Volume Control Damper

Identification * NF/VCD

S T A NDA R D C ONS T R UC T ION


L

Frame: 0.7 - 1.2mm galvanized steel channel provides greater rigidity and strength. Blade: Max. 6" spacing galvanized steel 0.7 - 1.0mm design for more strength and overlap coverage. Max. Length = 48".
H

Linkage: Type NF / VCD formed brackets of 0.7 - 1.0mm galvanized steel. Bearings: Washer sleeve bearing. Axles: 5/16", 3/8", 1/2" galvanized steel Sizes: Made to exact size as required. Dampers less than 9"H made with 3/4" x 3" x 3/4" channel frame. Hand Quadrant: For manual operation. Type Of Joint: S&D or TDC joint.

F RONT VIEW

Volume Control Damper


Identification * NF/VCD

V A R IA T IONS F E A T UR E S
Axles 5/16", 3/8", 1/2"

1. Drive Shafts: a. Extendable to 6" beyond frame. b. More than 8" using exterior bearing support. 2. Wider Frames: Frames wider than 4". 3. Axles: Stainless steel. 4. Seals Also available with neoprene side. 5. Bearings: Copper / Bronze sleeze bearing.

6" Max.

NF / VCD OPPOSED BLADES TYPE

SIDE VIEW

NAM FOONG (M) SDN BHD (8070-T)

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 30/9/99 NAM FOONG (M) SDN BHD (8070-T) Volume Control Damper Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct) Damper Position : FULLY OPEN SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000

TEST CONDITIONS Qs (l/s) 760 900 1270 1610 2070 Ps (Pa) 7 9 17 26 41

4000

8000

<47.0 <47.3 <50.3 54.1 59.8

<36.5 <37.6 43.4 49.3 54.8

<29.8 <32.2 40.9 47.5 54.7

26.6 30.8 38.6 44.7 50.7

23.5 27.7 35.8 42.1 47.5

<18.3 21.3 30.4 37.5 43.4

<18.0 <19.3 26.1 33.7 39.6

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 30/9/99 NAM FOONG (M) SDN BHD (8070-T) Volume Control Damper Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct) Damper Position : CLOSE 1 SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000

TEST CONDITIONS Qs (l/s) 760 900 1180 1470 1870 Ps (Pa) 13 19 30 45 72

4000

8000

<48.1 <49.1 <51.2 56.1 62.3

<38.6 <39.4 44.7 50.2 55.7

<31.0 35.1 42.5 48.7 55.4

26.5 32.1 39.3 44.8 51.1

21.3 26.9 34.5 40.6 46.7

<16.6 19.3 26.9 34.2 40.0

<17.6 <18.6 <21.8 29.3 33.6

LEGEND Qs Ps < Primary Air Flow Rate (l/s) Supply Static Pressure (Pa) Insufficient margin above background noise to allow accurate determination

NAM FOONG (M) SDN BHD (8070-T)

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 30/9/99 NAM FOONG (M) SDN BHD (8070-T) Volume Control Damper Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct) Damper Position : CLOSE 2 SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000

TEST CONDITIONS Qs (l/s) 680 810 960 1180 1420 Ps (Pa) 20 30 43 61 84

4000

8000

<46.7 <48.9 <51.2 55.1 60.0

<38.0 <41.2 45.8 50.3 54.1

<32.7 39.3 45.1 50.6 55.0

27.2 33.9 40.1 45.9 51.2

19.9 28.6 33.4 39.9 45.8

<15.3 23.0 24.4 31.8 38.4

<17.2 <20.4 <19.4 22.9 29.7

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 30/9/99 NAM FOONG (M) SDN BHD (8070-T) Volume Control Damper Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct) Damper Position : CLOSE 3 SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000

TEST CONDITIONS Qs (l/s) 570 670 810 985 1160 Ps (Pa) 24 34 48 69 93

4000

8000

<47.2 <49.2 <51.2 54.5 59.4

<39.1 <41.4 45.9 50.0 53.6

34.8 40.9 46.7 51.7 55.4

28.6 34.7 41.1 47.4 52.4

20.9 27.6 34.1 40.9 47.1

<15.2 <17.8 24.6 32.2 38.7

<17.1 <17.4 <18.8 22.2 29.3

LEGEND Qs Ps < Primary Air Flow Rate (l/s) Supply Static Pressure (Pa) Insufficient margin above background noise to allow accurate determination

NAM FOONG (M) SDN BHD (8070-T)

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 30/9/99 NAM FOONG (M) SDN BHD (8070-T) Volume Control Damper Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct) Damper Position : CLOSE 4 SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000

TEST CONDITIONS Qs (l/s) 570 670 800 980 Ps (Pa) 34 48 68 96

4000

8000

<48.9 <50.8 54.3 58.0

<41.1 44.5 48.8 52.9

39.7 45.4 50.5 54.8

33.4 40.4 46.7 52.0

26.7 34.1 40.5 47.0

<17.1 23.9 31.4 38.5

<17.3 <18.0 <21.5 28.5

LEGEND Qs Ps < Primary Air Flow Rate (l/s) Supply Static Pressure (Pa) Insufficient margin above background noise to allow accurate determination

NAM FOONG (M) SDN BHD (8070-T) ___________________________________________________________________________________ ___

PERFORMANCE NOTES
Units are tested accordance with the Air Diffusion Council (USA) Equipment Test Code 1062 : GRD-84. Measurements were taken in general accordance with the following standards :ACOUSTICS International Standard ISO 3741 Clause 8.3 (Method 11) Acoustics Determination of Sound Power Levels of Noise Sources Precision Methods for Broad-Band Sources in Reverberation Rooms. AIRFLOW Air Diffusion Council (USA) Equipment Test Code 1062 : GRD-84. THROW AND STATIC PRESSURE DROP Air Diffusion Council (USA) Equipment Test Code 1062 : GRD-84.

TEST SET UP AND PROCEDURE Reverberation Test Room has a volume of 170m3 has been qualified in accordance with the procedures in ISO 3741 for determination of sound power in octave bands with Centre Frequencies from 125 Hz to 8000 Hz. The Units under test were set up in the Air Distribution (Reverberation) Test Chamber and connected to a quiet air supply. The units were supplied with ambient temperature air at the specified airflow. The environmental test conditions in the reverberation chamber varied for each test within the following ranges : Test Air Temperature Room Air Temperature Barometric Pressure Relative Humidity 18 degrees C 2.0 degree C 20 degrees C 2.0 degree C 1040 millibar 5 millibar 60 10%

NAM FOONG (M) SDN BHD (8070-T) ___________________________________________________________________________________ ___

blade width DAMPER BLADES (SIDE VIEW)

DAMPER BLADES

PLAN VIEW OF DAMPER FOR EACH DAMPER SETTING, THE MEASURED APPARENT BLADE WIDTHS WERE AS FOLLOWS :-

Damper Setting Fully Open Close 1 Close 2 Close 3 Close 4

Apparent width of each damper blade, as measured from plan view (mm) 1 2 3 38 27 33 90 80 80 115 115 110 134 130 125 145 145 142

Volume Control Damper Blade Settings

NF - VOLUME CONTROL DAMPER PRESSURE DROP vs FLOW


The following data are obtained under damper tested on 610mm x 610mm at various blade positioned.

1000

75% Close Fully Close

50% Close

Fully Open 200 100 70 40 25% Close

PA

30 20 10 8 6 4 2 2 3 4 5 6 7 9 10 12

Velocity m/sec.