Brett Miller AE 475 Professor Bechtel Estimating and Scheduling Assignment Friday October 19, 2012
Assumptions:
Excavation: *The Following numbers were acquired from the given plans and personal calculations* *The excavation volume was used to have no slope to the top Depth: 15 Feet Area: 1966.3 Square Feet Volume: 9831.66 Cubic Yards Backfill Volume: 552 Cubic Yards *Penn State uses Engineered Fill* Figure 1 shows the plan of excavation. The building footprint is shown in red and the excavation is shown in brown. Figure 1:
Retaining Wall Footing: Concrete Strength: 3000 pounds per square inch Wall Mark: WF4.0 Length: 298.125 linear feet Rebar: Occurrence: This footing uses #6 size and has 8 bars continuously running the length of the footing, 1 every 9 inches on center in the top of the footing and one every 18 inches on center in the bottom of the footing. Weight of individual #6 bar: 1.502 pounds per foot Total Length of #6: 298.125 linear feet Total Weight in entire footing: 6,273.75 pounds
Retaining Wall: Assume CW2 for entire Wall The Footing of this wall was factored in on the previous page and will not be included with the wall in ICE. The concrete strength, per the concrete notes, is 4000 pounds per square inch Rebar: This wall uses #6 size bars and has 1 bar every 9 inches on center running vertically and 1 bar every 18 inches on center running horizontally. Weight of individual #6 bar: 1.502 pounds per foot Total Height of #6: 14 feet Total Length of #6: 298.35 linear feet Total Weight in entire wall: 10,815.84 pounds Total Volume of entire wall: 206.3 cubic yards Density of reinforcing: 52.43 pounds per cubic yard
CMU Wall Footing Concrete has a strength of 3000 pounds per square inch. WF2.0: Rebar: Occurrence: This Footing uses #5 bars. It has 2 continuously running the length of the footing, and has 1 every 11 inches on center. Weight of individual #5 bar: 1.043 pounds per foot Total Length of #5: 49.83 linear feet Total Weight in entire footing: 217 pounds WF3.0: Rebar: Occurrence: This Footing uses #5 bars and has 4 continuously running the length of the footing, and has 1 every 7 inches on center. Weight of individual #5 bar: 1.043 pounds per foot Total Length of #5: 183.5 linear feet Total Weight in entire footing: 1,391 pounds CMU Wall: Assume CW1 for entire wall The Footing of this wall was factored in above and will not be included with the wall in ICE. Rebar: This wall uses #5 rebar running vertically on 14 inch centers and running horizontally on 14 inch centers as well. Weight of individual #5 bar: 1.043 pounds per foot Density of reinforcing: 30.88 pounds per cubic yard
Column Pier Footings: For the footings, F3.0, F4.0, F4.0x3.0, F4.5, F5.0, F5.5, F6.0, F6.5, F8.0, F9.5, were all used and are further described in table 5 Concrete has a strength of 3000 pounds per square inch Column Piers: For this part of the project, the piers P1, P4, P5 and P7 were used. These are further shown in Table 6 Concrete has a strength of 4000 pounds per square inch Slab On Grade: Concrete has a strength of 3000 pounds per square inch Area: 9,480 square feet Perimeter: 550 feet Thickness: 4 inches For reinforcement, welded wire fabric was used instead of rebar
Assumption Tables:
The following are tables used in the calculation process. Table 1: Retaining Wall Footing Retaining Wall Footing Concrete Mark WF4.0 Mark WF4.0 Width 4 0 A Bars (4) #6 CONT Thickness Total Length 1 6 298.125 Retaining Wall Footing Rebar B Bars #6 @9 OC C Bars (2) #6 CONT D Bars #6 @ 18 OC Total Volume (ft3) 1790.125 Length (ft) 298.35 Total Volume (yd3) 66.3 Weight (lbs) 6273.75
Table 2: Retaining Wall Retaining Wall Concrete Mark CW2 Mark CW2 Thickness (in) 16 Height (ft) Length (ft) Volume (ft3) Volume (yd3) 206.3 Density (lb/yd3) 52.43
14 298.35 5569.2 Retaining Wall Rebar Vertical Horizontal Total Height Total Weight Reinforcing Reinforcing (ft) Length (ft) (lbs) #6 @ 9 OC #6 @ 18 OC 14 298.35 10815.84
Table 3: CMU Wall Footing CMU Wall Footing Mark WF2.0 WF3.0 Total Mark WF2.0 WF3.0 Total Table 4: CMU Wall CMU Wall Rebar Horizontal Total Reinforcing Height (ft) #5 @ 14 OC 14 Width 2 0 3 0 Thickness 1 0 1 4 Total Length 49.83 183.5 Total Volume (ft3) 99.66 734 833.66 Total Volume (yd3) 3.69 27.19 30.88 Weight (lbs) 217 1391 1608
CMU Wall Footing Rebar A Bars B Bars Length (ft) (2) # 5 CONT #5 @ 11 OC 49.83 (4) #5 CONT #5 @7 OC 183.5
Mark CW1
Vertical Reinforcing #5 @ 14 OC
Table 5: Column Pier Footings Column Piers Footing Concrete Mark F3.0 F4.0 F4.0X3.0 F4.5 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 Total Mark F3.0 F4.0 F4.0X3.0 F4.5 F5.0 F5.5 Volume (yd3) 0.444 0.79 0.59 1 1.388 2.054 2.444 2.869 4.346 6.128 A Bars (5) #5 (7) #5 (5) #5 (8) #5 (7) #6 (7) #7 Width 3 0 4 0 3 0 4 6 5 0 5 6 6 0 6 6 8 0 9 6 Length 3 0 4 0 4 0 4 6 5 0 5 6 6 0 6 6 8 0 9 6 Thickness 1 4 1 4 1 4 1 4 1 6 1 10 1 10 1 10 1 10 1 10 Quantity 8 9 1 4 4 7 6 3 1 8 Total Volume (yd3) 3.556 7.11 0.59 4 5.552 14.378 14.667 8.607 4.346 49.024 111.83 Weight (lbs) 31.29 58.41 44.85 75.1 105.14 157.39
Column Piers Footing Rebar B Bars C Bars D Bars (5) #5 N/A N/A (7) #5 N/A N/A (7) #5 N/A N/A (8) #5 N/A N/A (7) #6 N/A N/A (7) #7 N/A N/A
Length (ft) 3 4 3, 4 4 6 5 0 5 6
6 0 6 6 8 0 9 6
Table 6: Column Piers Column Piers Concrete Quantity Width Depth Height Volume (ft3) Volume (yd3) 9 2 0 2 0 3 0 108 4 2 1 4 1 4 3 0 10.67 0.395 1 2 0 2 6 3 0 15 0.56 1 2 0 2 6 3 0 15 0.56 Column Pier Rebar Reinforcing Weight (lbs) Volume (yd3) Density (lbs/yd3) (8) #8 64.08 0.44 145.64 (12) #6 54.07 0.198 273.08 (8) #7 49.06 0.56 87.61 (12) #8 96.12 0.56 171.64
Mark P1 P4 P5 P7 Mark P1 P4 P5 P7
Table 7: Slab On Grade Concrete Thickness (in) Slab on Grade 4 Area (ft2) 9480 Volume (ft3) 3160 Volume (yd3) 117
Sitework
02310.103 CUT & FILL DIRECT ON SITE 02310.107 ENGINEERED FILL 02310.112 EXCAV-LOAD-HAUL SURP 4-5MILES 02310.143 CUT-LOAD-HAUL VEG 4-5 MILES 02310.199 * CUT & FILL AREA * 02316.001 FINE GRADE FLOOR BY HAND 02316.021 Road gravel slab fill 02316.100 MACH EXCAV CONTINUOUS FTG 02316.100 MACH EXCAV CONTINUOUS FTG 02316.100 MACH EXCAV CONTINUOUS FTG 02316.102 FINE GRADE CONTINUOUS FTG 02316.102 FINE GRADE CONTINUOUS FTG 02316.102 FINE GRADE CONTINUOUS FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02830.150 **RETAINING WALL CONCRETE** 02830.155 4000 PSI CONC POUR DIRECT 02830.300 RE-STEEL RETAINING WALL 02830.400 POINT & PATCH 02830.501 FOOTING KEYWAYS 02830.522 RETAINING WALL FORMS 12-14' 02830.540 FORM RELEASE AGENT 02830.541 WALL FORM HARDWARE 02830.702 BITUMINOUS COATING 2-COATS 02830.890 * RETAINING WALL LENGTH * * Total Sitework 550.00 550.00 9,260.00 300.00 1,966.00 9,480.00 175.56 100.04 7.68 45.79 1,192.50 99.66 550.50 9.85 15.96 8.32 1.48 10.89 26.69 26.07 14.71 6.79 71.83 72.00 144.00 81.00 12.00 100.00 211.75 216.00 126.75 64.00 722.00 206.22 108.12 8,353.80 298.35 8,353.80 8,353.80 4,176.90 4,176.90 298.35 CUYD CUYD CUYD CUYD SQYD SQFT CUYD CUYD CUYD CUYD SQFT SQFT SQFT CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT **** CUYD CWT SQFT LNFT SQFT SQFT SQFT SQFT LNFT 1.7891 0.9779 2.9585 2.9921 0.4046 0.1183 6.9549 6.9549 6.9549 0.4761 0.4761 0.4761 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 14.6787 32.3636 0.1102 0.5761 3.2013 0.2226 0.6952 1.600 0.500 3.700 3.700 3.389 1.478 6.659 6.692 0.405 4.674 7.905 7.905 7.905 0.476 0.476 0.476 7.905 7.905 7.905 7.905 7.905 7.905 7.905 7.905 7.905 7.905 0.476 0.476 0.476 0.476 0.476 0.476 0.476 0.476 0.476 0.476 70.679 59.114 0.117 0.810 4.577 0.246 0.102 0.887 1,864.01 812.85 61,657.71 2,007.63 3,835.61 820.62 790.82 60.70 361.97 567.75 47.45 262.09 77.88 126.16 65.81 11.68 86.08 210.96 206.08 116.32 53.67 567.78 34.28 68.56 38.56 5.71 47.61 100.81 102.84 60.35 30.47 343.74 14,575.02 6,391.28 974.05 241.51 38,236.18 2,051.69 427.71 3,705.75 142,047.73
4.470
0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950
RET Footing WF2.0 CMU Footing WF3.0 CMU Footing RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5
Concrete
03110.510 03110.510 03110.510 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 CONTINUOUS FOOTING EDGE FORMS CONTINUOUS FOOTING EDGE FORMS CONTINUOUS FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS 906.38 103.66 497.21 127.68 191.52 95.76 18.62 120.00 281.82 263.95 142.97 58.66 SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 Page 1 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 4,952.80 566.44 2,716.95 697.69 1,046.54 523.27 101.75 655.73 1,539.98 1,442.34 781.27 320.52 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 10/18/2012 10:14 PM
03110.520 COLUMN FOOTING EDGE FORMS 557.23 03111.348 WOOD PIER FORMS 18.00 03111.348 WOOD PIER FORMS 2.66 03111.348 WOOD PIER FORMS 2.25 03111.348 WOOD PIER FORMS 2.25 03150.650 SCREEDS FOR SLAB 1,137.60 03150.900 FORM RELEASING AGENT 18.00 03150.900 FORM RELEASING AGENT 2.66 03150.900 FORM RELEASING AGENT 2.25 03150.900 FORM RELEASING AGENT 2.25 03210.155 PIER REBAR 0.04 03210.155 PIER REBAR 0.01 03210.155 PIER REBAR 03210.155 PIER REBAR 0.01 03210.200 CONTINUOUS FOOTING REBAR 62.74 03210.200 CONTINUOUS FOOTING REBAR 2.17 03210.200 CONTINUOUS FOOTING REBAR 13.91 03210.210 COLUMN FOOTING REBAR 2.50 03210.210 COLUMN FOOTING REBAR 5.26 03210.210 COLUMN FOOTING REBAR 3.00 03210.210 COLUMN FOOTING REBAR 0.45 03210.210 COLUMN FOOTING REBAR 4.21 03210.210 COLUMN FOOTING REBAR 11.02 03210.210 COLUMN FOOTING REBAR 11.77 03210.210 COLUMN FOOTING REBAR 12.75 03210.210 COLUMN FOOTING REBAR 3.27 03210.210 COLUMN FOOTING REBAR 74.56 03220.011 6x6 W2.1/W2.1 MESH 104.28 03310.150 **CONC IN CONTINUOUS FOOTING** 03310.150 **CONC IN CONTINUOUS FOOTING** 03310.150 **CONC IN CONTINUOUS FOOTING** 03310.151 3000 PSI DIRECT 66.25 03310.151 3000 PSI DIRECT 3.69 03310.151 3000 PSI DIRECT 27.18 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.201 3000 PSI DIRECT 3.55 03310.201 3000 PSI DIRECT 7.09 03310.201 3000 PSI DIRECT 3.99 03310.201 3000 PSI DIRECT 0.59 03310.201 3000 PSI DIRECT 5.56 03310.201 3000 PSI DIRECT 14.35 03310.201 3000 PSI DIRECT 14.66 03310.201 3000 PSI DIRECT 8.60 03310.201 3000 PSI DIRECT 4.34 03310.201 3000 PSI DIRECT 49.02 03310.350 **CONC IN SLAB ON GRADE** 03310.351 3000 PSI DIRECT 117.04 03310.750 **CONCRETE IN PIERS** 03310.750 **CONCRETE IN PIERS** 03310.750 **CONCRETE IN PIERS** 03310.750 **CONCRETE IN PIERS** X:\AE 475\Estimating and Scheduling Assignment\ICE\South Halls.est
SQFT SQFT SQFT SQFT SQFT LNFT SQFT SQFT SQFT SQFT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT SQS **** **** **** CUYD CUYD CUYD **** **** **** **** **** **** **** **** **** **** CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD **** CUYD **** **** **** ****
4.4257 1.0476 1.0476 1.0476 1.0476 0.9219 0.2095 0.2095 0.2095 0.2095 23.7333 23.7333 23.7333 23.7333 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 22.0080
1.039 1.161 1.161 1.161 1.161 0.320 0.023 0.023 0.023 0.023 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 10.650
5.464 2.208 2.208 2.208 2.208 1.242 0.233 0.233 0.233 0.233 50.483 50.483 50.483 50.483 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 32.658
3,044.94 39.75 5.87 4.97 4.97 1,412.79 4.19 0.62 0.52 0.52 2.04 0.38 0.17 0.33 3,672.38 127.02 814.23 146.53 307.72 175.84 26.25 246.18 644.91 689.15 746.59 191.44 4,364.70 3,405.58
F9.5 P1 P4 P5 P7 P1 P4 P5 P7 P1 P4 P5 P7 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5
11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090
55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000
66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009
234.11 468.22 263.38 39.02 366.72 947.36 967.96 568.00 286.80 3,235.48 7,725.50
03310.775 4000 PSI DIRECT 03310.775 4000 PSI DIRECT 03310.775 4000 PSI DIRECT 03310.775 4000 PSI DIRECT 03315.971 * CONTINUOUS FOOTING LENGTH * 03315.971 * CONTINUOUS FOOTING LENGTH * 03315.971 * CONTINUOUS FOOTING LENGTH * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.976 * SOG AREA * 03350.130 MACHINE TROWEL FINISH 03350.131 POINT & PATCH 03350.131 POINT & PATCH 03350.131 POINT & PATCH 03350.131 POINT & PATCH 03390.010 PROTECT & CURE * Total Concrete
0.03 CUYD CUYD CUYD CUYD 298.13 LNFT 49.83 LNFT 183.50 LNFT 8.00 EACH 9.00 EACH 4.00 EACH 1.00 EACH 4.00 EACH 7.00 EACH 6.00 EACH 3.00 EACH 1.00 EACH 8.00 EACH 9,480.00 SQFT 9,480.00 SQFT 18.00 SQFT 2.66 SQFT 2.25 SQFT 2.25 SQFT 9,480.00 SQFT
P1 P4 P5 P7 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5
P1 P4 P5 P7
Masonry
04210.011 MORTAR 04210.201 STANDARD SIZE FACE BRICK 04219.990 * MASONRY WALL AREA * 04220.102 FILL VOIDS W/ CONCRETE 04220.504 12X8X16 CONC BLOCK 04224.122 MASONRY REBAR 04930.011 CLEAN FACE BRICK * Total Masonry 15.37 21.40 3,266.62 32.48 3,674.95 25.55 3,266.62 CUYD M SQFT CUYD PCS CWT SQFT 566.9517 20.5520 2.5690 20.5520 0.4060 50.000 135.000 55.000 0.945 26.750 50.000 701.952 75.552 3.514 47.302 0.406 768.26 15,019.21 2,454.29 12,913.77 1,208.71 1,326.25 33,690.49
Page 3
10/18/2012 10:14 PM
South Halls Activity ID A1000 A1010 A1020 A1030 A1040 A1050 A1060 A1070 A1080 A1090 A1100 A1110 A1120 A1130 A1140 A1150 A1160 A1170 A1180 A1190 A1200 A1210 A1220 A1230 A1240 Activity Name Excavation Formwork - Retaining Wall/Column Footings Rebar - Retaining Wall/Column Footings Pour - Retaining Wall/Column Footings Cure - Retaining Wall/Column Footings Strip Formwork Formwork - Retaining Wall Rebar - Retaining Wall Pour - Retaining Wall Cure - Retaining Wall Strip Formwork Backfill Formwork - Column Piers Rebar - Column Piers Pour - Column Piers Cure - Column Piers Strip Formwork Formwork - CMU Wall Footings Rebar - CMU Wall Footings Pour - CMU Wall Footings Cure - CMU Wall Footings Strip Formwork Build - CMU Wall Installation - Welded Wire Fabric Pour - Slab On Grade
Classic Schedule Layout Original Remaining Schedule % Start Duration Duration Complete 11 5 5 2 5 2 7 7 2 5 2 5 5 5 2 5 1 5 5 2 5 2 10 4 3 11 5 5 2 5 2 7 7 2 5 2 5 5 5 2 5 1 5 5 2 5 2 10 4 3 100% 07-May-12 100% 21-May-12 100% 25-May-12 100% 01-Jun-12 100% 04-Jun-12 100% 08-Jun-12 100% 11-Jun-12 100% 19-Jun-12 100% 27-Jun-12 100% 28-Jun-12 100% 05-Jul-12 100% 06-Jul-12 100% 12-Jul-12 100% 20-Jul-12 100% 26-Jul-12* 100% 27-Jul-12 100% 02-Aug-12 100% 02-Aug-12 100% 08-Aug-12 100% 14-Aug-12 100% 15-Aug-12 100% 21-Aug-12 100% 22-Aug-12 100% 05-Sep-12 100% 10-Sep-12 Finish 21-May-12 25-May-12 01-Jun-12 04-Jun-12 08-Jun-12 11-Jun-12 19-Jun-12 27-Jun-12 28-Jun-12 05-Jul-12 06-Jul-12 12-Jul-12 18-Jul-12 26-Jul-12 27-Jul-12 02-Aug-12 02-Aug-12 08-Aug-12 14-Aug-12 15-Aug-12 21-Aug-12 22-Aug-12 05-Sep-12 10-Sep-12 12-Sep-12 Resources
19-Oct-12 00:31
Page 1 of 2
South Halls Budgeted Total Cost $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 Total Float May 2012 06 13 20 27 03 Excavation June 2012 10 17 24
Formwork - Retaining Wall/Column Footings Rebar - Retaining Wall/Column Footings Pour - Retaining Wall/Column Footings Cure - Retaining Wall/Column Footings Strip Formwork Formwork - Retaining Wall Rebar - Retaining Wall Pour - Retaining Wall Cure - Retaining Wall Strip Formwork Backfill Formwork - Column Piers Rebar - Column Piers Pour - Column Piers Cure - Column Piers Strip Formwork Formwork - CMU Wall Footings Rebar - CMU Wall Footings Pour - CMU Wall Footings Cure - CMU Wall Footings Strip Formwork Build - CMU Wall Installation - Welded Wire Fabric Pour - Slab On Grade
Page 2 of 2
References:
1. The entire footprint was used from SB 101 2. Details A1 and A3 were used from page SB 301 3. Details D1, D2, and D4 were used from SB 302 4. Footing Schedule Column, Footing Schedule Wall, and Pier Schedule were all used from SB 501 5. CMU Wall Reinforcing Schedule and Concrete Wall Reinforcing Schedule were both used from SF 601
CONCRETE NOTES
1. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THE AMERICAN CONCRETE INSTITUTE (ACI) SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301-08). 2. CAST-IN-PLACE CONCRETE SHALL ATTAIN THE FOLLOWING MINIMUM 28-DAY COMPRESSIVE STRENGTHS (f'c):
STEEL NOTES
1. FABRICATION AND ERECTION OF STRUCTURAL STEEL AND DESIGN OF CONNECTIONS SHALL BE IN ACCORDANCE WITH THE AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, DATED MARCH 9, 2005 AND THE AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES, DATED MARCH 18, 2005. UNLESS OTHERWISE NOTED, STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE ABOVE-LISTED AISC SPECIFICATION AND THE FOLLOWING: A. B. C. D. E. F. G. H. 3. SQUARE AND RECTANGULAR HSS ROUND HSS WIDE FLANGE SHAPES AND TEES CHANNELS AND S-SHAPES PLATES AND ANGLES HIGH STRENGTH BOLTS ANCHOR RODS W/ NUT AND WASHER THREADED ROD ASTM A500, GRADE B, Fy = 46 KSI ASTM A500, GRADE B, Fy = 42 KSI ASTM A992 ASTM A36/A36M ASTM A36/A36M ASTM F1852 ASTM F1554, GRADE 36 ASTM A36/A36M
SYMBOL
Wn DN [X'-X"]
DESCRIPTION
WALL TYPE SLOPE DIRECTION SPOT ELEVATION DECK OR BAR GRATING SPAN INDICATES ELEVATION REFERENCED TO FINISHED GROUND FLOOR KEYED CONSTRUCTION NOTE COLUMN REFERENCE LINE (CENTERLINE OF COLUMN) BRICK
DESCRIPTION
ANCHOR BOLT ABOVE FINISHED FLOOR APPROXIMATELY ARCHITECTURAL BOTTOM OF CONCRETE BOTTOM OF STEEL BEARING COLD-FORMED STEEL SLAB CONSTRUCTION JOINT CENTER LINE CLEAR CONCRETE MASONRY UNIT COLUMN CONNECTION CONCRETE CONTINUOUS DOWELED CONSTRUCTION JOINT DIAMETER DOWN DRAWING EACH EACH FACE EXPANSION JOINT ELEVATION EDGE OF CORBEL EDGE OF SLAB EQUAL EACH WAY FINISHED FLOOR ELEVATION FACE OF BRICK FAR SIDE FOOTING GAGE GALVANIZED HORIZONTAL 1000 LBS LONG LONG LEG HORIZONTAL LONG LEG VERTICAL LONG SIDE HORIZONTAL LONG SIDE VERTICAL MAXIMUM MANUFACTURER MINIMUM MIDDLE OF WALL NOT IN CONTRACT NUMBER NOMINAL NEAR SIDE NOT TO SCALE ON CENTER OPPOSITE PREMOLDED JOINT FILLER PLATE POUNDS PER LINEAR FOOT POUNDS PER SQUARE FOOT REINFORCING REQUIRED SCHEDULE SLAB DEPRESSION
2. 3. 4.
2. A. B. C. D. E. WALLS AND PIERS COMPOSITE DECK FILL (LIGHTWEIGHT CONCRETE) SLAB-ON-GRADE FOOTINGS ALL OTHER CONCRETE 4000 4000 3000 3000 4000 PSI PSI PSI PSI PSI
APPROX ARCH BOC BOS BRG CFS CJ CL CLR CMU COL CONN CONC
CONCRETE DENSITY SHALL BE NORMAL WEIGHT UNLESS SPECIFICALLY OTHERWISE NOTED. CONCRETE REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. PROVIDE SHEET-TYPE WELDED WIRE FABRIC. SHEET LAPS SHALL BE TIED AND LAPPED ONE FULL MESH SPACING PLUS 2". CONCRETE REINFORCING STEEL SHALL BE CONTINUOUS UNLESS OTHERWISE INDICATED. CONTINUOUS REINFORCING STEEL SHALL BE LAPPED IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 318 AND SHEET SB502. 4. MINIMUM CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS INDICATED. IN NO CASE SHALL REINFORCING COVER BE LESS THAN THE REQUIREMENTS OF ACI 301. A. B. C. D. CONCRETE DEPOSITED AGAINST THE GROUND CONCRETE EXPOSED TO EARTH OR WEATHER BEAMS AND COLUMNS SLABS AND WALLS NOT EXPOSED TO EARTH OR WEATHER 3 2 1 1/2 1 5. 6.
ALL SHOP AND FIELD WELDING SHALL BE BY CERTIFIED WELDERS AND SHALL CONFORM TO AWS STANDARDS. USE E70XX ELECTRODES UNLESS NOTED OTHERWISE. CURRENT AWS CERTIFICATIONS SHALL BE AVAILABLE AT THE JOB SITE FOR REVIEW BY THE OWNERS REPRESENTATIVE. ALL BOLTED CONNECTIONS, UNLESS OTHERWISE NOTED, SHALL USE HIGH-STRENGTH BOLTS WITH HARDENED CARBON STEEL WASHERS AS REQUIRED FOR THE CONNECTION LOADS. FOR CONNECTIONS NOT DETAILED AND OTHERS REQUIRED BY THE ERECTION PROCEDURES, THE FABRICATOR SHALL SUBMIT DETAILS AND CALCULATIONS TO THE ENGINEER OF RECORD FOR APPROVAL. FIELD CUTTING OF STRUCTURAL STEEL MEMBERS BY ANY TRADE SHALL NOT BE PERMITTED. BOLT HOLES SHALL NOT BE CUT OR ENLARGED BY FLAME CUTTING IN THE FIELD. ALL FIELD-BOLTED SHEAR CONNECTIONS SHALL BE PRE-TENSIONED CONNECTIONS, THREADS INCLUDED IN THE SHEAR PLANE. CONNECTION DESIGN IS DELEGATED TO THE CONTRACTOR. SUBMIT CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE COMMONWEALTH OF PENNSYLVANIA ALONG WITH THE SHOP DRAWINGS FOR CONNECTIONS OTHER THAN SIMPLE SHEAR CONNECTIONS. SHEAR CONNECTIONS FOR BEAMS SUPPORTING FLOOR AND ROOF GRAVITY LOADS SHALL BE DESIGNED FOR THE FACTORED REACTIONS SHOWN ON THE DRAWINGS. FOR CONDITIONS WHERE REACTIONS ARE NOT INDICATED ON THE DRAWINGS, SHEAR CONNECTIONS SHALL BE DESIGNED FOR 50 PERCENT OF THE MAXIMUM TOTAL UNIFORM LOAD AS INDICATED IN THE LOAD TABLES OF PART 3 OF THE AISC STEEL CONSTRUCTION MANUAL, 13TH EDITION, FOR THE BEAM SIZE, SPAN AND GRADE OF STEEL SPECIFIED. IN NO CASE SHALL THE MINIMUM NUMBER OF BOLTS IN A SHEAR CONNECTION BE LESS THAN THAT INDICATED IN NOTE #10. MOMENT CONNECTIONS SHALL BE DESIGNED FOR THE MOMENTS INDICATED ON THE DRAWINGS AND THE SHEAR CAPACITY AS INDICATED IN NOTE #8, UNLESS OTHERWISE NOTED. MOMENT CONNECTIONS MAY BE WELDED OR BOLTED WITH SLIP-CRITICAL CONNECTIONS AT THE FABRICATORS OPTION.
[X'-X"] X
DESIGN NOTES
1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES AND SPECIFICATIONS: A. B. "PENNSYLVANIA UNIFORM CONSTRUCTION CODE" DATED DECEMBER 31, 2009 2009 INTERNATIONAL BUILDING CODE (IBC) 9.
CONCRETE REINFORCING STEEL MARKED STANDARD HOOK SHALL HAVE A 90-DEGREE HOOK UNLESS OTHERWISE NOTED. STIRRUPS, TIES, 180-DEGREE HOOKS, AND 90-DEGREE HOOKS SHALL CONFORM TO THE REQUIREMENTS OF ACI 318. PROVIDE 1/2" THICK JOINT FILLER MATERIAL WHERE SLABS-ON-GRADE ABUT VERTICAL SURFACES.
CONCRETE
CONT DCJ
7.
EARTH FILL
DIA, DN
10. ALL EMBEDDED ITEMS SHALL BE PROPERLY PLACED, ACCURATELY POSITIONED, AND MAINTAINED SECURELY IN PLACE PRIOR TO AND DURING CONCRETE PLACEMENT. 11. REINFORCING STEEL SHALL BE SPREAD AT SLEEVES, TIEBACKS, RECESSES, AND OTHER EMBEDDED ITEMS UNLESS OTHERWISE INDICATED. REINFORCING SHALL NOT BE CUT TO FACILITATE PLACEMENT OF EMBEDDED ITEMS. 12. NO CONCRETE SHALL BE PLACED UNTIL THE OWNER OR THE OWNERS DESIGNATED REPRESENTATIVE HAS INSPECTED ALL EMBEDDED WORK, INCLUDING REINFORCING. 13. ALL EXPOSED CONCRETE EDGES SHALL BE CHAMFERED 3/4" OR AS INDICATED. 14. ALUMINUM SHALL NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE UNLESS EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CONCRETE REACTION AND ELECTROLYTIC ACTION BETWEEN ALUMINUM AND STEEL. 15. PROVIDE ADDITIONAL CONCRETE REQUIRED TO ACHIEVE SPECIFIED FLOOR FLATNESS CRITERIA.
8.
GROUT
DWG EA
C. ASCE 7-05, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES D. AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS DATED MARCH 9, 2005 E. F. AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES DATED MARCH 18, 2005 ACI 318-08, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
EF EJ
9.
G. ACI 530-08, BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES H. AISI NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS 2007 EDITION 2. DESIGN LOAD CRITERIA: A. LIVE LOADS (UNIFORM) ROOF ATTIC WALKWAYS PARTITION ALLOWANCE PRIVATE ROOMS AND CORRIDORS SERVING THEM PUBLIC ROOMS AND CORRIDORS SERVING THEM STAIRS AND EXITS STORAGE MECHANICAL/ELECTRICAL ROOMS TOILETS 30 PSF 40 PSF 15 PSF 40 PSF 100 PSF 100 PSF 125 PSF 125 PSF 100 PSF
10. BOLTED SHEAR CONNECTIONS FOR BEAMS SUPPORTING FLOOR, ROOF, AND STAIR GRAVITY LOADS SHALL CONTAIN A MINIMUM NUMBER OF HIGH STRENGTH BOLTS AS FOLLOWS. THE MINIMUM BOLT DIAMETER IS 3/4". WELDED WIRE FABRIC BEAM SIZE MINIMUM NUMBER OF ROWS OF BOLTS 2 3 4 5 6 7 10k END REACTIONS BEAM SIZE # SHEAR STUDS CAMBER W24x55 (16) C=1" (-2") 10k TOP OF STEEL ELEVATION RELATIVE TO TYPICAL TOS
MASONRY NOTES
1. ALL MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-08/ASCE 5-08/TMS 402-08) AND SPECIFICATION FOR MASONRY STRUCTURES (ACI 530.1-08/ASCE 6-08/TMS 402-08). DESIGN MASONRY ASSEMBLAGE STRENGTH, fm = 1500 PSI. NET AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY UNITS SHALL BE A MINIMUM OF 1900 PSI. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 AND BE MANUFACTURED WITH NORMAL WEIGHT AGGREGATE (OVEN-DRY UNIT WEIGHT=135 PCF, MAX). GROUT SHALL CONFORM TO ASTM C476 AND SHALL NOT CONTAIN ADMIXTURES. GROUT SHALL ATTAIN A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2000 PSI. GROUT POURS SHALL BE STOPPED 1-1/2 INCHES BELOW THE TOP OF A COURSE TO FORM A KEY AT POURED JOINTS. REINFORCING SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60 AND SHALL HAVE FABRICATION TOLERANCES IN ACCORDANCE WITH ACI 315. SHOP FABRICATE REINFORCING BARS WHICH ARE INDICATED TO BE BENT OR HOOKED.
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
2. 3. 4.
W27 W30
NOTE: LIVE LOAD REDUCTION WAS USED IN THE DESIGN OF THIS STRUCTURE B. SNOW LOAD: GROUND SNOW LOAD, Pg SNOW EXPOSURE FACTOR, Ce THERMAL FACTOR, Ct SNOW LOAD IMPORTANCE FACTOR, Is FLAT ROOF SNOW LOAD, Pf SLOPED-ROOF SNOW LOAD, Ps C. WIND LOADS: BASIC WIND SPEED, V OCCUPANCY CATEGORY WIND IMPORTANCE FACTOR, I WIND EXPOSURE CATEGORY GUST EFFECT FACTOR, G INTERNAL PRESSURE COEFFICIENTS, GCpi 90 MPH II 1.00 B 0.85 0.18 9. 30 PSF 0.9 1.1 1.0 21 PSF 21 PSF 5. 6.
11. THE CONTRACTOR SHALL SUBMIT FOR APPROVAL DRAWINGS AND DESIGN CALCULATIONS FOR ANY ALTERNATE DETAILS AND MEMBER SPLICES. 12. SHOP OR FIELD SPLICES OF STRUCTURAL STEEL MEMBERS ARE PROHIBITED EXCEPT AS DETAILED ON THE DRAWINGS, PERMITTED IN THE SPECIFICATIONS, AS INDICATED ON APPROVED SUBMITTALS, AND AS SPECIFICALLY APPROVED ON SHOP DRAWINGS PRIOR TO FABRICATION. 13. PAINT ALL STEEL BELOW GRADE WITH TWO COATS OF COAL TAR EPOXY.
LLH LLV LSH LSV MAX MFR MIN MOW NIC NO. NOM NS NTS OC OPP PJF
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
7. JOINT REINFORCING SHALL BE LADDER-TYPE HOT-DIP GALVANIZED STEEL WIRE, LAPPED 8" AT ENDS. 8. LOCATE JOINT REINFORCING 16 INCHES ON CENTER VERTICALLY. PROVIDE ADDITIONAL REINFORCING AT THE TOP OF ALL FOUNDATIONS AND IN THE TWO JOINTS IMMEDIATELY ABOVE AND BELOW ALL OPENINGS. EXTEND JOINT REINFORCING A MINIMUM OF 24 INCHES BEYOND THE OPENING ON EACH SIDE. PLACE PIPES AND CONDUITS PASSING HORIZONTALLY THROUGH MASONRY IN STEEL OR PVC SLEEVES OR CORED HOLES UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
10. ALUMINUM CONDUITS, PIPES, AND ACCESSORIES SHALL NOT BE EMBEDDED IN MASONRY GROUT, OR MORTAR, UNLESS EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CEMENT CHEMICAL REACTION OR ELECTROLYTIC REACTION BETWEEN ALUMINUM AND STEEL. 11. UNLESS OTHERWISE NOTED OR DETAILED, CENTER WALL REINFORCING IN BLOCK CELLS. USE NONMETALLIC BAR POSITIONERS. 12. PROVIDE DOWEL REINFORCING FROM FOUNDATION OF SAME SIZE AND SPACING AS VERTICAL WALL REINFORCING. LAP WALL REINFORCING A MINIMUM OF 48 BAR DIAMETERS. 13. HORIZONTAL JOINT REINFORCING SHALL BE DISCONTINUOUS AT ALL CONTROL JOINTS. 14. HORIZONTAL BOND BEAM REINFORCING SHALL BE CONTINUOUS THROUGH ALL CONTROL JOINTS.
PL PLF PSF
FOUNDATION NOTES
1. 2. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS IN THE GEOTECHNICAL REPORT PREPARED BY CMT LABORATORIES AND DATED OCTOBER 10, 2011 WITH MARCH 21, 2012 REVISIONS. FOUNDATIONS HAVE BEEN DESIGNED TO BEAR ON EXISTING NATURAL BEDROCK, CAPABLE OF SUPPORTING A NET ALLOWABLE DESIGN BEARING PRESSURE OF 8000 PSF. WHERE COMPETENT BEDROCK IS NOT ENCOUNTERED AT A FOOTING LOCATION, CONTACT STRUCTURAL ENGINEER OF RECORD FOR DESIGN OF A FOOTING ON FIRM NATURAL SOIL OR ENGINEERED FILL. PRIOR TO PLACING FOUNDATION CONCRETE, THE CONTRACTOR SHALL ENSURE THAT THE FOUNDATION EXCAVATIONS ARE INSPECTED BY AN INDEPENDENT TESTING LABORATORY AND GEOTECHNICAL ENGINEER REGISTERED IN THE COMMONWEALTH OF PENNSYLVANIA TO EVALUATE THE EXTENT OF LOOSE, SOFT OR OTHERWISE UNSATISFACTORY SOIL MATERIAL AND TO VERIFY THE DESIGN BEARING CAPACITY. SOILS NOT SUITABLE FOR FOUNDATION SUPPORT SHALL BE UNDERCUT AND REPLACED WITH ENGINEERED FILL AS RECOMMENDED IN THE GEOTECHNICAL REPORT. ADEQUATELY PROTECT FOUNDATION EXCAVATIONS TO PREVENT WATER FROM ACCUMULATING AND STANDING IN THE EXCAVATION BOTTOMS. FROST PROTECTION SHALL BE PROVIDED BY ERECTING FOOTINGS ON SOLID ROCK. WHERE SOLID ROCK IS NOT ENCOUNTERED, BOTTOM OF FOOTING SHALL EXTEND BELOW FROST LINE ELEVATION OF 42" BELOW GRADE. DO NOT PLACE FOUNDATION CONCRETE ON FROZEN OR SATURATED SUBGRADES.
SIMILAR SLAB SAWED (CONTRACTION) JOINT SLAB-ON-GRADE STANDARD TOP AND BOTTOM TOP OF CONCRETE TOP OF FOOTING TOP OF MASONRY TOP OF STEEL THICKENED SLAB TYPICAL UNLESS OTHERWISE NOTED VERTICAL WORKING POINT WELDED WIRE FABRIC
3. -31.5
4. 5. 6. 7. 8. 9.
COMPONENT TRIBUTARY AREA (ft2) WALL ZONE 0 - 20 4 5 NOTES: 1. 2. POSITIVE AND NEGATIVE SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY BUILDING ZONES ARE DEFINED IN ASCE 7 18.8 18.8 -20.3 -25.1 21 - 100 17.9 17.9 -19.4 -23.3 15.9 15.9 101 + -17.5 -19.5
TOS ENSURE THAT EARTH-FORMED FOOTINGS CONFORM TO THE SHAPE, LINES, AND THICKNESSES INDICATED ON THE FOUNDATION PLAN. EXCAVATION WIDTHS SHALL BE A MINIMUM OF 4 INCHES GREATER THAN DIMENSIONS INDICATED. PLACE FOUNDATION CONCRETE THE SAME DAY EXCAVATIONS ARE MADE OR AS SOON AS PRACTICAL THEREAFTER. DO NOT INSTALL FOUNDATIONS UNTIL FOUNDATION WORK HAS BEEN COORDINATED WITH ADJACENT UNDERGROUND UTILITIES AND STRUCTURES. TS TYP UON VERT WP WWF
10. FOOTINGS SHALL BE LOWERED AS REQUIRED TO PASS UNDER UTILITY LINES. STEP CONTINUOUS FOOTINGS DOWN AS SHOWN IN THE TYPICAL STEPPED FOOTING DETAIL ON SHEET SB501.
SEISMIC LOADS: OCCUPANCY CATEGORY SEISMIC IMPORTANCE FACTOR, Ie SPECTRAL RESPONSE ACCELERATION, Ss SPECTRAL RESPONSE ACCELERATION, S1 SPECTRAL RESPONSE COEFFICIENT, SDs SPECTRAL RESPONSE COEFFICIENT, SD1 SITE CLASS SEISMIC DESIGN CATEGORY BASIC SEISMIC FORCE-RESISTING SYSTEM II 1.0 0.147g 0.049g 0.118g 0.055g C A STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE (IN COMBINATION WITH ORDINARY REINFORCED CONCRETE SHEAR WALLS AT GROUND STORY) 3 0.01W EQUIVALENT LATERAL FORCE FOLLOWING DESIGN REQUIREMENTS OF ASCE 7-05 SECTION 11.7
SUBMIT SHOP DRAWINGS FOR ALL DELEGATED ENGINEERED SYSTEMS AND COMPONENTS TO THE STRUCTURAL ENGINEER OF RECORD. ALL SUBMITTALS FROM THE DELEGATED ENGINEER MUST BE SUBMITTED TO THE ENGINEER OF RECORD PRIOR TO THE START OF FABRICATION OF THE SYSTEM OR COMPONENT PART AND PRIOR TO ANY FIELD CONSTRUCTION THAT MAY BE AFFECTED BY THE SYSTEM OR COMPONENT PART. DELEGATED ENGINEERED SYSTEMS SHALL MEET ASCE 7-05 REQUIREMENTS FOR WIND, SEISMIC, AND LIVE LOADS. REFERENCE APPLICABLE SPECIFICATIONS FOR REQUIRED SUBMITTALS TO BE SIGNED AND SEALED BY QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR DELEGATED ENGINEERED SYSTEMS AND COMPONENTS.
4. 5.
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
F.
DESCRIPTION OF LATERAL LOAD-RESISTING SYSTEM: LATERAL LOAD-RESISTING SYSTEM AND STABILITY OF THE COMPLETED STRUCTURE IS PROVIDED BY STRUCTURAL STEEL BRACED FRAMES AT ALL FLOOR LEVELS AND ROOF LEVEL, IN COMBINATION WITH ORDINARY REINFORCED CONCRETE SHEAR WALLS AT THE GROUND FLOOR LEVEL. COMPOSITE CONCRETE SLABS AT FLOOR LEVELS ARE HORIZONTAL DIAPHRAGMS THAT DISTRIBUTE LATERAL WIND AND SEISMIC FORCES HORIZONTALLY TO THE COLLECTING ELEMENTS FOR THE BRACED FRAMES AND SHEAR WALLS. AT ROOF LEVEL, STEEL DECK SERVES AS A HORIZONTAL DIAPHRAGM THAT DISTRIBUTES HORIZONTAL LOADS TO COLLECTING ELEMENTS AND INTO THE BRACED FRAMES AT THE ROOF AND INTO THE MOMENT FRAMES AT THE VESTIBULE CANOPIES.
S-001
SHEET OF
STEPPED FOOTING
E
2.
ATTACH DECK TO SUPPORTS USING 3/4" x 4 3/16" LONG HEADED STUDS AT THE QUANTITY INDICATED ON THE FRAMING PLANS. WHERE STUD SPACING EXCEEDS 12" ON CENTER, WELD DECK TO SUPPORTS USING 5/8" PUDDLE WELDS AT 12" ON CENTER. SIDE LAP CONNECTIONS SHALL BE MADE WITH (3) #10 SCREW CONNECTIONS PER SPAN. FASTEN DISCONTINUOUS SIDE OF FLOOR DECK TO SUPPORTING STRUCTURE WITH 5/8" PUDDLE WELDS AT 12" ON CENTER UNLESS OTHERWISE NOTED. COMPOSITE ROOF DECK SHALL BE GALVANIZED STEEL CONFORMING TO ASTM A653-07 WITH A MINIMUM YIELD STRENGTH OF 50 KSI. COMPOSITE ROOF DECK SHALL BE 2" DEEP WITH 3" OF LIGHTWEIGHT CONCRETE TOPPING, MINIMUM; TOTAL SLAB THICKNESS = 5" MINIMUM. DECK RIBS SHALL BE SPACED AT 12" ON CENTER. COMPOSITE ROOF DECK SHALL HAVE THE FOLLOWING MINIMUM SECTION PROPERTIES: A. t=0.0358 in (20 Gage) B. Ip=0.406 in4/ft C. Sp=0.341 in3/ft D. Sn=0.346 in3/ft 3. ROOF DECK SHALL BE GALVANIZED STEEL CONFORMING TO ASTM A653-07 WITH A MINIMUM YIELD STRENGTH OF 33 KSI. STEEL ROOF DECK SHALL BE 1 1/2" DEEP WIDE RIB DECK WITH THE FOLLOWING MINIMUM SECTION PROPERTIES: A. B. C. D. t=0.0358 in (20 Gage) Ip=0.201 in4/ft Sp=0.234 in3/ft Sn=0.247 in3/ft
INCLUDE SECONDARY BENDING STRESSES DUE TO SUPERIMPOSED LOADS IN DESIGN OF CHORD MEMBERS. 3. LIMIT MIDSPAN DEFLECTION OF THE BOTTOM CHORD OF EACH TRUSS DUE TO LIVE LOAD TO SPAN/360 WITH A MAXIMUM OF 1. LIMIT MIDSPAN DEFLECTION OF THE BOTTOM CHORD OF EACH TRUSS DUE TO TOTAL LOAD TO SPAN/240 WITH A MAXIMUM OF 1. WHERE OVERLAY FRAMING IS INDICATED ON DRAWINGS, DESIGN TRUSSES SUPPORTING OVERLAY FRAMING FOR ADDITIONAL SUPERIMPOSED DEAD LOADS OF OVERLAY FRAMING. USE ACTUAL DEAD LOAD OF FRAMING AND SHEATHING (MINIMUM 10 PSF). PROVIDE PERMANENT CONTINUOUS LATERAL BRACING OF THE WEB AND CHORD MEMBERS IN ACCORDANCE WITH THE TYPICAL DETAIL ON SHEET SF502 IN THE LOCATIONS SPECIFIED BY THE TRUSS DESIGNER ON THE TRUSS SHOP DRAWINGS. DESIGN ROOF TRUSSES TO SUPPORT LOAD OF FALL PROTECTION SYSTEM. COORDINATE WITH FALL PROTECTION SYSTEM SHOWN ON SHEET AE141 AND LOADS PROVIDED BY FALL PROTECTION SUPPLIER.
4.
5. 6.
POST-INSTALLED ANCHORS
1. ALL POST-INSTALLED ANCHORS (IN CONCRETE OR CMU) ARE TO BE INSTALLED IN STRICT CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS (INCLUDING BUT NOT LIMITED TO DRILL BIT SIZE, PROPER CLEANING OF HOLES, INSTALLATION TORQUE, AND TEMPERATURE CONSTRAINTS). WHEN ADHESIVE ANCHORS ARE USED, REMOVE EXCESS ADHESIVE AT THE TOP OF THE HOLE BEFORE IT HARDENS. POST-INSTALLED ANCHORS SHALL BE INSTALLED AT NOT LESS THAN MINIMUM EDGE DISTANCES AND SPACINGS INDICATED IN THE MANUFACTURER'S LITERATURE. CONTRACTOR TO HAVE MANUFACTURER'S REPRESENTATIVE PERFORM PRODUCT INSTALLATION TRAINING ON SELECTED SYSTEMS. THE INDEPENDENT TESTING AGENCY SHALL PROVIDE THE INSPECTION OF ALL ANCHORS DURING INSTALLATION TO VERIFY CONFORMANCE WITH THE MANUFACTURER'S INSTALLATION RECOMMENDATIONS. CONFIRM THE ABSENCE OF REINFORCING STEEL BY DRILLING A 1/4" DIAMETER PILOT HOLE FOR EACH ANCHOR OR BY NONDESTRUCTIVE METHODS. DO NOT CUT REINFORCING STEEL WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL OBTAIN APPROVAL FROM STRUCTURAL ENGINEER OF RECORD PRIOR TO USING POST-INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST-IN-PLACE ANCHORS OR FOR SUBSTITUTIONS. CALCULATIONS FOR SUBSTITUTION REQUESTS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND STANDARDS AS REQUIRED BY THE BUILDING CODE. POST-INSTALLED ANCHORS IN CONCRETE SHALL BE SPECIFIED IN ACCORDANCE WITH ACI 318 APPENDIX D AND APPROPRIATE MANUFACTURER'S TABLES FOR ANCHOR PERFORMANCE VALUES AS DETERMINED FROM TESTING IN ACCORDANCE WITH ICC-ES ACCEPTANCE CRITERIA. CALCULATIONS FOR THE SELECTED ANCHOR SYSTEM SHALL BE PREPARED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER AND SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD. CALCULATIONS SHALL INCLUDE ANCHOR DIAMETER, EMBEDMENT DEPTH, ANCHOR MATERIAL, ADHESIVE MATERIAL (IF APPLICABLE), AND ANCHOR SYSTEM CAPACITY. AN ICC-ES-REPORT (ESR-XXXX) SHALL BE SUBMITTED THAT INDICATES ANCHORS HAVE BEEN DESIGNED AND TESTED FOR USE IN CRACKED CONCRETE. ALL ICC-APPROVED ANCHORS SHALL BE SUITABLE FOR SEISMIC AND WIND LOADS.
ROOF DECK SHALL BE FASTENED TO THE SUPPORTING STRUCTURE WITH #12 SELF-DRILLING SCREWS AT A 36/7 PATTERN. SIDE LAP CONNECTIONS SHALL BE MADE WITH #10 SELF-TAPPING SCREWS WITH FIVE SCREWS PER SPAN. FASTEN DISCONTINUOUS SIDE OF ROOF DECK TO SUPPORTING STRUCTURE WITH #12 SELF-DRILLING SCREWS, TWO PER DECK RIB, IN EACH DECK RIB. 4. 5. 6. WHERE 4 OR MORE SUPPORTS ARE PROVIDED, STEEL DECK SHALL SPAN CONTINUOUSLY OVER A MINIMUM OF 4 SUPPORTS (3-SPAN CONDITION), UNLESS OTHERWISE NOTED. ALL COMPOSITE STEEL FLOOR DECK IS DESIGNED AS UNSHORED CONSTRUCTION, UNLESS OTHERWISE NOTED. CONSTRUCTION JOINTS RUNNING PARALLEL TO BEAMS OR GIRDERS SHALL NOT COINCIDE WITH THE CENTER LINE OF THE BEAM OR GIRDER. CONSTRUCTION JOINTS RUNNING PERPENDICULAR TO BEAMS OR GIRDERS SHALL BE LOCATED AT APPROXIMATELY THE 1/3 POINT OF THE BEAM OR GIRDER SPAN. 14 GAGE RIDGE PLATES, VALLEY PLATES, AND MISCELLANEOUS METAL DECK ACCESSORIES SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR IN ACCORDANCE WITH THE DECK MANUFACTURER'S RECOMMENDATIONS. PERMANENT SUSPENDED LOADS SHALL NOT BE SUPPORTED BY STEEL ROOF DECK.
2. 3. 4. 5. 6.
7.
7.
8.
8.
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
9.
2. 3. 4. 5. 6. 7. 8.
10. MASONRY ANCHOR INSTALLATIONS ARE LIMITED TO ONE PER MASONRY CELL. 11. CONCRETE ANCHORS: A. MECHANICAL AND SCREW ANCHORS FOR USE IN CRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. B. ADHESIVE ANCHORS FOR USE IN CRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC308. C. GAS AND POWDER-ACTUATED FASTENERS FOR USE IN CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC70. 12. MASONRY ANCHORS: A. ANCHORAGE TO SOLID-GROUTED CONCRETE MASONRY: i. MECHANICAL AND SCREW ANCHORS FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC01 OR AC106, RESPECTIVELY. ii. ADHESIVE ANCHORS FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. B. ANCHORAGE TO HOLLOW CONCRETE MASONRY/UNREINFORCED CLAY BRICK MASONRY: i. SCREW ANCHORS FOR USE IN HOLLOW CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED IN ACCORDANCE WITH ICC-ES AC106. C. ADHESIVE ANCHORS WITH SCREEN TUBES SHALL BE TESTED AND QUALIFIED IN ACCORDANCE WITH ICC-ES AC58 OR AC60, AS APPROPRIATE. THE APPROPRIATE SCREEN TUBE SHALL BE USED AS RECOMMENDED BY THE ADHESIVE MANUFACTURER. D. ANCHORS SHALL BE CHOSEN TO RESIST MIN ALLOWABLE STRESS DESIGN (ASD) LOADS INDICATED ON DRAWINGS. ASD LOADS INDICATED TO NOT INCLUDE LOAD ADJUSTMENT FACTORS. 13. GAS AND POWDER-ACTUATED FASTENERS FOR USE IN CONCRETE, CMU, OR STEEL SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC70. NOTE: COORDINATE LOCATIONS OF WALL REINFORCEMENT WITH LOCATIONS OF POST-INSTALLED ANCHORS TO AVOID CONFLICT WHEN PLACING ANCHORS.
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
9.
10. CONNECTION REQUIREMENTS FOR COLD-FORMED MEMBERS ARE AS FOLLOWS, UNLESS OTHERWISE NOTED: CONDITION STUD-TO-TRACK TRACK TO STEEL BEAM CONNECTION (2) #10-16 SELF -DRILLING SCREWS WITH STUD SECURELY INTO TRACK 1/8" WELD EACH SIDE, 2" LONG SPACED AT 32" OC OR (2) 0.145" DIA POWDER ACTUATED FASTENERS AT 16" OC (2) 0.145" DIA POWDER ACTUATED FASTENERS THROUGH TRACK AT EACH STUD. PROVIDE 1 1/2" MINIMUM EMBEDMENT. MINIMUM SPACING = 4". CONCRETE EDGE DISTANCE = 3"
11. MAINTAIN 3/4" MINIMUM DISTANCE BETWEEN CENTERS OF CONNECTION SCREWS AND 3/4" MINIMUM DISTANCE FROM THE CENTER OF SCREW TO EDGE OF CONNECTED PART. INSTALL FASTENERS FROM THINNER THROUGH THICKER MATERIAL. 12. SUBMIT SHOP DRAWINGS TO THE DESIGN PROFESSIONAL FOR APPROVAL INDICATING ALL COLD-FORMED STEEL MEMBERS, CONNECTIONS, FASTENERS, OPENINGS AND OTHER COLD-FORMED STEEL RELATED ITEMS. 13. STUD MATERIAL INDICATED ON THE DRAWINGS SHALL HAVE A MINIMUM OF 1 5/8" FLANGES AND 1/2" STIFFENING RETURN LIPS. TRACK MATERIAL SHALL HAVE A MINIMUM OF 1 1/4" FLANGES (NO STIFFENING RETURN LIP). 14. MECHANICAL BRIDGING AT INTERVALS NOT EXCEEDING 4'-0" ON CENTER SHALL BRACE ALL LOAD-BEARING AND CURTAIN TYPE COLD-FORMED STEEL WALLS. BRIDGING SHALL BE IN PLACE PRIOR TO PLACING ANY LOADS ON THE STUD WALL. 15. CALCULATIONS FOR COLD-FORMED STEEL FRAMING ELEMENTS SHALL BE PREPARED AND SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE COMMONWEALTH OF PENNSYLVANIA AND SUBMITTED TO THE ENGINEER OF RECORD.
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:16:36 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt
Description
GENERAL NOTES
A
S-002
SHEET OF
3
SCHEDULE OF SPECIAL INSPECTION - MASONRY
5
SCHEDULE OF SPECIAL INSPECTION - SPRAYED FIRE-RESISTANT MATERIALS
ITEM
1. MATERIAL CERTIFICATIONS
QUALIFICATIONS
SI
SCOPE
- COLLECT MIX DESIGN FOR MORTAR - COLLECT MIX DESIGN FOR GROUT - CERTIFICATES OF COMPLIANCE FOR MASONRY CONSTITUENTS
ITEM
1. MATERIAL VERIFICATION AND QUALITY CONTROL
QUALIFICATIONS
SCSI SFSI S-EIT SE SI
SCOPE
- COLLECTING PRODUCT DATA ON SPRAY-APPLIED FIREPROOFING MATERIALS USED ONSITE AND VERIFYING THAT MATERIAL USED MATCHES APPROVED PRODUCT - COLLECTING ANY MATERIAL CERTIFICATIONS AND ACQUIRING ICC-ES FOR PRODUCT TO GUIDE SPECIAL INSPECTIONS
- VERIFY: PROPORTIONS OF SITE-PREPARED MORTAR - PERIODIC INSPECTION OF SITE PREPARED MORTAR AND BATCHING PROCEDURE 2. VERIFYING COMPLIANCE WITH APPROVED CONSTRUCTION DOCUMENTS SPRAY APPLIED FIREPROOFING MATERIALS SCSI SFSI SE - ENSURE THAT SUBSTRATES MATCH SURFACE PREPARATION AND CONDITION SPECIFIED BY FIREPROOFING MANUFACTURERS INSTRUCTIONS 100% VISUAL INSPECTION AND PERIODIC VERIFICATION OF SUBSTRATE TEMPERATURE - VERIFY THICKNESS AND DENSITY OF APPLICATION ON NOT LESS THAN 25% OF PROTECTED STRUCTURAL MEMBERS PER FLOOR, AND NO FEWER THAN 2 MEMBERS PER FLOOR. MEASUREMENTS SHALL BE MADE AT 9 LOCATIONS AROUND EACH BEAM AT EACH END OF A 12-INCH LENGTH. FOR APPLICATIONS <1 THICK, MINIMUM ALLOWABLE THICKNESS AT ANY POINT SHALL BE 25% LESS THAN SPECIFIED. FOR THICKNESSES OF 1 OR MORE, MINIMUM ALLOWABLE SHALL BE LESS THAN SPECIFIED. THICKNESS SHALL BE DETERMINED ACCORDING TO ASTM E605 - VERIFY BOND STRENGTH/ADHESION OF SPRAY-APPLIED FIREPROOFING (NOT LESS THAN 150 PSF) THROUGH PERIODIC PULLOFF TESTING, ACCORDING TO ASTM E 736. RATE OF TESTING SHALL BE ONE MEMBER PER 2500 SQUARE FEET OF SPRAYED AREA IN EACH STORY, BUT NOT LESS THAN ONE PER STORY - OBSERVING CONDITION OF FINISHED APPLICATION - PRIOR TO GROUTING, VERIFY LOCATION, SIZE, EXTENT, AND LAPS OF REINFORCEMENT IN WALLS, INCLUDING REINFORCEMENT AT CORNERS, INTERSECTIONS, EACH SIDE OF OPENINGS, ABOVE AND BELOW OPENINGS, AT WALL ENDS, AT CONTROL JOINTS, AND WITHIN BOND BEAMS - PRIOR TO GROUTING, VERIFY TYPE, SIZE, AND LOCATION OF ALL ANCHORS, EMBEDS, AND OTHER DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS, FRAMES, OR OTHER CONSTRUCTION - INSPECTOR SHALL TAKE NOTE OF ANY LOCATIONS WHERE REINFORCING STEEL PLACEMENT CONFLICTS WITH INSTALLATION OF OTHER ELEMENTS SHOWN ON DRAWINGS, AND REPORT THESE BEFORE GROUTING 3.INTUMESCENT AND MASTIC FIRE-RESISTANT COATINGS SCSI SFSI S-EIT SE
THE SPECIAL INSPECTOR SHALL KEEP RECORDS OF ALL INSPECTIONS, FURNISH INSPECTION REPORTS, AND IDENTIFY DISCREPANCIES AS DETAILED BY PROJECT SPECIFICATIONS AND RFP. A FINAL REPORT OF SPECIAL INSPECTIONS, DOCUMENTING THE COMPLETION OF ALL REQUIRED SPECIAL INSPECTIONS AND CONFIRMING THE CORRECTION OF ANY DISCREPANCIES, WILL BE SUBMITTED PRIOR TO ISSUANCE OF A CERTIFICATE OF USE AND OCCUPANCY. THE SPECIAL INSPECTIONS PROGRAM DOES NOT RELIEVE THE CONTRACTOR OF HIS OR HER RESPONSIBILITIES. JOB SITE SAFETY AND MEANS AND METHODS OF CONSTRUCTION ARE SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. SCHEDULE OF SPECIAL INSPECTION THE FOLLOWING SHEETS COMPRISE THE REQUIRED SCHEDULE OF SPECIAL INSPECTIONS FOR THIS PROJECT. THE CONSTRUCTION DIVISIONS WHICH REQUIRE SPECIAL INSPECTIONS FOR THIS PROJECT ARE AS FOLLOWS. SOILS SPECIAL FOUNDATIONS CAST-IN-PLACE CONCRETE STRUCTURAL LOAD BEARING PRECAST CONCRETE POST TENSIONED CONCRETE STRUCTURAL MASONRY WOOD SHEAR WALLS STRUCTURAL STEEL SEISMIC DESIGN CATEGORY: A BASIC WIND SPEED: 90 MPH WIND EXPOSURE CATEGORY: B QUALIFICATIONS OF INSPECTORS AND AGENTS OF SPECIAL INSPECTORS SITE RETAINING WALLS COLD-FORMED STEEL FRAMING WALL PANELS AND VENEERS SPRAYED FIRE-RESISTANT MATERIALS EXTERIOR INSULATION & FINISH SYSTEM (EIFS) PROGRESSIVE COLLAPSE BLAST RESISTANCE QUALITY ASSURANCE FOR PROGRESSIVE COLLAPSE POST-INSTALLED CONCRETE AND MASONRY ANCHORS
3. INSTALLATION OF MASONRY
- INSPECTION OF CONSTRUCTION OF MORTAR JOINTS, PRIOR TO BEGINNING MASONRY CONSTRUCTION - PERIODIC VERIFICATION OF MORTAR JOINT CONSTRUCTION PROCEDURES, SIZE, CONFIGURATION, AND TOOLING - VERIFICATION OF SIZE, LOCATION, AND EXTENT OF GROUTING OF STRUCTURAL ELEMENTS, INCLUDING BOND BEAMS, LINTELS, REINFORCED CELLS, BEAMS, HEADERS, CORNERS, INTERSECTIONS, AND CORBELS
4. REINFORCEMENT INSTALLATION
- PERIODIC INSPECTION OF JOINT REINFORCING IN MASONRY WALLS - PERIODIC INSPECTION OF LAP LENGTHS OF REINFORCING IN MASONRY WALLS
5. GROUTING OPERATIONS THE QUALIFICATIONS OF ALL PERSONNEL PERFORMING SPECIAL INSPECTION ACTIVITIES ARE SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL. THE CREDENTIALS OF ALL INSPECTORS SHALL BE PROVIDED IF REQUESTED. WHEN THE STRUCTURAL ENGINEER OF RECORD DEEMS IT APPROPRIATE THAT THE INDIVIDUAL PERFORMING A STIPULATED TEST OR INSPECTION HAVE A SPECIFIC CERTIFICATION OR LICENSE AS INDICATED BELOW, SUCH DESIGNATION WILL APPEAR ON THE SCHEDULE OF SPECIAL INSPECTIONS. THE SPECIAL INSPECTOR (SI) SHALL BE A LICENSED PROFESSIONAL ENGINEER WITH A MINIMUM OF 3 YEARS OF EXPERIENCE AS A SPECIAL INSPECTOR. 1. 2. SE GE S-EIT G-EIT G-TECH 1 G-TECH 2 C-TECH 1 C-TECH 2 S-TECH 1 STRUCTURAL ENGINEER: A LICENSED PE OR SE SPECIALIZING IN THE DESIGN OF BUILDING STRUCTURES. GEOTECHNICAL ENGINEER: A LICENSED PE SPECIALIZING IN SOIL MECHANICS AND FOUNDATIONS. STRUCTURAL ENGINEER-IN-TRAINING: A GRADUATE ENGINEER WHO HAS PASSED THE FUNDAMENTALS OF ENGINEERING EXAMINATION, WITH EXPERIENCE IN THE DESIGN OF BUILDING STRUCTURES AND WORKING UNDER THE SUPERVISION OF A LICENSED STRUCTURAL PE OR SE. GEOTECHNICAL ENGINEER-IN-TRAINING: A GRADUATE ENGINEER WHO HAS PASSED THE FUNDAMENTALS OF ENGINEERING EXAMINATION, WITH EXPERIENCE IN SOIL MECHANICS AND FOUNDATIONS AND WORKING UNDER THE SUPERVISION OF A LICENSED GEOTECHNICAL PE. GEOTECHNICAL TECHNICIAN 1: AN EXPERIENCED TECHNICIAN WITH NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET): LEVEL 2 SOILS CERTIFICATION. 8. WELDING REBAR 6. 7. 8. 9. GEOTECHNICAL TECHNICIAN 2: AN EXPERIENCED TECHNICIAN WITH NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET): LEVEL 2 GEOTECHNICAL ENGINEERING CERTIFICATION. CONCRETE TECHNICIAN 1: AN EXPERIENCED TECHNICIAN WITH AMERICAN CONCRETE INSTITUTE GRADE I CONCRETE FIELD TESTING TECHNICIAN OR GRADE I CONCRETE LABORATORY TESTING TECHNICIAN CERTIFICATION. CONCRETE TECHNICIAN 2: AN EXPERIENCED TECHNICIAN WITH AMERICAN CONCRETE INSTITUTE GRADE II CONCRETE LABORATORY TESTING TECHNICIAN OR ICBO REINFORCED CONCRETE SPECIAL INSPECTOR CERTIFICATION. STEEL TECHNICIAN 1: AN EXPERIENCED AMERICAN WELDING SOCIETY CERTIFIED ASSOCIATE WELDING INSPECTOR (CAWI) OR NON-DESTRUCTIVE TESTING TECHNICIAN ASNT-TC-1A LEVEL I. STEEL TECHNICIAN 2: AN EXPERIENCED AMERICAN WELDING SOCIETY CERTIFIED WELDING INSPECTOR (CWI) OR NON-DESTRUCTIVE TESTING TECHNICIAN ASNT-TC-1A LEVEL II OR ICBO CERTIFIED STRUCTURAL STEEL AND BOLTING SPECIAL INSPECTOR. STEEL TECHNICIAN 3: AN EXPERIENCED TECHNICIAN WHO IS AN AMERICAN WELDING SOCIETY CERTIFIED WELDING INSPECTOR (CWI) WITH A MINIMUM OF10 YEARS OF WELD INSPECTION EXPERIENCE OR A NON-DESTRUCTIVE TESTING TECHNICIAN ASNT-TC-1A LEVEL III OR ICBO CERTIFIED STRUCTURAL WELDING SPECIAL INSPECTOR. STRUCTURAL MASONRY SPECIAL INSPECTOR: AN EXPERIENCED MASONRY INSPECTOR WHO IS AN ICBO CERTIFIED STRUCTURAL MASONRY SPECIAL INSPECTOR. ICBO CERTIFIED SPRAY-APPLIED FIREPROOFING SPECIAL INSPECTOR. ICBO CERTIFIED PRESTRESSED CONCRETE SPECIAL INSPECTOR. CONCRETE TECHNICIAN WITH POST TENSIONING INSTITUTE LEVEL 2 CERTIFICATION. INSPECTION/TESTING COMPANY WITH FIRE PROTECTION ENGINEERING EXPERIENCE, MECHANICAL ENGINEERING EXPERIENCE, AND CERTIFICATION AS AIR BALANCERS. 7. OBSERVATION EVALUATION OF MASONRY STRENGTH 6. WEATHER PROTECTION
- PRIOR TO GROUTING, PERIODICALLY VERIFY CLEANLINESS OF GROUT SPACE - CONTINUOUS OBSERVATION OF THE PLACEMENT OF ALL GROUTING OF REINFORCED BUILDING WALLS, VERIFYING CORRECT EXTENT OF GROUTING - PERIODIC INSPECTION OF FULLY-GROUTED FOUNDATION WALLS AND WALL CAVITIES AT FOUNDATION, WHICH NEED NOT MEET REQUIREMENTS FOR CLEANLINESS OF GROUT SPACE
ITEM
1. MATERIAL VERIFICATION
QUALIFICATIONS
S-TECH 1 S-EIT SE SI S-TECH 1 S-EIT SE SI
SCOPE
- VERIFY AND RECORD PRODUCT DATA FOR 100% OF POST-INSTALLED ANCHORS, AND VERIFY THAT PRODUCT INSTALLED MATCHES APPROVED PRODUCT
3. 4. 5.
- PERIODICALLY VERIFY PROTECTION TECHNIQUES FOR MASONRY CONSTRUCTION BELOW 40F AND ABOVE 90F
- VERIFY DRILL BIT TO BE USED, HOLE DEPTH, PREPARATION, AND CLEANING ACCORDING TO MANUFACTURERS INSTRUCTIONS CONTAINED IN ICC-ES REPORT 100% OF ANCHORS - OBSERVE PROCEDURES USED IN ANCHOR INSTALLATION, CHECK AMBIENT TEMPERATURE AND SURFACE TEMPERATURE PERIODICALLY, VERIFY THAT ANCHORS ARE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS 100% OF ANCHORS
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
- CONTINUOUS OBSERVATION OF THE PREPARATION OF GROUT SPECIMENS, MORTAR SPECIMENS AND/OR PRISMS
3. ANCHOR TORQUE
S-TECH 1 S-EIT SE SI
- CONTINUOUS INSPECTION BY AWS-CWI OF REBAR WELDING, VERIFYING THAT WELDABLE REINFORCING IS USED AND APPROPRIATE PROCEDURES ARE FOLLOWED
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
ITEM
1. FABRICATOR CERTIFICATION/ QUALITY CONTROL PROCEDURES
QUALIFICATIONS
S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI
SCOPE
- ENSURE FABRICATOR IS AISC CERTIFIED PER CONTRACT DOCUMENTS TO SATISFY REQUIREMENTS OF IBC 1704.2.2 - COLLECT CERTIFICATE OF COMPLIANCE FROM FABRICATOR AT COMPLETION OF FABRICATION
12. SMSI 13. SFSI 14. PCSI 15. PTI 16. SCSI
2. WELDING
- COLLECT CERTIFICATE OF COMPLIANCE FOR WELD FILLER MATERIAL AND CONFIRM COMPLIANCE WITH CONTRACT DOCUMENTS - CONFIRM WELD FILLER MATERIAL IDENTIFICATION MARKINGS CONFORM TO AWS SPECIFICATION IN THE CONTRACT DOCUMENTS - CONTINUOUS VISUAL INSPECTION OF ALL COMPLETE AND PARTIAL PENETRATION WELDS - CONTINUOUS VISUAL INSPECTION OF ALL MULTIPLE PASS FILLET WELDS - CONTINUOUS VISUAL INSPECTION OF ALL SINGLE FILLET WELDS GREATER THAN 5/16"
C
SCHEDULE OF SPECIAL INSPECTION - SOILS (SPECIAL INSPECTION OF SOILS IS ONLY REQUIRED FOR SUBGRADE AND FILL PLACEMENT UNDER STRUCTURES REQUIRING SPECIAL INSPECTIONS.)
- PERIODIC (25% OF ALL) VISUAL INSPECTION OF FILLET WELDS 5/16 OR SMALLER - PERIODIC (25% OF ALL) VISUAL INSPECTION OF ROOF AND FLOOR DECK WELDS - PERIODIC (50% OF ALL) VISUAL INSPECTION OF WELDED REINFORCING STEEL
ITEM
1. SITE PREPARATION
QUALIFICATIONS
SI G-TECH S-EIT G-EIT GE SE
SCOPE
- PERIODIC INSPECTION OF TESTING OF FILL MATERIAL PLACEMENT INCLUDING PERIODIC OBSERVATION OF TESTING AGENCYS DENSITY TESTING METHODS AND FREQUENCY OF TESTING TO VERIFY COMPLIANCE WITH PROJECT SPECIFICATIONS/GEOTECHNICAL REPORT.
4. METAL DECK
- COLLECT MATERIAL DATA SHEETS FOR DECKING AND CONNECTORS OR FASTENERS - PERIODIC INSPECTION OF CONNECTIONS OF DECKING
5. BOLTING
- COLLECT MATERIAL DATA SHEETS FOR A325 AND A490 BOLTS, NUTS, AND WASHERS, AND CONFIRM COMPLIANCE WITH CONTRACT DOCUMENTS - COLLECT CERTIFICATE OF COMPLIANCE FROM BOLT SUPPLIER AT COMPLETION OF FABRICATION - PERIODIC (10% OF ALL) INSPECTION OF BOLTED CONNECTIONS TO CONFIRM BOLT MARKINGS CONFORM TO ASTM STANDARDS - PERIODIC (50% OF ALL) INSPECTION OF A325/A490 BOLTED (BEARING TYPE) CONNECTIONS - CONTINUOUS INSPECTION OF INSTALLATION OF A325/A490 BOLTED (SLIP CRITICAL) CONNECTIONS
ITEM
1. MIX DESIGN VERIFICATION
QUALIFICATIONS
SI C-TECH 1 C-TECH 2 S-EIT SE SI C-TECH 2 S-EIT SE
SCOPE
- COLLECT ACCEPTED MIX DESIGNS AND VERIFY APPROPRIATE MIX IS USED DURING SPECIFIC INSTALLATION
2.
REINFORCEMENT INSTALLATION
- PERIODIC INSPECTION OF REINFORCING STEEL AND WELDED WIRE FABRIC TO CONFIRM SIZE, SPACING, AND DETAILS CONFORM TO CONTRACT DOCUMENTS AT FOLLOWING FREQUENCY: - FOOTINGS AND FOUNDATIONS 50% OF ALL - FOUNDATION WALLS, BASEMENT WALLS, AND PEDESTALS 75% OF ALL - SLABS ON METAL DECK 50% OF ALL - COLUMNS AND SHEARWALLS 75% OF ALL - ELEVATED SLABS, JOISTS, AND BEAMS 75% OF ALL 6. MATERIAL CERTIFICATION S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI
- CONTINUOUS INSPECTION OF ALL PRE-TENSIONED BOLTS TO CONFIRM TENSIONING CONFORMS TO CONTRACT DOCUMENTS - COLLECT CERTIFIED MILL TEST REPORTS FOR ALL TYPES OF STRUCTURAL STEEL SPECIFIED IN THE CONTRACT DOCUMENTS AND CONFIRM COMPLIANCE WITH CONTRACT DOCUMENTS
3.
SI C-TECH 2 S-EIT SE
- CONTINUOUS INSPECTION OF CAST-IN-PLACE CONCRETE PLACEMENT - CONTINUOUS MONITORING OF SAMPLING OF FRESH CONCRETE, SLUMP TEST, AIR CONTENT TEST, TEMPERATURE OF CONCRETE, AND CREATION OF STRENGTH TEST SPECIMENS SCHEDULE OF SPECIAL INSPECTION SERVICES - SITE RETAINING WALLS
ITEM
SI C-TECH 2 S-EIT SE - PERIODIC INSPECTIONS OF CURING TECHNIQUES - PERIODIC INSPECTIONS OF COLD AND HOT WEATHER CONCRETING TECHNIQUES ALL SITE RETAINING WALLS RETAINING MORE THAN 5-0 OF EARTH REQUIRE SPECIAL INSPECTIONS. THIS INCLUDES FOOTINGS AND WALLS. SEE APPROPRIATE MATERIAL SPECIAL INSPECTION SCHEDULES FOR SPECIFIC REQUIREMENTS.
5.
SI C-TECH 2 S-EIT SE
- VERIFY WITH TESTING AGENCY REPORTS IN-SITU CONCRETE STRENGTH OF ELEVATED BEAMS AND SLABS PRIOR TO REMOVAL OF SHORINGS AND FORMS.
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
ITEM
1. PLANT CERTIFICATION/ QUALITY CONTROL PROCEDURES
QUALIFICATIONS
S-EIT SE SI
SCOPE
- ENSURE FABRICATOR IS AISI AND SSMA CERTIFIED PER CONTRACT DOCUMENTS TO SATISFY REQUIREMENTS OF IBC 1704.2.2 - COLLECT CERTIFICATE OF COMPLIANCE FROM FABRICATOR AT COMPLETION OF FABRICATION
2. MECHANICAL CONNECTIONS
A
3. FRAMING DETAILS
S-EIT SE SI S-EIT SE SI
- PERIODIC INSPECTION (50% OF ALL) OF FIELD CONNECTIONS INCLUDING ANCHORAGE TO THE STRUCTURAL FRAME
S-003
SHEET OF
- SITE STRIPPING AND SUBGRADE PREPARATION - FILL MATERIAL (ON-SITE AND/OR IMPORTED) CLASSIFICATION - FILL MATERIAL PLACEMENT (LIFT THICKNESS, MOISTURE CONTENT AND COMPACTION) - ALLOWABLE BEARING CAPACITY FOR FOOTINGS AND FOUNDATIONS
o 10% OF ALL BEAM-TO-BEAM CONNECTIONS o 25% OF ALL BEAM-TO-COLUMN CONNECTIONS o 50% OF ALL COLUMN SPLICE CONNECTIONS o 100% OF ALL CONNECTIONS OF MEMBERS WITHIN VERTICAL FRAMES
- COLLECT TESTING AGENCYS FIELD AND LABORATORY TEST REPORTS DURING SITE PREPARATION AND VERIFY THE FOLLOWING COMPLIES WITH THE PROJECT SPECIFICATIONS/GEOTECHNICAL REPORT:
3. STRUCTURAL DETAILS
- PERIODIC INSPECTION OF STEEL FRAMING JOINT DETAILS TO CONFIRM MEMBER SIZES AND CONNECTION DETAILS PER THE FOLLOWING:
SPECIAL INSPECTIONS
3
8" "B" BARS 1'-4" UON "C" BARS FINISHED GRADE (PAVING) SEE CIVIL 8" MIN [SEE CIVIL] FIN GRADE
PLAN NOTES
1. 2. 3. 4. NOTE: SITE WALLS ARE DESIGNED AS CANTILEVERED FOR FINAL BACKFILL CONDITIONS. CONTRACTOR TO ENSURE THAT BACKFILL IS EQUALIZED BELOW LOWER FINISHED GRADE ELEVATION ON EACH SIDE OF WALL BEFORE BACKFILLING REMAINING HEIGHT "H." MASONRY VENEER, SEE ARCH FINISHED GRADE SEE CIVIL ALL ELEVATIONS REFERENCED FROM GROUND FLOOR ELEVATION 1120-0 = [0-0]. TOP OF FOOTING ELEVATION SHALL BE [-1-4] UNLESS OTHERWISE NOTED. SPREAD FOOTINGS AND WALL FOOTINGS ARE NOTED ON PLAN AS FX.X AND WFX.X, RESPECTIVELY. SEE FOOTING SCHEDULES ON SFB501 FOR SIZE AND REINFORCING. SLAB ON GRADE SHALL BE 4 THICK REINFORCED WITH 6x6 W2.1xW2.1 WWF PLACED 1 1/2 BELOW TOP OF SLAB. PLACE SLAB ON 10 MIL VAPOR RETARDER OVER 6" OF COMPACTED PENNDOT 2A STONE. FOR TYPICAL FOUNDATION DETAILS, SEE SHEETS SB501 AND SB502. STEP FOOTINGS SO THAT UTILITIES PASS OVER TOP OF FOOTING AS PER TYPICAL DETAIL ON SHEET SB501. COORDINATE ALL FOOTING LOCATIONS WITH CIVIL, PLUMBING, AND ELECTRICAL DRAWINGS. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SAWED CONTROL JOINTS SPACED AT 15'-0" OC MAX WITH 1.5 MAX GRID ASPECT RATIO. JOINTS (SJ) MAY OPTIONALLY BE CONSTRUCTION JOINTS (CJ). SEE SHEETS SB501 AND SB502 FOR TYPICAL DETAILS. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501.
5. 8" "A" BARS, MOW 1'-4" "B" BARS, MOW FINISHED GRADE (PAVING) SEE CIVIL [SEE CIVIL] FIN GRADE 9. 7. 8. 6.
E
"B" BARS
30"
CLASS "B" LAP SPLICE, TYP SEE "TOP BAR TENSION REINFORCING" LAP SPLICE ON SB502
3'- 0"
10. SEE SHEETS SF201 AND SF202 FOR BRACED FRAME "BF-X' ELEVATIONS. 2x4 CONT KEYWAY B [SEE PLAN] TOF 1'-1" FTG LONGITUDINAL BARS 2x4 CONT KEYWAY GEOTEXTILE FILTER FABRIC WASHED STONE FILL T T EQ EQ [SEE PLAN] TOF #
KEY NOTES
DEPRESSED SLAB. SEE "TYPICAL SLAB ON GRADE DEPRESSION" ON SB502 SEE "TYPICAL THICKENED SLAB AT STAIR LANDING" ON SB502 SEE "TYPICAL THICKENED SLAB UNDER CMU WALL" ON SB502 HSS4x4x1/4 POST UNDER STAIR STRINGER BY STAIR ENGINEER. SEE "TYPICAL THICKENED SLAB AT STAIR LANDING" ON SB502 FOR SLAB THICKNESS AND REINFORCING OPENING IN SLAB FOR LINT TRAP, SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION GALVANIZED STEEL BAR GRATING WITH 1"x1/8" BEARING BARS AT 1 3/16" MAX SPACING AND 1/4" CROSS BARS AT 4" SPACING. SEPARATE BAR GRATING INTO FOUR REMOVABLE, EQUAL SECTIONS GALVANIZED STEEL LADDER IN MECHANICAL PIT, SEE ARCH FILL CAVITY BELOW GRADE WITH 3000 PSI CONCRETE, TYPICAL AT VESTIBULE
6" SLEEVE INVERT=[+6'-0"] 3" SLEEVE INVERT=[+8'-0"] 1 1/2" SLEEVE INVERT=[+7'-0"] 3" SLEEVE INVERT=[+7'-0"] 8" SLEEVE INVERT=[+7'-0"] 6" SLEEVE INVERT=[+6'-0"]
FTG TRANSVERSE BARS FTG LONGITUDINAL BARS W W 6" PERFORATED DRAIN PIPE
1 2 3 4
DOWELS WITH STD 90 HOOK TO MATCH SIZE AND SPACING OF VERT WALL REINFORCING
TYPE 2
5
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
7 8
#4 AT 10" OC #4 AT 10" OC
D1
PLAN DETAIL
NOT TO SCALE NOT TO SCALE
SW5
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
10
24'-3" 22'-11" [+5'-4"]
SW3
11
13'-6" 8'-3" 8'-10"
12
TOP OF CONCRETE WALL TO SLOPE 16" ABOVE TOP OF STAIR TREAD NOSING
1
24'-6" 18'-0"
2
14'-0" 11'-6"
SW3
3
9'-5"
3.9
4
1'-3" 16'-6"
5
8'-5" 2'-8" 2'-8"
6
8'-1" 14'-3" [ -6'-6" ]
7
16'-6" 2'-8" 2'-8" 2'-8" [ -4'-0" ] [ -5'-4" ] [ -2'-8" ] 7'-1"
8
1'-3"
8.1
9'-5"
9
14'-1"
[+6'-0"]
4'-0" SF SF
4'-0" SF
4'-0" SF SF
[+0'-8"]
SW2
10'-8" [+4'-0"]
[+2'-8"]
1'-0"
CW2
SF
A1 SB301
[-2'-0"]
CW2
4'-9" P1
[+ "] -0 6'
P1
P1
P1
F6.5
P1
1"
A
8'-4" 1'-4" SF
2'-0"
A.1
2'-6"
SJ CW3 F9.5 5
WF4.0
3'-0"
1'-4"
1'-0"
P5
A6
[ -2'-0" ] SF D1 SB302
[ -1'4" ]
[+ "] -0 6'
[+
"] -0 6'
SW3
1"
4'-8"
6'-0"
SF 4'-0" [+8'-0"] SF
13'-10"
4'-0"
[ +6'-0" ] 1"
[+ "] -0 6'
9'-10"
SJ, TYP 6" 10" WF4.0 F6.0 P7 F6.0 WF4.0 MW3 TS 8" CONCRETE SHEARWALL 6" F5.5 SJ, TYP F5.5 4" SOG SJ, TYP F5.0
4'-0"
2'-6 1/2"
7'-6"
6'-0"
SW2
4'-0"
4'-8"
D2 SB302
[0'-0"]
4'-0"
14'-6"
P3 F4.0
6' -0 "]
1"
8'-4"
SJ, TYP
D.9
1'-4" 10'-11"
F4.0
MW3 WF4.0
SF
1'-0"
[ -1'-4" ]
8'-8"
[ -4'-0" ]
CW2 4'-0"
SB301 P1
SF [ -4'-0" ]
16'-0"
1'-0"
2'-2"
[ -2'-8" ]
[ -2'-8" ]
TS
TS
MW4
WF4.0
2'-8"
D4 SB302
F5.5 TS
F5.5
TS
P6
BF-8
2"
WF4.0
H
7'-0" 13'-4"
7'-6"
2"
MW2
1'-4 1/8"
1'-0"
6'-0"
TOC
8"
SF [ -1'-4" ]
MW1
8'-8"
MW2
F9.5 SJ
[+0'-6"]
1'-9"
2'-5 1/2"
1"
MW1
2"
F4.5
F4.0
[ -1 '-4
"]
SF [-2'-8"]
18'-0"
SJ, TYP
8'-4"
1'-0"
P1 1'-4"
A3
SW3
MW3
WF3.0
"] -0 ' -4
1'-8" F4.0
1'-9"
] '-8" [ -2
[ -2 '-8
7'-8"
8'-10"
[ -4'-0" ] SF
F9.5
F3.0
[- 2 '-8 "
1'-4"
1"
TS
F4.0
5"
2"
1'-0"
8'-8"
TS
TS
SW1
SF
SF
SF
A1
8'-2 1/2"
1'-9 1/2"
10'-8"
2'-8"
SF
[-1'-4"]
SF
F3.0
2'-0 1/4"
[ -2'-8" ]
2'-2"
P1
1'-4" TYP
F4.0
F4.5 WF3.0
F4.5
[-
17'-2"
D
SW2
SF
[+
CW1
BF-C
4"
1'-0"
"] -0 6' [+
2'-0"
E
2 WF3.0
SF
]
SB301
F F.1
"]
[-3'-8"]
6'-0"
WF2.0
SW3
3'-6"
MW2
WF4.0
1' -4 "]
11'-3"
6"
1' -4
CW1
[-
3
"]
4'-0" 4'-0"
P2 F8.0
4"
2'-0" TYP.
H CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW J
8'-4"
F6.0
BF-H D2 SB302
[
[-
EJ
H.5
1'-8" 4'-8" F6.5 BF-1 SJ, TYP 4" SOG
SB301 1'-9"
A5 SB301
1"
F4.5
6'-0"
SJ, TYP
E5
1'-0"
SW3
[-2'-8"]
13'-10"
16'-6"
WF2.0
[] 4" 1'-
17'-0"
11'-1"
10'-11"
REVISIONS
No. Date Description
F4.0
"]
SW2
1'-0"
2'-0"
2'-0"
WF3.0
WF3.0
WF3.0
1'-0"
F5.0
F5.0
F5.0
F6.0
1'-9"
F3.0 P3 DN
SF
SW2
[-
1' -4
J.9
1'-4"
1'-0"
K
F5.5 [ -1'-4" ] [ -1'-4" ] 1'-0" 3'-0"
SW2 [-4'-8"] TOP OF CONCRETE WALL TO SLOPE 16" ABOVE TOP OF STAIR TREAD NOSING 9'-8" 6'-11 1/2" STAIR TREADS, SEE ARCH, TYP N 7'-5"
FOUNDATION PLAN
SW2
1'-0" 10'-10"
A3 11'-2" SB301
10'-0 1/2"
FOUNDATION PLAN
1/8" = 1'-0"
GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'
SB101
SHEET OF
4'-0"
WF2.0
CW4 F6.5
3'-6"
F3.0
40'-2"
SB301 F3.0
BF-12
WF4.0
WF2.0 F4.0x3.0 P4 A5
8'-1"
23'-6"
[+9'-4"]
"] -0 6' [+
2'-0"
F9.5
" -0 5' []
2
3
4
3.9
SEE PLAN
STEEL COLUMN, SEE PLAN #4 CONT. FILL CAVITY BELOW GRADE WITH 3000 PSI CONCRETE MASONRY VENEER, TYP, SEE ARCH STEEL COLUMN, SEE PLAN CFS STUD WALL, SEE ARCH CONCRETE SLAB-ON-GRADE TOC [SEE PLAN] PENNDOT 2A STONE FILL FILL CAVITY BELOW GRADE WITH 3000 PSI CONCRETE 1'-0" 4" JOINT SEALANT 1/2" PREMOLDED JOINT FILLER 3/4" WWF
1 1 3'-0" #5 AT 32" OC WITH STD 90 DEG HOOK 8" PENNDOT 2-A BASE COURSE VAPOR RETARDER, TYP.
8" CMU GROUT SOLID BELOW GRADE #5 VERT AT 32" OC SEE CONCRETE PIER SCHEDULE FOR REINFORCEMENT L5x3x1/4 (LLV) CONT WITH 3/4"x3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX
E5
SECTION
3/4" = 1'-0"
36 REINFORCING IN STEM WALL NOT SHOWN FOR CLARITY. SEE A5/SB301 FOR REINFORCING
3.9
SEE PLAN
COLUMN PER PLAN FILL CAVITY BELOW GRADE WITH 3000 PSI CONC TOC [SEE PLAN]
DOWELS WITH STD 90 HOOK TO MATCH VERT CMU REINF SIZE AND SPACING
3" CLR
3" CLR
SEE CONCRETE PIER SCHEDULE FOR REINFORCING (4) #4 DOWELS WITH STD 90 HOOK
1'-0"
2x4 KEYWAY, CONT PENNDOT 2-A STONE FILL 2x4 CONT KEY
L5x3x1/4 (LLV) CONT WITH 3/4" x 3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX ROUGHEN SURFACE TO 1/4" AMPLITUDE
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
SLAB AND DECK PER PLAN L5x3x1/4 (LLV) CONT WITH 3/4" x 3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX FACE OF CONC WALL BEYOND SEE CONC PIER SCHEDULE FOR REINF RETAINING WALL, SEE A1/SB301 FOR REINFORCING FOOTING SHALL BEAR ON BEDROCK ALONG COLUMN LINE 3 SEE FOOTING SCHEDULES OF SB501 FOR REINFORCING. FTG REINF NOT SHOWN FOR CLARITY FACE OF BEDROCK
D5
RETAINING WALL. SEE A1/SB501 FOR REINFORCING
SECTION
3/4" = 1'-0"
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
C1
SECTION
3/4" = 1'-0" #4 CONT MASONRY VENEER, SEE ARCH GROUT SOLID BELOW GRADE
C3
SECTION
3/4" = 1'-0" #4x3'-0" WITH STANDARD HOOK AT TOP AT 12" OC # 4 CONT ROUGHEN SURFACE TO 1/4" AMPLITUDE 1'-4" 2'-6"
L5x3x1/4 (LLV) GALV CONT WITH 3/4" x 3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX 1'-0" TYP
2x4 CONT KEY TOP AND BOTTOM, TYP REMOVABLE GALVANIZED STEEL BAR GRATING, SEE PLAN
1-#4 CONT ALL AROUND #4 AT 12" OC, TYP CONCRETE SLAB-ON-GRADE, TYP TOC [SEE PLAN]
MASONRY VENEER, SEE ARCH RIGID INSULATION, SEE ARCH ROUGHEN SURFACE TO 1/4" AMPLITUDE GROUT SOLID BELOW GRADE TOP OF SLAB [SEE PLAN] FINISHED GRADE [SEE CIVIL] 8" MIN 3" 4" EOS 2'-6"
L5x3x1/4 (LLV) CONT WITH 3/4" DIA x 3" EMBED HEAVY SCREW ANCHORS AT EA FRAME, 24" OC MAX #4 HOOKED BAR AT 12" OC, BEND DOWN AFTER PLACING DECK
VAPOR RETARDER, TYP CONT SELF-EXPANDING WATERSTOP AT TOP AND BOTTOM OF WALL DAMP PROOFING SEE ARCH
8" MIN
#4 BAR WITH STD 90 HOOK AT 12" OC L5x3x1/4 (LLV) CONT WITH 5/8" DIA x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC 1'-10" TYP LAP (2) #4 CONT
#4 AT 12" OC EACH WAY EACH FACE, TYP SUMP, SEE PLAN 1'-0" SLUMP TO SUMP DOWELS TO MATCH SIZE AND SPACING OF VERT WALL REINF CONTINUOUS SELF-EXPANDING WATERSTOP AT TOP AND BOTTOM OF WALL, TYP TOF [SEE PLAN]
1'-5"
TOPSOIL, SEE CIVIL PENNDOT 2A FILL FILTER FABRIC, DRAINAGE BOARD, AND PROTECTION BOARD BACKFILL FOW
L3x3x1/4 AT 24" OC 2'-0" 1/4 1/4 4" 8" CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF 1 1 L3x3x1/4 x 10" WITH (2) 5/8" DIA WEDGE-TYPE EXPANSION ANCHORS TYP EA END
1'-0"
1/4 1/4
3 3
1'-0"
1'-0"
4" 1'-10" TYP CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF
B1
SECTION
3/4" = 1'-0" 1'-0" FACE OF BEDROCK 1'-4"
B2
SECTION
3/4" = 1'-0"
B5
SECTION
3/4" = 1'-0"
B
PENNDOT 2A STONE FILL PROTECTION BOARD, SEE ARCH FILTER FABRIC AND DRAINAGE BOARD, SEE ARCH CLASS "B" LAP SPLICE, TYP. SEE "TOP BAR TENSION REINFORCING" LAP SPLICE ON SB502
2'- 5"
SEE "TYPICAL CONTROL JOINT AT RETAINING WALL" ON SB501 FOR LOCATING CONTROL JOINTS ALONG WALL SEE WALL REINFORCING SCHEDULE ON SF601 FOR WALL REINFORCING #4 CONT 1/2" JOINT FILLER MATERIAL SEE PLAN #4 BAR AT 12" OC CONC SLAB ON GRADE COLD-FORMED STEEL FRAMING, SEE ARCH DWGS 4" TOC [SEE PLAN] STOREFRONT, SEE ARCH 1 #4 CONT MASONRY VENEER, SEE ARCH GRADE VARIES TOC
3/ 4 "
POCKET BEAM INTO WALL. WIDTH OF POCKET SHALL BE 4 1/4" (1/8" GAP ON EA SIDE OF BEAM FLANGE). DO NOT GROUT SOLID REMOVABLE GALVANIZED STEEL BAR GRATING, SEE PLAN TOS [SEE PLAN]
0" 0"
1/ 2 "
TOC [SEE PLAN] #4 CONTINUOUS DOWELS TO MATCH SIZE AND SPACING OF VERT WALL REINF WITH STD 90 HOOK 3" CLR GROUT SOLID BELOW GRADE
CONCRETE TURNED-DOWN SLAB #5 @ 32" OC WITH 6" HOOK PERIMETER INSULATION, SEE ARCH DRAWINGS VAPOR RETARDER 8" 3'-0" 3/4" CLR [SEE PLAN] 8" MIN DAMP PROOFING SEE ARCH 8" CONCRETE STEM WALL 6" CMU, GROUT SOLID BELOW GRADE #4 HORIZ AT 12" OC EQ EQ 1
3'-0" VAPOR RETARDER CONT SELF-EXPANDING WATERSTOP DAMP PROOFING, SEE ARCH 2x4 CONT KEY
CONCRETE TURNED-DOWN SLAB SEE PLAN #5 x 3'-0" @ 32" OC WITH 6" HOOK 3/4"
GALV STEEL BEAM TO BE REMOVABLE FOR ACCESS TO EQUIPMENT IN PIT, SEE PLAN
8"
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
1'-2"
8" STEM WALL BELOW GRADE STD 90 HOOK, EACH END REINFORCING, SEE SCHEDULE DAMP PROOFING SEE ARCH
VAPOR RETARDER 1 PERIMETER INSULATION, SEE ARCH DRAWINGS ROUGHEN SURFACE TO 1/4" AMPLITUDE #4 VERT AT 18" OC WITH STD 90 HOOK TOF [SEE PLAN] 0"
5/ 8 "
A6
SECTION
3/4" = 1'-0"
2x4 CONT KEYWAY, TYP GROUT SOLID IN 2" x 16" MIN DEEP CORES IN BEDROCK
SURFACE OF BEDROCK
8" EQ
1'-4" EQ
2x4 CONT KEYWAY, TYP TOF [SEE PLAN] GEOTEXTILE FILTER FABRIC WASHED STONE FILL 6" PERFORATED DRAIN PIPE
NOTE: 1. ANCHORS SHALL BE DESIGNED FOR 18 KIP SHEAR LOAD PARALLEL TO ROCK SURFACE AND 10 KIP TENSION LOAD. LOADS ARE SERVICE-LEVEL.
0"
2x4 CONT KEYWAY CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING
9/ 1 6"
CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING #4 VERT AT 18" OC WITH STD 90 HOOK, EF
A1
A3
A5
GRAPHIC SCALE(S)
0 3/4" = 1' - 0" 6" 1' 2' 3' 4' 5'
SB301
SHEET OF
24" 24"
FOUNDATION SECTIONS
8" CONC WALL, SEE PLAN CONC WALL, SEE PLAN DOWELS TO MATCH SIZE AND SPACING OF VERTICAL WALL REINF. W/ STD 90 HOOK SLAB ON GRADE, SEE PLAN VAPOR RETARDER TOC [SEE PLAN]
2'- 167/ 2 56"
SEE PLAN 48"xBAR MIN LAP 8" MASONRY VENEER, SEE ARCH DRAWINGS SLAB ON GRADE, SEE PLAN GROUT SOLID BELOW GRADE
1'- 1015/ 256"
SEE PLAN
CMU WALL, SEE PLAN #4, CONT #5 @ 32" OC WITH STD 90 HOOK SLAB ON GRADE, SEE PLAN VAPOR RETARDER TOC [SEE PLAN] 1
MASONRY VENEER, SEE ARCH RIGID INSULATION, SEE ARCH ROUGHEN SURFACE TO 1/4" AMPLITUDE GROUT SOLID BELOW GRADE 4" EOS
#4 CONT
CLASS "B" LAP SPLICE. SEE TENSION REINF. LAP SPLICE ON SB502 2x4 CONT KEYWAY, TYP
#4 HOOKED BAR AT 12" OC, BEND DOWN AFTER PLACING DECK SLAB ON DECK, SEE PLAN 2'-6" TOP OF SLAB [SEE PLAN]
VAPOR RETARDER 4" SOLID CMU TOC [SEE PLAN] GRADE VARIES
4" SOLID CMU EQ EQ TOF [SEE PLAN] GEOTEXTILE FILTER FABRIC PERIMETER INSULATION, SEE ARCH DRAWINGS CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING 2x4 CONT KEYWAY, TYP DOWELS TO MATCH SIZE AND SPACING OF VERTICAL WALL REINF. W/ STD 90 HOOK CONCRETE FOOTING, SEE SCHEDULE ON SHEET SB501 FOR SIZE AND REINFORCING 6" PERFORATED DRAIN PIPE 2x4 CONT KEYWAY, TYP #4 VERT AT 18" OC WITH STD 90 HOOK EQ EQ TOF [SEE PLAN] GEOTEXTILE FILTER FABRIC DOWELS TO MATCH SIZE AND SPACING OF VERTICAL WALL REINF. W/ STD 90 HOOK 1 PERIMETER INSULATION, SEE ARCH DRAWINGS TOF [SEE PLAN] ROUGHEN SURFACE TO 1/4" AMPLITUDE #4 HORIZ AT @ 6" OC, MOW WASHED STONE FILL CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING
EQ
EQ
8" MIN
L5x3x1/4 (LLV) CONT WITH 5/8" DIA x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC MAX
D1
D
SECTION
3/4" = 1'-0"
D2
SECTION
3/4" = 1'-0"
D4
SECTION
3/4" = 1'-0"
D5
SECTION
3/4" = 1'-0"
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
#4 CONT ROUGHEN SURFACE TO 1/4" AMPLITUDE PAVING OR FINISHED GRADE, SEE CIVIL DWGS SLAB ON DECK, SEE PLAN #4 AT 12" OC TOP OF SLAB [SEE PLAN] FILTER FABRIC, DRAINAGE BOARD, AND PROTECTION BOARD, SEE ARCH 2'-0" 5 1/2" 1 1/4" CURTAIN WALL, SEE ARCH #4 CONT ROUGHEN SURFACE TO 1/4" AMPLITUDE #5 AT 12" OC TOP OF SLAB [SEE PLAN]
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
1'-0"
4"
2'-0"
NOTE: SEE PLAN VIEW OF "TYPICAL SLAB AT EXTERIOR OPENING" ON SB502 FOR SLAB REINF.
2'-6"
L5x3x1/4 (LLV) CONT WITH 5/8" DIA x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC MAX FILTER FABRIC, DRAINAGE BOARD, AND DAMPPROOFING, TYP 1'-4" CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF
L5x5x1/4 (LLV) CONT WITH 3/4" x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC MAX
C1
C
SECTION
3/4" = 1'-0"
C2
SECTION
3/4" = 1'-0"
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:16:49 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt
Description
SB302
SHEET OF
FOUNDATION SECTIONS
1
SLAB OR WALL REINFORCING, SEE PLAN OR SCHEDULE
YP
2
3" OC SPACING BETWEEN BARS, TYP
"T -0 2'
MASONRY VENEER, SEE ARCH TOP OF SLAB [SEE PLAN] TOS DECK NOT SHOWN FOR CLARITY 1/4" FULL DEPTH STIFFENERS
2'-0" TYP
[SEE PLAN]
LEVELING NUT AND WASHER, TYP 12" LONG CORBEL STEEL BEAM, SEE PLAN 1-#5 EACH FACE FOR WALLS, 2-#5 MID-DEPTH FOR SLABS AT EACH SIDE OF SLAB OR WALL OPENING ADD 1/2 OF REINFORCING INTERRUPTED BY OPENING [+9'-10"] UON 10" TOC (2) #4x8" LONG, EA END
ADDED REINFORCING AT OPENINGS IN CONCRETE SLAB OR WALL WHERE MAIN REINFORCING IS NOT INTERRUPTED
2' -0 "
ADDED REINFORCING AT OPENINGS IN CONCRETE SLAB OR WALL WHERE MAIN REINFORCING IS INTERRUPTED
NOTES: 1. COORDINATE OPENING SIZE AND LOCATION WITH MECHANICAL DWGS. 2. NO SPECIAL REINFORCING REQUIRED FOR OPENINGS 4" OR LESS.
SEE SHEET SF601 FOR BASE PLATE AND ANCHOR ROD DETAILS
ASTM A706 #3 AT 6" OC (2 TOTAL) WITH 180 HOOK AT END, WELD TO ANCHOR BAR ASTM A706 #4 ANCHOR BAR AT 6" OC
ASTM A706 #4 AT 6" OC (2 TOTAL) WELDED TO ANCHOR BAR AT EDGE OF SHELF 20" 8" 20" 1'-6" TYP
1'-6" TYP
8"
PLAN AT CORNER
1'-6" TYP 1'-6" TYP
D
SJ OR CJ
P TY
16" MIN FOR 8" STEP 32" MIN FOR 16" STEP
-
MASONRY VENEER, SEE ARCH 3" CLR TYP 0" 36 BAR DIAMETER LAP, TYP MATCH SIZE AND SPACING OF FOOTING TOP BAR REINFORCING NUT AND WASHER
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
SJ OR CJ
M 8"
,T IN
YP
M 8"
,T IN
YP J C
M 8"
, IN
STEEL BEAM, SEE PLAN 'A' BARS NOTES: GROUT POCKET SOLID 1 2 1 2 CONTINUOUS WALL FOOTING REINFORCING, SEE SCHEDULE ON THIS SHEET 12" MIN CONTINUOUS WALL FOOTING REINFORCING LEVELING NUT AND WASHER, TYP 8" CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF 2" 'B' BARS 3/4" x 4" STEEL BEARING PLATE EXTENDING MIN 3" EA SIDE OF BEAM BOTTOM FLANGE 1" NON-SHRINK GROUT (2) 3/4" DIA ANCHOR RODS WITH 9" MIN EMBED AND HEAVY HEX NUT AT BOTTOM 1. WHERE THREE BARS OCCUR, CENTER BAR SHALL BE TREATED AS AN INNER FACE BAR. 2. 'B' AND 'D' BARS NOT SHOWN FOR CLARITY.
EOS
SJ OR CJ
C
J C
SJ OR CJ
J
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
C J
EOS
EOS
SJ OR CJ
CORNER
1 13 / 25 6"
36 BAR
#4 AT 12" OC
IN "M 6 ' 1
2" CLR 24 BAR 12" MIN 24 BAR 12" MIN CORNER DOWELS SAME SIZE AND NUMBER AS HORIZONTAL WALL REINFORCING DOWELS SAME SIZE AND NUMBER AS HORIZONTAL WALL REINFORCING KEY CUT EVERY OTHER HORIZONTAL BAR AT JOINT
" 1'-6
N MI
8"
8"
8"
NOTES: 1. PROVIDE JOINTS AT 25'-0" OC ALONG WALL. 2. PROVIDE JOINTS 12'-0" FROM WALL CORNERS. 3/4" CHAMFER ON EACH FACE OF WALL
EXTERIOR FACE
PLAN AT CORNER
PLAN AT INTERSECTION
MARK
F3.0 F4.0 F4.0x3.0 F4.5 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5
W
3'-0" 4'-0" 3'-0" 4'-6" 5'-0" 5'-6" 6'-0" 6'-6" 8'-0" 9'-6"
FOOTING SCHEDULE - COLUMN DIMENSIONS REINFORCING L T 'A' BARS 'B' BARS 'C' BARS
3'-0" 4'-0" 4'-0" 4'-6" 5'-0" 5'-6" 6'-0" 6'-6" 8'-0" 9'-6" 1'-4" 1'-4" 1'-4" 1'-4" 1'-6" 1'-10" 1'-10" 1'-10" 1'-10" 1'-10" (5) #5 (7) #5 (5) #5 (8) #5 (7) #6 (7) #7 (8) #7 (8) #7 (10) #7 (12) #7 (5) #5 (7) #5 (7) #5 (8) #5 (7) #6 (7) #7 (8) #7 (8) #7 (10) #7 (12) #7 (8) #7 (12) #7
MARK
P1
DIMENSIONS W D
2' - 0" 1' - 5" 1' - 4" 1' - 4" 2' - 0" 2' - 8" 2' - 0" 2' - 0" 1' - 10" 1' - 4" 2' - 6" 2' - 6" 5' - 8" 2' - 6"
NOTES
TYPE 1 TYPE 1 TYPE 1 TYPE 2 TYPE 1 TYPE 3 TYPE 2
'D' BARS
(8) #7 (12) #7 P2 PRE-MOLDED JOINT FILLER AROUND COLUMN CONCRETE INFILL, SEE PLAN DETAILS ON THIS SHEET SEE TYPICAL ANCHOR ROD AND BASE PLATE DETAIL ON SF601 3" MIN CONCRETE SLAB-ON-GRADE T SEE PLAN TOC [SEE PLAN] P3 CL COLUMN AND FOOTING, UNLESS OTHERWISE NOTED CONSTRUCTION JOINT, TYP P4 P5 P6 P7
TOF [SEE PLAN] CONCRETE FOOTING, SEE SCHEDULE ON THIS SHEET FOR SIZE AND REINFORCING
MARK
WF2.0 WF3.0 WF4.0
FOOTING SCHEDULE - WALL DIMENSIONS REINFORCING W T 'A' BARS 'B' BARS 'C' BARS
2'-0" 3'-0" 4'-0" 1'-0" 1'-4" 1'-6" (2) #5 CONT (4) #5 CONT (4) #6 CONT #5 @ 11" OC #5 @ 7" OC #6 @ 9" OC (2) #6 CONT
NOTE: PROVIDE TYPICAL CONTINUOUS HORIZONTAL WALL REINFORCING THROUGH CONCRETE PIERS.
'D' BARS
#6 @ 18" OC PENNDOT 2A BASE COURSE VAPOR RETARDER #4 TIES AT 3" OC 2" TOP OF PIER [SEE SCHEDULE] D D CONCRETE PIER, SEE SCHEDULE ON THIS SHEET FOR SIZE AND REINFORCING CONCRETE FOOTING, SEE SCHEDULE ON THIS SHEET FOR SIZE AND REINFORCING TOF 0" TYP [SEE PLAN] 1 1/2" CLR 1 1/2" CLR PROVIDE STD 90 HOOK AT TOP OF FOUR CORNER BARS 2" CLR D
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
'B' AND 'D' BARS SEE PLAN COLUMN, WALL SIMILAR 'C' BARS T 'D' BARS L WALL (CONT) 'B' AND 'D' BARS
T/3
T/3
'A' BARS BOTTOM (AND TOP) REINFORCING CONTINUOUS THRU JOINT 4" 4" TIE BAR EACH SIDE OF CONSTRUCTION JOINT W
'B' BARS
W W
11/ 1 6"
2"
T/3
SECTION SECTION
PLAN AT COLUMN
PLAN AT WALL
PIER TYPE 1
PIER TYPE 2
SB501
SHEET OF
NOTE: WHERE THREE BARS OCCUR, CENTER BAR SHALL BE TREATED AS AN INNER FACE BAR
2-#5 CONT
C J C J
PLAN AT INTERSECTION
EDGE
INTERIOR
'Z' BARS SAME SIZE AND NUMBER AS CONTINUOUS FOOTING REINFORCING, BEND AS SHOWN
6" N MI
3
DEVELOPMENT LENGTH CONCRETE f'c SIZE #3 #4 #5 #6 #7 3000 PSI 17" 22" 28" 33" 48" 55" 62" 70" 78" 93" 124" 4000 PSI 15" 19" 24" 29" 42" 48" 54" 61" 67" 81" 107" 5000 PSI 13" 17" 22" 26" 37" 43" 48" 54" 60" 72" 96" #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 SIZE 17" 22" 28" 33" 48" 55" 62" 70" 78" 93" 124" 3000 PSI CLASS A CLASS B 22" 29" 36" 43" 63" 72" 81" 91" 101" 121" 161" Ld LAP SPLICE
4
Ls DEVELOPMENT LENGTH CONCRETE f'c 4000 PSI CLASS A 15" 19" 24" 29" 42" 48" 54" 61" 67" 81" 107" CLASS B 19" 25" 31" 37" 54" 62" 70" 79" 87" 105" 140" 13" 17" 22" 26" 37" 43" 48" 54" 60" 72" 96" CONCRETE f'c 5000 PSI CLASS A CLASS B 17" 22" 28" 33" 49" 55" 63" 70" 78" 94" 125" SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 3000 PSI 22" 29" 36" 43" 63" 72" 81" 91" 101" 121" 161" 4000 PSI 19" 25" 31" 37" 54" 62" 70" 79" 87" 105" 140" Ld
5
Ls LAP SPLICE CONCRETE f'c 4000 PSI CLASS A 19" 25" 31" 37" 54" 62" 70" 79" 87" 105" 140" CLASS B 24" 32" 40" 48" 71" 81" 91" 102" 113" 136" 181" 17" 22" 28" 33" 49" 55" 63" 70" 78" 94" 125"
5000 PSI 17" 22" 28" 33" 49" 55" 63" 70" 78" 94" 125"
SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 22" 29" 36" 43" 63" 72" 81" 91"
3000 PSI CLASS A CLASS B 28" 37" 47" 56" 81" 93" 105" 118" 131" 157" 209"
2-#5 CONT
1 1/2" UON
SIZE
SEE PLAN TOC [SEE PLAN]
STANDARD HOOKS STIRRUPS 90 180 AND TIES L L L=12 d b L=4 d b L=6 d b /12 d b 2 1/2" 2 1/2" 2 1/2" 2 1/2" 3" 3 1/2" 4" 4 1/2" 5" 5 1/2" 7" 9" 3" 4" 9" 10 1/2" 12" N/A N/A N/A N/A N/A
Ldh 90 CONCRETE f'c 4000 PSI 6" 7" 9" 11" 12" 14" 16" 18" 19" 24" 31" 180
Ldh DEVELOPMENT LENGTH CONCRETE f'c 5000 PSI 5" 7" 8" 10" 11" 12" 14" 16" 17" 21" 28" SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 3000 PSI 9" 11" 14" 17" 20" 22" 25" 28" 31" 37" 50" 4000 PSI 8" 10" 12" 14" 17" 19" 22" 24" 27" 33" 43"
Ls 30db
1. 2.
DESIGN METHOD IS BASED ON ACI 318-08. TOP BAR IS WHERE HORIZONTAL REINFORCING IS PLACED SUCH THAT MORE THAN 12 INCHES OF FRESH CONCRETE IS CAST BELOW THE DEVELOPMENT LENGTH OR SPLICE. BOTTOM BAR IS WHERE HORIZONTAL REINFORCING IS PLACED SUCH THAT LESS THAN 12 INCHES OF FRESH CONCRETE IS CAST BELOW THE DEVELOPMENT LENGTH OR SPLICE. LAP SPLICES OF DEFORMED BARS AND DEFORMED WIRE IN TENSION SHALL BE CLASS B SPLICES EXCEPT THAT CLASS A SPLICES ARE ALLOWED WHEN: A. THE AREA OF REINFORCEMENT PROVIDED IS AT LEAST TWICE THAT REQUIRED BY ANALYSIS OVER THE ENTIRE LENGTH OF THE SPLICE. TWICE THE AREA OF REQUIRED REINFORCING CANNOT BE ASSUMED UNLESS SPECIFICALLY INDICATED OTHERWISE ON THE DRAWINGS; AND ONE-HALF OR LESS OF THE TOTAL REINFORCING IS SPLICED WITHIN THE REQUIRED LAP LENGTH.
3000 PSI 7" 8" 10" 12" 14" 16" 18" 20" 22" 27" 35"
5000 PSI 7" 9" 12" 14" 16" 18" 21" 23" 26" 31" 41"
3.
#3 #4 #5 #6
4 1/2" 6" 7 1/2" 9" 10 1/2" 12" 13 1/2" 15" 16 1/2" 21" 27"
2 1/4" 3" 3 3/4" 4 1/2" 5 1/4" 6" 9 1/2" 10 3/4" 12" 18 1/4" 24"
1 1/2" 2" 2 1/2" 4 1/2" 5 1/4" 6" N/A N/A N/A N/A N/A
4.
1'-0"
0"
1/ 2 "
3" CLR
#7
1'-0" 2'-0" 8"
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
1'-0" 8"
#8 #9 #10 #11
B.
MINIMUM LENGTHS AND BENDS INDICATED, BENDS SHALL COMPLY WITH ACI 318. INDICATED BEND DIAMETERS ARE MEASURED ON THE INSIDE OF THE BAR.
51" 68"
#14 #18
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
COMPRESSION REINFORCING
CONCRETE SLAB-ON-GRADE, TYP #5 AT 24" OC, TYP WELDED WIRE FABRIC, TYP VAPOR RETARDER, TYP TOC #4 AT 12" OC EACH WAY EACH FACE
1'-0"
8"
2'-6" SQUARE
1'-0"
8" TYP
[SEE PLAN]
1 3'-0" TYP 2
1'-6" TYP
0" TYP
9/ 1 6"
1'-6"
TOF [SEE PLAN] #4 AT 12" OC EACH WAY 3'-0". FACE OF EQUIPMENT 6" MIN, TYP 0" TYP
5/ 8 "
C
1'-6" TYP
0" TYP
1/ 2 "
2" CLR
#5 TIES AT 12" OC
EQUIPMENT PAD 3/4" CHAMFER, TYP ROUGHEN SURFACE TO 1/8" AMPLITUDE AND APPLY BONDING AGENT 6"
8"
TOF NOTE: FOR DETAILS NOT NOTED, SEE TYPICAL SECTION THROUGH ELEVATOR PIT ON THIS SHEET #5 AT 12" OC EACH WAY EACH FACE 1'-0"
CONCRETE SLAB-ON-GRADE
0" TYP
[SEE PLAN]
1'-0" TYP
TOC
1'-0" TYP
NOT TO SCALE
PREVIOUS POUR
2" CLR
2" 2"
1 1/2" UON
[SEE PLAN] T
[SEE PLAN]
6"
6"
VAPOR RETARDER
VAPOR RETARDER
8" TYP
3" CLR
VAPOR RETARDER
6"
NOTE: EXTEND THICKENED SLAB 1'-6" BEYOND EACH STRINGER 1'-4" 1'-4"
8"
6"
6"
8"
VAPOR RETARDER
6"
TOC
1 1/2" UON
SEE PLAN
SUPPORTS FOR WELDED WIRE FABRIC AT 3' - 0" OC MAX EACH WAY
CONCRETE SLAB-ON-GRADE
L3x3x1/4x0'-4" WITH (1) 3/4" EXPANSION ANCHOR WITH 3" MIN EMBEDMENT
APPLY LIQUID CURING COMPOUND TO ENTIRE FACE OF PREVIOUS POUR TO PREVENT BONDING WELDED WIRE FABRIC, TYP
2x4 CONT KEY CONCRETE SLAB-ON-GRADE SEE PLAN TOC [SEE PLAN]
SLAB ON DECK
#4 AT 12" OC
WALL BEYOND 1-#4 CONT PAVING OR FINISHED GRADE, SEE CIVIL DRAWINGS
#5 HORIZ AT 16" OC, EF CONCRETE SLAB-ON-GRADE #4 AT 12" OC WITH STD 180 HOOK
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
ELEVATOR SHAFT
2'-6"
2'-6"
1-#4 AT RE-ENTRANT CORNER, MIDDLE OF SLAB, EACH SIDE 14" CONC STEM WALL DAMP PROOFING SEE ARCH GEOTEXTILE FILTER FABRIC 8"
3/4" CLR
TOC [SEE PLAN] WELDED WIRE FABRIC #4 VERT AT 18" OC WITH STD 90 HOOK CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING TOF [SEE PLAN] #4 HORIZ AT 12" OC, EF 2x4 KEYWAY TOC [SEE PLAN] 1 1/2" UON
2'-6"
45
2" C
LR
45
2" C
1-#4
LR
12" LAP MIN CMU WALL, SEE PLAN ELEVATOR DOOR OPENING SEE ARCH DWGS LIMESTONE VENEER, TYP
SEE PLAN 1 1
0"
PLAN
SECTION
EDGE OF SLAB
PLAN
6"
EQ
EQ
2"
1-#4
1'-0" MIN
VAPOR RETARDER
SB502
SHEET OF
5/ 8 "
SECTION
[SEE PLAN]
9/ 1 6"
" -4 1'
" -4 1'
PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5. REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+12-0]. LOW-SLOPE ROOF AREAS ARE 1 1/2" WIDE RIB, 20 GAGE STEEL ROOF DECK SUPPORTED ON STRUCTURAL STEEL FRAMING. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SLAB ON GRADE SHALL BE 4" THICK REINFORCED WITH 6x6 W2.1xW2.1 WWF PLACED 1 1/2" BELOW TOP OF SLAB. PLACE SLAB ON 6" OF COMPACTED PENNDOT 2A STONE. SEE SHEETS SF201 AND SF202 FOR BRACED FRAME "BF-X" ELEVATIONS. SEE SHEET SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES.
2. 3.
4. 5. 6. 7.
8. 9.
10. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS AND DEPRESSION CORNERS" ON SF501. 11. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
KEY NOTES
LOW SLOPE ROOF AREA POCKET COLUMN INTO WALL. WIDTH OF POCKET SHALL EQUAL WIDTH OF PIER. SEE "TYPICAL COLUMN BEARING ON PIER "DETAIL ON SB501 DEPRESSED SLAB COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 TOP OF CONCRETE ELEVATION AT SHEAR WALL BELOW = [+9'-10"]. SEE BRACED FRAME ELEVATIONS ON SF202 POCKET BEAM INTO WALL. WIDTH OF POCKET SHALL EXTEND MIN 4" EA. SIDE OF BEAM FLANGE. SEE "TYPICAL BEAM BEARING ON WALL" DETAIL ON SB501 SEE "TYPICAL BEAM BEARING ON CORBEL" DETAIL ON SB501 TOP OF CONCRETE WALL ELEVATION = [+5'-8"]. SEE B5/SF201 FOR ELEVATION OF THE WALL TOP OF CONCRETE WALL ELEVATION = [+10'-3"] SITE WALL, SEE SB101 FOR DESIGN SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
10
24'-3"
11
13'-6"
12
3 4
1
24'-6"
2
14'-0"
3
9'-5"
3.9
4
1'-3" 16'-6"
5
8'-5"
6
8'-1" B2
7
16'-6" 1'-3"
8.1
9'-5"
9
14'-1"
10 DN
10
SB301
1'-4"
A
9 10 11 W12X26 (14) W12X45 (44) 23'-6" W12X14 W16X45 (16)
A.1
W12X26 (22)
W12X26 (22)
W12X26 (22)
W12X26 (22)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (22)
W12X26 (16)
1"
SB301
W12X26 (14)
W12X26 (14)
C3
TYP SIM A5 SF301 W14X61 (34) 4'-9 1/2" 5 W14X82 (32) 2" W10X12 W10X12 W10X19 (12) W10X19 (12) W12X19 (-0'-2") W12X19 (-0'-2") 2" 3'-9" BF-C 2" A3 SF301 W12X16 W12X16 W12X16 W12X16 W14X48 (50)
TYP
W12X14
SB301
7'-6"
4" SOG A5 1" SB301 C-4 PIER TOC = [+9'-4"] W12X19 (10)
8'-4"
B6 SF301
TYP
W10X12
SIM
D.9 E
8'-8"
W12X26 (26)
17'-2"
W16X45 (14)
E
8'-8"
TYP 6
C2 SB302
A6 SF301
W8X13
W12X14 (+2'-0") 1 W10X12 (+2'-0") W12X14 (+2'-0") W12X14 (+2'-0") W12X14 (+2'-0") W12X14 (+2'-0") 1'-0" CANTILEVER, TYP D4 SF302 TYP C2 SF302
F
W10X12 9 W10X12 W12X26 (14) W12X26 (22) W12X26 (22) W12X16 W12X16 17'-2" W12X16 W12X16 TYP 2 3'-0"
W12X26 (8) (-0'-2") W10X12 ( +2'-0" ) W10X19 (12) (-0'-2") W18X40 (10) (-0'-2")
W14X30 (10)
F
1'-4"
W12X19 (10)
W10X19 (12)
W10X12
(-0'-2")
8'-4"
2"
W10X12
F.1
G
W12X14 (+2'-0") W16X26 WITH (2) HSS8X4X3/16 (LSH) 7'-6"
ELEV. SHAFT 11
A3 SF301
6'-3"
2"
3 W14X61 (38)
W12X26 (10)
H
C1 7'-0" SF302
B3 SF301
OPP ( +3'-0" )
H
W16X31 WITH (2) HSS8X4X3/16 (LSH)
OPEN
H.5
SIM
W10X12 W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (20) W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (14)
W10X12
OPP D2 SF302 ( +3'-0" ) W12X14 (+2'-0") W16X26 WITH (2) HSS8X4X3/16 (LSH) W12X14 (+2'-0") 1'-0" CANTILEVER, TYP W12X14 (+2'-0") 1'-4"
TYP
TYP
W10X12 C2
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW J REVISIONS
No. Date Description
W10X12
16'-6"
W10X12 (+2'-0")
8'-4"
W10X12
13'-10"
SIM
B6 SF301
J.9 K
W14X30 (42)
W14X30 (18)
W18X35 (20)
W14X30 (38) 1 W10X12 (+2'-0") W12X14 (+2'-0") 1'-0" CANTILEVER, TYP W12X14 (+2'-0") W10X12 (+2'-0") N
B6
C2 SF302
B6 SF301
C2 SF302
SF301
GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'
SF101
SHEET OF
W12X19
PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5. REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+24-0]. LOW-SLOPE ROOF AREAS ARE 1 1/2" WIDE RIB, 20 GAGE STEEL ROOF DECK SUPPORTED ON STRUCTURAL STEEL FRAMING. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.
2. 3.
4.
5. 6. 7. 8. 9.
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
KEY NOTES
LOW SLOPE ROOF AREA COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 DEPRESSED SLAB SEE "TYPICAL BEAM END CONNECTION - TORSION CLIP" ON SF302, WHERE INDICATED IN STAIRWELLS, TYP SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
1 2
3 4
1
24'-6"
2
14'-0"
3
9'-5"
3.9
4
1'-3" 16'-6" C2
5
8'-5"
6
8'-1"
7
16'-6" 1'-3"
8.1
9'-5"
9
14'-1"
10
24'-3"
11
13'-6"
12
5
W12X14 (+2'-6 1/2") 1'-0" CANTILEVER, TYP TYP W12X14 (+2'-6 1/2") W12X14 (+2'-6 1/2") 1'-4" D4 SF302
C2 SF302 END OF VENEER SHELF ANGLE 2" EOS W18X35 (20) W12X26 4 7" STAIRWELL TYP 16'-5 1/2" BF-12 W21X57 (16)
A
A1 SF301
A.1
8'-4"
W12X14 (+2'-6 1/2") W16X26 WITH (2) HSS8X4X3/16 (LSH) W12X14 (+2'-6 1/2") D2 W14X30 (16) SF302
W10X12 W10X12 (+2'-6 1/2") W12X26 (16) W12X26 (16) W12X26 (16)
W12X26 (16)
W12X26 (16)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
B6 SF302
13'-10"
(+3'-6 1/2")
SF301
W10X12
B3 SF301 OPEN
A5 W10X12 6'-6"
C1 SF302
7'-6"
W16X26 WITH (2) HSS8X4X3/16 (LSH) W12X14 (+2'-6 1/2") W10X12 (+2'-6 1/2") W12X14 (+2'-6 1/2") 1'-0" CANTILEVER, TYP TYP D4 SF302 W12X14 (+2'-6 1/2")
B3 SF301 W10X12 (+2'-6 1/2") W12X19 (10) W10X12 W18X40 (12) BF-4 ( +3'-6 1/2" )
2"
2" 3 1/2"
BF-C
2" W10X19 (12) A3 W12X16 W12X16 W12X16 W12X16 W12X16 W12X19 W12X16 W12X16 (-0'-2") SF301
W10X19 (12)
2 W12X19 W10X12
4'-8" EOS
3'-6" EOS
9"
W14X30 (12)
W12X19
D
8'-4"
(-0'-2")
C4 SF301
SIM 17'-2"
3" 3"
TYP
1'-4" EOS
W10X12
W10X12
3'-8 3/4"
2"
D.9
1'-4"
2-#4x20'-0" W14X30 (12) 2'-8 1/2" W10X12 W10X12 2'-1" EOS W14X30 (24)
A2 SF301
W14X30 (34)
W12X26 (8)
C2 4'-0" END OF VENEER SHELF ANGLE 10'-10" EOS W18X35 (8) 12'-5" A1 W18X35 SF301 7" W12X26 (19) SF302
E
8'-8"
8'-8"
TYP
F
9'-8" A1 W12X14 (-2'-0") 1'-7" CANTILEVER, TYP W12X14 (-2'-0")
W10X19 (12)
2" (-0'-2")
B6 SF302
STAIRWELL
W10X12
( -2'-0" )
A3 SF301 3
1'-0" 1'-4"
G
W12X14 (-2'-0") D1 SF302 TYP 7'-6"
TYP
8 1/2"
W12X26 (10)
H
9'-10" EOS
2"
W14X61 (26)
W10X12 (-2'-0") W12X14 (-2'-0") W8X10 (-2'-0") W12X14 (-2'-0") 1'-7" CANTILEVER, TYP 13'-10"
H CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW J
9'-8"
C1
W10X12 (-2'-0")
H.5
23'-6"
SF302
W10X12 TYP W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (20) W12X26 (14) TYP
W12X26 (14)
4'-8" EOS
W14X30 (30)
1'-4" EOS
SF302
W10X12
C4 SIM SF301
REVISIONS
No. Date Description
W18X40 (14)
BF-1
W10X12 A2 SF301 W18X35 (28) W10X12 (-2'-0") W12X14 (-2'-0") W12X14 (-2'-0") 1'-7" CANTILEVER, TYP
A2 SF301
W18X35 (26)
W18X35 (18)
W18X40 (40)
C6 SF301
10'-10" EOS
11'-2" EOS
C4 SF301
GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'
SF102
SHEET OF
4'-1 1/4"
W14X61 (34)
W18X55 (30)
W14X48 (50)
W14X48 (46)
W12X26 (8)
W12X16
W12X16
17'-2"
1'-4" EOS
9"
9"
6 1/2"
W10X12
TYP
TYP
23'-6"
( +3'-6 1/2" )
W14X34 (24)
W10X12
1'-4" EOS
PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5. REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+36-0]. LOW-SLOPE ROOF AREAS ARE 1 1/2" WIDE RIB, 20 GAGE STEEL ROOF DECK SUPPORTED ON STRUCTURAL STEEL FRAMING. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.
2. 3.
4.
5. 6. 7. 8. 9.
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
KEY NOTES
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
1 2
LOW SLOPE ROOF AREA COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 DEPRESSED SLAB SEE "TYPICAL BEAM END CONNECTION - TORSION CLIP" ON SF302, WHERE INDICATED IN STAIRWELLS, TYP SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502
1
24'-6"
2
14'-0"
3
9'-5"
3.9
4
1'-3" 16'-6" C4
5
8'-5"
6
8'-1"
7
16'-6"
8
10'-8"
9
14'-1"
10
24'-3" C4
11
13'-6"
12
SF301
A1 SF301
1'-4" EOS
W18X35 (34)
W18X35 (28)
4 7"
W10X12 (-4'-0 1/2") W12X26 (14) W14X30 (28) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W10X12 ( -4'-0 1/2" )
B
W12X14 (-4'-0 1/2") W12X35 (-4'-0 1/2") 13'-10" D1 SF302
W10X12 C4 SF302
TYP
TYP
W10X12
W10X12
( -4'-0 1/2" )
W10X12
7'-6"
2"
1'-4" EOS A3 W10X12 W12X26 (14) W12X16 W12X16 W12X16 W12X16 W12X16 W12X16 W12X16 C4 SF301 SIM
BF-C
W10X19 (12)
W12X19
W10X12
W10X12 (-4'-0 1/2") 9'-8" W12X14 (-4'-0 1/2") W12X14 (-4'-0 1/2") W12X14 (-4'-0 1/2") 1'-7" CANTILEVER, TYP A2 SF301
W12X19
3"
(-0'-2")
W10X12
TYP
W10X12
1'-0" EOS
2-#4x20'-0" 2" W14X30 (12) 9" 2'-8 1/2" W10X12 W10X12 1'-4" EOS B1 SF301 W12X26 (8) A2 W18X40 (14) (-0'-2") SF301 W10X12 W10X19 (12) W10X19 (12) (-0'-2") (-0'-2") (-0'-2") C6 SF301 2'-1" EOS C4 SF301 W14X30 (24) W14X30 (34) W12X26 (8) 2" EOS
A2 SF301
E
A1 8'-8" SF301 10'-10" EOS
W12X26 (12) C4 SF301 11'-2" EOS C6 SF301 B1 SF301 3'-0" W12X26 (8) 3'-0 1/2" W10X12 W10X12
W10X12
F
12'-5" A1 W18X35 SF301 17'-2"
W12X26 (10) W10X12 1'-4" EOS W21X57 (8) 7" W12X26 (20) W12X16 W12X16 W14X30 (42) 6'-1"
9"
W12X16
W12X16
W12X16
TYP
2"
B6 SF302 TYP 4
STAIRWELL
A3 SF301
W12X26 (10)
H
C1 9'-10" EOS SF302
W18X55 (30) 9" BF-H A5 1'-8" EOS C1 SF301 W10X12 1'-4" EOS SF302
3'-4" EOS
2"
1'-4" EOS
SIM
4'-8" EOS
3'-6" EOS
9"
W12X26 (14)
W12X26 (20)
W12X26 (20)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (20)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
23'-6"
4'-8" EOS
4'-0" EOS
TYP
SIM
3'-4" EOS
H.5
W10X12
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
A2 SF301
W18X35 (26)
W18X35 (18)
W18X40 (40)
W18X35 (28)
C6 SF301
11'-2" EOS
C6 SF301
10'-11" EOS
C6 SF301
GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'
SF103
SHEET OF
W14X61 (34)
W18X55 (30)
W14X48 (50)
W14X48 (46)
W14X30 (12)
6'-6"
SF302
6 1/2"
11"
C1
W12X26 (8)
PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5 REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+48-0]. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.
2. 3.
4. 5. 6. 7. 8.
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
KEY NOTES
COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 DEPRESSED SLAB SEE "TYPICAL BEAM END CONNECTION - TORSION CLIP" ON SF302, WHERE INDICATED IN STAIRWELLS, TYP SEE "TYPICAL MOMENT CONNECTION AT COLUMN" ON SHEET SF501 SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
2 3
1
24'-6"
2
23'-5"
3.9
1'-3"
4
16'-6"
5
8'-5"
6
8'-1"
7
16'-6"
8
24'-9"
10
24'-3" C4
11
13'-6"
12
4 5
A1 SF301
1'-4" EOS
1'-4" EOS
W18X40 (48)
W18X40 (38)
W12X26 A1 BF-12 7" 3 TYP W21X57 (16) SF301 16'-5 1/2" B6 SF302
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
23'-6"
W18X35 (28)
W10X12
TYP
TYP
W12X26 (14)
W14X34 (24)
3'-7" EOS
3'-4" EOS
4'-4" W14X61 (34) 9" W18X55 (30) 2" 9" BF-C 2" A3 W10X19 (12) W10X19 (12) SF301 W12X16 W12X16 W12X16 W12X16 W12X16 W12X19 W12X16 TYP W14X48 (50) W14X48 (46) 4'-1 1/4"
SF302
3'-7" EOS
W18X40 (14)
W12X19 (10)
C4 SF301
SIM
W12X19
W10X12
(-0'-2")
W12X19
(-0'-2")
17'-2"
BF-4
3'-8 3/4"
A2 SF301
3"
C4 8'-8" A1 SF301 10'-10" EOS W21X57 (12) 12'-5" A1 W18X40 W12X16 W12X16 SF301 17'-2" W12X26 (20) 1'-4" EOS SF301 11'-2" EOS
C6 SF301
9"
2-#4x20'-0" 2" W14X30 (12) 2'-8 1/2" W10X12 W10X12 B1 SF301 W12X26 (8) A2 W18X40 (14) (-0'-2") SF301 C6 SF301 2'-1" EOS W14X30 (42)
1'-4" EOS
1'-0" EOS
W10X12
W10X12
W12X26 (14)
A2 SF301
W18X35 (16)
C4 SF301
9"
W12X19 (10)
W12X16
W12X16
W12X16
TYP
W10X19 (12)
W10X19 (12)
W10X12 (-0'-2")
B6 SF302
STAIRWELL
A3 SF301 2
8 1/2"
W12X26 (10)
H
9'-10" EOS C1 SF302
2"
SF302
W18X55 (30) BF-H A5 SF301 1'-8" EOS SF302 W18X35 (28) W10X12 10" EOS 7'-2" C1
3'-4" EOS
TYP
7"
B1
2"
1'-4" EOS
4'-8" EOS
W10X12
3'-6" EOS
1'-4" EOS
W12X26 (20)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (14)
W12X26 (20)
W12X26 (14)
W12X26 (20)
1'-4" EOS
W12X26 (14)
W12X26 (14)
SIM 23'-6" 4'-8" EOS C4 SF301 W10X12 1'-0" EOS W18X40 (14) BF-1
TYP
TYP
W12X26 (14)
W10X12
4'-0" EOS
C4
SIM
3'-4" EOS
H.5
W10X12
1'-4" EOS
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
W10X12
A2
SF301
W18X40 (38)
1'-4" EOS
W18X35 (38)
W21X44 (33)
1'-4" EOS
W18X40 (38)
C6 SF301
10'-11" EOS
C6 SF301
GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'
SF104
SHEET OF
W14X30 (12)
6'-6"
SF302
7'-7" EOS
6 1/2"
C1
W10X12
A5 SF301
C1
PLAN NOTES
LOCATE AND COORDINATE MECHANICAL DUCTS 12 F E WP 1'-0" MIN 6" TOP CHORD 7 PROVIDE SUPPORT FOR MECHANICAL DUCTS K A RAFTER TAIL, WP OMIT AT RT-2 4'-8" F 7 1'-0" RAFTER TAIL, OMIT AT RT-2 LOCATE AND COORDINATE MECHANICAL DUCTS PROVIDE SUPPORT FOR MECHANICAL DUCTS 2. K 1. TYPICAL ROOF FRAMING IS 1 1/2 WIDE RIB, 20 GAGE, STEEL ROOF DECK ON ENGINEERED COLD-FORMED STEEL TRUSSES, SUPPORTED ON STRUCTURAL STEEL FRAMING. LOW-SLOPE ROOF AREA AND ELEVATOR CAP ARE 3" LIGHTWEIGHT CONCRETE ON 2" DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5". REINFORCE SLAB WITH 6x6-W2.1xW2.1 WWF PLACED 3/4" CLEAR OF TOP OF SLAB, FULLY SUPPORTED. MAXIMUM TRUSS SPACING IS 4-0 UON. COORDINATE LAYOUT OF COLD-FORMED TRUSSES WITH MECHANICAL DRAWINGS. TYP TOS AND TRUSS BEARING ELEVATION = [+60-0]. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULE. RT-X = ROOF TRUSS TYPE. SEE ROOF TRUSS PROFILES THIS SHEET. SEE "TYPICAL DRAG TRUSS TYPE A" ON SF501 AND "TYPICAL DRAG TRUSS TYPE B" ON SF502
3. 4.
4'-8"
4"
17'-2" 40'-8" AT ATTIC WALKWAY, PROVIDE 12" DEPTH IN BOTTOM CHORD FOR INSULATION THICKNESS
4"
17'-2"
ELEV SHAFT 40'-8" AT ATTIC WALKWAY, PROVIDE 12" DEPTH IN BOTTOM CHORD FOR INSULATION THICKNESS
5. 6. 7.
RT-3
LOCATE AND COORDINATE MECHANICAL DUCTS MIN 6" TOP CHORD PROVIDE SUPPORT FOR MECHANICAL DUCTS 600S162-33, CONT, TYP. KEEP AREA CLEAR OF DIAGONAL MEMBERS
WALKWAY SURFACE MADE OF 43 MIL STUDS, SIDE-TO-SIDE, FASTENED TO TRUSS BOTTOM CHORD
4'-8"
SUPPORT CONDITIONS MAY VARY FOR DIMENSIONS AND OTHER ELEMENTS, SEE RT-1 DETAIL
4"
17'-2" 40'-8"
GABLE END
RT-4
ATTIC WALKWAY
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
TRUSS PROFILES
NOT TO SCALE #
12"
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
KEY NOTES
LOW-SLOPE ROOF AREA STEEL KNEE-BRACED FRAME. SEE "TYPICAL STEEL-FRAMED KNEE BRACE" ON SHEET SF501 SLAB-ON-DECK ELEVATOR CAP. TOC = 6'-8" ABOVE TOP OF STEEL. SEE AE421 FOR ELEVATOR SUPPORT MEMBERS PROVIDED BY ELEVATOR SUPPLIER ROOF ACCESS HATCH. SEE DETAIL ON SHEET AE106 AND "TYPICAL DECK SUPPORT AT ROOF OPENING" ON SF502 OPENING IN CMU WALL FOR MECHANICAL DUCT. COORDINATE SIZE AND LOCATION WITH MECH DRAWINGS ATTIC ACCESS, SEE ARCH. SEPARATE TRUSSES AROUND OPENING MECHANICAL DUCTWORK IN ATTIC. COORDINATE LOCATIONS AND SIZES WITH MECHANICAL PLANS MECHANICAL SHAFT THROUGH ATTIC. LOCATE TRUSSES ON BOTH SIDES OF SHAFT (MANTAIN CLEAR AREA ABOVE SHAFT)
1 2
1
24'-6"
2
23'-5"
3.9
4
1'-3" 16'-6"
5
8'-5"
6
8'-1"
7
16'-6"
8
24'-9"
10
24'-3"
11
13'-6"
12
6 GABLE-END DRAG TRUSS. WIND LOAD = 20.6 K SEISMIC LD = 1.5 K D1 SF301 D3 SF301 2 W14X38 RT-1 12 7 12 RT-1 RT-1 7 W12X22 W12X26 W12X26 W12X22 TYP RT-2 W12X35 RT-1 RT-1 W18X60 RT-1 8'-9" DRAG TRUSS TYPE A 2 W10X22 2 GABLE-END DRAG TRUSS. WIND LOAD = 20.6 K SEISMIC LD = 1.5 K 7
W14X38
4'-6"
W10X12 W12X22 9" 5'-4" 23'-6" C6X10.5 W10X12 HSS6X6X3/16 ( +2'-8" ) 3'-8" 4'-6"
BF-12
RT-2
W12X26
3'-8"
5'-4"
C1
W8 0 X1
5'-2"
12
W10X12
ATTIC WALKWAY
D4 SF301
W10X12
D4 SF301
C6X10.5 C1
W10X12
TYP
BF-C
TYP 12 7
TYP
W12X22
5'-4"
W10X22
W10X22
W12X22
W10X22
W10X22
17'-2"
12
W10X12 W18X40
W12X22
SF301
C6X10.5 W14X34
W12X22
12 7 12 7
8'-9"
BF-4
D2 SIM SF301
E
3'-0 1/2" W12X26 8'-8"
W14X30
W14X30
W14X34
W12X30
W10X22
W10X12
W10X12
W10X12
W10X12
W10X12
W12X26
D5 SF301
C3 SF301
TYP
TYP
TYP
C3 1 SF301
F
4'-6" W14X34 8'-9"
W14X34 7
12
12 7
W14X30 3
W14X30
W14X30
W10X22
W10X22
W10X22
W10X22
W10X12 5'-4"
W12X22
W12X22
TYP 12 7
17'-2"
C2 SF301 5
W10X12 5'-4" C1 SF301 BF-8 W10X12 C6X10.5 HSS6X6X3/16 ( +2'-8" ) D4 SF301 5'-2" 3'-8"
TYP
12
C6X10.5
W14X38
W14X48
W10X12
5'-2"
12
D4 SF301
ATTIC WALKWAY 7 W12X26 7 12 W10X12 W10X12 W12X22 4'-6" W10X12 RT-1 W18X60
8'-9"
5'-4"
10 8X W
W10X12
W10X12 W12X30
3'-8"
W12X45
W12X26
23'-6"
TYP RT-2
C6X10.5
3'-8"
H.5
RT-4
RT-4
5'-4"
5'-4"
9"
C6X10.5
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
RT-1
RT-1
RT-3
RT-3
RT-1
RT-2
RT-2
RT-2
RT-1
12 7
12 7
12 7 12 7
8'-9"
RT-1
D2 SF301
D2 SF301
K
2
W14X38
W14X38
W14X43
W14X38
8'-9"
GRAPHIC SCALE(S)
5'
10'
15'
30'
SF105
SHEET OF
3'-8"
3'-8"
W14X43
W14X48
W14X38
W14X38
W12X22
W10X12
12
5'-2"
1
K
16'-6"
2
H.5 E
17'-2"
3
C H
4
F
17'-2"
5
C
23'-6"
6
A
HS S5 X5 X3 /1 P= 6 20 k
HS S5 X P= 30 k
5X 1/4
1/4 5X X S5 k HS 20 P=
1 /4 5X X S5 HS k 20 P=
W18X40 (14)
V=30k
C5 SF202
TYP W18X40 (14) V=30k FOURTH FLOOR [SEE PLAN] W21X57 (16) V=50k FOURTH FLOOR [SEE PLAN]
HS S
5X 5
HS
X3 /16
P= 40 k
P= 50 k
S5 X5 X
1/4
/4 X1 5 X S5 S k H 40 P=
/4 X1 X5 5 S HS k 40 P=
W18X40 (14)
V=20k
W18X40 (14)
V=20k
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
HS S
5X
HS S5
P= 60 k
5X
1/4
P= 70 k
X5 X5 /1
/8 X3 5 X S5 k HS 70 P=
/4 X1 X6 6 S HS k 70 P=
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
TYP
D4 SF202 OPP
HS S
5X
P= 80 k
5X
3/8
HS S6 X6 X3 P= /8 14 0k
1/2 5X X S5 k HS 80 = P
3/8 6X X S6 HS 0k 10 P=
W18X40 (10)
V=20k
W16X45 (16)
V=40k
COORDINATE WALL OPENINGS FOR DUCTWORK WITH MECHANICAL DRAWINGS BEAM BEYOND, TYP.
HS S5 X3 P= /8 11 0k X5
8"
COLUMN BEYOND
B1
B
B2
B4
B5
NOTES: 1. 2. BRACED FRAME CONNECTION DESIGN IS DELEGATED TO THE CONTRACTOR. AXIAL LOAD INDICATED AS P=x. DESIGN CONNECTION FOR TENSION AND COMPRESSION. VERTICAL SHEAR REACTION INDICATED AS V=x. FORCES ARE IN KIPS. FORCES SHOWN ARE FACTORED.
3.
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:17:17 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt REVISIONS
No. Date Description
GRAPHIC SCALE(S)
0 1/4" = 1' - 0" 1' 5' 10' 15'
SF201
SHEET OF
SLAB BEYOND
1/2 5X X S5 k HS 90 P=
1
6
24'-7"
2
8 6
24'-7"
3
8
CL OF FRAME
CL COL
TYP 1/4" FULL DEPTH STIFFENER EA SIDE OF BEAM AT EA END OF GUSSET PL BEAM, SEE PLAN TOS ERECTION BOLT, TYP
CAP PLATE
W14X48 V=20k
W14X48 V=20k
[SEE PLAN]
CL BEAM
CL BEAM
HS
HS S5 X5 X1 P= /4 30 k
/4 X1 X5 k S5 30 P=
HS S5 X5 X1 P= /4 30 k
HS /4 X1 X5 S5 3 P= 0k
GUSSET PLATE, 3/8" MIN. CENTER ON BEAM. FS NS ERECTION BOLT 6" MIN CL BRACE BRACE, SEE BRACED FRAME ELEVATION GUSSET PLATE, 3/8" MIN. CENTER ON BEAM. TYP. BRACE, SEE BRACED FRAME ELEVATION, TYP FS NS, 6" TYP MIN
C5 SF202
C5 SF202
CL BRACE, TYP
HS S5 X5 X1 P= /4 60 k
HS S5 X5 X1 P= /4 60 k
D4
D5
/4 X1 X5 S5 k HS 60 P=
/4 X1 X5 S5 k 60 HS P=
CL COLUMN GUSSET PLATE, 3/8" MIN. CENTER ON BEAM. SIZE TO SUIT. TOS [SEE PLAN] SLAB NOT SHOWN ERECTION BOLT CL BRACE
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
HS S5 X5 X1 P= /4 70 k
HS S5 X5
P=
D5 SF202
D5 SF202
L5x3x1/4 (LLV), 8" LONG AT 36" OC WITH 2 BOLTS AT EACH 6 1/2" TOC [SEE PLAN]
TYP
TYP
STEEL BEAM SEE ELEVATION FOR BRACE SIZE, SLOT HSS AS REQ'D AT GUSSET
/2" 1 1 IN M
70
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
X1 /4
/4 X1 X5 S5 k HS 70 P=
/4 X1 X5 S5 k HS 70 P=
CL BEAM
3/4" BOLT IN LONG-SLOTTED VERTICAL HOLES W18X55 (30) V=40k SECOND FLOOR [SEE PLAN] W18X55 (30) V=40k SECOND FLOOR [SEE PLAN] CONT WT4x10.5 WITH 3/4"x9" HEADED STUDS AT 18" OC
SEE PLAN FOR COL ORIENTATION WORKING POINT BEAM, SEE PLAN 6" MIN TYP EA SIDE 6" MIN
HS S5 X5 X1 P= /4 80 k
HS S5 X5 X1 P= /4 80 k
C4
/4 X1 X5 S5 k HS 80 P=
/4 X1 X5 S5 k HS 80 P=
C5
C4 SF202
C4 SF202 W14X82 (32) V=40k FIRST FLOOR [SEE PLAN] W14X82 (32) V=40k FIRST FLOOR [SEE PLAN] 3/4" HEADED STUDS, SEE PLAN 12 SLAB ON DECK, SEE PLAN SEE PLAN #4 HAIRPIN BARS @ 48" OC. #4 CONT 1/4" BENT PLATE, CONT 1" GAP, FILL WITH COMPRESSIBLE MATERIAL
1/4" FULL-DEPTH STIFFENER AT 48" OC MAX STEEL BEAM, SEE PLAN, TYP. GROUND FLOOR [SEE PLAN] GROUND FLOOR [SEE PLAN] 5/16 3-12
L6x4x5/8" (LLV), CONT WITH 2" VERT SLOTS FOR ANCHORS AT 6" OC (FILL 1/2 OF HOLES WITH ANCHORS)
4"
1" HEAVY-DUTY EXPANSION ANCHOR @ 12" OC, 4" NOM. EMBEDMENT WITH 12.2k SHEAR CAPACITY, PLACE AT BOTTOM OF SLOT.
B1
B2
B4
SECTION
3/4" = 1'-0"
NOTES: 1. 2. BRACED FRAME CONNECTION DESIGN IS DELEGATED TO THE CONTRACTOR. AXIAL LOAD INDICATED AS P=x. DESIGN CONNECTION FOR TENSION AND COMPRESSION. VERTICAL SHEAR REACTION INDICATED AS V=x. FORCES ARE IN KIPS. FORCES SHOWN ARE FACTORED.
3.
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:17:21 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt
Description
GRAPHIC SCALE(S)
0 1/4" = 1' - 0" 0 3/4" = 1' - 0" 0 1" = 1' - 0" 6" 1' 2' 3' 6" 1' 2' 3' 4' 5' 1' 5' 10' 15'
SF202
SHEET OF
1
COPING CAP, SEE ARCH
1
CFS TRUSS OVER FRAMING COPING CAP, SEE ARCH
6"
E
CFS STUDS MASONRY VENEER, SEE ARCH STEEL STUD FRAMING NOT SHOWN STEEL ROOF DECK, SEE PLAN
TOS [+62'-8"]
CFS TRUSS
L6x6x5/16, GALV, CONT LOOSE LINTEL DRAG TRUSS CONNECTION BY TRUSS SUPPLIER PL1/4"x12" CONT CONCRETE SLAB ON DECK, TYP. MASONRY VENEER, SEE ARCH 1'-0" L6x4x3/8 GALV LLH SHELF ANGLE 1-12 7 1/2" (2) 3/4" BOLTS AT EA. CONNECTION STL PLATE 1/4"x8"x12" AT 4'-0" OC MAX, COORD W/ TRUSS BRG LOCATIONS TOS [SEE PLAN]
MASONRY VENEER, SEE ARCH TOS [SEE PLAN] 3 5/8" CFS BLOCKING AT 24" OC
SHELF ANGLE [SEE ARCH] CFS TRUSS TOS [SEE PLAN] TOS [SEE PLAN] CFS ROOF TRUSS, SEE PLAN MASONRY VENEER, SEE ARCH 3 5/8" CFS BRACE AT EA TRUSS DEFLECTION TRACK DEFLECTION TRACK CFS STUDS BACKING UP MASONRY VENEER 4" TOS [SEE PLAN] L3x3x1/4, CONT 10"
CFS TRUSS 3 5/8" CFS BRACE AT EA TRUSS 3 5/8" CFS BRACE AT 24" OC
CURTAIN WALL, SEE ARCH (3) 3/4" BOLTS IN HORIZ SLOTS, SLIP CRITICAL L2x2x1/4, CONT C10x15.3 CANTILEVER STUB, SHOP WELD TO BEAM AT EA CHANNEL
D1
SECTION
3/4" = 1'-0"
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
MASONRY VENEER, SEE ARCH 6" CFS STUD WALL, SEE ARCH 2-12 HSS6x6x3/16, CONT PL3/16"x6" AT 16" OC FRP CORNICE, SEE ARCH TOS [+62'-8"] CFS TRUSSES, SEE PLAN L2x2x1/4, GALV
D2
SECTION
3/4" = 1'-0"
D3
SECTION
3/4" = 1'-0"
D4
SECTION
3/4" = 1'-0"
D5
#3 HAIRPIN BAR @ 48" OC EOS SEE PLAN #4 CONT 11" EOS 16 GA POURSTOP FASTENED TO DECK TOS [SEE PLAN] EA END, TYP WIND CONNECTION FOR CURTAIN WALL BY SUPPLIER SEE "TYPICAL VENEER SHELF ANGLE" DETAIL ON SF501 1/4" BENT PLATE, CONT 4" EOS TOP OF SLAB #4 CONT 1/4 2'-6" 3/4" TOP OF SLAB [SEE PLAN] 2-12 SEE "TYPICAL VENEER SHELF ANGLE" DETAIL ON SF501 TOP OF SLAB [SEE PLAN] SHELF ANGLE [SEE ARCH] #4 CONT
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
L6x6x5/16, CONT DRAG TRUSS CONNECTION BY TRUSS SUPPLIER PL1/4"x12" CONT, BREAK AT EACH PERPENDICULAR BEAM
[SEE PLAN] 8" CMU BOND BEAM WITH (2)#5 CONT 5/8" CARBON STEEL SCREW ANCHOR W/ 5" EMBED @ 24" OC. MAX W/ 3.4 KIP SHEAR CAPACITY PER ANCHOR ALONG FOUR SIDES OF ELEVATOR CAP LIGHT GAGE TRUSS PER PLAN, TYP TOP OF STEEL [ROOF]
10"
ELEVATOR CAP (SLAB ON DECK, SEE PLAN) L6x3 1/2x5/16 (LLV) CONT ON FOUR SIDES OF ELEVATOR CAP
2-12 MASONRY VENEER, SEE ARCH (3) 3/4" BOLTS IN HORIZ SLOTS, SLIP CRITICAL
STEEL BEAM, SEE PLAN MOMENT CONNECTION, SEE TYP DTL SEE PLAN FOR WALL TYPE AND REINF.
DECK DIRECTION VARIES 3 SIDES, TYP STEEL BEAM, SEE PLAN, WITH FULL DEPTH BOLTED CONNECTION, SLIP CRITICAL AT EXTERIOR END WALL STUDS BELOW OMITTED FOR CLARITY
BOLTED SHEAR CONNECTION, FULL DEPTH OF SUPPORTED MEMBER, WITH SLIP-CRITICAL BOLTS TO PREVENT ROTATION
C
C10x15.3 CANTILEVER STUB, SHOP WELD TO BEAM AT EACH CHANNEL
C1
SECTION
3/4" = 1'-0" ALUMINUM CURTAIN WALL SYSTEM, SEE ARCH DWGS 4" 1/4" CONT BENT PLATE TOP OF SLAB [SEE PLAN] CURTAIN WALL CONNECTION BY SUPPLIER WEDGE-INSERT ANCHOR AT EA CURTAIN WALL CONNECTION, COORDINATE LOCATIONS WITH CURTAIN WALL SUPPLIER
C2
SECTION
3/4" = 1'-0"
C3
SECTION
3/4" = 1'-0"
C4
SECTION
3/4" = 1'-0"
1/4" FULL DEPTH STIFFENER AT EACH SUPPORTED BEAM AND AT 48" OC MAX
C6
L2 1/2x2 1/2x1/4 x 12" LONG AT EACH CORNER AND AT 3'-0" OC MAX WITH (2) 1/2" DIA x 4" HEADED STUDS
SEE PLAN 2-12 2-12 TOP OF SLAB MASONRY VENEER, SEE ARCH DWGS
4"
COLD-FORMED STEEL POUR STOP BY DECK SUPPLIER #4 CONT TOC [SEE PLAN]
RECESS SLAB 1/4" AT EACH ANCHORAGE #4 BAR, CONTINUOUS, EXTEND 2'-0" PAST EACH CORNER BEAM, SEE PLAN 1/2" JOINT, FILL WITH FIRE CAULK
L3 1/2x2 1/2x1/4 (LLV), 12" LONG WITH (2) 1 1/2" VERTICAL SLOTS FOR ANCHORS, 2" FROM EACH END COORDINATE LOCATIONS AND REQUIREMENTS OF EMBEDS FOR ELEVATOR RAIL SUPPORTS WITH ELEVATOR SUPPLIER ELEVATOR SHAFT
EA END
[SEE PLAN] TOP OF STEEL [SEE PLAN] TOP OF STEEL [SEE PLAN] FULL-DEPTH STIFFENER AT EA BEAM CONN, ONE SIDE
HSS3x2x3/16, CONT (LSH) 1/4" STIFFENER NS/FS, ALIGN WITH HORIZ PLATE 3/8"x6"x8" VERT STL PLATE, CENTERED ON HORIZ PLATE 3/8"x8"x9" HORIZ STL PLATE W10 STL BEAM, SEE PLAN 1 1/2" MIN 3/16 POUR STOP AND OTHER ELEMENTS NOT SHOWN FOR CLARITY BEAM PER PLAN
BOLTED SHEAR CONNECTION, FULL DEPTH OF SUPPORTED MEMBER, WITH SLIP-CRITICAL BOLTS TO PREVENT ROTATION DEEP-LEG DEFLECTION TRACK AT HEAD OF WALL, TYP
STEEL BEAM, SEE PLAN NOMINAL 8" CONCRETE MASONRY WALL, SEE PLAN
B1
SECTION
3/4" = 1'-0"
B2
B3
B5
SECTION
3/4" = 1'-0"
B6
SECTION
3/4" = 1'-0" F 3/16" BENT PLATE RECESSED SLAB FOR JOINT COVER, SEE 4/AE514 1"
TOS [SEE PLAN] L7x4x3/8 GALV, CONT 3/16 3-8 1-12 NOTE: FOR OTHER ELEMENTS, SEE "TYPICAL VENEER SHELF ANGLE" ON SF501 TOC [SEE PLAN] 3-8 2-12 FULL-DEPTH STIFFENER, NS/FS. LOCATE AT CONNECTION FOR SUPPORTED BEAM AND AT 48" OC BEAM, SEE PLAN 2-12 SEE PLAN BOTTOM OF SHELF [SEE ARCH] SEE PLAN #3 AT 24" OC, 1/4 2-12 18" 18" VARIES 18" VARIES TOP OF SLAB [SEE PLAN] TOS [SEE PLAN] 1/4 1/4 1/4 1/4 L3x3x1/4, CONT STEEL BEAM, SEE PLAN STEEL BEAM, SEE PLAN 18" 1/4 2-12 SEE PLAN SEE PLAN 8" TYP 3/16 3/16 5/16"X2" PLATE, NS/FS (2) 3/4" BOLTS IN LONG SLOTS 1/4 TYP AT EA BEAM LOW-FRICTION STRUCTURAL BEARING WITH 10 KIPS CAPACITY, MIN 1/2" BEARING PLATE (3) 3/8" STIFFENERS 1/4 1/4 3/8" STIFFENER PLATE SECTION A-A 1/2" CLR
1/4
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
HSS8x6x3/8 LSH
#3 AT 24" OC,
A
4"
STAIR C8x11.5
A6
SECTION
1 1/2" = 1'-0"
GRAPHIC SCALE(S)
0 3/4" = 1' - 0" 6" 6" 3" 6" 1' 1' 9" 1' 2' 2' 3' 4' 3' 2' 5' 0 1" = 1' - 0" 0 1 1/2" = 1' - 0"
A1
SECTION
3/4" = 1'-0"
A2
SECTION
3/4" = 1'-0"
A3
SECTION
3/4" = 1'-0"
A5
SECTION
3/4" = 1'-0"
SF301
SHEET OF
3/16
2 #5 CONTINUOUS
FOUR 3/4" A325 BOLTS, FINGER TIGHTEN IN LONG VERT SLOTS, PRETENSION AFTER CONCRETE IS PLACED ON FLOOR DECK
5/8" x 4" HEAVY SCREW ANCHOR AT TOP OF VERTICAL SLOT, BACK OFF 1/4 TURN AFTER INSTALLATION
L4x4x3/8, CONT
MIN 14 GA CFS CLIP AT EA STUD W/ MIN (3) #12 SELF-DRILLING SCREWS, MIN IN EA LEG
3/16
EA END
3/16
MIN 14 GA CFS ANGLE CLIPS WITH MIN (3) #12 SCREWS, EA LEG
D1
SECTION
3/4" = 1'-0"
D2
SECTION
3/4" = 1'-0"
D4
SECTION
3/4" = 1'-0"
VARIES
D
WEDGE-INSERT ANCHOR AT EA CURTAIN WALL CONNECTION, COORDINATE LOCATIONS WITH CURTAIN WALL SUPPLIER EOS SEE PLAN
8"
16" MAX
3.9
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
#4 HAIRPIN @ 32" OC 8"
4'-0"
#3 HAIRPIN BAR @ 48" OC 1/4" BENT PLATE 8" EOS SEE PLAN L4x4x1/4" 3'-0" TOP OF SLAB 1/4" BENT PLATE CONT 1/4 2-12 DECK DIRECTION VARIES TOP OF SLAB [SEE PLAN] EA END, TYP BOLTED CONNECTION WITH VERTICAL SLOTS TO ALLOW DEFLECTION
8.1
VARIES
1/4
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
EA END, TYP L2 1/2x2 1/2x1/4 AT EACH STIFFENER, 48" OC MAX WALL STUDS BELOW OMITTED FOR CLARITY 3 SIDES, TYP WALL STUDS BELOW OMITTED FOR CLARITY L3x3x1/4 AT EA STIFFENER 1/4" FULL DEPTH STIFFENER AT EACH SUPPORTED BEAM AND AT 48" OC MAX STEEL BEAM, SEE PLAN, WITH FULL DEPTH BOLTED CONNECTION, SLIP CRITICAL AT EXTERIOR END 3/16 3/16 2-12 2-12 11" 3 1/2" WELDED TRIANGULAR ANGLE FRAME CONSTRUCTED WITH L2-1/2x2-1/2x1/4 SHAPES
1/4" FULL DEPTH STIFFENER AT EACH SUPPORTED BEAM AND AT 48" OC MAX
C1
SECTION
3/4" = 1'-0"
C2
SECTION
3/4" = 1'-0"
C4
SECTION
3/4" = 1'-0"
VARIES
[SEE PLAN]
L2 1/2x2 1/2x1/4 x 12" LONG AT EACH CORNER AND AT 3'-0" OC MAX WITH (2) 1/2" x 4" HEADED STUDS 3/16 #3 HAIRPIN BAR @ 48" OC 16" MAX 8" RECESS SLAB 1/4" AT EA ANCHORAGE #4 BAR, CONT, EXTEND 2'-0" PAST EA CORNER 2'-6" 3/4"
L3 1/2x2 1/2x1/4 (LLV) 12" LONG WITH (2) 1 1/2" VERTICAL SLOTS FOR ANCHORS, 2" FROM EACH END 5/8" x 4" HEAVY SCREW ANCHOR AT TOP OF VERTICAL SLOT, BACK OFF 1/4 TURN AFTER INSTALLATION
1" 3/16 3/16 BOTTOM OF SHELF L4x4x1/4 [SEE ARCH] TOS HSS COL, SEE PLAN [SEE PLAN] 1/4 AT BF-12, STOP CHANNEL SHORT OF GUSSET PLATE OF BRACED FRAME BEAM, SEE PLAN L3x3x3/8 AT 2'-6" OC 1/4" FULL-DEPTH STIFFENER 3" NOTE: FOR ELEMENTS NOT NOTED, SEE A1/SF301. 1/4 1/4 1/4 1/4 3 3 STAIR 1-12 3-8 8" 1/4 C4x7.2 L6x6x3/8 CONT
1"
1/2" JOINT, FILL WITH FIRE CAULK 1/4 2-12 EA END, TYP CMU WALL, SEE PLAN 1/4" CONT PLATE
L3x3x1/4 AT EA STIFFENER SEE PLAN 1/4" STIFFENER ON EA SIDE OF BEAM WEB @ 36" OC MAX
2 2
EA END
MOMENT RESISTING CONNECTION, SEE "TYPICAL MOMENT CONNECTIONS" DETAIL ON SHEET SF501
B1
B2
B6
SECTION
3/4" = 1'-0"
G
1/4 L3x3x1/4 1/4" x 4' GUSSET PLATE 5'-8" A2 SF302 5'-8" TOC [SEE PLAN] 2-8 1 1 6" 4
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
[SEE PLAN] L6x4x5/16 LLV (2) 3/4" BOLTS, FINGER TIGHT, IN LONG VERT SLOTS WITH DOUBLE NUT TO PREVENT BACKING TOS [SEE PLAN]
TOS [SEE PLAN] L6x4x5/16, PART OF SHOP WELDED ANGLE FRAME 3/16 3/16 2 2
A1
A2
ELEVATION DETAIL
3/4" = 1'-0"
SF302
SHEET OF
E
BOND BEAM, SEE CMU WALL SCHEDULE ON SF601 CMU WALL SEE PLAN L6x3x1/4 (LLV) CONT WITH 1/2" CARBON STEEL SCREW ANCHOR WITH 4 1/4" EMBED @ 2'-0" OC CENTERED ON LOWER DECK FLUTE AT EA SIDE OF CMU WALL. FIT ANGLES SNUG TIGHT TO WALL.
BUILD CMU WITH 1" CLEAR GAP AROUND STEEL ANGLE BOND BEAM, SEE CMU WALL SCHEDULE ON SF601 CMU WALL SEE PLAN
INTERSECTION
INTERRUPT JOINT REINF AT CJ JOINT STABILIZING ANCHOR AT 16" OC RAKE JOINT AND SEAL, EA FACE
WALL OPENING
CL COLUMN L4x4x1/4" KICKER @ 4'-0" OC SEE PLAN 1" GAP SEE PLAN SLAB ON DECK, SEE PLAN TOP OF SLAB [SEE PLAN] TYPICAL SHEAR CONNECTION AT BEAM ENDS 3/16 TYP EA END STEEL COL, SEE PLAN 4'-0"
3'-0"
CONTROL JOINT
2"
WORKING POINT 1/2" ERECTION BOLT EA END 3/16 3/16 2L3x3x1/4 BRACE 3 3 EA END, TYP
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
BOND BEAM, SEE CMU WALL SCHEDULE ON SF601 1/4" PLATE, TYP. 3/8" CONT BENT PL CMU WALL SEE PLAN STEEL BEAM, SEE PLAN, TYP. 3/4" BOLT IN LONG LONGITUDINALLY SLOTTED HOLES IN BENT PL AT 2'-0" OC, SHOP ATTACHED. INSTALL BOLT IN MIDDLE OF SLOT 9" MAX 5/8" CARBON STEEL SCREW ANCHOR WITH 5" EMBED AT 24" OC IN LONG VERTICALLY SLOTTED HOLES IN BENT PLATE. BACK OFF SCREW 1/4" TO ALLOW SLIP
6"
3/8" GUSSET PLATE, TYP 3/16 3/16 10 MIN TYP 10 MIN NOTE: DO NOT WELD BRACE TO GUSSETS UNTIL ROOF TRUSSES AND DECK HAVE BEEN PLACED.
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
2-12
EDGE OF SLAB
2"
BOTTOM OF SHELF
C
3"
BOND BEAM REINF. WITH 1-#4 BAR EXTEND REINFORCING 0'-8" MIN BEYOND OPENING. REINF. W/2-#5 BARS AT COMMONS, EXTENDED 1'-4" BEYOND OPENING.
L7x4x3/8 SHELF ANGLE, GALV, CONT, WITH 3/16" GAP BETWEEN SEGMENTS. PROVIDE HORIZ SLOTS, 1 1/2" LONG, FOR BOLTS AT 32" OC AND AT ENDS, COORD WITH WEDGE INSERTS
7/ 1 6"
ADDITIONAL VERTICAL WALL REINFORCING TOP REINFORCING, SEE LINTEL SCHEDULE BOTTOM OF LINTEL [SEE ARCH] W SEE LINTEL SCHEDULE FOR SIZE AND REINFORCING BOTTOM REINFORCING, SEE LINTEL SCHEDULE D
NOT TO SCALE
0" TYP
NOTE: VENEER MASONRY AND ANGLE LINTELS NOT SHOWN FOR CLARITY
GROUT SOLID 24" DEEP x16" WIDE 2 ADDITIONAL BARS AS SHOWN, SAME SIZE AS CONT REINF 1'-4" BRG 1'-4" BRG
SECTION
PLAN AT CORNER
EXTERIOR COLUMN LINES A AND K: WIND LOAD = 0.6 KIP SEISMIC LOAD = 0.15 KIP PER BRACING BAY, MIN 6 BAYS EA LINE CJP CJP
WIDTH 'W'
8" 8"
REINFORCING
2-#4 BOTTOM 2-#6 BOTTOM
DRAG TRUSS IS COMPRISED OF MULTIPLE BRACING BAYS, SEE PLAN FOR EXTENTS
33/ 6 4"
CFS CHANNEL BRACES, EA WAY AT EA PANEL WITH MIN FOUR #12 SCREWS, EA END. FASTEN TO EA INTERMEDIATE STUD. SIZE MEMBER AND FASTENING FOR LOAD.
BRICK VENEER CONTROL JOINT, SEE ARCH DWGS VENEER, SEE ARCH DWGS 2-12 2-12
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description
AT BEAM/GIRDER - TYPE 1
STEEL ANGLE 5" MIN 5" MIN CJP TYPICAL SHEAR CONNECTION CJP TOP OF OPENING [SEE ARCH] ANGLE LINTEL TOP OF OPENING [SEE ARCH] FOM 3/4" 6 1/2" STEEL ANGLE
NOTES: 1. 2. 3. 4. PROVIDE 8" MINIMUM BEARING AT EACH END OF ANGLE. TOE OF ANGLE SHALL BE LOCATED 3/4" FROM FACE OF BRICK. FOR EXACT SIZE AND LOCATION OF WALL OPENINGS, COORDINATE WITH ARCHITECTURAL DRAWINGS. ANGLE LINTEL SCHEDULE APPLIES ONLY TO ANGLE LINTELS NOT OTHERWISE SHOWN ON THE STRUCTURAL DRAWINGS. ANGLE LINTELS IN EXTERIOR WALLS SHALL BE HOT-DIP GALVANIZED. AT BRICK VENEER CONTROL JOINT, FORM SLIP PLANE BY PLACING FLASHING ABOVE AND BELOW ANGLE. PROVIDE 1/4" GAP AT EACH END OF ANGLE FOR THERMAL EXPANSION.
CFS TRACK, BOTTOM OF PANEL, WITH FASTENERS SPACED NO MORE THAN 6" OC.
1/4" MIN COVER PLATE TOP AND BOTTOM, SIZED BY FABRICATOR TO RESIST MOMENTS INDICATED ON PLAN STEEL BEAM, SEE PLAN
8" BRG CANTILEVER BEAM TYPICAL SHEAR CONNECTION BACKSPAN BEAM, WHERE SHOWN
8" BRG
ANGLE LINTEL
5. 6.
ELEVATION
SECTION
AT BEAM/GIRDER - TYPE 2
AT COLUMN
SF501
SHEET OF
TYPICAL VERTICAL REINFORCING MOW (IF SPACING IS LESS THAN CLEAR SPAN)
1/2" DIA A307 ERECTION BOLT AT EA END OF EA SLAB EDGE SEGMENT AT 48" MAX IN TRANSVERSE SLOTS
4
4"x4" - 68 MIL CONTINUOUS BENT RIDGE PLATE BETWEEN TRUSSES, ALTERNATE WITH OPEN SPACE TO ALLOW VENTILATION. CONNECT TO EACH TRUSS WITH (4) #12 SCREWS.
BEARING WALL
COLD-FORMED STEEL BRACING IN VERTICAL PLANE CENTERED ON BRACED STEEL FRAME BELOW
CONTINUOUS 362S162-43 STEEL STUD BRACING FOR LIGHT GAGE STEEL TRUSS BOTTOM CHORD (SPACE 10'-0" OC MAX AT BOTTOM CHORD PANEL POINTS) "VERT" 362S162-43 STEEL STUD CROSS BRACING OF WEB MEMBERS AT EACH ROW OF BOTTOM CHORD BRACING. LOCATE AT ENDS OF THE BOTTOM CHORD BRACING AND REPEAT AT 20'-0" OC (MAX) INTERVALS. 362S162-43 STEEL STUD BOTTOM CHORD DIAGONAL BRACING. LOCATE AT END OF BUILDING AND REPEAT AT 30'-0" OC (MAX) INTERVALS. PROVIDE 362S162-43 STEEL STUD CROSS BRACING AT 20'-0" OC AT PERMANENT CONTINUOUS LATERAL BRACING AS SPECIFIED BY THE TRUSS ENGINEER. COLD-FORMED STEEL ROOF TRUSS
E
3
1 3 2
LAP ALL LATERAL BOTTOM CHORD BRACES OVER A MINIMUM OF 2 TRUSSES. ALL CONNECTIONS SHOULD BE MADE WITH (3) SELF DRILLING SCREWS FOR DIAGONAL BRACING, AND (2) SELF DRILLING SCREWS FOR LATERAL BRACING.
BEARING WALL
NOTE: TRUSS MANUFACTURER SHALL DESIGN TRUSS-TO-BEARING CONNECTIONS FOR UPLIFT AS WELL AS 500 LBS MIN SHEAR AT EACH TRUSS-TO-BEARING CONNECTION ALONG EXTERIOR SUPPORTS
NOTE: TRUSS MANUFACTURER SHALL DESIGN COMPLETE BRACING SYSTEM AND PROVIDE PLANS AND DETAILS OF BRACING AS PART OF SHOP DRAWING SUBMITTAL. STEEL COLUMN STEEL BEAM
CONNECT COLD-FORMED STEEL DRAG TRUSS TO STEEL BEAM WITH 15 K SHEAR CAPACITY IN PLANE OF BRACED FRAME OVER LENGTH OF BRACED FRAME
STEEL COLUMN
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
12"
2'- 0"
STEEL ROOF DECK, SEE PLAN CENTER LINE OF SUPPORT REINFORCING PLATE, WELD OR SCREW TO ADJACENT RIBS AROUND OPENING FFE
1 1/ 2"
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
36/7 PATTERN
DECK PENETRATION, SEE MECH AND PLUMBING FOR SIZE AND LOCATIONS
36/5 PATTERN FASTENER, TYP ROOF DECK OR COMPOSITE FLOOR DECK FASTENERS AROUND PERIMETER OF BUILDING PENETRATE SLAB AT THIN SECTIONS ONLY
36/4 PATTERN
36/3 PATTERN
(4) #3 x 48" LONG PLACED AT 45 DEG TO DECK DIRECTION 1-#5 IN EACH ADJACENT DECK RIB WHERE SLEEVE PENETRATION OCCURS - EXTEND MIN 30" EA END, OR 4" PAST METAL DECK SUPPORT BEAMS
36" COVER WIDTH OPENING SIZE UP TO 6" DIA 6" TO 14" 36" WIDE SHEETS TYP NOTE: SEE GENERAL STEEL DECK NOTES FOR STEEL DECK SIZE, GAGE, FASTENER SIZE, TYPE, AND PATTERN, AND SIDE LAP CONNECTIONS OVER 14" REINFORCING NOT REQUIRED 16 GA. PLATE NOTES NOT REQUIRED SEE DETAIL ABOVE NOTE:
PENETRATIONS THROUGH SLAB IN THE OTHER DIRECTION (ALL WITHIN METAL DECK RIB) SHALL BE SPACED AT 3x PIPE (OR SLEEVE) DIAMETER ON CENTER, MINIMUM, EXCEPT AS PROVIDED IN "TYPICAL SLAB PENETRATION - MULTIPLE OPENINGS" DETAIL, THIS SHEET. PROVIDE STRUCTURAL SUPPORT FOR METAL DECK WHERE REQUIRED DUE TO CONDUIT OR SLEEVE PENETRATIONS.
CL BEAM 30" MIN SPACING SEE FRAMING PLAN SHEAR STUDS IN STRONG POSITION SHEAR STUDS IN STRONG POSITION
TYP
3/16 3/16
OPENING
CONT POUR STOP AT SLAB STEEL FLOOR DECK AND SLAB, SEE PLAN
REINFORCE DECK AROUND OPENINGS WITH 16 GA PLATE OPENING BLOCK OUT SLAB PENETRATIONS, DO NOT CORE SLAB. 8" DIA MAX. L4x4x1/4 FRAME AROUND OPENINGS, TYP NOTES: 1. WHERE DECK SPANS PERPENDICULAR TO BEAM, STUDS SHALL BE PLACED WITH ONE STUD IN ALTERNATE DECK FLUTES, STARTING AT ENDS. REMAINING REQUIRED STUDS SHALL BE PLACED, STARTING FROM ENDS, UNTIL TOTAL IS REACHED. USE SINGLE LINE OF STUDS, CENTERED OVER BEAM WEB, UNLESS MULTIPLE ROWS ARE NEEDED. STUD SPACING AT GIRDERS SHALL BE NO MORE THAN 24", NO LESS THAN 4 1/2", DISTRIBUTED EVENLY. WHERE MULTIPLE ROWS ARE NEEDED ON GIRDERS, STUDS SHALL BE STAGGERED 3" MIN. AXIS OF GROUP TO ALIGN WITH DIRECTION OF DECK RIBS
L5x5x5/16x0'-5" LONG EACH END OF L4x4, TYP JOIST OR BEAM, TYP STRONG POSITION 3. 4. 2.
STRONG POSITION
NOTE: SEE "TYPICAL SLAB PENETRATION" DETAIL, THIS SHEET, FOR SECTION AND OTHER ELEMENTS.
PLAN
SECTION A-A
TOPPING THICKNESS
HEADED STUD TYP, SEE GENERAL STEEL DECK NOTES WELDED WIRE FABRIC
CL GIRDER
#4x4'-0" AT 16" OC AT ALL GIRDERS SUPPORTING COMPOSITE BEAMS ON BOTH SIDES STEEL DECK
1/4 1/4
3 3
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
3/8" CAP PLATE AT TOP OF COLUMN
No.
Date
DECK HEIGHT
4"
MILL FINISHED FACE 3/4" CAP PLATE WITH (4) 3/4" ASTM A325 BOLTS 1/4" STIFFENER PLATE EACH SIDE
PJP
4"
AISC STANDARD SINGLE-PLATE SHEAR CONNECTION, TYP (BOTH SIDES IF APPLICABLE) NOTE: STEEL DECK OMITTED FOR CLARITY
AISC STANDARD SHEAR CONNECTION GIRDER, SEE PLAN FOR SIZE MILL FINISHED FACE
4"
SF502
SHEET OF
HSS6X6X5/16
HSS6X6X3/8
FOURTH FLOOR
O F 7U H R T
O F 7U H R T
11 2 " 6 1 / 7 '
THIRD FLOOR
R H D T I 6 11 2 " 6 1 / 5 '
HSS6X6X1/4
R H D T I 6
11 2 " 6 1 / 5 '
G I H 5G I H Y P O N A CH
11 6 " 5 1 '
G I H 5O N A C HO L Y PW
11 1 " 4 6 '
SECOND FLOOR
C E O S 4N D 11 2 " 6 1 / 4 3 '
C E O S 4N D
11 2 " 6 1 / 4 3 '
HSS6X6X5/16
HSS6X6X1/2
HSS8X6X5/8
HSS8X6X1/2
HSS6X6X5/8
HSS6X6X3/8
HSS6X6X3/8
HSS5X5X1/4
HSS5X5X3/8
HSS6X6X3/8
HSS5X5X1/2
HSS5X5X3/8
O L 3W O N A CG I H Y PH
HSS4X4X3/16
HSS4X4X3/16
HSS6X6X5/16
HSS5X5X1/2
HSS6X6X5/8
11 2 " 6 1 / 4 '
HSS6X6X5/16
HSS6X6X3/8
W10X33
HSS6X6X1/2
W10X33
L O 3 -W C A N O P L Y -W
11 2 " 6 1 / 3 '
FIRST FLOOR
T S R I F 2 11 2 " 6 1 / 3 '
T S R I F 2
11 2 " 6 1 / 3 '
W10X33
HSS4X4X3/16
HSS4X4X3/16
HSS4X4X3/16
W10X33
GROUND FLOOR
G 1R U O N D 11 0 " 2 '
HSS4X4X3/16
G 1R U O N D
300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
W10X33
11 0 " 2 '
BP-2
BP-2
BP-5
BP-1
BP-1
BP-4
BP-4
BP-7
BP-3
BP-6
BP-2
BP-2
BP-1
BP-2
BP-2
BP-2
BP-5
BP-1
BP-1
BP-4
BP-4
BP-8
BP-4
BP-1
BP-1
A-4
A-11
A-12
A.1-3, D.9-3
A.1-3.9, D.9-3.9
B-3, D-3
B-3.9, D-3.9
C-10
E-4
E-5
E-8, E-10
E-11, H.5-1
E-12
F-1, F-2
F-3.9
F-5
F-8
F.1-8.1
F.1-9
G-8.1
G-9, J-9
H-8
J-8.1
J.9-8.1
J.9-9
NOTES: 1. COLUMN SPLICES OCCUR AT LOCATIONS WHERE UPPER COLUMN SIZE AND LOWER COLUMN SIZE ARE INDICATED. SPLICE SHALL BE MADE AT AN ELEVATION OF 48" ABOVE TOP OF SECOND FLOOR SLAB. SEE "TYPICAL COLUMN SPLICE" DETAIL ON SF502. 2. SEE ANCHOR ROD AND BASE PLATE SCHEDULE ON SB501 FOR BASE PLATE TYPE.
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com
LENGTH 'N'
11 12 12 16 14 14 14 26
THICKNESS 't'
3/4 3/4 1 1-1/4 1 1-1/4 1-1/2 2
EMBEDMENT 'L'
9 9 12 12 16 24 24 16
PROJECTION 'P'
6" 6" 6" 7" 6" 8" 8" 8"
MARK
MW1
BP1
MARK
CW1 CW2 CW3 CW4
VERTICAL REINFORCING
#5 AT 14" OC, MOW #6 AT 9" OC, EF #5 AT 10" OC, EF #5 AT 10" OC, EF
HORIZONTAL REINFORCING
#5 AT 14" OC, MOW #6 AT 18" OC, EF #5 AT 10" OC, EF #5 AT 10" OC, EF
END REINFORCING
(6) #5, 1/2 EACH FACE WITH #3 TIES AT 8" OC N/A (4) #5, 1/2 EACH FACE WITH #3 TIES AT 8" OC (4) #5, 1/2 EACH FACE WITH #3 TIES AT 8" OC
A
BASE PLATE, SEE SCHEDULE 'P'
1 1/2"
N/2
1/4
PLAN A-A
CL COL
A
GUSSET PLATE, CENTER ON COLUMN
A
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW
Description
CL COLUMN AND BASE PLATE 2" GUSSET PL 4" 2" EQ EQ CL COL AND BASE PL EQ EQ B/2 2"
A
WALL END
WORKING POINT NUT WITH 2x2x1/2 PLATE WASHER, TYP TOF/TOP OF PIER [SEE PLAN] STEEL SHEAR LUG, 2" THICK x 14" LONG IN GROUTED POCKET 3 1/2" L 2" N P B
5"
2"
B/2
5"
5"
5"
5"
2"
CJP
5/16
N/2
N/2
ANCHOR ROD WITH HEAVY HEX NUT, TYP. SEE SCHEDULE. TACK TYP
SECTION A-A
NOTE: PROVIDE 2x2x1/2 PLATE WASHERS WITH STANDARD HOLE AT EACH ANCHOR ROD
S/2 S/2
S/2 S/2
SF601
SHEET OF
'L'
B/2
SCHEDULES