder proposes to follow his own standard surface finish and protection procedures or any other established painting procedures, like electrostatic painting etc., the procedure shall be submitted alongwith the Bids for Purchasers review & approval. The colour scheme as given below shall be followed for Fire Protection and Conditioning systems S.No. PIPE LINE Base colour FIRE RED FIRE RED FIRE RED FIRE RED Canary Yellow Canary Yellow Dark Admiralty Green Sea Green Sea Green Red Dark Blue Band colour Sea Green Sky Blue Air

12.3.3

12.3.4

12.3.5

12.3.6

Fire Protection System 1 Hydrant and Emulsifier system pipeline 2 Emulsifier system detection line water 3 Emulsifier system detection line Air 4 Pylon support pipes Air Conditioning System 5 Refrigerant gas pipeline at compressor suction 6 Refrigerant gas pipeline at compressor discharge 7 Refrigerant liquid pipeline 8 9 Chilled water pipeline Condenser water pipeline

The direction of flow shall be marked by (arrow) in black colour. Base Colour Direction of flow Band Colour

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page25of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 12.3.7 For aluminium casted surfaces, the surface shall be with smooth finish. Further, in case of aluminium enclosures the surface shall be coated with powder (coating thickness of 60 microns) after surface preparation for painting. HANDLING, STORING AND INSTALLATION In accordance with the specific installation instructions as shown on manufacturers drawings or as directed by the Purchaser or his representative, the Contractor shall unload, store, erect, install, wire, test and place into commercial use all the equipment included in the contract. Equipment shall be installed in a neat, workmanlike manner so that it is level, plumb, square and properly aligned and oriented. Commercial use of switchyard equipment means completion of all site tests specified and energisation at rated voltage. Contractor may engage manufacturers Engineers to supervise the unloading, transportation to site, storing, testing and commissioning of the various equipment being procured by them separately. Contractor shall unload, transport, store, erect, test and commission the equipment as per instructions of the manufacturers supervisory Engineer(s) and shall extend full cooperation to them. The contractor shall have to ensure that the hard and flat indoor and outdoor storage areas are in place prior to commencement of delivery of material at site. Contractor shall also ensure availability of proper unloading and material handling equipment like cranes etc. and polyester/nylon ropes of suitable capacity to avoid damage during unloading and handling of material at site. All indoor equipments shall be stored indoors. Outdoor equipment may be stored outdoors but on a hard and flat raised area properly covered with waterproof and dustproof covers to protect them from water seepage and moisture ingress. However, all associated control panels, marshalling boxes operating boxes etc. of outdoor equipments are to be stored indoors only. Storage of equipment on top of another one is not permitted if the wooden packing is used. Material opened for joint inspection shall be repacked properly as per manufacturers recommendations. During storage of material regular periodic monitoring of important parameters like oil level / leakage, SF6 / Nitrogen pressure etc. shall be ensured by the contractor. 13.4 In case of any doubt/misunderstanding as to the correct interpretation of manufacturers drawings or instructions, necessary clarifications shall be obtained from the Purchaser. Contractor shall be held responsible for any damage to the equipment consequent to not following manufacturers drawings/instructions correctly. Where assemblies are supplied in more than one section, Contractor shall make all necessary mechanical and electrical connections between sections including the connection between buses. Contractor shall also do necessary adjustments/alignments necessary for proper operation of circuit breakers, isolators and their operating mechanisms. All components shall be protected against damage during unloading, transportation, storage, installation, testing and commissioning. Any equipment damaged due to negligence or carelessness or otherwise shall be replaced by the Contractor at his own expense. Contractor shall be responsible for examining all the shipment and notify the Purchaser immediately of any damage, shortage, discrepancy etc. for the purpose of Purchasers information only. The Contractor shall submit to the Purchaser every week a report detailing all the receipts during the weeks. However, the Contractor shall be solely responsible for any shortages or damages in transit, Page26of74

13.0 13.1

13.2

13.3

13.5

13.6

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) handling and/or in storage and erection of the equipment at Site. Any demurrage, wharfage and other such charges claimed by the transporters, railways etc. shall be to the account of the Contractor. 13.7 The Contractor shall be fully responsible for the equipment/material until the same is handed over to the Purchaser in an operating condition after commissioning. Contractor shall be responsible for the maintenance of the equipment/material while in storage as well as after erection until taken over by Purchaser, as well as protection of the same against theft, element of nature, corrosion, damages etc. Where material / equipment is unloaded by Purchaser before the Contractor arrives at site or even when he is at site, Purchaser by right can hand over the same to Contractor and there upon it will be the responsibility of Contractor to store the material in an orderly and proper manner. The Contractor shall be responsible for making suitable indoor storage facilities, to store all equipment which requires indoor storage. The words erection and installation used in the specification are synonymous. Exposed live parts shall be placed high enough above ground to meet the requirements of electrical and other statutory safety codes. The design and workmanship shall be in accordance with the best engineering practices to ensure satisfactory performance throughout the service life. If at any stage during the execution of the Contract, it is observed that the erected equipment(s) do not meet the above minimum clearances as given in clause 4.7.1 the Contractor shall immediately proceed to correct the discrepancy at his risks and cost. Equipment Bases A cast iron or welded steel base plate shall be provided for all rotating equipment which is to be installed on a concrete base unless otherwise agreed to by the Purchaser. Each base plate shall support the unit and its drive assembly, shall be of a neat design with pads for anchoring the units, shall have a raised lip all around, and shall have threaded drain connections. 14.0 TOOLS AND TACKLES The Contractor shall supply with the equipment one complete set of all special tools and tackles for the erection, assembly, dis-assembly and maintenance of the equipment. However, these tools and tackles shall be separately, packed and brought on to Site. 15.0 15.1 AUXILIARY SUPPLY The sub-station auxiliary supply is normally met through a system indicated under section Electrical & Mechanical Auxiliaries having the following parameters. The auxiliary power for station supply, including the equipment drive, cooling system of any equipment, air-conditioning, lighting etc shall be designed for the specified Parameters as under. The DC supply for the instrumentation and PLCC system shall also conform the parameters as indicated in the following. Normal Voltage 415V 240V 220V Variation in Voltage + 10% + 10% 190V to 240V Frequency in HZ 50 + 5% 50 + 5% DC Phase/W ire 3/4 Wire 1/2 Wire Neutral connection Solidly Earthed. Solidly Earthed. Isolated 2 wire System Page27of74

13.8

13.9 13.10 13.11 13.12

13.13

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 110V 48V 95V to 120V _ DC DC _ Isolated 2 wire System 2 wire system (+) earthed

Combined variation of voltage and frequency shall be limited to + 10%. 16.0 16.1 SUPPORT STRUCTURE The equipment support structures shall be suitable for equipment connections at the first level i.e 14.0 meter, 8.0 meter and 5.9 meter from plinth level for 765 kV, 420 kV and 245 kV substations respectively. All equipment support structures shall be supplied alongwith brackets, angles, stools etc. for attaching the operating mechanism, control cabinets & marshalling box (wherever applicable) etc. Support structure shall meet the following mandatory requirements: The minimum vertical distance from the bottom of the lowest porcelain part of the bushing, porcelain enclosures or supporting insulators to the bottom of the equipment base, where it rests on the foundation pad shall be 2.55 metres. CLAMPS AND CONNECTORS INCLUDING TERMINAL CONNECTORS All power clamps and connectors shall conform to IS:5561 & NEMA CC1 and shall be made of materials listed below : a) For connecting ACSR conductors Aluminum alloy casting, conforming to designation A6 of IS:617 and all test shall conform to IS:617 Bimetallic connectors made from aluminum alloy casting, conforming to designation A6 of IS:617 with 2mm thick bimetallic liner and all test shall conform to IS:617 Galvanised mild steel shield wire i) Electrogalvanised for sizes below M12, for others hot dip galvanised. Electro-galvanised mild steel suitable for atleast service condition-3 as per IS:1573

16.2 16.2.1

17.0 17.1

b)

For connecting equipment terminals made of copper with ACSR conductors For connecting G.I i) Bolts, nuts & Plain, washers Spring washers for items a to c

c) d)

ii)

ii)

17.2

Necessary clamps and connectors shall be supplied for all equipment and connections. The requirement regarding external corona and RIV as specified for any equipment shall include its terminal fittings. If corona rings are required to meet these requirements they shall be considered as part of that equipment and included in the scope of work. Where copper to aluminum connections are required, bi-metallic clamps shall be used, which shall be properly designed to ensure that any deterioration of the connection is kept to a minimum and restricted to parts which are not current carrying or subjected to stress. Page28of74

17.3

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 17.4 Low voltage connectors, grounding connectors and accessories for grounding all equipment as specified in each particular case, are also included in the scope of Work. No current carrying part of any clamp shall be less than 10 mm thick. All ferrous parts shall be hot dip galvanised. Copper alloy liner of minimum 2 mm thickness shall be cast integral with aluminum body or 2 mm thick bi-metallic strips shall be provided for Bi-metallic clamps. All casting shall be free from blow holes, surface blisters, cracks and cavities. All sharp edges and corners shall be blurred and rounded off. Flexible connectors, braids or laminated straps made for the terminal clamps for bus posts shall be suitable for both expansion or through (fixed/sliding) type connection of 4" IPS AL. tube as required. In both the cases the clamp height (top of the mounting pad to centre line of the tube) should be same. Clamp shall be designed to carry the same current as the conductor and the temperature rise shall be equal or less than that of the conductor at the specified ambient temperature. The rated current for which the clamp/connector is designed with respect to the specified reference ambient temperature, shall also be indelibly marked on each component of the clamp/connector, except on the hardware. All current carrying parts shall be designed and manufactured to have minimum contact resistance. Clamps and connectors shall be designed to be corona controlled. Tests Clamps and connectors should be type tested as per IS:5561 and shall also be subjected to routine tests as per IS:5561. Following type test reports shall be submitted for approval as per clause 9.2 above except for sl. no.(ii) & (iii) for which type test once conducted shall be applicable (i.e. the requirement of test conducted within last ten years shall not be applicable). i) ii) iii) iv) 18.0 18.1 Temperature rise test (maximum temperature rise allowed is 35C over 50C ambient) Short time current test Corona (dry) and RIV (dry) test (for 220 KV and above voltage level clamps) Resistance test and tensile test BOXES &

17.5

17.6 17.7

17.8

17.9 17.10 17.11 17.11.1

CONTROL CABINETS, JUNCTION BOXES, TERMINAL MARSHALLING BOXES FOR OUTDOOR EQUIPMENT

All types of boxes, cabinets etc. shall generally conform to & be tested in accordance with IS-5039/IS-8623, IEC-60439, as applicable, and the clauses given below: Control cabinets, junction boxes, Marshalling boxes & terminal boxes shall be made of sheet steel or aluminum enclosure and shall be dust, water and vermin proof. Sheet steel used shall be atleast 2.0 mm thick cold rolled or 2.5 mm hot rolled or alternately 1.6 mm thick stainless steel can also be used. The box shall be properly braced to prevent wobbling. There shall be sufficient reinforcement to provide level surfaces, resistance to vibrations and rigidity during transportation and installation. In case of aluminum enclosed box the thickness of aluminum shall be such that it provides adequate rigidity and long life as comparable with sheet steel of specified thickness.

18.2

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page29of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 18.3 18.4 A canopy and sealing arrangements for operating rods shall be provided in marshalling boxes / Control cabinets to prevent ingress of rain water. Cabinet/boxes shall be provided with double hinged doors with padlocking arrangements. The distance between two hinges shall be adequate to ensure uniform sealing pressure against atmosphere. The quality of the gasket shall be such that it does not get damaged/cracked during the operation of the equipment. All doors, removable covers and plates shall be gasketed all around with suitably profiled EPDM/Neoprene gaskets. The gasket shall be tested in accordance with approved quality plan, IS:11149 and IS:3400. Ventilating Louvers, if provided, shall have screen and filters. The screen shall be fine wire mesh made of brass. All boxes/cabinets shall be designed for the entry of cables from bottom by means of weather proof and dust-proof connections. Boxes and cabinets shall be designed with generous clearances to avoid interference between the wiring entering from below and any terminal blocks or accessories mounted within the box or cabinet. Suitable cable gland plate above the base of the marshalling kiosk/box shall be provided for this purpose along with the proper blanking plates. Necessary number of cable glands shall be supplied and fitted on this gland plate. Gland plate shall have provision for some future glands to be provided later, if required. The Nickel plated glands shall be dust proof, screw on & double compression type and made of brass. The gland shall have provision for securing armour of the cable separately and shall be provided with earthing tag. The glands shall conform to BS:6121. A 240V, single phase, 50 Hz, 15 amp AC plug and socket shall be provided in the cabinet with ON-OFF switch for connection of hand lamps. Plug and socket shall be of industrial grade. For illumination, a fluorescent tube or CFL of approximately 9 to 15 watts shall be provided. The switching of the fittings shall be controlled by the door switch. . For junction boxes of smaller sizes such as lighting junction box, manual operated earth switch mechanism box etc., plug socket, heater and illumination is not required to be provided. 18.9 18.10 All control switches shall be of MCB/rotary switch type and Toggle/piano switches shall not be accepted. Positive earthing of the cabinet shall be ensured by providing two separate earthing pads. The earth wire shall be terminated on to the earthing pad and secured by the use of self etching washer. Earthing of hinged door shall be done by using a separate earth wire. The bay marshalling kiosks shall be provided with danger plate and a diagram showing the numbering/connection/feruling by pasting the same on the inside of the door. a) The following routine tests alongwith the routine tests as per IS:5039 shall also be conducted: i) ii) b) Check for wiring Visual and dimension check

18.5

18.6

18.7

18.8

18.11

18.12

The enclosure of bay marshalling kiosk, junction box, terminal box shall conform to IP-55 as per IS:13947 including application of, 2.5 KV rms for 1 (one) minute, insulation resistance and functional test after IP-55 test.

19.0 20.0

Deleted. TERMINAL BLOCKS AND WIRING Page30of74

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 20.1 Control and instrument leads from the switchboards or from other equipment will be brought to terminal boxes or control cabinets in conduits. All interphase and external connections to equipment or to control cubicles will be made through terminal blocks. Terminal blocks shall be 650V grade and have continuous rating to carry the maximum expected current on the terminals and non breakable type. These shall be of moulded piece, complete with insulated barriers, stud type terminals, washers, nuts and lock nuts. Screw clamp, overall insulated, insertion type, rail mounted terminals can be used in place of stud type terminals. But preferably the terminal blocks shall be non-disconnecting stud type of Elmex or Phoenix or Wago or equivalent make. Terminal blocks for current transformer and voltage transformer secondary leads shall be provided with test links and isolating facilities. The current transformer secondary leads shall also be provided with short circuiting and earthing facilities. The terminal shall be such that maximum contact area is achieved when a cable is terminated. The terminal shall have a locking characteristic to prevent cable from escaping from the terminal clamp unless it is done intentionally. The conducting part in contact with cable shall preferably be tinned or silver plated however Nickel plated copper or zinc plated steel shall also be acceptable. The terminal blocks shall be of extensible design. The terminal blocks shall have locking arrangement to prevent its escape from the mounting rails. The terminal blocks shall be fully enclosed with removable covers of transparent, non-deteriorating type plastic material. Insulating barriers shall be provided between the terminal blocks. These barriers shall not hinder the operator from carrying out the wiring without removing the barriers. Unless otherwise specified terminal blocks shall be suitable for connecting the following conductors on each side. a) b) 20.10 All circuits except CT/PT circuits All CT/PT circuits Minimum of two of 2.5 sq mm copper flexible. Minimum of 4 nos. of 2.5 sq mm copper flexible.

20.2

20.3

20.4

20.5 20.6 20.7 20.8

20.9

The arrangements shall be in such a manner so that it is possible to safely connect or disconnect terminals on live circuits and replace fuse links when the cabinet is live. Atleast 20 % spare terminals shall be provided on each panel/cubicle/box and these spare terminals shall be uniformly distributed on all terminals rows. There shall be a minimum clearance of 250 mm between the First/bottom row of terminal block and the associated cable gland plate for outdoor ground mounted marshalling box and the clearance between two rows of terminal blocks shall be a minimum of 150 mm. The Contractor shall furnish all wire, conduits and terminals for the necessary interphase electrical connections (where applicable) as well as between phases and common terminal boxes or control cabinets. For equipments rated for 400 kV and above the wiring required in these items shall be run in metallic ducts or shielded cables in order to avoid surge overvoltages either transferred through the equipment or due to transients induced from the EHV circuits.

20.11 20.12

20.13

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page31of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 20.14 All input and output terminals of each control cubicle shall be tested for surge withstand capability in accordance with the relevant IEC Publications, in both longitudinal and transverse modes. The Contractor shall also provide all necessary filtering, surge protection, interface relays and any other measures necessary to achieve an impulse withstand level at the cable interfaces of the equipment. LAMPS & SOCKETS Sockets All sockets (convenience outlets) shall be suitable to accept both 5 Amp & 15 Amp pin round Standard Indian plugs. They shall be switched sockets with shutters. 21.2 Hand Lamp: A 240 Volts, single Phase, 50 Hz AC plug point shall be provided in the interior of each cubicle with ON-OFF Switch for connection of hand lamps. 21.3 21.3.1 Switches and Fuses: Each panel shall be provided with necessary arrangements for receiving, distributing, isolating and fusing of DC and AC supplies for various control, signalling, lighting and space heater circuits. The incoming and sub-circuits shall be separately provided with miniature circuit breaker / switchfuse units. Selection of the main and Sub-circuit fuse ratings shall be such as to ensure selective clearance of sub-circuit faults. Potential circuits for relaying and metering shall be protected by HRC fuses. All fuses shall be of HRC cartridge type conforming to IS:9228 mounted on plug-in type fuse bases. Miniature circuit breakers with thermal protection and alarm contacts will also be accepted. All accessible live connection to fuse bases shall be adequately shrouded. Fuses shall have operation indicators for indicating blown fuse condition. Fuse carrier base shall have imprints of the fuse rating and voltage. Bushings, Hollow Column Insulators, Support Insulators: Bushings shall be manufactured and tested in accordance with IS:2099 & IEC60137 while hollow column insulators shall be manufactured and tested in accordance with IEC-62155/IS:5621.The support insulators shall be manufactured and tested as per IS:2544/IEC-60168 and IEC-60273. The insulators shall also conform to IEC-60815 as applicable. The bidder may also offer composite hollow insulators, conforming to IEC-61462. 22.2 Support insulators, bushings and hollow column insulators shall be manufactured from high quality porcelain. Porcelain used shall be homogeneous, free from laminations, cavities and other flaws or imperfections that might affect the mechanical or dielectric quality and shall be thoroughly vitrified tough and impervious to moisture. Glazing of the porcelain shall be uniform brown in colour, free from blisters, burrs and similar other defects. Support insulators/bushings/hollow column insulators shall be designed to have ample insulation, mechanical strength and rigidity for the conditions under which they will be used. When operating at normal rated voltage there shall be no electric discharge between the conductors and bushing which would cause corrosion or injury to conductors, insulators or supports by the formation of substances produced by Page32of74

21.0 21.1

21.3.2

22.0 22.1

22.3 22.4

22.5

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) chemical action. No radio interference shall be caused by the insulators/bushings when operating at the normal rated voltage. 22.6 Bushing porcelain shall be robust and capable of withstanding the internal pressures likely to occur in service. The design and location of clamps and the shape and the strength of the porcelain flange securing the bushing to the tank shall be such that there is no risk of fracture. All portions of the assembled porcelain enclosures and supports other than gaskets, which may in any way be exposed to the atmosphere shall be composed of completely non hygroscopic material such as metal or glazed porcelain. All iron parts shall be hot dip galvanised and all joints shall be air tight. Surface of joints shall be trued up porcelain parts by grinding and metal parts by machining. Insulator/bushing design shall be such as to ensure a uniform compressive pressure on the joints. Tests In bushing, hollow column insulators and support insulators shall conform to type tests and shall be subjected to routine tests in accordance with IS: 2099 & IS: 2544 & IS : 5621. 23.0 MOTORS Motors shall be Squirrel Cage three phase induction motors of sufficient size capable of satisfactory operation for the application and duty as required for the driven equipment and shall be subjected to routine tests as per applicable standards. The motors shall be of approved make. 23.1 Enclosures a) Motors to be installed outdoor without enclosure shall have hose proof enclosure equivalent to IP-55 as per IS: 4691. For motors to be installed indoor i.e. inside a box, the motor enclosure, shall be dust proof equivalent to IP-44 as per IS: 4691. Two independent earthing points shall be provided on opposite sides of the motor for bolted connection of earthing conductor. Motors shall have drain plugs so located that they will drain water resulting from condensation or other causes from all pockets in the motor casing. Motors weighing more than 25 Kg. shall be provided with eyebolts, lugs or other means to facilitate lifting. Continuous motor rating (name plate rating) shall be at least ten (10) percent above the maximum load demand of the driven equipment at design duty point and the motor shall not be over loaded at any operating point of driven equipment that will rise in service. Motor shall be capable at giving rated output without reduction in the expected life span when operated continuously in the system having the particulars as given in Clause 15.0 of this Section. All induction motors shall be suitable for full voltage direct-on-line starting. These shall be capable of starting and accelerating to the rated speed alongwith the driven equipment without exceeding the acceptable winding temperature even when the supply voltage drops down to 80% of the rated voltage. Page33of74

22.7

22.8

b) c) d) 23.2

Operational Features a)

b)

23.3

Starting Requirements: a)

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) b) c) d) Motors shall be capable of withstanding the electrodynamic stresses and heating imposed if it is started at a voltage of 110% of the rated value. The locked rotor current shall not exceed six (6) times the rated full load current for all motors, subject to tolerance as given in IS:325. Motors when started with the driven equipment imposing full starting torque under the supply voltage conditions specified under Clause 15.0 shall be capable of withstanding atleast two successive starts from cold condition at room temperature and one start from hot condition without injurious heating of winding. The motors shall also be suitable for three equally spread starts per hour under the above referred supply condition. The locked rotor withstand time under hot condition at 110% of rated voltage shall be more than starting time with the driven equipment of minimum permissible voltage by at least two seconds or 15% of the accelerating time whichever is greater. In case it is not possible to meet the above requirement, the Bidder shall offer centrifugal type speed switch mounted on the motor shaft which shall remain closed for speed lower than 20% and open for speeds above 20% of the rated speed. The speed switch shall be capable of withstanding 120% of the rated speed in either direction of rotation. The maximum permissible temperature rise over the ambient temperature of 50 degree C shall be within the limits specified in IS:325 (for 3 - phase induction motors) after adjustment due to increased ambient temperature specified. The double amplitude of motor vibration shall be within the limits specified in IS: 4729. Vibration shall also be within the limits specified by the relevant standard for the driven equipment when measured at the motor bearings. All the induction motors shall be capable of running at 80% of rated voltage for a period of 5 minutes with rated load commencing from hot condition.

e)

23.4

Running Requirements: a)

b)

c) 23.5

TESTING AND COMMISSIONING An indicative list of tests is given below. Contractor shall perform any additional test based on specialities of the items as per the field Q.P./Instructions of the equipment Contractor or Purchaser without any extra cost to the Purchaser. The Contractor shall arrange all instruments required for conducting these tests alongwith calibration certificates and shall furnish the list of instruments to the Purchaser for approval. (a) (b) (c) Insulation resistance. Phase sequence and proper direction of rotation. Any motor operating incorrectly shall be checked to determine the cause and the conditions corrected.

24.0 24.1 24.1.1

TECHNICAL REQUIREMENT OF EQUIPMENTS Technical requirements for 765kV Circuit Breaker Route-1 The manufacturer(s) whose 765 kV SF6 Circuit Breaker are offered, should have designed, manufactured, type tested (as per IEC/IS or equivalent standard) for 40kA or above fault level and should have supplied 715 kV or above class circuit

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page34of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) breakers which are in operation for at least two (2) years as on the date of bid opening. And wherever the specified fault level of the circuit breaker is more than 40 kA, in addition to the above, the offered Circuit Breaker should have been designed, manufactured and type tested to the specified fault level as on the date of bid opening. Further, a legally enforceable undertaking jointly by the bidder and manufacturer shall be furnished along with the bid to guarantee quality, timely supply, performance and supervision of erection, testing, and commissioning of the 765KV circuit breaker. The Bidder or his proposed manufacturer for 765kV class SF6 Circuit Breakers should have repair and maintenance facilities for these equipments in India. The repair and maintenance facilities shall be such that the equipment can be repaired and maintained without necessitating it to be taken outside the country. In case the Bidder or his proposed manufacturer is not having these facilities, he shall be required to supply 5% of total quantity (package-wise sum total of quantities for all substations), rounded off to the next higher integer, of Circuit Breaker to be supplied in the respective package, subject to a minimum of one complete 3phase circuit breaker as additional spares (excluding mandatory spares) in lieu of repair and maintenance facilities for 765 kV Circuit Breaker. OR 24.1.1 Route-2 Under each package maximum up to -------- numbers* of 765 kV class SF6 Circuit Breakers can also be offered from Indian manufacturers(a manufacturing company registered in India under the companies Act 1956) who have designed, manufactured, type tested (as per IEC/IS or equivalent standard) for 40kA or above fault level and supplied 345 kV or above class circuit breakers, which are in operation for at least two (2) years as on the date of bid opening and have manufactured and type tested to the required fault level of 40kA/50kA/63kA(as applicable) 765 kV SF6 Circuit Breaker as per IEC/IS or equivalent standard, as on date of bid opening; Provided that (a) A legally enforceable undertaking jointly by the bidder and Indian manufacturer is furnished along with the bid to guarantee quality, timely supply, performance and supervision of erection, testing, and commissioning of 765KV circuit breaker and to provide warranty obligations for four (4) years for the entire quantity to be supplied. (b) A confirmation letter from the manufacture is submitted along with the bid stating that they shall furnish performance guarantee for an amount of 10% of the ex works cost of the Circuit Breaker. This performance guarantee shall be in addition to the contract performance guarantee to be submitted by the bidder. Note- 1) * indicates that N/2 (applicable for even number of 3-phase Circuit Breaker) and (N-1)/2 (applicable for odd number 3-phase Circuit Breaker), where N= total number of 3-phase Circuit Breaker under each package.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page35of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 2) The balance quantity of circuit breakers in the package shall be necessarily supplied from a manufacturer meeting the requirement of clause 24.1.1- Route-1. 24.1.2 Bidder shall furnish an undertaking (as per the format in the bidding document) from 765kV Circuit Breaker manufacturer that erection, testing and commissioning of 765kV class SF6 Circuit Breaker shall be carried out under the supervision of 765kV Circuit Breaker manufacturer and after sales services & spares shall remain available for at least fifteen (15) years from the date of supply. Technical requirements for 765kV Isolators Route-1 The manufacturer whose isolator are offered, should have designed, manufactured, type tested (as per IS/IEC or equivalent standard) and supplied 715 kV or above class isolator and 40kA fault level which are in operation for at least 2 (two) years as on the date of bid opening And wherever the specified fault level of the isolator is more than 40 kA, in addition to the above, the offered Isolator should have been designed, manufactured, type tested to specified fault level in the subject package as on the date of bid opening. Further, a legally enforceable undertaking jointly by the bidder and manufacturer shall be furnished along with the bid to guarantee quality, timely supply and performance of the 765 KV Isolator. OR 24.2.(i) Route-2 Under each package maximum up to ------ numbers* 765 kV Isolators can also be offered from Isolator manufacturer(s) who have established production line in India based on technological support of a parent company or collaborator for 715 kV or above class isolator provided that :(i) such manufacturer(s) have manufactured and type tested 765 kV isolator or above (as per IEC/IS or equivalent standard) to the system fault level of 40 kA/ 50 kA/ 63 kA (as applicable). the parent company (Principal) or collaborator meets qualifying requirements stipulated under 24.2.(i) Route-1 given above.

24.2 24.2.(i)

(ii)

(iii) the manufacturer furnishes (jointly with parent company or collaborator ) (a) a legally enforceable undertaking to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) And (b) Furnishes a confirmation letter from the parent company or collaborator (as applicable) alongwith the bid stating that parent company or collaborator or subsidiary (as applicable) shall furnish performance guarantee for an amount of 10% of the cost of such equipment(s). This performance guarantee shall be in addition to contract performance guarantee to be submitted by the Bidder And TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page36of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) (c) a legally enforceable undertaking jointly by the bidder and manufacturer for warranty obligations for four (4) years for the entire quantity to be supplied, is to be submitted along with the bid. Note- 1) * indicates that N/2 (applicable for even number of 3-phase Isolator) and (N-1)/2 (applicable for odd number 3-phase Isolator), where N= total number of 3-phase Isolator under each package 2) The balance quantity of isolators in the package shall be necessarily supplied from a manufacturer meeting the requirement of clause 24.2.(i) - Route-1. 24.2. (ii) Bidder shall furnish undertaking alongwith the bid (as per the format in the bidding document) from the 765kV Isolator manufactures that erection, testing and commissioning of 765kV class isolators shall be carried out under the supervision of 765kV Isolator manufactures and after sales services and spares shall remain available for at least fifteen (15) years from the date of supply. Technical requirements for 765kV Instrument Transformers Route-1 The manufacturer(s) whose 765 kV Instrument transformers are offered, should have designed, manufactured, type tested (as per IEC/IS or equivalent standard) for 40kA or above fault level (fault level applicable for current transformer only) and supplied 715 kV or above class Instrument transformers, which are in operation for at least two (2) years as on the date of bid opening. And wherever the specified fault level of the Current transformers is more than 40 kA, in addition to the above, the offered Current transformers should have been designed, manufactured and type tested to the specified fault level as on the date of bid opening. Further, a legally enforceable undertaking jointly by the bidder and manufacturer shall be furnished along with the bid to guarantee quality, timely supply, and performance of the 765 KV Instrument Transformer. The Bidder or his proposed manufacturer for 765kV class Instrument transformers should have repair and maintenance facilities for these equipments in India. The repair and maintenance facilities shall be such that the equipment can be repaired and maintained without necessitating it to be taken outside the country. In case the Bidder or his proposed manufacturer is not having these facilities, he shall be required to supply 5% of total quantity(package-wise sum total of quantities for all substations), rounded off to the next higher integer, of Instrument transformers to be supplied in the respective package, subject to a minimum of 3 Nos of each type and rating of Instrument transformers as additional spares (excluding mandatory spares) in lieu of repair and maintenance facilities for 765 kV Instrument transformers. OR 24.3.(i) Route-2 Under each package maximum up to ------- numbers* 765 kV Instrument Transformers can also be offered from Instrument transformers manufacturer(s) who have established production line in India based on technological support of a parent company or collaborator company for 715 kV or above class Instrument transformers provided that :TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page37of74

. 24.3 24.3.(i)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) (i) such manufacturer(s) have manufactured and type tested 765 kV Instrument transformers or above (as per IEC/IS or equivalent standard) to the system fault level of 40 kA/ 50 kA/ 63 kA (fault level as applicable for current transformer only). (ii) the parent company (Principal) or collaborator meets qualifying requirements stipulated under 24.3.(i) Route-1 given above. (iii) the manufacturer furnishes (jointly with parent company or collaborator) (a) a legally enforceable undertaking to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) And (b) Furnishes a confirmation letter from the parent company or collaborator (as applicable) along with the bid stating that parent company or collaborator (as applicable) shall furnish performance guarantee for an amount of 10% of the cost of such equipment(s). This performance guarantee shall be in addition to contract performance guarantee to be submitted by the Bidder And (c) a legally enforceable undertaking jointly by the bidder and manufacturer for warranty obligations for four (4) years for the entire quantity to be supplied, is to be submitted along with the bid. Note- 1) * indicates that N/2 (applicable for even number of Instrument transformers) and (N-1)/2 (applicable for odd number Instrument transformers), where N= total number of Instrument transformers under each package 2) The balance quantity of instrument transformers in the package shall be necessarily supplied from a manufacturer meeting the requirement of clause 24.3.(i) - Route-1. OR 24.3.(i) Route-3 Under each package maximum up to -------- numbers* 765kV Instrument transformers can also be offered from Indian manufacturers ( a manufacturing company registered in India under company act 1956) who have designed, manufactured, type tested (as per IEC/IS or equivalent standard) for 40kA or above fault level (fault level is applicable for current transformers only) and supplied 345 kV or above class Instrument transformers, which are in operation for at least two (2) years as on the date of bid opening and have manufactured and type tested to the fault level of 40kA/50kA/63kA(fault level as applicable, for current transformers only) 765 kV or above Instrument transformers as per IEC/IS or equivalent standard, as on date of bid opening; Provided that: a legally enforceable undertaking jointly by the bidder and manufacturer is furnished along with the bid to guarantee quality, timely supply and performance of 765kV Instrument transformers and to provide warranty obligations for four (4) years for the entire quantity to be supplied, and a confirmation letter from the manufacture is submitted along with the bid stating that they shall furnish performance guarantee for an amount of 10 % of the ex works cost of the Instrument transformers. This performance guarantee shall be in addition to the contract performance guarantee to be submitted by the bidder. TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page38of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) Note- 1) * indicates that N/2 (applicable for even number of Instrument transformers) and (N-1)/2 (applicable for odd number Instrument transformers), where N= total number of Instrument transformers under each package 2) The balance quantity of instrument transformers in the package shall be necessarily supplied from a manufacturer meeting the requirement of clause 24.3.(i) - Route-1. 24.3. (ii) Bidder shall furnish an undertaking alongwith the bid (as per the format in the bidding document) from 765kV Instrument transformers manufacturer that erection, testing and commissioning of 765kV class Instrument transformers shall be carried out under the supervision of 765kV Instrument transformers manufacturer and after sales services & spares shall remain available for at least fifteen (15) years from the date of supply. Technical requirements for 765kV Surge Arresters Route-1 The manufacturer(s) whose 765 kV Surge Arresters are offered, should have designed, manufactured, type tested (as per IEC/IS or equivalent standard) with the specified energy capability and supplied 715 kV or above class Surge Arresters, which are in operation for at least two (2) years as on the date of bid opening. Further, a legally enforceable undertaking jointly by the bidder and manufacturer shall be furnished along with the bid to guarantee quality, timely supply and performance of the 765 KV Surge Arrester. OR 24.4.(i) Route-2 Under each package maximum up to -------- numbers* 765 kV class Surge arresters can also be offered from Surge Arresters manufacturer(s) who have established production line in India based on technological support of a parent company or collaborator for 715 kV or above class Surge Arresters provided that :(i) such manufacturer(s) have manufactured and type tested 765 kV or above Surge Arresters with the specified energy capability or above (as per IEC/IS or equivalent standard). (ii) the parent company (Principal) or collaborator meets qualifying requirements stipulated under 24.4.(i) Route-1 given above. (iii) the manufacturer furnishes (jointly with parent company or collaborator) (a) a legally enforceable undertaking to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) And (b) Furnishes a confirmation letter from the parent company or collaborator (as applicable) alongwith the bid stating that parent company or collaborator ( as applicable) shall furnish performance guarantee for an amount of 10% of the cost of such equipment(s). This performance guarantee shall be in addition to contract performance guarantee to be submitted by the Bidder And TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page39of74

24.4 24.4.(i)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) (c) a legally enforceable undertaking jointly by the bidder and manufacturer for warranty obligations for four (4) years for the entire quantity to be supplied, is to be submitted along with the bid. Note- 1) * indicates that N/2 (applicable for even number of Surge arrester) and (N-1)/2 (applicable for odd number 765 kV class Surge arresters) ,where N= total number of 765 kV class Surge arresters under each package 2) The balance quantity of Surge arresters in the package shall be necessarily supplied from a manufacturer meeting the requirement of clause 24.4.(i) - Route-1. OR 24.4.(i) Route-3 Under each package maximum up to -------- numbers* 765 kV class Surge arresters can also be offered from Indian manufacturers (a manufacturing company registered in India under company act 1956) who have designed, manufactured, type tested (as per IEC/IS or equivalent standard) and supplied 345 kV or above class Surge arresters, which are in operation for at least two (2) years as on the date of bid opening and have manufactured and type tested 765 kV or above class Surge arresters as per IEC/IS or equivalent standard, as on date of bid opening; Provided that : a legally enforceable undertaking jointly by the bidder and manufacturer is furnished along with the bid to guarantee quality, timely supply and performance of 765 kV class Surge arresters and to provide warranty obligations for four (4) years for the entire quantity to be supplied. And, a confirmation letter from the manufacture is submitted along with the bid stating that they shall furnish performance guarantee for an amount of 10 % of the ex works cost of the surge arresters. This performance guarantee shall be in addition to the contract performance guarantee to be submitted by the bidder. Note- 1) * indicates that N/2 (applicable for even number of Surge arrester) and (N-1)/2 (applicable for odd number 765 kV class Surge arresters) ,where N= total number of 765 kV class Surge arresters under each package 2) The balance quantity of Surge arresters in the package shall be necessarily supplied from a manufacturer meeting the requirement of clause 24.4.(i) - Route-1. 24.4. (ii) Bidder shall furnish an undertaking alongwith the bid (as per the format in the bidding document) from 765kV Surge Arresters manufacturer that erection, testing and commissioning of 765kV Surge Arresters shall be carried out under the supervision of 765kV Surge Arresters manufacturer and after sales services & spares shall remain available for at least fifteen (15) years from the date of supply. Circuit Breakers (Applicable for 400kV, 220kV & 132kV)

24.5

24.5.(i)(a) The manufacturer(s) whose SF6 Circuit Breaker are offered should have manufactured, type tested and supplied 345kV or above class circuit breaker of 40kA fault level which must be in operation for at least two(2) years as on the date of bid opening provided further that:

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page40of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) @24.5.(i)(b) the offered 400kV class Circuit Breaker should have been manufactured, type tested (to specified fault level in the subject package) and which must be in operation as on the date of bid opening. OR the offered 400kV class Circuit Breaker should have been manufactured and type tested (to specified fault level in the subject package) as on the date of bid opening and extended warranty of additional two (2) years over and above the warranty period specified for the package is given for the Circuit Breaker for which a declaration by the bidder is made in the bid. @ Clause applicable for 400kV class Breaker for fault level more than 40kA only. OR 24.5.(ii)(a) who have manufactured, type tested and supplied 220kV or above class circuit breaker and have established its manufacturing facilities in India, based on technological support of a parent company or collaborator for the circuit breaker provided that the parent company (Principals) or collaborator(s) meets criteria stipulated under clause 24.5.(i)(a) & (b)$ mentioned above. Further the 400kV class circuit breaker manufacturer shall furnish the following document alongwith the bid; $ 24.5(i)(b) applicable for 400kV Class Breaker for fault level more than 40kA only (i) a legally enforceable undertaking (jointly with the parent company or collaborator) to guarantee quality, timely supply, performance and warranty obligations as specified for the circuit breakers; and (ii) a confirmation letter from the parent company or collaborator alongwith the bid stating that parent company or collaborator shall furnish performance guarantee for an amount of 10 % of the ex-work cost of such equipment (s). This performance guarantee shall be in addition to Contract Performance Guarantee to be submitted by the Bidder. 24.6 24.6.(i) Isolators (Applicable for 400kV, 220kV & 132kV) The manufacturer whose isolator(s) are offered, should have manufactured & type tested as per IS/IEC or equivalent standard and supplied the isolator for the specified system voltage and 25kA fault level or above and which must be in operation for at least 2 (two) years as on the date of bid opening. In addition to the above the offered Isolator should have been manufactured and type tested to specified fault level as on the date of bid opening. OR Isolators can also be offered from isolator manufacturer(s) who have established production line in India based on technological support of a parent company or collaborator for the isolator provided that (a) such manufacturer(s) have manufactured and type tested the isolator (as per IEC/IS or equivalent standard) to the specified fault level. (b) the parent company (Principal) or collaborator meets qualifying requirements stipulated under 24.6.(i) given above.

24.6.(ii)

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page41of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) (c) Furnishes (jointly with parent company or collaborator) a legally enforceable undertaking to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) (d) Furnishes a confirmation letter from the parent company or collaborator alongwith the bid stating that parent company or collaborator shall furnish performance guarantee for an amount of 10% of the cost of such equipment(s). This performance guarantee shall be in addition to contract performance guarantee to be submitted by the Bidder 24.7 24.7.(i) Instrument Transformers (Applicable for 400kV, 220kV & 132kV) The manufacturer whose instrument transformers are offered, should have manufactured & type tested as per IS/IEC or equivalent standard and supplied the same for the specified system voltage for CT & CVT and 25kA fault level or above (fault level applicable for current transformer only). These equipment should be in operation for at least 2 (two) years as on the date of bid opening. In addition to the above the offered Current transformer should have been manufactured and type tested to specified fault level as on the date of bid opening. OR 24.7.(ii) Instrument Transformers can also be offered from Instrument Transformer manufacturer(s) who have established production line in India based on technological support of a parent company or collaborator for the Instrument Transformer provided that (a) such manufacturer(s) have manufactured and type tested the Instrument Transformer (as per IEC/IS or equivalent standard) to the specified fault level (fault level applicable for current transformer only). (b) the parent company (Principal) or collaborator meets qualifying requirements stipulated under 24.7.(i) given above. (c) Furnishes (jointly with parent company or collaborator) a legally enforceable undertaking to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) (d) Furnishes a confirmation letter from the parent company or collaborator alongwith the bid stating that parent company or collaborator shall furnish performance guarantee for an amount of 10% of the cost of such equipment(s). This performance guarantee shall be in addition to contract performance guarantee to be submitted by the Bidder 24.8 24.8. (i) Surge Arresters (Applicable for 400kV, 220kV & 132 kV) The manufacturer whose Surge Arresters are offered should have manufactured and type tested as per IEC/IS or equivalent standard and supplied the Surge Arrester for the specified energy capability with rated system voltage and which are in operation for at least 2 (two) years as on the date of bid opening. Or Surge Arresters can also be offered from Surge Arrester manufacturer(s) who have established production line in India based on technological support of a parent company or collaborator for the Surge Arresters provided that Page42of74

24.8. (ii)

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR)

(a) such manufacturer(s) have manufactured and type tested the Surge Arrester (as per IEC/IS or equivalent standard) to the specified energy capability with rated system voltage. (b) the parent company (Principal) or collaborator meets qualifying requirements stipulated under 24.8.(i) given above. (c) Furnishes (jointly with parent company or collaborator) a legally enforceable undertaking to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) (d) Furnishes a confirmation letter from the parent company or collaborator alongwith the bid stating that parent company or collaborator shall furnish performance guarantee for an amount of 10% of the cost of such equipment(s). This performance guarantee shall be in addition to contract performance guarantee to be submitted by the Bidder. 24.9 220KV Grade XLPE Power Cables The cable shall be from the manufacturer who must have designed, manufactured, type tested and supplied in a single contract at least 15 (fifteen) km of single core, 220kV or higher grade XLPE insulated cable which must be in operation for at least 2 (two) years as on the date of bid opening.. 24.10 132KV Grade XLPE Power Cables The cable shall be from the manufacturer who must have designed, manufactured, type tested and supplied in a single contract at least 15 (fifteen) km of single core, 132kV or higher grade XLPE insulated cable which must be in operation for at least 2 (two) years as on the date of bid opening. 24.11 24.11.1 1.1 KV Grade Power & Control Cables Applicable for PVC Control Cable The manufacturers, whose PVC control cables are offered, should have designed, manufactured, tested and supplied in a single contract at least 100 Kms of 1.1 KV grade PVC insulated control cables as on the date of bid opening. Further the manufacturer should also have designed, manufactured, tested and supplied at least 1 km of 27C x 2.5 Sq.mm or higher size as on the date of bid opening. 24.11.2 Applicable for PVC Power Cable The manufacturer, whose PVC Power Cables are offered, should have designed, manufactured, tested and supplied in a single contract atleast 100 Kms of 1.1 KV or higher grade PVC insulated power cables as on the date of bid opening. Further the manufacturer should also have designed, manufactured, tested and supplied at least 1 km of 1C x 150 Sq. mm or higher size as on the date of bid opening. 24.11.3 Applicable for XLPE Power Cables The Manufacturer, whose XLPE Power cables are offered, should have designed, manufactured, tested and supplied in a single contract atleast 25 Kms of 1.1 KV or higher grade XLPE insulated power cables as on the date of bid opening. Further the manufacturer should also have designed, manufactured, tested and supplied at least 1 km of 1C x 630 Sq. mm or higher size as on the date of bid opening. 24.12 LT Switchgear Page43of74

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 24.12.1 The Manufacturer whose LT Switchgear are offered, should be a manufacturer of LT Switchboards of the type and rating being offered. He should have designed, manufactured, tested and supplied at least 50 nos. draw out circuit breaker panels, out of which at least 5 nos. should have been with relay and protection schemes with current transformer. He should have also manufactured at least 50 nos MCC panels comprising of MCCBs (ie Moulded Case Circuit Breakers) modules of the type offered which should be in successful operation as on date of bid opening. The Switchgear items (such as circuit breakers, fuse switch units, contactors etc.), may be of his own make or shall be procured from reputed manufacturers and of proven design. At least one hundred circuit breakers of the make and type being offered shall be operating satisfactory as on date of bid opening. Battery and Battery Charger Requirements for Battery Manufacturers The manufacturer whose Batteries are offered should have designed, manufactured and supplied DC Batteries of the type specified and being offered, having a capacity of at least 600 AH and these shall be operating satisfactorily for two years in power sector and/or industrial installations as on date of bid opening. 24.13.2 Requirements for Battery Charger Manufacturers The manufacturer, whose Battery Chargers are offered, should have designed, manufactured and supplied Battery Chargers generally of the type offered, with static automatic voltage regulators and having a continuous output of atleast ten (10) KW and these should be in successful as on the date of bid opening. 24.14 LT Transformers The manufacturer, whose transformers are offered should have designed, manufactured, type tested including short circuit test as per IEC/IS or equivalent standards and supplied transformers of at least 33 kV class of 800 KVA or higher. The transformer should have been in successful operation for at least 2 years as on the date of bid opening. 24.15 Fire Fighting System The bidder or his sub-vendor should have designed, supplied, tested, erected and commissioned at least one number fire protection system of the each type described in (i), (ii) and (iii) below in installations such as power plants, substations, refineries, fertilizer plants or other industrial or commercial installations. Such systems must have been designed to the recommendations of Tariff Advisory Committee of India or any other international reputed authority like (FOC, London or NFPA, USA etc.) executed during last ten (10) years and should have been in successful operation for at least 2 years as on the date of bid opening. (i) (ii) (iii) Automatic hydrant type fire protection system Automatic high velocity or automatic medium velocity water spray type fire protection system Smoke detection system.

24.12.2

24.13 24.13.1

In case bidder himself do not meet the requirement of design, he can engage a consultant(s) who must have designed i) Automatic hydrant type fire protection system, ii) Automatic high velocity or automatic medium velocity water spray type fire protection system and iii) Smoke detection system, which must be in successful operation for at least two years as on the date of bid opening. TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page44of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 24.16 24.16.1 Control, Relay & Protection System and Sub-station Automation System (as applicable) The manufacturer whose Control, Relay & Protection System (Control & protection Intelligent Electronic Devices (IEDs)), and Sub-station Automation System (If applicable) are offered should have designed, manufactured, tested, installed and commissioned Control, Relay & Protection system along with Sub-station Automation System which must be in satisfactory operation on (i) 400 kV system [for 765kV substation] & (ii) specified voltage level or above [for 400kV & below substation] for atleast 2 (two) years on the date of bid opening. AND 24.16.2 The Manufacturer or their joint venture or subsidiary company must have established repair, testing and integration (for at least 4 bays) facilities for Control, Relay & Protection System and Sub-station Automation System in India. PLCC (765 kV, 400 kV, 220 kV & 132 kV) The manufacturer whose PLCC panels are offered should have designed, manufactured, tested, supplied and commissioned PLCC panels for (i) 400kV system or above [for 765 kV & 400 kV substation], (ii) 220 kV System or above [for 220 kV Substation] & (iii) 132 kV system or above [for 132 kV substation] and the same should be in successful operation for atleast 2 (two) years as on the date of bid opening. The manufacturer whose line traps are offered should have designed, manufactured tested, supplied and commissioned similar line traps for (i) 400kV system or above voltage level and 40 kA fault level [for 765 kV & 400 kV substation], (ii) specified voltage level or above and specified fault level [for 220 kV & 132 kV substation] and should be in successful operation for atleast 2 (two) years as on the date of bid opening. PLCC Panels/line traps manufactured by the manufacturer meeting the requirements at Clause No. 24.17.1 & 24.17.2 except that the PLCC Panels/line traps manufactured, tested and supplied by them is not in operation for the stipulated period can also be offered provided the manufacturer furnishes an undertaking jointly executed by him and his collaborator, who in turn fully meets the requirement specified at 24.17.1/24.17.2 above as per the format enclosed in the bid document for successful performance of the equipment offered. The manufacturer(s) whose PLCC Panels/Line traps are offered who have recently established production line in India for the specified system voltage or above class, based on technological support of a parent company or collaborator for the respective equipment(s) can also be considered provided the parent company (Principal) or collaborator meets qualifying requirements stipulated under clause no 24.17.1/24.17.2 given above. And Furnishes (jointly with parent company or collaborator) a legally enforceable undertaking to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) And Furnishes a confirmation letter from the parent company or collaborator alongwith the bid stating that parent company or collaborator shall furnish performance guarantee for an amount of 10% of the cost of such equipment(s). This performance guarantee shall be in addition to contract performance guarantee to be submitted by the Bidder. TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page45of74

24.17 24.17.1

24.17.2

24.17.3

24.17.4

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) 24.17.5 The digital PLCC Panels can also be offered from manufacturer(s) who have established integration & testing facilities for digital PLCC in India provided the digital PLCC modules/hardware/software are sourced from their parent company (principal) who meets the QR stipulated under clause 24.17.1.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page46of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR)

ANNEXURE-A CORONA AND RADIO INTERFERENCE VOLTAGE (RIV) TEST 1. General Unless otherwise stipulated, all equipment together with its associated connectors, where applicable, shall be tested for external corona (for 400kV & above) both by observing the voltage level for the extinction of visible corona under falling power frequency voltage and by measurement of radio interference voltage (RIV) for 132kV above. 2. Test Levels: The test voltage levels for measurement of external RIV and for corona extinction voltage are listed under the relevant clauses of the specification. 3. 3.1 Test Methods for RIV: RIV tests shall be made according to measuring circuit as per International Special-Committee on Radio Interference (CISPR) Publication 16-1(1993) Part -1. The measuring circuit shall preferably be tuned to frequency with 10% of 0.5 Mhz but other frequencies in the range of 0.5 MHz to 2 MHz may be used, the measuring frequency being recorded. The results shall be in microvolts. Alternatively, RIV tests shall be in accordance with NEMA standard Publication No. 107-1964, except otherwise noted herein. In measurement of, RIV, temporary additional external corona shielding may be provided. In measurements of RIV only standard fittings of identical type supplied with the equipment and a simulation of the connections as used in the actual installation will be permitted in the vicinity within 3.5 meters of terminals. Ambient noise shall be measured before and after each series of tests to ensure that there is no variation in ambient noise level. If variation is present, the lowest ambient noise level will form basis for the measurements. RIV levels shall be measured at increasing and decreasing voltages of 85%, 100%, and 110% of the specified RIV test voltage for all equipment unless otherwise specified. The specified RIV test voltage for 765kV, 400 kV, 220 KV is listed in the detailed specification together with maximum permissible RIV level in microvolts. The metering instruments shall be as per CISPR recommendation or equivalent device so long as it has been used by other testing authorities. The RIV measurement may be made with a noise meter. A calibration procedure of the frequency to which noise meter shall be tuned shall establish the ratio of voltage at the high voltage terminal to voltage read by noisel meter. Test Methods for Visible Corona The purpose of this test is to determine the corona extinction voltage of apparatus, connectors etc. The test shall be carried out in the same manner as RIV test described above with the exception that RIV measurements are not required during test and a search technique shall be used near the onset and extinction voltage, when the test voltage is raised and lowered to determine their precise values. The test voltage shall be raised to 110% of specified corona TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12) Page47of74

3.2 3.3

3.4

3.5 3.6

4.

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) extinction voltage and maintained there for five minutes. In case corona inception does not take place at 110%, test shall be stopped, otherwise test shall be continued and the voltage will then be decreased slowly until all visible corona disappears. The procedure shall be repeated at least 4 times with corona inception and extinction voltage recorded each time. The corona extinction voltage for purposes of determining compliance with the specification shall be the lowest of the four values at which visible corona (negative or positive polarity) disappears. Photographs with laboratory in complete darkness shall be taken under test conditions, at all voltage steps i.e. 85%, 100%, and 110%. Additional photographs shall be taken at corona inception and extinction voltages. At least two views shall be photographed in each case using Panchromatic film with an ASA daylight rating of 400 with an exposure of two minutes at a lens aperture of f/5.6 or equivalent. The photographic process shall be such that prints are available for inspection and comparison with conditions as determined from direct observation. Photographs shall be taken from above and below the level of connector so as to show corona on bushing, insulators and all parts of energised connectors. The photographs shall be framed such that test object essentially, fills the frame with no cut-off. For recording purpose, modern devices utilizing UV recording methods such as image intensifier may also be used. 4.1 The test shall be recorded on each photograph. Additional photograph shall be taken from each camera position with lights on to show the relative position of test object to facilitate precise corona location from the photographic evidence. In addition to photographs of the test object preferably four photographs shall be taken of the complete test assembly showing relative positions of all the test equipment and test objects. These four photographs shall be taken from four points equally spaced around the test arrangement to show its features from all sides. Drawings of the laboratory and test set up locations shall be provided to indicate camera positions and angles. The precise location of camera shall be approved by Purchasers inspector, after determining the best camera locations by trial energisation of test object at a voltage which results in corona. The test to determine the visible corona extinction voltage need not be carried out simultaneously with test to determine RIV levels. However, both test shall be carried out with the same test set up and as little time duration between tests as possible. No modification on treatment of the sample between tests will be allowed. Simultaneous RIV and visible corona extinction voltage testing may be permitted at the discretion of Purchasers inspector if, in his opinion, it will not prejudice other test. Test Records: In addition to the information previously mentioned and the requirements specified as per CISPR or NEMA 107-1964 the following data shall be included in test report: a) b) c) d) Background noise before and after test. Detailed procedure of application of test voltage. Measurements of RIV levels expressed in micro volts at each level. Results and observations with regard to location and type of interference sources detected at each step.

4.2

4.3 4.4

5.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page48of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) e) f) Test voltage shall be recorded when measured RIV passes through 100 microvolts in each direction. Onset and extinction of visual corona for each of the four tests required shall be recorded.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page49of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR)

ANNEXURE - B SEISMIC WITHSTAND TEST PROCEDURE The seismic withstanding test on the complete equipment (for 132kV and above) shall be carried out alongwith supporting structure. The Bidder shall arrange to transport the structure from his Contractors premises/POWERGRID sites for the purpose of seismic withstand test only. The seismic level specified shall be applied at the base of the structure. The accelerometers shall be provided at the Terminal Pad of the equipment and any other point as agreed by the Purchaser. The seismic test shall be carried out in all possible combinations of the equipment. The seismic test procedure shall be furnished for approval of the Purchaser.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page50of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR)

ANNEXURE - C LIST OF SPECIFICATIONS GENERAL STANDARDS AND CODES India Electricity Rules Indian Electricity Act Indian Electricity (Supply) Act Indian Factories Act IS-5, IS-335, IS-617, IS-1448 (P1 to P 145) IS-2071 (P1 to P3) IS-12063 IS-2165 P1:1997 P2:1983 IS-3043 IS-6103 IS-6104 IS-6262 IS-6792 IS-5578 IS-11353 IS-8263 IS-9224 (Part 1,2&4) IEC-60060 (Part 1 to P4) IEC 60068 IEC-60117 IEC-60156, IEC-60270, Code of Practice for Earthing Method of Test for Specific Resistance (Resistivity) of Electrical Insulating Liquids Method of Test for Interfacial Tension of Oil against Water by the Ring Method Method of test for Power factor & Dielectric Constant of Electrical Insulating Liquids. Method for determination of electric strength of insulating oils. Guide for marking of insulated conductors. Guide for uniform system of marking & identification of conductors & apparatus terminals. Methods for Radio Interference Test on High voltage Insulators. Low Voltage Fuses High Voltage Test Techniques Environmental Test Graphical Symbols Method for the Determination of the Electrical Strength of Insulation Oils. Partial Discharge Measurements. Insulation Coordination. Colors for Ready Mixed Paints and Enamels. New Insulating Oils.

Aluminium and Aluminium Alloy Ingots and Castings for General Engineering Purposes Methods of Test for Petroleum and its Products. Methods of High Voltage Testing. Classification of degrees of protection provided by enclosures of electrical equipment.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page51of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IEC-60376 IEC-60437 IEC-60507 IEC-62271-1 IEC-60815 IEC-60865 (P1 & P2) ANSI-C.1/NFPA.70 ANSI-C37.90A ANSI-C63.21, C63.3 C36.4ANSI-C68.1 ANSI-C76.1/EEE21 ANSI-SI-4 ANSI-Y32-2/C337.2 ANSI-Z55.11 NEMA-107T NEMA-ICS-II CISPR-1 CSA-Z299.1-1978h CSA-Z299.2-1979h CSA-Z299.3-1979h CSA-Z299.4-1979h Specification and Acceptance of New Sulphur Hexafloride Radio Interference Test on High Voltage Insulators. Artificial Pollution Tests on High Voltage Insulators to be used on AC Systems. Common Specification for High Voltage Switchgear & Controlgear Standards. Guide for the Selection of Insulators in respect of Polluted Conditions. Short Circuit Current - Calculation of effects. National Electrical Code Guide for Surge Withstand Capability (SWC) Tests Specification for Electromagnetic Noise and Field Strength Instrumentation 10 KHz to 1 GHZ Techniquest for Dielectric Tests Standard General Requirements and Test Procedure for Outdoor Apparatus Bushings. Specification for Sound Level Metres Drawing Symbols Gray Finishes for Industrial Apparatus and Equipment No. 61 Light Gray Methods of Measurements of RIV of High Voltage Apparatus General Standards for Industrial Control and Systems Part ICSI-109 Specification for CISPR Radio Interference Measuring Apparatus for the frequency range 0.15 MHz to 30 MHz Quality Assurance Program Requirements Quality Control Program Requirements Quality Verification Program Requirements Inspection Program Requirements

TRANSFORMERS AND REACTORS IS:10028 (Part 2 & 3) Code of practice for selection, installation & maintenance of Transformers (P1:1993), (P2:1991), (P3:1991) Power Transformers Dimensions for Porcelain transformer Bushings for use in lightly polluted atmospheres. Fittings and Accessories for Power Transformers

IS-2026 (P1 to P4) IS-3347 (part 1 to Part 8) IS-3639

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page52of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-6600 IEC-60076 (Part 1 to 5) IEC-60214 IEC-60289 IEC- 60354 IEC-60076-10 ANSI-C571280 ANSI-C571290 ANSI-C5716 ANSI-C5721 ANSI-C5792 Guide for Loading of OIl immersed Transformers. Power Transformers On-Load Tap-Changers. Reactors. Loading Guide for Oil - Immersed power trans formers Determination of Transformer and Reactor Sound Levels General requirements for Distribution, Power and Regulating Transformers Test Code for Distribution, Power and Regulation Transformers Terminology & Test Code for Current Limiting Reactors Requirements, Terminology and Test Code for Shunt Reactors Rated Over 500 KVA Guide for Loading Oil-Immersed Power Transformers upto and including 100 MVA with 55 deg C or 65 deg C Winding Rise Standard Techniques for High Voltage Testing High-voltage switchgear and controlgear - Part 100: Alternating current circuit-breakers High-voltage switchgear and controlgear - Part 101: Synthetic testing Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than 1 000 V High-voltage switchgear and controlgear - Part 110: Inductive load switching High-voltage switchgear and controlgear - Part 110: Inductive load switching TRANSFORMERS AND COUPLING

ANSI-CG,1EEE-4 CIRCUIT BREAKERS IEC-62271-100 IEC-62271-101 IEC-62155

IEC-62271-110 IEC-62271-109

CURRENT TRANSFORMERS, VOLTAGE CAPACITOR VOLTAGE TRANSFORMERS IS-2705- (P1 to P4) IS:3156- (P1 to P4) IS-4379 IEC-60044-1 IEC-60044-2 IEC-60044-5 IEC-60358 -

Current Transformers. Voltage Transformers. Identification of the Contents of Industrial Gas Cylinders Current transformers. Inductive Voltage Transformers.
Instrument transformers - Part 5: Capacitor voltage transformers

Coupling capacitors and capacitor dividers.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page53of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IEC-60044-4 IEC-60481 ANSI-C5713 ANSIC92.2 ANSI-C93.1 BUSHING IS-2099 IEC-60137 SURGE ARRESTERS IS-3070 (PART2) IEC-60099-4 IEC-60099-5 ANSI-C62.1 NEMA-LA 1 IS-722, IS-1248, IS-3231, 3231 (P-3) IS:5039 IEC-60068.2.2 IEC-60529 IEC-60947-4-1 IEC-61095 IEC-60439 (P1 & 2) ANSI-C37.20 ANSI-C37.50 ANSI-C39 ANSI-C83 IS: 8623: (Part I to 3) NEMA-AB NEMA-CS NEMA-PB-1 NEMA-SG-5 Lightning arresters for alternating current systems : Metal oxide lightning arrestors without gaps. Metal oxide surge arrestors without gaps Selection and application recommendation IEE Standards for S A for AC Power Circuits Surge Arresters Electrical relays for power system protection Distributed pillars for Voltages not Exceeding 1000 Volts. Basic environmental testing procedures Part 2: Test B: Dry heat Degree of Protection provided by enclosures. Low voltage switchgear and control gear. Electromechanical Contactors for household and similar purposes. Low Voltage Switchgear and control gear assemblies Switchgear Assemblies, including metal enclosed bus. Test Procedures for Low Voltage Alternating Current Power Circuit Breakers Electric Measuring instrument Components for Electric Equipment Specification for Switchgear & Control Assemblies. Moulded Case Circuit and Systems Industrial Controls and Systems Panel Boards Low voltage Power Circuit breakers Page54of74 Bushings for Alternating Voltages above 1000V Insulated Bushings for Alternating Voltages above 1000V Instrument Transformes : Measurement of Partial Discharges Coupling Devices for power Line Carrier Systems. Requirements for Instrument transformers Power Line Coupling voltage Transformers Requirements for Power Line Carrier Coupling Capacitors

CUBICLES AND PANELS & OTHER RELATED EQUIPMENTS

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) NEMA-SG-3 NEMA-SG-6 NEMA-5E-3 1248 (P1 to P9) Disconnecting switches IEC-62271-102 High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches

Power Switchgear Assemblies Power switching Equipment Motor Control Centers Direct acting indicating analogue electrical measuring instruments & their accessories.

IEC-60265 (Part 1 & 2) ANSI-C37.32

High Voltage switches Schedule of preferred Ratings, Manufacturing Specifications and Application Guide for high voltage Air Switches, Bus supports and switch accessories Test Code for high voltage air switches Power switching equipment Line traps for AC power system. Methods of tests for line traps. Coupling devices for PLC systems. Methods of test for coupling devices for PLC systems. Line traps for A.C. power systems. Coupling Devices for power line carrier systems. Single sideboard power line carrier terminals Planning of (single Side-Band) power line carrier systems. Teleprotection report by Committee 34 & 35. Guide on power line carrier 1979. International Radio Consultative Committee International Telegraph & Telephone Consultative Committee Electric Industries Association Recommendations for Direct Acting indicating analogue electrical measuring instruments and their accessories. Electrical relays. Dimensions of mechanical structures of the 482.6mm (19 inches) series. Expression of the performance of electrical & electronic measuring equipment. Symbols for Alternating-Current Electricity meters. Page55of74

ANSI-C37.34 NEMA-SG6 PLCC and line traps IS-8792 IS-8793 IS-8997 IS-8998 IEC-60353 IEC-60481 IEC-60495 IEC-60683 CIGRE CIGRE CCIR CCITT EIA IEC-60051: (P1 to P9) IEC-60255 (Part 1 to 23) IEC-60297 (P1 to P4) IEC-60359 IEC-60387

Protection and control equipment

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IEC-60447 IEC-60521 IEC-60547 Man machine interface (MMI) - Actuating principles. Class 0.5, 1 and 2 alternating current watt hour metres Modular plug-in Unit and standard 19-inch rack mounting unit based on NIM Standard (for electronic nuclear instruments) Screw threads Bolts and Nuts Relays, Station Controls etc. Manual and automatic station control, supervisory and associated telemetering equipment Relays and relay systems associated with electric power apparatus Requirements for electrical analog indicating instruments Three phase induction motors. Degree of protection provided by enclosure for rotating electrical machinery. Rotating electrical machines Three phase induction motors

ANSI-81 ANSI-B18 ANSI-C37.1 ANSI-C37.2 ANSI-C37.2 ANSI-C39.1 MOTORS IS-325 IS-4691 IEC-60034 (P1 to P19:) IEC-Document 2

(Central Office) NEMA-MGI Motors and Generators Electronic equipment and components MIL-21B, MIL-833 & MIL-2750 IEC-60068 (P1 to P5) IEC-60326 (P1 to P2) IS-1363 (P1 to P3) IS-1364 (P1 to P5) IS-3138 ISO-898 ASTM Clamps & connectors IS-5561 NEMA-CC1 NEMA-CC 3 Electric power connectors. Electric Power connectors for sub station Connectors for Use between aluminium or aluminumCopper Overhead Conductors Fittings for Aluminum and steel cored Al conductors for overhead power lines. Page56of74 Environmental testing Printed boards Material and workmanship standards Hexagon headbolts, screws and nuts of product grade C. Hexagon head bolts, screws and nuts of products grades A and B. Hexagonal Bolts and Nuts (M42 to M150) Fasteners: Bolts, screws and studs Specification and tests for materials

Bus hardware and insulators IS: 2121 -

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-731 IS-2486 (P1 to P4) IEC-60120 IEC-60137 IEC-60168 Porcelain insulators for overhead power lines with a nominal voltage greater than 1000 V. Insulator fittings for overhead power lines with a nominal voltage greater than 1000 V. Dimensions of Ball and Socket Couplings of string insulator units. Insulated bushings for alternating voltages above 1000 V. Tests on indoor and outdoor post insulators of ceramic material or glass for Systems with Nominal Voltages Greater than 1000 V.
Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than 1 000 V

IEC-62155

IEC-60273 IEC-61462

Characteristices of indoor and outdoor post insulators for systems with nominal voltages greater than 1000V. Pressurized and un-pressurized insulator for use in electrical equipment with rated voltage greater than 1000V Definitions, Test methods, acceptance criteria and design recommendations Insulators for overhead lines with nominal voltage above 1000V-ceramic or glass insulator units for a.c. systems Characteristics of String Insulator Units of the cap and pintype. Locking devices for ball and socket couplings of string insulator units : dimensions and tests. Insulators for overhead lines with a nominal voltage above 1000 V. Characteristics of string insulator units of the long rod type. Dimensions of Clevis and tongue couplings of string insulator units. Wet process proelain insulators Test methods for electrical power insulators For insulators, wet-process porcelain and toughened glass suspension type For wet-process porcelain insulators apparatus, posttype Iron and steel hardware Recommendations of the CISPR, tolerances of form and of Position, Part 1 Zinc Coating (Hot-Dip) on iron and steel hardware Dimensions & tolerances for Wrought Aluminum and Aluminum Alloys drawn round tube. Page57of74

IEC-60305

IEC-60372 (1984) IEC-60383 (P1 and P2) IEC-60433 IEC-60471 ANSI-C29 ANSI-C29.1 ANSI-C92.2 ANSI-C29.8 ANSI-G.8 CISPR-7B ASTM A-153 IS-2678

Strain and rigid bus-conductor

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-5082 ASTM-B 230-82 ASTM-B 231-81 ASTM-B 221 ASTM-B 236-83 ASTM-B 317-83 Wrought Aluminum and Aluminum Alloy Bars. Rods, Tubes and Sections for Electrical purposes. Aluminum 1350 H19 Wire for electrical purposes Concentric - lay - stranded, aluminum 1350 conductors Aluminum - Alloy extruded bar, road, wire, shape Aluminum bars for electrical purpose (Bus-bars) Aluminum-Alloy extruded bar, rod, pipe and structural shapes for electrical purposes (Bus Conductors)

Batteries and batteries charger Battery IS:1651 IS:1652 IS:1146 IS:6071 IS:266 IS:1069 IS:3116 IS:1248 IS:10918 IEC:60896-21&22 IEC: 60623 IEC:60622 IEC:60623 IEC:60896-11 IEEE-485 IEEE-1115 IEEE-1187 IEEE-1188 IEEE-1189 Battery Charger Stationary Cells and Batteries, Lead-Acid Type (with Tubular Positive Plates) Stationary Cells and Batteries, Lead-Acid Type (with Plante Positive Plates) Rubber and Plastic Containers for Lead-Acid Storage Batteries Synthetic Separators for Lead-Acid Batteries Specification for Sulphuric Acid Specification for Water for Storage Batteries Specification for Sealing Compound for Lead-Acid Batteries Indicating Instruments Vented type nickel Cadmium Batteries Lead Acid Batteries Valve Regulated types Methods of Tests & Requirements Vented type nickel Cadmium Batteries Secondary Cells & Batteries Sealed Ni-Cd rechargeable single cell Secondary Cells & Batteries Vented Ni-Cd rechargeable single cell Stationary Lead Acid Batteries Vented Type General requirements & method of tests Recommended practices for sizing of Lead Acid Batteries Sizing of Ni-Cd Batteries Recommended practices for design & installation of VRLA Batteries Recommended practices for design & installation of VRLA Batteries Guide for selection of VRLA Batteries

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page58of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS:3895 IS:4540 IS:6619 IS:2026 IS:2959 IS:1248 IS:2208 IS:13947 (Part-3) Mono-crystalline Semiconductor Rectifier Cells and Stacks Mono-crystalline Semiconductor Rectifier Assemblies and Equipment. Safety Code for Semiconductor Rectifier Equipment Power Transformers AC Contactors for Voltages not Exceeding 1000 Volts Indicating Instruments HRC Fuses Air break switches, air break disconnectors & fuse combination units for voltage not exceeding 1000V AC or 1200V DC Degree of protection provided by enclosures for low voltage switchgear and controlgear. Code of practice for phosphating of Iron and Steel Electrical relays for power system protection Electrical relay for AC Systems Colours for ready mix paint Recommended Design for installation design and installation of large lead storage batteries for generating stations and substations. Sizing large lead storage batteries for generating stations and substations Measuring the minimum oxygen concentration to support candle like combustion of plastics (oxygen index) PVC insulated cables for working voltages upto and including 1100 Volts. Code of practice for installation and maintenance of power cables, upto and including 33 kV rating PVC insulated (heavy duty) electric cables (part 1) for working voltage upto and including 1100 V. Part (2) for working voltage from 3.3 kV upto and including 11kV. Aluminium conductor for insulated cables Copper Conductor in insulated cables. Recommended current ratings for cables. Mild steel wires, formed wires and tapes for armouring of cables. PVC insulating and sheath of electric cables. Elastometric insulating and sheath of electric cables. Page59of74

IS:2147 IS:6005 IS:3231 IS:3842 IS:5 IEEE-484

IEEE-485 Wires and cables ASTMD-2863

IS-694 IS-1255 IS-1554 (P1 and P2)

IS:1753 IS:2982 IS-3961 (P1 to P5) IS-3975 IS-5831 IS-6380

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-7098 Cross linked polyethylene insulated PVC sheathed cables for working voltage upto and including 1100 volts. Cross-linked polyethyle insulated PVC sheathed cables for working voltage from 3.3kV upto and including 33 kV. Conductors for insulated electrical cables and flexible cords. Aluminum Conductors for insulated cables. Specification for drums for electric cables. Radio Frequency cables. Guide to the Selection of High Voltage Cables. Low frequency cables and wires with PVC insulation and PVC sheath. Polyvinyl Chloride insulated cables of rated voltages up to and including 450/750V. Conductors of insulated cables Impulse tests on cables and their accessories. Calculation of the continuous current rating of cables (100% load factor). Standard colours for insulation for low-frequency cables and wires. Fire resisting characteristics of Electric cables. Tests on electric cables under fire conditions. Extruded solid dielectric insulated power cables for rated voltages from 1 kV upto to 30 kV Tests on gases evolved during combustion of electric cables. Safety code for air conditioning Safety code for Mechanical Refrigeration Standard for Positive Displacement RefrigerationCompressor and Condensing Units Shell and tube type heat exchanger Method of testing for rating of liquid coolers Refrigeration Piping Steel for general structural purposes Specification for Metal Air Dust Specification for Galvanised Steel Sheets Specification for Wrought Aluminium and Aluminium Sheet & Strip Hot rolled cast steel sheet & strip Page60of74

IS-7098

IS-8130 IS-1753 IS-10418 IEC-60096 (part 0 to p4) IEC-60183 IEC-60189 (P1 to P7) IEC-60227 (P1 to P7) IEC-60228 IEC-60230 IEC-60287 (P1 to P3) IEC-60304 IEC-60331 IEC-60332 (P1 to P3) IEC-60502 IEC-754 (P1 and P2)

AIR conditioning and ventilation IS-659 IS-660 ARI:520 IS:4503 ASHRAE-24 ANSI-B-31.5 IS:2062 IS:655 IS:277 IS-737 IS-1079 -

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-3588 IS-2312 BS-848 BS-6540 Part-I BS-3928 US-PED-2098 MIL-STD-282 ASHRAE-52 IS:3069 IS:4671 IS:8183 IS:3346 ASTM-C-591-69 IS:4894 BS:848 IS:325 IS:4722 IS:1231 IS:2233 IS:2254 IS:7816 IS:4029 IS:4729 IS:4691 IS:7572 IS:2148 BS:4999 (Part-51) Galvanizing IS-209 Zinc Ingot Page61of74 Specification for Electrical Axial Flow Fans Propeller Type AC VentilationFans Methods of Performance Test for Fans Air Filters used in Air Conditioning and General Ventilation Sodium Flame Test for Air Filters (Other than for Air Supply to I.C. Engines and Compressors) Method of cold DOP & hot DOP test DOP smoke penetration method Air cleaning device used in general ventilation for removing particle matter Glossary of Terms, Symbols and Units Relating to Thermal Insulation Materials. Expanded Polystyrene for Thermal Insulation Purposes Bonded Mineral Wool Evaluation of Thermal Conductivity properties by means of guarded hot plate method Standard specification for rigid preformed cellular urethane thermal insulation Centrifugal Fans Method of Performance Test for Centrifugal Fans Induction motors, three-phase Rotating electrical machines Three phase foot mounted Induction motors, dimensions of Designations of types of construction and mounting arrangements of rotating electrical machines Vertical shaft motors for pumps, dimensions of Guide for testing insulation resistance of rotating machines Guide for testing three phase induction motors Rotating electrical machines, vibration of, Measurement and evaluation of Degree of protection provided by enclosures for rotating electrical machinery Guide for testing single-phase a.c. motors Flame proof enclosure for electrical apparatus Noise levels

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-2629 IS-2633 ASTM-A-123 Recommended Practice for Hot-Dip galvanizing on iron and steel. Methods for testing uniformity of coating of zinc coated articles. Specification for zinc (Hot Galavanizing) Coatings, on products Fabricated from rolled, pressed and forged steel shapes, plates, bars and strips. Zinc-coated (Galvanized) steel barbed wire Code of practice for phosphating of iron and steel. Gray finishes for industrial apparatus and equipment Steel structure painting council

ASTM-A-121-77 Painting IS-6005 ANSI-Z551 SSPEC Fire protection system

Fire protection manul issued by tariff advisory committee (TAC) of India HORIZONTAL CENTRIFUGAL PUMPS IS:1520 IS:9137 IS:5120 API-610 BS:599 PTC-8.2 DIESEL ENGINES IS:10000 IS:10002 Methods of tests for internal combustion engines Specification for performance requirements for constant speed compression ignition engines for general purposes (above 20 kW) The performance of reciprocating compression ignition (Diesel) engines, utilising liquid fuel only, for general purposes Reciprocating internal combustion engines performance Dimensions for pipe threads where pressure tight joints are required on threads Internal combustion engine PTC-17 Codes of Diesel Engine Manufacturers Association, USA Non percolating flexible fire fighting delivery hose Sheet rubber jointing and rubber inserting jointing Horizontal centrifugal pumps for clear, cold and fresh water Code for acceptance test for centrifugal & axial pumps Technical requirement - Rotodynamic special purpose pumps Centrifugal pumps for general services Hydraulic Institutes Standards Methods of testing pumps Power Test Codes - Centrifugal pumps

BS:5514

ISO:3046 IS:554 ASME Power Test Code

PIPING VALVES & SPECIALITIES IS:636 IS:638 -

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page62of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS:778 IS:780 IS:901 IS:902 IS:903 IS:1538 IS:1903 IS:2062 IS:2379 IS:2643 IS:2685 IS:2906 IS:3582 IS:3589 IS:4038 IS:4927 IS:5290 IS:5312 (Part-I) IS:5306 Part-I Part-II BS:5150 IS:325 IS:900 IS:996 IS:1231 IS:2148 Code of practice for fire extinguishing installations and equipment on premises Hydrant systems, hose reels and foam inlets Sprinkler systems Specification for cast iron gate valves Three phase induction motors Code of practice for installation and maintenance of induction motors Single phase small AC and universal electric motors Dimensions of three phase foot mounted induction motors Flame proof enclosure of electrical apparatus Gun metal gate, globe and check valves for general purpose Sluice valves for water works purposes (50 to 300 mm) Couplings, double male and double female instantaneous pattern for fire fighting Suction hose couplings for fire fighting purposes Fire hose delivery couplings branch pipe nozzles and nozzle spanner Cast iron fittings for pressure pipes for water, gas and sewage Ball valve (horizontal plunger type) including floats for water supply purposes SP for weldable structural steel Colour Code for the identification of pipelines Dimensions of pipe threads for fastening purposes Code of Practice for selection, installation and maintenance of sluice valves Sluice valves for water-works purposes (350 to 1200 mm size) Basket strainers for fire fighting purposes (cylindrical type) Electrically welded steel pipes for water, gas and sewage (150 to 2000 mm nominal diameter) Foot valves for water works purposes Unlined flax canvas hose for fire fighting Landing valves (internal hydrant) Swing check type reflex (non-return) valves

MOTORS & ANNUNCIATION PANELS

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page63of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS:2223 IS:2253 IS:2254 IS:3202 IS:4029 IS:4691 IS:4722 IS:4729 IS:5572 IS:6362 IS:6381 IS:7816 IS:4064 IEC DOCUMENT 2 (Control Office) 432 VDE 0530 Part I/66 IS:9224 (Part-II) IS:6875 IS:694 IS:1248 IS:375 IS:2147 IS:5 IS:2959 PG Test Procedures NFPA-13 NFPA-15 NFPA-12A NFPA-72E NFPA-12 Standard for the installation of sprinkler system Standard for water spray fixed system for the fire protection Standard for Halong 1301 Fire Extinguishing System Standard on Antomatic Fire Detectors Standard on Carbon dioxide extinguisher systems Page64of74 Push Button and Control Switches PVC Insulated cables Indicating instruments Auxiliary wiring & busbar markings Degree of protection Colour Relay and timers Contactors Three Phase Induction Motor HRC Fuses Dimensions of flange mounted AC induction motors Designations for types of construction and mounting arrangements of rotating electrical machines Dimensions of vertical shaft motors for pumps Code of practice for climate proofing of electrical equipment Guide for testing three phase induction motors Degree of protection provided by enclosure for rotating electrical machinery Rotating electrical machines Measurement and evaluation of vibration of rotating electrical machines Classification of hazardous areas for electrical (Part-I) installations (Areas having gases and vapours) Designation of methods of cooling for rotating electrical machines Construction and testing of electrical apparatus with type of protection e Guide for testing insulation for rotating machine Air break switches Three Phase Induction Motor

Fire Protection Manual by TAC (Latest Edition)

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS:3034 IS:2878 IS:2171 IS:940 D.G. SET IS:10002 Specification for performance requirements for constant speed compression ignition (diesel engine) for general purposes Method of tests for internal combustion engines Rotating electrical machines-specification Degree of protection provided by enclosures Permissible limit of noise levels for rotating electrical machines. Indian Explosive Act 1932 Method of Chemical Analysis of pig iron, cast iron and plain carbon and low alloy steels. Code of practice for use of structural steel in overhead transmission line towers. Code of practice for use of steel tubes in general building construction Dimensions for hot rolled steel beam, column channel and angle sections. Covered electrodes for manual arc welding of carbon of carbon manganese steel. Code of Practice for use of metal arc welding for general construction in Mild steel Code of practice for training and testing of metal arc welders. Part 1 : Manual Metal arc welding. Code of practice for design loads (other than earthquake) for buildings and structures. Steel tubes for structural purposes. Recommended practice for radiographic examination of fusion welded butt joints in steel plates. Hexagonal head bolts, screws & nuts of products grade C. Hexagon headbolts, screws and nuts of product grades A and B. Technical supply condition for threaded steel fasteners. Methods for bend test. Method for tensile testing of steel products. Page65of74 Fire of industrial building: CO2 (Carbon dioxide) Type Extinguisher DC (Dry Chemical Powder) type Pressurised Water Type

Electrical generating and distributing stations code of practice

IS:10000 IS:4722 IS:12063 IS:12065

Steel structures IS-228 (1992) IS-802 (P1 to 3:) IS-806 IS-808 IS-814 IS-816 IS-817 IS-875 (P1 to P4) IS-1161 IS-1182 IS-1363 (P1 to P3) IS-1364 IS-1367 (P1 to P18) IS-1599 IS-1608 -

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-1893 IS-1978 IS-2062 IS-2595 IS-3063 IS-3664 IS-7205 IS-9595 ANSI-B18.2.1 ANSI-B18.2.2 ANSI-G8.14 ASTM-A6 ASTM-A36 ASTM-A47 ASTM-A143 Criteria for earthquake resistant design of structures. Line Pipe. Steel for general structural purposes. Code of practice for Radiographic testing. Single coil rectagular section spring washers for bolts, nuts and screws. Code of practice for ultrasonic pulse echo testing by contact and immersion methods. Safety code for erection of structural steel work. Recommendations for metal arc welding of carbon and carbon manganese steels. Inch series square and Hexagonal bolts and screws Square and hexagonal nuts Round head bolts Specification for General Requirements for rolled steel plates, shapes, sheet piling and bars of structural use Specifications of structural steel Specification for malleable iron castings Practice for safeguarding against embilement of Hot Galvanized structural steel products and procedure for detaching embrilement Specification for high strength low alloy structural steel Specification for low and intermediate tensile strength carbon steel plates of structural quality Specification for Galvanized steel transmission tower bolts and nuts Specification for High strength low alloy structural manganese vanadium steel. Specification for High strength low alloy colombiumVanadium steel of structural quality Code for welding in building construction welding inspection Structural welding code American institute of steel construction Manufactured graphite electrodes Mild steel tubes, tubulars and other wrought steel fittings Seamless Electrically welded steel pipes for water, gas and sewage. Steel pipe flanges Boiler and pressure vessel code Page66of74

ASTM-A242 ASTM-A283 ASTM-A394 ASTM-441 ASTM-A572 AWS D1-0 AWS D1-1 AISC NEMA-CG1 IS-1239 (Part 1 and 2) IS-3589 IS-6392 ASME

Piping and pressure vessels

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) ASTM-A120 Specification for pipe steel, black and hot dipped, zinccoated (Galvanized) welded and seamless steel pipe for ordinary use Specification for pipe, steel, black, and hot-dipped, zinc coated welded and seamless Seamless carbon steel pipe for high temperature service Low and intermediate tensile strength carbon-silicon steel plates for machine parts and general construction. Pipe fittings of wrought carbon steel and alloy steel for moderate and elevated temperatures Specification for forgings, carbon steel for general purpose piping Forgings, carbon steel for piping components Carbon steel externally threated standard fasteners Alloy steel and stainless steel bolting materials for high temperature service Flat rolled electrical steel for magnetic applications Cupola malleable iron Pipe threads (Except dry seal) Cast iron pipe flangesand glanged fitting. Class 25, 125, 250 and 800 Malleable iron threaded fittings, class 150 and 300 Pipe flanges and flanged fittings, steel nickel alloy and other special alloys Factory-made wrought steel butt welding fittings Forged steel fittings, socket-welding and threaded Ferrous pipe plug, bushings and locknuts with piplethreads Butt welding ends Fire hose couplings screw thread. Inch series square and hexagonal bolts and screws Square and hexagonal nuts Lock washers Plain washers Power piping Welded and seamless wrought steel pipe Stainless steel pipe 33 grade ordinary portland cement. Galvanized steel chain link fence fabric Page67of74

ASTM-A53 ASTM-A106 ASTM-A284 ASTM-A234 ASTM-S181 ASTM-A105 ASTM-A307 ASTM-A193 ASTM-A345 ASTM-A197 ANSI-B2.1 ANSI-B16.1 ANSI-B16.1 ANSI-B16.5 ANSI-B16.9 ANSI-B16.11 ANSI-B16.14 ANSI-B16.25 ANSI-B18.1.1 ANSI-B18.2.1 ANSI-B18.2.2 NSI-B18.21.1 ANSI-B18.21.2 ANSI-B31.1 ANSI-B36.10 ANSI-B36.9 IS-269 IS2721

Other civil works standards

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS-278 IS-383 IS-432 (P1 and P2) IS-456 IS-516 IS-800 IS-806 IS-1172 IS-1199 IS-1566 IS-1742 IS-1785 IS-1786 IS-1811 IS-1893 IS-2062 IS-2064 IS-2065 IS-2090 IS-2140 IS-2470 (P1 & P2) IS-2514 IS-2645 IS-3025 (Part 1 to Part 48) IS-4091 IS-4111 (Part 1 to P5) IS-4990 IS-5600 Code of practice for ancillary structures in sewerage system. Plywood for concrete shuttering work. Sewage and drainage pumps. Methods of sampling and test (Physical and chemical) for water and waste water. Code of practice for design and construction of foundations for transmission line towers and poles. Galvanized steel barbed wire for fencing. Coarse and fine aggregates from natural sources for concrete. Mild steel and medium tensile steel bars and hard-dawn steel wire for concrete reinforcement. Code of practice for plain and reinforced concrete. Method of test for strength of concrete. Code of practice for general construction in steel. Steel tubes for structural purposes. Basic requirements for water supply, drainage and sanitation. Methods of sampling and analysis of concrete. Hard-dawn steel wire fabric for concrete reinforcement. Code of Practice for Building drainage. Plain hard-drawn steel wire for prestressed concrete. High strength deformed Steel Bars and wires for concrete reinforcement. Methods of sampling Foundry sands. Criteria for earthquake resistant design of structures. Steel for general structural purposes. Selection, installation and maintenance of sanitary appliances-code of practices. Code of practice for water supply in buildings. High tension steel bars used in prestressed concrete. Standard Galvanized steel wire for fencing. Code of practice for installation of septic tanks. Concrete vibrating tables. Integral cement waterproofing compounds.

National buiding code of India 1970

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page68of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) USBR E12 ASTM-A392-81 ASTM-D1557-80 ASTM-D1586 (1967) ASTM-D2049-69 ASTM-D2435 Earth Manual by United States Department of the interior Bureau of Reclamation Zinc/Coated steel chain link fence fabric test for moisture-density relation of soils using 10-lb (4.5 kg) rame land 18-in. (457 mm) Drop. Penetration Test and Split-Barrel Sampling of Soils Test Method for Relative Density of Cohesionless Soils Test method for Unconsolidated, (1982) Undrained Strengths of Cohesive Soils in Triaxial Compression. BS-5075 CPWD IS:6745 Specification for accelerating Part I Admixtures, Retarding Admixtures and Water Reducing Admixtures. Latest CPWD specifications

ACSR MOOSE CONDUCTOR Methods for Determination of BS:443-1969 Mass of zinc coating on zinc coated Iron and Steel Articles Methods for Radio Interference Test on High Voltage Insulators NEMA:107-1964 CISPR Zinc Ingot BS:3436-1961 IEC:209-1966 Aluminum Conductors for

IS:8263 IEC:437-1973 IS:209 IS:398 Part - V BS:215(Part-II) BS:215(Part-II) IS:1778 IS:1521 IS:2629

Overhead Transmission Purposes Aluminium Conductors galvanized IEC:209-1966 steel reinforced extra high voltage (400 kV and above) Reels and Drums forBS:1559-1949 Bare Conductors Method for Tensile Testing Recommended practice for Hot dip Galvanising on Iron and Steel. Method for Testing Uniformity of coating of zinc Coated Articles. Hot dip galvanised coatings on round steel wires ASTMA-472-729 Method for Tensile Testing ISO/R:89-1959 of Steel Wire Reels and Drums for Bare Conductors ISO/R89-1959of steel wire

IS:2633 IS:4826

GALVANISED STEEL EARTHWIRE IS:1521 IS:1778

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page69of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS:2629 IS:2633 IS:4826 IS:6745 IS:209 IS:398 (Pt. I to P5:1992) IS:1913 IS:3528 IS:4012 IS:4013 IS:10322 IS:10322 IS:2206 IS:10322 IS:10322 IS:10322 IS:2418 IS:9900 IS:1258 IS:3323 IS:1534 IS:1569 IS:2215 IS:3324 IS:418 IS:3553 IS:2713 IS:280 IS:9537 IS:3480 IS:2667 Recommended practice for Hot Dip Galvanising on Iron and Steel. Methods for testing Uniformity of Coating of Zinc Coated Articles. Hot dip Galvanised Coatings ASTM:A 475-72a Steel Wires BS:443-1969 on Round

Method for Determination BS:443-1969of mass of Zinc Coating on Zinc coated Iron and Steel Articles. Zinc ingot BS:3463-1961 BS:215 (Part-II) Aluminum Conductors for

overhead transmission purposes. General and safety requirements for electric lighting fittings. Water proof electric lighting fittings. Dust proof electric lighting fittings. Dust tight proof electric lighting fittings. Industrial lighting fittings with metal reflectors. Industrial lighting fittings with plastic reflectors. Well glass lighting fittings for use under ground in mines (nonflameproof type). Specification for flood light. Specification for decorative lighting outfits. Luminaries for street lighting Tubular fluorescent lamps High pressure mercury vapour lamps. Specification for Bayonet lamp fluorescent lamp. Bi-pin lamp holder tubular fluorescent lamps. Ballasts for use in fluorescent lighting fittings. (Part-I) Capacitors for use in fluorescent lighting fittings. Starters for fluorescent lamps. Holders for starters for tubular fluorescent lamps GLS lamps Water tight electric fittings Tubular steel poles MS wire for general engg. purposes Rigid steel conduits for electrical wiring Flexible steel conduits for electrical wiring Fittings for rigid steel conduits for electrical wiring Page70of74

Lighting Fixtures and Accessories

Conduits, Accessories and Junction Boxes

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS:3837 IS:4649 IS:5133 IS:2629 Lighting Panels IS:13947 IS:8828 IS:5 IS:2551 IS:2705 IS:9224 (7)IS:5082 (8)IS:8623 (9)IS:1248 Electrical Installation IS:1293 IS:371 IS:3854 IS:5216 IS:732 IS:3043 IS:3646 IS:1944 IS:5571 IS:800 IS:2633 IS:6005 3 pin plug Two to three ceiling roses Switches for domestic and similar purposes Guide for safety procedures and practices in electrical work. Code of practice for electrical wiring installation (system voltage not exceeding 650 Volts.) Code of practice for earthing. Code of practice of interior illumination part II & III. Code of practice for lighting of public through fares. Guide for selection of electrical equipment for hazardous areas. Code of practice for use of structural steel in general building construction. Methods of Testing uniformity of coating on zinc coated articles. Code of practice for phosphating iron and steel. INDIAN ELECTRICITY ACT INDIAN ELECTRICITY RULES LT SWITCHGEAR IS:8623 (Part-I) Specification for low voltage switchgear and control gear assemblies Page71of74 LV Switchgear and Control gear(Part 1 to 5) Circuit breakers for over current protection for house hold and similar installations. Ready mix paints Danger notice plates Current transformers HRC Cartridge fuse links for voltage above 650V(Part-2) Wrought aluminium and Al. alloys, bars, rods, tubes and sections for electrical purposes. Factory built Assemblies of Switchgear and Control Gear for voltages upto and including 1000V AC and 1200V DC. Direct Acting electrical indicating instruments Accessories for rigid steel conduits for electrical wiring Adaptors for flexible steel conduits. Steel and Cast Iron Boxes Hot dip galvanising of Iron & Steel.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) IS:13947 (Part-I) IS:13947 (part-2) IS:13947 (part-3) Specification for low voltage switchgear and control gear, Part 1 General Rules Specification for low voltage switchgear and control gear, Part 2 circuit breakers. Specification for low voltage switchgear and control gear. Part 3 Switches, Disconnectors, Switch-disconnectors and fuse combination units Specification for low voltage switchgear and control gear. Part 4 Contactors and motors starters. Specification for low voltage switchgear and control gear. Part 5 Control-circuit devices and switching elements Specification for low voltage switchgear and control gear. Part 6 Multiple function switching devices. Specification for low voltage switchgear and control gear. Part 7 Ancillary equipments Degree of protection provided by enclosures Current Transformers Voltage Transformers Electrical relays for power system protection Electrical indicating instruments AC Electricity meters Guide for Marking of insulated conductors of apparatus terminals Low voltage fuses for voltage not exceeding 1000V AC or 1500V DC Part 1 General Requirements Low voltage fuses for voltage not exceeding 1000V AC or 1500V DC Part 2 Fuses for use of authorized persons Code of practice of phosphating iron and steel Wrought Aluminum and Aluminum alloys for electrical purposes Hot dip galvanising

IS:13947 (part-4) IS:13947 (part-5) IS:13947 (part-6) IS:13947 (part-7) IS:12063 IS:2705 IS:3156 IS:3231 IS:1248 IS:722 IS:5578 IS:13703 (part 1) IS:13703 (part 2) IS:6005 IS:5082 IS:2633

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page72of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) ANNEXURE - D LIST OF DRAWINGS/DOCUMENTS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 14. 15 16. 17. 18. 19. Single Line Diagram Electrical Layout Plan and Sections DSLP Calculation and drawing Earthmat Design (if applicable) Structure Layout (Plan & Section) drawing Cantilever Strength calculations (if applicable) Design calculation for Sag Tension stringing chart GTP and drawings for Bus-Post Insulator Tension/suspension string insulator and Hardware Assembly GTP and drawing Soil Investigation Report (if applicable) Circuit Breakers (765kV, 400kV, 220kV,132 kV- As applicable) - GA drawing, GTP, Type test Reports CTs & CVTs (765kV, 400kV, 220kV,132 kV- As applicable) - GA drawing, GTP, Type test Reports Surge Arrestors (624kV, 336kV, 216kV,120 kV- As applicable) - GA drawing, GTP, Type test Reports Isolators (765kV, 400kV, 220kV,132 kV- As applicable) - GA drawing, GTP, Type test Reports Control and Relay Panels - GTP and technical literature PLCC & LINE TRAP - GTP and technical literature Civil Works (as applicable) - Control Room Building Structure Design, Foundation Design & Drg., Plinth Beam Design & Drg. and column Design & Drg. upto G.F. Level Auto transformer foundation design/drawings Reactor foundation design/drawings 765kV, 400kV and 220kV Tower foundation design/drawings.

. NOTE : 1.

The list of drawings/ documents mentioned above is a standard list. Some of the items may not be applicable and need not to be referred for a particular substation package. In case type tests are to be repeated, then approval of type test reports is not required at this stage. Category II approved drawings shall also be considered for release of second advance.

2. 3.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page73of74

SECTION- GENERAL TECHNICAL REQUIREMENTS (GTR) Annexure- E LIST OF THE MAKES FOR WHICH TYPE TEST REPORTS NOT REQUIRED TO BE SUBMITTED S.No. 1. 2. 3. 4. 5. 6. 7. 8. 9. ITEM DESCRIPTION Out door receptacles Tre foil clamp Diesel Engine Alternator Motors Cable Glands Junction Box Lighting Fixtures ACSR Conductor (Bersimis/ Moose/ Zebra) AAC Conductor (BULL) G.S. Earthwire MAKE CGL/ B&C / BCH / Sakti, Chennai /Indo Asian Moulded Fibre Glass Products, Calcutta K.Cummins / Ruston & Hornsby AVK / KIRLOSKAR / STAMFORD KEC / Siemens/ NGEF/Crompton/ABB Sunil & Co. / Arup/ Comet / QPIE Sarvana / ECS / C&S /Vikas/ Maktel/Unilac/Jasper/ Amara raja Phillips/CGL/Bajaj Sterlite/Apar/HVPL/ Sharavathy/Hiren Aluminium Ltd./Smita/Deepak Cables/Polycab wires/Cabcon Sterlite/Cabcon Sharavathy/Bharat Wire Ropes/Ramswarup

11. 12 NOTE :

For a new make other than above/POWERGRID approved list of sub vendor, type test reports as per relevant standard shall be submitted for Purchasers approval.

TechnicalSpecification:GTR C/ENGG/SPEC/GTR(Rev.No.:12)

Page74of74