VOLUME FLOW CONTROLLERS

VOLUME FLOW CONTROLLERS


CONSTANT VOLUME FLOW CONTROLLERS RECTANGULAR KP
Description
Constant volume flow controllers KP and KP-I are mechanical controllers used to maintain a constant volume flow rate
independently of the pressure variations in ventilation and air conditioning systems. Controllers can be installed in a
supply and extract air systems.
Each controller is set to the required flow rate and subjected to the aerodynamic function test conducted in our test
facility.
The flow rate can be easily set or reset by adjusting the control lever on the calibrated scale. This is done by loosing
the control lever's wing bolt and turning the control lever's arrow pointer to the desired value. When adjusted, the
control lever is fixed by tightening the wing bolt.
Controllers work at the differential pressure range from 50 to 1000 Pa and the air velocity range from 3 to 10 m/s. As a
reference value, recomended air velocity is around 6,5 m/s, where the accuracy of a constant flow rate is usually
within a tolerance from 5% of the set value.
The controller can operate, without the direct influence of weather conditions on the operation, within a temperature
range of -20C up to 80C and relative humidity up to 80%.
Controllers should be stored in closed and dry places at temperatures from -20C to +60C.
Controller versions:
KP - Constant volume flow controller, rectangular
KP-I - Constant volume flow controller, rectangular - insulated

Technical data
Construction
Casing
CASING - made of galvanised sheet steel
Shock absorber
MECHANISM - control lever mechanism adjusts the
spring tension to control the air flow
DAMPER BLADE - provides resistance to the air flow
SHOCK ABSORBER - serves to absorbe the damper
blade vibration coused by the air flow
Damper blade

Control lever
Mechanism
Insulation Cladding

KP

INSULATION CLADDING - 30 mm mineral wool layer


with galvanised sheet steel outer cover

VOLUME FLOW CONTROLLERS


Dimensions
Dual controller

30

B
B + 60

150
200
250
300
350
400
450
500
550
600

150

200

250

300

P
P
P
P
P
P
P
O
O
O

P
P
P
P
P
P
P
P
P
P

P
P
P
P
P
P
P
P
P
P

P
P
P
P
P
P
P
P
P
P

385

03

H
B

H
H + 60

30

H
H + 60

Single controller

B
B+60

30

385
H

400

450

500

550

600

P
P
P
P
P

P
P
P
P
P

P
P
P
P
P

P
P
P
P
P

P
P
P
P
P

1800

2000

2500

B
400
450
500
550
600

Quick selection Table


Q (m/h)

BxH (mm)

200

300

400

500

600

700

260

150x150
200x150
250x150
300x150
400x150
450x150
200x200
250x200
300x200
350x200
400x200
450x200
500x200
550x200
600x200
250x250
300x250
350x250
400x250
450x250
500x250
550x250
600x250
300x300
350x300
400x300
450x300
500x300
550x300
600x300

800

900

1000

1200

1400

1600

3000

3500

4000

5000

6000

740
960

400
400

1200
1800

600
600

2100
2500

700
1400

600
600

1700
1800

700

2500

800
900

3300
3400
3600

1000
1080

4000

1200
900

2900
2190

600
800

2600
970

3200
1080

3600
4000
3800
4300
3600

1200
1400
1500
1700
2900

900
1100

3300
1300
1500
1900
1900
1900

3800
4000
4200
4500
6100

Order codes
Constant volume flow
controller, rectangular

KP/KP-I - BxH - Q
Required flow rate (m3/h)
Constant volume flow controller,
rectangular - insulated

Dimensions

KP

VOLUME FLOW CONTROLLERS


Flow rate range in relation to duct cross section
*Flow rate calibration possible at air velocities from 3 to 10 m/s
=1,2 kg/m
1900

7000
6000
5000

1500

4000

10 m/s

1000
900
800
700
600
500

3000
2000

300

1500
900
800
700
600

3 m/s
200

Q [I/s]

Q [m/H]

400

150

500
400

100
90
80
70
60
50

300
200

40

0,2

0,15

0,1

0,09

0,08

0,07

0,06

0,05

0,04

0,035

0,03

0,02

0,025

30

100

A [m2]

Minimum static pressure difference at the controller.


250
225
200

Dp [Pa]

175
150
125
100
75
50
25
0
0

KP

10

11

12

v (m/s)

Legend:
Q (m3/h or l/s)
v (m/s)
A (m2)
Dp (Pa)

flow rate
air velocity
effective outlet area
static pressure difference

VOLUME FLOW CONTROLLERS


Flow noise levels
Single controller
Dp = 100 Pa

Dp = 250 Pa

Dp = 500 Pa

Sound power Lw [dB(A)]

Sound power Lw [dB(A)]

Model

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

300

2000 Hz

600

300

1000 Hz

450

300

500 Hz

300

200

250 Hz

400

200

125 Hz

300

200

63 Hz

200

150

Q [m3/h]

300

150

v [m/s]

150

H [mm]

B [mm]

Sound power Lw [dB(A)]

243

48

47

46

44

42

40

38

35

48

56

55

54

52

50

48

46

43

56

62

61

60

58

56

54

52

49

62

486

53

53

51

50

48

47

44

42

54

61

60

59

58

56

54

52

50

62

67

66

65

64

62

61

58

56

68

729

56

55

55

53

52

50

48

46

57

64

63

62

61

60

58

56

54

65

70

69

68

67

66

64

62

60

71

486

51

49

48

46

44

42

39

36

49

59

57

56

54

52

50

47

44

57

65

63

62

60

58

56

53

50

63

972

55

55

53

52

50

48

46

43

56

63

63

61

60

58

56

54

51

64

69

69

67

66

64

62

60

57

70

1458

58

58

57

55

54

52

50

47

59

66

65

65

63

62

60

58

55

67

72

72

71

69

68

66

64

61

73

432

51

49

48

46

44

42

39

36

49

59

57

56

54

52

50

47

44

57

65

63

62

60

58

56

53

50

63

864

55

55

53

52

50

48

46

43

56

63

63

61

60

58

56

54

51

64

69

69

67

66

64

62

60

57

69

1296

58

58

57

55

54

52

50

47

59

66

65

65

63

62

60

58

55

67

72

72

71

69

68

66

64

61

70

648

52

51

49

47

45

43

40

37

50

60

59

57

55

53

51

48

45

58

66

65

63

61

59

57

54

51

64

1296

57

56

55

53

51

49

47

44

57

65

64

63

61

59

57

55

52

65

71

70

69

67

65

63

61

58

71

1944

60

59

58

56

55

53

51

48

60

68

67

66

64

63

61

58

56

68

74

73

72

70

69

67

64

62

74

864

53

51

50

48

46

43

40

37

51

61

59

58

56

54

51

48

45

59

67

65

64

62

60

57

54

51

65

1728

58

57

55

54

52

50

47

44

57

66

65

63

62

60

58

55

52

65

72

71

69

68

666

64

61

58

71

2592

60

60

59

57

55

53

51

48

61

68

68

67

65

63

61

59

56

69

74

74

73

71

69

67

65

62

75

972

53

52

50

48

46

44

41

38

52

61

60

58

56

54

52

49

46

60

67

66

64

62

60

58

55

52

66

1944

59

57

56

55

53

50

48

45

58

66

65

64

62

61

58

56

53

66

73

71

70

68

67

64

62

59

72

2916

61

61

59

58

56

54

52

49

62

69

68

67

66

64

62

60

57

70

75

74

73

72

70

68

66

63

76

1458

55

53

52

49

47

45

42

38

53

63

61

59

57

55

52

50

46

61

69

67

66

63

61

58

56

52

67

2916

60

59

57

56

54

51

49

46

59

68

67

65

64

62

59

57

54

67

74

73

71

70

68

65

63

60

73

4374

63

62

61

59

57

55

53

50

63

71

70

69

67

65

63

61

58

71

77

76

75

73

71

69

67

64

77

1944

55

54

52

50

48

45

42

39

53

63

62

60

58

56

53

50

47

61

69

68

66

64

62

59

56

53

67

3888

61

59

58

56

54

52

49

46

60

69

67

66

64

62

60

57

54

68

75

73

72

70

68

66

63

60

74

5832

64

63

61

60

58

56

53

50

63

72

71

69

68

66

64

61

58

71

78

77

75

74

72

70

67

64

77

KP

VOLUME FLOW CONTROLLERS

Single controller - insulated


Dp = 100 Pa

Dp = 250 Pa

Dp = 500 Pa

Model

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

300

2000 Hz

600

300

1000 Hz

450

300

500 Hz

300

200

250 Hz

400

200

125 Hz

300

200

63 Hz

200

150

Sound power Lw [dB(A)]

Q [m3/h]

300

150

Sound power Lw [dB(A)]

v [m/s]

150

H [mm]

B [mm]

Sound power Lw [dB(A)]

243

39

38

37

35

33

31

29

26

39

47

46

45

43

41

39

37

34

47

53

52

51

49

47

45

43

40

53

486

44

44

42

41

39

38

35

33

45

52

51

50

49

47

45

43

41

53

58

57

56

55

53

52

49

47

59

729

47

46

46

44

43

41

39

37

48

55

54

53

52

51

49

47

45

56

61

60

59

58

57

55

53

51

62

486

42

40

39

37

35

33

30

27

40

50

48

47

45

43

41

38

35

48

56

54

53

51

49

47

44

41

54

972

46

46

44

43

41

41

39

36

49

56

56

54

53

51

49

47

44

57

62

60

58

57

55

53

51

48

61

1458

49

49

48

46

45

45

41

38

50

57

56

56

54

53

51

49

46

58

63

63

62

60

59

57

55

52

64

432

42

40

39

37

35

35

30

27

40

50

48

47

45

43

41

38

35

48

56

54

53

51

49

47

44

41

54

864

46

46

44

43

41

41

37

34

47

54

54

52

51

49

47

45

42

55

60

60

58

57

55

53

51

48

60

1296

49

49

48

46

45

45

41

38

50

57

56

56

54

53

51

49

46

58

63

63

62

60

59

57

55

52

61

648

43

42

40

38

36

36

31

28

41

51

50

48

46

44

42

39

36

49

57

56

54

52

50

48

45

42

55

1296

48

47

46

44

42

42

38

35

48

56

55

54

52

50

48

46

43

56

62

61

60

58

56

54

52

49

62

1944

51

50

49

47

46

46

42

39

51

59

58

57

55

54

52

49

47

59

65

64

63

61

60

58

55

53

65

864

44

42

41

39

37

36

31

28

42

52

50

49

47

45

42

39

36

50

58

56

55

53

51

48

45

42

56

1728

49

48

46

45

43

43

38

35

48

57

56

54

53

51

49

46

43

56

63

62

60

59

56

55

52

49

62

2592

51

51

50

48

46

44

42

39

52

59

59

58

56

54

52

50

47

60

65

65

64

62

60

58

56

53

66

972

44

43

41

39

37

35

32

29

43

52

51

49

47

45

43

40

37

51

58

57

55

53

51

49

46

43

57

1944

50

48

47

46

44

41

39

36

49

57

56

55

53

52

49

47

44

57

64

62

61

59

58

55

53

50

63

2916

52

52

50

49

47

45

43

40

53

60

59

58

57

55

53

51

48

61

66

65

64

63

61

59

57

54

67

1458

46

44

43

40

38

36

33

29

44

54

52

50

48

46

43

41

37

52

60

58

57

54

52

49

47

43

58

2916

51

50

48

47

45

42

40

37

50

59

58

56

55

53

50

48

45

58

65

64

62

61

59

56

54

51

64

4374

54

53

52

50

48

46

44

41

54

62

61

60

58

56

54

52

49

62

68

67

66

64

62

60

58

55

68

1944

46

45

43

41

39

36

33

30

44

54

53

51

49

47

44

41

38

52

60

59

57

55

53

50

47

44

58

3888

52

50

49

47

45

43

40

37

51

60

58

57

55

53

51

48

45

59

66

64

63

61

59

57

54

51

65

5832

55

54

52

51

49

47

44

41

54

63

62

60

59

57

55

52

49

62

69

68

66

65

63

61

58

55

68

Sound power level in dB(A)/octave in relation to reference sound power (10-12 W)

KP

VOLUME FLOW CONTROLLERS

Dual controller
Dp = 100 Pa

Dp = 250 Pa

Dp = 500 Pa

Model

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

600

500 Hz

600

500

250 Hz

600

500

125 Hz

500

400

63 Hz

600

400

Sound power Lw [dB(A)]

Q [m3/h]

500

400

Sound power Lw [dB(A)]

v [m/s]

400

H [mm]

B [mm]

Sound power Lw [dB(A)]

1728

55

54

52

50

48

45

42

39

53

63

62

60

58

56

53

50

47

61

69

68

66

64

62

59

56

53

67

3456

61

59

58

56

54

52

49

46

60

69

66

64

62

60

57

54

68

73

72

70

68

66

63

60

74

5184

72

71

69

68

66

64

61

58

71

78

77

75

74

72

70

67

64

77

2160

56

55

53

51

48

45

42

39

54

64

63

61

59

56

53

50

47

62

70

69

67

65

62

59

56

53

68

4320

61

60

59

57

55

52

50

47

60

69

68

67

65

63

60

58

55

68

75

74

73

71

69

66

64

61

74

6480

72

71

70

68

68

64

62

59

72

78

77

76

74

72

70

68

65

78

2592

57

55

53

51

49

46

43

40

54

65

63

61

59

57

54

51

47

62

71

69

67

65

63

60

57

53

68

5184

62

61

59

57

55

53

50

47

61

70

69

67

65

63

61

58

55

68

76

75

73

71

69

67

64

61

75

776

73

72

70

69

67

64

62

59

72

79

78

76

75

73

70

68

65

78

2700

57

55

53

51

49

46

43

40

54

65

63

61

59

57

54

51

48

62

71

69

67

65

63

60

57

54

68

5400

62

61

59

57

55

53

50

47

61

71

69

67

65

63

61

58

55

69

76

75

73

72

69

67

64

61

75

8100

73

72

71

69

67

65

62

59

72

79

78

77

75

73

71

68

65

78

3240

57

55

54

52

49

46

43

40

55

65

64

62

60

57

54

51

48

63

71

70

68

66

63

60

57

54

75

6480

63

61

60

58

56

53

50

47

61

71

69

68

66

63

61

58

55

69

77

76

74

72

70

67

64

61

75

9720

74

73

71

67

65

62

60

73

80

79

77

76

73

71

69

66

79

3888

58

56

54

52

50

47

44

40

55

66

64

62

60

58

55

52

48

63

72

70

68

66

64

61

58

54

69

7776

64

62

61

59

56

54

51

48

62

71

70

68

67

64

61

59

56

70

77

76

75

73

70

68

65

62

76

11664

74

73

72

70

68

66

63

60

73

81

79

78

76

74

72

69

66

79

KP

VOLUME FLOW CONTROLLERS

Dual controller - insulated


Dp = 100 Pa

Dp = 250 Pa

Dp = 500 Pa

Model

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

600

500 Hz

600

500

250 Hz

600

500

125 Hz

500

400

63 Hz

600

400

Sound power Lw [dB(A)]

Q [m3/h]

500

400

Sound power Lw [dB(A)]

v [m/s]

400

H [mm]

B [mm]

Sound power Lw [dB(A)]

1728

46

45

43

41

39

36

33

30

44

54

53

51

49

47

44

41

38

52

60

59

57

55

53

50

47

44

58

3456

52

50

49

47

45

43

40

37

51

60

-4

57

55

53

51

48

45

59

-4

64

63

61

59

57

54

51

65

5184

63

62

60

59

57

55

52

49

62

69

68

66

65

63

61

58

55

68

2160

47

46

44

42

39

36

33

30

45

55

54

52

50

47

44

41

38

53

61

60

58

56

53

50

47

44

59

4320

52

51

50

48

46

43

41

38

51

60

59

58

56

54

51

49

46

59

66

65

64

62

60

57

55

52

65

6480

63

62

61

59

59

55

53

50

63

69

68

67

65

63

61

59

56

69

2592

48

46

44

42

40

37

34

31

45

56

54

52

50

48

45

42

38

53

62

60

58

56

54

51

48

44

59

5184

53

52

50

48

46

44

41

38

52

61

60

58

56

54

52

49

46

59

67

66

64

62

60

58

55

52

66

776

64

63

61

60

58

55

53

50

63

70

69

67

66

64

61

59

56

69

2700

48

46

44

42

40

37

34

31

45

56

54

52

50

48

45

42

39

53

62

60

58

56

54

51

48

45

59

5400

53

52

50

48

46

44

41

38

52

62

60

58

56

54

52

49

46

60

67

66

64

63

60

58

55

52

66

8100

64

63

62

60

58

56

53

50

63

70

69

68

66

64

62

59

56

69

3240

48

46

45

43

40

37

34

31

46

56

55

53

51

48

45

42

39

54

62

61

59

57

54

51

48

45

66

6480

54

52

51

49

47

44

41

38

52

62

60

59

57

54

52

49

46

60

68

67

65

63

61

58

55

52

66

9720

65

64

62

-9

58

56

53

51

64

71

70

68

67

64

62

60

57

70

3888

49

47

45

43

41

38

35

31

46

57

55

53

51

49

46

43

39

54

63

61

59

57

55

52

49

45

60

7776

55

53

52

50

47

45

42

39

53

62

61

59

58

55

52

50

47

61

68

67

66

64

61

59

56

53

67

11664

65

64

63

61

59

57

54

51

64

72

70

69

67

65

63

60

57

70

Sound power level in dB(A)/octave in relation to reference sound power (10-12 W)

KP

VOLUME FLOW CONTROLLERS


Installation
Rectangular controllers are flanged on both sides for connection with the standard 30 mm ventilation duct flange.
The controller can be installed in horizontal, vertical or inclined mounted duct in a manner that the rotational axis of the
dampe blade is always in a horizontal position. Also it is necessary to pay attention to the correct mounting direction
shown with the air flow direction arrow on the controller.
Required length of the straight duct section is Lmin3dek before and Lmin1,5dek after the the controller. If this
lengths are smaller, deviations of the set flow rate can occure and the stated accuracy of the flow rate may not be
achived; therefore, such installations are not recommended.
Controllers are maintenance free.

AIR FLOW

HB

INCORRECT
INSTALLATION

CORRECT
INSTALLATION

Lmin = 3dek

dek =

2BH
B+H

KP

VOLUME FLOW CONTROLLERS


CONSTANT VOLUME FLOW CONTROLLERS CIRCULAR KC
Description
Controller versions:
KC - Constant volume flow controller, circular
KC-I - Constant volume flow controller, circular insulated

Technical data
Construction
The damper blades shaft is supported by two smooth-running maintenance-free brass bearings. Pneumatic shock
absorber smooths out the damping shock impulse, preventing the vibration and oscillation of the damper blade to
ensure sensitive responding behaviour and a precise control.

Shock absorber

CASING - made of galvanised sheet steel

Casing

MECHANISM - control lever mechanism adjusts the


spring tension to control the air flow
Control
lever

DAMPER BLADE - provides resistance to the air flow


SHOCK ABSORBER - serves to absorbe the damper
blade vibration coused by the air flow

Mechanism
Damper blade

Insulated version:
Controllers are available with 30 mm acoustic and thermal insulation.
Insulation Cladding
INSULATION CLADDING - 30 mm mineral wool layer
with galvanised sheet steel outer

KC

VOLUME FLOW CONTROLLERS


Dimensions

45

45

Diameter (N)
[mm]

Length (L)
[mm]

80
100
125
160
200
250
315
355
400

300
300
300
300
300
400
400
400
400

Quick selection Table

400

Q=1000

355

Q=900

Q=2800

Q=800

315
250

Q=2400
Q=1560

Q=560

200

Q=250

160

Q=900
Q=500

Q=180

125

Q=100

100

Q=280

Q=70

6000

5000

4000

3000

2000

500
600
700
800
900
1000

400

Q=145

50
60
70
80
90
100

40

30

20

Q=45

300

80

Q=220

200

N [mm]

Q=4000

Q (m3/h)

Order codes

Constant volume flow


controller, circular

KC/KC-I - N - Q
Required flow rate (m3/h)
Constant volume flow
controller, circular - insulated

10

Dimension

KC

VOLUME FLOW CONTROLLERS


Flow rate range in relation to duct cross section
*Flow rate calibration possible at air velocities from 3 to 10 m/s

5000

1300

= 1,2 kg/ m3

4000

1000
90 0
80 0
70 0
60 0
50 0

3000
2000

40 0

10 m/s

30 0

1000
90 0
800
70 0
600
50 0

20 0
150

40 0

10 0
90
80
70
60
50

3 m/s
30 0
20 0
150

Q [I/s]

Q [m/H]

1500

40
30

100
90
80
70
60
50

20

40

10
9
8

400

315

250

200

160

125

80

100

30

Minimum static pressure difference at the controller.


250
225
200

Dp [Pa]

175
150
125
100
75
50
25
0
0

KC

10

11

12

v (m/s)

Legend:
Q (m3/h or l/s)
v (m/s)
A (m2)
Dp (Pa)

flow rate
air velocity
effective outlet area
static pressure difference

11

VOLUME FLOW CONTROLLERS


Flow noise levels [dB(A)]
If air is blown into a room, additional attenuation occurs as a result of the duct outlet attenuation and room attenuation
and because of that, a reduction in the sound level.
The room and outlet attenuation can be calculated according to VDI 2081. As a rough estimate, approx. 8 dB can be
deducted.
To maintain a required noise pressure level, it may be necessary to install a suitable sound attenuator between the
volume flow controller and the room, or to insulate the duct.
The flow noise is heavily dependent on local conditions, like dimensions of the duct (height, width, length) behind the
sound attenuator and the insulation of the duct. The specified data can provide only a reference values. The noise
pressure level can rise if there is an additional noise source such as a ventilator or unfavorable air flow conditions. If
this additional noise pressure level is smaller than approx. 10 dB of the noise pressure level of the volume flow
controller, it will have no increasing effect on the addition of both.

Constant volume flow controller, circular - KC


Dp = 100 Pa

12

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

40

48

47

46

44

42

40

38

35

48

56

55

54

52

50

48

46

43

56

62

61

60

58

56

54

52

49

62

82

53

53

51

50

48

47

44

42

54

60

60

59

58

57

54

52

50

62

67

66

65

64

62

61

58

56

68

125

56

55

55

53

52

50

48

46

57

64

63

62

61

60

58

56

54

65

70

69

68

67

66

64

62

60

71

70

51

49

48

46

44

42

39

36

49

58

57

56

54

52

50

47

44

57

65

63

62

60

58

56

53

50

63

135

55

55

53

52

50

48

46

43

58

63

63

61

60

58

56

54

51

64

69

69

67

66

64

62

60

57

70

200

58

58

57

55

54

52

50

47

59

66

65

65

63

62

60

58

55

67

72

72

71

69

68

66

64

61

73

100

51

49

48

46

44

42

39

36

49

59

57

56

54

52

50

47

44

57

67

63

62

60

58

56

53

50

63

190

55

55

53

52

50

48

46

43

56

63

63

61

60

58

56

54

51

64

69

69

67

66

64

62

60

57

69

280

58

58

57

55

54

52

50

47

59

66

65

65

63

62

60

58

55

67

72

72

71

69

68

66

64

61

70

180

52

51

49

47

45

43

40

37

50

60

59

57

55

53

51

48

45

58

66

65

63

61

59

57

54

51

64

340

57

56

55

53

51

49

47

44

57

68

64

63

61

59

57

55

52

65

71

70

69

67

65

63

61

58

71

500

60

59

58

56

55

53

51

48

60

68

67

66

64

63

61

57

56

68

74

73

72

70

69

67

64

62

74

250

53

51

50

48

46

43

40

37

51

61

59

58

56

54

51

48

45

59

67

65

64

62

60

57

54

51

67

575

58

57

55

54

52

50

47

46

57

66

65

63

62

60

58

55

52

65

72

71

69

68

65

64

61

58

71

900

60

60

59

57

55

53

51

58

61

68

68

67

65

63

61

59

56

69

74

74

73

71

69

67

65

62

75

500

53

52

50

48

46

44

41

38

52

61

60

58

56

54

52

49

46

60

67

66

64

62

60

58

55

52

66

1000

59

57

56

55

53

50

48

45

58

66

65

64

62

61

58

56

53

66

73

71

70

68

67

64

62

59

72

1500

61

61

59

58

56

54

52

59

62

69

68

67

66

64

62

60

57

70

75

74

73

72

70

68

66

63

76

600

55

53

52

49

47

45

42

38

53

63

61

59

57

55

52

50

46

61

69

67

66

63

61

58

56

52

67

1400

60

59

57

56

54

51

49

46

59

68

67

65

64

62

59

57

54

67

74

73

71

70

68

65

63

60

73

2200

63

62

61

59

57

55

53

50

63

71

70

69

67

65

63

61

58

71

77

76

75

73

71

69

67

64

77

1000

55

54

52

50

48

45

42

39

53

63

62

60

58

56

53

50

47

61

69

68

66

64

62

59

56

53

67

2200

61

59

58

56

54

52

49

46

60

69

67

66

64

62

60

57

54

68

75

72

72

70

68

66

63

60

74

3800

65

63

61

60

58

56

53

50

63

72

71

69

68

66

64

61

58

71

78

77

75

74

72

70

67

64

77

8000 Hz

400

4000 Hz

315

2000 Hz

250

1000 Hz

200

500 Hz

160

250 Hz

125

Sound power Lw [dB(A)]

125 Hz

100

Dp = 500 Pa

Sound power Lw [dB(A)]

63 Hz

80

Dp = 250 Pa

Sound power Lw [dB(A)]

Q [m /h]

[mm]

Model

KC

VOLUME FLOW CONTROLLERS

Constant volume flow controller, circular insulated - KC-I


Dp = 100 Pa
Sound power Lw [dB(A)]
63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

TOT Hz

37

36

34

32

30

28

25

38

46

45

44

42

40

38

36

33

46

52

51

50

48

46

44

42

39

52

43

43

41

40

38

37

34

32

44

50

50

49

48

47

44

42

40

52

57

56

55

54

52

51

48

46

58

125

46

45

45

43

42

40

38

36

47

54

53

52

51

50

48

46

44

55

60

59

58

57

56

54

52

50

61

70

41

39

38

36

34

32

29

26

39

48

47

46

44

42

40

37

34

47

55

53

52

50

48

46

43

40

53

135

45

45

43

42

40

38

36

33

48

53

53

51

50

48

46

44

41

54

59

59

57

56

54

52

50

47

60

200

48

48

47

45

44

42

40

37

49

56

55

55

53

52

50

48

45

57

62

62

61

59

58

56

54

51

63

100

41

39

38

36

34

32

29

26

39

49

47

46

44

42

40

37

34

47

57

53

52

50

48

46

43

40

53

190

45

45

43

42

40

38

36

33

46

53

53

51

50

48

46

44

41

54

59

59

57

56

54

52

50

47

59

280

48

48

47

45

44

42

40

37

49

56

55

55

53

52

50

48

45

57

62

62

61

59

58

56

54

51

60

180

42

41

39

37

35

33

30

27

40

50

49

47

45

43

41

38

35

48

56

55

53

51

49

47

44

41

54

340

47

46

45

43

41

39

37

34

47

58

54

53

51

49

47

45

42

55

61

60

59

57

55

53

51

48

61

500

50

49

48

46

45

43

41

38

50

58

57

56

54

53

51

47

46

58

64

63

62

60

59

57

54

52

64

250

43

41

40

38

36

33

30

27

41

51

49

48

46

44

41

38

35

49

57

55

54

52

50

47

44

41

57

575

48

47

45

44

42

40

37

36

47

56

55

53

52

50

48

45

42

55

62

61

59

58

55

54

51

48

61

900

50

50

49

47

45

43

41

48

51

58

58

57

55

53

51

49

46

59

64

64

63

61

59

57

55

52

65

500

43

42

40

38

36

34

31

28

42

51

50

48

46

44

42

39

36

50

57

56

54

52

50

48

45

42

56

1000

49

47

46

45

43

40

38

35

48

56

55

54

52

51

48

46

43

56

63

61

60

58

57

54

52

49

62

1500

51

51

49

48

46

44

42

49

52

59

58

57

56

54

52

50

47

60

65

64

63

62

60

58

56

53

66

600

45

43

42

39

37

35

32

28

43

53

51

49

47

45

42

40

36

51

59

57

56

53

51

48

46

42

57

1400

50

49

47

46

44

41

39

36

49

58

57

55

54

52

49

47

44

57

64

63

61

60

58

55

53

50

63

2200

53

52

51

49

47

45

43

40

53

61

60

59

57

55

53

51

48

61

67

66

65

63

61

59

57

54

67

1000

45

44

42

40

38

35

32

29

43

53

52

50

48

46

43

40

37

51

59

58

56

54

52

49

46

43

57

2200

51

49

48

46

44

42

39

36

50

59

57

56

54

52

50

47

44

58

65

62

62

60

58

56

53

50

64

3800

55

53

51

50

48

46

43

40

53

62

61

59

58

56

54

51

48

61

68

67

65

64

62

60

57

54

67

[mm]

38

82

100

125

160

200

315

400

Dp = 500 Pa
Sound power Lw [dB(A)]

40
80

250

Dp = 250 Pa
Sound power Lw [dB(A)]

Q [m3/h]

Model

Sound power level in dB(A)/octave in relation to reference sound power (10-12 W)

KC

13

VOLUME FLOW CONTROLLERS


Installation
Curcular controllers are connected to a duct like a standard ventilation duct fitting.
The controller can be installed in horizontal, vertical or inclined mounted duct in a manner that the rotational axis of the
dampe blade is always in a horizontal position. Also it is necessary to pay attention to the correct mounting direction
shown with the air flow direction arrow on the controller.
Required length of the straight duct section is L3d before and L1,5d after the the controller. If this lengths are
smaller, deviations of the set flow rate can occure and the stated accuracy of the flow rate may not be achived;
therefore, such installations are not recommended.
Controllers are maintenance free.

AIR FLOW

min. 150

Lmin = 3 x N

14

INCORRECT
INSTALLATION

CORRECT
INSTALLATION

KC

VOLUME FLOW CONTROLLERS


VARIABLE VOLUME FLOW CONTROLLERS RECTANGULAR VP
Description
Variable volume flow controllers are used for pressure-independent volume flow regulation in variable or constant
capacity ventilation and air conditioning systems. Controllers can be installed in a supply and extract air systems.
The controller consists of a casing, damper blades, flow probes and VAV actuator.
Depending on project requirements, variable volume flow controllers can be controlled by the room temperature
sensor, air quality sensor or pressure sensor.
The controller compares the actual value signal with the setpoint value and sends an output signal to the electric
actuator which adjusts the damper blades to maintain the set point value.

Technical data
Construction
Casing
CASING - made of galvanised sheet steel
Flow Probes
DAMPER BLADES - opposite moving, made of
galvanised sheet steel, with sealing. Thermal insulated
blades in insulated version

Damper Blades

FLOW PROBES - sending the actual value signal to the


controller which compares it with the setpoint value and
sends an output signal to the electric actuator which
adjusts the damper blades to maintain the set point
value
ACTUATOR / CONTROLLER - Electric actuator with
controll components

Actuator
/ Controller
Blade rotation mechanism
Insulated version:
Insulation Cladding

Insulated version: Controllers are available with 30 mm


acoustic and thermal insulation.

INSULATION CLADDING - 30 mm mineral wool layer


with galvanised sheet steel outer cover

VP

15

VOLUME FLOW CONTROLLERS


Dimensions

H
H+60

30

60

L
30

B
B+60

H
B
200
300
400
500
600
700
800
900
1000

400

100

200

300

400

500

600

700

800

900

1000

P
P
P
O
O
O
O
O
O

P
P
P
P
P
P
P
O
O

P
P
P
P
P
P
P
P
P

P
P
P
P
P
P
P
P
P

P
P
P
P
P
P
P
P
P

P
P
P
P
P
P
P
P
P

P
P
P
P
P
P
P
P
P

P
P
P
P
P
P
P
P
P

O
P
P
P
P
P
P
P
P

O
P
P
P
P
P
P
P
P

B [mm] - from 200 to 1000 mm in steps of 100 mm


H [mm] - from 100 to 1000 mm in steps of 100 mm

Effective Outlet Area [m]


H /B

200

300

400

500

600

700

800

900

1000

100

0,017

0,0255

0,034

200

0,034

0,051

0,068

0,085

0,102

0,119

0,136

O
O

300

0,051

0,0765

0,102

0,1275

0,153

0,1785

0,204

0,2295

O
O
O

400

0,068

0,102

0,136

0,17

0,204

0,238

0,272

0,306

0,34

500

0,085

0,1275

0,17

0,2125

0,255

0,2975

0,34

0,3825

0,425

600

0,102

0,153

0,204

0,255

0,306

0,357

0,408

0,459

0,51

700

O
O
O
O

0,1785

0,238

0,2975

0,357

0,4165

0,476

0,5355

0,595

800
900
1000

0,204

0,272

0,34

0,408

0,476

0,544

0,612

0,68

0,2295

0,306

0,3825

0,459

0,5355

0,612

0,6885

0,765

0,34

0,425

0,51

0,595

0,68

0,765

0,85

Order codes
Variable volume flow
controller, rectangular

VP/VP-I - BH - Q
Variable volume
flow controller,
rectangular - insulated

16

Dimensions

Required minimum and maximum


flow rate [m/h] (if there is no
specification from the customer,
controller will be set to the
standard values)

VP

VOLUME FLOW CONTROLLERS


Flow noise levels [dB(A)]
Dp = 100 Pa

200

300

400

500

600

300

400

500

600

VP

Dp = 500 Pa

Dp = 1000 Pa

500 Hz

1000 Hz

2000 Hz

4000 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

Sound power Lw [dB(A)]

250 Hz

Sound power Lw [dB(A)]

125 Hz

Sound power Lw [dB(A)]

Q [m3/h]

300

Dp = 250 Pa

Sound power Lw [dB(A)]


v [m/s]

200

H [mm]

B [mm]

Type

183,6

46

45

44

43

40

36

52

52

51

51

49

47

58

58

57

57

55

53

65

66

65

65

64

61

367,2

52

51

50

49

47

42

57

57

56

55

53

51

62

63

62

61

60

58

68

69

68

68

68

66

550,8

57

57

57

55

53

49

63

62

62

60

59

57

63

64

65

64

64

62

70

72

71

71

70

69

12

734,4

59

58

58

56

54

51

66

65

65

63

62

60

69

69

68

68

67

65

72

74

73

74

73

72

280,8

47

46

45

44

41

37

53

53

52

52

50

48

59

59

58

58

56

54

66

67

66

66

65

62

561,6

53

52

51

50

48

43

58

58

57

56

54

52

63

64

63

62

61

59

69

70

69

69

69

67

842,4

58

58

58

56

54

50

64

63

63

61

60

58

64

65

66

65

65

63

71

73

72

72

71

70

12

1123

60

59

59

57

55

52

67

66

66

64

63

61

70

70

69

69

68

66

73

75

74

75

74

73

367,2

48

47

46

45

42

38

54

54

53

53

51

49

60

60

59

59

57

55

67

68

67

67

66

63

734,4

54

53

52

51

49

44

59

59

58

57

55

53

64

65

64

63

62

60

70

71

70

70

70

68

100

100

200
9

1102

59

59

59

57

55

51

65

64

64

62

61

59

65

66

67

66

66

64

72

74

73

73

72

71

12

1469

61

60

60

58

56

53

68

67

67

65

64

62

71

71

70

70

69

67

74

76

75

76

75

74

550,8

49

48

47

46

43

39

55

55

54

54

52

50

61

61

60

60

58

56

68

69

68

68

67

64

1102

55

54

53

52

50

45

60

60

59

58

56

54

65

66

65

64

63

61

71

72

71

71

71

69

200
9

1652

60

60

60

58

56

52

66

65

65

63

62

60

66

67

68

67

67

65

73

75

74

74

73

72

12

2203

62

61

61

59

57

54

69

68

68

66

65

63

72

72

71

71

70

68

75

77

76

77

76

75

734,4

50

49

48

47

44

40

56

56

55

55

53

51

62

62

61

61

59

57

69

70

69

69

68

65

1469

56

55

54

53

51

46

61

61

60

59

57

55

66

67

66

65

64

62

72

73

72

72

72

70

2203

61

61

61

59

57

53

67

66

66

64

63

61

67

68

69

68

68

66

74

76

75

75

74

73

12

2938

63

62

62

60

58

55

70

69

69

67

66

64

73

73

72

72

71

69

76

78

77

78

77

76

918

51

50

49

48

45

41

57

57

56

56

54

52

63

63

62

62

60

58

70

71

70

70

69

66

1836

57

56

55

54

52

47

62

62

61

60

58

56

67

68

67

66

65

63

73

74

73

73

73

71

200

200
9

2754

62

62

62

60

58

54

68

67

67

65

64

62

68

69

70

69

69

67

75

77

76

76

75

74

12

3672

64

63

63

61

59

56

71

70

70

68

67

65

74

74

73

73

72

70

77

79

78

79

78

77

1102

52

51

50

49

46

42

58

58

57

57

55

53

64

64

63

63

61

59

71

72

71

71

70

67

2203

58

57

56

55

53

48

63

63

62

61

59

57

68

69

68

67

66

64

74

75

74

74

74

72

200
9

3305

63

63

63

61

59

55

69

68

68

66

65

63

69

70

71

70

70

68

76

78

77

77

76

75

12

4406

65

64

64

62

60

57

72

71

71

69

68

66

75

75

74

74

73

71

78

80

79

80

79

78

831,6

51

50

49

48

45

41

57

57

56

56

54

52

63

63

62

62

60

58

70

71

70

70

69

66

1663

57

56

55

54

52

47

62

62

61

60

58

56

67

68

67

66

65

63

73

74

73

73

73

71

300
9

2495

62

62

62

60

58

54

68

67

67

65

64

62

68

69

70

69

69

67

75

77

76

76

75

74

12

3326

64

63

63

61

59

56

71

70

70

68

67

65

74

74

73

73

72

70

77

79

78

79

78

77

1102

52

51

50

49

46

42

58

58

57

57

55

53

64

64

63

63

61

59

71

72

71

71

70

67

2203

58

57

56

55

53

48

63

63

62

61

59

57

68

69

68

67

66

64

74

75

74

74

74

72

300
9

3305

63

63

63

61

59

55

69

68

68

66

65

63

69

70

71

70

70

68

76

78

77

77

76

75

12

4406

65

64

64

62

60

57

72

71

71

69

68

66

75

75

74

74

73

71

78

80

79

80

79

78

1382

53

52

51

50

47

43

59

59

58

58

56

54

65

65

64

64

62

60

72

73

72

72

71

68

2765

59

58

57

56

54

49

64

64

63

62

60

58

69

70

69

68

67

65

75

76

75

75

75

73

300
9

4147

64

64

64

62

60

56

70

69

69

67

66

64

70

71

72

71

71

69

77

79

78

78

77

76

12

5530

66

65

65

63

61

58

73

72

72

70

69

67

76

76

75

75

74

72

79

81

80

81

80

79

1652

54

53

52

51

48

44

60

60

59

59

57

55

66

66

65

65

63

61

73

74

73

73

72

69

3305

60

59

58

57

55

50

65

65

64

63

61

59

70

71

70

69

68

66

76

77

76

76

76

74

4957

65

65

65

63

61

57

71

70

70

68

67

65

71

72

73

72

72

70

78

80

79

79

78

77

12

6610

67

66

66

64

62

59

74

73

73

71

70

68

77

77

76

76

75

73

80

82

81

82

81

80

300

17

VOLUME FLOW CONTROLLERS


Actuator / Controller
Siemens GDB 181.1E/3
Wiring diagram:

1
(G)

7
(Y2)

(G0)
2

6
(Y1)

(
)
8
(YC)
Tool

(U)
9

Belimo LMV-D3-MP

The input signal

The output signal

Conventional controll

Belimo MP-Bus controll

Technical data
Nominal torqueTorque: 5 Nm /10Nm
Nominal / maximum rotation angle: 90/95 2
Operating voltage / frequency: AC 24V 20% / 50/60 Hz
Degree of protection acc. to EN 60529: IP 54
Safety class acc. to EN 60730: III
Operation temperature: 0 - 50C
Storage temperature: -25 70C

18

VP

VOLUME FLOW CONTROLLERS


Installation
Rectangular controllers are flanged on both sides for connection with the standard 30 mm ventilation duct flange.
Recomended length of the straight duct section before the controller is Lmin2B at the bends and LminB at the
take-offs.

AIR FLOW

AIR FLOW

HB

HB

min. 2B
min. B

VP

19

VOLUME FLOW CONTROLLERS


VARIABLE VOLUME FLOW CONTROLLERS CIRCULAR VC
Technical data
Construction
Actuator / Controller

Casing

CASING - made of galvanised sheet steel


ACTUATOR / CONTROLLER - Electric actuator with
controll components
DAMPER BLADE - made of galvanised sheet steel

Damper
Blade

FLOW PROBES - sending the actual value signal to the


controller which compares it with the setpoint value and
sends an output signal to the electric actuator which
adjusts the damper blades to maintain the set point
value

Flow Probes
Insulated version: Controllers are available with 30 mm
acoustic and thermal insulation.

Insulated version:
Insulation Cladding

INSULATION CLADDING - 30 mm mineral wool layer


with galvanised sheet steel outer cover

Dimensions
45

20

Diameter (N)
[mm]

Length (L)
[mm]

100
125
160
200
250
315
400

550
550
550
550
550
715
715

VC

VOLUME FLOW CONTROLLERS


Quick selection Table

400

250
160
125
10 15

m/s

6000
7000
8000
9000
10000

5000

4000

500
600
700
800
900
1000

400

300

200

50
60
70
80
90
100

Vk

3000

100

2000

N [mm]

315

Q (m3/h)

Order codes

Variable volume flow


controller, circular

VC/VC-I - N - Q
Variable volume flow
controller, circular - insulated

VC

Dimensions

Required minimum and maximum


flow rate [m/h] (if there is no
specification from the customer,
controller will be set to the
standard values)

21

VOLUME FLOW CONTROLLERS


Flow noise levels [dB(A)]

22

VC

VOLUME FLOW CONTROLLERS


Installation
Curcular controllers are connected to a duct like a standard ventilation duct fitting.

Recomended length of the straight duct section before the controller:

min. 2

min. 2

AIR FLOW

min. 2

VC

23

DAMPER CONTROLLERS
MULTI-BLADE REGULATION DAMPERS GALVANIZED
Description
Rectangular multi-blade regulation damper with opposite moving blades, used to control or shut of f the air flow in
ventilation and air conditioning systems. Made of galvanised sheet steel, unit length 200 mm.
Manual control
Casing
CASING - made of galvanised sheet steel

Damper blades

DAMPER BLADES - opposite moving, made of


galvanised sheet steel, with sealing. Thermal
insulated blades in insulated version
CONTROL LEVER - for manual adjustment
according to the scale
BLADE ROTATION MECHANISM - consists of a
brass control shaft and synchronized nylon gear
wheels with bearings
Control lever
Blade rotation mechanism
Actuator control
Casing
ACTUATOR - electric actuator, non-spring return /
spring return (safety function - in case of a power
failure the actuator closes the damper), open-close
or modulating control, 24V or 230V power supply

Damper blades

Actuator

Blade rotation mechanism


Actuator control, insulated version
Insulation Cladding

24

INSULATION CLADDING - 30 mm mineral wool


layer with galvanised sheet steel outer cover

RZPP

DAMPER CONTROLLERS
Dimensions
Manual control

H+60

30

15

30

200

B+60
min
max

B
200
2100

H
100
1500

NOTE: It is possible to produce a damper with the width (B) over 2100 mm, in that case the damper is split in three air
shaft openings. When the width (B) is over 1400 mm the damper is split in two air shaft openings.
Width (B) in steps of 50 mm and height (H) in steps of 100 mm.
Non-standard dimensions are available upon customer's request.

Actuator control, insulated version

H+60

30

60

30

200

B+60

RZPP

25

DAMPER CONTROLLERS
MULTI-BLADE REGULATION DAMPERS ALUMINIUM
Description
Rectangular multi-blade regulation damper with opposite moving blades, used to control or
shut off the air flow in ventilation and air conditioning systems. Made of extruded aluminium profiles, unit length 125
mm.
Manual control
CASING - made of galvanised sheet steel

Casing

DAMPER BLADES - opposite moving, made of extruded


aluminium profiles, with sealing gaskets
Blade rotation
mechanism
Damper
blades

CONTROL HANDLE - for manual adjustment of the


damper blades
BLADE ROTATION MECHANISM - consists of a brass
control shaft and synchronized nylon gear wheels with
bearings

Control handle

Actuator control
Casing
ACTUATOR - electric actuator, non-spring return / spring
return (safety function - in case of a power failure the
actuator closes the damper), open-close or modulating
control, 24V or 230V power supply

Damper
blades

Blade rotation
mechanism
Actuator

26

RZPP

DAMPER CONTROLLERS
Dimensions
Actuator control

Manual control

50

B
B+70

H+50

25

95

125

35

min
max

125

B
200
2100

H
210
1510

NOTE: It is possible to produce a damper with the width (B) over 2100 mm, in that case the damper is split in three air
shaft openings. When the width (B) is over 1400 mm the damper is split in two air shaft openings.
Width (B) and height (H) in steps of 100 mm.
Non-standard dimensions are available upon customer's request.

Order codes

Multi-blade regulation
damper, rectangular,
opposed

Dimensions

RZPP-material - BH - control
Zn - galvanised sheet steel
Al - aluminium

RZPP

R - manual
M - actuator

27

DAMPER CONTROLLERS
Technical data
Effective Outlet Area [m] for galvanized and aluminium multi-blade regulation dampers
H/B

200

300

400

500

600

700

800

900

1000

100

0,017

0,0255

0,034

0,0425

0,051

0,0595

0,068

0,0765

0,085

200

0,034

0,051

0,068

0,085

0,102

0,119

0,136

0,153

0,17

300

0,051

0,0765

0,102

0,1275

0,153

0,1785

0,204

0,2295

0,255

400

0,068

0,102

0,136

0,17

0,204

0,238

0,272

0,306

0,34

500

0,085

0,1275

0,17

0,2125

0,255

0,2975

0,34

0,3825

0,425

600

0,102

0,153

0,204

0,255

0,306

0,357

0,408

0,459

0,51

700

0,119

0,1785

0,238

0,2975

0,357

0,4165

0,476

0,5355

0,595

800

0,136

0,204

0,272

0,34

0,408

0,476

0,544

0,612

0,68

900

0,153

0,2295

0,306

0,3825

0,459

0,5355

0,612

0,6885

0,765

1000

0,17

0,255

0,34

0,425

0,51

0,595

0,68

0,765

0,85

type A

type B

Dpt(Pa)

Dpt(Pa)

HB

HB

CORRECTION FACTOR FOR DPt type B: Kp


a
Kp

0
10
20 30 40 50 60
2,7 1,33 1,15 1,25 1,16 1,16 1,2

DPt (type B) = Kp x DPt (type A)

28

RZPP

DAMPER CONTROLLERS

Face velocity, pressure loss and sound power level: type A

A face (m)

V face (m/s)
1

4
3.5
3
2.5
2

1.5

1.5

1
0.8

(m

3/h

0.3
0.2
0.15
0.1
0.08
40
30

7 8 9 10 12

0,02
2000
1500
1000
700
500
400
300

50

50

40
30

60

20
10

200
150

80 0

100
80
60
40
30
20
15

65
)
0
6 ( A)
55 ( dB
=
0
5
1
a
w
45 L

10
5
4
3
2
1

15 17 20

20
0

0,03

DPt (Pa)

15
12 0000
5
11 0
95 000 00
80 000 0
70 000
60 000
48 000
40 000
33 000
28 000
24 000
0
17 00
00
0
14
12 000
0
10 00
0
80 00
00
65
55 00
0
45 0
0
35 0
30 00
25 00
0
18 0
16 00
0
13 0
11 00
0
90 0
0
70
0

0.6
0.5
0.4

0.06
0.05
0.04

70

75

40

1.5

7 8 9 10 12

15 17 20

V face (m/s)

RZPP

29

DAMPER CONTROLLERS
SINGLE-BLADE REGULATION DAMPERS RECTANGULAR
Description
Single-blade regulation dampers are mainly used for regulation and balancing of ventilation and air conditioning
systems. Blade angle adjustment 090. Made of galvanised sheet steel with working temperature range from -20C
up to +90C for manual and +50C for actuator controlled version. Easy installation and rigid construction.
Manual control

Casing
CASING - made of galvanised sheet steel
DAMPER BLADE - made of galvanised sheet steel
CONTROL HANDLE - for manual adjustment of the
damper blade

Control handle
Damper blade
Casing

Actuator control

ACTUATOR - electric actuator, 24V or 230V power


supply

Actuator
Damper blade

Dimensions

60

20

Width (B) and height (H) in steps of 50 mm.


Non-standard dimensions are available upon customer's
request.

30

L=H+50

min
max

B
100
500

H
100
500

RZ-P

DAMPER CONTROLLERS
SINGLE-BLADE REGULATION DAMPERS CIRCULAR
Manual control
Casing

Control handle

Damper blade

Casing

Actuator control

Damper blade
Actuator

Dimensions

45

RZ-C

80

Type

Diameter (N)
[mm]

Lenght (L)
[mm]

RZC-100
RZC-125
RZC-150
RZC-160
RZC-200
RZC-250
RZC-315
RZC-355
RZC-400
RZC-450
RZC-500

100
125
150
160
200
250
315
355
400
450
500

250
250
250
250
250
350
350
350
600
600
600

31

DAMPER CONTROLLERS
MULTI-BLADE REGULATION DAMPERS WITH ROUND CONNECTION
Description
Used to control or shut off the air flow in round ducts with diameters over 500 mm. It consists of a rectangular multiblade regulation damper with opposite moving blades and specially constructed connection for the round duct.
Actuator control

Manual control
Regulation Damper

Regulation Damper

Closed end with connection for round duct

Closed end with connection for round duct

Dimensions

45

N
N+65

32,5

80

203
363

Tip

Promjer (N)
[mm]

RZC-560
RZC-600
RZC-630
RZC-650
RZC-710
RZC-800
RZC-900
RZC-1000
RZC-1250
RZC-1400
RZC-1600

560
600
630
650
710
800
900
1000
1250
1400
1600

Order codes

Regulation
damper

P - rectangular
C - circular

BH - rectangular
N - circular

RZ - P/C-material - dimension - control


Zn - galvanised sheet steel
Al - aluminium
Inox stainless steel

32

R - manual
M - actuator

RZ

Gornjostupnika 126
10255 Zagreb, Croatia
Tel.: +385 1 6589 244
Fax: +385 1 6589 243
e-mail: info@klima-kontakt.hr
www.klima-kontakt.hr