OptiX BWS 1600G Installation Guide

Contents

Contents
7 Installing and Routing Cables.................................................................................................7-1
7.1 Installing and Routing Power Cables ............................................................................................................7-2 7.1.1 Installation Preparation ........................................................................................................................7-2 7.1.2 Procedure for Upward Cabling ............................................................................................................7-6 7.1.3 Procedure for Downward Cabling .......................................................................................................7-9 7.1.4 Resistance Measurement before Power-Up .......................................................................................7-13 7.2 Installing and Routing Alarm Cables ..........................................................................................................7-13 7.2.1 Introduction to ALARM Interface and Cables...................................................................................7-13 7.2.2 Pin Assignment ..................................................................................................................................7-16 7.2.3 Procedure for Installing Alarm Cables ...............................................................................................7-17 7.3 Installing and Routing Clock Cables...........................................................................................................7-19 7.3.1 Introduction to Clock Interfaces.........................................................................................................7-19 7.3.2 Installation Procedure ........................................................................................................................7-19 7.4 Installing and Routing Network Cables ......................................................................................................7-21 7.4.1 Connecting Network Cables ..............................................................................................................7-21 7.4.2 Core Wire Colors of Network Cables ................................................................................................7-23 7.4.3 Installing Cables Between the Subrack and HUB..............................................................................7-25 7.4.4 Installing Network Cables Between NM Computer and HUB ..........................................................7-26

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

OptiX BWS 1600G Installation Guide

Figures

Figures
Figure 7-1 Cabinet power cable terminals..........................................................................................................7-2 Figure 7-2 Power switches .................................................................................................................................7-3 Figure 7-3 Subrack power cable terminals .........................................................................................................7-4 Figure 7-4 Connection of the power cables........................................................................................................7-5 Figure 7-5 Upward cabling for the protection grounding cables........................................................................7-7 Figure 7-6 Connection of power cables terminals ..............................................................................................7-8 Figure 7-7 Downward cabling for protection grounding cables....................................................................... 7-11 Figure 7-8 Connection of power cables terminals ............................................................................................7-12 Figure 7-9 ALARM interface ...........................................................................................................................7-14 Figure 7-10 Alarm cables .................................................................................................................................7-14 Figure 7-11 The alarm input transfer cable.......................................................................................................7-15 Figure 7-12 Alarm transfer cable......................................................................................................................7-15 Figure 7-13 Alarm cascading............................................................................................................................7-18 Figure 7-14 Subrack interface area...................................................................................................................7-19 Figure 7-15 Routing of clock cables.................................................................................................................7-20 Figure 7-16 Downward cabling........................................................................................................................7-21 Figure 7-17 Ethernet interfaces in the interface area of the subrack ................................................................7-21 Figure 7-18 Connection of network cables.......................................................................................................7-22 Figure 7-19 Network cable...............................................................................................................................7-23 Figure 7-20 Pin numbering of RJ45 connector.................................................................................................7-23 Figure 7-21 Connection relationship of straight-through network cables ........................................................7-24 Figure 7-22 Connection relationship of crossover network cables...................................................................7-24 Figure 7-23 Routing network cables in HUB plug-in frame ............................................................................7-26

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

iii

OptiX BWS 1600G Installation Guide

Tables

Tables
Table 7-1 Pin assignment of the external alarm input cable .............................................................................7-16 Table 7-2 Alarm output cable connection relationship .....................................................................................7-17 Table 7-3 Core wire colors of two connectors of the straight-through network cable ......................................7-24 Table 7-4 Core wire colors of two connectors of the crossover network cable ................................................7-25

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

7

Installing and Routing Cables

The cable system of the OptiX BWS 1600G optical transmission equipment is divided into internal cables and external cables. Internal cables are used to connect electrical interfaces in one cabinet. They have been installed in the cabinet before shipment and delivered together with the cabinet. They do not require on-site installation. External cables are used to connect electrical interfaces of one cabinet with those of other cabinet(s) or peripherals and require on-site installation. The external cables mainly consist of: Power cable (-48V/-60V power cable, power grounding cable) Protection grounding cable External alarm cable Clock cable Network cable

This chapter describes the procedure for installing and routing the cables as well as the precautions. Contents of this chapter: Title 7.1 Installing and Routing Power Cables 7.2 Installing and Routing Alarm Cables 7.3 Installing and Routing Clock Cables 7.4 Installing and Routing Network Cables Description Describes how to install and route the cabinet power cables and protection grounding cables. Describes how to install and route the external alarm cables. Describes how to install and route the clock cables. Describes how to install and route the network cables.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-1

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Remove the side doors before you install the cables. Refer to Chapter 2 "Removing doors of the cabinet" for the way to remove side doors.

For the orderliness and correctness of cable installation and for the convenience of maintenance, it is required to identify various equipment cables with labels during the on-site installation. Refer to Appendix B "Engineering Labels for Cables" for the way to paste labels and the information on them.

7.1 Installing and Routing Power Cables


This chapter describes how to install and route power cables and protection grounding cable.

7.1.1 Installation Preparation


Introduction to Cabinet Power Cable Terminal
The basic function of cabinet power cables is to lead -48V/-60V power supply, power ground (BGND) and protection ground (PGND) into the cabinet. All power cables are connected to the mapping terminals on the cabinet power panel at the top of the cabinet. The terminals on the cabinet power panel are shown in Figure 7-1. Figure 7-1 Cabinet power cable terminals
2 0A 20A 20A 2A 20A 20A 20A 2A

RTN(+) NEG(-)

RTN(+) NEG(- )

OUT1

OUT2

OUT3

AUX

O UT1

OUT2

OUT3

AUX

ON

ON

ON

ON

ON

ON

O FF

O FF

O FF

O FF

O FF

O FF

ALARM SERIAL
TEST

RUN PO W ER IN AL M SW 1 SW 2 SW 3

RUN PO W ER IN AL M SW 1 SW 2 SW 3

RUN AL M

MU TE

PMU PDU

PDU

RTN (+): Power grounding cable terminal NEG (-): Power cable terminal Grounding mark: Two grounding bolts

Introduction to Power Switch


All the power switches of the cabinet are on the panel of the power box. See Figure 7-2.

7-2

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Figure 7-2 Power switches


20A
R TN (+) N EG( - )

20A

20A

2A
R TN ( +) N EG( -)

20A

20A

20A

2A

O UT1

O UT2

O UT3

AU X

O UT1

O UT2

O UT3

AU X

ON OFF

ON OFF

ON OFF

ON OFF

ON OFF

ON OFF
AL AR M SER IA L

RUN ALM POWER IN SW1 PD U SW2 SW3

RUN ALM POWER IN SW1 PD U SW2 SW3

TEST
MUTE

RUN ALM PMU

ON

ON

ON

OFF

OFF

OFF

POWER IN

SW1

SW2

SW3

The cabinet supports dual power inputs (working and protection). Two power distribute units (PDU) are on the left side and the right side of the power box to provide two independent power supplies. "SW1"~"SW3" of each PDU on the panel of the power box are three power output switches.

SW1: Controls power supply of upper subrack SW2: Controls power supply of middle subrack SW3: Controls power supply of lower subrack

Introduction to Subrack Power Cable Terminal


The basic function of subrack power cables is to lead -48V DC power supply into the subrack. One end of the subrack power cables is connected to the output terminal on the cabinet power panel. The other end is connected to the mapping terminal in the interface area of the subrack.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-3

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Figure 7-3 shows the power cable terminals in the interface area of the subrack. Figure 7-3 Subrack power cable terminals

POWER1 POWER2
ETHERNET 1 ETHERNET 2 CLKIN 1 2 CLKOUT OCU CLKIN 1 2 3

3 PHONE 1 PHONE 2

6 F&f Serial 1 Serial 2 ALM F1 OAM


POWER1 POWER2

PHONE 3

Connection of Power Cables


Figure 7-4 shows the connection of power cables.

There are two types of power cables for a cabinet to access external power.

Black and blue: black for the grounding cable; blue for the power supply cable Gray and blue: blue for the grounding cable; gray for the power supply cable

7-4

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Figure 7-4 Connection of the power cables

AUX OUT3 OUT2 OUT1

OUT1 OUT2 OUT3 AUX NEG(-) NEG(-)

-48 V -48 V Office power supply 0V 0V

Office ground RTN(+) RTN(+)

HUB

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-5

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

7.1.2 Procedure for Upward Cabling


Purpose This procedure describes how to install and route the cabinet power cables and protection grounding cables in upward cabling mode. Cross screwdriver, Power cables, Protection grounding cable, Wire cutter, Wire stripper, Crimp tool Prerequisites Required/As needed The office power supply is prepared. The voltage ranges from 38.4 V DC to 72 V DC. Required

Tools /Materials

Install the PGND cable before you install the power cables.

Ensure that the power of the DC power distribution cabinet is shut off before you take any of the steps below.
If the cable is short, stop the cabling, and replace it with an appropriate one. Do not extend the cable by means of connecting or soldering. For detailed information about how to install the protection grounding cables in a cabinet with the grounding copper plat, refer to Chapter 1 "Installing Grounding Cables in a Cabinet" in OptiX BWS 1600G Backbone DWDM Optical Transmission System Document Update. Determine whether to use upward cabling mode or downward cabling mode according to the conditions in the equipment room. For downward cabling mode, refers to Section 7.1.3 "Procedure for Downward Cabling".

Step 1 Lay the cabinet power cables on the upper cabling frame. Lead the end installed with cord end terminal to the top of the cabinet. Step 2 Connect the lug of the green-yellow protection grounding cable to the grounding bolts at the top of the cabinet. See Figure 7-5.
Choose a way to install the protection grounding cable according to the specification of the lug and the amount of the grounding bolts at the top of the cabinet.

If the lug is OT single-hole naked crimping connector, install the protection grounding cable as shown in Figure 7-5 (1), (2). If the lug is OT dual-hole naked crimping connector, install the protection grounding cable as shown in Figure 7-5 (3), (4).

7-6

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Figure 7-5 Upward cabling for the protection grounding cables

3
1 2

5 4
3 4

1. Cabling frame 2. Protection grounding cable 3. OT single-hole naked crimping connector and two grounding bolts 4. OT dual-hole naked crimping connector and two grounding bolts 5. OT dual-hole naked crimping connector and one grounding bolt 6. OT single-hole naked crimping connector and one grounding bolt

Step 3 Lead the -48 V power cables and power grounding cables to the input cable terminal on the power distribution box panel through the power cable hole on the top of the cabinet. Step 4 Connect the power grounding cables. See Figure 7-6.

Plug the cord end terminal of the black power cable directly, with the fluted side facing the front of the cabinet, from up to down, into the input cable terminal marked with RTN1 (+) or RTN2 (+). Tighten the bolt to fix it.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-7

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

When you choose the black and blue power cable, choose the black cable as the power grounding cable. When you choose the gray and blue power cable, choose the blue cable as the power grounding cable

Step 5 Connect the -48 V power cables. See Figure 7-6.


Plug the cord end terminal of the blue power cable directly, from up to down, with the fluted side facing the front of the cabinet, into the input cable terminal marked with NEG1 (-) or NEG2 (-). Tighten the bolt to fix it.

Figure 7-6 Connection of power cables terminals

1 2

1. Power cables 4. -48 V power cable

2. Cabling frame 5. Power box

3. Power grounding cable

When you choose the black and blue power cable, choose the blue cable as the -48V power cable. When you choose the gray and blue power cable, choose the gray cable as the -48V power cable

Step 6 Add common washers and spring washers on the grounding bolts to fix the lugs firmly. Step 7 Put all the cables at the top of the cabinet in order. Bundle them properly. Step 8 Lay and bundle the cables on the upper cabling frame. Step 9 Lead power cables to the DC power distribution cabinet or other power supply equipment.

7-8

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Step 10 Lead the protection grounding cable to the protection grounding bar in the equipment room. Step 11 Cut the slack of the cables. Make the lugs in compliance with the corresponding terminals. Finally fix the cables to corresponding terminals.

When you make the lugs on both ends of the protection grounding cable and the lug on the end of the power cable connected to DC power distribution cabinet, the lugs should hold the strands tightly, and are wrapped tightly by the plastic insulation tape, so as not to uncover the naked cables and the lug stems. Step 12 Connect subrack power cables and HUB power cables. See Figure 7-4. Step 13 Attach labels to the cables. Refer to Appendix B "Engineering Labels for Cables" for the way to paste labels and the information on them. ----End.

7.1.3 Procedure for Downward Cabling


Purpose Tools /Materials Prerequisites Required/As needed This procedure describes how to install and route the cabinet power cables in downward cabling mode. Cross screwdriver, Power cable, Protection grounding cable Wire cutter, Wire stripper, Crimp tool The office power supply is prepared. The voltage ranges from 38.4 V DC to 72 V DC. Required

Install the PGND cable before you install the power cable.

Ensure that the power of the DC power distribution cabinet is shut off before you take any of the steps below.
If the cable is short, stop the cabling, and replace it with an appropriate one. Do not extend the cable by means of connecting or soldering. Determine whether to use upward cabling mode or downward cabling mode according to the conditions in the equipment room. Upward cabling mode refers to Section 7.1.2 "Procedure for Upward Cabling".

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-9

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Step 1 Lay the power cables under the antistatic floor. Lead the end installed with cord end terminal to the bottom of the cabinet. Step 2 Route power cable in the downward cabling mode.

Lead the cables into the cabinet through the support and then the power cable hole on the bottom of the cabinet. Lay them upward to the top of the cabinet along the signal cabling area at the right side of the cabinet. Lead -48V power cables and power grounding cables to the position of input cable terminal on the power distribution box through the space between the upper enclosure frame of the cabinet and the power distribution box. Lead PGND cable to the grounding bolt through the cabling hole on the top of the cabinet.

Step 3 Connect the lug of the green-yellow protection grounding cable to the grounding bolts at the top of the cabinet. See Figure 7-7.
Choose a way to install the protection grounding cable according to the specification of the lug and the amount of the grounding bolts at the top of the cabinet

If the lug is OT single-hole naked crimping connector, install the protection grounding cable as shown in Figure 7-7 (1), (2). If the lug is OT dual-hole naked crimping connector, install the protection grounding cable as shown in Figure 7-7 (3), (4).

7-10

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Figure 7-7 Downward cabling for protection grounding cables


5 6

1. Signal cabling area 2. Subrack 3. Support 4. Protection grounding cable 5. OT single-hole naked crimping connector and two grounding bolts 6. OT dual-hole naked crimping connector and two grounding bolts 7. OT dual-hole naked crimping connector and one grounding bolt 8. OT single-hole naked crimping connector and one grounding bolt

Step 4 Connect the power grounding cable. See Figure 7-8.


Plug the cord end terminal of the black power cable directly, with the fluted side facing the front of the cabinet, from up to down, into the input cable terminal marked with RTN1 (+) or RTN2 (+). Tighten the bolt to fix it.

When you choose the black and blue power cable, choose the black cable as the power grounding cable. When you choose the gray and blue power cable, choose the blue cable as the power grounding cable.

Step 5 Connect the -48V power cable. See Figure 7-8.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-11

7 Installing and Routing Cables


OptiX BWS 1600G Installation Guide

Plug the cord end terminal of the blue power cable directly, from up to down, with the fluted side facing the front of the cabinet, into the input cable terminal marked with NEG1 (-) or NEG2 (-). Tighten the bolt to fix it.

Figure 7-8 Connection of power cables terminals

1. Signal cabling area 5. Power grounding cable

2. Subrack 6. -48 V power cable

3. Support 7. Power box

4. Protection grounding cable

When you choose the black and blue power cable, choose the blue cable as the -48V power cable. When you choose the gray and blue power cable, choose the gray cable as the -48V power cable

Step 6 Add common washers and spring washers on the grounding bolts to fix the lugs firmly. Step 7 Put all the cables in the cabinet in order. Bundle them properly. Step 8 Lay and bundle the power cables under the antistatic floor.

7-12

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Step 9 Lead power cables and power grounding cables to the DC power distribution cabinet or other power supply equipment. Step 10 Lead the protection grounding cable to the protection grounding bar in the equipment room. Step 11 Cut the slack of the cables. Make the lugs in compliance with the corresponding terminals. Finally fix the cables to corresponding terminals.

When you make the lugs on both ends of the protection grounding cable and the lug on the end of the power cable connected to DC power distribution cabinet, the lugs should hold the strands tightly, and are wrapped tightly by the plastic insulation tape, so as not to uncover the naked cables and the lug stems. Step 12 Connect subrack power cables and HUB power cables. See Figure 7-4. Step 13 Attach labels to the cables. Refer to Appendix B "Engineering Labels for Cables" for the way to paste labels and the information on them. ----End.

7.1.4 Resistance Measurement before Power-Up


Before you power up the equipment, please use multimeter to measure the resistance between the power (NEG(-)) and the power ground (RTN(+))/PGND on the left side and the right side respectively. When the subrack power switches (SW1/SW2/SW3) are turned off, the resistance measured should be several kilo-ohms. If the measured resistance is less than 20 ohms, it shows that the short circuit exists between the power and the power ground/protection ground. Make sure to power up the equipment after eliminating the faults.

7.2 Installing and Routing Alarm Cables


This section describes how to install and route alarm cables.

7.2.1 Introduction to ALARM Interface and Cables


ALARM Interface
In the power box, the PMU board implements alarm input, alarm output and alarm cascading functions. The ALARM on the PMU is an external alarm interface, used for alarm/Boolean value input/output between the cabinet and users centralized alarm system. Up to 16 Boolean values can be input to the cabinet, while four Boolean values can be output. Output Boolean values from different cabinets can be cascaded.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-13

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

The positions of the PMU and ALARM interface in the power box are shown in Figure 7-9. Figure 7-9 ALARM interface

20A

20A

2 0A

2A

20A

2 0A

20A

2A

RTN(+) NEG(-)

RTN(+) NEG(-)

OUT 1

OU T 2

OUT 3

AU X

OU T 1

OUT2

OUT 3

AU X

ON

ON

ON

ON

ON

ON

O FF

O FF

O FF

O FF

O FF

O FF

AL AR M SER IAL
TEST RUN AL M

RUN PO W ER IN AL M SW 1 SW 2 SW 3

RUN PO W ER IN AL M SW 1 SW 2 SW 3

M U TE

PMU PDU

ALARM SERIAL
TEST
MU TE

PDU

RUN ALM

PMU

Alarm Cables
The alarm cables are shown in Figure 7-10:

X1 is a DB50 connector, inserted in the ALARM interface on the power box. W2 and W3 are alarm cascading/output cables, and X2 and X3 are DB9 connectors (male) for realizing alarm signal cascading and output. W1 is an alarm input cable. X4 is a DB37 connector (female) for accessing external alarm signals.

Figure 7-10 Alarm cables


W2 X2

W1

X1 X4 W3 X3

Alarm Input Transfer Cable


When external alarms are input, a 10 m alarm input transfer cable (DB37 male connector at one end and the other end reserved) is required to be connected with the alarm input cable. The external alarm input transfer cable is shown in Figure 7-11.

7-14

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Figure 7-11 The alarm input transfer cable


Pin.1

Pin.37

10m

If no external alarm is input for centralized monitoring in this station, the alarm input transfer cable is not required and W1 alarm input cable is reserved.

Alarm Transfer Cable


If a number of cabinets are installed side by side, the alarms of the cabinets can be cascaded via an alarm transfer cable and then output to the centralized alarm system.

Since the cascading connectors of the alarm cables shown in Figure 7-10 are all DB9 male connectors, another transfer cable with the both ends being DB9 female connectors is required for cascading alarms. The alarm transfer cable is shown in Figure 7-12 Figure 7-12 Alarm transfer cable

Alarm Output Transfer Cable


In the last cabinet for alarm cascading, alarm signals are output to the power distribution cabinet or the designated centralized alarm system in the equipment room via an alarm output transfer cable. One end of the alarm output transfer cable is DB9 female connector. It is connected to the cascading/output connector of the alarm cable as shown in Figure 7-10. The other end has no connector and is directly connected to the designated position through the core wire.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-15

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

7.2.2 Pin Assignment


Alarm Input Transfer Cable
The reserved end of the alarm input transfer cable has signal wires in five different colors: BLUE (8 in total), GRAY (6 in total), PINK (6 in total), Green (6 in total) and Orange (6 in total). The signal wires in the same color distinguish themselves by the tiny square spots in different colors (RED and BLK) on the wires.
(1) The core wire with red tiny square spots is defined as signal wire, while the core wire with black tiny square spots is defined as ground. (2) Each "x" means that there is a group of one tiny square spot at intervals. (e.g. BLUE/REDxxx means that there is a group of three red square spots on a blue signal wire at intervals.)

The pin assignment of the alarm input transfer cable is shown in Table 7-1. Table 7-1 Pin assignment of the external alarm input cable Pin No. Pin.1 Pin.2 Pin.3 Pin.4 Pin.5 Pin.6 Pin.7 Pin.8 Pin.9 Pin.10 Pin.11 Pin.12 Pin.13 Pin.14 Pin.15 Pin.16 Color and mark PINK/ REDx PINK/ BLKx ORG/ REDx ORG/ BLKx BLUE/ REDx BLUE/ BLKx GRN/ REDx GRN/ BLKx GRAY/ REDx GRAY/ BLKx PINK/ REDxx PINK/ BLKxx ORG/ REDxx ORG/ BLKxx BLUE/ REDxx BLUE/ BLKxx 7 4 10 3 9 8 2 Channel No. 1 Pin No. Pin.17 Pin.18 Pin.19 Pin.20 Pin.21 Pin.22 Pin.23 Pin.24 Pin.25 Pin.26 Pin.27 Pin.28 Pin.29 Pin.30 Pin.31 Pin.32 Color and mark GRN/ REDxx GRN/ BLKxx GRAY/ REDxx GRAY/ BLKxx PINK/ REDxxx PINK/ BLKxxx ORG/ REDxxx ORG/ BLKxxx BLUE/ REDxxx BLUE/ BLKxxx GRN/ REDxxx GRN/ BLKxxx GRAY/ REDxxx GRAY/ BLKxxx BLUE/ REDxxxx BLUE/ BLKxxxx 16 15 11 5 12 14 13 Channel No. 6

7-16

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Alarm Output Transfer Cable


The pin assignment of the alarm output cable is shown in Table 7-2. Table 7-2 Alarm output cable connection relationship Signal wire Major alarm Major alarm ground Critical alarm Critical alarm ground Auxiliary alarm 1 Auxiliary alarm 1 ground Auxiliary alarm 2 Auxiliary alarm 2 ground Color of core wire BLUE WHITE ORANGE WHITE GREEN WHITE BROWN WHITE Auxiliary alarm Boolean value 1 Auxiliary alarm Boolean value 2 Critical alarm Boolean value Output Major alarm Boolean value

7.2.3 Procedure for Installing Alarm Cables


Purpose Tools /Materials This procedure describes how to install alarm cables. Alarm cable Alarm input transfer cable Alarm cascading transfer cable Alarm output transfer cable Prerequisites Required/As needed The monitoring system in the equipment room has been installed properly, with interfaces reserved for use. Required

External alarm input includes environmental variables such as access control, smog, and so on. It is mainly to access various environment alarms in the equipment room for centralized monitoring. The user accesses the external alarm values directly. After the software judgment, the valid signals will be displayed at the NM. The OptiX BWS 1600G equipment can provide 4 alarm outputs: one is for critical alarm, another one for major alarm interface, and the other two for auxiliary alarm Boolean value.

Step 1 One alarm cable is used for each cabinet. Step 2 Plug the DB50 connector of the alarm cable in the ALARM interface on the power box of the cabinet. See Figure 7-13 (a). Step 3 Use the alarm transfer cable to connect the alarm cascading cables of adjacent cabinets to realize alarm cascading. See Figure 7-13 (b).

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-17

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Step 4 Connect the alarm input transfer cable to the alarm input cable of the last cabinet in the cascading. See Figure 7-13 (c). Step 5 Connect the reserved end of the input transfer cable to the monitoring system in the equipment room. Its pin assignment is shown in Table 7-1. Step 6 Use the alarm output transfer cable with one end to be connected to the alarm cascading/output cable of the last cabinet in the cascading. See Figure 7-13 (d). Step 7 Connect the other end of the alarm output transfer cable to the power distribution cabinet or the designated centralized alarm system in the equipment room through core wire. Its pin arrangement is shown in Table 7-2. Step 8 Route and bundle the surplus part of all alarm cables at the top of the cabinet. Step 9 Attach labels to all the alarm cables. Refer to Appendix B "Engineering Labels for Cables" for the way to paste labels and the information on them. Figure 7-13 Alarm cascading

1. Cabinet 2. Alarm cascading/output cable 4. Alarm transfer cable 5. Alarm input transfer cable 7. Alarm Boolean value from external system 8. Alarm Boolean value to centralized alarm system

3. Alarm input cable 6. Alarm output transfer cable

----End.

7-18

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

7.3 Installing and Routing Clock Cables


7.3.1 Introduction to Clock Interfaces
Each subrack of the OptiX BWS 1600G has 11 clock interfaces of three types, which are located in the interface area of the subrack, as shown in Figure 7-14. Figure 7-14 Subrack interface area
OCU CLKIN CLKIN CLKOUT

ETHERNET 1 ETHERNET 2 CLKIN 1 2

CLKOUT OCU CLKIN 1 2 3

3 PHONE 1 PHONE 2

6 F&f Serial 1 Serial 2 ALM F1 OAM


POWER1 POWER2

PHONE 3

The functions of clock interfaces are as follows:


CLKIN 1~3: SMB socket, three external clock input interfaces CLKOUT 1~6: SMB socket, 6 clock output interfaces OCU CKLIN: SMB socket, providing 2 external clock source interfaces for the OCU board.

7.3.2 Installation Procedure


Determine the subrack to be connected with the clock cable according to the configuration requirements and the cabling mode according to the conditions in the equipment room.

Procedure for Upward Cabling


Purpose Tools /Materials Prerequisites Required/As needed This procedure describes how to install clock cables in upward cabling mode. Clock cables The BITS system in the equipment room has been installed properly, with interfaces reserved for use. As needed

Step 1 Lead the clock cable into the cabinet from the left signal cable hole on the top of the cabinet. Step 2 Lay the clock cable to the corresponding subrack along the signal cabling area on the left of the cabinet.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-19

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Step 3 Lead the clock cable to the subrack interface area from the space at the left side of the subrack interface area. See Figure 7-15. Figure 7-15 Routing of clock cables

Step 4 Plug the connector of the clock cable into the corresponding clock interface in the subrack interface area and tighten it properly. Step 5 Lay the clock cable on the upward cabling frame and connect it to the corresponding BITS system in the equipment room. Step 6 Bundle the clock cables and attach labels to them. Refer to Appendix B Engineering Labels for Cables for the way to paste labels and the information on them. ----End.

Procedure for Downward Cabling


Purpose Tools /Materials Prerequisites Required/As needed This procedure describes how to install clock cables in downward cabling mode. Clock cables The BITS system in the equipment room has been installed properly, with interfaces reserved for use. As needed

Step 1 Pass the clock cable through the subrack, and lead it into the cabinet from the left signal cable hole on the bottom of the cabinet. Step 2 Lay the clock cable to the corresponding subrack along the signal cabling area on the left of the cabinet. Step 3 Lead the clock cable to the subrack interface area from the trough at the side of the subrack interface area. See Figure 7-16.

7-20

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Figure 7-16 Downward cabling

Step 4 Plug the connector of the clock cable into the corresponding clock interface in the subrack interface area and tighten it properly. Step 5 Lay the clock cable under the ESD floor and connect it to the corresponding BITS system in the equipment room. Step 6 Bundle the clock cables and attach labels to them. Refer to Appendix C Engineering Labels for Cables for the way to paste labels and the information on them. ----End.

7.4 Installing and Routing Network Cables


7.4.1 Connecting Network Cables
Each subrack of the OptiX BWS 1600G has two Ethernet interfaces, ETHERNET1 and ETHERNET2. They are at the upper left corner of the interface area of the subrack. See Figure 7-17. Figure 7-17 Ethernet interfaces in the interface area of the subrack
ETHERNET 2 ETHERNET 1

ETHERNET 1 ETHERNET 2 CLKIN 1 2

CLKOUT OCU CLKIN 1 2 3

3 PHONE 1 PHONE 2

6 F&f Serial 1 Serial 2 ALM F1 OAM


POWER1 POWER2

PHONE 3

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-21

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Connecting ETHERNET1
ETHERNET1 is used to realize the communication between subracks. In this case, a straight-through network cable should be made on the site. The method is to connect ETHERNET1 interface of all the subracks in the OTM, OLA or OADM equipment to the HUB at the bottom of the cabinet. At the station with NM, the straight-through cable is also required to connect cabinet HUB to the network interface of the NM computer. Figure 7-18 shows the connection of ETHERNET1 network cables. Figure 7-18 Connection of network cables

Interface area of upper subrack

Subrack ETHERNET1
Interface area of middle subrack

Network cables

Interface area of lower subrack

NM computer

HUB

Network cables

Connecting ETHERNET2
ETHERNET2 is used for inter-subrack communication required by special network function. Some network functions, such as ALC and APE, etc., need the support of multiple boards. When these boards are in different subracks, the straight-through network cable is required to connect ETHERNET2 of each subrack to another HUB at the bottom of the cabinet, so as to enable communication between subracks through internal protocol. If only two subracks are to be connected, it is recommended to connect ETHERNET2 of the two subracks with a crossover network cable.

7-22

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

ETHERNET1 and ETHERNET2 in the subrack interface area cannot be substituted for each other. Port 1 and UPLINK port of the HUB cannot be used simultaneously

7.4.2 Core Wire Colors of Network Cables


The structure of the network cable is an 8-core category-5 twisted pair cable with RJ-45 connectors on both ends. See Figure 7-19. Figure 7-19 Network cable

8 6 3 2 1

8 6 3 2 1

X1

X2

The network cable includes the straight-through cable and crossover cable. The straight-through cable and the cross-over cable differ in connection relationship but have the same structure. Both the straight-through and crossover network cables adopt the RJ45 connector. The connector pins are numbered as follows: Turn the pin side upward, hold the cable close to your side, and the pins are numbered 1~8 from left to right. See Figure 7-20. Figure 7-20 Pin numbering of RJ45 connector
PIN #8 PIN #1

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-23

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Straight-through Network Cable


The connection is shown in Figure 7-21. The core wire colors of two connectors of the straight-through network cable are shown in Table 7-3. Figure 7-21 Connection relationship of straight-through network cables

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

Table 7-3 Core wire colors of two connectors of the straight-through network cable Network cable connector Head end Tail end Color of core wire 1 White and orange White and orange 2 Orange Orange 3 White and green White and green 4 Blue Blue 5 White and blue White and blue 6 Green Green 7 White and brown White and brown 8 Brown Brown

Crossover Network Cable


The connection relationship of crossover network cables is shown in Figure 7-22. The core wire colors of two connectors of the crossover network cable are shown in Table 7-4. Figure 7-22 Connection relationship of crossover network cables

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

7-24

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Table 7-4 Core wire colors of two connectors of the crossover network cable Network cable connector Head end Tail end Color of core wire 1 White and orange White and green 2 Orange Green 3 White and green White and orange 4 Blue Blue 5 White and blue White and blue 6 Green Orange 7 White and brown White and brown 8 Brown Brown

Usually, there are four pairs of twisted pair cables in the 8-core network cable. Pins 1 and 2 of RJ-45 connector should share a pair of twisted pair cables. Pins 3 and 6 should share another pair of twisted pair cables. Otherwise, the signal transmission distance will be greatly limited.

7.4.3 Installing Cables Between the Subrack and HUB


Purpose Tools /Materials Prerequisites Required/As needed This procedure describes how to install network cables. Crimping pliers with crystal head, Ethernet cables Cable ties The subracks and HUB have been installed. Required

The connection of network cables of ETHERNET1 is taken as an example. That of ETHERNET2 is basically the same.

Step 1 Cut out a network cable according to the distance between ETHERNET1 of each subrack and the HUB at the bottom of the cabinet. Step 2 Make RJ-45 connector at the both sides of all network cables. For the core wire colors of straight-through cable, see Section 7.4.2 in this chapter. Step 3 Lay the network cables along the signal cabling area on the left of the cabinet. Step 4 Lay one end to the corresponding subrack interface area. Step 5 Lay the other end to the HUB at the bottom of the cabinet. Step 6 Lead the network cable into the subrack interface area along the trough at the side of the subrack interface area. Step 7 Insert the network cable into ETHERNET1. Step 8 Lead the other end of the network cable into the subrack from the Hub plug-in frame. Insert it into the corresponding HUB port. See Figure 7-23.

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-25

7 Installing and Routing Cables

OptiX BWS 1600G Installation Guide

Figure 7-23 Routing network cables in HUB plug-in frame

2 3

1. Cabinet signal cabling area 3. Cabling hole on HUB plug-in frame

2. Network cables 4. HUB plug-in frame

----End.

7.4.4 Installing Network Cables Between NM Computer and HUB


Decide whether to use upward cabling or downward cabling according to the condition in the equipment room.

Upward Cabling
Purpose Tools /Materials Prerequisites Required/As needed This procedure describes how to install network cables between NM computer and HUB in upward cabling mode. Crimping pliers with crystal head, Ethernet cables Cable ties The Ethernet equipment in the equipment room has been installed, with interfaces reserved for use. Required

Step 1 Cut out a network cable according to the distance between the NM computer network port and the HUB Step 2 Make Rj45 connectors at the both ends of the network cable. For the core wire colors of straight-through cable, see Section 7.4.2 in this chapter. Step 3 Lead one end of the network cable through the left side cabling hole on the top of the cabinet.

7-26

Huawei Technologies Proprietary

Issue 03 (2007-04-30)

OptiX BWS 1600G Installation Guide

7 Installing and Routing Cables

Step 4 Route the cables to the HUB at the cabinet bottom along the signal cabling area on the left side of the cabinet. Step 5 Lead the network cable into the HUB plug-in frame from the Cabling hole. Insert it into the corresponding HUB port. See Figure 7-23. Step 6 Lay the network cable on the upper cabling frame. Step 7 Lead the other end of the network cable to the network interface of the NM computer in the equipment room. Step 8 Bundle the network cables. Attach labels to them. Refer to Appendix B "Engineering Labels for Cables". ----End.

Downward Cabling
Purpose Tools /Materials Prerequisites Required/As needed This procedure describes how to install network cables between NM computer and HUB in downward cabling mode. Crimping pliers with crystal head, Ethernet cables Cable ties The Ethernet equipment in the equipment room has been installed, with interfaces reserved for use. Required

Step 1 Cut out a network cable according to the distance between the NM computer and the HUB. Step 2 Make RJ45 connectors at the both sides of the network cable. For the core wire colors of straight-through cable, see Section 7.4.2 in this chapter. Step 3 Through the support, lead one end of the network cable through the left side cabling hole at the bottom of the cabinet. Step 4 Lead the network cable into the HUB plug-in frame from the Cabling hole. Insert it into the corresponding HUB port. See Figure 7-23. Step 5 Lay the network cable under the antistatic floor. Step 6 Lead the other end of the network cable to the network interface of the NM computer in the equipment room. Step 7 Bundle the network cables. Attach labels to them. Refer to Appendix B "Engineering Labels for Cables". ----End

Issue 03 (2007-04-30)

Huawei Technologies Proprietary

7-27