You are on page 1of 19

2 kWP Solar PV System Offer

Mr.Adeeb Ghanem Residence Amman - Jordan


Coordinates: 31.962, 35.893

Customer Identification Code: 13-08-A01

AGE Energy Mob: +962-79-62 000 72 Tel: +962-6-566 9333 Fax: +962-6-553 8239 info@ageenergy.com www.ageenergy.com

Tel: +962 6 566 9333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

Page 1 of 7

1. Executive Summary:
Date: 15 August 2013 Ref.: JOQ1-13-08-A01 Dear Mr.Adeeb Ghanem,

We are pleased to submit our technical and commercial offer for the 02 kWp Solar Power System - Grid Tie. The offer included the scope of works for Supply of Materials and Installation for the solar power system. We believe that this offer meets with your requirements and look forward to receiving your order. Furthermore, if you required any additional information or assistance, please don't hesitate to contact us. Please indicate your unique customer identification code for all your correspondence for easily retrieving your project information.

Customer Identification Code: 13-08-A01

Yours faithfully, Adeeb Ghanem

General Manager

The information in this document is confidential to the person to whom it is addressed and should not be disclosed to any other person. It may not be reproduced in whole, or in part, nor may any of the information contained therein be disclosed without the prior consent of the directors of AGE Energy. A recipient may not solicit, directly or indirectly (whether through an agent or otherwise) the participation of another institution or person without the prior approval of the directors of the Company.

Tel: +962 6 5669333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

Page 2 of 7

2. Project Information:
Client Information
Name

Adeeb George Ghanem


Assigned Identification Number

13-08-A01
Mobile Phone Email

079-6200072
Company

06-566 9333

adeeb.ghanem@ageenergy.com

Home User
Site Address City Country

Shmeisani Area
Building/House Number

Amman
Street Name

Jordan
Neighborhood Name

7 ,Atp 1
Site Coordinates

Abu Jandal
Latitude

Al Abdali
Longitude

31.957 Load Information


Connection Type Main Circuit Breaker Rating (A)

35.946
Tariff Scheme

Single Phase
Monthly Consumption (kWh)

40
Average Monthly Bill Value (JOD)

Residential
Utility Company

310 Site Characteristics


Building Type

55
Roof Space Available

JEPCO
Mounting Space Type

Apartments Complex
Clear Sky

Yes
Shadow Effect

Free Standing
Building Age

100%

2%

15

Tel: +962 6 5669333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

Page 3 of 7

3. Proposed System:
Electrical Characteristics of Solar PV System
Nominal AC power Annual energy yield (approx.)*: Modules Rating Number of Modules Number of Strings

1.95 kW 3685 250 8 2 kWh W Panels Strings

Energy Characteristics of Solar PV System


House Consumption Month Number of Days Monthly Consumption During Daylight* PV System Generation Monthly Coverage %

Monthly

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

31 28 31 30 31 30 31 31 30 31 30 31

310 310 310 310 310 310 310 310 310 310 310 310

kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh

124 124 124 124 124 124 124 124 124 124 124 124

kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh

212 226 306 328 366 389 391 380 345 298 234 208

kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh

170.97% 182.26% 246.77% 264.52% 295.16% 313.71% 315.32% 306.45% 278.23% 240.32% 188.71% 167.74%

* : Assuming that loads during sunshine hours are 40% of the monthly load

Tel: +962 6 5669333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

Page 4 of 7

4. System Components:
2kWp AGE Euro System
PV Panel Brand Cell Type Make Max Power Vmp Imp Size Weight Output guarantee Certification Inverter Brand Type Make Max. DC Input Power Rated AC Output Power Warranty Certification : : : : : : : : : : : : : : : : : 25 years (CE) Martifer Monocrystalline Euorpe 250W 35.5V 4.24A 1580*808*45 mm 16kg/pc 25 years (CE, ROHS, IEC, TUV certified) SMA Grid Tie Euorpe

QTY

QTY

Aluminum fixating structure 3 Brand Type Make Certification : : : : MPrime Free Standing Euorpe (CE)

QTY

SET

PV Solar Cable Brand Type Make Certification : : : : ELDRA 4mm2 Euorpe (CE)

QTY

50m

AC Breaker

QTY: 1 QTY: 1 QTY: 1

Distributi on Box Fuse Box

QTY: 1 QTY: 1 QTY: 1

DC Disconnect 5 Balance of System Combiner Box

Fuses

Tel: +962 6 5669333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

Page 5 of 7

5. Commercial Offer:
SALES QUOTE
AGE- JOQ1-13-08-A01 August 1, 2013

Customer

Contact

Deliver To

Adeeb George Ghanem 7 Abu Jandal Street, Apt 1 Shmeisani Area , Behind Ramada Hotel Tel : (962-79) 62 000 72 Account

Adeeb George Ghanem 7 Abu Jandal Street, Apt 1 Shmeisani Area , Behind Ramada Hotel Tel : (962-79) 62 000 72 Terms Due Date

Adeeb George Ghanem 7 Abu Jandal Street, Apt 1 Shmeisani Area , Behind Ramada Hotel Tel : (962-79) 62 000 72 Account Rep Schedule Date

Quotation

PO #

Reference

Ship VIA

Page

Printed
15/08/2013 1:29:57PM

AGE- JOQ1-13-08-A01
SR
1

Item
250W PV Panel Grid Tie Inverter Roof Top Mounting Kit Solar Cable AC Breaker DC Disconnect Combiner Box Distribution Box Fuse Box

Description
PV Module 250W Multi Crystalline Grid Tie Inverter suitable for 2kWP Aluminum Frame Set for Roof mounting Free Standing Solar Cable 6mm2 120C/1kV HFFR PV AC 1IN 3PH SW 230/32/30mA SPD CG DC Disconnect 500 DC V Solar Combiner Box Pre-Smart Meter DB 20A Fuse Box Strings 15Amp 600VDC JEPCO Application Fees and Smart Meter Outdoor, WIFI/IP Camera with Access Point, 3m Pole

Qty
8
PCS

Unit Price

Amount

PCS

Set

4 5 6 7 8 9

50 1 1 1 1 1 2 1

PCS PCS PCS PCS PCS PCS LOT

10 Fuses 11 12 Utility Permits (Optional) : IP Camera

50 JOD 150 JOD 100 JOD Total : 2,650.00 JOD Sales Tax : 16% on System Only 3066.00 JOD

1 1

PCS

(Optional) : Home Monitoring Single Phase, Wireless Home Smart Meter with Web 13 Kit Access NOTE: 1) 2) 3) The prices on this quote are valid for only 15 Days. Electrical and civil works not included will be at additional measured costs Utility permits and induced fees

PCS

Tel: +962 6 5669333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

Page 6 of 7

6. Offer Terms:
Excluded Items:
Price does not include any Civil Work and conducting, electrical components not part of

the system Any material not mentioned in the quotation Any Work not included in above scope of works Any additional fee/charges required to get work permits or approvals Installation of any equipment/cables/conduits not provided as per this offer is excluded.

Terms & Conditions of Payment


80 % as down payment immediately to be paid after signing the contract 15 % upon completing the equipment installation at site 5% upon system commissioning

Project Period:
Delivery will be 16-20 weeks from the date of receiving of down payment. Installation period will be 1 weeks after receiving of material.

Validity of the offer:


Our offer is valid for 15 days from the date of this letter.

Tel: +962 6 5669333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

Page 7 of 7

7. Attachments:
1. Simulation of PV System 2. Single Line Diagram 3. PV Panel Specifications 4. Inverter Specifications 5. Mounting Fixture Specifications 6. Solar Cable Specification

Tel: +962 6 5669333

e-mail: info@ageenergy.com

P.O.Box: 811941 Amman-11181 Amman-Jordan

AGE Energy Amman - Jordan

AGE Energy Amman - Jordan

Mob: +962-79-62 000 72 Tel: +962-6-566 9333 Fax: +962-6-553 8239 info@ageenergy.com www.ageenergy.com Project name: Project number: Project file: System overview 8 x Martifer Solar 250M (PV array 1)
Azimuth angle: 0, Inclination: 25, Mounting type: Roof, PV peak power: 2.00 kWp

Adeeb Ghanem Residence 1308A01

Location: Jordan / Amman Grid voltage: 1~230 V

1 x SB 2000HF-30 Technical data


Total number of PV modules: PV peak power: Number of inverters: Nominal AC power: AC active power: Active power ratio: Annual energy yield (approx.)*: 8 2.00 kWp 1 2.00 kW 2.00 kW 100 % 3684.90 kWh Energy usability factor: Performance ratio (approx.)*: Spec. energy yield (approx.)*: Line losses (in % of PV energy): Unbalanced load: Self-consumption: Self-consumption quota: 100 % 84.2 % 1842 kWh/kWp --2.00 kVA ----Sunny Design 2.30.0.R

Signature
*Important: The yield values displayed are estimates. They are determined mathematically. SMA Solar Technology AG accepts no responsibility for the real yield value which can deviate from the yield values displayed here. Reasons for deviations are various outside conditions, such as soiling of the PV Modules or fluctuations in the efficiency of the PV modules.

1/2

Evaluation of design
Project name: Adeeb Ghanem Residence Project number: 1308A01 Project file: Part project 1 Location: Jordan / Amman Cell temperature: Record Low Temperature: -10.00 C Average High Temperature: 50.00 C Record High Temperature: 70.00 C

1 x SB 2000HF-30
PV peak power: Total number of PV modules: Number of inverters: Max. DC power: Max. AC power: Grid voltage: Nominal power ratio: 2.00 kWp 8 1 2.10 kW 2.00 kW 230 V 105 % SB 2000HF-30

Technical data
Input A: PV array 1 8 x Martifer Solar 250M, Azimuth angle: 0, Inclination: 25, Mounting type: Roof Input A: Number of strings: PV modules per string: Peak power (input): Typical PV voltage: Min. PV voltage: Min. DC voltage (Grid voltage 230 V): Max. PV voltage: Max. DC voltage (Inverter): Max. current of PV array: Max. DC current:

1 8 2.00 kWp 215 V 194 V 175 V 334 V 700 V 8.3 A 12.0 A

PV/Inverter compatible

Sunny Design 2.30.0.R

2/2

Sample Single Line Diagram


#6 AWG Teck Cable PSPV #1 NEMA 3R (Note 2)
Array Combined Box

PV Array, 2 Sets 2 strings of 13-198w Panels (Note 1)

#10 MC

#6 AWG Teck Cable PSPV #2 (Note 2)

#10 MC

DC Disconnect #2 (Note 3) DC Disconnect #1 (Note 3)

DC/AC Inverter #2 (Note 4, 5, & 6) DC/AC Inverter #1 (Note 4, 5, & 6)

Inverter AC Output Disconnect, Fused, System Ground (Note 7, 8)

Lockable AC Disconnect With Signage (Note 9)

#3 Teck Cable Energy Meter (Note 10)


To Utility L1

L2

Notes: 1. 2. 3. 4. 5. 6. 7. 8. 9. PV Array consists of 2 sets of 199-watt connected in series parallel 2 strings of 13 panels connected series (tl of 52 panels). A DC-Surge/ Lightning arrestor installed in the PSPV-Fused solar arrays. PV Array Wiring to PSPV Combiner box is #10 AWG MC Connectors to Interface w/ modules. PV Array Combiner/ Junction boxes provides transition from array MC-Wiring to TECK cable and 15 amp fusing. PV Power Source DC-Disconnect #1 & #2 (Un-fused) rated at 30 amp Switch, 600VDC, Type 3R enclosure. Ground-Fault Protection is provided in the Fronius IG 5100s DC to AC Inverters #1 & #2. DC/AC Inverters #1 & #2 are XANTREX GT5000 which are rated at 5.0kW AC output and are rated to provide a Maximum AC Current of 20.83 amps at 240-Volts at 40-deg. Celsius each. Both inverters are listed to UL-1741 Utility Interactive. Inverters AC Output Disconnect Switch, Fusible with Neutral, 2-Pole, 60 amps, 240VAC, NEMA 3R. AC Disconnect has 2-60 amp, 250 VAC, Dual element, time-delay, RK5 and System Level Grounding. AC Utility Switch, Un-fused, 3-Pole, 60A, 600VAC, NEMA 3R Safety Disconnect. This switch has an easy to read waterproof sign reading WARNING, TWO POWER SOURCES PARALLEL SYSTEM and houses a system single line diagram of the entire PV system. 100 amp utility revenue meter with waterproof signage reading WARNING, TWO POWER SOURCES PARALELL SYSTEM) posted clearly visible. Equipment grounding conductors on AC and DC side are sized according to code. Solar panels, racks and PSPV combiner boxes, inverters and switch panels are all grounded and linked to a common ground located at the Fused AC-60 Amp Disconnect Panel. Utility tie in is by a TECK Cable 3C-6AWG, maximum of 200 feet long, to be determined at time of installation.

Professional Engineer
Project:

New Solar Installation


Date: Jan. 01, 2010 Drawing No.

10. 11. 12. 13.

Drawn by: An. Engineer

Title: One-Line Diagram for 10-kW MicroFIT PV System

0000-0000

PV MODULES
M 230-255 | 3R
THE COMPANY
D FR E E PI

Specialized in the distribution of PV modules, kits and components, MPrime focuses on flexibility, excellence in service and continuous technological innovation, in order to provide our clients all over the world with the best portfolio, service and warranties. Part of Martifer Solar, MPrime benefits from a wide international experience in solar photovoltaic installations.

MPRIME MODULE STRENGTHS


Efficiency and life performance incremented with the linear warranty. Positive power up to 4.99 Watts. Its 4 mm glass is suitable for hail and snow climates, and its internal textured surface increases the solar radiation absorption. Suitable under extreme mechanical loading pressure of 7000 Pa. Produced in a fully automated and robotized PV production line with a yearly installed capacity of 50 MW, extendable to 100 MW, with highly controlled processes and environment, allowing the production of a module with the highest level of quality. Available with silver or black frame and some back cover colors. Manufacturing facility included by the certifications ISO 9001, ISO 14001 and OSHAS 18001.

WARRANTY
MPrime ensures its modules with a first-class warranty: 25 years performance linear warranty: maximum annual decrease of 0.68% after year number two. Year 25: 80.7%. In accordance with the applicable MPrime Guarantee Conditions in force at the time of purchase and available in MPrime modules warranty certificate. Product warranty: 10 years.

BENEFITS OF THE LINEAR WARRANTY


100%

CERTIFICATION
TV Factory Inspection IEC 61215, IEC 61730.1, IEC 61730.2 Kitemark licence (KM 566314) Conformity to CE Safety class II Heavy Snow Load tested 5400 Pa Mechanical load tested 7000 Pa UNI 9177 (Reaction to fire test):class 2 PV Cycle Member Product rated by Inmetro with energy eficiency A, in accordance with the Brazilian Labeling Program. * *Applies for power classes 230, 235 and 240W

97% 95%

90%

85%

MPrime added value


80%

75%

10

11 12

13 14

15 16

17

18 19 20

21 22

23

24 25

MPrime performance linear warranty Standard performance warranty

PV MODULES
M 230-255 | 3R
Module Type: MxxxP xxx = values from 230W to 255W in steps of 5W

ELECTRICAL SPECIFICATIONS *
Nominal Power (Wp) Positive Power Tolerance MPP Current (A) MPP Voltage (V) Open Circuit Voltage (V) Short Circuit Current (A) Module Efficiency Maximum System Voltage (V) Maximum Series Fuse Rating (A) NOCT Temperature Coefficients:
Power Voltage Current
Tolerance of measured maximum power: 3%

PMPP PNOM IMPP VMPP/UMPP VOC/UOC ISC (%) VSYST I

230
7.92 29.09 37.04 8.39 14.3

235
8.05 29.23 37.13 8.42 14.6

240
8.13 29.55 37.23 8.47 14.9 1000 15 452

245
8.25 29.73 37.36 8.60 15.2

250
8.34 30.02 37.60 8.68 15.6

255
8.47 30.13 37.83 8.74 15.8

[PNOM-0; PNOM+4.99W]

(PNOM) (Voc) (Isc)

-0.424%/C -0.313% /C +0.059%/C

* Values at Standard Test Conditions STC (air mass AM 1.5, irradiance 1000 W/sqm, cell temperature 25C)

MECHANICAL SPECIFICATIONS
Dimensions Weight Solar Cells Front Cover Encapsulant Back Cover Frame Diodes Junction Box Cable Connectors 1639 x 982 x 35 mm 20 kg 60 Multicrystalline 6 inch cells Tempered and Textured 4 mm Glass EVA (Ethylene Vinyl Acetate) PPE (Polyester Polyester Primer) Black/blue/white/transparent Silver anodized aluminium/black

DIMENSIONS (All gures are in mm.)


35 165 1639 4x mounting holes 8 245 4x grounding holes 4
982
Front view Left view Back view

3 Bypass Diodes (10.5A) IP 65 W/ 3 Bypass Diodes 2 Cables of 0.8 m Weidmller connector (MC4 compatible) or optional w/ Tyco connector

PACKAGING
Modules per pallet Modules per 40 ft container 40 modules 600 modules

I-V CURVES (240W MODULE)


I-V Curve at Different Irradiance Levels
10 9 8 7 Current, A 6 5 4 3 2 1 0 0 5 10 15 20 Voltage, V 25 30 35 40 700 W/m

I-V Curve at Different Temperatures


10 9 8 7 Current, A 6 5 4 3 2 1 0 0 5 10 15 20 Voltage, V 25 30 35 40

20 C 25 C 30 C 35 C 40 C 45 C

800 W/m 900 W/m 1000 W/m 1100 W/m

Cell temperature: 25C

Irradiance: A.M. 1,5; 1000W/m

CAUTION: read safety and installation instructions before using the product. (available in WWW.MPRIMESOLAR.COM). DISCLAIMER: specifications included in this datasheet are subject to change without notice from the company. In case of any conflicts/problems that may arise due to misinterpretation, prevailing conditions are the ones described in the original version (in English).

MPRIME SOLAR SOLUTIONS, S.A. ZONA INDUSTRIAL, APARTADO 17 / 3684-001 OLIVEIRA DE FRADES, PORTUGAL TEL. +351 232 811 381 FAX. +352 232 767 750 E. INFO.PT@MPRIMESOLAR.COM WWW.MPRIMESOLAR.COM

PT065-TCD-MODULEII/10/03.13(EN)

165

819

245

SUNNY BOY 2000HF / 2500HF / 3000HF


SB 2000HF-30 / SB 2500HF-30 / SB 3000HF-30

High Yields
Maximum efficiency 96.3 % The best tracking efficiency with OptiTrac MPP tracking Shade management with OptiTrac Global Peak *

Safe
Galvanic isolation Integrated ESS DC switchdisconnector Theft protection

Simple
Quick and easy configuration thanks to Quick Module DC plug system SUNCLIX Suitable for generator grounding

Communicative
Graphic display Bluetooth technology as standard

SUNNY BOY 2000HF / 2500HF / 3000HF


Simply high yields
This is the new generation of galvanically isolated inverters packed full of the latest SMA technology, the Sunny Boy HF series provides the highest yields for transformer inverters of this performance class. Installation is now easier than ever thanks to the DC connector system SUNCLIX, the plug-in generator grounding (optional), and an easily accessible configuration area including easier mounting due to the reduced weight. The wide input voltage range from 175 to 700 volts gives you extraordinary flexibility for your plant design, and the modern graphic display and wireless Bluetooth communication system make the devices highly user-friendly.

Input (DC) Max. DC power (@ cos = 1) Max. DC voltage MPP voltage range DC nominal voltage Min. DC voltage / start voltage Max. input current / per string Number of MPP trackers / strings per MPP tracker Output (AC) AC nominal power (@ 230 V, 50 Hz) Max. AC apparent power Nominal AC voltage; range AC grid frequency; range Max. output current Power factor (cos ) Phase conductors / connection phases Eciency Max. eciency / Euro-eta Protection devices DC reverse-polarity protection ESS switch-disconnector AC short circuit protection Ground fault monitoring Grid monitoring (SMA Grid Guard) Galvanically isolated / all-pole sensitive fault current monitoring unit Protection class / overvoltage category General data Dimensions (W / H / D) in mm Weight Operating temperature range Noise emission (typical) Internal consumption: (night) Topology Cooling concept Electronics protection rating / connection area (as per IEC 60529) Climatic category (per IEC 60721-3-4) Features DC connection: SUNCLIX AC connection: screw terminal / plug connector / spring-type terminal Display: text line / graphic Interfaces: RS485 / Bluetooth Warranty: 5 / 10 / 15 / 20 / 25 years Certificates and permits (more available on request) * In planning ** On Demand *** Does not apply to all national deviations of EN 50438 Standard features Optional features not available Provisional data, as of November 2010 data at nominal conditions Type designation

2100 W 700 V 175 V 560 V 530 V 175 V / 220 V 12 A / 12 A 1/2 2000 W 2000 VA 220, 230, 240 V; 180 280 V 50, 60 Hz; 4.5 Hz 11.4 A 1 1/1 96.3 % / 95.0 % / I / III 348 / 580 / 145 17 kg 25 C +60 C www.SMA-Solar.com <1W HF transformer OptiCool IP65 / IP54 4K4H

2600 W 700 V 175 V 560 V 530 V 175 V / 220 V 15 A / 15 A 1/2 2500 W 2500 VA 220, 230, 240 V; 180 280 V 50, 60 Hz; 4.5 Hz 14.2 A 1 1/1 96, 3 % / 95.3 % / I / III 348 / 580 / 145 17 kg 25 C +60 C www.SMA-Solar.com <1W HF transformer OptiCool IP65 / IP54 4K4H

3150 W 700 V 210 V 560 V 530 V 175 V / 220 V 15 A / 15 A 1/2 3000 W 3000 VA 220, 230, 240 V; 180 280 V 50, 60 Hz; 4.5 Hz 15 A 1 1/1 96.3 % / 95.4 % / I / III 348 / 580 / 145 17 kg 25 C +60 C www.SMA-Solar.com <1W HF transformer OptiCool IP65 / IP54 4K4H

// // // / / / / / / //// //// //// CE, VDE 0126-1-1, Enel-GUIDA Ed. 1.1, RD 1663, G83/1-1, PPC, AS4777, UTE C 15-712-1**, EN 50438***, C10/C11, PPDS

SB 2000HF-30

SB 2500HF-30

SB 3000HF-30

Accessories
SMA Plug-in Grounding PLUGIN-GRD-10-NR Quick Module RS485 + multi-function relay 485QM-10-NR

www.SMA-Solar.com

SMA Solar Technology AG

SB3000HF-DEN104423 SMA and Sunny Boy are registered trademarks of SMA Solar Technology AG. Bluetooth is a registered trademark owned by Bluetooth SIG, Inc. SUNCLIX is a registered trademark owned by PHOENIX CONTACT GmbH & Co. KG. Text and illustrations reflect the current state of the technology at the time of publication. Technical modifications reserved. No liability for printing errors. Printed on chlorine-free paper.

Technical data

Sunny Boy 2000HF

Sunny Boy 2500HF

Sunny Boy 3000HF

FLAT ROOF SOLUTION


THE COMPANY

SMARTROOFING

Specialized in the distribution of PV modules, kits and components, MPrime focuses on flexibility, excellence in service and continuous technological innovation, in order to provide our clients all over the world with the best portfolio, service and warranties. Part of Martifer Solar, MPrime benefits from a wide international experience in solar photovoltaic installations.

SMARTROOFING PREMIUM FLAT ROOF SOLUTION


MPrime Smartroofing Flat Roof Solution has been designed for the installation of tilted modules on rooftops. For the material used, anodized aluminium, it is especially adapted to aggressive environment including maritime one. The safe installation on rooftop is guaranteed by foundation supports. It is adapted for the use of independent modules systems.

ADVANTAGES
Highly robust Easy and fast installation Long durability and reliability High security system: high quality material and stability test according to technical standards Flexible system adaptable to all kinds of installation

WARRANTY
Limited warranty 10 years.

DESIGN STANDARD
We recommend the use of this structure with the MPrime modules, certified by:

Smartroofing Flat Roof Solution design is completed in accordance with the relevant codes of practice (RSA for Portugal and EC0 - Basis, EC1 - Actions, and EC9 - Aluminium for the remaining Euro zone) considering installation location.

FLAT ROOF SOLUTION


TECHNICAL SPECIFICATIONS
Triangle Structure: Aluminium alloy 6063 (in conformity with EN 10204/2.1 statement): Surface treatment: anodized 15 m Chemical composition conform with EN 573-3 standard Mechanical properties: minimum hardness of 13 Wb

SMARTROOFING

OPTIONAL COMPONENTS
Security-ball-protection - A2 Self-tapping screw - A2 EPDM Connection of various packs A/F 6 Shank length: 100 to 250 mm, thread lenght: 70 mm; thread diameter top: 10 mm, bottom: 8 mm 2 channel connectors 350 mm (ref. 0100041339), 4 hammer head screws (0 100041343), 4 hexagon flange nuts (0 100041386)

COMPONENTS AND MODULAR SOLUTIONS


REFERENCE 0300237223 0300239964 PICTURE DESCRIPTION Pack 2: Flat Roof Structure - 2 PV Modules REFERENCE 0200616684 DESCRIPTION Mounting triangle: this reference includes all the components necessary to build the triangle (detailed above) Angle Brace 1,516 mm Angle Brace 1,320 mm Angle Brace 785 mm Angle Brace 310 mm Angle Brace 1634 mm - remaining Europe Zone Angle Brace 1905 mm - remaining Europe Zone Angle Brace 1460 mm - Portugal Angle Brace 1333 mm - Portugal Screw DIN933 M10 x 30 - A4 Hexagon Flange Nut DIN 6923 M10 x 1.25 - A4 REFERENCE 0300237222 0300239963 DESCRIPTION Pack 4: Flat Roof Structure - 4 PV Modules DIMENSIONS (MM) PACK 2 PACK 4 PACK 2 PACK 4

1,516 x 1,320 x 785 50 x 50 x 3 50 x 50 x 3 50 x 50 x 3 50 x 50 x 3 50 x 50 x 3 M10 x 30 M10 x 1.25

2 2 2 2 2 1 12 12

4 4 4 4 4 3 23 23

2 2 2 2 2 1 12 12

3 3 3 3 3 2 18 18

0100062803 0100062804 0100062805 0100062806 0100132794 0100132793 0100132796 0100132795 0100041342 0100041386 PREMIUM ALU CHANNELS 0100041327 0100037112 0100041341 FIXATION OF THE TRIANGLES ON THE CHANNELS 0100041343 0100041386 FIXATION OF THE MODULES ON THE CHANNELS 0100041329 0100041328 0100019537 0100041344 Consult

Premium Mounting Channel 2,100 mm - Alu Premium Mounting Channel 4,150 mm - Alu Channel Lid

64 x 55 64 x 55 64 x 55

2 2 4 4

2 2 4 4

Hammer Head Screw M10 x 25 - A4 Hexagon Flange Nut DIN 6923 M10 x 1.25 - A4

M10 x 25 M10 x 1.25

4 4

8 8

4 4

6 6

End Clamp - 35 - 45 - 50 - Alu Middle Clamp - Alu Hammer Mutter Nut M8 - A4 Screw DIN912 M8 x 30 - A4 Photovoltaic Module (not included in the packs)

L70 x 20 L70 x 20 M8 M8 x 30 1,639 x 982 x 35*

4 2 6 6 2

4 6 10 10 4

4 2 6 6 2

4 6 10 10 4

*Other dimensions under consultation


TECHNICAL DRAWING E.U. Version

132

1516

957

30
450 1200 2100 450 500 1050 1050 4150 1050 500

RIGHT VIEW

FRONT VIEW

FRONT VIEW

CAUTION: read safety and installation instructions before using the product. (available in WWW.MPRIMESOLAR.COM). DISCLAIMER: specications included in this datasheet are subject to change without notice from the company. In case of any conicts/problems that may arise due to misinterpretation, prevailing conditions are the ones described in the original version (in English).

MPRIME SOLAR SOLUTIONS, S.A. ZONA INDUSTRIAL, APARTADO 17 / 3684-001 OLIVEIRA DE FRADES, PORTUGAL TEL. +351 232 811 381 FAX. +352 232 767 750 E. INFO.PT@MPRIMESOLAR.COM WWW.MPRIMESOLAR.COM

PT065-TCD-FLROOF/03/04.13(EN)

PRODUCTSPECIFICATION

B0102
1/2

ELDSOLAR STD

Conductor Core insulation Diameter over insulation Colour coding Outer sheath Diameter over sheath Type

Tinned copper conductor according to class 5 of IEC 60228 Special EPR compound See table Black, red ord blue Special halogen free TPR compound color : black, red or blue See table Outer diameter (mm) Max. conductor resistance at 20C (/km) 8.21 5.09 3.39 1.95 1.24 0.795 0.565 0.393 0.277 0.210 0.164 Weight approx. (kg/km) Current carrying capacity acc. HD 604 at 30 C (A) 42 56 71 96 128 173 217 265 336 415 485

Construction

Diameter over insulation approx. (mm) 3.6 4.6 5.0 6.5 7.7 9.0 10.8 12.1 14.2 16.3 17.6

1 x 2.5 mm 1 x 4 mm 1 x 6 mm 1 x 10 mm 1 x 16 mm 1 x 25 mm 1 x 35 mm 1 x 50 mm 1 x 70 mm 1 x 95 mm 1 x 120 mm

5.6 0,15 6,5 0.2 7,1 0,2 9,2 0,2 10.0 0,3 11.5 0,3 13.2 0.3 14.7 0.3 17.1 0.3 19.1 0.3 20.9 0.3

45 65 85 130 186 271 384 509 727 925 1190

Type

Operating voltage U0/U Test voltage in production Temperature range Short circuit temperature Bending radius Standard Outer marking Use Further information Halogen free Delivery Standard

0.6/1 kV AC max 1.8 kV DC 6000V DC Ambient -40 C to + 90 C, max conductor temperature 90 C 300C 5xD Dimensions based on NEN 3356. ELD-SOLAR yxn mm + UV CE Cable is intended to be used for fixed and flexible connection of solar panels. Excellent ozone and UV resistance according to EN 50267-2-1 and EN 60684-2 500m on non returnable reels / 100m on rings Dimensions based on NEN 3356.
Technical information about products can be changed Without notification in advance. No rights can be derived from this specification.

properties General

ELDRA - setting the standards

PRODUCTSPECIFICATION

B0102
2/2

ELDSOLAR STD

Uitgave

ELDRA
Dept. O & T

Naam Opgezet door vrijgave IH JF

datum 30-07-09 31-07-09

Naam Datum Wijz.nr.

ELDRA - setting the standards

Technical information about products can be changed Without notification in advance. No rights can be derived from this specification.

You might also like