TECK 90 (MINUS 40C) HL CABLE, 600 VOLT, XLP (RW90)

XLP Insulation

Copper
Conductor

Binder Tape

Copper
Ground Wire

SPEC 8-19-2

Ver. 7.1

Interlocked Armor

Inner PVC Jacket

Revised: 12/10/08

PVC Jacket

90C CONDUCTOR TEMPERATURE, WET OR DRY


Conductor
Size AWG
or KCMIL

No. of
Strands+

Nominal
O.D.

Approximate O.D. in Inches

Inner
Jacket
in Mils

Size
AWG
Copper
Ground
Wire

Over
Inner
Jacket

Over
Armor

Over
Overall
Jacket

Ampacity**
30C
Ambient

Approximate
Net
Weight~
LBS/KFT

45
45
45
45
55
55
55
55
55
65
65
65
65
65
80
80
80

60
60
80
80
80
80
80
80
80
110
110
110
110
110
110
110
140

8
8
8
6
6
6
6
4
4
4
4
3
3
2
2
2
1

0.68
0.75
0.89
1.02
1.15
1.24
1.33
1.44
1.56
1.77
1.88
1.99
2.09
2.26
2.50
2.72
3.10

0.86
0.94
1.07
1.20
1.33
1.42
1.51
1.62
1.91
2.12
2.23
2.34
2.44
2.61
2.85
3.07
3.45

0.96
1.05
1.18
1.30
1.43
1.52
1.63
1.74
2.03
2.24
2.35
2.49
2.59
2.76
3.00
3.24
3.62

45
65
85
120
140
155
185
210
235
265
295
325
345
395
455
500
585

525
695
950
1290
1555
1820
2175
2630
3075
3835
4405
5085
5650
6800
8030
9750
12710

45
45
45
45
55
55
55
55
55
65
65
65
65
65
80
80
80

60
60
80
80
80
80
80
80
110
110
110
110
110
110
140
140
140

8
8
8
6
6
6
6
4
4
4
4
3
3
2
2
2
1

0.74
0.83
0.98
1.12
1.27
1.36
1.47
1.59
1.78
1.95
2.08
2.20
2.31
2.51
2.83
3.08
3.44

0.92
1.01
1.16
1.30
1.45
1.54
1.65
1.94
2.13
2.30
2.43
2.55
2.66
2.86
3.18
3.43
3.79

1.02
1.11
1.26
1.40
1.55
1.66
1.77
2.06
2.25
2.45
2.58
2.70
2.81
3.01
3.35
3.60
3.96

45
65
85
120
140
155
185
210
235
265
295
325
345
395
455
500
585

615
825
1135
1570
1905
2280
2700
3350
4000
4860
5605
6380
7120
8605
10450
12630
16230

Insulation
in Mils

THREE CONDUCTOR 600 VOLT


8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000

7
7
7
7
19
19
19
19
19
37
37
37
37
37
61
61
61

0.14
0.18
0.23
0.28
0.32
0.36
0.41
0.46
0.51
0.56
0.61
0.66
0.71
0.79
0.87
0.97
1.12

FOUR CONDUCTOR 600 VOLT


8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000

7
7
7
7
19
19
19
19
19
37
37
37
37
37
61
61
61

0.14
0.18
0.23
0.28
0.32
0.36
0.41
0.46
0.51
0.56
0.61
0.66
0.71
0.79
0.87
0.97
1.12

Note:**Based on cables in free air run, per CEC Part 1, Tables 1 & 2.
For four conductor cable the fourth conductor is a neutral. Otherwise
the maximum ampacity is 80% of the table figures. For other installations refer to the CEC.
~Weights based on aluminum armor assembly.
+
19 stranding is combination unilay per ASTM 787.

The above data is approximate and subject to normal manufacturing


tolerances.

STANDARDS AND RATINGS:

1. Listed as Teck 90 by CSA per CSA C22.2 No. 131.


2. Listed as FT4 & HL by CSA per CSA C22.2 No. 174.
3. Conforms to ICEA S-95-658/NEMA WC70 Nonshielded 0-2KV Cables.