Power factor correction and harmonic filtering

Capacitors and banks 50 Hz 400/415 V network voltage


Detuned reactors (DR)

The detuned reactors (DR) are designed to protect capacitors and avoid harmonic amplification present on the network.

Detuned reactors 400 V - 50 Hz Tuning order: 4.3 (215 Hz)


Power restored by the assembly reactor-capacitor 6.25 kvar/400 V - 50 Hz 12.5 kvar/400 V - 50 Hz 25 kvar/400 V - 50 Hz 50 kvar/400 V - 50 Hz 100 kvar/400 V - 50 Hz Power restored by the assembly reactor-capacitor 6.25 kvar/400 V - 50 Hz 12.5 kvar/400 V - 50 Hz 25 kvar/400 V - 50 Hz 50 kvar/400 V - 50 Hz 100 kvar/400 V - 50 Hz Power restored by the assembly reactor-capacitor 6.25 kvar/400 V - 50 Hz 12.5 kvar/400 V - 50 Hz 25 kvar/400 V - 50 Hz 50 kvar/400 V - 50 Hz 100 kvar/400 V - 50 Hz L (mH) 4.71 2.37 1.18 0.592 0.296 I1 (A) 9 17.9 35.8 71.7 143.3 Power losses (W) 100 150 200 320 480 Power losses (W) 100 150 200 300 450 Power losses (W) 100 150 200 400 600 Ref.

PB100029-60

51573 52404 52405 52406 52407 Ref.

Tuning order: 3.8 (190 Hz)


L (mH) 6.03 3 1.5 0.75 0.37 I1 (A) 9.1 18.2 36.4 72.8 145.5

51568 52352 52353 52354 51569 Ref.

Tuning order: 2.7 (135 Hz)


L (mH) 12.56 6.63 3.14 1.57 0.78 I1 (A) 9.3 17.6 37.2 74.5 149

Detuned reactors (DR)

51563 51564 51565 51566 51567

Technical data
b three phase, dry, with magnetic circuit, impregnated b cooling: natural b degre of protection: IP00 b class: H b standard: IEC 60289, EN 60289 b rated voltage: 400/415 V three phase 50 Hz b tuning order (relative impedance): 4.3 (5.4 %) ; 3.8 (6.9 %) ; 2.7 (13.7 %) b tolerance on L per phase: - 5, +5 % b v v v b maximum permissible current: Imp = Imp = 1.31 . I1 for tuning order 4.3 Imp = 1.19 . I1 for tuning order 3.8 Imp = 1.12 . I1 for tuning order 2.7 harmonic current spectrum:
2 + I2 + I2 + I2 ] [ ( 11 . I1 ) 2 + I 3 5 7 11

in % of current (I1) Current I3 Current I5 Current I7 Current I11

Tuning order 4.3 2% 69 % 19 % 6%

Tuning order 3.8 3% 44 % 13 % 5%

Tuning order 2.7 6% 17 % 6% 2%

b b b b b

insulation level: 1.1 kV thermal withstand Isc: 25 x Irms, 2 x 0.5 second dynamic withstand: 2.2 Isc (peak value) dielectric test 50 Hz between windings and windings/earth: 3.3 kV 1 minute thermal protection connected on terminal block 250 V AC 2 A.

3 janvier 2006

437E3285_Ver2.0.fm/1

Power factor correction and harmonic filtering

Capacitors and banks 50 Hz 400/415 V network voltage


Detuned reactors (DR)

Conditions of use
b b b b b use: indoor storage temperature: -40 C, +60 C relative humidity in operation: 20 to 80 % withstand in salt mist: 250 h operating temperature/altitude:
Minimum (C) 0 0 Maximum (C) 55 50 Highest average over all periods of: 1 year 24 h 40 50 35 45

Altitude (m) 1000 > 1000 y 2000

Installation
b forced cooling system compulsory b windings of the detuned reactors fitted in upright position to ensure a good cooling system b power connection : v screw type connector for detuned reactors 6.25 and 12.5 kvar v drilled terminals for detuned reactors 25, 50 and 100 kvar b capacitors to be used in conjunction with detuned reactors must be rated at 470 V for a 400/415 V network.

Dimensions
DB102283

Tuning order: 4.3 (215 Hz)


Power restored by the assembly reactor-capacitor 6.25 kvar/400 V - 50 Hz 12.5 kvar/400 V - 50 Hz 25 kvar/400 V - 50 Hz 50 kvar/400 V - 50 Hz 100 kvar/400 V - 50 Hz Power restored by the assembly reactor-capacitor 6.25 kvar/400 V - 50 Hz 12.5 kvar/400 V - 50 Hz 25 kvar/400 V - 50 Hz 50 kvar/400 V - 50 Hz 100 kvar/400 V - 50 Hz Fixing center distance (mm) 110 x 87 205 x 110 205 x 110
(1)

Dimensions maximum (mm) H L D 230 230 230 270 330 200 245 240 260 380 140 140 140 160 220

Weight (kg) 8.6 12 18.5 25 42 Weight (kg) 8.5 10 18 27 42 Weight (kg) 9 13 22 32 57

Detuned reactors (DR)

205 x 120 Fixing center distance (mm) 110 x 87 205 x 110 205 x 110
(1)

Tuning order: 3.8 (190 Hz)


Dimensions maximum (mm) H L D 230 230 230 270 330 200 245 240 260 380 140 140 140 160 220

205 x 120

Tuning order: 2.7 (135 Hz)


Power restored Fixing center by the assembly distance (mm) reactor-capacitor 6.25 kvar/400 V - 50 Hz 110 x 87 12.5 kvar/400 V - 50 Hz 205 x 110 25 kvar/400 V - 50 Hz 205 x 110 (1) 50 kvar/400 V - 50 Hz 100 kvar/400 V - 50 Hz 205 x 120 (1) 205 x 120 or 205 x 130 mm. Dimensions maximum (mm) H L D 230 230 230 270 330 200 245 240 260 380 140 145 140 160 220

437E3285_Ver2.0.fm/2

3 janvier 2006