You are on page 1of 40

30HXA,HXC076-271

ECOLOGIC Fluid-Cooled and


Condenserless Chillers
50/60 Hz

Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-40
Step 1 Inspect Shipment . . . . . . . . . . . . . . . . . . . 1
Step 2 Rig and Place Unit . . . . . . . . . . . . . . . . . . 1
Step 3 Piping Connections . . . . . . . . . . . . . . . . 15
COOLER FLUID, VENT, AND DRAIN
BRINE UNITS
PREPARATION FOR YEAR-ROUND
OPERATION
FILL FLUID LOOP
INSULATE COOLER HEADS
30HXA PIPING, VALVE, AND SWITCH
INSTALLATION
30HXC PIPING AND VALVE INSTALLATION
INSTALL PRESSURE RELIEF REFRIGERANT
VENT PIPING
Step 4 Make Electrical Connections . . . . . . 21
FIELD POWER CONNECTIONS
FIELD CONTROL POWER CONNECTIONS
CONDENSER FAN CONTROL FOR
CONDENSER UNITS USED WITH
30HXA UNITS
Step 5 Install Accessories . . . . . . . . . . . . . . . 25
ELECTRICAL
30HXA LOW-AMBIENT OPERATION
MINIMUM LOAD ACCESSORY
MISCELLANEOUS ACCESSORIES
Step 6 Leak Test Unit . . . . . . . . . . . . . . . . . . . . 25
30HXC UNITS
30HXA UNITS
Step 7 Refrigerant Charge . . . . . . . . . . . . . . . 40
30HXC UNITS
30HXA UNITS

SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components, and equipment location. Only trained, qualified installers and service mechanics should install, start up, and
service this equipment.
When working on the equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky
equipment.

IMPORTANT: This equipment generates, uses, and can


radiate radio frequency energy. If not installed and
used in accordance with these instructions, this equipment may cause radio interference. The equipment has
been tested and found to comply with the limits of
a Class A computing device as defined by the FCC
(Federal Communications Commission, U.S.A.) Regulations, Subpart J of Part 15, which are designed to
provide reasonable protection against such interference when operated in a commercial environment.

INTRODUCTION
These instructions cover installation of 30HX liquid chillers with electronic controls and units with factory-installed
options (FIOPs).

INSTALLATION
Step 1 Inspect Shipment Inspect unit for damage upon arrival. If damage is found, file a claim with the
shipping company right away. Do not store units in an area
exposed to weather because of sensitive control mechanisms and electronic devices.
Locate unit indoors. When considering unit location, consult National Electrical Code (NEC, U.S.A.) and local code
requirements. Allow sufficient space for wiring, piping, and
service. Install unit in an area which will not be exposed to
subfreezing weather. See Fig. 1-8 for clearance details.
Allow the following clearances for service access:
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ft (610 mm)
Ends . . . . . . . . . . . . . . . . tube removal at one (either) end;
3 ft (914 mm) at opposite end.
Be sure surface beneath unit is level and is capable of
supporting the operating weight of the unit. See Fig. 9 and
Tables 1A and 1B for unit mounting and operating weights.
If necessary, add supporting structure (steel beams or reenforced concrete slabs) to floor to transfer weight to nearest
beams.

Step 2 Rig and Place Unit


Rig unit from the top heat exchanger only. Rigging from
the bottom heat exchanger will cause the unit to be lifted
unsafely. Personal injury or damage to the unit may
occur.
Copy continued on page 15.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Catalog No. 533-004
Printed in U.S.A.
Form 30HX-7SI
Pg 1
8-99
Replaces: 30HX-4SI
Tab 5c

106

096

086

076

UNIT
30HXC

OPERATING
WEIGHT
lb (kg)
5700
(2586)
5723
(2597)
5855
(2657)
6177
(2803)
B
45.87
(1165)
45.87
(1165)
37.63
(956)
37.63
(956)

45.87
(1165)
45.87
(1165)
54.12
(1375)
54.12
(1375)

32.50
(826)
32.50
(826)
32.50
(826)
33.50
(851)

DIMENSION in. (mm)


D
65.22
(1657)
65.22
(1657)
65.22
(1657)
67.22
(1707)

LEGEND

Denotes center of gravity.

Fig. 1 Dimensions, 30HXC076-106

Std
Minus
Plus
Std
Minus
Plus

076,086,096
076,086,096
076,086,096
106
106
106

UNIT 30HXC

3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).

2.

K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.

4.68 (119)
5.14 (131)
5.14 (131)
5.14 (131)

4.68 (119)

4.68 (119)
5.14 (131)
5.14 (131)
5.14 (131)

4.68 (119)

DIMENSIONS in. (mm)


A
B
4.68 (119)
4.68 (119)

4
3
2
4

NUMBER
OF PASSES

49
59
59
59

49

49

CONNECTION
SIZES

146

136

126

116

UNIT
30HXC

OPERATING WEIGHT
lb (kg)
6415
(2911)
6465
(2933)
6688
(3034)
6718
(3048)

LEGEND

Denotes center of gravity.

Fig. 2 Dimensions, 30HXC116-146

Std
Minus
Plus

116,126,136,146
116,126,136,146
116,126,136,146

UNIT 30HXC

3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).

2.

K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.

0.00
4.68 (119)

0.00
4.68 (119)

DIMENSIONS in. (mm)


A
B
4.68 (119)
4.68 (119)

1
3

NUMBER
OF PASSES

49
49

49

CONNECTION
SIZES

186

171

161

UNIT
30HXC

7452
(3381)
7660
(3475)
7854
(3564)

OPERATING
WEIGHT
lb (kg)

DIMENSIONS
in. (mm)
A
B
72.12
50.63
(1832)
(1286)
61.37
61.37
(1559)
(1559)
61.37
61.37
(1559)
(1559)

LEGEND

Denotes center of gravity.

Fig. 3 Dimensions, 30HXC161-186

3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).

2.

K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.

Std
Minus
Plus

161,171,186
161,171,186
161,171,186

UNIT 30HXC

0.00
4.68 (119)

A
4.68 (119)

0.00
4.68 (119)

B
4.68 (119)

DIMENSIONS in. (mm)

1
3

NUMBER OF PASSES

59
59

59

CONNECTION SIZES

271

261

246

206

UNIT
30HXC

10,581
(4799)
10,969
(4976)
10,992
(4986)
11,029
(5003)

OPERATING
WEIGHT
lb (kg)

DIMENSIONS
in. (mm)
A
33.88
(860)
34.38
(873)
34.38
(873)
34.38
(873)

LEGEND

Denotes center of gravity.

Fig. 4 Dimensions, 30HXC206-271

Denotes accessory or factoryinstalled option.


4. Dimensions are in inches (millimeters) and
weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).

3.

2.

K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and
refrigerant.

Std
Minus
Plus

206,246,261,271
206,246,261,271

UNIT 30HXC
206,246,261,271

0.00
5.53 (140)

0.00
5.53 (140)

DIMENSIONS in. (mm)


A
B
5.53 (140)
5.53 (140)

1
3

NUMBER OF
PASSES

69
69

69

CONNECTION
SIZES

Std
Minus
Plus

Std
Minus

Plus

076,086,096
076,086,096
076,086,096

106
106

106

A
8.48
(215)
8.48
(215)
8.48
(215)
10.48
(266)

5.14 (131)

5.14 (131)
5.14 (131)

5.14 (131)

5.14 (131)
5.14 (131)

B
4.68 (119)
4.68 (119)
4.68 (119)

DIMENSIONS
in. (mm)

A
4.68 (119)
4.68 (119)
4.68 (119)

4717
(2140)
4744
(2152)
4835
(2194)
5151
(2337)

OPERATING
WEIGHT lb (kg)

UNIT 30HXA

106

096

086

076

UNIT
30HXA

3
2

3
2
4

NUMBER OF
PASSES

B
45.87
(1165)
45.87
(1165)
54.12
(1375)
54.12
(1375)

59

59
59

49
49
49

CONNECTION
SIZES

C
45.87
(1165)
45.87
(1165)
37.63
(956)
37.63
(956)

D
32.50
(826)
32.50
(826)
32.50
(826)
33.50
(851)

H
59.48
(1511)
59.48
(1511)
42.77
(1086)
42.77
(1086)

J
5.72
(145)
5.72
(145)
5.72
(145)
5.87
(149)

L
46.25
(1175)
46.25
(1175)
38.00
(965)
38.00
(965)

K.O.
SAE
THK
TYP

K
45.81
(1164)
45.81
(1164)
54.06
(1373)
54.06
(1373)

Knockout
Society of Automotive Engineers, U.S.A.
Thickness
Typical

LEGEND

Denotes center of gravity.

3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).

2.

NOTES:
1. Operating weight includes weight of water and refrigerant.

Fig. 5 Dimensions, 30HXA076-106

DIMENSIONS in. (mm)


E
F
G
43.50
65.22
13.93
(1105) (1657) (354)
43.50
65.22
13.93
(1105) (1657) (354)
43.50
65.22
22.15
(1105) (1657) (563)
45.50
67.22
22.15
(1156) (1707) (563)

146

136

126

116

UNIT
30HXA

OPERATING
WEIGHT
lb (kg)
5163
(2342)
5205
(2362)
5309
(2408)
5333
(2420)

Denotes center of gravity.

Minus
Plus

116,126,136,146
116,126,136,146

0.00
4.68 (119)

0.00
4.68 (119)

DIMENSIONS in. (mm)


A
B
4.68 (119)
4.68 (119)

Fig. 6 Dimensions, 30HXA116-146

Std

116,126,136,146

UNIT 30HXA

NUMBER OF
PASSES

49

49

49

CONNECTION
SIZES

3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).

2.

NOTES:
1. Operating weight includes weight of water and refrigerant.

LEGEND
K.O. Knockout
THK Thickness
TYP Typical

161
171
186

Std

Minus
Plus

161,171,186

161,171,186
161,171,186

UNIT 30HXA

5752 (2610)
5777 (2621)
5946 (2698)

UNIT
OPERATING
30HXA WEIGHT lb (kg)

0.00
5.14 (131)

A
5.14 (131)

0.00
5.14 (131)

B
5.14 (131)

DIMENSIONS in. (mm)

1
3

NUMBER OF
PASSES
59
59

59

CONNECTION
SIZES

DIMENSIONS in.
A
B
C
72.12 (1832) 50.63 (1286) 48.56 (1233)
61.37 (1559) 61.37 (1559) 43.25 (1099)
61.37 (1559) 61.37 (1559) 43.25 (1099)

LEGEND

Denotes center of gravity.

Denotes accessory or
factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance
around machine 369 (914.4).

3.

2.

K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.

Fig. 7 Dimensions, 30HXA161-186

D
E
72.06 (1830) 51.00 (1295)
61.31 (1572) 61.75 (1568)
61.31 (1572) 61.75 (1568)

(mm)

UNIT
30HXA
206
246
261
271

OPERATING
WEIGHT lb (kg)
7485 (3395)
7621 (3457)
7621 (3457)
7621 (3457)

Fig. 8 Dimensions, 30HXA206-271

Denotes center of gravity.


Denotes accessory or factoryinstalled option.
4. Dimensions are in inches (millimeters) and
weights are in lb (kg).
5. Recommended service clearance around
machine 36 (914.4).

2.
3.

NOTES:
1. Operating weight includes weight of water and
refrigerant.

LEGEND
K.O. Knockout
THK Thickness
TYP Typical

WEIGHT DISTRIBUTION AT EACH MOUNTING PLATE,


30HXC UNITS lb (kg)
UNIT
30HXC
076
086
096
106
116
126
136
146
161
171
186
206
246
261
271

738
738
686
730
728
738
758
763
817
936
962
948
985
985
985

1
(335)
(335)
(311)
(331)
(330)
(335)
(344)
(346)
(371)
(425)
(436)
(430)
(447)
(447)
(447)

943
947
968
1028
1114
1127
1176
1182
1272
1318
1361
2406
2515
2520
2529

2
(428)
(430)
(439)
(466)
(505)
(511)
(533)
(536)
(577)
(598)
(617)
(1091)
(1141)
(1143)
(1147)

MOUNTING PLATE NO.


3
4
595 (270)
1110 (503)
597 (271)
1112 (504)
693 (314)
1027 (466)
744 (337)
1073 (487)
777 (352)
1053 (478)
780 (354)
1061 (481)
811 (368)
1083 (491)
815 (370)
1085 (492)
908 (412)
1219 (553)
840 (381)
1379 (626)
860 (390)
1410 (640)
1243 (564)
1201 (545)
1306 (592)
1154 (523)
1311 (595)
1154 (523)
1318 (598)
1154 (523)

1418
1427
1447
1510
1615
1628
1689
1697
1890
1946
1996
3133
3276
3283
3294

5
(643)
(647)
(656)
(685)
(733)
(738)
(766)
(770)
(857)
(883)
(905)
(1421)
(1486)
(1489)
(1494)

6
896 (406)
902 (409)
1034 (469)
1092 (495)
1127 (511)
1131 (513)
1171 (531)
1172 (532)
1346 (610)
1241 (563)
1265 (574)
1650 (748)
1733 (786)
1739 (789)
1749 (793)

30HXA UNITS lb (kg)


UNIT
30HXA
076
086
096
106
116
126
136
146
161
171
186
206
246
261
271

1
555 (252)
555 (252)
509 (231)
555 (252)
530 (240)
540 (245)
548 (249)
551 (250)
560 (254)
627 (284)
648 (294)
671 (304)
681 (309)
681 (309)
681 (309)

2
793 (360)
798 (362)
808 (367)
869 (394)
895 (406)
905 (410)
926 (420)
930 (422)
965 (438)
968 (439)
1004 (455)
1702 (772)
1748 (793)
1748 (793)
1748 (793)

MOUNTING PLATE NO.


3
4
418 (190)
926 (420)
418 (190)
928 (421)
493 (224)
848 (385)
541 (245)
896 (406)
540 (245)
855 (388)
541 (245)
864 (392)
555 (252)
874 (396)
555 (252)
883 (400)
598 (271)
954 (433)
534 (242)
1072 (486)
552 (250)
1110 (504)
879 (399)
850 (385)
911 (413)
797 (362)
911 (413)
797 (362)
911 (413)
797 (362)

NOTE: See pages Fig. 1-8 for center of gravity details.

Fig. 9 Weight Distribution at Mounting Plates

10

5
1326 (601)
1340 (608)
1350 (612)
1410 (640)
1456 (660)
1468 (666)
1498 (679)
1506 (683)
1650 (748)
1658 (752)
1703 (772)
2216 (1005)
2276 (1032)
2276 (1032)
2276 (1032)

6
699 (317)
705 (320)
827 (375)
880 (399)
887 (402)
887 (402)
908 (412)
908 (412)
1025 (465)
918 (416)
939 (426)
1167 (529)
1209 (548)
1209 (548)
1209 (548)

Table 1A Physical Data, English


UNIT SIZE 30HX
UNIT WEIGHT (lb)
Fluid Cooled (HXC)
Condenserless (HXA)
COMPRESSORS
Quantity
Nominal Capacity per
Compressor (tons)
Economizer
No. Capacity Steps
Standard
Optional (maximum)
Minimum Step Capacity (%)
Standard
Optional
REFRIGERANT
Charge* (lb) Circuit A/Circuit B
COOLER
Part No. 10HX400
Net Fluid Volume (gal)
Maximum Refrigerant Pressure
(psig)
Maximum Fluid-Side Pressure
(psig)
Fluid Connections
Inlet and Outlet (in.)
Drain (in. NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (lb air/min)
30HXA OIL SEPARATOR
Part No. 09RX400
Maximum Refrigerant Pressure
(psig)
Refrigerant Connections (in.)
Discharge
Liquid
Relief Valve
Connection (in. SAE Flare)
Flow Capacity (lb air/min)
CONDENSER (HXC)
Part No. 09RX400
Net Fluid Volume (gal)
Maximum Refrigerant Pressure
(psig)
Maximum Water-Side Pressure
(psig)
Water Connections (in.)
Inlet and Outlet
Drain (NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (lb air/min)

076

086

096

5700
4717

5723
4744

5855
4835

106

116

126

136

146

6177
6415
6465
5151
5163
5205
Semi-Hermetic, Twin Screw
2
2
2

6688
5309

6718
5333

39/39
No

46/39
No

56/39
No

66/39
No

66/46
No

66/56
No

80/56
No

80/66
No

6
8

6
8

6
8

6
8

6
8

6
8

6
8

6
8

20
10

20
10

20
10

20
10

20
10

20
10

60/60

76/65

124/89

119/100

001
17.0

001
17.0

006
24.0

006
24.0

220

220

220

220

220

220

220

220

300

300

300

300

300

300

300

300

12

12

12

12

12

12

12

12

34
31.7

34
31.7

3 4
31.7

3 4
31.7

3 4
31.7

3 4
31.7

3 4
31.7

34
31.7

165
320

165
320

166
320

166
320

167
320

167
320

167
320

167
320

218
118

218
118

218
118

218
118

218
118

218
118

218
118

218
118

58
21.6

58
21.6

5 8
21.6

58
21.6

173
16.8
220

173
16.8
220

5 8
5 8
5 8
5 8
21.6
21.6
21.6
21.6
Shell and Tube with Enhanced Copper Tubes
174
174
175
175
18.3
18.3
23.9
23.9
220
220
220
220

176
27.5
220

176
27.5
220

300

300

300

300

300

300

300

300

12

12

12

12

12

12

12

12

34
31.7

34
31.7

3 4
31.7

3 4
31.7

3 4
31.7

3 4
31.7

3 4
31.7

34
31.7

20
20
10
10
R-134a
94/70
110/70
105/76
112/89
Shell and Tube with Enhanced Copper Tubes
002
010
007
007
19.0
22.6
21.4
21.4

LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.

11

Table 1A Physical Data, English (cont)


UNIT SIZE 30HX
UNIT WEIGHT (lb)
Fluid Cooled (HXC)
Condenserless (HXA)
COMPRESSORS
Quantity
Nominal Capacity per
Compressor (tons)
Economizer
No. Capacity Steps
Standard
Optional (maximum)
Minimum Step Capacity (%)
Standard
Optional
REFRIGERANT
Charge* (lb) Circuit A/Circuit B
COOLER TYPE
Part No. 10HX400
Net Fluid Volume (gal)
Maximum Refrigerant Pressure
(psig)
Maximum Fluid-Side Pressure
(psig)
Fluid Connections
Inlet and Outlet (in.)
Drain (NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (lb air/min)
30HXA OIL SEPARATOR
Part No. 09RX400
Maximum Refrigerant Pressure
(psig)
Refrigerant Connections (in.)
Discharge
Liquid
Relief Valve
Connection (in. SAE Flare)
Flow Capacity (lb air/min)
CONDENSER (HXC)
Part No. 09RX400
Net Fluid Volume (gal)
Maximum Refrigerant Pressure
(psig)
Maximum Water-Side Pressure
(psig)
Water Connections (in.)
Inlet and Outlet
Drain (NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (lb air/min)

161

171

186

206

246

7452
5752

7660
5777

7854
10,581
10,969
5946
7,485
7,621
Semi-Hermetic, Twin Screw
2
3
3

261

271

10,992
7,621

11,029
7,621

80/56
Yes

66/80
Yes

80/80
Yes

66/39/80
Yes

80/56/80
Yes

80/66/80
Yes

80/80/80
Yes

6
8

6
8

6
8

8
11

8
11

8
11

8
11

20
10

20
10

20
10

150/110

119/140

104
28.5

012
28.5

220

220

220

220

220

220

220

300

300

300

300

300

300

300

12

12

12

34

34

34

34

34
31.7

3 4
31.7

34
31.7

3 4
31.7

3 4
31.7

34
31.7

34
31.7

167
320

168
320

168
320

106
320

106
320

106
320

106
320

218
138

218
138

218
138

218 (2)
158/138

218 (2)
158/138

218 (2)
158/138

218 (2)
158/138

58
21.6

5 8
21.6

58
21.6

58
21.6

177
30.6
220

178
37.6
220

180
55.1
220

180
55.1
220

300

300

300

300

300

300

300

12

12

12

34

34

34

34

34
31.7

3 4
31.7

34
31.7

3 4
31.7

3 4
31.7

34
31.7

34
31.7

13
13
13
7
7
7
R-134a
135/135
220/135
220/135
220/135
Shell and Tube with Enhanced Copper Tubes
013
125
126
126
33.4
43.1
47.2
47.2

58
5 8
5 8
21.6
21.6
21.6
Shell and Tube with Enhanced Copper Tubes
178
179
180
37.6
47.6
55.1
220
220
220

LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.
Circuit A/Circuit B.

12

13
7
220/135
126
47.2

Table 1B Physical Data, SI


UNIT SIZE 30HX
UNIT WEIGHT (kg)
Fluid Cooled (HXC)
Condenserless (HXA)
COMPRESSORS
Quantity
Nominal Capacity per
Compressor (kW)
Economizer
No. Capacity Steps
Standard
Optional (maximum)
Minimum Step Capacity (%)
Standard
Optional
REFRIGERANT
Charge* (kg) Circuit A/Circuit B
COOLER
Part No. 10HX400
Net Fluid Volume (L)
Maximum Refrigerant
Pressure (kPa)
Maximum Fluid-Side
Pressure (kPa)
Fluid Connections
Inlet and Outlet (in.)
Drain (NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (kg air/min)
30HXA OIL SEPARATOR
Part No. 09RX400
Maximum Refrigerant
Pressure (kPa)
Refrigerant Connections (in.)
Discharge
Liquid
Relief Valve
Connection (in. SAE Flare)
Flow Capacity (kg air/min)
CONDENSER (HXC)
Part No. 09RX400
Net Fluid Volume (L)
Maximum Refrigerant
Pressure (kPa)
Maximum Water-Side
Pressure (kPa)
Water Connections (in.)
Inlet and Outlet
Drain (NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (kg air/min)

076

086

096

2586
2140

2597
2152

2657
2194

106

116

2803
2911
2337
2342
Semi-Hermetic, Twin Screw
2
2

126

136

146

2933
2362

3034
2408

3048
2420

137/137
No

162/137
No

197/137
No

232/137
No

232/137
No

232/197
No

281/197
No

281/232
No

6
8

6
8

6
8

6
8

6
8

6
8

6
8

6
8

20
10

20
10

20
10

20
10

20
10

20
10

20
10

20
10

27.3/27.3

34.5/29.5

56.4/40.5

54.1/45.5

001
64.3

001
64.3

006
90.8

006
90.8

1517

1517

1517

1517

1517

1517

1517

1517

2068

2068

2068

2068

2068

2068

2068

2068

12

12

12

12

12

12

12

12

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

165
2205

165
2205

166
2205

166
2205

166
2205

167
2205

167
2205

167
2205

218
118

218
118

218
118

218
118

218
118

218
118

218
118

218
118

58
9.80

58
9.80

58
9.80

58
9.80

173
63.6
1517

173
63.6
1517

58
9.80
Tubes
175
90.5
1517

176
104.1
1517

176
104.1
1517

2068

2068

2068

2068

2068

2068

2068

2068

12

12

12

12

12

12

12

12

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

34
14.38

R-134a
42.7/31.8
50.0/31.8
47.7/34.5
50.9/40.5
Shell and Tube with Enhanced Copper Tubes
002
010
007
007
71.9
85.5
81.0
81.0

58
58
58
9.80
9.80
9.80
Shell and Tube with Enhanced Copper
174
174
175
69.3
69.3
90.5
1517
1517
1517

LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.

13

Table 1B Physical Data, SI (cont)


UNIT SIZE 30HX
UNIT WEIGHT (kg)
Fluid Cooled (HXC)
Condenserless (HXA)
COMPRESSORS
Quantity
Nominal Capacity per
Compressor (kW)
Economizer
No. Capacity Steps
Standard
Optional (maximum)
Minimum Step Capacity (%)
Standard
Optional
REFRIGERANT
Charge* (kg) Circuit A/Circuit B
COOLER
Part No. 10HX400
Net Fluid Volume (L)
Maximum Refrigerant
Pressure (kPa)
Maximum Fluid-Side
Pressure (kPa)
Fluid Connections
Inlet and Outlet (in.)
Drain (NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (kg air/min)
30HXA OIL SEPARATOR
Part No. 09RX400
Maximum Refrigerant
Pressure (kPa)
Refrigerant Connections (in.)
Discharge
Liquid
Relief Valve
Connection (in. SAE Flare)
Flow Capacity (kg air/min)
CONDENSER (HXC)
Part No. 09RX400
Net Fluid Volume (L)
Maximum Refrigerant
Pressure (kPa)
Maximum Water-Side
Pressure (kPa)
Water Connections (in.)
Inlet and Outlet
Drain (NPT)
Relief Valve
Connection (in. NPTF)
Flow Capacity (kg air/min)

161

171

186

3381
2610

3475
2621

3564
2698

206

246

261

271

4799
4976
3395
3457
Semi-Hermetic, Twin Screw
3
3

4986
3457

5003
3457

281/197
Yes

232/281
Yes

281/281
Yes

232/137/281
Yes

281/197/281
Yes

281/232/281
Yes

281/281/281
Yes

6
8

6
8

6
8

8
11

8
11

8
11

8
11

20
10

20
10

20
10

68.2/50.0

54.1/63.6

104
107.9

012
107.9

1517

1517

1517

1517

1517

1517

1517

2068

2068

2068

2068

2068

2068

2068

12

12

12

34

34

34

34

34
14.28

3 4
14.38

3 4
14.38

34
14.38

3 4
14.38

3 4
14.38

3 4
14.38

167
2205

168
2205

168
2205

106
2205

106
2205

106
2205

106
2205

218
138

218
138

218
138

218 (2)
158/138

218 (2)
158/138

218 (2)
158/138

218 (2)
158/138

58
9.80

5 8
9.80

177
115.8
1517

178
142.3
1517

2068

2068

2068

2068

2068

2068

2068

12

12

12

34

34

34

34

34
14.38

3 4
14.38

3 4
14.38

34
14.38

3 4
14.38

3 4
14.38

3 4
14.38

13
13
13
7
7
7
R-134a
61.2/61.2
99.8/61.2
99.8/61.2
99.8/61.2
Shell and Tube with Enhanced Copper Tubes
013
125
126
126
126.4
163.2
178.7
178.8

5 8
58
9.80
9.80
Shell and Tube with Enhanced
178
179
142.3
177.9
1517
1517

LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.
Cricuit A/Circuit B.

14

5 8
5 8
9.80
9.80
Copper Tubes
180
180
208.6
208.6
1517
1517

13
7
99.8/61.2
126
178.7

5 8
9.80

180
208.6
1517

5. Bolt the weld flanges back onto their respective fluid heads.

Do not remove unit from skid until unit is in its final


location. Rig from the rigging holes provided in the top
heat exchanger. See Fig. 1-9 for rigging and center of gravity information. Lower the unit carefully onto the floor or
roller. Push or pull only on the skid, not the unit. If the unit
is moved on rollers, use a minimum of 3 evenly-spaced
rollers.

IMPORTANT: When bolting the weld flange to the


fluid heads, be sure to locate the flanges so that the
holes in each flange are completely aligned with the
holes in each fluid head. If installed incorrectly, part
of the holes in the fluid head will be blocked off.
This will result in impaired fluid flow and high pressure drop.

IMPORTANT: Some of the unit skids are larger than


standard door openings. Be sure that the path to the
units final destination is wide enough to accommodate unit shipping skid. Remove the skid if necessary. If skid is removed and rollers are used, attach
rollers to unit tube sheets while moving unit.

Tighten all cooler head bolts to 250 ft-lb (339 N-m)


before filling system with water (or brine).

Areas where unit mounting points will be located must be


level to within 1/16 in. per ft (5 mm per m) along the long
axis of the unit. Once unit is in place and level, bolt unit to
the floor. Use isolation pads under the unit to aid in vibration
isolation as required.

6. Install field-supplied differential flow switches in the cooler


piping for protection against loss of flow. The differential
flow switches must be installed on top of the pipe in a
horizontal run and should be at least 5 pipe diameters from
any bend. Install the low-pressure differential flow switch
into the outlet piping, and install the high-pressure differential flow switch into the inlet line piping as shown
in Fig. 12.

Step 3 Piping Connections See Fig. 10 and


11 for typical piping applications.
COOLER FLUID, VENT, AND DRAIN The inlet (return) fluid connection is always the lower of the 2 cooler
connections. See Fig. 10 for locations. A screen strainer with
a minimum of 20 mesh should be installed ahead of the cooler
inlet to prevent debris from damaging internal tubes of the
cooler. Outlet (supply) fluid connection is the upper connection of the 2 cooler connections.
The cooler has weld flanges to connect the field-supplied
piping. Plan the piping arrangement in accordance with good
piping practices and so that the piping does not cross in front
of the cooler head. Use flexible connections on cooler piping to reduce vibration transmission. Offset the piping to permit removal of the cooler head for maintenance. Install pipe
hangers where needed. Make sure no weight or stress is placed
on the water nozzle.
To install cooler piping:
1. Remove bolts on weld flanges, and remove flanges from
cooler fluid heads.

IMPORTANT: Loss of flow protection is required


for all 30HX chillers.
7. Provide openings in fluid piping for pressure gages and
thermometers (if used). These openings should be 5 to 10
pipe diameters from the unit water nozzles. For thorough
mixing and temperature stabilization, wells in the leaving fluid pipe should extend at least 2 in. (50 mm) into
the pipe.
Accessory Victaulic-type connections are available. Follow the connection directions provided with the accessory.
Although cooler has an air vent, it is recommended that a
field-supplied air vent be installed in the system to facilitate
servicing. Field-supplied shut-off and balancing valves should
also be installed to facilitate servicing and flow balancing.
Locate valves in return and supply fluid lines as close to
the chiller as possible. Locate air vent at highest point of the
cooler fluid system. See Fig. 10.
Provide drain connections at all low points to permit complete drainage of the system.
BRINE UNITS Special factory modifications to the units
are required to allow them to operate at fluid temperatures
less than 34 F (1.1 C). Be sure that the fluid has sufficient
inhibited ethylene glycol or other suitable corrosionresistant antifreeze solution to prevent cooler freeze up.
PREPARATION FOR YEAR-ROUND OPERATION In
areas where the piping or unit is exposed to 32 F (0 C) or
lower ambient temperatures, freeze-up protection is recommended using inhibited ethylene glycol or other suitable
corrosion-resistant antifreeze solution and electric heater tapes.
Heater tapes should have a rating for area ambient temperatures and be covered with a suitable thickness of closed-cell
insulation. Route power for the heater tapes from a separately fused disconnect. Mount the disconnect within sight
from the unit per local or NEC codes. Identify disconnect as
heater tape power source with warning that power must not
be turned off except when servicing unit.

Remove the weld flanges before welding piping to


the flanges. Refer to Fig. 1-8 for weld flange locations. Failure to remove the flanges may damage the
temperature sensors.
2. To keep debris from entering the heat exchanger during
shipping and storage, the gaskets between the weld flanges
and the fluid heads are solid sheets that block off the
fluid connections. Remove bolts on weld flanges, and remove the perforated gasket material blocking the connections manually, or if necessary, use a sharp knife to
carefully cut along the perforations to remove the excess
gasket material.
IMPORTANT: Be sure to remove flanges and cut
holes in the gaskets between the flanges and the fluid
heads as indicated.
3. Apply a thin coat of oil to both sides of each gasket to
help ensure a good seal, and reattach each gasket to each
fluid head.
4. Using appropriate precautions to avoid warping or deforming the weld flanges, weld the field-supplied piping
to the flanges.

FILL FLUID LOOP Fill the fluid loop with water (or brine)
and a corrosion-resistant inhibitor suitable for the water of
the area. Consult the local water authority for characteristics
of area water and a recommended inhibitor for the cooler
fluid loop.
15

16
Fig. 10 Typical Cooler (30HXA, HXC) and Condenser (30HXC Only) Piping and Wiring

NOTES:
1. Wiring and piping shown are for general point-of-connection only and are not
intended to show details for specific installation. Certified field wiring and dimensional diagrams are available upon request. The 30HXA and HXC units should be
installed using certified drawings.
2. All wiring must comply with applicable codes.
3. Refer to Carrier System Design Manual for details regarding piping techniques.
4. Piping, wiring, switches, valves, vent, gages, strainers, drain, and vibration isolation are all field supplied.
5. Water connections are shown on left side of control box in this figure. Actual connections are on right side of control box.

LEGEND
Field Wiring
Field Piping

NOTES:
1. Piping shown is for general point-of-connection only and is not intended to show
details for a specific installation. Certified field wiring and dimensional drawings
are available upon request. The 30HXA units should be installed using certified
drawings.
2. Refer to Carrier System Design Manual for details regarding piping techniques.
3. Piping and pressure relief devices are field supplied.
4. Vent pipes properly per local codes.
ACCESSORY SOUND ENCLOSURE

RELIEF VALVES
(IF REQUIRED BY
CODE)

COMPRESSOR

DOUBLE RISER
(IF REQUIRED)
COOLER*

OIL
SEPARATOR

DISCHARGE
LINES
LIQUID LINES
LIQUID LINE
SOLENOID VALVES
LIQUID LINE
(IF REQUIRED)
ANGLE VALVE
MECHANICAL ROOM

CONDENSER

*See Fig. 10 for typical cooler piping.

Fig. 11 Typical 30HXA Refrigerant Piping to Remote Condenser

LEGEND
COM Common
N.O. Normally Open

Fig. 12 Differential Flow Switch

17

30HXA Low-Ambient Considerations In installations


where outdoor ambient temperatures may be below 34 F
(1.1 C), it is recommended that inhibited ethylene glycol or
other suitable corrosion-resistant antifreeze solution be used in
the cooler loop to prevent cooler freeze-up.
If valves are installed in the liquid lines, it is recommended
that field-supplied pressure relief valves be installed in each
liquid line and the pressure setting should be 320 psig
(2205 kPa). Most local codes require that the relief valves be
vented directly outdoors. The vent must not be smaller than the
relief valve outlet.
Fan-Cycling Pressure Switches In order to provide proper
head-pressure control in 30HXA units, install fan-cycling pressure switches in each circuit in the liquid line between the separate condenser unit and expansion device. The switches are
shipped from the factory with the 30HXA units. Refer to the
Carrier 09DK condenser installation literature for details on the
location and installation of the switches. Since the 30HXA is
an HFC-134a unit, switch selection is based on R-134a refrigerant pressures.
NOTES: The switches that are standard with the Carrier 09DK
condensers are designed for R-22 operation and must not
be used. Instead use the switches shipped with the chiller
(Part No. HK02YB097). Switches open at 97 psig ( 10 psi),
and close at 185 psig ( 10 psi).
Back-Pressure Valve, 30HXA Units The 30HXA backpressure valves are supplied with an integral mounting flange.
The valves mount on the 30HXA oil separator. This eliminates
unnecessary brazing when installing the discharge piping, and
allows the installer to orient the valve in any desired manner.

A drain connection is located at the bottom of the cooler


head. See Fig. 1-8 for connection location. Install shut-off
valves to the drain line before filling the system with fluid.
IMPORTANT: Before starting the unit, be sure all of the
air has been purged from the system.
INSULATE COOLER HEADS Once the cooler water
lines and drain and vent lines have been installed and checked
for leaks, insulate the cooler heads with a suitable thickness of
closed-cell insulation. This will minimize the amount of condensation that forms on the cooler heads. When insulating the
cooler heads, allow for service access and removal of heads.
IMPORTANT: Before starting the unit, be sure all of the
air has been purged from the system.
30HXA PIPING, VALVE, AND SWITCH
INSTALLATION
Relieve Pressure and Recover Refrigerant The 30HXA
units are shipped from the factory with a holding charge of
R-134a. Before opening the refrigerant system, relieve system
pressure and recover system refrigerant through the charging
valve on the cooler.
30HXA Refrigerant Piping (See Fig. 11) When running
the refrigerant piping from the 30HXA unit to the remote condenser(s), avoid excessive pressure drops. Minimizing line
pressure drop is critical to the proper operation of the unit expansion device. The pressure drop using R-134a refrigerant is
different than when using R-22 refrigerant. See Tables 2 and 3
for an example for a 2 F (1.1 C) pressure drop in saturated temperature in the discharge (hot gas) line and liquid line, respectively. Refer to Fig. 13 and 14 for line sizing information for
the discharge and liquid lines for 30HXA (R-134a) units.

IMPORTANT: The back-pressure valves are not


mounted to the 30HXA chiller at the factory. They are
packaged and supplied attached to the unit shipping
skid. These valves must be installed at the time of chiller
installation. Failure to install the back-pressure valves
will result in improper unit operation.

Table 2 Discharge Line 2 F (1.1 C) Drop in


Saturated Temperature Example
SATURATED
DISCHARGE
TEMP
F
C
126
52.2
124
51.1
PRESSURE

PRESSURE
R-134a
Psig
187.5
182.0
5.5

Complete the steps below to install the flanged backpressure valves on the 30HXA chiller before running discharge
piping. Follow these steps for both refrigerant circuits.
1. Be sure to remove nitrogen charge or properly recover
refrigerant charge before removing the blank-off plate.
Remove the blank-off plate from the mating flange on
top of the coil separator by removing the screws from
the flange. See Fig. 15 for location.
2. Using the screws that were removed in Step 1, bolt the
flanged back-pressure valve to the mating flange on
top of the coil separator. An O-ring is included in the
box with the back-pressure valve for sealing the
flange.
The valve may be oriented in any desired position in to
make discharge piping easier. Install pipe hangers
where needed. Make sure no weight or stress is placed
on the back-pressure valve.

R-22

kPa
1293
1255
38

Psig
281.6
274.3
7.3

kPA
1942
1891
51

Table 3 Liquid Line 2 F (1.1 C) Drop in


Saturated Temperature Example
SATURATED
LIQUID
TEMP
F
C
100
37.7
98
36.7
PRESSURE

PRESSURE
R-134a
Psig
124.3
120.1
4.2

kPa
857
828
29

R-22
Psig
195.9
190.2
5.7

kPA
1351
1311
40

Discharge lines should be looped above the compressors to


prevent charge from flowing back to the oil separator and compressor during unit shutdown. The discharge line must be
brazed to the back-pressure valve located on the top of the oil
separator. The valve cap that is brazed to the back-pressure
valve at the factory must be removed prior to brazing the discharge line. Be sure to wrap back-pressure valve when brazing
discharge line to avoid damaging the valve.

18

3. Once the back-pressure valve has been mounted to the


mating flange, and the piping is properly supported, a fieldsupplied 14-in. (6.4 mm) copper line must be run from
the 14-in. NPT port on the back-pressure valve cap to the
14-in. SAE flare fitting on the motor cooling line. The
equalizer line must be installed in order for the unit to
function properly.
NOTE: A ball valve can be installed in the equalizer line
to facilitate servicing.
4. After mounting the back-pressure valve to the unit, properly supporting it, and running the 14-in. equalizer line,
the discharge piping may be installed.
5. Repeat Steps 1-4 for the other refrigerant circuit.

Remove the weld flanges before welding piping to


the flanges. Refer to Fig. 1-8 for weld flange locations. Failure to remove the flanges may cause damage to the unit.
2. To keep debris from entering the heat exchanger during
shipping and storage, the gaskets between the weld flanges
and the fluid heads are solid sheets that block off the fluid
connections. Remove the perforated gasket material blocking the connections manually, or if necessary, use a sharp
knife to carefully cut along the perforations to remove
the excess gasket material.

Evacuation and Dehydration Because the 30HXA


systems use polyolester oil, which can absorb moisture, it
is important to minimize the amount of time that the system interior is left exposed to the atmosphere. Minimizing
the exposure time of the oil to the atmosphere will minimize the amount of moisture that needs to be removed during evacuation.
Once all of the piping connections are complete, leak
test the unit and then pull a deep dehydration vacuum. Connect the vacuum pump to the charging valve at the bottom
of the oil separator and to the liquid line service valve. For
best results, it is recommended that a vacuum of at least
500 microns (0.5 mm Hg) be obtained. Afterwards, to
ensure that no moisture is present in the system, perform a
standing vacuum-rise test.
With the unit in deep vacuum (500 microns or less), isolate the vacuum pump from the system. Observe the rateof-rise of the vacuum in the system. If the vacuum rises by
more than 50 microns in a 30-minute time period, then
continue the dehydration process. Maintain a vacuum on the
system until the standing vacuum requirement is met. This
will ensure a dry system.
By following these evacuation and dehydration procedures, the amount of moisture present in the system will
be minimized, and the factory-supplied filter driers will
provide adequate moisture protection. If additional moisture
protection is desired, additional filter-driers may be installed
in the liquid lines between the condenser(s) and expansion
devices. Be sure to consider the pressure drop of the filter
drier when determining piping requirements.
For further 30HXA piping instructions, proceed to the section titled Install Pressure Relief Refrigerant Vent Piping,
page 21.
30HXC PIPING AND VALVE INSTALLATION
30HXC Condenser Connections The inlet fluid connection is always the lower of the 2 condenser connections.
It is recommended that a screen strainer with a minimum of
20 mesh be installed ahead of the condenser inlet to prevent
debris from damaging the internal condenser tubes.
The outlet water connection is the upper connection of
the 2 connections. The condenser has weld couplings to connect field-supplied piping. Plan the piping arrangement in
accordance with good piping practices and so that the piping
does not cross in front of the condenser head. Use flexible
connections on the condenser piping to reduce vibration transmission. Offset the piping to permit condenser head removal
for maintenance purposes. Install pipe hangers where needed.
Make sure no weight or stress is placed on the water nozzle.
To install condenser piping:
1. Remove bolts on weld flanges, and remove flanges from
condenser water heads.

IMPORTANT: Be sure to remove flanges and cut


holes in the gaskets between the flanges and the water heads as indicated.
3. Apply a thin coat of oil to both sides of each gasket to
help ensure a good seal, and reattach each gasket to each
water head.
4. Weld the field-supplied piping to the weld flanges.
NOTE: Use appropriate precautions when welding to avoid
warping or deforming the weld flanges.
5. Bolt the weld flanges back onto their respective water heads.
IMPORTANT: When bolting the weld flanges to the
fluid heads, be sure to locate the flanges so that the
holes in the flanges are completely aligned with the
holes in the fluid heads. If flanges are installed incorrectly, parts of the holes in the fluid head can be
blocked off. This will result in impaired fluid flow
in high pressure drop applications.

Tighten all condenser head bolts to 250 ft-lb (339 N-m)


before filling system with water (or brine).
Provide openings in water piping for pressure gages
and thermometers (if used). These openings should be 5 to
10 pipe diameters from the unit water nozzles. For thorough
mixing and temperature stabilization, wells in the leaving
water pipe should extend at least 2 in. (50 mm) into the pipe.
Accessory Victaulic-type connections and condenser
water thermistors are available. Follow the connection
directions as provided with the accessory. If accessory differential pressure switch, water flow switch, or condenser
water thermistor is to be installed, install the proper fittings
into the condenser water lines before water is connected.
Although condenser has an air vent, it is recommended
that a field-supplied air vent be installed in the system to
facilitate servicing. Field-supplied shut-off and balancing valves
should also be installed to facilitate servicing and flow balancing. Locate valves in inlet and outlet lines as close to the
chiller as possible. Locate air vents at the highest point of
the system loop. See Fig. 10.
Provide drain connections at all low points in the loop to
permit complete system drainage.
IMPORTANT: Before starting the unit, be sure all of
the air has been purged from the system.

19

500

137.2

450

121.9

400

106.7

350

91.4

76.2

61.0

45.7

EQUIVALENT LINE LENGTH (FT)

EQUIVALENT LINE LENGTH (M)

152.4

300

250

200
15

/8"

150

.3

13

/8"

100

30.4

15.2

50

(41

mm

(34

.9 m

m)

1 1/8

" (28

30

40

50

60

70

.6 m

80

m)

100

90

110

120

130

140

150

160

170

180

190

200

457

492

527

562

598

633

668

703

TONS COOLING
105

141

176

211

246

280

387
422
kW COOLING

352

316

NOTES:
1. Values are for a 2 F pressure drop at 125 F (51.7 C)
saturated discharge temperature, and 105 F (40.6 C)
liquid refrigerant temperature.
2. Size each circuit separately.

152.4

500

137.2

450

121.9

400

106.7

350

91.4

76.2

61.0

45.7

30.4

EQUIVALENT LINE LENGTH (FT)

EQUIVALENT LINE LENGTH (M)

Fig. 13 R-134a Liquid Line Sizing, 30HXA Units

300

250
31

/8"

200

(79

.4)

mm

150
2 5/8

" (66

100
2 1/

8" (5

15.2

50

0
30

40

50

60

70

80

90

4.0

.7 m

m)

mm

100

130

140

457
422
387
kW COOLING

492

110

120

150

160

170

180

190

200

TONS COOLING
105

141

176

211

246

281

316

352

NOTES:
1. Values are for a 2 F pressure drop at 125 F (51.7 C)
saturated discharge temperature, and 105 F (40.6 C)
liquid refrigerant temperature.
2. Size each circuit separately.

Fig. 14 R-134a Discharge Line Sizing, 30HXA Units


20

527

562

598

633

668

703

Fig. 15 Field-Supplied 14-in. (6.4 mm) Copper Tube, 30HXA Units


30HXC Condenser Temperature Regulating Valve For
installations where entering condensing water temperature
could be below 70 F (21.1 C), a field-supplied leaving water
temperature regulating valve is required. Operation below
70 F (21.1 C) without this valve may cause the unit to shut
down on low oil pressure alarms.
NOTE: This valve should be a temperature-controlled valve
(DO NOT USE a pressure-controlled valve) which controls
to 80 F (26.7 C) leaving water temperature. A valve that can
be controlled by a 4 to 20 mA signal is also supported by the
product integrated control (PIC) options module. Figure 16
shows the installation details for the regulating valve.

piping is required by local codes, these connections have been


provided to aid in the connection of vent piping in
accordance with ASHRAE 15 (American Society of Heating, Refrigeration, and Air Conditioning Engineers), Safety
Code for Mechanical Refrigeration. If vent piping is
required, do not restrict the vent flow in any way.
NOTE: When accessory suction service valve kit is installed, there are 2 additional high-side pressure relief valves.
These are located on the discharge line between the muffler
and the discharge shut-off valve. Pipe these valves per local
codes.

IMPORTANT: A separate, field-supplied power supply must be used with the 4 to 20 mA valve. Failure
to use a separate power supply may result in damage
to the chiller processor module (PSIO).

electrical characteristics of the available power supply must


agree with the unit nameplate rating. Supply voltage must
be within the limits shown.
FIELD POWER CONNECTIONS (See Fig. 17 and 18)
All power wiring must comply with applicable local and national codes. Install field-supplied, branch circuit fused disconnect(s) of a type that can be locked off or open. Disconnect(s) must be located within sight and readily accessible
from the unit in compliance with NEC Article 440-14. See
Tables 4A and 4B for unit electrical data. See Tables 5A and
5B for compressor electrical data.

Step 4 Make Electrical Connections The

IMPORTANT: On brine applications where leaving


cooler water is less than 34 F (1.1 C), a minimum
water flow of 0.75 gpm/ton (0.14 L/s per kW) should
be maintained at all times.
INSTALL PRESSURE RELIEF REFRIGERANT VENT
PIPING The low side relief valves on all units are provided with 34-in. female NPT connections, and are located
on top of the cooler shell. See Fig. 1-8. There are 2 relief
valves for the cooler; one on each circuit. Make the vent
connection to the low side relief valve by installing a male
NPT to copper OD braze adapter. Braze a 90 degree shortradius elbow to the adapter. This will allow enough space to
make vent connections to the elbow.
The 30HXA high side relief valves are provided with a
58-in. SAE (Society of Automotive Engineers, U.S.A.) flare
connection. The 30HXC high side relief valves are provided
with a 14-in. female NPT flare connection, and are located
on the bottom of the condenser shell.
There are 2 relief valves for the oil separator (30HXA)
or condenser (30HXC); one for each circuit. Most local codes
require that these devices be piped to the outside. If vent

IMPORTANT: The 30HX units have a factory-installed


option available for a non-fused disconnect for unit power
supply. If the unit is equipped with this option, all field
power wiring should be made to the non-fused disconnect since no terminal blocks are supplied.
All units have a single location for power entry to simplify the field power wiring. Maximum wire size that the
unit terminal block or non-fused disconnect will accept is
500 kcmil.
All units require at least one field-supplied power supply.
Refer to Fig. 17 and 18 for a list of units that require 2 fieldsupplied power supplies. Units that require 2 power supplies
are listed under TB1B in the Standard Power and NonFused Disconnect Option sections of Fig. 17 and 18.
Copy continued on page 25.
21

OUTLET

30HXC CONDENSER

SENSOR
INLET

TEMPERATURE CONTROLLED VALVE (PENN VALVE)


BYPASS VALVE

OUTLET

30HXC CONDENSER
SENSOR

INLET

TEMPERATURE CONTROLLED VALVE

OPTIONAL BYPASS VALVE FOR NORMAL DUTY.


BYPASS VALVE REQUIRED FOR BRINE
APPLICATIONS TO PREVENT CONDENSER FREEZE-UP.

CHILLER CONTROL PANEL

OUTLET

30HXC CONDENSER

INLET

4 TO 20 mA WATER REGULATING VALVE


(SEPARATE FIELD-SUPPLIED POWER SUPPLY REQUIRED)

Fig. 16 Condenser Temperature Regulating Valve Installation

22

23
ALM
CA-1M
CB-1M
CCN
CDFC
CDFS
CDWP
CWFS
CWP
CWPI
LLSV
NEC
TB

LEGEND
Alarm
Compressor A1, 1M Contactor
Compressor B1, 1M Contactor
Carrier Comfort Network
Condenser Fan Contactor
Condenser Flow Switch
Condenser Water Pump
Chilled Water Flow Switch
Chilled Water Pump
Chilled Water Pump Interlock
Liquid Line Solenoid Valve
National Electrical Code
Terminal Block
Field Power Wiring
Field Control Wiring
Factory Installed Wiring

Fig. 17 Field Wiring, 30HXA,C076-186

NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be
in compliance with all applicable codes.
2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Maximum incoming wire
size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source (except 380/415 v units) through a fieldsupplied disconnect with 15 amp maximum protection for 115 volt control circuits and 15 amp maximum protection for 230 volt control circuit. Connect control circuit power to terminals 1 and 2 of TB4. Control circuit
conductors for all units must be copper only. Control circuit power is factory wired for 380/415 v units.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The contacts must be rated
for dry circuit application capable of handling a 24 vac to 50 mA load. Remove jumper between 13 and 14 of
TB2 if remote ON-OFF is installed.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI)
functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
6. Terminals 4 and 5 of TB2 are for control of chilled water pump starter. The maximum load allowed for the chilled
water pump relay is 125 va sealed, 1250 va inrush at 115 or 230 volt.
7. Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va
inrush at 115 or 230 volt.
8. Terminal 6 of TB2 is for condenser water pump (HXC only) or circuit B condenser fan contactor (HXA only).
Terminal 1 of TB2 is for circuit A condenser fan contactor (HXA only). The maximum load allowed is 125 va
sealed, 1250 va inrush at 115 or 230 volt. Install CDWP or CDFC-B between TB2-6 and TB4-2 (unit control
power neutral). Install CDFC-A between TB2-1 and TB4-2 (unit control power neutral). Separate field power
supply is not required.
9. Terminals J7-25 and J7-32 of PSIO2 are for condenser flow switch (CDFS). The contacts must be rated for dry
circuit application capable of handling a 24 vac to 50 mA load. Separate field power supply is required.

24
ALM
CA-1M
CB-1M
CCN
CDFC
CDFS
CDWP
CWFS
CWP
CWPI
LLSV
NEC
TB

LEGEND
Alarm
Compressor A1, 1M Contactor
Compressor B1, 1M Contactor
Carrier Comfort Network
Condenser Fan Contactor
Condenser Flow Switch
Condenser Water Pump
Chilled Water Flow Switch
Chilled Water Pump
Chilled Water Pump Interlock
Liquid Line Solenoid Valve
National Electrical Code
Terminal Block
Field Power Wiring
Field Control Wiring
Factory Installed Wiring

Fig. 18 Field Wiring, 30HXA,C206-271

NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be
in compliance with all applicable codes.
2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Maximum incoming wire
size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source (except 380/415 v units) through a fieldsupplied disconnect with 15 amp maximum protection for 115 volt control circuits and 15 amp maximum protection for 230 volt control circuit. Connect control circuit power to terminals 1 and 2 of TB4. Control circuit
conductors for all units must be copper only. Control circuit power is factory wired for 380/415 v units.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The contacts must be rated
for dry circuit application capable of handling a 24 vac to 50 mA load. Remove jumper between 13 and 14 of
TB2 if remote ON-OFF is installed.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI)
functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
6. Terminals 4 and 5 of TB2 are for control of chilled water pump starter. The maximum load allowed for the chilled
water pump relay is 125 va sealed, 1250 va inrush at 115 or 230 volt.
7. Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va
inrush at 115 or 230 volt.
8. Terminal 6 of TB2 is for condenser water pump (HXC only) or circuit B condenser fan contactor (HXA only).
Terminal 1 of TB2 is for circuit A condenser fan contactor (HXA only). The maximum load allowed is 125 va
sealed, 1250 va inrush at 115 or 230 volt. Install CDWP or CDFC-B between TB2-6 and TB4-2 (unit control
power neutral). Install CDFC-A between TB2-1 and TB4-2 (unit control power neutral). Separate field power
supply is not required.
9. Terminals J7-25 and J7-32 of PSIO2 are for condenser flow switch (CDFS). The contacts must be rated for dry
circuit application capable of handling a 24 vac to 50 mA load. Separate field power supply is required.

FIELD CONTROL POWER CONNECTIONS (See Fig. 17


and 18) Units with a power supply of 208/230-, 460-, and
575-3-60 require a separate 115-1-60 control circuit power
supply. Units with a 380/415-3-50 power supply have factory pre-wired 230-1-50 control circuit power. A separate power supply is NOT required for these units. All other
units require a separate 230 v control circuit power supply.
Field control power connections are made at terminals 1 and
2 of TB4.
NOTE: Units with a 380/415 V main power supply do NOT
require a separate field-supplied control power supply. These
units have factory pre-wired control power.
Terminals TB2-11 and TB2-12 are provided for field
installation of a chilled water (fluid) pump interlock (CWPI)
and a chilled water (fluid) flow switch (CWFS). These
devices must be installed in series. Contacts must be rated
for dry circuit applications capable of handling a 24-vac to
50 mA load.
An accessory remote on-off switch can be wired into TB2-13
and TB2-14. See Fig. 17 and 18 for remote on-off, CWPI,
and CWFS wiring. Contacts must be rated for dry circuit
application capable of handling a 24-vac to 50 mA load.

NOTE: The fan contactor relays are pre-wired to unit control power. A separate power supply is NOT required. The
maximum load allowed for these relays is 125 va sealed,
1250 va inrush at 115 or 230 volts.

Step 5 Install Accessories


ELECTRICAL Several optional control accessories are
available to provide the following features:
Control transformer
Cooler pump/flow switch interlock
Cooler pump control
Expanded display panel
Remote alarm
Remote on-off
Pulldown control
Occupancy scheduling
Demand limit control
Temperature reset (from occupied space or outdoor-air
temperature)
Dual set point control
Condenser water sensors
Level II communications
(CCN [Carrier Comfort Network])
Refer to Controls, Start-up, Operation, Service, and Troubleshooting literature and separate accessory installation
instructions for additional information.
30HXA LOW-AMBIENT OPERATION If outdoor ambient operating temperatures below 60 F (15 C) are
expected, refer to separate Carrier 09DK condenser unit
installation instructions for low-ambient operation using
accessory Motormastert III control.
MINIMUM LOAD ACCESSORY If minimum load
accessory is required, use the appropriate package. Refer to
unit Price Pages or contact your local Carrier representative
for more details. For installation details, refer to separate installation instructions supplied with the accessory
package.
MISCELLANEOUS ACCESSORIES For applications
requiring special accessories, the following packages are available: control power transformer, sound reduction enclosure,
external vibration isolation, expanded display, Victaulictype connections, temperature reset sensor, and chilled fluid
flow switch. Refer to individual accessory installation
instructions for installation details.

Do not use interlocks or other safety device contacts connected between TB2 terminals 13 and 14 as remote
on-off. Connection of safeties or other interlocks between these 2 terminals will result in an electrical
bypass if the REMOTE-OFF-LOCAL switch is in
the LOCAL position. If remote on-off unit control is
required, a field-supplied relay must be installed in the
unit control box and wired as shown in Fig. 17 and 18.
Failure to wire the remote on-off as recommended will
result in tube freeze damage.
Terminals 2 and 3 of TB2 have been provided for a fieldsupplied remote alarm (ALM). If an audible alarm is
installed, an alarm shutoff is also recommended. Contacts
are rated for 125 va at either 115 or 230 v control power. See
Fig. 17 and 18.
Terminals 4 and 5 of TB2 have been provided for a fieldsupplied chilled water (fluid) pump relay (CWP). Use relays
with a coil rating of at least 75 va. A field-supplied power
supply of appropriate voltage must be provided. Contacts are
rated for 125 va at either 115 or 230 v control power. See
Fig. 17 and 18.
Terminal 6 of TB2 has been provided for a field-supplied
Circuit B fan control relay for the remote condenser (30HXA)
or a condenser pump relay (30HXC). Use relays with a coil
rating of at least 75 va. Terminal 1 of TB2 has been provided
for a field-supplied Circuit A fan control relay for a remote
condenser (30HXA only). Use relays with a coil rating of at
least 75 va. A separate field power supply is NOT required.
Connect Circuit B fan relay/Condenser Pump Relay between TB2-6 and TB4-2 (control power neutral). Use relays
with a coil rating of at least 75 va. Connect Circuit A fan
relay between TB2-1 and TB4-2. Maximum Load Allowed
for the fan/condenser pump relays is 125 va sealed, 1250 va
inrush at 115 or 230 volts.
CONDENSER FAN CONTROL FOR CONDENSER UNITS
USED WITH 30HXA UNITS The PIC control options
module and optional relay board provide two control outputs for energizing and deenergizing remote fan contactors.
If desired, wire the Circuit A main fan contactor between
TB2-1 and the unit control power neutral (TB4-2). The
Circuit B main fan contactor may be wired between TB2-6
and the unit control power neutral (TB4-2). This will cause
the main fans to be on when the compressors are on. Refer
to Fig. 17 and 18 for wiring details.

Step 6 Leak Test Unit


30HXC UNITS These units are shipped from the factory with a full charge of R-134a or a nitrogen holding charge
(see Tables 1A and 1B). Perform a leak test to ensure that
leaks have not developed during unit shipment. Dehydration
of the system is not required unless the entire refrigerant charge
has been lost. There are a number of Swage-Lok fittings used
on the refrigerant piping. If a leak is detected at any of these
fittings, tighten outside nut 18 turn.

DO NOT OVERTIGHTEN THESE FITTINGS. Overtightening will result in the tube being crushed and will
cause a refrigerant system leak.
30HXA UNITS These units are shipped with a holding
charge of R-134a. Leak test and dehydrate the complete system (including both field and factory installed piping).
NOTE: Proper dehydration of 30HXA units is important to
ensure that no moisture is left in the system. Refer to the
separate section on Evacuation and Dehydration on page 19.
Copy continued on page 40.
25

Table 4A Unit Electrical Data, 30HXC Units

UNIT
30HXC

076

086

096

106

116

126

136

VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50

POWER CIRCUIT*

CONTROL CIRCUIT

ICF

MCA

MOCP

Recommended
Fuse Size

Voltage
(Single
Ph)

Min

Max

MCA

MOCP

WD

XL

187
187
414
518
342

253
253
506
633
418

123
123
100
80
121

200
200
150
110
175

175
150
125
100
150

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

307
307
148
118
169

374
299
419

207
207
342

253
253
440

115
115
126

200
200
175

150
150
150

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

266
266
165

400

187
187
414
518
342

253
253
506
633
418

148
123
111
89
135

250
200
150
125
200

200
150
125
100
175

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

307
307
148
118
169

374
299
419

207
207
342

253
253
440

140
115
140

250
200
200

75
150
175

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

305
305
190

479

187
187
414
518
342

253
253
506
633
418

181
122
126
101
153

300
200
175
150
225

225
150
150
125
175

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

354
354
172
137
195

449
359
502

207
207
342

253
253
440

169
115
158

300
200
225

225
150
200

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

347
347
216

562

187
187
414
518
342

253
253
506
633
418

219
123
143
115
174

350
200
200
175
250

300
150
175
150
200

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

405
405
197
158
223

529
423
590

207
207
342

253
253
440

202
115
178

350
200
250

250
150
225

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

397
397
247

661

187
187
414
518
342

253
253
506
633
418

219
148
153
122
185

350
250
225
175
250

300
200
175
150
225

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

426
426
207
166
234

539
431
601

207
207
342

253
253
440

202
140
190

350
250
250

250
175
225

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

417
417
259

673

187
187
414
518
342

253
253
506
633
418

219
181
165
131
199

350
300
225
175
250

300
225
200
150
225

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

452
452
219
175
248

551
440
615

207
207
342

253
253
440

202
169
204

350
300
300

250
225
250

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

440
440
273

687

187
187
414
518
342

253
253
506
633
418

263
181
184
147
222

450
300
250
200
300

350
225
225
175
300

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

512
512
249
199
282

646
536
720

207
207
342

253
253
440

245
169
230

400
300
300

300
225
300

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

496
496
308

797

See legend and notes on page 28.

26

Table 4A Unit Electrical Data, 30HXC Units (cont)

UNIT
30HXC

146

161

171

186

206

VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50

POWER CIRCUIT*

CONTROL CIRCUIT

ICF

MCA

MOCP

Recommended
Fuse Size

Voltage
(Single
Ph)

Min

Max

MCA

MOCP

WD

XL

187
187
414
518
342

253
253
506
633
418

263
219
198
158
240

450
350
250
225
350

350
300
225
200
300

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

542
542
262
210
299

659
547
737

207
207
342

253
253
440

245
202
246

400
350
350

300
250
300

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

523
523
324

813

187
187
414
518
342

253
253
506
633
418

285
197
200
160
242

500
350
300
225
350

350
250
250
200
300

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

591
591
287
230
325

756
605
843

207
207
342

253
253
440

266
182
249

450
300
350

350
225
300

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

578
578
358

944

187
187
414
518
342

253
253
506
633
418

238
285
215
172
260

400
500
300
250
350

300
400
250
200
300

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

624
624
302
242
343

771
617
861

207
207
342

253
253
440

219
266
267

350
450
350

300
350
300

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

607
607
376

962

187
187
414
518
342

253
253
506
633
418

285
285
232
185
281

500
500
300
250
400

400
400
300
225
350

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

661
661
319
255
364

788
630
882

207
207
342

253
253
440

266
266
289

450
450
400

350
350
350

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

645
645
399

985

187
187
414
518
342

253
253
506
633
418

345
285
263
210
319

500
500
350
250
400

400
350
300
250
350

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

907
907
247
198
277

716
573
795

207
207
342

253
253
440

318
266
327

450
450
450

400
350
400

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

892
892
307

893

See legend and notes on page 28.

27

Table 4A Unit Electrical Data, 30HXC Units (cont)

UNIT
30HXC

246

261

271

VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50

POWER CIRCUIT*

CONTROL CIRCUIT

ICF

MCA

MOCP

Recommended
Fuse Size

Voltage
(Single
Ph)

Min

Max

MCA

MOCP

WD

XL

187
187
414
518
342

253
253
506
633
418

443
285
303
242
367

600
500
400
300
450

600
350
350
300
400

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

1024
1024
287
230
325

756
605
843

207
207
342

253
253
440

411
266
378

600
450
500

500
350
450

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

1010
1010
358

944

187
187
414
518
342

253
253
506
633
418

476
285
318
254
385

700
500
400
300
500

600
350
350
300
450

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

1057
1057
302
242
343

771
617
861

207
207
342

253
253
440

400
266
395

600
450
500

500
350
450

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

1039
1039
376

962

187
187
414
518
342

253
253
506
633
418

514
285
335
268
406

700
500
400
350
500

600
350
400
300
450

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

1094
1094
319
255
364

788
630
882

207
207
342

253
253
440

478
266
418

600
450
500

600
350
350

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

1077
1077
399

985

LEGEND
Full Load Amps
Maximum Instantaneous Current Flow during start-up
(the point in the starting sequence where the sum of the
LRA for the start-up compressor, plus the total RLA for
all running compressors, plus the total FLA for all running fan motors is at a maximum)
LRA
Locked Rotor Amps
MCA Minimum Circuit Ampacity (for wire sizing)
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps
WD
Wye-Delta Start
XL
Across-the-Line Start
*Units with one MCA, MOCP, and fuse size value have one terminal
block and require one power supply. Units with one MCA, MOCP,
and fuse value for Circuit A and another for Circuit B have 2 terminal
blocks and require 2 power supplies.
Wye-Delta Start is standard. Not available in across-the-line start.

2. Control circuit power must be supplied from a separate source through


a field-supplied disconnect (except for 380/415-50 units). The control circuit accessory transformer may be applied to power from
the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.
6. The MOCP is calculated as follows:
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size
the fuse one size down from the result. The RLAs are listed on the
unit nameplate.
The recommended fuse size in amps (RFA) is calculated as
follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size
the fuse one size up from the result. The RLAs are listed on the
unit nameplate.

FLA
ICF

NOTES:
1. Each main power source must be supplied from a field-supplied
fused electrical service with a (factory- or field-installed) disconnect located in sight from the unit.

28

Table 4B Unit Electrical Data, 30HXA Units

UNIT
30HXA

076

086

096

106

116

126

136

VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50

POWER CIRCUIT*

CONTROL CIRCUIT

ICF

MCA

MOCP

Recommended
Fuse Size

Voltage
(Single
Ph)

Min

Max

MCA

MOCP

WD

XL

187
187
414
518
342

253
253
506
633
418

180
180
146
117
177

300
300
200
150
250

225
225
175
150
200

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

451
451
218
175
248

550
440
615

207
207
342

253
253
440

169
169
183

300
300
250

225
225
225

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

440
440
273

687

187
187
414
518
342

253
253
506
633
418

215
180
162
130
196

350
300
225
175
250

300
225
200
150
225

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

511
511
248
199
282

645
536
720

207
207
342

253
253
440

205
169
206

350
300
300

250
225
250

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

496
496
308

797

187
187
414
518
342

253
253
506
633
418

262
180
183
147
222

450
300
250
200
300

350
225
225
175
300

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

577
577
281
225
318

750
600
836

207
207
342

253
253
440

248
169
231

400
300
350

300
225
300

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

567
567
352

938

187
187
414
518
342

253
253
506
633
418

319
180
209
167
253

500
300
300
250
350

400
225
250
200
300

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

662
662
324
259
365

885
708
985

207
207
342

253
253
440

300
169
263

500
300
400

400
225
300

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

620
620
385

1042

187
187
414
518
342

253
253
506
633
418

319
215
222
177
269

500
350
300
250
400

400
300
300
200
350

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

690
690
337
269
380

898
718
1000

207
207
342

253
253
440

300
205
281

500
350
400

400
250
350

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

649
649
402

1059

187
187
414
518
342

253
253
506
633
418

319
262
239
191
289

500
450
350
250
400

400
350
300
225
350

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

728
728
354
283
401

915
732
1021

207
207
342

253
253
440

300
248
302

500
400
400

400
300
350

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

683
683
423

1080

187
187
414
518
342

253
253
506
633
418

389
262
271
216
328

700
450
400
300
450

500
350
350
250
400

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

791
791
386
309
436

1015
812
1132

207
207
342

253
253
440

369
248
343

600
400
500

450
300
400

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

817
817
507

1346

See legend and notes on page 31.

29

Table 4B Unit Electrical Data, 30HXA Units (cont)

UNIT
30HXA

146

161

171

186

206

VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B

POWER CIRCUIT*

CONTROL CIRCUIT

ICF

MCA

MOCP

Recommended
Fuse Size

Voltage
(Single
Ph)

Min

Max

MCA

MOCP

WD

XL

187
187
414
518
342

253
253
506
633
418

389
319
291
233
353

700
500
400
300
500

500
400
350
300
400

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

837
837
406
325
461

1035
828
1157

207
207
342

253
253
440

369
300
369

600
500
500

450
400
450

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

859
859
532

1371

187
187
414
518
342

253
253
506
633
418

437
295
304
243
368

700
500
450
350
500

600
400
350
300
450

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

979
979
478
382
539

1282
1025
1428

207
207
342

253
253
440

415
275
385

700
450
500

500
350
450

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

858
858
533

1398

187
187
414
518
342

253
253
506
633
418

359
437
327
261
396

600
700
450
350
500

450
600
400
300
450

115-60
115-60
115-60
115-60
230-60

104
104
104
104
207

127
127
127
127
254

15
15
15
15
15

15
15
15
15
15

1030
1030
501
401
567

1305
1044
1456

207
207
342

253
253
440

334
415
413

600
700
600

450
500
500

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

905
905
562

1427

187
187
414
518

253
253
506
633

437
437
355
284

700
700
500
400

600
600
400
350

115-60
115-60
115-60
115-60

104
104
104
104

127
127
127
127

15
15
15
15

15
15
15
15

1093
1093
529
539

1333
1066

342
342

418
418

239
239

400
400

300
300

230-60
230-60

207
207

254
254

15
15

15
15

601
601

1490
1490

207
207
342

253
253
440

415
415
453

700
700
600

500
500
600

230-50
230-50
230-50

198
198
198

254
254
254

15
15

15
15

970
970
601

1466

187
187

253
253

521
437

800
700

600
600

115-60
115-60

104
104

127
127

15
15

15
15

743
743

414
414

506
506

235
197

350
350

300
250

115-60
115-60

104
104

127
127

15
15

15
15

364
371

993
1175

518
518

633
633

188
158

250
250

225
200

115-60
115-60

104
104

127
127

15
15

15
15

292
297

796
940

342
342

418
418

285
239

400
400

350
300

230-60
230-60

207
207

254
254

15
15

15
15

410
410

1106
1299

207
207

253
253

486
415

700
700

600
500

230-50
230-50

207
207

254
254

15
15

15
15

771
638

342
342

440
440

294
252

450
450

350
250

230-50
230-50

207
207

254
254

15
15

15
15

479
400

1318
1265

30

Table 4B Unit Electrical Data, 30HXA Units (cont)


UNIT
30HXA

246

261

271

VOLTAGE
Supplied
Nameplate
V-Hz (3 Ph)
Min
Max
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B

POWER CIRCUIT*

CONTROL CIRCUIT

MCA

MOCP

Recommended
Fuse Size

187
187

253
253

673
437

1000
700

800
600

414
414

506
506

304
197

450
350

350
250

518
518

633
633

243
158

350
250

300
200

Voltage
(Single Ph)
115-60
115-60

342
342

418
418

368
239

500
400

450
300

207
207

253
253

636
415

800
700

800
500

342
342

440
440

385
252

500
450

450
350

187
187

253
253

724
437

1000
700

1000
600

414
414

506
506

327
197

450
350

400
250

518
518

633
633

261
158

350
250

300
200

342
342

418
418

396
239

500
400

450
300

342
342

440
440

413
252

600
450

500
350

187
187

253
253

787
437

1000
700

1000
600

414
414

506
506

355
197

500
350

400
250

518
518

633
633

284
158

400
250

350
200

600
400

500
300

207
207

253
253

748
415

1000
700

1000
500

342
342

440
440

453
252

600
450

15

104

127

15

15

15

207
207
104
104
104

254
254
127
127
127

15
15
15
15
15

230-50

207

254

15

15

104

127

15
15

382
297

1025
940

539
410

1428
1299

748
638

533
400

1398
1265

1030
743

501
371

1305
1175

401
297

1044
940

567
410

1456
1299

905
538

562
400

1427
1265

1093
743

529
371

1333
1175

423
297

1066
940

601
410

1490
1299

970
638

601
400

1466
1265

15
15
15

115-60

104

127

15

15

230-60

207

254

15

15

230-50

207

254

15

15

230-50

207

254

15

15

600
350

1282
1175

15
15

127

478
371

15

15

104

15

254

15

979
743

15

207

254

XL

15

230-60

207

WD

15

254

115-60

430
239

15

207

115-60

418
418

127

230-60

230-50

342
342

104

15

115-60

800
500

MOCP

15

115-60

1000
700

MCA

127

115-60

683
415

Max

104

230-50

253
253

Min

115-60

230-50

207
207

ICF

6. The MOCP is calculated as follows:


MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the
fuse one size down from the result. The RLAs are listed on the unit
nameplate.
The recommended fuse size in amps (RFA) is calculated as follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the
fuse one size up from the result. The RLAs are listed on the unit
nameplate.
7. Units have the following power wiring terminal blocks and parallel
conductors:

LEGEND
Full Load Amps
Maximum Instantaneous Current Flow during start-up (the
point in the starting sequence where the sum of the LRA for
the start-up compressor, plus the total RLA for all running
compressors, plus the total FLA for all running fan motors is
at a maximum)
LRA
Locked Rotor Amps
MCA
Minimum Circuit Ampacity (for wire sizing)
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps
WD
Wye-Delta Start
XL
Across-the-Line Start
*Units with one MCA, MOCP, and fuse size value have one terminal block
and require one power supply. Units with one MCA, MOCP, and fuse
value for Circuit A and another for Circuit B have 2 terminal blocks and
require 2 power supplies.
Wye-Delta Start is standard. Not available in across-the-line start.
**The 30HXA186, 380-3-60 and 30HXA206-271 units have 2 terminal blocks/
non-fused disconnects and 6 parallel conductors.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service with a (factory- or field-installed) disconnect located in sight from
the unit.
2. Control circuit power must be supplied from a separate source through
a field-supplied disconnect (except for 380/415-50 units). An accessory control transformer may be used to provide control circuit power
from the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.
FLA
ICF

VOLTAGE
208/230
460
575
380
230
380/415

31

TERMINAL
BLOCKS
OR NON-FUSED
DISCONNECTS**
2
1
1
1
2
1

CONDUCTORS
6
3
3
3
6
3

Table 5A Compressor Electrical Data, 30HXC Units


UNIT SIZE
30HXC

076-XL

076-WD

086-XL

086-WD

096-XL

096-WD

106-XL

106-WD

LRA
RLA
WD
XL

LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start

NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

COMPRESSOR NUMBERS
A1
RLA
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
53.6
42.8
64.9
*
67.7
118.6
53.6
42.8
64.9
111.8
67.7
*
65.5
52.3
79.2
*
81.7
144.9
65.5
52.3
79.2
134.9
81.7
*
79.2
63.3
95.9
*
97.8
175.4
79.2
63.3
95.9
161.7
97.8

B1
LRA
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
423
209
104
83
115
213
134
*
405
324
448
*
506
256
128
102
141
255
160
*
485
388
536
*
605
307
153
123
169
305
191

RLA
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8

LRA
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
344
209
104
83
115
174
109

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

32

Table 5A Compressor Electrical Data, 30HXC Units (cont)


UNIT SIZE
30HXC

116-XL

116-WD

126-XL

126-WD

136-XL

136-WD

146-XL

146-WD

LRA
RLA
WD
XL

LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start

NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

COMPRESSOR NUMBERS
A1
RLA
*
79.2
63.3
95.9
*
87.8
175.4
79.2
63.3
95.5
161.7
97.8
*
79.2
63.3
95.9
*
97.8
175.4
79.2
63.3
95.9
161.7
97.8
*
94.9
75.8
114.9
*
118.8
210.0
94.6
75.8
114.9
196.3
118.8
*
94.9
75.8
114.9
*
118.8
210.0
94.9
75.8
114.9
196.3
118.8

B1
LRA
*
485
388
536
*
605
307
153
123
169
305
191
*
485
388
536
*
605
307
153
123
169
305
191
*
580
484
641
*
715
367
183
147
203
361
226
*
580
484
641
*
715
367
183
147
203
361
226

RLA
*
53.6
42.8
64.9
*
67.7
118.6
53.6
42.8
64.9
111.8
67.7
*
65.5
52.3
79.2
*
81.7
144.9
65.5
52.3
79.2
134.9
81.7
*
65.5
52.3
79.2
*
81.7
144.9
65.5
52.3
79.2
134.9
81.7
*
79.2
63.3
95.9
*
97.8
175.4
79.2
63.3
95.9
161.7
97.8

LRA
*
330
264
365
*
423
209
104
83
115
213
134
*
405
324
448
*
506
256
128
102
141
255
160
*
405
324
448
*
506
256
128
102
141
255
160
*
485
388
536
*
605
307
153
123
169
305
191

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

33

Table 5A Compressor Electrical Data, 30HXC Units (cont)


UNIT SIZE
30HXC

161-XL

161-WD

171-XL

171-WD

186-XL

186-WD

LRA
RLA
WD
XL

LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start

NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

COMPRESSOR NUMBERS
A1
RLA
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
86.1
68.8
104.2
*
105.8
190.6
86.1
68.8
104.2
174.8
105.8
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6

B1
LRA
*
685
548
757
*
856
433
216
173
239
432
270
*
580
484
641
*
715
367
183
147
203
361
233
*
685
548
757
*
856
433
216
173
239
432
270

RLA
*
71.2
56.9
86.2
*
88.2
157.6
71.2
56.9
86.2
145.7
88.2
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6

LRA
*
525
420
580
*
600
350
175
140
193
348
200
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

34

Table 5A Compressor Electrical Data, 30HXC Units (cont)


UNIT SIZE
30HXC

206-XL

206-WD

246-XL

246-WD

261-XL

261-WD

271-XL

271-WD

NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

LEGEND
LRA
RLA
WD
XL

A1
RLA
*
86.1
68.8
104.2
*
105.8
190.6
86.1
68.8
104.2
174.8
105.8
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6

LRA
*
580
484
641
*
715
367
183
147
203
361
233
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270

COMPRESSOR NUMBERS
A2
RLA
LRA
*
*
44.3
330
35.4
264
53.7
365
*
*
55.8
344
98.1
209
44.3
104
35.4
83
53.7
115
92.1
174
55.8
109
*
*
71.2
525
56.9
420
86.2
580
*
*
88.2
600
157.6
350
71.2
175
56.9
140
86.2
193
145.7
348
88.2
200
*
*
86.1
580
68.8
484
104.2
641
*
*
105.8
715
190.6
367
86.1
183
68.8
147
104.2
203
174.8
361
105.8
233
*
*
103.1
685
82.4
548
124.8
757
*
*
128.6
856
228.8
433
103.1
216
82.4
173
124.8
239
212.5
432
128.6
270

B1
RLA
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6

LRA
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

Locked Rotor Amps


Rated Load Amps
Wye-Delta Start
Across-the-Line Start

35

Table 5B Compressor Electrical Data, 30HXA Units


UNIT SIZE
30HXA

076-XL

076-WD

086-XL

086-WD

096-XL

096-WD

106-XL

106-WD

LRA
RLA
WD
XL

LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start

NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

COMPRESSOR NUMBERS
A1
RLA
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
77.6
62.1
94.0
*
99.2
171.9
77.6
62.1
94.0
163.9
99.2
*
94.8
75.7
114.7
*
119.9
209.8
94.8
75.5
114.7
198.2
119.9
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4

B1
LRA
*
485
388
536
*
605
307
153
123
169
305
191
*
580
484
641
*
715
367
183
147
203
361
226
*
685
548
757
*
856
433
216
173
239
432
270
*
820
656
906
*
960
518
259
207
286
485
303

RLA
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5

LRA
*
485
388
536
*
605
307
153
123
169
305
191
*
485
388
536
*
605
307
153
123
169
305
191
*
485
388
536
*
685
307
153
123
169
305
191
*
485
388
536
*
605
307
153
123
169
305
191

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

36

Table 5B Compressor Electrical Data, 30HXA Units (cont)


UNIT SIZE
30HXA

116-XL

116-WD

126-XL

126-WD

136-XL

136-WD

146-XL

146-WD

LRA
RLA
WD
XL

LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start

NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

COMPRESSOR NUMBERS
A1
RLA
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4
*
140.7
112.4
170.2
*
178.8
311.4
140.7
112.4
170.2
295.3
178.8
*
140.7
112.4
170.2
*
178.8
311.4
140.7
112.4
170.2
295.3
178.8

B1
LRA
*
820
656
906
*
960
578
259
207
286
485
303
*
820
656
906
*
960
518
259
207
286
485
303
*
920
736
1017
*
1226
581
291
233
321
619
387
*
920
736
1017
*
1226
581
291
233
321
619
387

RLA
*
77.6
62.1
94.0
*
99.2
171.9
77.6
62.1
94.0
163.9
99.2
*
94.8
75.7
114.7
*
119.9
209.8
94.8
75.7
114.7
198.2
119.9
*
94.8
75.7
114.7
*
119.9
209.8
94.8
75.7
114.7
198.2
119.9
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4

LRA
*
580
484
641
*
715
367
183
147
203
361
226
*
685
548
757
*
856
447
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
276
*
820
656
906
*
960
518
259
207
286
485
303

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

37

Table 5B Compressor Electrical Data, 30HXA Units (cont)


UNIT SIZE
30HXA

161-XL

161-WD

171-XL

171-WD

186-XL

186-WD

LRA
RLA
WD
XL

LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start

NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

COMPRESSOR NUMBERS
A1
RLA
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
129.6
103.6
156.9
*
161.7
286.9
129.6
103.6
156.9
267.2
161.7
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2

B1
LRA
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
920
736
1017
*
1226
581
291
233
321
619
387
*
1175
940
1299
*
1265
743
371
297
410
638
400

RLA
*
106.6
85.1
129.0
*
133.4
235.9
106.6
85.1
129.0
220.3
133.4
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2

LRA
*
790
630
870
*
1045
527
263
211
290
607
348
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

38

Table 5B Compressor Electrical Data, 30HXA Units (cont)


UNIT SIZE
30HXA

206-XL

206-WD

246-XL

246-WD

261-XL

261-WD

271-XL

271-WD

LRA
RLA
WD
XL

NAMEPLATE
V-Ph
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50

A1
RLA
*
129.6
103.6
156.9
*
161.7
286.9
129.6
103.6
156.9
267.2
161.7
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2

LRA
*
920
736
1017
*
1226
581
291
233
321
619
387
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400

COMPRESSOR NUMBERS
A2
RLA
LRA
*
*
73.1
580
58.5
484
88.5
641
*
*
92.0
715
162.0
367
73.1
183
58.5
147
88.5
203
152.0
361
92.0
226
*
*
106.6
820
85.1
656
129.0
906
*
*
133.4
960
235.9
518
106.6
259
85.1
207
129.0
286
220.3
485
133.4
303
*
*
129.6
920
103.6
736
156.9
1017
*
*
161.7
1226
286.9
581
129.6
291
103.6
233
156.9
321
267.2
619
161.7
387
*
*
157.9
1175
126.2
940
191.2
1299
*
*
201.2
1265
349.6
743
157.9
371
126.2
297
191.2
410
332.3
638
201.2
400

LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start

*Units are shipped with wye-delta as standard. Across-the-line start is not available.

39

B1
RLA
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2

LRA
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400

Step 7 Refrigerant Charge


IMPORTANT: These units are designed for use with
R-134a only. DO NOT USE ANY OTHER REFRIGERANT in these units without first consulting your
Carrier representative.

4. Check for a clear sight glass. If the unit is not fully loaded,
the sight glass may be flashing. This condition is normal
for a partially loaded unit. If the unit is fully loaded and
the sight glass is flashing, check EXV valve position. If
it is greater than 60% add additional charge.

NOTE: The liquid charging method is recommended for complete charging or when additional charge is required.

When charging, circulate water through the condenser and cooler at all times to prevent freezing. Freezing
damage is considered abuse and may void the Carrier
warranty.

DO NOT OVERCHARGE system. Overcharging results in higher discharge pressure with higher cooling
fluid consumption, possible compressor damage, and higher
power consumption.
30HXC UNITS The 30HXC units are shipped from
the factory with a full charge of R-134a. Unit should not
need to be charged at installation unless a leak was detected
in Step 6 Leak Test Unit section. If dehydration and
recharging is necessary, use industry standard practices or
refer to Carrier Standard Services Techniques Manual or the
Controls, Start-Up, Operation, Service, and Troubleshooting
Guide as required.
30HXA UNITS The 30HXA units are shipped with a holding charge of R-134a. The complete charge for the 30HXA,
the remote condenser(s), and interconnecting piping must be
field supplied.
To charge the 30HXA systems:
1. An initial refrigerant charge must be added after evacuation to allow the unit to start. Add approximately
2 lb/nominal ton (0.9 kg/nominal kW) liquid refrigerant
charge to the condenser. This amount of charge should be
sufficient to allow the unit to start. The approximate system charges are shown in Table 6 and cooler refrigerant
capacity is shown in Table 7.
2. Raise the compressor discharge to approximately 125 F
(51.7 C) saturated discharge temperature (185 psig
[1276 kPa]) by throttling the condenser air (or water)
intake.
3. Add liquid charge into the cooler until there is approximately 18 to 20 F (10.0 to 11.1 C) of system subcooling
(saturated discharge temperature actual temperature
entering the electronic expansion device [EXD]). When
adding charge, use the 14-in. Schrader-type fitting
located on the tube going into the bottom of the cooler.
This fitting is located between the EXD and the cooler.
When adding charge during unit operation, always use
this port so that the cooler liquid level sensor can detect
the additional charge and adjust the EXD valve position.
NOTE: Electronic Expansion Device (EXD) refers to EXV
(Electronic Expansion Valve) (076-146 units) or Economizer (161-271 units).

Table 6 30HXA System Charge


for Start-Up
UNIT
30HXA
076
086
096
106
116
126
136
146
161
171
186
206
246
261
271

CIRCUIT A
CHARGE
lb
kg
75
34.0
94
42.6
114
51.7
134
60.8
137
62.1
137
62.1
147
66.7
161
73.0
190
86.2
154
69.9
186
84.4
224
101.6
288
130.6
311
141.1
335
152.0

CIRCUIT B
CHARGE
lb
kg
75
34.0
80
36.3
80
36.3
80
36.3
95
43.1
116
52.6
125
56.7
132
59.9
132
59.9
86
84.4
86
84.4
169
76.7
169
76.7
168
76.2
165
74.8

Table 7 Cooler Refrigerant Capacity


UNIT SIZE
30HXA
076,086
096
106
116,126
136,146
161
171
186
206
246-271

CKT
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B

TOTAL
VOLUME
3
Ft
m3
2.538
0.072
2.538
0.072
2.813
0.080
1.929
0.055
3.945
0.112
2.705
0.077
4.044
0.115
2.810
0.080
3.777
0.107
2.625
0.074
5.297
0.150
3.682
0.104
4.490
0.127
4.490
0.127
4.068
0.115
4.068
0.115
7.523
0.213
4.946
0.140
7.090
0.201
4.661
0.132

REFRIGERANT
CAPACITY
lb
kg
161
73.0
161
73.0
178
80.7
122
55.3
250
113.4
172
78.0
256
116.1
178
80.7
240
108.9
167
75.8
336
152.4
234
106.1
285
129.3
285
129.3
258
117.0
258
117.3
477
216.4
314
142.4
450
204.1
296
134.3

Copyright 1999 Carrier Corporation


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Catalog No. 533-004
Printed in U.S.A.
Form 30HX-7SI
Pg 40
8-99
Replaces: 30HX-4SI
Tab 5c

You might also like