BioHeat Piping Layout Concept Diagram Multi-Heat Boiler Installation with Circulators
Date
SCALE
Symbol Key
Supply and Return from Heating Zones (typical)
Ball Valve Purging Valve Weighted Check Valve Pressure Relief Valve Pressure Reducing Valve
DWG NO
REV
02-29-2008 N/A
MH
SHEET
4 1 OF 1 D
Air Separator Circulator (w/isolation flanges) P1 P2 P3 Boiler Drain Backflow Preventer Termovar Valve
1"
Burn Back Flood Water Pressure Tank Contents of water-Tank 5 Gal Pressure Max.-145 psi
Notes: A
Termovar Mixing Valve with 61 C element. A Balancing Valve Must be Used above Port 1 when Kit # K4440A-3 is used The boilers C-3 circulator needs to wired through a switch or RIB relay as per owners manual. (Part # RIBU1C) An aquastat can be used to switch on fossil fuel boiler. Honeywell aquastat L4006A or equivalent. (Part # L4006A) Circulator or Zone Valve Controller Domestic cold water is connected as shown for Model 1.5 and 2.5. Model 4.0 has only one connection to the SYR-Valve burn back piping. An aquastat is used to prevent the boiler from going into stand-by for extended periods of time. It is set to a few degrees above the boilers set-point and needs to activate a heating circuit that is at least 10% of the boilers rated output. A Honeywell L6006C or equivalent can be used. (Part # L6006C)
O
Balancing Valve
(Ball Valve)
C3
1"
3 B A
1
TV-1
B C D C6 E F
SYR-Valve
C5
Drain
Drain
Multi-Heat Boiler
Note: This is only a concept drawing. Final design, installation and code compliance details are the responsibility of the designer/installer of the system.
BioHeat USA, Inc 4 Britton Lane Lyme, NH 03768 Drawn by: TSP Checked by:
SCALE
BioHeat Piping Layout Concept Diagram Multiple Boiler Installation with Circulators and Open Expansion
Date DWG NO REV Vent Open Expansion
T
Ball Valve Purging Valve
Symbol Key
02-29-2008 N/A
Multi-MH
SHEET
1 1 OF 1
Sight Glass
E
Burn Back Flood Water Pressure Tank Contents of water-Tank 5 Gal Pressure Max.-145 psi
Burn Back Flood Water Pressure Tank Contents of water-Tank 5 Gal Pressure Max.-145 psi
Air Separator
Drain
P1 C1 C
Feed Feed Heat Exchanger
P2
C2
A G
Balancing Valve
(Ball Valve)
Termovar Mixing Valve with 61 C element. Balancing Valve Must be Used above Port 1. The boilers C-3 circulator needs to wired through a switch or RIB relay as per owners manual. (Part # RIBU1C) An aquastat or sensor can be used to switch on fossil fuel boiler. Domestic cold water is connected as shown for Model 1.5 and 2.5. Model 4.0 has only one connection to the SYR-Valve burn back piping. Open Expansion Tank-Please refer to BioHeat Open Expansion Bulletin for more information. It is necessary to have a minimum constant load on the boiler when it is operating to prevent it from going into stand-by mode for long periods of time. An aquastat is used to prevent the boiler from going into stand-by for extended periods of time. It is set to a few degrees above the boilers set-point and needs to activate a heating circuit that is at least 10% of the boilers rated output. A Honeywell L6006C or equivalent can be used. (Tarm Part # L6006C)
B C
1 3 C3
2
TV-1
Balancing Valve
(Ball Valve)
D E
1 C4 3
2
TV-2
A B B C5
SYR-Valve SYR-Valve
F C6 G
T T
Drain
Drain
Drain
Drain
Multi-Heat Boiler 1
Multi-Heat Boiler 2
Note: This is only a concept drawing. Final design, installation and code compliance details are the responsibility of the designer/installer of the system.