Contents
ABB
Nr ID Name
Events
Description
Display events on the ECT (Excitation Control Terminal): Touch Events The Event Logger contains a table with the last 1000 entries. As soon as this window is selected, an automatic upload will start. If a new entry occurs, the panel reads this out of the UNITROL System and the table will automatically be updated.
Dynamic list of actual events Event logger table
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Rp Fault: The monitoring of Converter 1 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 1 20000 ThyrFlt_Rp_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Tn Fault: The monitoring of Converter 1 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 2 20001 ThyrFlt_Tn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Sp Fault: The monitoring of Converter 1 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 3 20002 ThyrFlt_Sp_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Rn Fault: The monitoring of Converter 1 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 4 20003 ThyrFlt_Rn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Tp Fault: The monitoring of Converter 1 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 5 20004 ThyrFlt_Tp_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Sn Fault: The monitoring of Converter 1 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 6 20005 ThyrFlt_Sn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter) 7 20006 FuseFlt_Rp_CCI1
Related parameters:
ABB
Nr ID Name
Events
Description
Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 8 20007 FuseFlt_Tn_CCI1 - Converter redundancy fault Twin - Converter Trip
ABB
Nr ID Name
Events
Description
Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 9 20008 FuseFlt_Sp_CCI1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 10 20009 FuseFlt_Rn_CCI1 N-1 - Converter redundancy fault Twin - Converter Trip
10
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 11 20010 FuseFlt_Tp_CCI1 - Converter redundancy fault Twin - Converter Trip
11
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 12 20011 FuseFlt_Sn_CCI1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 13 20012 TOCD_R_CCI1 N-1 - Converter alarm Twin - Converter alarm
12
ABB
Nr ID Name
----
Events
Further steps:
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 14 20013 TOCD_S_CCI1 N-1 - Converter alarm Twin - Converter alarm
13
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 15 20014 TOCD_T_CCI1 N-1 - Converter alarm Twin - Converter alarm
Default reaction: N-1 16 20015 UfOpCeil_CCI1 - Converter alarm Twin - Converter alarm
14
ABB
Nr ID Name
Events
CCI1. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 1
17
20016
DevTypeErr_CCI1
15
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
19
20018
LinkFault_CCI1
Further steps: - Check optical link cabling to CCI CCI1. Redundant Power 1 fail
Further steps: - Check cabling and power supply CCI1. Redundant Power 2 fail
Possible reasons: - Power supply fault at input 2 (X2:1-2) 21 20020 RedPwrFail2_CCI1 Default reaction: - Converter Redundancy Fault
Related parameters:
16
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CCI1. CPU Watchdog
23
20022
CPUWatchdog_CCI1
Further steps:
17
ABB
Nr ID Name
Events
- Reboot device
Description
24
20023
UfFreeze_CCI1
18
ABB
Nr ID Name
Events
Description
27
20026
USynFreeze_CCI1
19
ABB
Nr ID Name
Events
Description
Further steps: - Check optical link cabling to AC 800PEC CCI1. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 30 20029 AdvFuseBlow_CCI1 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
20
ABB
Nr ID Name
Events
Description
31
20030
IConvOpCeil_CCI1
21
ABB
Nr ID Name
Events
CCI1. Cooling failure
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI1. Fan 1 Supply 1 fault
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters
22
ABB
Nr ID Name
Events
- Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
23
ABB
Nr ID Name
Events
CCI1. Fan 2 Supply 1 fault
Description
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI1. Fan 2 Supply 2 fault
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
37
20036
Fan2Supply2Flt_CCI1
Further steps:
24
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
Default reaction: - Converter Redundancy fault 38 20037 MCB1Fault_CCI1 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI1. Fan Supply Miniature Circuit Breaker 2 fault
Possible reasons: - Fan 2 defective 39 20038 MCB2Fault_CCI1 Default reaction: - Converter Redundancy fault
Related parameters:
25
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 40 20039 ThyrTemp1Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
26
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 41 20040 ThyrTemp2Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
27
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI1. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 43 20042 ThyrTemp4Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
28
ABB
Nr ID Name
Events
Description
CCI1. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 44 20043 ThyrTemp5Lev1Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
29
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI1. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 46 20045 AirTemp1Lev1Flt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
30
ABB
Nr ID Name
Events
Description
CCI1. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Thyristor Rp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 48 20047 ThyrTemp1SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
31
ABB
Nr ID Name
Events
- Re-check sensor circuit
Description
Possible reasons: - Sensor circuit open >156 C - Sensor short-circuit < -13 C
Default reaction: - Converter alarm 49 20048 ThyrTemp2SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
32
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 50 20049 ThyrTemp3SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI1. Thyristor Rn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 51 20050 ThyrTemp4SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
33
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 52 20051 ThyrTemp5SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI1. Thyristor Sn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 53 20052 ThyrTemp6SensFl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
34
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 54 20053 AirTemp1SensFlt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Re-check sensor circuit CCI1. Air Temperature 2 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 55 20054 AirTemp2SensFlt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
35
ABB
Nr ID Name
Events
CCI1. Snubber Switch fault
Description
Default reaction: N-1 56 20055 SnubberSwiFlt_CCI1 - Converter alarm TWIN - Converter Trip
36
ABB
Nr ID Name
Events
CCI1. Thyristor Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI1. Converter cabinet Door fault
Further steps: - Close converter cabinet door CCI1. Software Version fault
37
ABB
Nr ID Name
Events
Description
CCI1. NegConvFault_CCI1
Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration
Possible reason: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
62
20061
PulseBlockFault_CCI1
38
ABB
Nr
64
ID
20063
Name
Event2_31_CCI1
Events
Description
65
20064
ThyrTemp1Lev2Fl_CCI1
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI1. Thyristor Tn Case Temperature above trip level
Default reaction: - Converter Trip 66 20065 ThyrTemp2Lev2Fl_CCI1 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
39
ABB
Nr ID Name
Events
Description
67
20066
ThyrTemp3Lev2Fl_CCI1
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
40
ABB
Nr ID Name
Events
Description
68
20067
ThyrTemp4Lev2Fl_CCI1
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI1. Thyristor Tp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
41
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
70
20069
ThyrTemp6Lev2Fl_CCI1
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
42
ABB
Nr ID Name
Events
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI1. Air Temperature 2 ( Air outlet chimney ) above fault level
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 72 20071 AirTemp2Lev2Flt_CCI1 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
43
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90
20072 20073 20074 20075 20076 20077 20078 20079 20080 20081 20082 20083 20084 20085 20086 20087 20088 20089
Event3_08_CCI1 Event3_09_CCI1 Event3_10_CCI1 Event3_11_CCI1 Event3_12_CCI1 Event3_13_CCI1 Event3_14_CCI1 Event3_15_CCI1 Event3_16_CCI1 Event3_17_CCI1 Event3_18_CCI1 Event3_19_CCI1 Event3_20_CCI1 Event3_21_CCI1 Event3_22_CCI1 Event3_23_CCI1 Event3_24_CCI1 Event3_25_CCI1
44
ABB
Nr
91 92 93 94 95 96
ID
20090 20091 20092 20093 20094 20095
Name
Event3_26_CCI1 Event3_27_CCI1 Event3_28_CCI1 Event3_29_CCI1 Event3_30_CCI1 Event3_31_CCI1
Events
Description
CCI2. Thyristor Rp Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 97 20100 ThyrFlt_Rp_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip
45
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Tn Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 98 20101 ThyrFlt_Tn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip
46
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Sp Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 99 20102 ThyrFlt_Sp_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip
47
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Rn Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 100 20103 ThyrFlt_Rn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip
48
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Tp Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 101 20104 ThyrFlt_Tp_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip
49
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Sn Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 102 20105 ThyrFlt_Sn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 103 20106 FuseFlt_Rp_CCI2
Related parameters:
50
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 104 20107 FuseFlt_Tn_CCI2 - Converter redundancy fault Twin - Converter Trip
51
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 105 20108 FuseFlt_Sp_CCI2 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 106 20109 FuseFlt_Rn_CCI2 N-1 - Converter redundancy fault Twin - Converter Trip
52
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 107 20110 FuseFlt_Tp_CCI2 - Converter redundancy fault Twin - Converter Trip
53
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 108 20111 FuseFlt_Sn_CCI2 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 109 20112 TOCD_R_CCI2 N-1 - Converter alarm Twin - Converter alarm
54
ABB
Nr ID Name
----
Events
Further steps:
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 110 20113 TOCD_S_CCI2 N-1 - Converter alarm Twin - Converter alarm
55
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 111 20114 TOCD_T_CCI2 N-1 - Converter alarm Twin - Converter alarm
Default reaction: N-1 112 20115 UfOpCeil_CCI2 - Converter alarm Twin - Converter alarm
56
ABB
Nr ID Name
Events
CCI2. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 2
113
20116
DevTypeErr_CCI2
57
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
115
20118
LinkFault_CCI2
Further steps: - Check optical link cabling to CCI CCI2. Redundant Power 1 fail
Further steps: - Check cabling and power supply CCI2. Redundant Power 2 fail
Possible reasons: - Power supply fault at input 2 (X2:1-2) 117 20120 RedPwrFail2_CCI2 Default reaction: - Converter Redundancy Fault
Related parameters:
58
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CCI2. CPU Watchdog
119
20122
CPUWatchdog_CCI2
Further steps:
59
ABB
Nr ID Name
Events
- Reboot device
Description
120
20123
UfFreeze_CCI2
60
ABB
Nr ID Name
Events
Description
123
20126
USynFreeze_CCI2
Possible reasons: - Two or all three connections lost 124 20127 USynAllLost_CCI2
61
ABB
Nr ID Name
Events
Description
Further steps: - Check optical link cabling to AC 800PEC CCI2. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 126 20129 AdvFuseBlow_CCI2 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
62
ABB
Nr ID Name
Events
Description
127
20130
IConvOpCeil_CCI2
63
ABB
Nr ID Name
Events
CCI2. Cooling failure
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI2. Fan 1 Supply 1 fault
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters
64
ABB
Nr ID Name
Events
- Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
65
ABB
Nr ID Name
Events
CCI2. Fan 2 Supply 1 fault
Description
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI2. Fan 2 Supply 2 fault
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
133
20136
Fan2Supply2Flt_CCI2
Further steps:
66
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
Default reaction: - Converter Redundancy fault 134 20137 MCB1Fault_CCI2 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI2. Fan Supply Miniature Circuit Breaker 2 fault
Possible reasons: - Fan 2 defective 135 20138 MCB2Fault_CCI2 Default reaction: - Converter Redundancy fault
Related parameters:
67
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 136 20139 ThyrTemp1Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
68
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 137 20140 ThyrTemp2Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
69
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI2. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 139 20142 ThyrTemp4Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
70
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 140 20143 ThyrTemp5Lev1Fl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
71
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI2. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 142 20145 AirTemp1Lev1Flt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
72
ABB
Nr ID Name
Events
Description
CCI2. Air Temperature 2 ( Air outlet chimmey ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Thyristor Rp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 144 20147 ThyrTemp1SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
73
ABB
Nr ID Name
Events
- Re-check sensor circuit
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 145 20148 ThyrTemp2SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
74
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 146 20149 ThyrTemp3SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI2. Thyristor Rn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 147 20150 ThyrTemp4SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
75
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 148 20151 ThyrTemp5SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI2. Thyristor Sn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 149 20152 ThyrTemp6SensFl_CCI2 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
76
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 150 20153 AirTemp1SensFlt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Re-check sensor circuit CCI2. Air Temperature 2 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 151 20154 AirTemp2SensFlt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
77
ABB
Nr ID Name
Events
CCI2. Snubber Switch fault
Description
Default reaction: N-1 152 20155 SnubberSwiFlt_CCI2 - Converter alarm TWIN - Converter Trip
78
ABB
Nr ID Name
Events
CCI2. Thyristor Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI2. Converter cabinet Door fault
Further steps: - Close converter cabinet door CCI2. Software Version fault
79
ABB
Nr ID Name
Events
Description
CCI2. NegConvFault_CCI2
Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration
Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
158
20161
PulseBlockFault_CCI2
80
ABB
Nr
160
ID
20163
Name
Event2_31_CCI2
Events
Description
161
20164
ThyrTemp1Lev2Fl_CCI2
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI2. Thyristor Tn Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
81
ABB
Nr ID Name
Events
Description
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
163
20166
ThyrTemp3Lev2Fl_CCI2
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
82
ABB
Nr ID Name
Events
Description
164
20167
ThyrTemp4Lev2Fl_CCI2
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI2. Thyristor Tp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
83
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
166
20169
ThyrTemp6Lev2Fl_CCI2
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
84
ABB
Nr ID Name
Events
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI2. Air Temperature 2 ( Air outlet chimney ) above fault level
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 168 20171 AirTemp2Lev2Flt_CCI2 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
85
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
169 1'341 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187
20172 21500 20174 20175 20176 20177 20178 20179 20180 20181 20182 20183 20184 20185 20186 20187 20188 20189 20190
Event3_08_CCI2 Event4_14 Event3_10_CCI2 Event3_11_CCI2 Event3_12_CCI2 Event3_13_CCI2 Event3_14_CCI2 Event3_15_CCI2 Event3_16_CCI2 Event3_17_CCI2 Event3_18_CCI2 Event3_19_CCI2 Event3_20_CCI2 Event3_21_CCI2 Event3_22_CCI2 Event3_23_CCI2 Event3_24_CCI2 Event3_25_CCI2 Event3_26_CCI2
86
ABB
Nr
188 189 190 191 192
ID
20191 20192 20193 20194 20195
Name
Event3_27_CCI2 Event3_28_CCI2 Event3_29_CCI2 Event3_30_CCI2 Event3_31_CCI2
Events
Description
CCI3. Thyristor Rp Fault: The monitoring of Converter 3 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 193 20200 ThyrFlt_Rp_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip
87
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Tn Fault: The monitoring of Converter 3 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 194 20201 ThyrFlt_Tn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip
88
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Sp Fault: The monitoring of Converter 3 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 195 20202 ThyrFlt_Sp_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip
89
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Rn Fault: The monitoring of Converter 3 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 196 20203 ThyrFlt_Rn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip
90
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Tp Fault: The monitoring of Converter 3 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 197 20204 ThyrFlt_Tp_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip
91
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Sn Fault: The monitoring of Converter 3 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 198 20205 ThyrFlt_Sn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 199 20206 FuseFlt_Rp_CCI3
Related parameters:
92
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 200 20207 FuseFlt_Tn_CCI3 - Converter redundancy fault Twin - Converter Trip
93
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 201 20208 FuseFlt_Sp_CCI3 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 202 20209 FuseFlt_Rn_CCI3 N-1 - Converter redundancy fault Twin - Converter Trip
94
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 203 20210 FuseFlt_Tp_CCI3 - Converter redundancy fault Twin - Converter Trip
95
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 204 20211 FuseFlt_Sn_CCI3 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 205 20212 TOCD_R_CCI3 N-1 - Converter alarm Twin - Converter alarm
96
ABB
Nr ID Name
----
Events
Further steps:
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 206 20213 TOCD_S_CCI3 N-1 - Converter alarm Twin - Converter alarm
97
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 207 20215 TOCD_T_CCI3 N-1 - Converter alarm Twin - Converter alarm
Default reaction: N-1 208 20216 UfOpCeil_CCI3 - Converter alarm Twin - Converter alarm
98
ABB
Nr ID Name
Events
CCI3. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 3
209
20217
DevTypeErr_CCI3
99
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
211
20219
LinkFault_CCI3
Further steps: - Check optical link cabling to CCI CCI3. Redundant Power 1 fail
Further steps: - Check cabling and power supply CCI3. Redundant Power 2 fail
Possible reasons: - Power supply fault at input 2 (X2:1-2) 213 20221 RedPwrFail2_CCI3 Default reaction: - Converter Redundancy Fault
Related parameters:
100
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CCI3. CPU Watchdog
215
20223
CPUWatchdog_CCI3
Further steps:
101
ABB
Nr ID Name
Events
- Reboot device
Description
216
20224
UfFreeze_CCI3
102
ABB
Nr ID Name
Events
Description
219
20227
USynFreeze_CCI3
Possible reasons: - Two or all three connections lost 220 20228 USynAllLost_CCI3
103
ABB
Nr ID Name
Events
Description
Further steps: - Check optical link cabling to AC 800PEC CCI3. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 222 20230 AdvFuseBlow_CCI3 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
104
ABB
Nr ID Name
Events
Description
223
20231
IConvOpCeil_CCI3
105
ABB
Nr ID Name
Events
CCI3. Cooling failure
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI3. Fan 1 Supply 1 fault
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters
106
ABB
Nr ID Name
Events
- Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
107
ABB
Nr ID Name
Events
CCI3. Fan 2 Supply 1 fault
Description
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI3. Fan 2 Supply 2 fault
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
229
20237
Fan2Supply2Flt_CCI3
Further steps:
108
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace preasure sensor
Default reaction: - Converter Redundancy fault 230 20238 MCB1Fault_CCI3 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI3. Fan Supply Miniature Circuit Breaker 2 fault
Possible reasons: - Fan 2 defective 231 20239 MCB2Fault_CCI3 Default reaction: - Converter Redundancy fault
Related parameters:
109
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 232 20240 ThyrTemp1Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
110
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 233 20241 ThyrTemp2Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
111
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI3. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 235 20243 ThyrTemp4Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
112
ABB
Nr ID Name
Events
Description
CCI3. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 236 20244 ThyrTemp5Lev1Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
113
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI3. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 238 20246 AirTemp1Lev1Flt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
114
ABB
Nr ID Name
Events
Description
CCI3. Air Temperature 2 ( Air outlet chimmey ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Thyristor Rp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 240 20248 ThyrTemp1SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
115
ABB
Nr ID Name
Events
- Re-check sensor circuit
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 241 20249 ThyrTemp2SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
116
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 242 20250 ThyrTemp3SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI3. Thyristor Rn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 243 20251 ThyrTemp4SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
117
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 244 20252 ThyrTemp5SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI3. Thyristor Sn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 245 20253 ThyrTemp6SensFl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
118
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 246 20254 AirTemp1SensFlt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Re-check sensor circuit CCI3. Air Temperature 2 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 247 20255 AirTemp2SensFlt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
119
ABB
Nr ID Name
Events
CCI3. Snubber Switch fault
Description
Default reaction: N-1 248 20256 SnubberSwiFlt_CCI3 - Converter alarm TWIN - Converter Trip
120
ABB
Nr ID Name
Events
CCI3. Thyristor Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI3. Converter cabinet Door fault
Further steps: - Close converter cabinet door CCI3. Software Version fault
121
ABB
Nr ID Name
Events
Description
CCI3. NegConvFault_CCI3
Possible reasons: - The DI12 signal of Converter I/O does not match converter configuration
Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
254
20262
PulseBlockFault_CCI3
122
ABB
Nr
256
ID
20264
Name
Event2_31_CCI3
Events
Description
257
20265
ThyrTemp1Lev2Fl_CCI3
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI3. Thyristor Tn Case Temperature above trip level
Default reaction: - Converter Trip 258 20266 ThyrTemp2Lev2Fl_CCI3 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
123
ABB
Nr ID Name
Events
Description
259
20267
ThyrTemp3Lev2Fl_CCI3
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters 1'343 20268 ForceAuto
124
ABB
Nr ID Name
Events
Description
260
20269
ThyrTemp4Lev2Fl_CCI3
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI3. Thyristor Tp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
125
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
262
20271
ThyrTemp6Lev2Fl_CCI3
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
126
ABB
Nr ID Name
Events
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI3. Air Temperature 2 ( Air outlet chimney ) above fault level
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 264 20273 AirTemp2Lev2Flt_CCI3 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
127
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282
20274 20275 20276 20277 20278 20279 20280 20281 20282 20283 20284 20285 20286 20287 20288 20289 20290 20291
Event3_08_CCI3 Event3_09_CCI3 Event3_10_CCI3 Event3_11_CCI3 Event3_12_CCI3 Event3_13_CCI3 Event3_14_CCI3 Event3_15_CCI3 Event3_16_CCI3 Event3_17_CCI3 Event3_18_CCI3 Event3_19_CCI3 Event3_20_CCI3 Event3_21_CCI3 Event3_22_CCI3 Event3_23_CCI3 Event3_24_CCI3 Event3_25_CCI3
128
ABB
Nr
283 284 285 286 287 288
ID
20292 20293 20294 20295 20300 20301
Name
Event3_26_CCI3 Event3_27_CCI3 Event3_28_CCI3 Event3_29_CCI3 Event3_30_CCI3 Event3_31_CCI3
Events
Description
CCI4. Thyristor Rp Fault: The monitoring of Converter 4 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 289 20302 ThyrFlt_Rp_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip
129
ABB
Nr ID Name
Events
Description
CCI4. Thyristor Tn Fault: The monitoring of Converter 4 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 290 20303 ThyrFlt_Tn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip
130
ABB
Nr ID Name
Events
Description
CCI4. Thyristor Sp Fault: The monitoring of Converter 4 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 291 20304 ThyrFlt_Sp_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip
131
ABB
Nr ID Name
Events
Description
CCI4. Thyristor Rn Fault: The monitoring of Converter 4 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 292 20305 ThyrFlt_Rn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip
Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ---CCI4. Thyristor Tp Fault: The monitoring of Converter 4 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty 293 20306 ThyrFlt_Tp_CCI4 - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
132
ABB
Nr ID Name
Events
Description
CCI4. Thyristor Sn Fault: The monitoring of Converter 4 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time)
Default reaction: 294 20307 ThyrFlt_Sn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip
Further steps:
133
ABB
Nr ID Name
----
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction
Default reaction: N-1 295 20308 FuseFlt_Rp_CCI4 - Converter redundancy fault Twin - Converter Trip
134
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 296 20309 FuseFlt_Tn_CCI4 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 297 20310 FuseFlt_Sp_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip
135
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 298 20311 FuseFlt_Rn_CCI4 - Converter redundancy fault Twin - Converter Trip
136
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 299 20312 FuseFlt_Tp_CCI4 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 300 20313 FuseFlt_Sn_CCI4 N-1 - Converter redundancy fault Twin - Converter Trip
137
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 301 20314 TOCD_R_CCI4 N-1 - Converter alarm Twin - Converter alarm
138
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 302 20315 TOCD_S_CCI4 N-1 - Converter alarm Twin - Converter alarm
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 303 20317 TOCD_T_CCI4 N-1 - Converter alarm Twin - Converter alarm
Further steps:
139
ABB
Nr ID Name
----
Events
Description
Default reaction: N-1 304 20318 UfOpCeil_CCI4 - Converter alarm Twin - Converter alarm
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) 305 20319 DevTypeErr_CCI4 - Wrong installer archive loaded to CCI 4
140
ABB
Nr ID Name
----
Events
Related parameters:
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
307
20321
LinkFault_CCI4
141
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CCI4. Redundant Power 2 fail
Further steps: - Check cabling and power supply CCI4. Precision Power fail
Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing 310 20324 PrciPwrFail_CCI4 Default reaction: - Converter Trip
142
ABB
Nr ID Name
Events
Description
Further steps: - Reboot device - Download installer archive - Replace board CCI4. Field Voltage measurement failure
Possible reasons: - Operation amplifier blocked (frozen) - ADC failure 312 20326 UfFreeze_CCI4 Default reaction: - Converter Alarm
143
ABB
Nr ID Name
Events
Description
144
ABB
Nr ID Name
Events
Description
315
20329
USynFreeze_CCI4
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) 317 20331 SelfTrip_CCI4
145
ABB
Nr ID Name
Events
Description
CCI4. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 318 20332 AdvFuseBlow_CCI4 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
Further steps: - Check thyristors - Check fuses CCI4. Converter Current measurement failure
319
20333
IConvOpCeil_CCI4
Further steps:
146
ABB
Nr ID Name
Events
- Replace board
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
321
20335
CoolingFailure_CCI4
147
ABB
Nr ID Name
Events
- Clean air inlet filters - Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
148
ABB
Nr ID Name
Events
CCI4. Fan 1 Supply 2 fault
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI4. Fan 2 Supply 1 fault
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
324
20338
Fan2Supply1Flt_CCI4
Further steps:
149
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace preasure sensor
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
150
ABB
Nr ID Name
Events
Description
Default reaction: - Converter Redundancy fault 326 20340 MCB1Fault_CCI4 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI4. Fan Supply Miniature Circuit Breaker 2 fault
Default reaction: - Converter Redundancy fault 327 20341 MCB2Fault_CCI4 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
151
ABB
Nr ID Name
Events
Description
CCI4. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 328 20342 ThyrTemp1Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI4. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
152
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI4. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 330 20344 ThyrTemp3Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
153
ABB
Nr ID Name
Events
Description
CCI4. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 331 20345 ThyrTemp4Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI4. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
154
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI4. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 333 20347 ThyrTemp6Lev1Fl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
155
ABB
Nr ID Name
Events
Description
CCI4. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 334 20348 AirTemp1Lev1Flt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI4. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
335
20349
AirTemp2Lev1Flt_CCI4
Conv_ConverterModule1 \ EnaCabinetTempMeas
156
ABB
Nr ID Name
Events
Further steps:
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 336 20350 ThyrTemp1SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
157
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 337 20351 ThyrTemp2SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI4. Thyristor Sp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 338 20352 ThyrTemp3SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
158
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 339 20353 ThyrTemp4SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI4. Thyristor Tp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 340 20354 ThyrTemp5SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
159
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 341 20355 ThyrTemp6SensFl_CCI4 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI4. Air Temperature 1 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 342 20356 AirTemp1SensFlt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
160
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 343 20357 AirTemp2SensFlt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Default reaction: N-1 344 20358 SnubberSwiFlt_CCI4 - Converter alarm TWIN - Converter Trip
161
ABB
Nr ID Name
Events
CCI4. Snubber Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI4. Converter cabinet Door fault
Possible reasons: - Digital input for open door activated 347 20361 DoorFlt_CCI4
162
ABB
Nr ID Name
Events
Description
Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration
163
ABB
Nr ID Name
Events
Description
Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
350
20364
PulseBlockFault_CCI4
Further steps: - Re-check HW input 351 352 20365 20366 TestPosition_CCI4 Event2_31_CCI4 CCI4. Thyristor Rp Case Temperature above trip level
353
20367
ThyrTemp1Lev2Fl_CCI4
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
164
ABB
Nr ID Name
Events
Description
354
20368
ThyrTemp2Lev2Fl_CCI4
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI4. Thyristor Sp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
165
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
1'345
20370
356
20371
ThyrTemp4Lev2Fl_CCI4
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
166
ABB
Nr ID Name
Events
Description
357
20372
ThyrTemp5Lev2Fl_CCI4
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI4. Thyristor Sn Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
167
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
168
ABB
Nr ID Name
Events
Description
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 360 20375 AirTemp2Lev2Flt_CCI4 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters 361 362 363 364 365 366 367 368 369 370 371 372 373 374 20376 20377 20378 20379 20380 20381 20382 20383 20384 20385 20386 20387 20388 20389 Event3_08_CCI4 Event3_09_CCI4 Event3_10_CCI4 Event3_11_CCI4 Event3_12_CCI4 Event3_13_CCI4 Event3_14_CCI4 Event3_15_CCI4 Event3_16_CCI4 Event3_17_CCI4 Event3_18_CCI4 Event3_19_CCI4 Event3_20_CCI4 Event3_21_CCI4
169
ABB
Nr
375 376 377 378 379 380 381 382 383 384
ID
20390 20391 20392 20393 20394 20395 20400 20401 20402 20403
Name
Event3_22_CCI4 Event3_23_CCI4 Event3_24_CCI4 Event3_25_CCI4 Event3_26_CCI4 Event3_27_CCI4 Event3_28_CCI4 Event3_29_CCI4 Event3_30_CCI4 Event3_31_CCI4
Events
Description
CCI5. Thyristor Rp Fault: The monitoring of Converter 5 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 385 20404 ThyrFlt_Rp_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip
170
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Tn Fault: The monitoring of Converter 5 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 386 20405 ThyrFlt_Tn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip
171
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Sp Fault: The monitoring of Converter 5 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 387 20406 ThyrFlt_Sp_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip
172
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Rn Fault: The monitoring of Converter 5 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 388 20407 ThyrFlt_Rn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip
173
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Tp Fault: The monitoring of Converter 5 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 389 20408 ThyrFlt_Tp_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip
174
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Sn Fault: The monitoring of Converter 5 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 390 20409 ThyrFlt_Sn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 391 20410 FuseFlt_Rp_CCI5
Related parameters:
175
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 392 20411 FuseFlt_Tn_CCI5 - Converter redundancy fault Twin - Converter Trip
176
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 393 20412 FuseFlt_Sp_CCI5 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 394 20413 FuseFlt_Rn_CCI5 N-1 - Converter redundancy fault Twin - Converter Trip
177
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 395 20414 FuseFlt_Tp_CCI5 - Converter redundancy fault Twin - Converter Trip
178
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 396 20415 FuseFlt_Sn_CCI5 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 397 20416 TOCD_R_CCI5 N-1 - Converter alarm Twin - Converter alarm
179
ABB
Nr ID Name
----
Events
Further steps:
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 398 20417 TOCD_S_CCI5 N-1 - Converter alarm Twin - Converter alarm
180
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 399 20419 TOCD_T_CCI5 N-1 - Converter alarm Twin - Converter alarm
Default reaction: N-1 400 20420 UfOpCeil_CCI5 - Converter alarm Twin - Converter alarm
181
ABB
Nr ID Name
Events
CCI5. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 5
401
20421
DevTypeErr_CCI5
182
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
403
20423
LinkFault_CCI5
Further steps: - Check optical link cabling to CCI CCI5. Redundant Power 1 fail
Further steps: - Check cabling and power supply CCI5. Redundant Power 2 fail
Possible reasons: - Power supply fault at input 2 (X2:1-2) 405 20425 RedPwrFail2_CCI5 Default reaction: - Converter Redundancy Fault
Related parameters:
183
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CCI5. CPU Watchdog
407
20427
CPUWatchdog_CCI5
Further steps:
184
ABB
Nr ID Name
Events
- Reboot device
Description
408
20428
UfFreeze_CCI5
185
ABB
Nr ID Name
Events
Description
411
20431
USynFreeze_CCI5
Possible reasons: - Two or all three connections lost 412 20432 USynAllLost_CCI5
186
ABB
Nr ID Name
Events
Description
Further steps: - Check optical link cabling to AC 800PEC CCI5. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 414 20434 AdvFuseBlow_CCI5 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
187
ABB
Nr ID Name
Events
Description
415
20435
IConvOpCeil_CCI5
188
ABB
Nr ID Name
Events
CCI5. Cooling failure
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI5. Fan 1 Supply 1 fault
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters
189
ABB
Nr ID Name
Events
- Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
190
ABB
Nr ID Name
Events
CCI5. Fan 2 Supply 1 fault
Description
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI5. Fan 2 Supply 2 fault
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
421
20441
Fan2Supply2Flt_CCI5
Further steps:
191
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
Default reaction: - Converter Redundancy fault 422 20442 MCB1Fault_CCI5 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI5. Fan Supply Miniature Circuit Breaker 2 fault
Possible reasons: - Fan 2 defective 423 20443 MCB2Fault_CCI5 Default reaction: - Converter Redundancy fault
Related parameters:
192
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 424 20444 ThyrTemp1Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
193
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 425 20445 ThyrTemp2Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
194
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI5. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 427 20447 ThyrTemp4Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
195
ABB
Nr ID Name
Events
Description
CCI5. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 428 20448 ThyrTemp5Lev1Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
196
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI5. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 430 20450 AirTemp1Lev1Flt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
197
ABB
Nr ID Name
Events
Description
CCI5. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Thyristor Rp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 432 20452 ThyrTemp1SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
198
ABB
Nr ID Name
Events
- Re-check sensor circuit
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 433 20453 ThyrTemp2SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
199
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 434 20454 ThyrTemp3SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI5. Thyristor Rn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 435 20455 ThyrTemp4SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
200
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 436 20456 ThyrTemp5SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI5. Thyristor Sn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 437 20457 ThyrTemp6SensFl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
201
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 438 20458 AirTemp1SensFlt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Re-check sensor circuit CCI5. Air Temperature 2 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 439 20459 AirTemp2SensFlt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
202
ABB
Nr ID Name
Events
CCI5. Snubber Switch fault
Description
Default reaction: N-1 440 20460 SnubberSwiFlt_CCI5 - Converter alarm TWIN - Converter Trip
203
ABB
Nr ID Name
Events
CCI5. Thyristor Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI5. Converter cabinet Door fault
Further steps: - Close converter cabinet door CCI5. Software Version fault
204
ABB
Nr ID Name
Events
Description
CCI5. NegConvFault_CCI5
Possible reasons: - The DI 12 signal of Converter I/O does not match to converter configuration
Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
446
20466
PulseBlockFault_CCI5
205
ABB
Nr
448
ID
20468
Name
Event2_31_CCI5
Events
Description
449
20469
ThyrTemp1Lev2Fl_CCI5
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI5. Thyristor Tn Case Temperature above trip level
Default reaction: - Converter Trip 450 20470 ThyrTemp2Lev2Fl_CCI5 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
206
ABB
Nr ID Name
Events
Description
451
20471
ThyrTemp3Lev2Fl_CCI5
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters 1'347 20472 ForceBU
207
ABB
Nr ID Name
Events
Description
452
20473
ThyrTemp4Lev2Fl_CCI5
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI5. Thyristor Tp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
208
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
454
20475
ThyrTemp6Lev2Fl_CCI5
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
209
ABB
Nr ID Name
Events
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI5. Air Temperature 2 ( Air outlet chimney ) above fault level
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 456 20477 AirTemp2Lev2Flt_CCI5 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
210
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474
20478 20479 20480 20481 20482 20483 20484 20485 20486 20487 20488 20489 20490 20491 20492 20493 20494 20495
Event3_08_CCI5 Event3_09_CCI5 Event3_10_CCI5 Event3_11_CCI5 Event3_12_CCI5 Event3_13_CCI5 Event3_14_CCI5 Event3_15_CCI5 Event3_16_CCI5 Event3_17_CCI5 Event3_18_CCI5 Event3_19_CCI5 Event3_20_CCI5 Event3_21_CCI5 Event3_22_CCI5 Event3_23_CCI5 Event3_24_CCI5 Event3_25_CCI5
211
ABB
Nr
475 476 477 478 479 480
ID
20500 20501 20502 20503 20504 20505
Name
Event3_26_CCI5 Event3_27_CCI5 Event3_28_CCI5 Event3_29_CCI5 Event3_30_CCI5 Event3_31_CCI5
Events
Description
CCI6. Thyristor Rp Fault: The monitoring of Converter 6 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 481 20506 ThyrFlt_Rp_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip
212
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Tn Fault: The monitoring of Converter 6 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 482 20507 ThyrFlt_Tn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip
213
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Sp Fault: The monitoring of Converter 6 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 483 20508 ThyrFlt_Sp_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip
214
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Rn Fault: The monitoring of Converter 6 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 484 20509 ThyrFlt_Rn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip
215
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Tp Fault: The monitoring of Converter 6 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 485 20510 ThyrFlt_Tp_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip
216
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Sn Fault: The monitoring of Converter 6 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 486 20511 ThyrFlt_Sn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 487 20512 FuseFlt_Rp_CCI6
Related parameters:
217
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 488 20513 FuseFlt_Tn_CCI6 - Converter redundancy fault Twin - Converter Trip
218
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 489 20514 FuseFlt_Sp_CCI6 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 490 20515 FuseFlt_Rn_CCI6 N-1 - Converter redundancy fault Twin - Converter Trip
219
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 491 20516 FuseFlt_Tp_CCI6 - Converter redundancy fault Twin - Converter Trip
220
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 492 20517 FuseFlt_Sn_CCI6 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 493 20518 TOCD_R_CCI6 N-1 - Converter alarm Twin - Converter alarm
221
ABB
Nr ID Name
----
Events
Further steps:
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 494 20519 TOCD_S_CCI6 N-1 - Converter alarm Twin - Converter alarm
222
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 495 20521 TOCD_T_CCI6 N-1 - Converter alarm Twin - Converter alarm
Default reaction: N-1 496 20522 UfOpCeil_CCI6 - Converter alarm Twin - Converter alarm
223
ABB
Nr ID Name
Events
CCI6. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 6
497
20523
DevTypeErr_CCI6
224
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
499
20525
LinkFault_CCI6
Further steps: - Check optical link cabling to CCI CCI6. Redundant Power 1 fail
Further steps: - Check cabling and power supply CCI6. Redundant Power 2 fail
Possible reasons: - Power supply fault at input 2 (X2:1-2) 501 20527 RedPwrFail2_CCI6 Default reaction: - Converter Redundancy Fault
Related parameters:
225
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CCI - Both pover supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CCI6. CPU Watchdog
503
20529
CPUWatchdog_CCI6
Further steps:
226
ABB
Nr ID Name
Events
- Reboot device
Description
504
20530
UfFreeze_CCI6
227
ABB
Nr ID Name
Events
Description
507
20533
USynFreeze_CCI6
Possible reasons: - Two or all three connections lost 508 20534 USynAllLost_CCI6
228
ABB
Nr ID Name
Events
Description
Further steps: - Check optical link cabling to AC 800PEC CCI6. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 510 20536 AdvFuseBlow_CCI6 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
229
ABB
Nr ID Name
Events
Description
511
20537
IConvOpCeil_CCI6
230
ABB
Nr ID Name
Events
CCI6. Cooling failure
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI6. Fan 1 Supply 1 fault
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters
231
ABB
Nr ID Name
Events
- Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
232
ABB
Nr ID Name
Events
CCI6. Fan 2 Supply 1 fault
Description
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI6. Fan 2 Supply 2 fault
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
517
20543
Fan2Supply2Flt_CCI6
Further steps:
233
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
Default reaction: - Converter Redundancy fault 518 20544 MCB1Fault_CCI6 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI6. Fan Supply Miniature Circuit Breaker 2 fault
Possible reasons: - Fan 2 defective 519 20545 MCB2Fault_CCI6 Default reaction: - Converter Redundancy fault
Related parameters:
234
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 520 20546 ThyrTemp1Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
235
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 521 20547 ThyrTemp2Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
236
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI6. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 523 20549 ThyrTemp4Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
237
ABB
Nr ID Name
Events
Description
CCI6. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 524 20550 ThyrTemp5Lev1Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
238
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI6. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 526 20552 AirTemp1Lev1Flt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
239
ABB
Nr ID Name
Events
Description
CCI6. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Thyristor Rp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 528 20554 ThyrTemp1SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
240
ABB
Nr ID Name
Events
- Re-check sensor circuit
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 529 20555 ThyrTemp2SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
241
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 530 20556 ThyrTemp3SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI6. Thyristor Rn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 531 20557 ThyrTemp4SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
242
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 532 20558 ThyrTemp5SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI6. Thyristor Sn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 533 20559 ThyrTemp6SensFl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
243
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 534 20560 AirTemp1SensFlt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Re-check sensor circuit CCI6. Air Temperature 2 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 535 20561 AirTemp2SensFlt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
244
ABB
Nr ID Name
Events
CCI6. Snubber Switch fault
Description
Default reaction: N-1 536 20562 SnubberSwiFlt_CCI6 - Converter alarm TWIN - Converter Trip
245
ABB
Nr ID Name
Events
CCI6. Thyristor Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI6. Converter cabinet Door fault
Further steps: - Close converter cabinet door CCI6. Software Version fault
246
ABB
Nr ID Name
Events
Description
CCI6. NegConvFault_CCI6
Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration
Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
542
20568
PulseBlockFault_CCI6
247
ABB
Nr
544
ID
20570
Name
Event2_31_CCI6
Events
Description
545
20571
ThyrTemp1Lev2Fl_CCI6
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI6. Thyristor Tn Case Temperature above trip level
Default reaction: - Converter Trip 546 20572 ThyrTemp2Lev2Fl_CCI6 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
248
ABB
Nr ID Name
Events
Description
547
20573
ThyrTemp3Lev2Fl_CCI6
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
249
ABB
Nr ID Name
Events
Description
548
20574
ThyrTemp4Lev2Fl_CCI6
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI6. Thyristor Tp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
250
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
550
20576
ThyrTemp6Lev2Fl_CCI6
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
251
ABB
Nr ID Name
Events
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI6. Air Temperature 2 ( Air outlet chimney ) above fault level
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 552 20578 AirTemp2Lev2Flt_CCI6 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
252
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570
20579 20580 20581 20582 20583 20584 20585 20586 20587 20588 20589 20590 20591 20592 20593 20594 20595 20600
Event3_08_CCI6 Event3_09_CCI6 Event3_10_CCI6 Event3_11_CCI6 Event3_12_CCI6 Event3_13_CCI6 Event3_14_CCI6 Event3_15_CCI6 Event3_16_CCI6 Event3_17_CCI6 Event3_18_CCI6 Event3_19_CCI6 Event3_20_CCI6 Event3_21_CCI6 Event3_22_CCI6 Event3_23_CCI6 Event3_24_CCI6 Event3_25_CCI6
253
ABB
Nr
571 572 573 574 575 576
ID
20601 20602 20603 20604 20605 20606
Name
Event3_26_CCI6 Event3_27_CCI6 Event3_28_CCI6 Event3_29_CCI6 Event3_30_CCI6 Event3_31_CCI6
Events
Description
CCI7. Thyristor Rp Fault: The monitoring of Converter 7 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 577 20607 ThyrFlt_Rp_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip
254
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Tn Fault: The monitoring of Converter 7 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 578 20608 ThyrFlt_Tn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip
255
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Sp Fault: The monitoring of Converter 7 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 579 20609 ThyrFlt_Sp_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip
256
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Rn Fault: The monitoring of Converter 7 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 580 20610 ThyrFlt_Rn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip
257
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Tp Fault: The monitoring of Converter 7 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 581 20611 ThyrFlt_Tp_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip
258
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Sn Fault: The monitoring of Converter 7 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 582 20612 ThyrFlt_Sn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 583 20613 FuseFlt_Rp_CCI7
Related parameters:
259
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 584 20614 FuseFlt_Tn_CCI7 - Converter redundancy fault Twin - Converter Trip
260
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 585 20615 FuseFlt_Sp_CCI7 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 586 20616 FuseFlt_Rn_CCI7 N-1 - Converter redundancy fault Twin - Converter Trip
261
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 587 20617 FuseFlt_Tp_CCI7 - Converter redundancy fault Twin - Converter Trip
262
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 588 20618 FuseFlt_Sn_CCI7 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 589 20619 TOCD_R_CCI7 N-1 - Converter alarm Twin - Converter alarm
263
ABB
Nr ID Name
----
Events
Further steps:
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 590 20620 TOCD_S_CCI7 N-1 - Converter alarm Twin - Converter alarm
264
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 591 20621 TOCD_T_CCI7 N-1 - Converter alarm Twin - Converter alarm
Default reaction: N-1 592 20622 UfOpCeil_CCI7 - Converter alarm Twin - Converter alarm
265
ABB
Nr ID Name
Events
CCI7. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 2
593
20623
DevTypeErr_CCI7
266
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
595
20625
LinkFault_CCI7
Further steps: - Check optical link cabling to CCI CCI7. Redundant Power 1 fail
Further steps: - Check cabling and power supply CCI7. Redundant Power 2 fail
Possible reasons: - Power supply fault at input 2 (X2:1-2) 597 20627 RedPwrFail2_CCI7 Default reaction: - Converter Redundancy Fault
Related parameters:
267
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CCI7. CPU Watchdog
599
20629
CPUWatchdog_CCI7
Further steps:
268
ABB
Nr ID Name
Events
- Reboot device
Description
600
20630
UfFreeze_CCI7
269
ABB
Nr ID Name
Events
Description
603
20633
USynFreeze_CCI7
Possible reasons: - Two or all three connections lost 604 20634 USynAllLost_CCI7
270
ABB
Nr ID Name
Events
Description
Further steps: - Check optical link cabling to AC 800PEC CCI7. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 606 20636 AdvFuseBlow_CCI7 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
271
ABB
Nr ID Name
Events
Description
607
20637
IConvOpCeil_CCI7
272
ABB
Nr ID Name
Events
CCI7. Cooling failure
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI7. Fan 1 Supply 1 fault
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters
273
ABB
Nr ID Name
Events
- Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
274
ABB
Nr ID Name
Events
CCI7. Fan 2 Supply 1 fault
Description
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI7. Fan 2 Supply 2 fault
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
613
20643
Fan2Supply2Flt_CCI7
Further steps:
275
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
Default reaction: - Converter Redundancy fault 614 20644 MCB1Fault_CCI7 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - replace fan (HW-schematic page 410) - re-check cabling CCI7. Fan Supply Miniature Circuit Breaker 2 fault
Possible reasons: - Fan 2 defective 615 20645 MCB2Fault_CCI7 Default reaction: - Converter Redundancy fault
Related parameters:
276
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 616 20646 ThyrTemp1Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
277
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 617 20647 ThyrTemp2Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
278
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI7. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 619 20649 ThyrTemp4Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
279
ABB
Nr ID Name
Events
Description
CCI7. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 620 20650 ThyrTemp5Lev1Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
280
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI7. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 622 20652 AirTemp1Lev1Flt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
281
ABB
Nr ID Name
Events
Description
CCI7. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Thyristor Rp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 624 20654 ThyrTemp1SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
282
ABB
Nr ID Name
Events
- Re-check sensor circuit
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 625 20655 ThyrTemp2SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
283
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 626 20656 ThyrTemp3SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI7. Thyristor Rn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 627 20657 ThyrTemp4SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
284
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 628 20658 ThyrTemp5SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI7. Thyristor Sn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 629 20659 ThyrTemp6SensFl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
285
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 630 20660 AirTemp1SensFlt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Re-check sensor circuit CCI7. Air Temperature 2 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 631 20661 AirTemp2SensFlt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
286
ABB
Nr ID Name
Events
CCI7. Snubber Switch fault
Description
Default reaction: N-1 632 20662 SnubberSwiFlt_CCI7 - Converter alarm TWIN - Converter Trip
287
ABB
Nr ID Name
Events
CCI7. Thyristor Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI7. Converter cabinet Door fault
Further steps: - Close converter cabinet door CCI7. Software Version fault
288
ABB
Nr ID Name
Events
Description
CCI7. NegConvFault_CCI7
Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration
Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
638
20668
PulseBlockFault_CCI7
289
ABB
Nr
640
ID
20670
Name
Event2_31_CCI7
Events
Description
641
20671
ThyrTemp1Lev2Fl_CCI7
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI7. Thyristor Tn Case Temperature above trip level
Default reaction: - Converter Trip 642 20672 ThyrTemp2Lev2Fl_CCI7 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
290
ABB
Nr ID Name
Events
Description
643
20673
ThyrTemp3Lev2Fl_CCI7
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
291
ABB
Nr ID Name
Events
Description
644
20674
ThyrTemp4Lev2Fl_CCI7
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI7. Thyristor Tp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
292
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
646
20676
ThyrTemp6Lev2Fl_CCI7
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
293
ABB
Nr ID Name
Events
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI7. Air Temperature 2 ( Air outlet chimney ) above fault level
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 648 20678 AirTemp2Lev2Flt_CCI7 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
294
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666
20679 20680 20681 20682 20683 20684 20685 20686 20687 20688 20689 20690 20691 20692 20693 20694 20695 20700
Event3_08_CCI7 Event3_09_CCI7 Event3_10_CCI7 Event3_11_CCI7 Event3_12_CCI7 Event3_13_CCI7 Event3_14_CCI7 Event3_15_CCI7 Event3_16_CCI7 Event3_17_CCI7 Event3_18_CCI7 Event3_19_CCI7 Event3_20_CCI7 Event3_21_CCI7 Event3_22_CCI7 Event3_23_CCI7 Event3_24_CCI7 Event3_25_CCI7
295
ABB
Nr
667 668 669 670 671 672
ID
20701 20702 20703 20704 20705 20706
Name
Event3_26_CCI7 Event3_27_CCI7 Event3_28_CCI7 Event3_29_CCI7 Event3_30_CCI7 Event3_31_CCI7
Events
Description
CCI8. Thyristor Rp Fault: The monitoring of Converter 8 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 673 20707 ThyrFlt_Rp_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip
296
ABB
Nr ID Name
Events
Description
CCI8. Thyristor Tn Fault: The monitoring of Converter 8 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 674 20708 ThyrFlt_Tn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip
297
ABB
Nr ID Name
Events
Description
CCI8. Thyristor Sp Fault: The monitoring of Converter 8 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 675 20709 ThyrFlt_Sp_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip
298
ABB
Nr ID Name
Events
Description
CCI8. Thyristor Rn Fault: The monitoring of Converter 8 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 676 20710 ThyrFlt_Rn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip
299
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Tp Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 677 20711 ThyrFlt_Tp_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip
300
ABB
Nr ID Name
Events
Description
CCI2. Thyristor Sn Fault: The monitoring of Converter 2 has detected a non conducting thyristor
Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time)
Default reaction: 678 20712 ThyrFlt_Sn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) 679 20713 FuseFlt_Rp_CCI8
Related parameters:
301
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 680 20714 FuseFlt_Tn_CCI8 - Converter redundancy fault Twin - Converter Trip
302
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 681 20715 FuseFlt_Sp_CCI8 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 682 20716 FuseFlt_Rn_CCI8 N-1 - Converter redundancy fault Twin - Converter Trip
303
ABB
Nr ID Name
Events
TFFDnumOfPeriods
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 683 20717 FuseFlt_Tp_CCI8 - Converter redundancy fault Twin - Converter Trip
304
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: N-1 684 20718 FuseFlt_Sn_CCI8 - Converter redundancy fault Twin - Converter Trip
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 685 20719 TOCD_R_CCI8 N-1 - Converter alarm Twin - Converter alarm
305
ABB
Nr ID Name
----
Events
Further steps:
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 686 20720 TOCD_S_CCI8 N-1 - Converter alarm Twin - Converter alarm
306
ABB
Nr ID Name
Events
Description
Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter)
Default reaction: 687 20721 TOCD_T_CCI8 N-1 - Converter alarm Twin - Converter alarm
Default reaction: N-1 688 20722 UfOpCeil_CCI8 - Converter alarm Twin - Converter alarm
307
ABB
Nr ID Name
Events
CCI8. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 8
689
20723
DevTypeErr_CCI8
308
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
691
20725
LinkFault_CCI8
Further steps: - Check optical link cabling to CCI CCI8. Redundant Power 1 fail
Further steps: - Check cabling and power supply CCI8. Redundant Power 2 fail
Possible reasons: - Power supply fault at input 2 (X2:1-2) 693 20727 RedPwrFail2_CCI8 Default reaction: - Converter Redundancy Fault
Related parameters:
309
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CCI8. CPU Watchdog
695
20729
CPUWatchdog_CCI8
Further steps:
310
ABB
Nr ID Name
Events
- Reboot device
Description
696
20730
UfFreeze_CCI8
311
ABB
Nr ID Name
Events
Description
699
20733
USynFreeze_CCI8
Possible reasons: - Two or all three connections lost 700 20734 USynAllLost_CCI8
312
ABB
Nr ID Name
Events
Description
Further steps: - Check optical link cabling to AC 800PEC CCI8. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses
Default reaction: - Converter Trip 702 20736 AdvFuseBlow_CCI8 Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown
313
ABB
Nr ID Name
Events
Description
703
20737
IConvOpCeil_CCI8
314
ABB
Nr ID Name
Events
CCI8. Cooling failure
Description
Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters
Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor CCI8. Fan 1 Supply 1 fault
Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters
315
ABB
Nr ID Name
Events
- Replace pressure sensor
Description
Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
316
ABB
Nr ID Name
Events
CCI8. Fan 2 Supply 1 fault
Description
Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters
Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor CCI8. Fan 2 Supply 2 fault
Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters
709
20743
Fan2Supply2Flt_CCI8
Further steps:
317
ABB
Nr ID Name
Events
- Replace fan
Description
- Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor
Default reaction: - Converter Redundancy fault 710 20744 MCB1Fault_CCI8 Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord
Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling CCI8. Fan Supply Miniature Circuit Breaker 2 fault
Possible reasons: - Fan 2 defective 711 20745 MCB2Fault_CCI8 Default reaction: - Converter Redundancy fault
Related parameters:
318
ABB
Nr ID Name
Events
Description
CCI8. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 712 20746 ThyrTemp1Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
319
ABB
Nr ID Name
Events
Description
CCI8. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 713 20747 ThyrTemp2Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
320
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI8. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 715 20749 ThyrTemp4Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
321
ABB
Nr ID Name
Events
Description
CCI8. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 716 20750 ThyrTemp5Lev1Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10 K)
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
322
ABB
Nr ID Name
Events
Description
- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
CCI8. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10 K)
Default reaction: - Converter alarm 718 20752 AirTemp1Lev1Flt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters
323
ABB
Nr ID Name
Events
Description
CCI8. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10 K)
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Thyristor Rp Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 720 20754 ThyrTemp1SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps:
324
ABB
Nr ID Name
Events
- Re-check sensor circuit
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 721 20755 ThyrTemp2SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
325
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 722 20756 ThyrTemp3SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - re-check sensor circuit CCI8. Thyristor Rn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 723 20757 ThyrTemp4SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
326
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 724 20758 ThyrTemp5SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Re-check sensor circuit CCI8. Thyristor Sn Case Temperature Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 725 20759 ThyrTemp6SensFl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
327
ABB
Nr ID Name
Events
Description
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 726 20760 AirTemp1SensFlt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Re-check sensor circuit CCI8. Air Temperature 2 Sensor fault
Possible reasons: - Sensor circuit open - Sensor circuit shorten >156 C < -13 C
Default reaction: - Converter alarm 727 20761 AirTemp2SensFlt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
328
ABB
Nr ID Name
Events
CCI8. Snubber Switch fault
Description
Default reaction: N-1 728 20762 SnubberSwiFlt_CCI8 - Converter alarm TWIN - Converter Trip
329
ABB
Nr ID Name
Events
CCI8. Thyristor Fuse fault
Description
Further steps: - Check and replace faulty thyristors - Check and replace blown fuses CCI8. Converter cabinet Door fault
Further steps: - Close converter cabinet door CCI8. Software Version fault
330
ABB
Nr ID Name
Events
Description
CCI8. NegConvFault_CCI8
Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration
Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive
734
20768
PulseBlockFault_CCI8
331
ABB
Nr
736
ID
20770
Name
Event2_31_CCI8
Events
Description
737
20771
ThyrTemp1Lev2Fl_CCI8
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI8. Thyristor Tn Case Temperature above trip level
Default reaction: - Converter Trip 738 20772 ThyrTemp2Lev2Fl_CCI8 Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas
Conv_ConverterModule1 \ EnaThyrTempMeas
332
ABB
Nr ID Name
Events
Description
739
20773
ThyrTemp3Lev2Fl_CCI8
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
333
ABB
Nr ID Name
Events
Description
740
20774
ThyrTemp4Lev2Fl_CCI8
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters CCI8. Thyristor Tp Case Temperature above trip level
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)
334
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
742
20776
ThyrTemp6Lev2Fl_CCI8
Conv_ConverterModule1 \ EnaThyrTempMeas
Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters
335
ABB
Nr ID Name
Events
Description
Conv_ConverterModule1 \ EnaCabinetTempMeas
Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters CCI8. Air Temperature 2 ( Air outlet chimney ) above fault level
Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working
Default reaction: - Converter alarm 744 20778 AirTemp2Lev2Flt_CCI8 Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas
Conv_ConverterModule1 \ EnaCabinetTempMeas
336
ABB
Nr ID Name
Events
- Clean air inlet filters
Description
745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762
20779 20780 20781 20782 20783 20784 20785 20786 20787 20788 20789 20790 20791 20792 20793 20794 20795 21000
Event3_08_CCI8 Event3_09_CCI8 Event3_10_CCI8 Event3_11_CCI8 Event3_12_CCI8 Event3_13_CCI8 Event3_14_CCI8 Event3_15_CCI8 Event3_16_CCI8 Event3_17_CCI8 Event3_18_CCI8 Event3_19_CCI8 Event3_20_CCI8 Event3_21_CCI8 Event3_22_CCI8 Event3_23_CCI8 Event3_24_CCI8 Event3_25_CCI8
337
ABB
Nr
763 764 765 766 767 768
ID
21001 21002 21003 21004 21005 21006
Name
Event3_26_CCI8 Event3_27_CCI8 Event3_28_CCI8 Event3_29_CCI8 Event3_30_CCI8 Event3_31_CCI8
Events
Description
Default reaction: - Trip 769 21007 OvrCurrInstFlt Related parameters: ProtOvercurrentMon \ Ifskal Ifinst InstDelay
Related parameters: ProtOvercurrentMon / Ifskal 770 21008 OvrCurrInvFlt Ifstart SelCurve k FixInvDelay ThermalDownTime
Further steps:
338
ABB
Nr ID Name
----
Events
Description
771
21009
PQProtFlt
Related parameters: Prot_PQMon \ Characteristic_QP10 Characteristic_QP08 Characteristic_QP06 Characteristic_QP04 Characteristic_QP02 Characteristic_QP00 DelayTime
339
ABB
Nr ID Name
Events
V/Hz Protection fault
Description
Possible reasons: - The machine voltage was higher than the V/Hz protection characteristic
772
21010
VHzProtFlt
Possible reasons: - Short circuit on DC side which was not possible to clear due to a 200ms pulse blocking period
773
21011
DCSCTrip
Prot_Protection \ EnableIConvMon
340
ABB
Nr ID Name
Events
EnableConvFaultDetection
Description
S800 Watchdog
Possible reasons: - Powerfail or FPGA freeze on other Channel detected 775 21013 OtherCHHWFlt Default reaction: - Immediate changeover to this channel
Related parameters:
341
ABB
Nr ID Name
----
Events
Description
Further steps: - Check power supply - Replace hardware Other Channel Link fault detected by AC 800PEC
Possible reasons: - Optical link cabling to other AC 800PEC interrupted (OM1 Link 1&2) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) 777 21015 OtherCHLinkFlt
Further steps:
342
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCM Backup Channel interrupted (OM1 Link 3) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
778
21016
BUCHLinkFlt
343
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCM interrupted (OM1 Link 4) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
779
21017
CCMLinkFlt
Further steps: - Check optical link cabling to CCM Other Channel Software version fault
344
ABB
Nr ID Name
Events
Description
Further steps: - Download required software version CCM Software version fault
Further steps: - Download required software version Other Channel Redundant Link 1 Address Error Link fault detected by AC 800PEC
Possible reasons: - Optical link cabling to other AC 800PEC connected to wrong optical port (Link 1 to Link 1 ) - CCM Hex switch setting not correct
783
21021
OtherCHAddrErr1
345
ABB
Nr ID Name
----
Events
Related parameters:
Description
Other Channel Redundant Link 2 Address Error Link fault detected by AC 800PEC
Possible reasons: - Optical link cabling to other AC 800PEC connected to wrong optical port (OM1 Link 2 to OM1 Link 2 ) - CCM Hex switch setting not correct
784
21022
OtherCHAddrErr2
Further steps: - Check optical link cabling to other channel Backup Channel Address Error
785
21023
BUCHAddressErr
346
ABB
Nr ID Name
----
Events
Further steps:
Description
Further steps: ---Other Channel Device Type Error on Redundant Link 1 Device Type Error detected by AC 800PEC
Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 1) - Wrong installer archive loaded to other AC 800PEC
787
21025
OtherCHDevType1
347
ABB
Nr ID Name
Events
Description
Other Channel Device Type Error on Redundant Link 2 Device Type Error detected by AC 800PEC
Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 2) - Wrong installer archive loaded to other AC 800PEC
788
21026
OtherCHDevType2
Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 3) - Wrong installer archive loaded to CCM BU
Default reaction: 789 21027 BUDevTypeErr - Channel to back-up link loss - Alarm
348
ABB
Nr ID Name
Events
CCM Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 4) - Wrong installer archive loaded to CCM 1
790
21028
CCMDevTypeErr
Possible reasons: - Internal power fail on AC 800PEC - Both power supply inputs are missing
Default reaction: 791 21029 PowerFail - channel fault, if possible channel transfer
349
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CCM Redundant Power 1 fail
Further steps: - Check cabling and power supply Backup CCM Redundant Power 2 fail
794
21032
BURedPwrFail2
350
ABB
Nr ID Name
Events
Further steps:
Description
Further steps: - Check cabling and power supply BU Precision Power fail
Possible reasons: - Internal power fail on CCM - BU - Both power supply inputs are missing
351
ABB
Nr ID Name
Events
CCM Precision Power fail
Description
Possible reasons: - Internal power fail on CCM - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CPU Watchdog
352
ABB
Nr ID Name
Events
Description
Further steps: - Reboot device - Download installer archive - Replace board CCM CPU Watchdog
353
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI1 interrupted (OM2 Link 1) - CCI1 CPU failure - Internal power fail on CCI1 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI1 - Wrong HEX Switch setting at CCI1 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 801 21039 CCI1Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match converter configuration
Related parameters: - Verify the listing together with the individual events
354
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI2 interrupted (OM2 Link 1) - CCI2 CPU failure - Internal power fail on CCI2 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI2 - Wrong HEX Switch setting at CCI2 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 802 21040 CCI2Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 2 signal of Converter I/O does not match to converter configuration
Related parameters: - Verify the listing together with the individual events
355
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI3 interrupted (OM2 Link 1) - CCI3 CPU failure - Internal power fail on CCI3 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI3 - Wrong HEX Switch setting at CCI3 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 803 21041 CCI3Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration
Related parameters: - Verify the listing together with the individual events
356
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI4 interrupted (OM2 Link 1) - CCI4 CPU failure - Internal power fail on CCI4 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI4 - Wrong HEX Switch setting at CCI4 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 804 21042 CCI4Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration
Related parameters: - Verify the listing together with the individual events
357
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI5 interrupted (OM2 Link 1) - CCI5 CPU failure - Internal power fail on CCI5 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI5 - Wrong HEX Switch setting at CCI5 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 805 21043 CCI5Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration
Related parameters: - Verify the listing together with the individual events
358
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI6 interrupted (OM2 Link 1) - CCI6 CPU failure - Internal power fail on CCI6 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI6 - Wrong HEX Switch setting at CCI6 - Insufficient converter cooling - Overtemerature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 806 21044 CCI6Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration
Related parameters: - Verify the listing together with the individual events
359
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI7 interrupted (OM2 Link 1) - CCI7 CPU failure - Internal power fail on CCI7 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI7 - Wrong HEX Switch setting at CCI7 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 807 21045 CCI7Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration
Related parameters: - Verify the listing together with the individual events
360
ABB
Nr ID Name
Events
Description
Possible reasons: - Optical link cabling to CCI8 interrupted (OM2 Link 1) - CCI8 CPU failure - Internal power fail on CCI8 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI8 - Wrong HEX Switch setting at CCI8 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) 808 21046 CCI8Trip - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration
Related parameters: - Verify the listing together with the individual events
361
ABB
Nr ID Name
Events
CCI1 Redundancy fault
Description
Possible reasons: - Power supply fault at CCI1 input 1 (X1:1-2) - Power supply fault at CCI1 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 809 21047 CCI1RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Power supply fault at CCI2 input 1 (X1:1-2) - Power supply fault at CCI2 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 810 21048 CCI2RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
362
ABB
Nr ID Name
Events
CCI3 Redundancy fault
Description
Possible reasons: - Power supply fault at CCI3 input 1 (X1:1-2) - Power supply fault at CCI3 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 811 21049 CCI3RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Power supply fault at CCI4 input 1 (X1:1-2) - Power supply fault at CCI4 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 812 21050 CCI4RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
363
ABB
Nr ID Name
Events
CCI5 Redundancy fault
Description
Possible reasons: - Power supply fault at CCI5 input 1 (X1:1-2) - Power supply fault at CCI5 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 813 21051 CCI5RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Power supply fault at CCI6 input 1 (X1:1-2) - Power supply fault at CCI6 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 814 21052 CCI6RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
364
ABB
Nr ID Name
Events
CCI7 Redundancy fault
Description
Possible reasons: - Power supply fault at CCI7 input 1 (X1:1-2) - Power supply fault at CCI7 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 815 21053 CCI7RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Power supply fault at CCI8 input 1 (X1:1-2) - Power supply fault at CCI8 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault 816 21054 CCI8RedFault Default reaction: - Redundancy Fault
Related parameters: - Verify the listing together with the individual events
365
ABB
Nr ID Name
Events
CCI1 Alarm
Description
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 817 21055 CCI1Alarm - Converter cabinet door open - Wrong SW version
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air 818 21056 CCI2Alarm - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version
366
ABB
Nr ID Name
Events
Related parameters:
Description
CCI3 Alarm
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 819 21057 CCI3Alarm - Converter cabinet door open - Wrong SW version
Related parameters: - Verify the listing together with the individual events
367
ABB
Nr ID Name
Events
CCI4 Alarm
Description
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 820 21058 CCI4Alarm - Converter cabinet door open - Wrong SW version
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) 821 21059 CCI5Alarm - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version
368
ABB
Nr ID Name
Events
Related parameters:
Description
CCI6 Alarm
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 822 21060 CCI6Alatm - Converter cabinet door open - Wrong SW version
Related parameters: Verify the listing together with the individual events
369
ABB
Nr ID Name
Events
CCI7 Alarm
Description
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) 823 21061 CCI7Alarm - Converter cabinet door open - Wrong SW version
Related parameters: Verify the listing together with the individual events
Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air 824 21062 CCI8Alarm - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version
370
ABB
Nr ID Name
Events
Related parameters:
Description
Possible reasons: - Operation amplifier blocked at ceiling level 826 21064 PTMonOpampCeil
371
ABB
Nr ID Name
Events
Description
827
21065
PTMonADCFreeze
372
ABB
Nr ID Name
Events
Description
Possible reasons: - Operation amplifier blocked (frozen) - ADC failure 831 21069 CTMonADCFreeze Default reaction: - Auto fault
373
ABB
Nr ID Name
Events
Description
Possible reasons: - One connection lost (if only two CT-measurement circuits are used)
Possible reasons: - Optical link cabling to CIO1 interrupted (Link 1) - CIO1 CPU failure - Internal power fail on CIO1 833 21071 CIO1Trip - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO1 - Wrong HEX Switch setting at CIO1
Related parameters:
374
ABB
Nr ID Name
Events
Description
CIO2 Trip
Possible reasons: - Optical link cabling to CIO2 interrupted (Link 3) - CIO2 CPU failure - Internal power fail on CIO2 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO2 834 21072 CIO2Trip - Wrong HEX Switch setting at CIO2
Related parameters: - Verify the listing together with the individual events
375
ABB
Nr ID Name
Events
CIO3 Trip
Description
Possible reasons: - Optical link cabling to CIO3 interrupted (Link 1) - CIO3 CPU failure - Internal power fail on CIO3 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO3 835 21073 CIO3Trip - Wrong HEX Switch setting at CIO3
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Optical link cabling to CIO4 interrupted (Link 3) - CIO4 CPU failure - Internal power fail on CIO4 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO4 836 21074 CIO4Trip - Wrong HEX Switch setting at CIO4
Related parameters: - Verify the listing together with the individual events
376
ABB
Nr ID Name
Events
CIO5 Trip
Description
Possible reasons: - Optical link cabling to CIO5 interrupted (Link 1) - CIO5 CPU failure - Internal power fail on CIO5 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO5 837 21075 CIO5Trip - Wrong HEX Switch setting at CIO5
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Optical link cabling to CIO6 interrupted (Link 3) - CIO6 CPU failure - Internal power fail on CIO6 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO6 838 21076 CIO6Trip - Wrong HEX Switch setting at CIO6
Related parameters: - Verify the listing together with the individual events
377
ABB
Nr ID Name
Events
CIO7 Trip
Description
Possible reasons: - Optical link cabling to CIO7 interrupted (Link 1) - CIO7 CPU failure - Internal power fail on CIO7 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO7 839 21077 CIO7Trip - Wrong HEX Switch setting at CIO7
Related parameters: - Verify the listing together with the individual events
Possible reasons: - Optical link cabling to CIO8 interrupted (Link 3) - CIO8 CPU failure - Internal power fail on CIO8 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO8 840 21078 CIO8Trip - Wrong HEX Switch setting at CIO8
Related parameters: - Verify the listing together with the individual events
378
ABB
Nr ID Name
Events
CIO1 Redundancy fault
Description
Possible reasons: - Power supply fault at CIO1 input 1 (X1:1-2) - Power supply fault at CIO1 input 2 (X2:3-4)
841
21079
CIO1RedFault
Further steps: - Check cabling and power supply CIO2 Redundancy fault
Possible reasons: - Power supply fault at CIO2 input 1 (X1:1-2) - Power supply fault at CIO2 input 2 (X2:3-4)
842
21080
CIO2RedFault
Further steps: - Check cabling and power supply CIO3 Redundancy fault
Possible reasons: - Power supply fault at CIO3 input 1 (X1:1-2) 843 21081 CIO3RedFault - Power supply fault at CIO3 input 2 (X2:3-4)
379
ABB
Nr ID Name
Events
Related parameters:
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Power supply fault at CIO4 input 1 (X1:1-2) - Power supply fault at CIO4 input 2 (X2:3-4)
844
21082
CIO4RedFault
Further steps: - Check cabling and power supply CIO5 Redundancy fault
Possible reasons: - Power supply fault at CIO5 input 1 (X1:1-2) - Power supply fault at CIO5 input 2 (X2:3-4)
845
21083
CIO5RedFault
380
ABB
Nr ID Name
Events
CIO6 Redundancy fault
Description
Possible reasons: - Power supply fault at CIO6 input 1 (X1:1-2) - Power supply fault at CIO6 input 2 (X2:3-4)
846
21084
CIO6RedFault
Further steps: - Check cabling and power supply CIO7 Redundancy fault
Possible reasons: - Power supply fault at CIO7 input 1 (X1:1-2) - Power supply fault at CIO7 input 2 (X2:3-4)
847
21085
CIO7RedFault
Further steps: - Check cabling and power supply CIO8 Redundancy fault
Possible reasons: - Power supply fault at CIO8 input 1 (X1:1-2) 848 21086 CIO8RedFault - Power supply fault at CIO8 input 2 (X2:3-4)
381
ABB
Nr ID Name
Events
Related parameters:
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
CIO1 Alarm
Possible reasons: - Wrong SW version on CIO1 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)
Related parameters: Meas_CIO1 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 849 21087 CIO1Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
382
ABB
Nr ID Name
Events
CIO2 Alarm
Description
Possible reasons: - Wrong SW version on CIO2 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)
Related parameters: Meas_CIO2 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 850 21088 CIO2Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
383
ABB
Nr ID Name
Events
CIO3 Alarm
Description
Possible reasons: - Wrong SW version on CIO3 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)
Related parameters: Meas_CIO3 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 851 21089 CIO3Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
384
ABB
Nr ID Name
Events
CIO4 Alarm
Description
Possible reasons: - Wrong SW version on CIO4 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)
Related parameters: Meas_CIO4 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 852 21090 CIO4Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
385
ABB
Nr ID Name
Events
CIO5 Alarm
Description
Possible reasons: - Wrong SW version on CIO5 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)
Related parameters: Meas_CIO5 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 853 21091 CIO5Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
386
ABB
Nr ID Name
Events
CIO6 Alarm
Description
Possible reasons: - Wrong SW version on CIO6 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800)
Related parameters: Meas_CIO6 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 854 21092 CIO6Alatm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
387
ABB
Nr ID Name
Events
CIO7 Alarm
Description
Possible reasons: - Wrong SW version on CIO7 - Temperature sensor fault at CIO temerature input 1,2 or 3 (X800)
Related parameters: Meas_CIO7 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 855 21093 CIO7Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
388
ABB
Nr ID Name
Events
CIO8 Alarm
Description
Possible reasons: - Wrong SW version on CIO8 - Temperature sensor fault at CIO temerature input 1,2 or 3 (X800)
Related parameters: Meas_CIO8 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection 856 21094 CIO8Alarm EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq
Possible reasons: - Defective I/O section on CCM Board - Wiring faults 857 21095 SmallIODev_CH Default reaction: - Alarm
389
ABB
Nr ID Name
Events
Description
Further steps: - Check wiring - Replace device Other Channel Channel fault
Further steps:
390
ABB
Nr ID Name
Events
- Check other channel
Description
Further steps: - Check Back-up channel Automatic channel transfer occurred. (Channel transfer not forced by the user)
Possible reasons: - CCM link fault - CCM Address error - CCM device type error - AC 800PEC Power fail 861 21099 CHXferFlt - CCM Power fail - CCM CPU watchdog - AC 800PEC CPU watchdog - CCM link fault - CIO config word fault - Manual fault in manual mode - Auto and manual mode fault
391
ABB
Nr ID Name
----
Events
Default reaction:
Description
865
21103
EFRStage1Flt
Prot_Protection \ EnaEarthFaultMon
392
ABB
Nr ID Name
Events
Description
866
21104
EFRStage2Flt
Prot_Protection \ EnaEarthFaultMon
Possible reasons: - Serial link to device IRDH275 is disturbed - Link to selected CIO failed
Default reaction: - Alarm 867 21105 EFRCommFlt Related parameters: Prot_EarthFaultMon \ SelectIRDH275 SelectCIO
Prot_Protection \ EnaEarthFaultMon
393
ABB
Nr ID Name
Events
Field-flashing timeout
Description
Possible reasons: - Field Flashing breaker was closed for a longer time than expected
Possible reasons: - The overall excitation starting time was longer than the supervision time - Converter electronics was not able to fire thyristors
394
ABB
Nr ID Name
Events
Description
395
ABB
Nr ID Name
Events
Description
Possible reasons: - Aux not ready input (CIO1 DI09 activated) - Aux ready input (CIO3 DI06 not activated)
396
ABB
Nr ID Name
Events
Field Bus External Trip
Description
Possible reasons: - Trip via fieldbus. Fieldbus control word Bit 2 (Bits 015) - Bit 2 is logic zero
874
21112
FieldBusExtTrip
Further steps: ---Converter Redundancy Stage fault level 1 More thyristors in the same branch as defined with stage level parameter are not conducting
Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors 875 21113 ConvRed1Flt - Blocked CCI
397
ABB
Nr ID Name
Events
Description
Converter Redundancy Stage fault level 2 More thyristors in the same branch as defined with stage level parameter are not conducting
Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors 876 21114 ConvRed2Flt - Blocked CCI
Further steps: ---Converter Redundancy Stage fault level 3 More thyristors in the same branch as defined with stage level parameter are not conducting
Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's 877 21115 ConvRed3Flt - Defective pulse amplifiers - Blocked Thyristors - Blocked CCI
398
ABB
Nr ID Name
Events
Description
Converter Redundance Stage fault level 4 More thyristors in the same branch as defined with stage level parameter are not conducting
Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors 878 21116 ConvRed4Flt - Blocked CCI
399
ABB
Nr ID Name
Events
Description
400
ABB
Nr ID Name
Events
Description
Possible reasons: - The field overvoltage protection (crowbar) was responding to a positive or negative field overvoltage - Negative field overvoltage occurs if an interruption occurs in the power supply or field circuit
881
21119
CrowbarOVFlt
Further steps: - Check whether there is (or has been) a problem with the generator. If not, report the problem to ABB. - Check the function of the field breaker at the input or output of the converter. - Check connection line and insulation resistance of the field winding. - Check Positive field overvoltage, this error is usually caused by a generator fault, which induces negative field current, such as pole slip, short circuit at the generator terminals etc.
401
ABB
Nr ID Name
Events
Description
Possible reasons: - UNITROL 6000 monitors the rotor temperature, which is calculated from the excitation current, excitation voltage and the resulting field resistance. Alarm is triggered if this value exceeds the set temperature.
Further steps: - Check whether the rotor has been overloaded for a long time and whether the rotor cooling system is working properly.
402
ABB
Nr ID Name
Events
Description
Possible reasons: - UNITROL 6000 monitors the rotor temperature, which is calculated from the excitation current, excitation voltage and the resulting field resistance. Alarm is triggered if this value exceeds the set temperature.
Further steps: - Check whether the rotor has been overloaded for a long time and whether the rotor cooling system is working properly. 884 885 886 887 888 21122 21123 21124 21125 21126 Event4_19 Event4_20 Event4_21 Event4_22 Event4_23
403
ABB
Nr ID Name
Events
Description
Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working
Default reaction: - Alarm 889 21127 LocalCTOPCFlt Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime
Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT Remote CT1 OPC Communication fault
Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective
890
21128
RemCT1OPCFlt
404
ABB
Nr ID Name
Events
Description
Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective
Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT
405
ABB
Nr ID Name
Events
Description
Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective
Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT Remote CT4 OPC Communication fault
Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective
893
21131
RemCT4OPCFlt
406
ABB
Nr ID Name
Events
- Check OPC server
Description
Block Startup
Possible reasons: - Converter CTs not connected - CSI defective 895 21133 ManFailExcOn - CCI defective
Related parameters:
407
ABB
Nr ID Name
Events
Description
Prot_Protection \ EnaIfExcOnMon
Default reaction: - Alarm 896 21134 FBCommFlt - Release of the Fieldbus operation request
897
21135
ExcTrTmpFlt1
408
ABB
Nr ID Name
Events
EnaTemp1 EnaTemp2 EnaTemp3
Description
898
21136
ExcTrTmpFlt2
409
ABB
Nr ID Name
Events
Description
Possible reasons: - Circuit to sensor open - Level 2 picked up without level 1 alive - Level 1 and 2 picked up within 100 ms
Default reaction: - Alarm 899 21137 ExcTrSensorFlt Related parameters: ExcTrafoMon \ dTdtDetectLevel EnableExcTrafoMon EnaTemp1 EnaTemp2 EnaTemp3
Possible reasons: - Digital input "Oil Level in excitation transformer below limit" activated
410
ABB
Nr ID Name
Events
Description
Possible reasons: - Digital input "Oil Level in excitation transformer above limit " activated
Possible reasons: - Digital input "Oil temperature in excitation transformer above limit 1" activated
Possible reasons: - Digital input "Oil temperature in excitation transformer above limit 2" activated 903 21141 ExcTrOilTmpFlt2 Default reaction: - Trip
411
ABB
Nr ID Name
Events
Description
Possible reasons: - Digital input "Excitation Transformer Buchholz fault 1" activated
Possible reasons: - Digital input "Excitation Transformer Buchholz fault 2" activated
412
ABB
Nr ID Name
Events
Description
Default reaction: - Alarm 906 21144 PSU1ICU1Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU1ICU1 \ SourceConfigWord
Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V80 Source 2 Fault
Default reaction: - Alarm 907 21145 PSU1ICU1Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU1ICU1 \ SourceConfigWord
413
ABB
Nr ID Name
Events
Description
Default reaction: - Alarm 908 21146 PSU1ICU1Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU1ICU1 \ SourceConfigWord
Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V80 Signal Fault
Prot_PSU1ICU1 \ SourceConfigWord
414
ABB
Nr ID Name
Events
Description
Possible reasons: - See corresponding hardware diagram - APD +ER-Q801 or +ER-Q802 defective - Monitoring line to I/O board interrupted
Prot_PSU1APDGrp1 \ Enable
Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 1 Fault
Default reaction: - Alarm 911 21149 PSU1ICU2Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU1ICU2 \ SourceConfigWord
415
ABB
Nr ID Name
Events
Description
Default reaction: - Alarm 912 21150 PSU1ICU2Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU1ICU2 \ SourceConfigWord
Further steps: ---Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 3 Fault
Default reaction: - Alarm 913 21151 PSU1ICU2Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU1ICU2 \ SourceConfigWord
416
ABB
Nr ID Name
Events
Description
Prot_PSU1ICU2 \ SourceConfigWord
Possible reasons: - See corresponding hardware diagram - APD +ER-Q801 or +ER-Q802 defective - Monitoring line to I/O board interrupted
Prot_PSU1APDGrp2 \ Enable
417
ABB
Nr ID Name
Events
Description
Default reaction: - Alarm 916 21154 PSU2ICU1Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU2ICU1 \ SourceConfigWord
Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V80 Source 2 Fault
Default reaction: - Alarm 917 21155 PSU2ICU1Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU2ICU1 \ SourceConfigWord
418
ABB
Nr ID Name
Events
Description
Default reaction: - Alarm 918 21156 PSU2ICU1Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU2ICU1 \ SourceConfigWord
Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V80 Signal Fault
Prot_PSU2ICU1 \ SourceConfigWord
419
ABB
Nr ID Name
Events
Description
Possible reasons: - See corresponding hardware diagramm - APD +EE-Q801 or +EE-Q802 or +EE-Q803 defective - Monitoring line to I/O board interrupted
Prot_PSU2APDGrp1 \ Enable
Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 1 Fault
Default reaction: - Alarm 921 21159 PSU2ICU2Src1Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU2ICU2 \ SourceConfigWord
420
ABB
Nr ID Name
Events
Description
Default reaction: - Alarm 922 21160 PSU2ICU2Src2Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU2ICU1 \ SourceConfigWord
Further steps: ---Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 3 Fault
Default reaction: - Alarm 923 21161 PSU2ICU2Src3Flt Related parameters: Prot_Protection \ EnablePowerSupplyMon
Prot_PSU2ICU2 \ SourceConfigWord
421
ABB
Nr ID Name
Events
Description
Prot_PSU2ICU2 \ SourceConfigWord
Possible reasons: - See corresponding hardware diagram - APD +EE-Q811 or +EE-Q812 or +EE-Q813 defective - Monitoring line to I/O board interrupted
Prot_PSU2APDGrp2 \ Enable
422
ABB
Nr ID Name
Events
CIT software version fault
Description
Possible reasons: - The downloaded CIT software version is not compatible with M/S software version
Possible reasons: - One or both analog input signals for the DE/NDE temperature signals are below the supervision level
423
ABB
Nr ID Name
Events
ColdgasAnaInFlt
Description
Possible reasons: - One or both analog input signals for the DE/NDE temperature signals are below the supervision level
Possible reasons: - Channel 1 and Channel 2 are indicated as the active one after start-up
Default reaction: - Alarm 929 21167 PreSelectionFlt - none channel is starting as the active one
424
ABB
Nr ID Name
Events
Description
931
21169
DCSCBlockPulses
425
ABB
Nr ID Name
Events
TFCDthreshold
Description
ExtSCReleaseFaultClearing
932
21170
IntSCAlphaMin
426
ABB
Nr ID Name
Events
Internal Short-Circuit
Description
933
21171
IntSCTrip
Possible reasons: - All 3 Phases measure less than 5% voltage and at the same time more than 140% current
934
21172
GenSC3Phase
427
ABB
Nr ID Name
Events
Description
Possible reasons: - One or two Phases measure less than 5% voltage and at the same time more than 140% current
935
21173
GenSC2Phase
Possible reasons: - All 3 Phases measure less than 80% voltage and at the same time more than 120% current
936
21174
DistantSC3Phase
428
ABB
Nr ID Name
Events
Description
Possible reasons: - One or two Phases measure less than 80% voltage and at the same time more than 120% current
937
21175
DistantSC2Phase
Further steps: ---Any Short-Circuit deteced This signal is followed by a signal of the range 21165 . . .21168 to get better information
Possible reasons: - High current and at the same time a low voltage detected
938
21176
AnySC
429
ABB
Nr ID Name
Events
Description
Default reaction: 940 21178 CTOvercurrent - Alarm - Blocking of single phase CT-Monitoring
Possible reasons: - The active channel is faulty and there is no possibility to transfer to another channel
Possible reasons: - There is a Manual Fault while the Unit is running in Manual Mode 942 21180 MANFltinMAN Default reaction: - Channel fault
Related parameters:
430
ABB
Nr ID Name
----
Events
Description
Possible reasons: - Auto Mode as well as Manual Mode of the same channel are faulty
Possible reasons: - Check the Event List regarding event numbers 20700 to 20795
431
ABB
Nr ID Name
Events
Converter configuration fault
Description
Possible reasons: - ConverterSystemConfigWord <1 or >8 - ConverterSystemConfigWord not equal to 2 and parameter EnableColdStandby = True - ConverterNegCurrConfigWord =1 and parameter EnableColdStandby = True
945
21183
ConverterCfgFlt
432
ABB
Nr ID Name
Events
IO configuration fault
Description
948
23410
IntSCDet
433
ABB
Nr ID Name
Events
Description
Possible reasons: - Opt cabling interrupted - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
949
21188
OtherCHLink1Flt
Further steps: - Check optical link cabling to other channel Other Channel Redundant Link 2 Fault.
Possible reasons: - Opt cabling interrupted - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
950
21189
OtherCHLink2Flt
434
ABB
Nr ID Name
Events
Description
Further steps: - Reboot device - Download installer archive - Replace board Other Channel Power Fail
Possible reasons: - Internal power fail on AC 800PEC of other channel - Both power supply inputs are missing
435
ABB
Nr ID Name
Events
External Trip
Description
Further steps: ---Hot-startup fault. Channel started after: Channel fault, reset manual as soon as the Regulator deviation between channel 1 and channel 2 is zero
Possible reasons: -
957
21193
HotStartUpFlt
Default reaction: -
Further steps: ---Hardware Fault on this channel detected by the Other Channel or the Backup Channel
Related parameters:
436
ABB
Nr ID Name
----
Events
Description
Possible reasons: -
Possible reasons: -
437
ABB
Nr ID Name
Events
Description
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
961
21197
FCB1Off1CoilFlt
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
962
21198
FCB1Off2CoilFlt
438
ABB
Nr ID Name
Events
Description
Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time
Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.
964
21200
FCB1TurnOnFlt
439
ABB
Nr ID Name
Events
Description
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
965
21201
FCB1TurnOffFlt
Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil)
966
21202
FCB1ManOffFlt
440
ABB
Nr ID Name
Events
Isolator 1 Turn-On Fault
Description
Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.
967
21203
Iso1lTurnOnFlt
Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing.
968
21204
Iso1lTurnOffFlt
441
ABB
Nr ID Name
Events
Description
Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time
Possible reasons: - The Isolator was opened manually when it was on-load
442
ABB
Nr ID Name
Events
Description
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
971
21207
FCB2Off1CoilFlt
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
972
21208
FCB2Off2CoilFlt
443
ABB
Nr ID Name
Events
Description
Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time
Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.
974
21210
FCB2TurnOnFlt
444
ABB
Nr ID Name
Events
Description
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
975
21211
FCB2TurnOffFlt
Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil)
976
21212
FCB2ManOffFlt
445
ABB
Nr ID Name
Events
Isolator 2 Turn-On Fault
Description
Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.
977
21213
Iso2lTurnOnFlt
Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing.
978
21214
Iso2lTurnOffFlt
446
ABB
Nr ID Name
Events
Description
Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time
Possible reasons: - The Isolator was opened manually when it was on-load
447
ABB
Nr ID Name
Events
Description
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
981
21217
FCB3Off1CoilFlt
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
982
21218
FCB3Off2CoilFlt
448
ABB
Nr ID Name
Events
Description
Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time
Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.
984
21220
FCB3TurnOnFlt
449
ABB
Nr ID Name
Events
Description
Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing.
985
21221
FCB3TurnOffFlt
Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil)
986
21222
FCB3ManOffFlt
450
ABB
Nr ID Name
Events
Isolator 3 Turn-On Fault
Description
Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing.
987
21223
Iso3lTurnOnFlt
Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing.
988
21224
Iso3lTurnOffFlt
451
ABB
Nr ID Name
Events
Description
Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time
Possible reasons: - The Isolator was opened manually when it was on load
Further steps: ---991 21227 FCBNotChgdFlt Field Circuit Breaker not charged fault
452
ABB
Nr ID Name
Events
Description
Possible reasons: - Too high synchronous voltage, generator voltage or field current while excitation start with fire all thyristors
Further steps: ---993 994 995 996 997 998 999 1'000 1'001 1'002 1'003 1'004 1'005 1'006 1'007 1'008 1'009 1'010 1'011 1'012 1'013 1'014 1'015 1'016 1'017 1'018 1'019 1'020 1'021 1'022 1'023 1'024 21229 21230 21231 21232 21233 21234 21235 21236 21237 21238 21239 21240 21241 21242 21243 21244 21245 21246 21247 21248 21249 21250 21251 21252 21253 21254 21255 22000 22001 22002 22003 22004 Event8_00 Event8_01 Event8_02 Event8_03 Event8_04 Event8_05 Event8_06 Event8_07 Event8_08 Event8_09 Event8_10 Event8_11 Event8_12 Event8_13 Event8_14 Event8_15 Event8_16 Event8_17 Event8_18 Event8_19 Event8_20 Event8_21 Event8_22 Event8_23 Event8_24 Event8_25 Event8_26 Event8_27 Event8_28 Event8_29 Event8_30 Event8_31
453
ABB
Nr ID Name
Events
CIO1. Link Fault
Description
Possible reasons: - Optical link cabling to CIO interrupted (OM2 Link 5) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
1'025
22005
LinkFault_CIO1
Further steps: - Check optical link cabling to CIO CIO1. Redundant Power fail 1
Further steps: - Check cabling and power supply CIO1. Redundant Power fail 2
Possible reasons: - Power supply fault at input 2 (X2:3-4) 1'027 22007 RedPwrFail2_CIO1 Default reaction: - Redundancy Fault
Related parameters:
454
ABB
Nr ID Name
Events
Description
Prot_PowerSupplyMon \ EnableRedundantSupply
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
Further steps: - Check cabling and power supply - Replace board CIO1. CPU Watchdog
1'029
22009
CPUWatchdog_CIO1
Further steps:
455
ABB
Nr ID Name
Events
- Reboot device
Description
456
ABB
Nr ID Name
Events
CIO1. Device Type Error
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 5) - Wrong installer archive loaded to CIO
1'032
22012
DevTypeErr_CIO1
Further steps: - Check optical link cabling to CIO CIO1 Digital IO deviation between IO's of Channel 1 and Channel 2
457
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'034
22014
Temp1SnsFlt_CIO1
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'035
22015
Temp2SnsFlt_CIO1
458
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'036
22016
Temp3SnsFlt_CIO1
Further steps: ---1'037 1'038 1'039 1'040 1'041 1'042 1'043 1'044 1'045 1'046 1'047 1'048 1'049 1'050 1'051 1'052 1'053 22017 22018 22019 22020 22021 22022 22023 22024 22025 22026 22027 22028 22029 22030 22031 22100 22101 Event1_12_CIO1 Event1_13_CIO1 Event1_14_CIO1 Event1_15_CIO1 Event1_16_CIO1 Event1_17_CIO1 Event1_18_CIO1 Event1_19_CIO1 Event1_20_CIO1 Event1_21_CIO1 Event1_22_CIO1 Event1_23_CIO1 Event1_24_CIO1 Event1_25_CIO1 Event1_26_CIO1 Event1_27_CIO1 Event1_28_CIO1
459
ABB
Nr
1'054 1'055 1'056
ID
22102 22103 22104
Name
Event1_29_CIO1 Event1_30_CIO1 Event1_31_CIO1
Events
Description
Possible reasons: - Optical link cabling to CIO1 interrupted (OM6 Link 3) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt)
1'057
22105
LinkFault_CIO2
Further steps: - Check optical link cabling to CIO CIO2. Redundant Power fail 1
460
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CIO2. Precision Power fail
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
461
ABB
Nr ID Name
Events
CIO2. CPU Watchdog
Description
Further steps: - Reboot device - Download installer archive - Replace board CIO2. Software Version fault
462
ABB
Nr ID Name
Events
CIO2. Address Error
Description
Further steps: - Check Hex-Swtich setting on CIO CIO2. Device Type Error
Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO
1'064
22112
DevTypeErr_CIO2
Further steps: - Check optical link cabling to CIO CIO2. Digital IO deviation between IO's of Channel 1 and Channel 2
Possible reasons: - Defective I/O section on CIO Board - Wiring faults 1'065 22113 SigConsistFlt_CIO2 Default reaction: - Alarm
463
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'066
22114
Temp1SnsFlt_CIO2
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'067 22115 Temp2SnsFlt_CIO2 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
464
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'068
22116
Temp3SnsFlt_CIO2
Further steps: ---1'069 1'070 1'071 1'072 1'073 1'074 1'075 1'076 1'077 22117 22118 22119 22120 22121 22122 22123 22124 22125 Event1_12_CIO2 Event1_13_CIO2 Event1_14_CIO2 Event1_15_CIO2 Event1_16_CIO2 Event1_17_CIO2 Event1_18_CIO2 Event1_19_CIO2 Event1_20_CIO2
465
ABB
Nr
1'078 1'079 1'080 1'081 1'082 1'083 1'084 1'085 1'086 1'087 1'088
ID
22126 22127 22128 22129 22130 22131 22200 22201 22202 22203 22204
Name
Event1_21_CIO2 Event1_22_CIO2 Event1_23_CIO2 Event1_24_CIO2 Event1_25_CIO2 Event1_26_CIO2 Event1_27_CIO2 Event1_28_CIO2 Event1_29_CIO2 Event1_30_CIO2 Event1_31_CIO2
Events
Description
Further steps: - Check optical link cabling to CIO CIO3. Redundant Power fail 1
Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'090 22206 RedPwrFail1_CIO3
466
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CIO3. Precision Power fail
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
467
ABB
Nr ID Name
Events
CIO3. CPU Watchdog
Description
Further steps: - Reboot device - Download installer archive - Replace board CIO3. Software Version fault
468
ABB
Nr ID Name
Events
CIO3. Address Error
Description
Further steps: - Check Hex-Swtich setting on CIO CIO3. Device Type Error
Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 6) - Wrong installer archive loaded to CIO3
1'096
22212
DevTypeErr_CIO3
Further steps: - Check optical link cabling to CIO CIO3. Digital IO deviation between IO's of Channel 1 and Channel 2
Possible reasons: - Defective I/O section on CIO Board 1'097 22213 SigConsistFlt_CIO3 - Wiring faults
Related parameters:
469
ABB
Nr ID Name
----
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'098
22214
Temp1SnsFlt_CIO3
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'099 22215 Temp2SnsFlt_CIO3 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
470
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'100
22216
Temp3SnsFlt_CIO3
Further steps: ---1'101 1'102 1'103 1'104 1'105 1'106 1'107 1'108 1'109 22217 22218 22219 22220 22221 22222 22223 22224 22225 Event1_12_CIO3 Event1_13_CIO3 Event1_14_CIO3 Event1_15_CIO3 Event1_16_CIO3 Event1_17_CIO3 Event1_18_CIO3 Event1_19_CIO3 Event1_20_CIO3
471
ABB
Nr
1'110 1'111 1'112 1'113 1'114 1'115 1'116 1'117 1'118 1'119 1'120
ID
22226 22227 22228 22229 22230 22231 22300 22301 22302 22303 22304
Name
Event1_21_CIO3 Event1_22_CIO3 Event1_23_CIO3 Event1_24_CIO3 Event1_25_CIO3 Event1_26_CIO3 Event1_27_CIO3 Event1_28_CIO3 Event1_29_CIO3 Event1_30_CIO3 Event1_31_CIO3
Events
Description
Further steps: - Check optical link cabling to CIO CIO4. Redundant Power fail 1
Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'122 22306 RedPwrFail1_CIO4
472
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CIO4. Precision Power fail
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
473
ABB
Nr ID Name
Events
CIO4. CPU Watchdog
Description
Further steps: - Reboot device - Download installer archive - Replace board CIO4. Software Version fault
1'126
22310
VersionFlt_CIO4
Possible reasons: - Wrong HEX Switch setting at CIO 1'127 22311 AddressErr_CIO4 Default reaction: - CIO Trip
Related parameters:
474
ABB
Nr ID Name
----
Events
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO
1'128
22312
DevTypeErr_CIO4
Further steps: - Check optical link cabling to CIO CIO4. Digital IO deviation between IO's of Channel 1 and Channel 2
475
ABB
Nr ID Name
Events
- Replace device
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'130
22314
Temp1SnsFlt_CIO4
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'131 22315 Temp2SnsFlt_CIO4 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
476
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'132
22316
Temp3SnsFlt_CIO4
Further steps: ---1'133 1'134 1'135 1'136 1'137 1'138 1'139 1'140 1'141 22317 22318 22319 22320 22321 22322 22323 22324 22325 Event1_12_CIO4 Event1_13_CIO4 Event1_14_CIO4 Event1_15_CIO4 Event1_16_CIO4 Event1_17_CIO4 Event1_18_CIO4 Event1_19_CIO4 Event1_20_CIO4
477
ABB
Nr
1'142 1'143 1'144 1'145 1'146 1'147 1'148 1'149 1'150 1'151 1'152
ID
22326 22327 22328 22329 22330 22331 22400 22401 22402 22403 22404
Name
Event1_21_CIO4 Event1_22_CIO4 Event1_23_CIO4 Event1_24_CIO4 Event1_25_CIO4 Event1_26_CIO4 Event1_27_CIO4 Event1_28_CIO4 Event1_29_CIO4 Event1_30_CIO4 Event1_31_CIO4
Events
Description
Further steps: - Check optical link cabling to CIO CIO5. Redundant Power fail 1
Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'154 22406 RedPwrFail1_CIO5
478
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CIO5. Precision Power fail
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
479
ABB
Nr ID Name
Events
CIO5. CPU Watchdog
Description
Default reaction: 1'157 22409 CPUWatchdog_CIO5 - CIO Trip Related parameters: ----
Further steps: - Reboot device - Download installer archive - Replace board CIO5. Software Version fault
Further steps: - Download required software version CIO5. Address Error Possible reasons: - Wrong HEX Switch setting at CIO
1'159
22411
AddressErr_CIO5
480
ABB
Nr ID Name
Events
Description
Possible reasons: - Wrong device connected to AC 800PEC (OM3 Link 5) - Wrong installer archive loaded to CIO
1'160
22412
DevTypeErr_CIO5
Further steps: - Check optical link cabling to CIO CIO5.Digital IO deviation between IO's of Channel 1 and Channel 2
481
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'162
22414
Temp1SnsFlt_CIO5
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'163
22415
Temp2SnsFlt_CIO5
482
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'164
22416
Temp3SnsFlt_CIO5
Further steps: ---1'165 1'166 1'167 1'168 1'169 1'170 1'171 1'172 1'173 1'174 1'175 1'176 1'177 1'178 1'179 1'180 1'181 22417 22418 22419 22420 22421 22422 22423 22424 22425 22426 22427 22428 22429 22430 22431 22500 22501 Event1_12_CIO5 Event1_13_CIO5 Event1_14_CIO5 Event1_15_CIO5 Event1_16_CIO5 Event1_17_CIO5 Event1_18_CIO5 Event1_19_CIO5 Event1_20_CIO5 Event1_21_CIO5 Event1_22_CIO5 Event1_23_CIO5 Event1_24_CIO5 Event1_25_CIO5 Event1_26_CIO5 Event1_27_CIO5 Event1_28_CIO5
483
ABB
Nr
1'182 1'183 1'184
ID
22502 22503 22504
Name
Event1_29_CIO5 Event1_30_CIO5 Event1_31_CIO5
Events
Description
Further steps: - Check optical link cabling to CIO CIO6. Redundant Power fail 1
484
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CIO6. Precision Power fail
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
485
ABB
Nr ID Name
Events
CIO6. CPU Watchdog
Description
Further steps: - Reboot device - Download installer archive - Replace board CIO6. Software Version fault
486
ABB
Nr ID Name
Events
CIO6. Address Error
Description
Further steps: - Check Hex-Swtich setting on CIO CIO6. Device Type Error
Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO
1'192
22512
DevTypeErr_CIO6
Further steps: - Check optical link cabling to CIO CIO6. Temperature Sensor 1 fault
Possible reasons: PT100 PTC 1'193 22513 SigConsistFlt_CIO6 - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at senor cabling > 181.6 Ohm > --- Ohm
487
ABB
Nr ID Name
----
Events
Related parameters:
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'194
22514
Temp1SnsFlt_CIO6
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'195 22515 Temp2SnsFlt_CIO6 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
488
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'196
22516
Temp3SnsFlt_CIO6
Further steps: ---1'197 1'198 1'199 1'200 1'201 1'202 1'203 1'204 1'205 22517 22518 22519 22520 22521 22522 22523 22524 22525 Event1_12_CIO6 Event1_13_CIO6 Event1_14_CIO6 Event1_15_CIO6 Event1_16_CIO6 Event1_17_CIO6 Event1_18_CIO6 Event1_19_CIO6 Event1_20_CIO6
489
ABB
Nr
1'206 1'207 1'208 1'209 1'210 1'211 1'212 1'213 1'214 1'215 1'216
ID
22526 22527 22528 22529 22530 22531 22600 22601 22602 22603 22604
Name
Event1_21_CIO6 Event1_22_CIO6 Event1_23_CIO6 Event1_24_CIO6 Event1_25_CIO6 Event1_26_CIO6 Event1_27_CIO6 Event1_28_CIO6 Event1_29_CIO6 Event1_30_CIO6 Event1_31_CIO6
Events
Description
Further steps: - Check optical link cabling to CIO CIO7. Redundant Power fail 1
Possible reasons: - Power supply fault at input 1 (X1:1-2) 1'218 22606 RedPwrFail1_CIO7
490
ABB
Nr ID Name
Events
Description
Further steps: - Check cabling and power supply CIO7. Precision Power fail
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
491
ABB
Nr ID Name
Events
CIO7. CPU Watchdog
Description
Further steps: - Reboot device - Download installer archive - Replace board CIO7. Software Version fault
492
ABB
Nr ID Name
Events
CIO7. Address Error
Description
Further steps: - Check Hex-Swtich setting on CIO CIO7. Device Type Error
Possible reasons: - Wrong device connected to AC 800PEC (OM3 Link 6) - Wrong installer archive loaded to CIO
1'224
22612
DevTypeErr_CIO7
Further steps: - Check optical link cabling to CIO CIO7. Digital IO deviation between IO's of Channel 1 and Channel 2
Possible reasons: - Defective I/O section on CIO Board 1'225 22613 SigConsistFlt_CIO7 - Wiring faults
Related parameters:
493
ABB
Nr ID Name
----
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'226
22614
Temp1SnsFlt_CIO7
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'227 22615 Temp2SnsFlt_CIO7 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
494
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'228
22616
Temp3SnsFlt_CIO7
Further steps: ---1'229 1'230 1'231 1'232 1'233 1'234 1'235 1'236 1'237 22617 22618 22619 22620 22621 22622 22623 22624 22625 Event1_12_CIO7 Event1_13_CIO7 Event1_14_CIO7 Event1_15_CIO7 Event1_16_CIO7 Event1_17_CIO7 Event1_18_CIO7 Event1_19_CIO7 Event1_20_CIO7
495
ABB
Nr
1'238 1'239 1'240 1'241 1'242 1'243 1'244 1'245 1'246 1'247 1'248
ID
22626 22627 22628 22629 22630 22631 22700 22701 22702 22703 22704
Name
Event1_21_CIO7 Event1_22_CIO7 Event1_23_CIO7 Event1_24_CIO7 Event1_25_CIO7 Event1_26_CIO7 Event1_27_CIO7 Event1_28_CIO7 Event1_29_CIO7 Event1_30_CIO7 Event1_31_CIO7
Events
Description
1'249
22705
LinkFault_CIO8
Further steps: - Check optical link cabling to CIO CIO8. Redundant Power fail 1
1'250
22706
RedPwrFail1_CIO8
496
ABB
Nr ID Name
Events
Further steps:
Description
Further steps: - Check cabling and power supply CIO8. Precision Power fail
Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing
497
ABB
Nr ID Name
Events
CIO8. CPU Watchdog
Description
Further steps: - Reboot device - Download installer archive - Replace board CIO8. Software Version fault
498
ABB
Nr ID Name
Events
CIO8. Address Error
Description
Further steps: - Check Hex-Swtich setting on CIO CIO8. Device Type Error
Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO
1'256
22712
DevTypeErr_CIO8
Further steps: - Check optical link cabling to CIO CIO8. Digital IO deviation between IO's of Channel 1 and Channel 2
Possible reasons: - Defective I/O section on CIO Board 1'257 22713 SigConsistFlt_CIO8 - Wiring faults
Related parameters:
499
ABB
Nr ID Name
----
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'258
22714
Temp1SnsFlt_CIO8
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm 1'259 22715 Temp2SnsFlt_CIO8 - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
500
ABB
Nr ID Name
Events
Description
Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm
1'260
22716
Temp3SnsFlt_CIO8
Further steps: ---1'261 1'262 1'263 1'264 1'265 1'266 1'267 1'268 1'269 22717 22718 22719 22720 22721 22722 22723 22724 22725 Event1_12_CIO8 Event1_13_CIO8 Event1_14_CIO8 Event1_15_CIO8 Event1_16_CIO8 Event1_17_CIO8 Event1_18_CIO8 Event1_19_CIO8 Event1_20_CIO8
501
ABB
Nr
1'270 1'271 1'272 1'273 1'274 1'275 1'276 1'277 1'278 1'279 1'280
ID
22726 22727 22728 22729 22730 22731 23000 23001 23002 23003 23004
Name
Event1_21_CIO8 Event1_22_CIO8 Event1_23_CIO8 Event1_24_CIO8 Event1_25_CIO8 Event1_26_CIO8 Event1_27_CIO8 Event1_28_CIO8 Event1_29_CIO8 Event1_30_CIO8 Event1_31_CIO8
Events
Description
Possible reasons: - One or more events which are assigned to "Channel Fault" has (have) occurred - The signal was forced by the command "Force Channel Fault"
Default reaction: 1'281 23005 ChannelFault - Single channel -> Trip - Redundant system -> Channel transfer
502
ABB
Nr ID Name
Events
Auto Fault - Group alarm
Description
Possible reasons: - One or more events which are assigned to "Auto Fault" has (have) occurred - The signal was forced by the command "Force Auto Fault"
Default reaction: 1'282 23006 AutoFault - Single channel -> Transfer to "Manual Mode" - Redundant system -> Channel transfer, own channel transfer to "Manual Mode"
Further steps: - according to individual event description Manual Fault - Group alarm
Possible reasons: - One or more events which are assigned to "Manual Fault" has (have) occurred - The signal was forced by the command "Force Manual Fault"
Default reaction: 1'283 23007 ManualFault - Single channel -> Trip - Redundant system -> Channel transfer
503
ABB
Nr ID Name
Events
Description
Possible reasons: - One or more events which are assigned to "Other Channel Hardware Fault" has (have) occurred - The signal was forced by the command "Force Other Channel Hardware Fault"
1'284
23008
OtherCHHWFault
Further steps: - According to individual event description Backup Channel Hardware Fault - Group alarm
Possible reasons: - One or more events which are assigned to Auto Fault has (have) accured - The signal was forced by the command "Force Auto Fault"
Default reaction: 1'285 23009 BUCHHWFault - Single channel -> Transfer to "Manual Mode" - Reduadant system -> Channel transfer, own channel transfer to "Manual Mode"
504
ABB
Nr ID Name
Events
Description
Possible reasons: - One or more events which are assigned to Channel to Backup Link Loss has (have) occurred - The signal was forced by the command "Channel to Backup Link Loss"
1'286
23010
CHtoBULinkLoss
Further steps: - According to individual event description Emergency Stop - Group alarm
Possible reasons: - One or more events which are assigned to "Emergency Stop" has (have) occurred - The signal was forced by the command "Emergency Stop"
Default reaction: 1'287 23011 EmergencyStop - Excitation is swiched off - Fieldbreaker is opened
505
ABB
Nr ID Name
Events
Trip 1 - Group alarm
Description
Possible reasons: - One or more events which are assigned to "Trip 1" has (have) occurred - The signal was forced by the command "Trip 1"
Default reaction: 1'288 23100 Trip1 - Trip command given to Plant Protection - Excitation is swiched off - Fieldbreaker is opened
Possible reasons: - One or more events which are assigned to "Trip 2" has (have) occurred - The signal was forced by the command "Trip 2"
Default reaction: - Trip request given to Plant Protection 1'289 23101 Trip2 - If accepted - Excitation is swiched off - Fieldbreaker is opened
506
ABB
Nr ID Name
Events
Startup Inhibit - Group alarm
Description
Possible reasons: - One or more events which are assigned to "Startup Inhibit" has (have) occurred - The signal was forced by the command "Force Startup Inhibit"
Default reaction: 1'290 23102 StartupInhibit - Blocking of Fieldbreaker Close command - Blocking of Excitation On command
Further steps: - According to individual event description Redundancy Fault - Group alarm
Possible reasons: - One or more events which are assigned to "Redundancy Fault" has (have) occurred - The signal was forced by the command "Redundancy Fault"
1'291
23103
RedundancyFault
507
ABB
Nr ID Name
Events
Alarm - Group alarm
Description
Possible reasons: - One or more events which are assigned to "Alarm" has (have) occurred - The signal was forced by the command "Alarm"
1'292
23104
Alarm
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Channel Fault"
508
ABB
Nr ID Name
Events
Force Auto Fault
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Auto Fault"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Manual Fault"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Other Channel Hardware Fault"
1'296
23108
ForceOtherCHHWFault
Related parameters:
509
ABB
Nr ID Name
----
Events
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Backup Channel Hardware Fault"
1'297
23109
ForceBUCHHWFault
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Channel to Backup Link Loss"
1'298
23110
ForceCHtoBULinkLoss
Further steps:
510
ABB
Nr ID Name
----
Events
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Emergency Stop"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Trip"
511
ABB
Nr ID Name
Events
Force Trip 2
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "conditional Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Startup Inhibit"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Redundancy Fault" 1'303 23203 ForceRedundancyFault Default reaction: ----
Related parameters:
512
ABB
Nr ID Name
----
Events
Description
Force Alarm
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Alarm"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI1 Trip"
513
ABB
Nr ID Name
Events
Force CCI2 Trip
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI2 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI3 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI4 Trip" 1'308 23300 ForceCCI4Trip Default reaction: ----
Related parameters:
514
ABB
Nr ID Name
----
Events
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI5 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI6 Trip"
515
ABB
Nr ID Name
Events
Force CCI7 Trip
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI7 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI8 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO1 Trip" 1'313 23305 ForceCIO1Trip Default reaction: ----
Related parameters:
516
ABB
Nr ID Name
----
Events
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO2 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO3 Trip"
517
ABB
Nr ID Name
Events
Force CIO4 Trip
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO4 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO5 Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO6 Trip" 1'318 23402 ForceCIO6Trip Default reaction: ----
Related parameters:
518
ABB
Nr ID Name
----
Events
Description
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO7Trip"
Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO8 Trip"
519
ABB
Nr ID Name
Events
Reset
Description
Possible reasons: - The Excitation System reached the "AuxReady" main state
Possible reasons: - The Excitation System reached the "AuxOn" main state
1'323
23407
AuxOn
520
ABB
Nr ID Name
----
Events
Further steps:
Description
Ready State
Possible reasons: - The Excitation System reached the "Ready" main state
Possible reasons: - The Excitation System reached the "Operation" main State
521
ABB
Nr ID Name
Events
Manual Control Active
Description
Possible reasons: - The Excitation System changed the control to "this Channel"
522
ABB
Nr ID Name
Events
Transient Recorder Trigger
Description
Possible reasons: - The Transient Recorder in the Excitation System was triggered either by a - Trip - Channel Fault - Auto Fault - Manual Fault or 1'328 23412 TRTrig - manually
Further steps: ---1'330 1'332 1'340 23414 23415 20173 ActUfMeasFlt Event6_27 Event3_09_CCI2