You are on page 1of 8

FIOD 1600 Manual

The FIOD series products add digital capability to your PLC / SCADA. FIOD 1600 model has 16 digital inputs. The digital inputs are isolated from the host device. It has one (2 Wire RS485) communication port. The COM port is used to connect any modbus master device (PLC / SCADA / Operator Interface device). This module supports Modbus RTU (Slave) protocol.

Renu Electronics Private Limited


Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

support@renuelectronics.com

Website:

www.renuelectronics.com

FIOD 1600 Manual


Dimensional Details:
FIOD units are shipped with a separate DIN rail plate which can be attached to the unit, if desired. User can use the unit with or without the DIN rail plate. Following sketch shows dimensional details of FIOD with the DIN rail plate.

70.

00

35

.00

Renu Electronics Private Limited


Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

100.00

support@renuelectronics.com

Website:

www.renuelectronics.com

FIOD 1600 Manual


PLC Communication The unit supports Modbus RTU (Slave) protocol. Dedicated modbus registers are used for tracking inputs. Unit scans all the inputs continuously and stores this information into Input register. The communication parametes and unit address are set by DIP switch. Specifications: 1. 2. 3. 4. 5. 6. 7. 8. 9. Power Supply Digital Inputs Communication Port I/O Terminals Operating Temperature Storage Temperature Humidity Mounting Dimensions (DIN rail) : : : : : : : : : 24 VDC +/- 10% 0 to 5 V DC Low; 12 to 28 V DC High 2 Wire RS-485 Pluggable terminals. 0OC to 60OC -20OC to 80OC 10% to 90% (Non condensing) DIN rail mounting 70 X 100 X 35 mm

Communication Parameters And Modbus Tag Definition Unit supports MODBUS driver for communication with Master device. COM Port Setting:

COMM PORT SETTING


ADDR5 ADDR4 ADDR3 ADDR2 ADDR1
ON

ADDR6 BAUD1 BAUD2 PARITY1 PARITY2


SD

1 2 3 4 5 6 7 8 9 10

Renu Electronics Private Limited


Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

support@renuelectronics.com

Website:

www.renuelectronics.com

FIOD 1600 Manual

UNIT ID 1 2 . . . . 64

ADDR6 0 0

ADDR5 0 0

ADDR4 0 0

ADDR3 0 0

ADDR2 0 0

ADDR1 0 1

BAUD RATE 9600 19200 57600 115200

BAUD2 0 0 1 1

BAUD1 0 1 0 1

PARITY NONE ODD EVEN

PARITY2 0 0 1

PARITY1 0 1 0

The following dedicated modbus registers are assigned to digital inputs and digital outputs. Digital I/P MODBUS Tag. Input Register I/P1 (X0) I/P2 (X1) I/P3 (X2) I/P4 (X3) I/P5 (X4) I/P6 (X5) I/P7 (X6) I/P8 (X7) 40001_0 40001_1 40001_2 40001_3 40001_4 40001_5 40001_6 40001_7 (Bit 0) (Bit 1) (Bit 2) (Bit 3) (Bit 4) (Bit 5) (Bit 6) (Bit 7) Input Coil 00001 00002 00003 00004 00005 00006 00007 00008

Renu Electronics Private Limited


Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

support@renuelectronics.com

Website:

www.renuelectronics.com

FIOD 1600 Manual


Digital I/P MODBUS Tag. Input Register I/P9 (X8) I/P10 (X9) I/P11 (X10) I/P12 (X11) I/P13 (X12) I/P14 (X13) I/P15 (X14) I/P16 (X15) 40001_8 40001_9 40001_10 40001_11 40001_12 40001_13 40001_14 40001_15 (Bit 8) (Bit 9) (Bit 10) (Bit 11) (Bit 12) (Bit 13) (Bit 14) (Bit 15) Input Coil 00009 00010 00011 00012 00013 00014 00015 00016

Port Details (2 Wire RS485 Port): -

Renu Electronics Private Limited


Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

support@renuelectronics.com

Website:

www.renuelectronics.com

FIOD 1600 Manual


GND GND B A
TERM TERM REST REST

GND B A

M A S T E R

NC DC+ DCDC-

Multidropping connection: M A S T E R

GND

FIOD Unit 1

B A

FIOD Unit 2

FIOD Unit n

Note: Where n is up to 32. Connecting repeater can increase it to 64.

Renu Electronics Private Limited


Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

support@renuelectronics.com

Website:

www.renuelectronics.com

FIOD 1600 Manual


Power Supply Connection: -

GND GND B A
TERM TERM REST REST

NC DC+ DCDC+ 24VDC


+/- 10%

EARTH

Wiring Diagram: Digital Inputs should be wired as given below:

Wiring Diagram for testing Digital Inputs

SW1 SW2

X0 X1

SW16 24VDC

X15

+ IP COM

Closing SWx will turn on respective inputs.


Renu Electronics Private Limited
Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

support@renuelectronics.com

Website:

www.renuelectronics.com

FIOD 1600 Manual


Notes:

MANUAL REVISION If you contact us in reference to this manual, please include the following document number Name : User Manual For FIOD1600 Part Number : URML402 Document : UMAN\FIOD-1600\1106 Revision : 2
Revision Number Rev 1 Rev 2 Document Number Date Description Panel dimensions and port details are added. Power supply, multidropping wiring added.

UMAN\FIOD-1600\1106 22-11-2006 UMAN\FIOD-1600\1106 29-11-2006

Renu Electronics Private Limited


Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:

support@renuelectronics.com

Website:

www.renuelectronics.com

You might also like