Professional Documents
Culture Documents
Pumps
INFORMATION PACK
Medias transporting energy have to be pumped. This Info Pack covers mechanical pumps. refrigerant is often called brine (even though it in scientific sense only covers the salt based solutions). Phase changing refrigerants obtain heat as they evaporate at the cooling surface when changing from liquid to gas. In this setup the cooling surface is called an evaporator. The transition of liquid to vapour happens at a constant temperature meaning that the evaporator has the same temperature on the entire surface. The phase change requires a lot of energy meaning that a small amount of liquid can obtain a lot of heat. As the liquid evaporates it returns to the cooling plant as vapour where it condenses and release the energy (heat) obtained during the evaporation. The liquid is then pumped back to the cooling surface where it evaporates once again. Secondary refrigerants obtain heat by simple temperature change of the liquid: The liquid enters a cooling surface at a low temperature and returns warmer, meaning that the cooling surface is coldest were the liquid enters and warmer where it exits. The increase of temperature in the liquid is proportional to the heat removed at the cooling surface. The heated liquid is then pumped to a cooling plant, cooled to the initial cold temperature and circulated back to the cooling surface.
Power consumption
The theoretical power required for pumping fluids is determined by: Where: P is the power input in kW is the density of the fluid in kg/m3 Q is the flow rate in L/s g is gravity = 9,81m/s2 H is the pressure difference (head) across the pump in m As and g are constant, the power consumption is linear dependent on only two parameters flow and pressure difference across the pump. So to minimize the power consumption the flow and pressure difference have to be minimized. The flow is given by the required cooling. The pressure difference is determined by pressure drop in the distribution system which consist of friction loss (dynamic head) height difference in the system (static head) in open systems To calculate the electrical power consumption the efficiency of both the drive line (electrical motor and if installed the VSD (Variable Speed Drive) and the pump:
To minimize the power consumption in pumps the flow and pressure difference have to be minimized
Where: is the cooling capacity in kW is the mass flow of refrigerant in kg/s hvap is the heat obtained per kg refrigerant that evaporates Evaporating ammonia in a cooling surface at 30 C takes 925 kJ/L of ammonia that evaporates. For comparison CO2 only takes 325 kJ/L, meaning that using CO2, rather than ammonia, require bigger pumps. The flooded evaporators (cooling surfaces) used in such systems often have a circulation rate higher than 1, meaning that the amount of refrigerant that is applied exceeds the amount that evaporates. Having a higher circulation rate makes the heat exchanger more efficient and must be considered when calculating the necessary pump capacity. Using the above example at -30 C and a circulation rate of 1,3 (meaning that an additional 30 % of refrigerant is pumped), it is possible to calculate the required volume flow at a cooling capacity of 100 kW: Using ammonia as refrigerant:
Figure 1
Using CO2 as refrigerant:
H
Compared to the evaporating refrigerants above the flow rates are 10-40 times greater when using secondary refrigerants, meaning that pipes and pumps are very different. The flow rates can be reduced by increasing the temperature differences but as this result in a lowering of the evaporating temperature it will increase the energy consumption of the cooling plant it is important to find the right balance between temperature and flow.
Type of pumps
At a given cooling demand the pump capacity is determined by the circulation rate and characteristics of the specific refrigerant. A lot of different types of mechanical pumps exist such as Centrifugal Membrane Gear Impeller Only centrifugal pumps will be covered by the following as this type by far the most used in refrigeration systems.
Figure 2
Static head
Figure 3
New duty point Closing valve
Figure 6
helps the pump thus requiring less pressure from the pump. When the static head is negative, the system curve starts below 0 as shown in figure 6. As the static pressure is negative, the total pressure required by the pump is the pressure from friction loss, minus the static head.
Secondary refrigerants
Cooling systems using secondary refrigerants are either closed or open systems. In closed systems the fluid is sealed from the surroundings throughout the system. In open systems the fluid is in contact with the atmosphere thus making it an open system. This is the case in systems using cooling towers or large storage tanks that are not pressurized.
Figure 4
The system curve is highly depending on the system design and the fluid to be pumped (viscosity) The static head (and hereby the energy consumption) varies dependent on the type of system.
Figure 5
Figure 7
high risk of cavitation in systems using evaporating refrigerants, as these are very close to the saturation pressure. Secondary refrigerants (e.g. water and brines) at low temperature on the other hand, are very far from the saturation pressure and will only cavitate at a very low pressure (which can be made is an inlet valve is being closed!). The pressure drop inside a pump depends on3 the design of that specific pump and because of this different pumps tend to cavitate at different pressures and flow rates.
NPSH (m)
Figure 10
The minimum suction pressure required for a specific pump can be read from the pumps NPSH-curve. NPSH stands for net positive suction head and accounts for the balance in positive (gravity and absolute pressure) and negative pressures (friction losses) at a certain flow rate. Effectively, NPSH is the needed minimum difference of the pressure at the suction side of the pump and the fluids saturation pressure and all pumps require a certain NPSH not to cavitate. The required NPSH is found in the pumps specifications and a curve for a specific pump could be like the one the figure 10. The NPSH-curve shows the minimum NPSH required at different flow rates for a specific pump. Higher flow rates tend to require higher NPSH, as the pressure loss inside the pump increases with the flow. In order to avoid cavitation, the pressure of the fluid on the suction side of the pump must exceed the saturation pressure according to the NPSH-curve. Note that dynamic pressure losses must be considered as well. As stated before in pump circulated systems more liquid refrigerant is pumped into the distribution lines to the evaporators than evaporated. If problems arise like too little refrigerant supplied to an evaporator one could jump to the conclusion just to raise the flow into the system. But due to the shape of the NPSH curve one could end up having cavitation in the pump.
H2
H1
Figure 8
H
Static head
Figure 9
As long as the inlet (secondary refrigerants) or evaporation (direct systems) temperature is not changed a change in the cooling (or heating) demand is adjusted by regulating the flow. At reduced flow the pressure loss from friction is also reduced meaning that the pumps power consumption should decrease. When fixed speed pumps are used, the flow is adjusted using valves meaning that the pressure will increase or decrease as the flow is adjusted. By adjusting the flow rate using valves, the system is adjusted to fit a certain pump rather than adjusting the pump according to the system. This is illustrated on figure 4. The figure shows how adjusting valves will change the flow rate when a certain pump is used. Instead of changing the system pressure drop, the pump curve could be altered by adjusting the speed of the pump. Looking at the system curve with the valve open, it is clear that less flow is possible at much lower pressure levels. This means that the duty point with the valve closed could have been met using a lot less pressure thus reducing the energy consumption. This is illustrated in figure 11 where a new pump curve (at low speed) meets the system curve with the valve open. The figure shows how the new duty point is reached by changing the pump curve rather Equations of affinity Changing the speed of a centrifugal pump affects pressure, flow and energy consumption according to the equations of affinity shown below (index b = after and a = before the change): The ratio of the flow changes linear to the ratio in speed:
Constant pressure
Constant pressure means that the pump will keep a certain pressure according to a specified set point and adjust the speed to maintain the pressure at this set point as the flow rate fluctuates. Figure 12 below shows the duty points using constant pressure control mode.
Proportional pressure
In proportional pressure, the pressure in the system is reduced proportional to the flow rate. This control mode means higher energy savings at low flow rates as the pressure is reduced even further. The installer chooses two set points for the pressure levels: One pressure level at the highest flow rate and another at zero flow. The pump will reduce the speed so that the pressure never exceeds the set point. The duty points are at the same pressure until the pump reaches full speed at a certain flow rate. At higher flow rates, duty points will follow the pump curve at full speed. The pump will adjust the pressure proportional according to these two set points. Figure 13 shows the duty points using proportional pressure control mode. The pump adjusts the speed automatically to vary pressure at different flow rates as determined by the two set points. Proportional pressure is the best way to reduce the energy consumption of a pump in systems with fluctuation flow rates. The pump adjusts the speed automatically to vary pressure at different flow rates as determined by the two set points. Proportional pressure is the best way to reduce the energy consumption of a pump in systems with fluctuation flow rates. The pump adjusts the speed automatically to vary pressure at different flow rates as determined by the two set points. Proportional pressure is the best way to reduce the energy consumption of a pump in systems with fluctuation flow rates.
Figure 11
H
Setpoint
Figure 12
H
Setpoint
Setpoint
The ratio in head and power consumption are squared and cubed, meaning that the pressure is reduced to at half speed and the power consumption to 1/8:
Figure 13
Figure 14 shows two of the duty points using a fixed speed pump (blue) compared to the proportional pressure control mode (green). At the duty point at around half of the highest flow rate, the pump slows down using proportional pressure, meaning that the pressure in the system is actually less than half compared to a fixed speed pump. As the pump slows down, the valves in the system will open further to provide the proper flow rate. The proportional pressure control mode actually affects the system and force the valves to open meaning that the system require less pressure at a given flow rate thus making the system curve less steep compared to a fixed speed installation. Ideally the flow should be adjusted by pump speed alone meaning that all duty points would be on the system curve at the highest flow rate as illustrated on figure 15. The figure shows a system with no valves meaning that the system curve is static and the required pressure at a given flow is always the same. This is not the case in most applications where pumps provide flow for several circuits each controlled by a valve. In these applications the system curve will change depending on the demand which means that the pump must provide a pressure just above the required in order to detect the fluctuations and adjust the speed accordingly. This can be optimized using the proportional pressure control mode and the two set points are adjusted to an exact fit of a given system. Figure 16 shows a proportional pressure setup where the pressure is kept just above the required at all flow rates. In this setup the pump will provide a pressure just high enough to detect fluctuations in the system as valves open or close. This control strategy will force valves to open as much as possible and avoid energy consuming pressure losses yet provide sufficient pressure in all situations.
System curve Flow @ max speed
Prop. pres.
Figure 14
H
systems trouble can occur when pipe distances (and hereby friction loss) PED=Pedestrian between a pump anddoors the different valves are varying. In such applications it is important to register the available pressure at the most critical points in the system and control the pump speed accordingly. It can be very complicated to find the lowest possible working pressure in a system, and as the cycle between max and min cooling demand often is one year, a change of the setup might cause trouble at a much later point. Because of this, it is often recommended to use a constant pressure control mode and only use proportional pressure with caution. However the benefits using proportional pressure should be exploited in new systems or at system rebuilds, where the characteristics of pipes and valves are considered anyway.
Figure 15
H
Pump curve
Figure 16
Energy wise, the best control strategy in most systems is a combination of controlling both valves (system curve) and pump speed (pump curve) so that the pressure is reduced along with the flow rate. But it can be difficult to find the correct ratio if a systems characteristics is not very well known. A low working pressure can cause valves to lose their function and hereby cause inadequate cooling. In big
The work associated with this information pack has been carried out in accordance with the highest academic standards and reasonable endeavours have been made to achieve the degree of reliability and accuracy appropriate to work of this kind. However, the ICE-E project does not have control over the use to which the results of this work may be put by the Company and the Company will therefore be deemed to have satisfied itself in every respect as to the suitability and fitness of the work for any par ticular purpose or application. In no circumstances will the ICE-E project, its servants or agents accept liability however caused arising from any error or inaccuracy in any operation, advice or report arising from this work, nor from any resulting damage, loss, expenses or claim. ICE-E 2012