Preface
The Infinity CMX Installation Guide presents instructions for installing the various CMX controllers. It first presents site preparation information and then step-by-step installation instructions. We recommend you read Infinity Network Configuration Guide to plan your entire network before installing a single controller.
iii
www.PDF-Zoo.com
iv
www.PDF-Zoo.com
TOC
Contents
www.PDF-Zoo.com
Connecting to the Infinity Modem ..............................................17 Wiring Infinet to the CMX 240 ...................................................18 Wiring the TankNet and Probe Power Supply ............................19 About the Safety Barriers ............................................................21 Powering Up CMX 240 Series Controller .............................................23 Connecting the Battery ................................................................24 Interpreting Status Lights Inside Cabinet ...............................................25 Custom Port Status Lights ...........................................................25 Communication Status Lights ......................................................25 Infinet Status Lights .....................................................................26 Modem Power Light ....................................................................27 System Activity Status Lights .....................................................27 Using the CLEAR MEMORY Button .........................................28 Connecting the Andover Controls Service Tool ..........................28
vi
www.PDF-Zoo.com
TOC
Figures
Figure 1. Backplate with Dimensions and Eyelets for Mounting CMX 240 ..............................................................................11 Figure 2. Cabinet with Dimensions and Eyelets for Mounting CMX 240 ..............................................................................12 Figure 3. Metal Plate and Screw for Power Supply Wire .........................13 Figure 4. Locations of Ports and Connectors on the CMX 240 Face Plate ............................................................16 Figure 5. Jumpering P1 Pins for CMX 240, Top View .............................18 Figure 6. Infinet Cable Wiring ....................................................................19 Figure 7. Attaching the TankNet and Probe Power Supply Cables .....20 Figure 8. Diagram of Safety Barrier Connection ................................22 Figure 9. Custom Port Status Lights ...........................................................25 Figure 10. Communication Status Lights for Comm1 .................................26 Figure 11. Communication Status Lights for Infinet ...................................26 Figure 12. System Activity Status Lights .....................................................27 Figure A-1. Pinouts for Cables Connecting to RS-232 Ports on Controller................................................................................... A-3 Figure B-1. Switch Settings for Switches 2 and 3 on Tank Probe ..............B-2 Figure B-2. Switch Settings for Tank Probes on Channels 1 through 6 ......B-3
vii
www.PDF-Zoo.com
Tables
Table 1. Number of Infinet Controllers Allowed on Various CMX 240s ................................................................5 Table 2. AC Input Voltage Selection .................................................14 Table A-1 Pinouts for RS-232 Comm Port with Male DB25 Connector to Terminal .......................................................A-1
viii
www.PDF-Zoo.com
Appendix A gives the pinouts for the RS-232 port cables. Appendix B shows you how to set some probe switches.
Warranty Registration
Your warranty is effective for 18 months starting on the date the system is shipped.
www.PDF-Zoo.com
Warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions in this manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Note
This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Avis
Le prsent appareil numrique nmet pas de bruits radiolectriques dpassant les limites applicables aux appareils numriques de la class A prescrites dans le Rglement sur le brouillage radiolectrique dict par le ministre des Communications du Canada.
www.PDF-Zoo.com
Warning
All wiring and installations must comply with local, state, and national electrical codes.
Cabinet Dimensions
Each Infinity CMX 240 cabinet is approximately 15 19 4.75 in. You can order the CMX 240 with or without the cabinet.
Controller Dimensions
Each Infinity CMX 240 controller without a cabinet is approximately 12.54 14.25 2.75 in.
www.PDF-Zoo.com
Power Requirements
Warning
Be sure your installation complies with local, state, and national electrical codes.
Caution
The CMX 240 series controller should receive power from its own independent, unswitched circuit. The CMX 240 requires 24/115/230 VAC +/-20%, 50/60 Hz rated at 30 VA with a modem and 20 VA without a modem.
Modem
You can use the Infinity modem with any CMX 240, but the modem is not required. If you order any CMX 240 with the Infinity modem, the modem is already installed. If you order any CMX 240 without a modem and then add the Infinity modem later, refer to the Infinity Modem Installation Guide for instructions on how to install the modem.
Infinet Cables
The maximum cable length for Infinet is 4,000 ft. at 19,200 baud (up to 32 Infinet controllers). You can extend Infinet beyond 4,000 ft. or put more than 32 Infinet controllers on less than 4,000 ft. by using the InfiLink 200 amplification module.
www.PDF-Zoo.com
Cables that form Infinet are 24-gauge, single-twisted-pair, tinned, shielded copper wire. Use the following cables1 or their equivalents:
Note
You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to communicate reliably. Brand Rex # H 9002 (single-pair) Anixter # 9J2401021 (single-pair plenum cable) The cable should have a nominal impedance of 100 and a nominal velocity of propagation of 78%. The capacitance of the Infinet cable should be smaller than or equal to 12.5 pF/ft between conductors and smaller than or equal to 22 pF/ft between the conductor connected to ground and the next conductor.
The differences between the CMX 240/241 and the CMX 245/246 are differences in what you can program them to do. The CMX 245 and 246 allow you to choose Command mode on a terminal connected to COMM2. For details, see the Infinity Controller Programmers Guide.
1. You can also use any cables you may already have in place for ACNET or LBUS.
www.PDF-Zoo.com
Lightning Protection
Warning
When running cables (Infinet) between buildings you must install lightning arresters for Infinet to prevent electromagnetic disturbances. Use lightning arresters at each point where Infinet cable enters or exits a building. Use the following arrester: Two pair gas tube arrester, Andover Controls # 01-2100-299.
www.PDF-Zoo.com
Warning
Be sure to have your grounds inspected before you begin the installation process to be sure your municipality follows the National Electrical Code. Many municipalities do not and often have substandard electrical grounds. An example of a substandard ground is a galvanized steel cold water pipe. As the pipe corrodes, it does not act as a true ground. The corrosion acts as an insulator, raising the potential of the pipe with respect to the ground. When lightning strikes in the area of the installation, it drastically changes the potential of the earth. Since properly grounded Andover Controls units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach ground through the Andover Controls system. The surge of current can destroy electronic components on the controller board. Surges of much lower potential than lightning also impact the reliability of Andover Controls equipment.
www.PDF-Zoo.com
Environmental Requirements
The CMX 240 controllers operate in rooms with temperatures ranging from 40 to 120F and with humidity between 10 and 95%, noncondensing.
www.PDF-Zoo.com
Parts Required
To install a single controller you start with the following parts: CMX 240 Series Controller Cabinet (provided or other enclosure) Modem (optional) AC Power Cable Infinet Cable TankNet Cable and Intrinsic Safety Barriers (optional, for connecting TankNet) Probe Power Supply Cable and Intrinsic Safety Barriers (optional, for use with TankNet) Telephone Cable (optional, for connecting to modem) RS-232 Cables for Terminal, Printer, or Modem (see the Appendix A for specifications)
www.PDF-Zoo.com
Warning
Never drill holes in the CMX cabinet or boards. A metal shaving could easily short circuit the electronics. 1. Pull the cable for a terminal or printer through the opening on the left side of the cabinet. 2. Pull cables for Infinet through the left side opening. 3. Pull the AC cable through the opening on the top left side of the cabinet.
10
www.PDF-Zoo.com
Figure 1. Backplate with Dimensions and Eyelets for Mounting CMX 240
2.000 .015 8.550 4.275 .45 4 Places
14.25
13.150 11.50
6.575
.23
REF
11
www.PDF-Zoo.com
Figure 2 shows the dimensions of the cabinet, provided with the controller (if purchased), and the location of the mounting screw holes.
Figure 2. Cabinet with Dimensions and Eyelets for Mounting CMX 240
15.00 1.33 12.35 1.00
AC INPUT
GND NEU HOT
USE COPPER
CONDUCTORS
ONLY
AC INPUT VOLTAGE SELECTION 24V 115V 230V FROM TO FROM TO FROM TO E3 E7 E3 E5 --E2 E6 E2 E4 E2 E4 P2 E1 P2 E1 P2 E5
CMX240
19.00 17.00
TD COMM1 RD RTS AC POWER MODEM POWER F5, 2A CPU SCAN ERROR TD COMM2 RD RTS
+ SHLD
INFINET
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: ( 1 ) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND ( 2 ) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
12
www.PDF-Zoo.com
Caution
Be sure to connect all three wires, GND, NEU, and HOT. Otherwise, the controller could malfunction. 2. Notice that the three wires at the end of your AC cable are green, white, and black. 3. Place the green wire under the metal plate behind the top screw, labeled GND. 4. Tighten the screw with a flathead screw driver. Figure 3 shows the position of the plate, where to place the wire, and how the screw fits on the plate. You can see how the screw holds the plate in place once you tighten it.
Insert Wire Here 5. Place the white wire under the metal plate behind the middle screw, labeled NEU.
CMX 240 Series Installation Guide 13
www.PDF-Zoo.com
6. Tighten the screw with a flathead screw driver. 7. Place the black wire under the metal plate behind the bottom screw, labeled HOT. 8. Tighten the screw with a flathead screw driver.
To change the voltage from 115 V to 230 V, proceed as follows: 1. Remove the jumper from E3 to E5. 2. Leave the jumper E2 to E4 as it is. 3. Disconnect the jumper end from E1 and move it to E5 so it jumpers P2 to E5. To change the voltage from 115 V to 24 V, proceed as follows: 1. Disconnect the jumper end from E5 and move it to E7 so it jumpers E3 to E7. 2. Disconnect the jumper from E4 and connect it to E6, so it jumpers E2 to E6. 3. Leave the jumper P2 to E1 as it is.
14
www.PDF-Zoo.com
Custom Port
The Custom Port is used for a TankNet of level sensing probes or any device you have ordered custom software for (see your Andover Controls representative). It is located just above COMM1, on the left side of the board.
Communications Port
Notice that the CMX 240 series controller has two RS-232 communication ports, labeled COMM1 and COMM2 on the left side of the board. You can attach a cable to each port. COMM1 is preset for you to connect a printer to. COMM2 is preset for you to connect either a terminal or Infinity modem to. (COMM1 and COMM2 can be connected to a printer, terminal, computer, or modem by changing the port mode in the software.) COMM1 and COMM2 cannot connect to an LBUS or Infinet cable.
Infinet Connector
The Infinet connector is located below COMM2 on the left side of the board.
Service Port
The port labeled SERVICE PORT connects the Andover Controls Service Tool to the CMX 240 controller. You can carry around the tool and plug it in as required to see how the controller system is functioning. See your Andover Controls representative about availability of the tool. Figure 4 shows the location of various parts inside any CMX 240. You may want to refer to this figure to locate parts during the installation.
CMX 240 Series Installation Guide 15
www.PDF-Zoo.com
Figure 4. Locations of Ports and Connectors on the CMX 240 Face Plate
AC INPUT
GND NEU HOT
CMX240
TD RD +26V
CLEAR MEMORY
6V BATTERY
F2 3A,250V SLOW BLOW
+ -
TD
COMM1
RD RTS AC POWER
MODEM POWER
F5, 2A
COMM2
RD RTS
+ SHLD
INFINET
TD
SERVICE PORT
F6, 1/8A
RD
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: ( 1 ) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND ( 2 ) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
16
www.PDF-Zoo.com
Caution
You must be absolutely certain P1 is jumpered correctly or you may blow the F1 (2A picofuse) on the modem. If you have any questions contact your Andover Controls representative.
17
www.PDF-Zoo.com
2. Be absolutely certain that the left two pins are jumpered. You will see 5V above the left pin. Figure 5 shows how to correctly jumper the pins.
3. Connect the modem power cable to the CMX 240 controller port labeled MODEM POWER, on the left side just below COMM1. 4. Plug the end of the RS-232 cable, hanging from the modem, into the COMM1 or COMM2 port on the CMX 240 controller. 5. Run the telephone cable through the nearest knockout in the cabinet to the wall jack.
Note
You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to ensure reliable communications. You wire the Infinet to all CMX 240s using the following procedure: 1. Open the front of the controller cabinet. Notice that to the lower left is a port labeled Infinet. The end of the Infinet cable has two wires and a shield. You wire them to the block terminal connector on the Infinet port. 2. String the cable through the cable hole on the left side of the controller.
18
www.PDF-Zoo.com
Figure 6 illustrates how to wire the Infinet cable to the removable terminal block connector on the lower left corner of all CMX 240s.
3. Trim back the shield over the wires. 4. Take the first wire for the incoming Infinet and the first wire for the outgoing Infinet and slip both in the hole beneath the screw labeled with a plus sign (top). 5. Tighten the screw down on them until the screw holds the wires in place. 6. Slip the second (usually black) wire from each Infinet cable under the screw labeled with a minus sign (middle) and tighten the screw down on them. 7. Slip the shields from the incoming and outgoing Infinet cables under the screw labeled SHLD (bottom) and tighten the screw down on them.
19
www.PDF-Zoo.com
Custom Port
Wiring TankNet
To connect the TankNet to the CUSTOM PORT use the following procedure: 1. Trim back the shield over the wires. 2. Slip the positive wire through the hole beneath the screw labeled with a plus sign. 3. Tighten the screw down on it until the screw holds the wires in place. 4. Slip the negative wire under the screw labeled with a minus sign and tighten the screw down on the wire. 5. Tie back the shield. 6. Read the following section about safety barriers and then wire them.
20
www.PDF-Zoo.com
3. Tighten the screw down on the wire until the screw holds the wire in place. 4. Slip the +26V wire under the screw labeled +26V and tighten the screw down on the wire. 5. Tie back the shield. 6. Read the following section and wire the safety barriers.
21
www.PDF-Zoo.com
Note
Any CMX 240 can supply 26 V at 70 mA current for up to 20 tank probes. Refer to the manufacturers documentation for probe information. The TankNet requires a communications Stahl intrinsic safety barrier. After you connect TankNet to any CMX 240 controller, you wire the other end of the TankNet cable to the safety barriers. The probe power supply cable requires a power supply Stahl intrinsic safety barrier. After you connect the power supply cable to any CMX 240 controller, you wire the other end to the safety barrier. Figure 8 is an illustration of the safety barrier connection.
To Probe
To Probe
Safe Area
Hazardous Area
22
www.PDF-Zoo.com
23
www.PDF-Zoo.com
3. The RD lights begins flashing only if data is being received from COMM1, COMM2, CUSTOM PORT, or the Infinet. This may not happen immediately. 4. If the CPU light flashes every 0.1 sec, it means the CPU has failed a RAM or ROM test. Call your Andover Controls representative for assistance.
24
www.PDF-Zoo.com
The first light is yellow, the second green, the third red. These lights indicate the activity of the custom port. The different colored lights flash to indicate the following: TD (Yellow)Flashes when the custom port is transmitting data. RD (Green)Flashes when the custom port is receiving data. +26V (Red)Lights up to indicate power is being supplied to the
-probe. Does not light up when F4 ( 1 8 A picofuse) is blown.
25
www.PDF-Zoo.com
The first light is yellow, the second green, the third red. The lights to the right of COMM1 indicate communication activity through the COMM1 port. The lights to the right of COMM2 indicate communication activity through the COMM2 port. The different colored lights flash to indicate the following: TD (Yellow)Flashes when the communication port is transmitting data. RD (Green)Flashes when the custom port is receiving data. RTS (Red)Lights up to indicate equipment (modem, terminal, printer) is on-line.
The different colored lights flash to indicate the following: TD (Yellow)Flashes when the Infinet is transmitting data. RD (Green)Flashes when the Infinet is receiving data.
26 CMX 240 Series Installation Guide
www.PDF-Zoo.com
All these lights, except of course the ERROR light, turn on when the power comes up. The lights blink to indicate activity. The purposes of the four lights are as follows: AC POWERLights up to indicate the AC power is on. Does not light up when the controller is running on battery backup. CPUFlashes every 0.2 sec that the controller is active. SCANFlashes once for every scan of the controller. ERRORLights up if the controller fails the internal integrity check.
27
www.PDF-Zoo.com
28
www.PDF-Zoo.com
Appendix A
A-1
www.PDF-Zoo.com
Table A-1 shows the pinouts for the RS-232 port on the Infinity CMX 240 controller.
Table A-1. Pinouts for RS-232 Comm Porta with Male DB25 Connector to Terminal
Pin Number 1 2 3 4 5 6 7 8 9 10 20 22 Purpose Chassis TD RD RTS CTS DSR GND DCD (CXD) +V -V DTR RI Direction --From To From To To --To From From From To Required NO YES YES MODEM MODEM MODEM YES MODEM NO NO MODEM NO
a. "To" and "From" are in relation to the Infinity CMX 240 controller. "Modem" means it is required for the modem.
Figure A-1 shows the required and optional pinouts for cables connecting a terminal to the controller, a modem to the controller, and a modem to the terminal.
A-2
www.PDF-Zoo.com
20
20
A-3
www.PDF-Zoo.com
A-4
www.PDF-Zoo.com
Appendix B
B-1
www.PDF-Zoo.com
Hardware Installation
Set the tank probe switches as follows: 1. Set the second and third switches to ON for Andover Controls software. If they are not ON (enabled), you do not see error messages. Figure B-1 shows the settings for switches 2 and 3 on the probe.
ON 1
2 3 4
5 6 7
8 9
Note
The Power Supply Override should be set to OFF because you do not want to override the power supply. 2. Set the switch 1 to OFF to not override the power supply. 3. Set switches 4 through 9 to the address that corresponds to the channel number of the probe. Figure B-2 shows the address switch settings for the tank probe channels 1 through 6. Be sure that the probe you assign to channel 1 in the Point window is set to address 0, as shown. The other channels correspond to subsequent address numbers. Refer to the MTS Systems Corporation documentation for further information on how to set the address switches.
B-2
www.PDF-Zoo.com
Hardware Installation
ON 1
2 3 4
5 6 7
8 9
ON 1
2 3
4 5 6
7 8 9
Channel 2 (Address 1)
ON 1
2 3
4 5 6
7 8 9
Channel 3 (Address 2)
ON 1 2 3
4 5 6
7 8
Channel 4 (Address 3)
ON 1
2 3
4 5 6
7 8 9
Channel 5 (Address 4)
ON 1 2 3
4 5 6
7 8
Channel 6 (Address 5)
B-3
www.PDF-Zoo.com
Hardware Installation
B-4
www.PDF-Zoo.com
Index
A
AC power wiring 13 AC Power light inside 27 AC voltage setting 14 Andover Controls Service Tool using 28
D
dimensions cabinet 3 controller 3
E
ERROR light inside 27
F
features unique to CMX 240 1
B
barrier connection 22
G
ground correcting 7 inspecting 7 requirements 6
C
cabinet dimensions 3 eyelets measurements to 10 cable connecting to modem 18 for Infinet 5 for lightning protection 6 Infinet port 15 port for RS-232 15 RS-232 pinouts A-2 circuit requirements for power 4 codes complying with 4 communication ports locations of 15 communications port COMM1 use 15 COMM2 15 computer connecting 17 configuration planning 8 controller dimensions 3 CPU light inside 27
I
Infinet connecting 18 lightning arrester for 6 Infinet cable connecting 19 Infinet cable numbers 5 INFINET RD light inside 26 INFINET TD light inside 26 intrinsic safety barrier TankNet 20, 21 wiring 21
J
jumper for CMX 240 17 for Infinity CX 9000 17 for Infinity CX 9200 17
L
lightning arrester for Infinet 6
Index-1
www.PDF-Zoo.com
M
modem baud rate of 4 mounting steps to 10
S
safety barrier connection 22 SCAN light inside 27 service port location of 15 purpose of 28 shields for Infinet cable connecting 19 status lights communication ports 25, 26 system and network activity 27
P
parts inside the controller 15 requirements 9 power requirements 4 circuit 4 power surges preventing 6 powerup executing 23 procedure to prepare for 23 probe switch settings B-2
T
TankNet instrinsic safety barrier 20, 21 temperatures for operating 8 terminal connecting 17
R
repair packaging required to ship for 9 requirements parts 9 RS-232 port pinouts A-2
V
voltage selecting for AC power 14
Index-2
www.PDF-Zoo.com
W
wiring connecting Infinet cable 19 correct wire gauge for ground 7 intrinsic safety barriers 21
Index-3
www.PDF-Zoo.com
Index-4
www.PDF-Zoo.com
30-3001-391
www.PDF-Zoo.com