Product note Kabeldon dry plug-in cable termination for GIS and TRF CD 145

Dry plug-in cable termination 145 kV suitable as a xed connection point in a gas-insulated switchgear or an oil-lled transformer box. Designed to meet the requirements of internationally accepted standards.

1 2 9 3 4 10

5 6

CD 145 contains of two main parts as follows. CD 145: Plug-in termination kit including 1. Plug-in connector Aluminium or copper mechanical connector. Including two contact springs made from silver-plated copper. 2. Locking half Made of aluminium. 3. Stress relief cone The stress relief cone is made from EPDM rubber and designed for geometric field control. It is premolded which enables routine testing. 4. Pre-loaded spring assembly Made from aluminium. 5. Box body Made from aluminium alloy. 6. Earth clamp The earth clamp is made from tin-plated brass and clamped with stainless steel bolts. The earth clamp has a nominal cross section of 1050 mm. 7. Cable clamp Made from aluminium alloy. The clamp secures the cable in a fixed position. Bitumized paper is used for a snug fit under the cable clamp.

CDI 145: Insulator kit including 8. Top fitting Top fitting is made from silver-plated aluminium. 9. Insulator Insulator is made from epxoy with an integrated screen interruption. 10. Pressure ring Made of stainless steel with a packing made of paper laminate.

Main technical data


Electrical data, IEC standard 60840 Highest voltage for equipment, Um Rated voltage, U Value of U0 for determination of test voltage Heating cycle voltage test, 2U0 Partial discharges test <5pC, 1.5U0 Lighting impulse voltage test, BIL Power frequency voltage test, 2.5U0 Voltage kV 145 132138 76 152 114 + 650 190

Dimensions in mm

470 mm

320

14 (12x) 1149 mm CDI 145, insulator kit. 283

345 Type testing in a high voltage laboratory. Insulator mounting ring for CD 145.
Document ID: 7ABA102357

CD 145, termination kit.

Common specifications Classifications Rated frequency, Hz Max inclination, degrees Dimensions according to IEC 62271-209 (GIS) HV GIS/TRF 50/60 No limitations
CST 170 Corona shield for installation in transformer. CBT Contact bolt for installation in transformer.

Routine test Epoxy insulator according to EN 50089 Dimensional and electric test is perfomed on each stress relief cone Visual inspection is performed on all parts of the termination Cable range Prepared insulation (mm) Conductor Cu/Al (mm) Oversheath (mm) Oversheath (mm) 4496 3002000 150 CUW 130 PAL, MET

Packaging CD 145 CDI 145 Insulator mounting ring

Gross weight kg 33 25 6

Dimensions mm 800 x 400 x 450 700 x 340 x 340 340 x 340 x 60

Dimensions and weights may vary as products occasionally have different packaging.

Accessories for TRF


Corona shield

Designation CST 170 CBT 84-170

Contact bolt for TRF

Storage When stored in original, unopened packaging at temperatures in the range of -30C to 30C: The stress relief cone has a shelf life of ten years from date of manufacture. Tapes and grease have a shelf life of five years. Metal hardwares have no shelf life limit.

Optional equipment Insulator protective cover Installation tool Peeling and stripping tool Spare peeling blade Spare stripping blade Slot knife

Designation IPC RKM 145 SH 80, SH 130 FK-SH 80, FK-SH 130 IK-SH 80, IK-SH 130 SLK-SH 80, SLK-SH 130 JSA, SCK

For additional information, please visit: www.abb.com/cableaccessories


Copyright 2013 ABB. All rights reserved. Specications subject to change without notice.

Base plate for slot knife and stripping blade BSL-SH 130 Earthing kit