SIRIUS 3RW30 / 3RW40 168 Manual, 01/2010, 535 1995-02 DS01 15.2 Control by pushbutton 15.2.1 Control of the 3RW30 by pushbutton Figure WARNING 15-2 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (2) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] (1)(2) (1) L -S4 T3 L3 T2 L2 T1 L1 -Q1 -Q11 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> N 1 A2 A1 -Q11 14 13 -S1 -F1 (3) ON Motor stop Motor start S t a r t (3) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Typical circuit diagrams 15.2 Control by pushbutton SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 169 15.2.2 Control of the 3RW40 by pushbutton Figure 15-3 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit Figure 15-4 Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (2) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. N L (1) -S4 98 1 A2 A1 -Q11 24 23 14 13 96 95 -Q11 -S2 -S1 -F1 (1)(2) T3 L3 T2 L2 T1 L1 -Q1 3RW40 -Q11 M W1 V1 U1 -M1 l>> l>> l>> Motor stop S t a r t >1.5 s Motor start O N F A l L U R E O V E R L O A D
/ B Y P A S S E D RESET L (1) N -S4 98 3 2 E2 E1 1 A2 A1 -Q11 24 23 14 13 96 95 -Q11 -S2 -S1 -F1 Motor stop S t a r t Motor start O N 0.2 to 4 s 3 R U 1 9 0 0 - 2 A
( r e m o t e
R E S E T ) F A l L U R E O V E R L O A D
/ RESET B Y P A S S E D Typical circuit diagrams 15.3 Control by switch SIRIUS 3RW30 / 3RW40 170 Manual, 01/2010, 535 1995-02 DS01 15.3 Control by switch 15.3.1 Control of the 3RW30 by switch Figure WARNING 15-5 Wiring of the control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] S t a r t O N (2) (1)(3) (1) -H1 T3 L3 T2 L2 T1 L1 -Q1 -Q11 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> N L 1 A2 A1 -Q11 14 13 -S1 -F1 (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Typical circuit diagrams 15.3 Control by switch SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 171 15.3.2 Control of the 3RW40 by switch Figure 15-6 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit Figure 15-7 Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (1)(3) T3 L3 T2 L2 T1 L1 -Q1 3RW40 -Q11 M W1 V1 U1 -M1 l>> l>> l>> F a u l t S t a r t >1.5 s RESET O V E R L O A D
/ F A l L U R E B Y P A S S E D O N
/
R U N N (1) L (2) -H2 -H3 98 1 A2 A1 -Q11 -H1 24 23 14 13 96 95 -Q11 -S2 -S1 -F1 N (2) (1) L -H2 -H3 98 3 2 E2 E1 1 A2 A1 -Q11 -H1 24 23 14 13 96 95 -Q11 -S2 -S1 -F1 O V E R L O A D
/ F A l L U R E F a u l t S t a r t B Y P A S S E D O N
/
R U N 0.2 to 4 s 3 R U 1 9 0 0 - 2 A
( r e m o t e
R E S E T ) RESET WARNING Typical circuit diagrams 15.4 Control in automatic mode SIRIUS 3RW30 / 3RW40 172 Manual, 01/2010, 535 1995-02 DS01 (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. 15.4 Control in automatic mode 15.4.1 Control of the 3RW30 in automatic mode Figure 15-8 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. S t a r t ON / OFF ON (1)(3) (1) -H1 T3 L3 T2 L2 T1 L1 -Q1 -Q11 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> 1 A2 A1 -Q11 14 13 -S1 -F1 L N (2) WARNING Typical circuit diagrams 15.4 Control in automatic mode SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 173 (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] 15.4.2 Control of the 3RW40 in automatic mode Figure 15-9 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. B Y P A S S E D O V E R L O A D
/
F A l L U R E RESET >1.5 s ON / OFF S t a r t F a u l t O N
/
R U N -F1 L -Q11 95 96 13 14 23 24 -H1 -Q11 A1 A2 1 98 -H3 -H2 (2)(4) (1) N (1)(3) T3 L3 T2 L2 T1 L1 -Q1 3RW40 -Q11 M W1 V1 U1 -M1 l>> l>> l>> -S1 Typical circuit diagrams 15.4 Control in automatic mode SIRIUS 3RW30 / 3RW40 174 Manual, 01/2010, 535 1995-02 DS01 Figure WARNING 15-10 Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] F a u l t S t a r t O N
/
R U N 0.2 to 4 s RESET 3 R U 1 9 0 0 - 2 A
( r e m o t e
R E S E T ) ON / OFF O V E R L O A D
/ F A l L U R E B Y P A S S E D N (1) (2)(4) -H2 -H3 98 3 2 E2 E1 1 A2 A1 -Q11 -H1 24 23 14 13 96 95 -Q11 -S2 -S1 -F1 L (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. Note (4) Idle time until restart. Owing to the intrinsic protection (3RW), an idle time of at least five minutes must be allowed prior to restarting if the device is switched on and off by means of the control voltage under field conditions. > 5 min U s ON OFF t Typical circuit diagrams 15.5 Control by PLC SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 175 For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. 15.5 Control by PLC 15.5.1 Control of the 3RW30 with 24 V DC by PLC Figure WARNING 15-11 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] 24 V DC lnput PLC Output PLC O N S t a r t O V E R L O A D (2) (1)(3) (1) L M 96 95 98 14 13 -Q11 T3 L3 T2 L2 T1 L1 -Q1 -Q1 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> 1 A2 A1 -Q11 -F1 (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Typical circuit diagrams 15.5 Control by PLC SIRIUS 3RW30 / 3RW40 176 Manual, 01/2010, 535 1995-02 DS01 15.5.2 Control of the 3RW40 by PLC Figure 15-12 Wiring of the 3RW40 2 to 3RW40 4 control circuit (with 24 V control voltage) and the 3RW40 2 to 3RW40 7 main circuit Figure 15-13 Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . O V E R L O A D
/
F A l L U R E B Y P A S S E D O N
/
R U N >1.5 s RESET PLC lnput S t a r t Coupling relay control for RESET >1.5 sec +24 V DC +24 V DC PLC Output N (2) M (1) L -K1 98 1 A2 A1 -Q11 24 23 14 13 96 95 -Q11 -K1 -F1 (1)(3) -Q21 T3 L3 T2 L2 T1 L1 -Q1 -Q11 M W1 V1 U1 -M1 l>> l>> l>> +24 V DC O V E R L O A D
/
F A l L U R E S t a r t O N
/
R U N 0.2 to 4 s B Y P A S S E D RESET 3 R U 1 9 0 0 - 2 A
( r e m o t e
R E S E T ) PLC lnput PLC Output N (2) (1) M 98 E2 E1 A2 A1 -Q11 24 23 14 13 96 95 -Q11 -S2 -F1 L 3 2 1 WARNING Typical circuit diagrams 15.6 Control with an optional main / line contactor SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 177 (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. 15.6 Control with an optional main / line contactor 15.6.1 Control of the 3RW30 with a main contactor Figure 15-14 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. S t a r t (2) (1)(3) (1) A2 A1 -Q21 T3 L3 T2 L2 T1 L1 -Q1 -Q11 3RW30 -Q11 -Q21 M U1 -M1 l>> l>> l>> L A2 A1 -Q11 ON 14 13 -S1 -F1 N W1 V1 1 WARNING Typical circuit diagrams 15.6 Control with an optional main / line contactor SIRIUS 3RW30 / 3RW40 178 Manual, 01/2010, 535 1995-02 DS01 (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] 15.6.2 Control of the 3RW40 with a main contactor Figure 15-15 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. O V E R L O A D
/
F A l L U R E F a u l t S t a r t B Y P A S S E D R U N >1.5 s RESET (1) L N (1)(3) (2) -Q21 -Q21 -H3 98 1 A2 A1 -Q11 -H1 24 23 14 13 96 95 -Q11 -S2 -S1 -F1 T3 L3 T2 L2 T1 L1 -Q1 3RW40 -Q11 M W1 V1 U1 -M1 l>> l>> l>> Typical circuit diagrams 15.6 Control with an optional main / line contactor SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 179 Figure WARNING 15-16 Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. O V E R L O A D
/
F A l L U R E F a u l t S t a r t B Y P A S S E D R U N 0.2 to 4 s RESET 3 R U 1 9 0 0 - 2 A
( r e m o t e
R E S E T ) -Q21 N (2) (1) -H3 98 3 2 E2 E1 L 1 A2 A1 -Q11 -H1 24 23 14 13 96 95 -Q11 -S2 -S1 -F1 Note If a soft stop is required, the function of output 13/14 must be reparameterized to "RUN" (refer to Commissioning the 3RW40 [Page 98]). (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. Typical circuit diagrams 15.7 Reversing circuit SIRIUS 3RW30 / 3RW40 180 Manual, 01/2010, 535 1995-02 DS01 15.7 Reversing circuit 15.7.1 3RW30 reversing circuit Figure WARNING 15-17 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] S t a r t M o t o r
C W
M o t o r
C C W
Motor CW Motor CCW Motor CCW Motor CW Motor stop O N (1) L -K1 A2 A1 -K1 -S2 -S1 -Q22 -Q21 U -Q21 -Q22 -S2 A2 A1 U -Q22 -Q21 -S1 A2 A1 (2) -Q11 -Q22 (1)(3) -Q21 T3 L3 T2 L2 T1 L1 -Q1 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> 1 A2 A1 -Q11 14 13 -K1 -F1 N -F1 -S4 -S4 U -S4 (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Typical circuit diagrams 15.7 Reversing circuit SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 181 15.7.2 3RW40 reversing circuit Figure 15-18 Wiring of the 3RW40 2 to 3RW40 5 control circuit and the 3RW40 2 to 3RW40 7 main circuit 1 M o t o r
C C W -S2 M o t o r
C W Motor CW Motor CW Motor CCW Motor CCW Motor Stop RESET >1.5 s O V E R L O A D
/
F A l L U R E O N
/
R U N B Y P A S S E D S t a r t F a u l t -F1 -K1 -Q11 A1 A2 -Q11 98 96 13 14 23 24 -H1 95 A1 A2 -S1 -Q21 -Q22 U A1 A2 -S2 -Q22 -Q21 U -Q21 -Q22 -S1 -S2 -K1 A1 A2 U -K1 -S4 (2) (1) L N l>> l>> l>> -M1 U1 V1 W1 M -Q11 3RW40 -Q1 T1 T2 T3 -Q21 -Q22 (1)(3) L1 L2 L3 -S4 -S4 Typical circuit diagrams 15.7 Reversing circuit SIRIUS 3RW30 / 3RW40 182 Manual, 01/2010, 535 1995-02 DS01 Figure WARNING NOTICE 15-19 Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. 3 R U 1 9 0 0 - 2 A
( r e m o t e
R E S E T ) Motor stop Motor CW Motor CW Motor CCW Motor CCW M o t o r
C W M o t o r
C C W O V E R L O A D
/
F A l L U R E O N
/
R U N B Y P A S S E D 0.2 to 4 s RESET F a u l t S t a r t -F1 -K1 -Q11 98 96 13 14 23 24 -H1 -Q11 A1 A2 1 E1 E2 2 3 95 A1 A2 -S1 -Q21 -Q22 U A1 A2 -S2 -Q22 -Q21 U -Q21 -Q22 -S1 -S2 -K1 A1 A2 U -K1 -S4 (2) (1) L N -S2 -S4 -S4 (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. Typical circuit diagrams 15.8 Control of a magnetic parking brake SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 183 15.8 Control of a magnetic parking brake 15.8.1 3RW30 motor with magnetic parking brake Figure WARNING 15-20 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] B r a k e OVERLOAD O V E R L O A DO N S t a r t N (1)(3) (1) L (2) 95 98 96 -H1 T3 L3 T2 L2 T1 L1 -Q1 -Q11 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> 1 A2 A1 -Q11 14 13 -S1 -F1 -Q11 (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Typical circuit diagrams 15.8 Control of a magnetic parking brake SIRIUS 3RW30 / 3RW40 184 Manual, 01/2010, 535 1995-02 DS01 15.8.2 3RW40 2 to 3RW40 4, control of a motor with a magnetic parking brake Figure WARNING NOTICE 15-21 Wiring of the 3RW40 2 to 3RW40 4 control / main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. -S2 B r a k e B Y P A S S E D O N O V E R L O A D S t a r t Fault RESET >1.5 s -F1 -S1 23 14 -Q11 A1 A2 1 -H1 96 98 95 (2) (1) L -Q11 24 13 N (1)(3) T3 L3 T2 L2 T1 L1 -Q1 3RW40 -Q11 M W1 V1 U1 -M1 l>> l>> l>> (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. Typical circuit diagrams 15.8 Control of a magnetic parking brake SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 185 15.8.3 3RW40 5 to 3RW40 7, control of a motor with a magnetic parking brake Figure WARNING NOTICE 15-22 Wiring of the 3RW40 5 to 3RW40 7 control / main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. Fault S t a r t 3 R U 1 9 0 0 - 2 A ( r e m o t e
R E S E T ) B r a k e B Y P A S S E D O N O V E R L O A D
/
F A l L U R E 0.2 to 4 s RESET -F1 -S2 -S1 23 14 -H1 96 98 95 (2) (1) L -Q11 24 13 -Q11 A1 A2 1 E1 E2 2 3 N (1)(3) T3 L3 T2 L2 T1 L1 -Q1 3RW40 -Q11 M W1 V1 U1 -M1 l>> l>> l>> (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. Typical circuit diagrams 15.9 Emergency stop SIRIUS 3RW30 / 3RW40 186 Manual, 01/2010, 535 1995-02 DS01 15.9 Emergency stop 15.9.1 3RW30 emergency stop and 3TK2823 safety relay Figure 15-23 Wiring of the emergency stop control circuit and the 3TK28 safety relay Figure 15-24 Wiring of the 3RW30 control and main circuits On Emergency stop (3TK reset) L+ (24VDC) Y21 Y22 A2 14 24 Y34 Y33 23 13 Y12 Y11 A1 3 T K 2 8 2 3 - 1 C B 3 0 -Q22 -Q21 -S3 -S4 M -Q22 -Q21 (2) 3RW30 Start / Motor Overload Emergency stop S t a r t O N O V E R L O A D
/
F A l L U R E Stop -Q22 -Q21 (1)(3) N (1) L (2) -H2 -Q22 -Q21 -Q22 -Q21 96 95 98 14 13 -Q11 -Q1 -H1 T3 L3 T2 L2 T1 L1 -Q1 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> 1 A2 A1 -Q11 -S1 -F1 WARNING Typical circuit diagrams 15.9 Emergency stop SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 187 (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] 15.9.2 3RW40 2 to 3RW40 4 emergency stop and 3TK2823 safety relay Figure 15-25 Wiring of the emergency stop control circuit and the 3TK28 safety relay (2) Automatic restart. Can result in death, serious injury, or property damage. - If the 3TK28 is reset Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Emergency stop L+ (24VDC) On (3TK RESET) -Q21 -Q22 M -S4 -S3 -Q21 -Q22 3 T K 2 8 2 3 - 1 C B 3 0 A1 Y11 Y12 13 23 Y33 Y34 24 14 A2 Y22 Y21 (2) Typical circuit diagrams 15.9 Emergency stop SIRIUS 3RW30 / 3RW40 188 Manual, 01/2010, 535 1995-02 DS01 Figure WARNING NOTICE 15-26 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. Emergency stop S t a r t Fault No control voltage 3RW40 -S2 -S1 Start / stop 3RW30 RESET >1.5 s O N
/
R U N O V E R L O A D
/
F A l L U R E B Y P A S S E D -F1 -Q11 A1 A2 1 l>> l>> l>> -M1 U1 V1 W1 M -Q11 3RW40 -Q1 L1 T1 L2 T2 L3 T3 -H1 -Q21 -Q22 -Q21 -Q22 -H2 (2) (1) L N (1)(3) -Q21 -Q22 -Q11 95 96 13 14 23 24 98 (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command (3TK or 3RW) if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. If the soft stop function is set (ramp-down time potentiometer set to >0 s) and the emergency stop circuit is tripped, a "Missing load voltage, phase failure / missing load" fault may be indicated on the soft starter. In this case, the soft starter must be reset according to the selected RESET MODE. Typical circuit diagrams 15.9 Emergency stop SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 189 15.9.3 3RW40 5 to 3RW40 7 emergency stop and 3TK2823 safety relay Figure 15-27 Wiring of the emergency stop control circuit and the 3TK28 safety relay Figure 15-28 Wiring of the 3RW40 5 to 3RW40 7 control circuit and the 3RW40 2 to 3RW40 7 main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . On Emergency stop (3TK RESET) L+ (24VDC) Y21 Y22 A2 14 24 Y34 Y33 23 13 Y12 Y11 A1 3 T K 2 8 2 3 - 1 C B 3 0 -Q22 -Q21 -S3 -S4 M -Q22 -Q21 (2) -S1 Start / Stop 3RW44 S t a r t Fault 3RW44 Emergen- cy stop -S2 3 R U 1 9 0 0 - 2 A ( r e m o t e
R E S E T ) 0.2 to 4 s 3RW RESET O N
/
R U N O V E R L O A D
/
F A l L U R E B Y P A S S E D -F1 l>> l>> l>> -M1 U1 V1 W1 M -Q11 3RW40 -Q1 L1 T1 L2 T2 L3 T3 -H1 -Q21 -Q22 -Q21 -Q22 -H2 (2) (1) L N (1)(3) -Q21 -Q22 -Q11 95 96 13 14 23 24 98 -Q11 A1 A2 1 E1 E2 2 3 WARNING NOTICE Typical circuit diagrams 15.9 Emergency stop SIRIUS 3RW30 / 3RW40 190 Manual, 01/2010, 535 1995-02 DS01 (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command (3TK or 3RW) if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. If the soft stop function is set (ramp-down time potentiometer set to >0 s) and the emergency stop circuit is tripped, a "Missing load voltage, phase failure / missing load" fault may be indicated on the soft starter. In this case, the soft starter must be reset according to the selected RESET MODE. Typical circuit diagrams 15.10 3RW and contactor for emergency starting SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 191 15.10 3RW and contactor for emergency starting 15.10.1 3RW30 and contactor for emergency starting Figure WARNING 15-29 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] (Direct starting) Start / stop Direct starter contactor S t a r t O N Selector switch Soft start (1) L N -Q21 (1) U 98 96 95 -Q21 A2 A1 -H1 T3 L3 T2 L2 T1 L1 -Q1 -Q11 3RW30 -Q11 M W1 V1 U1 -M1 l>> l>> l>> 1 A2 A1 -Q11 14 13 -S1 -F1 -F1 (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to Troubleshooting chapter) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Typical circuit diagrams 15.10 3RW and contactor for emergency starting SIRIUS 3RW30 / 3RW40 192 Manual, 01/2010, 535 1995-02 DS01 15.10.2 3RW40 and contactor for emergency starting Figure 15-30 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit Figure 15-31 Wiring of the 3RW40 5 to 3RW40 7 control circuit S t a r t Fault Direct starter contactor Selector switch Soft start (Direct starting) Start / stop B Y P A S S E D O N
/
R U N O V E R L O A D
/
F A l L U R E 1.5 s RESET -S1 -Q11 95 96 13 14 23 24 -H1 -Q11 A1 A2 1 98 -H3 -H2 -F1 A1 A2 -Q21 95 96 98 U (1) L N l>> l>> l>> -M1 U1 V1 W1 M -Q11 3RW40 -Q1 L1 T1 L2 T2 L3 T3 (1) -Q21 -S2 S t a r t Fault Direct starting Selector switch Soft start (Direct starting) Start / stop Direct starter contactor B Y P A S S E D O N
/
R U N O V E R L O A D
/
F A l L U R E -S2 0.2 to 4 s RESET -S1 -Q11 95 96 13 14 23 24 -H1 -Q11 A1 A2 1 E1 E2 2 3 98 -H3 -H2 -F1 A1 A2 -Q21 95 96 98 U N (1) L WARNING Typical circuit diagrams 15.10 3RW and contactor for emergency starting SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 193 (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. Typical circuit diagrams 15.11 Dahlander / multispeed motor SIRIUS 3RW30 / 3RW40 194 Manual, 01/2010, 535 1995-02 DS01 15.11 Dahlander / multispeed motor 15.11.1 3RW30 and Dahlander motor starting Figure WARNING 15-32 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . A u x i l i a r y
c o n t a c t o r
f o r
s w i t c h o v e r
d e l a y
( r e s p o n s e
d e l a y
5 0 0
m s ) S t a r
c o n t a c t o r ,
h i g h
s p e e d M a i n
c o n t a c t o r ,
h i g h
s p e e d M a i n
c o n t a c t o r ,
l o w
s p e e d
F a u l t S t a r t Low speed Start High speed Start For motor overload protection, set rated current for low speed For motor overload protection, set rated current for high speed O N Motor stop (e.g. 3RB) (1)(3) (2) (2) (1) L T3 L3 T2 L2 T1 L1 -Q1 -Q11 -F2 -Q11 -Q21 -Q31 M W2 V2 U2 W1 V1 U1 -M1 -Q32 l>> l>> l>> A2 A1 A2 A1 A2 A1 A2 A1 N 1 A2 A1 -Q11 -H1 -Q32 -Q21 -Q31 -Q32 -K1 -Q21 96 95 98 -Q31 -Q32 -K1 -S1 -Q21 -S2 -S4 14 13 96 95 98 -Q1 -Q21 -Q31 -F1 -F2 3RW30 (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting [Page 44]) are automatically reset when the system returns to normal. An automatic restart is initiated and the 3RW restarted if a start command is present at the input. If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. Typical circuit diagrams 15.11 Dahlander / multispeed motor SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 195 (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] 15.11.2 3RW40 2 to 3RW40 4 and Dahlander motor starting Figure 15-33 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . High speed Low speed A u x i l i a r y
c o n t a c t o r
f o r
s w i t c h o v e r
d e l a y
( r e s p o n s e
d e l a y
5 0 0
m s ) S t a r
c o n t a c t o r ,
h i g h
s p e e d M a i n
c o n t a c t o r ,
h i g h
s p e e d M a i n
c o n t a c t o r ,
l o w
s p e e d
For motor overload protection, set rated current for low speed For motor overload protection, set rated current for high speed (e.g. 3RB) Motor stop Start B Y P A S S E D O N
/
R U N >1.5 s RESET Start S t a r t F a u l t -S1 -S2 -S2 -S4 -F1 -Q31 -Q21 -Q11 98 95 96 13 14 23 24 -Q21 -K1 -Q32 -Q31 98 95 96 -Q21 -K1 -Q32 -Q31 -Q21 -Q32 -H1 -Q11 A1 A2 1 A1 A2 A1 A2 A1 A2 A1 A2 -F2 (1) L (2) (2) N l>> l>> l>> -Q32 -F2 -M1 U1 V1 W1 U2 V2 W2 M -Q31 -Q21 -Q11 3RW40 -Q1 L1 T1 L2 T2 L3 T3 (1)(3) WARNING NOTICE Typical circuit diagrams 15.11 Dahlander / multispeed motor SIRIUS 3RW30 / 3RW40 196 Manual, 01/2010, 535 1995-02 DS01 (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. Typical circuit diagrams 15.11 Dahlander / multispeed motor SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01 197 15.11.3 3RW40 5 to 3RW40 7 and Dahlander motor starting Figure 15-34 Wiring of the 3RW40 5 to 3RW40 7 control circuit -S1 -S2 -S4 -S2 Low speed High speed A u x i l i a r y
c o n t a c t o r
f o r
s w i t c h o v e r
d e l a y
( r e s p o n s e
d e l a y
5 0 0
m s ) S t a r
c o n t a c t o r ,
h i g h
s p e e d M a i n
c o n t a c t o r ,
h i g h
s p e e d M a i n
c o n t a c t o r ,
l o w
s p e e d
3 R U 1 9 0 0 - 2 A ( r e m o t e
R E S E T ) Motor stop S t a r t F a u l t Start Start O N
/
R U N B Y P A S S E D 0.2 to 4 s RESET -F1 -Q31 -Q21 -Q11 98 95 96 13 14 23 24 -Q21 -K1 -Q32 -Q31 98 95 96 -Q21 -K1 -Q32 -Q31 -Q21 -Q32 -H1 -Q11 A1 A2 1 A1 A2 A1 A2 A1 A2 A1 A2 -F2 E1 E2 2 3 (1) L (2) (2) N Typical circuit diagrams 15.11 Dahlander / multispeed motor SIRIUS 3RW30 / 3RW40 198 Manual, 01/2010, 535 1995-02 DS01 Figure WARNING NOTICE 15-35 Wiring of the 3RW40 5 to 3RW40 7 main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For motor overload protection, set rated current for low speed For motor overload protection, set rated current for high speed (1)(3) l>> l>> l>> -Q32 -F2 (z.B. 3RB) -M1 U1 V1 W1 U2 V2 W2 M -Q31 -Q21 -Q11 3RW40 -Q1 L1 T1 L2 T2 L3 T3 (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present. This particularly applies if the motor protection has tripped. For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96) in the controller. No soft stop possible. Set the ramp-down time to 0 s with the potentiometer.