COOLING LOAD CALCULATION Method: Using Cooling Load Temperature Differences (CLTD), Solar Cooling Load Factors (SCL) and Internal Cooling Load Factors (CLF) 1.0 Design Conditions 1.1 Indoor Design Condition For most of comfort system, the recommended indoor temperature and relative humidity are: 1) Summer: 73 to 79 oF. The load calculations are usually based on 75 oF dry bulb temperature and 50% RH. 2) Winter: 70 to 72 oF dry bulb temperature with 20-30% RH. 1.2 Outdoor Design Condition Outdoor design conditions are determine from published data for specific location, based on weather bureau or airport records. Basic climate and HVAC design condition data can be obtained from ASHRAE Handbook. 2.0 Cooling Loads Classification
Instantaneous Heat Gain 1.1

Convective component

Instantaneous Cooling Load

Heat Extraction by Equipment

Radiative Component

Convection (with time delay)

Furnishings, Conv structure, variable heat storage

Schematic Relation of Heat Gain to Cooling load

2.1 External Loads 2.1.1 Roofs, External Walls & Conduction through glass (sensible loads) Q = U X A X CLTD (Btu/hr) .......... (1) Q = Thermal transmittance for roof or wall or glass. (1997 ASHRAE Fundamentals-Chapter 24) A = area of roof, wall or glass calculated from building plans.

Property of Refee Lubong-GBIF/0409

CLTD = Cooling Load Temperature Difference for roof, wall or glass. (1997 ASHRAE Fundamentals-Chapter 28, tables 30,31,32,33 & 34. 2.1.2 Solar Load through Glass, Skylights and Plastic sheets (radiant sensible load) Q = A X SHGC X CLF (Btu/hr) ......... (2) A = Area of glass, skylights or plastic sheets calculated from building plans. SHGC = Solar Heat Gain Coefficient. (1997 ASHRAE Fundamentals-Chapter 28, table 35) CLF = Solar Cooling Load factor. (1997 ASHRAE Fundamentals-Chapter 28, table 36) 2.1.3 Partitions, Ceiling & Floors Q = U X A X ( Ta - Ti ) Btu/hr ..........(3) A = Area of partition, ceiling or floor calculated from building plans. Ta = Temperature of adjacent space. (Note: If adjacent space is not conditioned and temperature is not available, use outdoor temperature less 5 oF) Ti = Inside design temperature of conditioned space (assumed constant). 2.1.4 Ventilation & Infiltration Air (refer ASHRAE Standard 62 for minimum ventilation requirement) Qsensible = 1.08 X CFM X (To TL) (Btu/hr) .......... (4) Qlatent = 4840 X CFM X (Wo WL) (Btu/hr) ......... (5) Qtotal = 4.5 X CFM X (Ho HL) (Btu/hr) ......... (6) CFM = Ventilation air flow rate To = Outside dry bulb temperature, oF . TL = Dry bulb temperature of air leaving the cooling coil, oF. Wo = Outside humidity ratio(Ib of water per Ib of dry air). WL = Humidity ratio of air leaving the cooling coil (Ib of water per Ib of dry air). Ho = Outside/inside air enthalpy (Btu per Ib of dry air). HL = Enthalpy of air leaving the cooling coil (Btu per Ib of dry air). (Refer to 1997 ASHRAE Fundamentals, Chapter 25 for determining infiltration)

Property of Refee Lubong-GBIF/0409

2.2 Internal Loads 2.2.1 People Qsensible = N X Qs X CLF (Btu/hr) .......... (7) Qlatent = N X QL (Btu/hr) ......... (8) N = Number of people Qs, QL = Sensible and Latent heat gain from occupancy is given in 1997 ASHRAE Fundamentals, Chapter 28, table 3. CLF = Cooling Load factor, by hour of occupancy, refer 1997 ASHRAE Fundamentals, Chapter 28, table 37. Note: CLF = 1.0 if operation is 24 hours or cooling is off at night or during weekends. 2.2.2 Lights (sensible heat gain) Q = 3.41 X W X FUT X FBF X CLF (Btu/hr) ......... (9) W = Installed lamp watt input from electrical lighting plan lighting load data. FUT = Lighting use factor, as appropriate. FBF = Balast factor allowance, as appropriate. CLF = Cooling Load factor, by hour of occupancy (refer 1997 ASHRAE Fundamentals, Chapter 28, table 38. Note: CLF = 1.0, if operation is 24 hours or cooling is off at night or during weekends). 2.2.3 Power Loads & Motors 2.2.3.1 Heat gain of power driven equipment and motor when both are located inside the space to be conditioned. Q = 2545 X (P/Eff) X FUM X FLM (Btu/hr) ......... (10) P = Horsepower rating from electrical power plans or manufacturers data. Eff = Equipment motor efficiency, as decimal fraction. FUM = Motor use factor (normally = 1.0) FLM = Motor load factor (normally = 1.0) (Note: FUM = 1.0 if operation is 24 hours) 2.2.3.2 Heat gain of when driven equipment is located inside the space to be conditioned and motor is outside the space or air stream. Q = 2545 X (P/Eff) X FUM X FLM (Btu/hr) .......... (11)

Property of Refee Lubong-GBIF/0409

P = Horsepower rating from electrical power plans or manufacturers data. Eff = Equipment motor efficiency, as decimal fraction. FUM = Motor use factor (normally = 1.0) FLM = Motor load factor (normally = 1.0) (Note: FUM = 1.0 if operation is 24 hours) 2.2.3.3 Heat gain of when driven equipment is located outside the space to be conditioned and motor is inside the space or air stream. Q = 2545 X P X [(1.0-Eff)/Eff] X FUM X FLM (Btu/hr) ......... (12) P = Horsepower rating from electrical power plans or manufacturers data. Eff = Equipment motor efficiency, as decimal fraction. FUM = Motor use factor (normally = 1.0) FLM = Motor load factor (normally = 1.0) (Note: FUM = 1.0 if operation is 24 hours) 2.2.4 Appliances Q = 3.14 X W X Fu X FR X CLF (Btu/hr) ......... (13) W = Installed rating appliances in watts. Refer to 1997 ASHRAE Fundamentals, Chapter 28; table 5 thru 9 or use manufacturer s data. For computers, monitors, printers and miscellaneous office equipment, refer to 2001 ASHRAE Fundamentals , Chapter 29, tables 8, 9 & 10. FU = Usage factor. Refer to ASHRAE Fundamentals, Chapter 28, table 6 & 7. FR = Radiation factor. Refer to ASHRAE Fundamentals, Chapter 28, table 6 & 7. CLF = Cooling Load factor, by hour of occupancy (refer 1997 ASHRAE Fundamentals, Chapter 28, table 37 & 39. Note: CLF = 1.0, if operation is 24 hours or cooling is off at night or during weekends). 2.2.5 Heat Gain from HVAC system 2.2.5.1 Supply Fan Heat Load The heat energy is calculated as follows: Q = 2545 X [P/(Eff1 X Eff2)] ......... (14) P = Horsepower rating from electrical power plans or manufacturers data.

Property of Refee Lubong-GBIF/0409

2545 = conversion factor for converting horsepower to Btu/hr Eff1 = Full load motor and drive efficiency. Eff2 = Fan static efficiency. Note: Refer to 1997 ASHRAE Fundamentals, Chapter 28; table 4 for motor heat gain. 2.2.5.2 Duct Heat Gain Only the heat gained by the duct supply system is significant. This heat gain is normally estimated as a percentage of the space sensible cooling load (usually 1% to 5%) and applied to the temperature of the air leaving the cooling coil in the form of temperature increase.

3.0 Total Load The total load is the summation of external and internal load or both sensible and latent loads. Usually 10% safety margin is added but it all depends on how accurate are the inputs. The final load is then used to size the HVAC equipment. HVAC equipment is rated in Btuh, but is commonly expressed in tonnage. A Btu (British thermal unit) is the amount of heat needed to raise one pound of water one degree Fahrenheit. A Tone of cooling load is actually 12,000 Btu per hour heat extraction equipment. The term ton comes from the amount of cooling provided by two thousand pound or one tonne of ice.