LV Qualified Persons
Prevent Recurrence
Safety Facts
Average of 4,000 non-disabling and 3,600 disabling electrical contact injuries annually in the United States. One person is electrocuted in the workplace every day. Electrocutions are the fourth leading cause of traumatic occupational fatalities. Over 2,000 workers are sent to burn centers each year with electrical burns.
Safety Facts
An electrical industry 10-year study of 120,000 workers 125 i injuries j i per year 77% electrical arc injuries 21% permanent disabilities 2.4% fatalities
Based on ED France data, IEEE Presentation from M. Capelli-Schellpfeffer, M.D. Electrical Trauma Research Program (University of Chicago)
4
Safety Facts
700 650 600 550 500 450 400
1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006
Statistics from BLS website,. Analysis by Hugh Hoagland ArcWear.com. To see calculations, visit www.arcwear.com/stats.mht.
Safety Facts
Safety Overall
1 to 300 1 Fatality
30 Lost-Time j Injuries
1 to 10
1 Fatality
Electrical Safety
10 Recordable Injuries
38
Probability of Survival
100 80
25% Body Burn 50% Body Burn 75% Body Burn Arc Exposure w/ FR
Chance of Survival, %
60 40 20 0
Shirt Burns
20-29
30-39
40-49
50-59
Responsibilities to Contractors
Responsibilities to Contractors
TESTING IS TOUCHING.
Layering Principles
NFPA 70E does not recognize non-FR layers as adding arc flash protection in HRC tables. Only FR layers can be counted toward the total protective t ti calorie l i count. t Although layered FR garments may provide protection beyond the actual calorie count, only the arc rating values of individual layers is acceptable in the total count unless the system is tested.
NFPA 70E Annex M
Safety glasses Hearing protection Leather gloves if rubber insulating gloves are not required for shock protection Non-melting, flammable clothing with 4.5 oz/yd2
Minimum requirements your location may require additional PPE.
Category 1 4 cal/cm
Safety glasses 4 cal/cm2 arc arc-rated face shield or flash hood Hearing protection Leather gloves if rubber insulating gloves are not required for shock protection Hard hat Leather work shoes, as needed
Back Exposure
Balaclava and shield No Safety Glasses
Arc-rated gloves if rubber insulating gloves Arcare not required for shock protection Total of 25 cal/cm2 arc arc-rated protection: Shirt and pants, coveralls, arc flash suit, or any combination. 25 cal/cm2 arc-rated flash hood
10
Arc-rated gloves if rubber insulating gloves Arcare not required for shock protection Total of 40 cal/cm2 arc arc-rated protection: Shirt and pants, coveralls, arc flash suit, or any combination. 40 cal/cm2 arc-rated flash hood
Either
HRC 2
Or
HRC4
Category 2 8 cal/cm Category 4 40 cal/cm
11
12
Hazard Assessment
Regulations & Standards NFPA 70B requires power circuit breakers be maintained & calibrated on an interval required by the manufacture or every three to five years. Breaker maintenance and calibration are critical to arc flash protection.
NFPA 70E 205.3 Overcurrent Device ANSI/NETA MTS-2007 is equivalent.
12
13
Hazard Assessment
Equipment must be field labeled with labels displaying either the incident energy level or the required PPE.
WARNING
Table Changes
14
Table Changes
Table Changes
Table Changes
15
Alerting Techniques
Safety signs & tags Warn about electrical hazards. Must meet ANSI Z535. Barricades and signs
Used when signs are not adequate or exposed, live parts are present. Placed at the limited approach boundary or arc flash boundary, which ever greater. Attendants Used when signs and barricades do not provide sufficient warning. 88
Levels of Training
Adequate for the tasks involved. All persons must be trained in any safety-related practices necessary for their safety. To work inside the limited approach boundary, an unqualified person must be trained on:
Hazards involved and potential injuries. PPE required. Distances to maintain. Other safe work practices related to task.
NFPA 70E 110.6
16
Retraining required:
Supervision or annual inspection indicate employees not complying with required work practices. New technology, new types of equipment, or changes in procedures require different safe work practices. If safe work practices not normally used are required.
Documentation Required
Demonstrated proficiency. Name and dates training conducted. Maintained for duration of employment.
NFPA 70E 110.6 (D)
17
NESC
National Electric Safety Code Updated Regularly ANSI C-2 NEC is ANSI C-3 Safety for Utilities
NESC Hazard Assessment Clothing effective as of January 1, 2009 Arc Flash Assessment required If exposure greater than 2 cal/cm
employer shall require employees to wear clothing that has an effective arc rating not less than the anticipated level of arc energy
18
Things to do, Review Conduct Hazard Analysis/Selective Coordination study Determine a hazard mitigation strategy Update Single Line Drawings p Electrical Safety y Program g Develop Select PPE Train employees Label equipment Audit for compliance Review program annually
Contact Information
www e hazard com www.e-hazard.com questions@e-hazard.com Or call us at 502-716-7073
19