75-110 A 1000 900 800 700 100 200 300 400 500 600 .5 .6 .7 .8 .

9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

Temp. 0 10-50 60

Shift index for long-time delay only.

125-250 A 1000 900 800 700 100 200 300 400 500 600 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 1000 900 800 700 600 500 400 300

1000 900 800 700 600 500 400 300

Ambient compensated. For ambients above 50 C and below 10 C, shift the unity index for long-time delay (thermal) portion of curve to desired ambient. Maximum Total Clearing Time Minimum Total Clearing Time

Magnetic Trip Setting Ranges


Trip Unit Ampacity
70 80 90 100 110 125 150 175 200 225 250

Setting (amps) LO HI
600 700 600 600 660 600 700 800 900 1000 1000 900 1000 900 1250 1250 1250 1500 1750 2000 2250 2250

200

200

100 90 80 70 60

Range tolerance is 80-130% of setting.

TIME IN SECONDS

50 40 30

50 40 30

20

Minimum Total Clearing Time

20

10 9 8 7 6 5 4 3

HI Magnetic Setting

10 9 8 7 6 5 4

Magnetic pickup levels shown for reference. Specific settings and tolerances shown in table above. LO Magnetic Setting 70 & 80 A HI Magnetic Setting
.9 .8 .7 .6 .5 .4 .3

GES-6103F

.6 .5 .4 .3

90 & 110 A

LO Magnetic Setting 125, 150, 175, 200, 225 & 250A

.2

LO Magnetic Setting
.1 .09 .08 .07 .06 .05 .04 .03

HI Magnetic Setting 100 A

.2

.1 .09 .08 .07 .06

Application Determines End of Curve

.05 .04 .03

.02

.02

.01 .5 .6 .7 .8 .9 1 75-110 A 2 3 4 5 .5 6 7 8 9 10 .6 .7 .8 .9 1 20 2 30 3 40 4 50 60 70 80 90 5 100 200 300 400 500 600 1000 100 900 800 700

.01

6 7 8 9 10

20

30

40

50 60 70 80 90

125-250 A

MULTIPLES OF CURRENT RATING

GE Consumer & Industrial Electrical Distribution


Current Ratings 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 Amperes Voltage Ratings 600 Vac, 250 Vdc Frequency Ratings 50/60 Hertz
01.04

Molded-Case Circuit Breaker F 225 Line Types TFJ, TFK, THFK


Ambient Compensated Long-Time Delay and Instantaneous Time-Current Curves
Curves show ambient-compensated circuit breaker in open air, 10-50C, wired with conductors of corresponding rating, no prior load. For all other ambients, use rating shift index at top of sheet.

GES-6103F
Adjustments Long-time delay thermal trip: not adjustable. Instantaneous magnetic trip: continuously adjustable, factory set on HI. Blocks show trip range at marked points on instantaneous dials. Note1: Operation above 60 Hertz and 50C may require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application Manual.

GES-6103F

1 .9 .8 .7

TIME IN SECONDS

Maximum Total Clearing Time

100 90 80 70 60

200

300

400

500

600

1000 900 800 700