Professional Documents
Culture Documents
These notes have a higher priority than statements made in other documents. Please carefully read the notes, as they include important information for you regarding the installation and use of the system.
AP01465665
AP01509913
The horizontal scrollbar is missing in the wizard mask drive - additional data in special conditions. In Simotion SCOUT PROFIdrive telegrams 3 and 4 cannot be selected directly on PROFINET.
If this problem occurs restart the wizard. The user must fix the settings manually for telegrams 3 and 4 on PROFINET in Simotion SCOUT. After the power supply of TM150 is interrupted and a fault is shown, restart the whole SINAMICS DCM including TM150. Use data set DS47 in Ethernet/IP with only 1 parameter. Do not take the MMC card from one SINAMICS DCM to another if you use know how protection in combination with copy protection.
Firmware AP01508154
AP01528432 AP01530523
AP01530614
AP01531342
If the power supply (24V) of the terminal module TM150 is interrupted, the communication between TM150 and DCM can't be recovered after reconnection. Data set DS47 in Ethernet/IP supports reading of 1 parameter only, but not 2 or more. Activating copy protection via p7769 and p7759 in combination with know how protection leads to a system crash if the MMC card is taken from one SINAMICS DCM to another. Using "Load to file system" in combination with activated know how protection leads to a system crash after restoring the output files. If PROFIdrive telegrams 3 or 4 are used, F60031 is shown shortly after running the motor.
DCM V1.4
Data set DS47 in Ethernet/IP supports writing of several parameters but only 1 can be read.
Using "Load to file system" in combination with activated know how protection will generate corrupted output files on the MMC card. Although the speed setpoint in parameter p50621 is connected, the standard setpoint channel is not calculated as well as r52174. Users must be informed to be careful with setting p50269 to 0 or 1 because this can damage the system under certain circumstances.
DCM V1.4
Disable the setpoint / actual speed monitoring by deactivating F60031 or setting the threshold p50388 to 200%. Keep the information of this list entry in mind.
DCM V1.4
Documentation AP01535131 A warning is missing in parameter list at p50269 "Freeze field current setpoint operating mode".
DCM V1.4
Page 1 of 1