SUPPLY OF PLUG VALVES (MOV)

DATA SHEET FOR MOV ACTUATOR 1.0 Site Conditions 1.1 Altitude 1.2 Design ambient temperature 1.3 Humidity 1.4 Climate 1 .5 Project site : Less than 1000 m : 50C : Highly to moderately dry : Highly dusty, corrosive as prevalent in a refinery/petrochemical installations : LONI TERMINAL
HINDUSTAN PETROLEUM CORPORATION LIMITED KADAM WAKWASTI TAL-HAVELI VILLAGE LONI KALBOUR, PUNE SOLAPUR ROAD PUNE-412201 PH-020-26913382, 6913304/82/09

2.0 System Conditions 2.1 Supply voltage 2.2 Supply frequency 2.3 System earthing 3.0 Operating Environment 3.1 Area Classification 3.2 Gas Group 3.3 Temperature Class 3.4 Construction 3.5 Ingress Protection 3.6 Painting 3.7 Whether K-Mass type or equivalent fireproofing required : No : Zone 2 : IIA/IIB : T3 : Flameproof Ex (d) : IP68 : Epoxy base : 415V 10%, 3-phase AC for MOV : 5OHz 3% : Solidly earthed

4.0 Valve Duty, Mode of Control and Devices for Control 4.1 Valve duty a. Fully open and fully closed b. Partialy open and partially closed DATA SHEET FOR MOV ACTUATOR : Yes : No Page 1 of 4

HINDUSTAN PETROLEUM CORP. LTD

SUPPLY OF PLUG VALVES (MOV)

4.2 Control requirement 4.3 Local/Remote/Off selector switch on MOV Actuator 4.4 Compatiability for interfacing with 2 wire control system 4.4.1 Setting of Adjustable parameters Of actuator (for 2 wire control System) 4.5 Continuous position indication 4.5.1 Local

: Local & Remote for all MOVs : Required : Required : From field and remote thru master control station /PLC for 2 wire control

: Mechanical/LCD indication required : Not required : Required

4.5.2 Remote- Potentiometer! Transducer for remote continuous indication 4.6 Intermediate travel limit switch 4.7 Potential free contacts for Indication on remote panel and other interlocks 4.9.1 For valve open position 4.9.2 For valve closed position 4.9.3 For remote indication of position of Local/Remote selector switch 4.9.4 For availability of MOV actuator for remote operation (contact from monitoring relay) 4.9.5 For indicating valve operation in progress 4.10 Remote Emergency Stop push button for stopping actuator 4.11 DCS interface for Remote control/ indication

: Required : Required : Required : Required

: Not required : Not required : Remote Control requirement shall be as per Cl.4.2 above/Remote indication required for all MOVs

4.12 Maximum time of operation - Opening : 60-90 seconds

DATA SHEET FOR MOV ACTUATOR

Page 2 of 4

HINDUSTAN PETROLEUM CORP. LTD

SUPPLY OF PLUG VALVES (MOV)

- Closing plugs for unused entries (To be supplied along with MOV actuator) 4.14 Make of MOV Actuator

: 60-90 seconds

4.13 Double compression cable glands and : Flameproof & WP type

: Rotork/Limitorque/Auma/Biffi

5.0 Test and Approval Certificates for Flameproof Actuators 5.1 For Indigenous make MOV Actuators 5.2 For Imported make MOV Actuators 5.3 Submission of Type test certificates 6.0 Special Requirements NOTES: 1. Area Classification Zone, Gas group and Temperature class indicated at S .Nos. 3.1 to 3.3 above refer to IS/IEC standards. 2. The purchaser shall provide single point power supply to the actuator as per S.No. 1.0 above. Any other control supply voltage required shall be internally derived by the manufacturer within the actuator. 3. In case vendor decides to provide Rotork IQ make actuators, vendor shall also supply infra red (remote) type, intrinsic safe setting/commissioning tools as required for commissioning. 4. Vendor shall furnish complete data as per Part-II of this data sheet for each MOV Actuator. 5. Remote Input signals for Opening/Closing/Stopping the MOV shall be provided through the momentary closing of separate potential free contacts in owners panel. Necessary controls required for running the motor for the complete opening/closing sequence of the valve using such input signals shall be provided by manufacturer in the actuator. 6. Vendor shall supply Maintenance spares for two years trouble free operation & maintenance of the MOV actuators as per Purchase order(P.O.).Vendor shall also supply spares along with quantity required for commissioning the MOVs. : Refer clause no. 7.0 of specification : Refer clause no. 7.0 of specification : Required : NIL

DATA SHEET FOR MOV ACTUATOR

Page 3 of 4

HINDUSTAN PETROLEUM CORP. LTD

SUPPLY OF PLUG VALVES (MOV)

DATA SHEET FOR MOV ACTUATOR Part-II: DATA BY VENDOR 1.0 Actuator 1.1 Make : 1.2 Type & Catalogue No. : 1.3 Applicable Wiring Diagram No. : 1.4 Valve duty : 1.5 Maximum permissible number of Open/Close cycles per hour : 1.6 Internal control supply used in actuator : V, AC 1.7 Recommended backup HRC fuse rating : 2.0 Motor 2.1 Make : 2.2 KW rating : 2.3 Rated speed in RPM : 2.4 Enclosure : 2.5 Locked rotor (starting) current : 2.6 Rated torque (seating) current : 2.7 Average load current : 3.0 Basis for sizing and selection of actuator: 4,0 Test and approval certificates : Furnished/Not furnished 5.0 Component Makes 5.1 Contactors : 5.2 Push buttons : 5.3 Selector switches :