South Halls Estimating and Scheduling

Brett Miller AE 475 Professor Bechtel Estimating and Scheduling Assignment Friday October 19, 2012

Assumptions:
Excavation: *The Following numbers were acquired from the given plans and personal calculations* *The excavation volume was used to have no slope to the top Depth: 15 Feet Area: 1966.3 Square Feet Volume: 9831.66 Cubic Yards Backfill Volume: 552 Cubic Yards *Penn State uses Engineered Fill* Figure 1 shows the plan of excavation. The building footprint is shown in red and the excavation is shown in brown. Figure 1:

Retaining Wall Footing: Concrete Strength: 3000 pounds per square inch Wall Mark: WF4.0 Length: 298.125 linear feet Rebar: Occurrence: This footing uses #6 size and has 8 bars continuously running the length of the footing, 1 every 9 inches on center in the top of the footing and one every 18 inches on center in the bottom of the footing. Weight of individual #6 bar: 1.502 pounds per foot Total Length of #6: 298.125 linear feet Total Weight in entire footing: 6,273.75 pounds

Retaining Wall: Assume CW2 for entire Wall The Footing of this wall was factored in on the previous page and will not be included with the wall in ICE. The concrete strength, per the concrete notes, is 4000 pounds per square inch Rebar: This wall uses #6 size bars and has 1 bar every 9 inches on center running vertically and 1 bar every 18 inches on center running horizontally. Weight of individual #6 bar: 1.502 pounds per foot Total Height of #6: 14 feet Total Length of #6: 298.35 linear feet Total Weight in entire wall: 10,815.84 pounds Total Volume of entire wall: 206.3 cubic yards Density of reinforcing: 52.43 pounds per cubic yard

CMU Wall Footing Concrete has a strength of 3000 pounds per square inch. WF2.0: Rebar: Occurrence: This Footing uses #5 bars. It has 2 continuously running the length of the footing, and has 1 every 11 inches on center. Weight of individual #5 bar: 1.043 pounds per foot Total Length of #5: 49.83 linear feet Total Weight in entire footing: 217 pounds WF3.0: Rebar: Occurrence: This Footing uses #5 bars and has 4 continuously running the length of the footing, and has 1 every 7 inches on center. Weight of individual #5 bar: 1.043 pounds per foot Total Length of #5: 183.5 linear feet Total Weight in entire footing: 1,391 pounds CMU Wall: Assume CW1 for entire wall The Footing of this wall was factored in above and will not be included with the wall in ICE. Rebar: This wall uses #5 rebar running vertically on 14 inch centers and running horizontally on 14 inch centers as well. Weight of individual #5 bar: 1.043 pounds per foot Density of reinforcing: 30.88 pounds per cubic yard

Column Pier Footings: For the footings, F3.0, F4.0, F4.0x3.0, F4.5, F5.0, F5.5, F6.0, F6.5, F8.0, F9.5, were all used and are further described in table 5 Concrete has a strength of 3000 pounds per square inch Column Piers: For this part of the project, the piers P1, P4, P5 and P7 were used. These are further shown in Table 6 Concrete has a strength of 4000 pounds per square inch Slab On Grade: Concrete has a strength of 3000 pounds per square inch Area: 9,480 square feet Perimeter: 550 feet Thickness: 4 inches For reinforcement, welded wire fabric was used instead of rebar

Assumption Tables:
The following are tables used in the calculation process. Table 1: Retaining Wall Footing Retaining Wall Footing Concrete Mark WF4.0 Mark WF4.0 Width 4 0 A Bars (4) #6 CONT Thickness Total Length 1 6 298.125 Retaining Wall Footing Rebar B Bars #6 @9 OC C Bars (2) #6 CONT D Bars #6 @ 18 OC Total Volume (ft3) 1790.125 Length (ft) 298.35 Total Volume (yd3) 66.3 Weight (lbs) 6273.75

Table 2: Retaining Wall Retaining Wall Concrete Mark CW2 Mark CW2 Thickness (in) 16 Height (ft) Length (ft) Volume (ft3) Volume (yd3) 206.3 Density (lb/yd3) 52.43

14 298.35 5569.2 Retaining Wall Rebar Vertical Horizontal Total Height Total Weight Reinforcing Reinforcing (ft) Length (ft) (lbs) #6 @ 9 OC #6 @ 18 OC 14 298.35 10815.84

Table 3: CMU Wall Footing CMU Wall Footing Mark WF2.0 WF3.0 Total Mark WF2.0 WF3.0 Total Table 4: CMU Wall CMU Wall Rebar Horizontal Total Reinforcing Height (ft) #5 @ 14 OC 14 Width 2 0 3 0 Thickness 1 0 1 4 Total Length 49.83 183.5 Total Volume (ft3) 99.66 734 833.66 Total Volume (yd3) 3.69 27.19 30.88 Weight (lbs) 217 1391 1608

CMU Wall Footing Rebar A Bars B Bars Length (ft) (2) # 5 CONT #5 @ 11 OC 49.83 (4) #5 CONT #5 @7 OC 183.5

Mark CW1

Vertical Reinforcing #5 @ 14 OC

Total Length (ft) 233.33

Weight (lbs) 7949.86

Density (lb/yd3) 30.88

Table 5: Column Pier Footings Column Piers Footing Concrete Mark F3.0 F4.0 F4.0X3.0 F4.5 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 Total Mark F3.0 F4.0 F4.0X3.0 F4.5 F5.0 F5.5 Volume (yd3) 0.444 0.79 0.59 1 1.388 2.054 2.444 2.869 4.346 6.128 A Bars (5) #5 (7) #5 (5) #5 (8) #5 (7) #6 (7) #7 Width 3 0 4 0 3 0 4 6 5 0 5 6 6 0 6 6 8 0 9 6 Length 3 0 4 0 4 0 4 6 5 0 5 6 6 0 6 6 8 0 9 6 Thickness 1 4 1 4 1 4 1 4 1 6 1 10 1 10 1 10 1 10 1 10 Quantity 8 9 1 4 4 7 6 3 1 8 Total Volume (yd3) 3.556 7.11 0.59 4 5.552 14.378 14.667 8.607 4.346 49.024 111.83 Weight (lbs) 31.29 58.41 44.85 75.1 105.14 157.39

Column Piers Footing Rebar B Bars C Bars D Bars (5) #5 N/A N/A (7) #5 N/A N/A (7) #5 N/A N/A (8) #5 N/A N/A (7) #6 N/A N/A (7) #7 N/A N/A

Length (ft) 3 4 3, 4 4 6 5 0 5 6

F6.0 F6.5 F8.0 F9.5 Total

(8) #7 (8) #7 (10) #7 (12) #7

(8) #7 (8) #7 (10) #7 (12) #7

N/A (8) #7 N/A (12) #7

N/A (8) #7 N/A (12) #7

6 0 6 6 8 0 9 6

196.22 425.15 327.04 932.06 2352.65

Table 6: Column Piers Column Piers Concrete Quantity Width Depth Height Volume (ft3) Volume (yd3) 9 2 0 2 0 3 0 108 4 2 1 4 1 4 3 0 10.67 0.395 1 2 0 2 6 3 0 15 0.56 1 2 0 2 6 3 0 15 0.56 Column Pier Rebar Reinforcing Weight (lbs) Volume (yd3) Density (lbs/yd3) (8) #8 64.08 0.44 145.64 (12) #6 54.07 0.198 273.08 (8) #7 49.06 0.56 87.61 (12) #8 96.12 0.56 171.64

Mark P1 P4 P5 P7 Mark P1 P4 P5 P7

Table 7: Slab On Grade Concrete Thickness (in) Slab on Grade 4 Area (ft2) 9480 Volume (ft3) 3160 Volume (yd3) 117

South Halls Estimate Detail - Standard Construction Project


Detail - Without Taxes and Insurance Estimator : Project Size : sqft ItemCode Description Quantity UM Lab.Unit Mat.Unit Eqp.Unit Sub.Unit Eqp.Rent.Unit Temp.Mat.Unit Other Unit Tot.UnitCost TotalCost Note Group 1: Divisions

Sitework
02310.103 CUT & FILL DIRECT ON SITE 02310.107 ENGINEERED FILL 02310.112 EXCAV-LOAD-HAUL SURP 4-5MILES 02310.143 CUT-LOAD-HAUL VEG 4-5 MILES 02310.199 * CUT & FILL AREA * 02316.001 FINE GRADE FLOOR BY HAND 02316.021 Road gravel slab fill 02316.100 MACH EXCAV CONTINUOUS FTG 02316.100 MACH EXCAV CONTINUOUS FTG 02316.100 MACH EXCAV CONTINUOUS FTG 02316.102 FINE GRADE CONTINUOUS FTG 02316.102 FINE GRADE CONTINUOUS FTG 02316.102 FINE GRADE CONTINUOUS FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.110 MACH EXCAV COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02316.112 FINE GRADE @ COLUMN FTG 02830.150 **RETAINING WALL CONCRETE** 02830.155 4000 PSI CONC POUR DIRECT 02830.300 RE-STEEL RETAINING WALL 02830.400 POINT & PATCH 02830.501 FOOTING KEYWAYS 02830.522 RETAINING WALL FORMS 12-14' 02830.540 FORM RELEASE AGENT 02830.541 WALL FORM HARDWARE 02830.702 BITUMINOUS COATING 2-COATS 02830.890 * RETAINING WALL LENGTH * * Total Sitework 550.00 550.00 9,260.00 300.00 1,966.00 9,480.00 175.56 100.04 7.68 45.79 1,192.50 99.66 550.50 9.85 15.96 8.32 1.48 10.89 26.69 26.07 14.71 6.79 71.83 72.00 144.00 81.00 12.00 100.00 211.75 216.00 126.75 64.00 722.00 206.22 108.12 8,353.80 298.35 8,353.80 8,353.80 4,176.90 4,176.90 298.35 CUYD CUYD CUYD CUYD SQYD SQFT CUYD CUYD CUYD CUYD SQFT SQFT SQFT CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT **** CUYD CWT SQFT LNFT SQFT SQFT SQFT SQFT LNFT 1.7891 0.9779 2.9585 2.9921 0.4046 0.1183 6.9549 6.9549 6.9549 0.4761 0.4761 0.4761 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 6.9549 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 0.4761 14.6787 32.3636 0.1102 0.5761 3.2013 0.2226 0.6952 1.600 0.500 3.700 3.700 3.389 1.478 6.659 6.692 0.405 4.674 7.905 7.905 7.905 0.476 0.476 0.476 7.905 7.905 7.905 7.905 7.905 7.905 7.905 7.905 7.905 7.905 0.476 0.476 0.476 0.476 0.476 0.476 0.476 0.476 0.476 0.476 70.679 59.114 0.117 0.810 4.577 0.246 0.102 0.887 1,864.01 812.85 61,657.71 2,007.63 3,835.61 820.62 790.82 60.70 361.97 567.75 47.45 262.09 77.88 126.16 65.81 11.68 86.08 210.96 206.08 116.32 53.67 567.78 34.28 68.56 38.56 5.71 47.61 100.81 102.84 60.35 30.47 343.74 14,575.02 6,391.28 974.05 241.51 38,236.18 2,051.69 427.71 3,705.75 142,047.73

4.470

0.086 0.950 0.950 0.950

0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950

RET Footing WF2.0 CMU Footing WF3.0 CMU Footing RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5

56.000 26.750 0.006 0.233 1.376 0.023 0.102 0.192

Concrete
03110.510 03110.510 03110.510 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 03110.520 CONTINUOUS FOOTING EDGE FORMS CONTINUOUS FOOTING EDGE FORMS CONTINUOUS FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS COLUMN FOOTING EDGE FORMS 906.38 103.66 497.21 127.68 191.52 95.76 18.62 120.00 281.82 263.95 142.97 58.66 SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT SQFT 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 4.4257 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 1.039 Page 1 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 5.464 4,952.80 566.44 2,716.95 697.69 1,046.54 523.27 101.75 655.73 1,539.98 1,442.34 781.27 320.52 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 10/18/2012 10:14 PM

X:\AE 475\Estimating and Scheduling Assignment\ICE\South Halls.est

South Halls Estimate Detail - Standard Construction Project


Detail - Without Taxes and Insurance Estimator : Project Size : sqft ItemCode Description Quantity UM Lab.Unit Mat.Unit Eqp.Unit Sub.Unit Eqp.Rent.Unit Temp.Mat.Unit Other Unit Tot.UnitCost TotalCost Note Group 1: Divisions

03110.520 COLUMN FOOTING EDGE FORMS 557.23 03111.348 WOOD PIER FORMS 18.00 03111.348 WOOD PIER FORMS 2.66 03111.348 WOOD PIER FORMS 2.25 03111.348 WOOD PIER FORMS 2.25 03150.650 SCREEDS FOR SLAB 1,137.60 03150.900 FORM RELEASING AGENT 18.00 03150.900 FORM RELEASING AGENT 2.66 03150.900 FORM RELEASING AGENT 2.25 03150.900 FORM RELEASING AGENT 2.25 03210.155 PIER REBAR 0.04 03210.155 PIER REBAR 0.01 03210.155 PIER REBAR 03210.155 PIER REBAR 0.01 03210.200 CONTINUOUS FOOTING REBAR 62.74 03210.200 CONTINUOUS FOOTING REBAR 2.17 03210.200 CONTINUOUS FOOTING REBAR 13.91 03210.210 COLUMN FOOTING REBAR 2.50 03210.210 COLUMN FOOTING REBAR 5.26 03210.210 COLUMN FOOTING REBAR 3.00 03210.210 COLUMN FOOTING REBAR 0.45 03210.210 COLUMN FOOTING REBAR 4.21 03210.210 COLUMN FOOTING REBAR 11.02 03210.210 COLUMN FOOTING REBAR 11.77 03210.210 COLUMN FOOTING REBAR 12.75 03210.210 COLUMN FOOTING REBAR 3.27 03210.210 COLUMN FOOTING REBAR 74.56 03220.011 6x6 W2.1/W2.1 MESH 104.28 03310.150 **CONC IN CONTINUOUS FOOTING** 03310.150 **CONC IN CONTINUOUS FOOTING** 03310.150 **CONC IN CONTINUOUS FOOTING** 03310.151 3000 PSI DIRECT 66.25 03310.151 3000 PSI DIRECT 3.69 03310.151 3000 PSI DIRECT 27.18 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.200 **CONC IN COLUMN FOOTING** 03310.201 3000 PSI DIRECT 3.55 03310.201 3000 PSI DIRECT 7.09 03310.201 3000 PSI DIRECT 3.99 03310.201 3000 PSI DIRECT 0.59 03310.201 3000 PSI DIRECT 5.56 03310.201 3000 PSI DIRECT 14.35 03310.201 3000 PSI DIRECT 14.66 03310.201 3000 PSI DIRECT 8.60 03310.201 3000 PSI DIRECT 4.34 03310.201 3000 PSI DIRECT 49.02 03310.350 **CONC IN SLAB ON GRADE** 03310.351 3000 PSI DIRECT 117.04 03310.750 **CONCRETE IN PIERS** 03310.750 **CONCRETE IN PIERS** 03310.750 **CONCRETE IN PIERS** 03310.750 **CONCRETE IN PIERS** X:\AE 475\Estimating and Scheduling Assignment\ICE\South Halls.est

SQFT SQFT SQFT SQFT SQFT LNFT SQFT SQFT SQFT SQFT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT CWT SQS **** **** **** CUYD CUYD CUYD **** **** **** **** **** **** **** **** **** **** CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD CUYD **** CUYD **** **** **** ****

4.4257 1.0476 1.0476 1.0476 1.0476 0.9219 0.2095 0.2095 0.2095 0.2095 23.7333 23.7333 23.7333 23.7333 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 31.7857 22.0080

1.039 1.161 1.161 1.161 1.161 0.320 0.023 0.023 0.023 0.023 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 26.750 10.650

5.464 2.208 2.208 2.208 2.208 1.242 0.233 0.233 0.233 0.233 50.483 50.483 50.483 50.483 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 58.536 32.658

3,044.94 39.75 5.87 4.97 4.97 1,412.79 4.19 0.62 0.52 0.52 2.04 0.38 0.17 0.33 3,672.38 127.02 814.23 146.53 307.72 175.84 26.25 246.18 644.91 689.15 746.59 191.44 4,364.70 3,405.58

F9.5 P1 P4 P5 P7 P1 P4 P5 P7 P1 P4 P5 P7 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5 F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5

11.0090 11.0090 11.0090

55.000 55.000 55.000

66.009 66.009 66.009

4,373.10 243.65 1,794.02

11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090 11.0090

55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000 55.000

66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009 66.009

234.11 468.22 263.38 39.02 366.72 947.36 967.96 568.00 286.80 3,235.48 7,725.50

P1 P4 P5 P7 Page 2 10/18/2012 10:14 PM

South Halls Estimate Detail - Standard Construction Project


Detail - Without Taxes and Insurance Estimator : Project Size : sqft ItemCode Description Quantity UM Lab.Unit Mat.Unit Eqp.Unit Sub.Unit Eqp.Rent.Unit Temp.Mat.Unit Other Unit Tot.UnitCost TotalCost Note Group 1: Divisions

03310.775 4000 PSI DIRECT 03310.775 4000 PSI DIRECT 03310.775 4000 PSI DIRECT 03310.775 4000 PSI DIRECT 03315.971 * CONTINUOUS FOOTING LENGTH * 03315.971 * CONTINUOUS FOOTING LENGTH * 03315.971 * CONTINUOUS FOOTING LENGTH * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.972 * NO. OF COLUMN FOOTINGS * 03315.976 * SOG AREA * 03350.130 MACHINE TROWEL FINISH 03350.131 POINT & PATCH 03350.131 POINT & PATCH 03350.131 POINT & PATCH 03350.131 POINT & PATCH 03390.010 PROTECT & CURE * Total Concrete

0.03 CUYD CUYD CUYD CUYD 298.13 LNFT 49.83 LNFT 183.50 LNFT 8.00 EACH 9.00 EACH 4.00 EACH 1.00 EACH 4.00 EACH 7.00 EACH 6.00 EACH 3.00 EACH 1.00 EACH 8.00 EACH 9,480.00 SQFT 9,480.00 SQFT 18.00 SQFT 2.66 SQFT 2.25 SQFT 2.25 SQFT 9,480.00 SQFT

16.0131 16.0131 16.0131 16.0131

56.000 56.000 56.000 56.000

72.013 72.013 72.013 72.013

2.00 0.20 0.28 0.28

P1 P4 P5 P7 RET Footing WF2.0 CMU Footing WF3.0 CMU Footing F3.0 F4.0 F4.5 F4x3 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5

0.3304 0.1102 0.1102 0.1102 0.1102 0.1102

0.013 0.013 0.013 0.013 0.019

0.330 0.123 0.123 0.123 0.123 0.129

3,132.19 2.21 0.33 0.28 0.28 1,226.71 61,303.90

P1 P4 P5 P7

Masonry
04210.011 MORTAR 04210.201 STANDARD SIZE FACE BRICK 04219.990 * MASONRY WALL AREA * 04220.102 FILL VOIDS W/ CONCRETE 04220.504 12X8X16 CONC BLOCK 04224.122 MASONRY REBAR 04930.011 CLEAN FACE BRICK * Total Masonry 15.37 21.40 3,266.62 32.48 3,674.95 25.55 3,266.62 CUYD M SQFT CUYD PCS CWT SQFT 566.9517 20.5520 2.5690 20.5520 0.4060 50.000 135.000 55.000 0.945 26.750 50.000 701.952 75.552 3.514 47.302 0.406 768.26 15,019.21 2,454.29 12,913.77 1,208.71 1,326.25 33,690.49

Thermal and moisture protection


07140.011 WATERPROOFING ON MASONRY 07260.012 6MIL VISQUEEN SUBGRADE PAPER * Total Thermal and moisture protection Total Direct Cost 3,266.62 SQFT 104.28 SQS 0.4983 1.1018 0.358 2.900 0.857 4.002 2,798.51 417.31 3,215.82 240,257.94

X:\AE 475\Estimating and Scheduling Assignment\ICE\South Halls.est

Page 3

10/18/2012 10:14 PM

South Halls Activity ID A1000 A1010 A1020 A1030 A1040 A1050 A1060 A1070 A1080 A1090 A1100 A1110 A1120 A1130 A1140 A1150 A1160 A1170 A1180 A1190 A1200 A1210 A1220 A1230 A1240 Activity Name Excavation Formwork - Retaining Wall/Column Footings Rebar - Retaining Wall/Column Footings Pour - Retaining Wall/Column Footings Cure - Retaining Wall/Column Footings Strip Formwork Formwork - Retaining Wall Rebar - Retaining Wall Pour - Retaining Wall Cure - Retaining Wall Strip Formwork Backfill Formwork - Column Piers Rebar - Column Piers Pour - Column Piers Cure - Column Piers Strip Formwork Formwork - CMU Wall Footings Rebar - CMU Wall Footings Pour - CMU Wall Footings Cure - CMU Wall Footings Strip Formwork Build - CMU Wall Installation - Welded Wire Fabric Pour - Slab On Grade

Classic Schedule Layout Original Remaining Schedule % Start Duration Duration Complete 11 5 5 2 5 2 7 7 2 5 2 5 5 5 2 5 1 5 5 2 5 2 10 4 3 11 5 5 2 5 2 7 7 2 5 2 5 5 5 2 5 1 5 5 2 5 2 10 4 3 100% 07-May-12 100% 21-May-12 100% 25-May-12 100% 01-Jun-12 100% 04-Jun-12 100% 08-Jun-12 100% 11-Jun-12 100% 19-Jun-12 100% 27-Jun-12 100% 28-Jun-12 100% 05-Jul-12 100% 06-Jul-12 100% 12-Jul-12 100% 20-Jul-12 100% 26-Jul-12* 100% 27-Jul-12 100% 02-Aug-12 100% 02-Aug-12 100% 08-Aug-12 100% 14-Aug-12 100% 15-Aug-12 100% 21-Aug-12 100% 22-Aug-12 100% 05-Sep-12 100% 10-Sep-12 Finish 21-May-12 25-May-12 01-Jun-12 04-Jun-12 08-Jun-12 11-Jun-12 19-Jun-12 27-Jun-12 28-Jun-12 05-Jul-12 06-Jul-12 12-Jul-12 18-Jul-12 26-Jul-12 27-Jul-12 02-Aug-12 02-Aug-12 08-Aug-12 14-Aug-12 15-Aug-12 21-Aug-12 22-Aug-12 05-Sep-12 10-Sep-12 12-Sep-12 Resources

19-Oct-12 00:31

Actual Work Remaining Work

Critical Remaining ... Milestone

Page 1 of 2

TASK filter: All Activities Oracle Corporation

South Halls Budgeted Total Cost $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 Total Float May 2012 06 13 20 27 03 Excavation June 2012 10 17 24

Classic Schedule Layout July 2012 01 08 15 22 29 05 August 2012 12 19 26 02 September 2012 09 16 23 30

19-Oct-12 00:31 October 2012 07 14 21

Formwork - Retaining Wall/Column Footings Rebar - Retaining Wall/Column Footings Pour - Retaining Wall/Column Footings Cure - Retaining Wall/Column Footings Strip Formwork Formwork - Retaining Wall Rebar - Retaining Wall Pour - Retaining Wall Cure - Retaining Wall Strip Formwork Backfill Formwork - Column Piers Rebar - Column Piers Pour - Column Piers Cure - Column Piers Strip Formwork Formwork - CMU Wall Footings Rebar - CMU Wall Footings Pour - CMU Wall Footings Cure - CMU Wall Footings Strip Formwork Build - CMU Wall Installation - Welded Wire Fabric Pour - Slab On Grade

Actual Work Remaining Work

Critical Remaining ... Milestone

Page 2 of 2

TASK filter: All Activities Oracle Corporation

Gantt Chart Narrative


I arbitrarily decided that this project would begin May 7th, 2012; the first normal work day after Penn States finals week. To begin my schedule, I started with the 9,831.66 cubic yard excavation which includes building space along with strip and spread footings. Once done with excavation, the work on the strip and spread footing was able to commence. The work, including framing, placing rebar, pouring concrete, allowing the concrete to cure, and striping the formwork, was estimated to take a total of nineteen days. The strip and spread footing are able to be completed simultaneously due to their differing locations on site. After these footings were complete, the retaining wall was able to be formed, have its rebar placed, be poured, cure, and have its forms striped. After the wall was up the backfill was poured in. Once the backfill was done, the column piers went through the same process of being formed, have their rebar placed, be poured, cure, and have their forms striped. Now that the column piers were complete, the CMU wall footing was formed, reinforced, poured, cured and striped of its form. With the foundation done, the CMU was next to go up. Lastly, with all of the walls in, there was no need to form the slab on grade so the welded wire fabric was laid down and the concrete poured. The durations for these activities were subjectively assumed.

References:
1. The entire footprint was used from SB 101 2. Details A1 and A3 were used from page SB 301 3. Details D1, D2, and D4 were used from SB 302 4. Footing Schedule Column, Footing Schedule Wall, and Pier Schedule were all used from SB 501 5. CMU Wall Reinforcing Schedule and Concrete Wall Reinforcing Schedule were both used from SF 601

*These references were used throughout the assignment*

STRUCTURAL LEGEND GENERAL NOTES


1. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL OTHER DRAWINGS. COORDINATE THE WORK OF OTHER TRADES INCLUDING, BUT NOT LIMITED TO THE REQUIREMENTS FOR SLEEVES, INSERTS, HOLES, HANGERS, AND ANCHORS. ELEVATIONS ON THE STRUCTURAL DRAWINGS ARE DENOTED AS [X-X] REFERENCED TO THE FINISHED GROUND FLOOR ELEVATION DATUM. REPORT DISCREPANCIES IN DIMENSIONS BETWEEN DIFFERENT DRAWINGS TO THE OWNERS REPRESENTATIVE PRIOR TO BEGINNING WORK IN AREAS THAT WILL BE AFFECTED. DETAILS ENTITLED OR NOTED AS TYPICAL APPLY NOT ONLY WHERE SPECIFICALLY INDICATED OR REFERENCED, BUT ALSO IN ALL OTHER CASES WHERE THE NATURE OF THE CONSTRUCTION REQUIRES THEIR USE. DETERMINE APPLICABILITY OF TYPICAL DETAILS FROM DESCRIPTIVE TITLES OR FROM THE SIMILARITY OF A CONSTRUCTION CONDITION TO ANOTHER CONDITION WHERE THE DETAIL IS SPECIFICALLY INDICATED OR REFERENCED. THE STRUCTURAL DRAWINGS CONTAINED HEREIN REPRESENT THE FINISHED STRUCTURE. PROVIDE ALL TEMPORARY GUYING AND BRACING REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL ALL STRUCTURAL WORK, INCLUDING CONNECTIONS, IS COMPLETE. THE ANALYSIS, DESIGN, SAFETY, ADEQUACY, AND INSPECTION OF ERECTION BRACING, SHORING, AND OTHER TEMPORARY SUPPORTS ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. CONSTRUCTION MEANS, METHODS, TECHNIQUES, AND SEQUENCES AND SUPERVISION OF THE WORK ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP DRAWINGS UNDER ANY CIRCUMSTANCE. 8. 3. 4. 5. 5. 6. 7. 6. 7.

STRUCTURAL ABBREVIATIONS SYMBOL


AB AFF

CONCRETE NOTES
1. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THE AMERICAN CONCRETE INSTITUTE (ACI) SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301-08). 2. CAST-IN-PLACE CONCRETE SHALL ATTAIN THE FOLLOWING MINIMUM 28-DAY COMPRESSIVE STRENGTHS (f'c):

STEEL NOTES
1. FABRICATION AND ERECTION OF STRUCTURAL STEEL AND DESIGN OF CONNECTIONS SHALL BE IN ACCORDANCE WITH THE AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, DATED MARCH 9, 2005 AND THE AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES, DATED MARCH 18, 2005. UNLESS OTHERWISE NOTED, STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE ABOVE-LISTED AISC SPECIFICATION AND THE FOLLOWING: A. B. C. D. E. F. G. H. 3. SQUARE AND RECTANGULAR HSS ROUND HSS WIDE FLANGE SHAPES AND TEES CHANNELS AND S-SHAPES PLATES AND ANGLES HIGH STRENGTH BOLTS ANCHOR RODS W/ NUT AND WASHER THREADED ROD ASTM A500, GRADE B, Fy = 46 KSI ASTM A500, GRADE B, Fy = 42 KSI ASTM A992 ASTM A36/A36M ASTM A36/A36M ASTM F1852 ASTM F1554, GRADE 36 ASTM A36/A36M

SYMBOL
Wn DN [X'-X"]

DESCRIPTION
WALL TYPE SLOPE DIRECTION SPOT ELEVATION DECK OR BAR GRATING SPAN INDICATES ELEVATION REFERENCED TO FINISHED GROUND FLOOR KEYED CONSTRUCTION NOTE COLUMN REFERENCE LINE (CENTERLINE OF COLUMN) BRICK

DESCRIPTION
ANCHOR BOLT ABOVE FINISHED FLOOR APPROXIMATELY ARCHITECTURAL BOTTOM OF CONCRETE BOTTOM OF STEEL BEARING COLD-FORMED STEEL SLAB CONSTRUCTION JOINT CENTER LINE CLEAR CONCRETE MASONRY UNIT COLUMN CONNECTION CONCRETE CONTINUOUS DOWELED CONSTRUCTION JOINT DIAMETER DOWN DRAWING EACH EACH FACE EXPANSION JOINT ELEVATION EDGE OF CORBEL EDGE OF SLAB EQUAL EACH WAY FINISHED FLOOR ELEVATION FACE OF BRICK FAR SIDE FOOTING GAGE GALVANIZED HORIZONTAL 1000 LBS LONG LONG LEG HORIZONTAL LONG LEG VERTICAL LONG SIDE HORIZONTAL LONG SIDE VERTICAL MAXIMUM MANUFACTURER MINIMUM MIDDLE OF WALL NOT IN CONTRACT NUMBER NOMINAL NEAR SIDE NOT TO SCALE ON CENTER OPPOSITE PREMOLDED JOINT FILLER PLATE POUNDS PER LINEAR FOOT POUNDS PER SQUARE FOOT REINFORCING REQUIRED SCHEDULE SLAB DEPRESSION

Architecture & Engineering

2. 3. 4.

2. A. B. C. D. E. WALLS AND PIERS COMPOSITE DECK FILL (LIGHTWEIGHT CONCRETE) SLAB-ON-GRADE FOOTINGS ALL OTHER CONCRETE 4000 4000 3000 3000 4000 PSI PSI PSI PSI PSI

APPROX ARCH BOC BOS BRG CFS CJ CL CLR CMU COL CONN CONC

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

CONCRETE DENSITY SHALL BE NORMAL WEIGHT UNLESS SPECIFICALLY OTHERWISE NOTED. CONCRETE REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. PROVIDE SHEET-TYPE WELDED WIRE FABRIC. SHEET LAPS SHALL BE TIED AND LAPPED ONE FULL MESH SPACING PLUS 2". CONCRETE REINFORCING STEEL SHALL BE CONTINUOUS UNLESS OTHERWISE INDICATED. CONTINUOUS REINFORCING STEEL SHALL BE LAPPED IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 318 AND SHEET SB502. 4. MINIMUM CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS INDICATED. IN NO CASE SHALL REINFORCING COVER BE LESS THAN THE REQUIREMENTS OF ACI 301. A. B. C. D. CONCRETE DEPOSITED AGAINST THE GROUND CONCRETE EXPOSED TO EARTH OR WEATHER BEAMS AND COLUMNS SLABS AND WALLS NOT EXPOSED TO EARTH OR WEATHER 3 2 1 1/2 1 5. 6.

ALL SHOP AND FIELD WELDING SHALL BE BY CERTIFIED WELDERS AND SHALL CONFORM TO AWS STANDARDS. USE E70XX ELECTRODES UNLESS NOTED OTHERWISE. CURRENT AWS CERTIFICATIONS SHALL BE AVAILABLE AT THE JOB SITE FOR REVIEW BY THE OWNERS REPRESENTATIVE. ALL BOLTED CONNECTIONS, UNLESS OTHERWISE NOTED, SHALL USE HIGH-STRENGTH BOLTS WITH HARDENED CARBON STEEL WASHERS AS REQUIRED FOR THE CONNECTION LOADS. FOR CONNECTIONS NOT DETAILED AND OTHERS REQUIRED BY THE ERECTION PROCEDURES, THE FABRICATOR SHALL SUBMIT DETAILS AND CALCULATIONS TO THE ENGINEER OF RECORD FOR APPROVAL. FIELD CUTTING OF STRUCTURAL STEEL MEMBERS BY ANY TRADE SHALL NOT BE PERMITTED. BOLT HOLES SHALL NOT BE CUT OR ENLARGED BY FLAME CUTTING IN THE FIELD. ALL FIELD-BOLTED SHEAR CONNECTIONS SHALL BE PRE-TENSIONED CONNECTIONS, THREADS INCLUDED IN THE SHEAR PLANE. CONNECTION DESIGN IS DELEGATED TO THE CONTRACTOR. SUBMIT CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE COMMONWEALTH OF PENNSYLVANIA ALONG WITH THE SHOP DRAWINGS FOR CONNECTIONS OTHER THAN SIMPLE SHEAR CONNECTIONS. SHEAR CONNECTIONS FOR BEAMS SUPPORTING FLOOR AND ROOF GRAVITY LOADS SHALL BE DESIGNED FOR THE FACTORED REACTIONS SHOWN ON THE DRAWINGS. FOR CONDITIONS WHERE REACTIONS ARE NOT INDICATED ON THE DRAWINGS, SHEAR CONNECTIONS SHALL BE DESIGNED FOR 50 PERCENT OF THE MAXIMUM TOTAL UNIFORM LOAD AS INDICATED IN THE LOAD TABLES OF PART 3 OF THE AISC STEEL CONSTRUCTION MANUAL, 13TH EDITION, FOR THE BEAM SIZE, SPAN AND GRADE OF STEEL SPECIFIED. IN NO CASE SHALL THE MINIMUM NUMBER OF BOLTS IN A SHEAR CONNECTION BE LESS THAN THAT INDICATED IN NOTE #10. MOMENT CONNECTIONS SHALL BE DESIGNED FOR THE MOMENTS INDICATED ON THE DRAWINGS AND THE SHEAR CAPACITY AS INDICATED IN NOTE #8, UNLESS OTHERWISE NOTED. MOMENT CONNECTIONS MAY BE WELDED OR BOLTED WITH SLIP-CRITICAL CONNECTIONS AT THE FABRICATORS OPTION.

[X'-X"] X

DESIGN NOTES
1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES AND SPECIFICATIONS: A. B. "PENNSYLVANIA UNIFORM CONSTRUCTION CODE" DATED DECEMBER 31, 2009 2009 INTERNATIONAL BUILDING CODE (IBC) 9.

CONCRETE REINFORCING STEEL MARKED STANDARD HOOK SHALL HAVE A 90-DEGREE HOOK UNLESS OTHERWISE NOTED. STIRRUPS, TIES, 180-DEGREE HOOKS, AND 90-DEGREE HOOKS SHALL CONFORM TO THE REQUIREMENTS OF ACI 318. PROVIDE 1/2" THICK JOINT FILLER MATERIAL WHERE SLABS-ON-GRADE ABUT VERTICAL SURFACES.

CONCRETE

CONT DCJ

7.

EARTH FILL

DIA, DN

10. ALL EMBEDDED ITEMS SHALL BE PROPERLY PLACED, ACCURATELY POSITIONED, AND MAINTAINED SECURELY IN PLACE PRIOR TO AND DURING CONCRETE PLACEMENT. 11. REINFORCING STEEL SHALL BE SPREAD AT SLEEVES, TIEBACKS, RECESSES, AND OTHER EMBEDDED ITEMS UNLESS OTHERWISE INDICATED. REINFORCING SHALL NOT BE CUT TO FACILITATE PLACEMENT OF EMBEDDED ITEMS. 12. NO CONCRETE SHALL BE PLACED UNTIL THE OWNER OR THE OWNERS DESIGNATED REPRESENTATIVE HAS INSPECTED ALL EMBEDDED WORK, INCLUDING REINFORCING. 13. ALL EXPOSED CONCRETE EDGES SHALL BE CHAMFERED 3/4" OR AS INDICATED. 14. ALUMINUM SHALL NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE UNLESS EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CONCRETE REACTION AND ELECTROLYTIC ACTION BETWEEN ALUMINUM AND STEEL. 15. PROVIDE ADDITIONAL CONCRETE REQUIRED TO ACHIEVE SPECIFIED FLOOR FLATNESS CRITERIA.

8.

GROUT

DWG EA

C. ASCE 7-05, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES D. AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS DATED MARCH 9, 2005 E. F. AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES DATED MARCH 18, 2005 ACI 318-08, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE

CONCRETE MASONRY UNIT (CMU) SLAB DEPRESSION MOMENT CONNECTION

EF EJ

9.

ELEV EOC EOS

G. ACI 530-08, BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES H. AISI NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS 2007 EDITION 2. DESIGN LOAD CRITERIA: A. LIVE LOADS (UNIFORM) ROOF ATTIC WALKWAYS PARTITION ALLOWANCE PRIVATE ROOMS AND CORRIDORS SERVING THEM PUBLIC ROOMS AND CORRIDORS SERVING THEM STAIRS AND EXITS STORAGE MECHANICAL/ELECTRICAL ROOMS TOILETS 30 PSF 40 PSF 15 PSF 40 PSF 100 PSF 100 PSF 125 PSF 125 PSF 100 PSF

10. BOLTED SHEAR CONNECTIONS FOR BEAMS SUPPORTING FLOOR, ROOF, AND STAIR GRAVITY LOADS SHALL CONTAIN A MINIMUM NUMBER OF HIGH STRENGTH BOLTS AS FOLLOWS. THE MINIMUM BOLT DIAMETER IS 3/4". WELDED WIRE FABRIC BEAM SIZE MINIMUM NUMBER OF ROWS OF BOLTS 2 3 4 5 6 7 10k END REACTIONS BEAM SIZE # SHEAR STUDS CAMBER W24x55 (16) C=1" (-2") 10k TOP OF STEEL ELEVATION RELATIVE TO TYPICAL TOS

EQ EW FFE FOB FS FST GA GALV HORIZ KIP (k) LG

MASONRY NOTES
1. ALL MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-08/ASCE 5-08/TMS 402-08) AND SPECIFICATION FOR MASONRY STRUCTURES (ACI 530.1-08/ASCE 6-08/TMS 402-08). DESIGN MASONRY ASSEMBLAGE STRENGTH, fm = 1500 PSI. NET AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY UNITS SHALL BE A MINIMUM OF 1900 PSI. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 AND BE MANUFACTURED WITH NORMAL WEIGHT AGGREGATE (OVEN-DRY UNIT WEIGHT=135 PCF, MAX). GROUT SHALL CONFORM TO ASTM C476 AND SHALL NOT CONTAIN ADMIXTURES. GROUT SHALL ATTAIN A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2000 PSI. GROUT POURS SHALL BE STOPPED 1-1/2 INCHES BELOW THE TOP OF A COURSE TO FORM A KEY AT POURED JOINTS. REINFORCING SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60 AND SHALL HAVE FABRICATION TOLERANCES IN ACCORDANCE WITH ACI 315. SHOP FABRICATE REINFORCING BARS WHICH ARE INDICATED TO BE BENT OR HOOKED.

W10 W12, W14 W16, W18 W21, W24

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

2. 3. 4.

W27 W30

NOTE: LIVE LOAD REDUCTION WAS USED IN THE DESIGN OF THIS STRUCTURE B. SNOW LOAD: GROUND SNOW LOAD, Pg SNOW EXPOSURE FACTOR, Ce THERMAL FACTOR, Ct SNOW LOAD IMPORTANCE FACTOR, Is FLAT ROOF SNOW LOAD, Pf SLOPED-ROOF SNOW LOAD, Ps C. WIND LOADS: BASIC WIND SPEED, V OCCUPANCY CATEGORY WIND IMPORTANCE FACTOR, I WIND EXPOSURE CATEGORY GUST EFFECT FACTOR, G INTERNAL PRESSURE COEFFICIENTS, GCpi 90 MPH II 1.00 B 0.85 0.18 9. 30 PSF 0.9 1.1 1.0 21 PSF 21 PSF 5. 6.

11. THE CONTRACTOR SHALL SUBMIT FOR APPROVAL DRAWINGS AND DESIGN CALCULATIONS FOR ANY ALTERNATE DETAILS AND MEMBER SPLICES. 12. SHOP OR FIELD SPLICES OF STRUCTURAL STEEL MEMBERS ARE PROHIBITED EXCEPT AS DETAILED ON THE DRAWINGS, PERMITTED IN THE SPECIFICATIONS, AS INDICATED ON APPROVED SUBMITTALS, AND AS SPECIFICALLY APPROVED ON SHOP DRAWINGS PRIOR TO FABRICATION. 13. PAINT ALL STEEL BELOW GRADE WITH TWO COATS OF COAL TAR EPOXY.

LLH LLV LSH LSV MAX MFR MIN MOW NIC NO. NOM NS NTS OC OPP PJF

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

7. JOINT REINFORCING SHALL BE LADDER-TYPE HOT-DIP GALVANIZED STEEL WIRE, LAPPED 8" AT ENDS. 8. LOCATE JOINT REINFORCING 16 INCHES ON CENTER VERTICALLY. PROVIDE ADDITIONAL REINFORCING AT THE TOP OF ALL FOUNDATIONS AND IN THE TWO JOINTS IMMEDIATELY ABOVE AND BELOW ALL OPENINGS. EXTEND JOINT REINFORCING A MINIMUM OF 24 INCHES BEYOND THE OPENING ON EACH SIDE. PLACE PIPES AND CONDUITS PASSING HORIZONTALLY THROUGH MASONRY IN STEEL OR PVC SLEEVES OR CORED HOLES UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

10. ALUMINUM CONDUITS, PIPES, AND ACCESSORIES SHALL NOT BE EMBEDDED IN MASONRY GROUT, OR MORTAR, UNLESS EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CEMENT CHEMICAL REACTION OR ELECTROLYTIC REACTION BETWEEN ALUMINUM AND STEEL. 11. UNLESS OTHERWISE NOTED OR DETAILED, CENTER WALL REINFORCING IN BLOCK CELLS. USE NONMETALLIC BAR POSITIONERS. 12. PROVIDE DOWEL REINFORCING FROM FOUNDATION OF SAME SIZE AND SPACING AS VERTICAL WALL REINFORCING. LAP WALL REINFORCING A MINIMUM OF 48 BAR DIAMETERS. 13. HORIZONTAL JOINT REINFORCING SHALL BE DISCONTINUOUS AT ALL CONTROL JOINTS. 14. HORIZONTAL BOND BEAM REINFORCING SHALL BE CONTINUOUS THROUGH ALL CONTROL JOINTS.

D. COMPONENTS AND CLADDING WIND PRESSURES:

DESIGN WIND PRESSURE FOR ROOF COMPONENTS (PSF)


C
COMPONENT TRIBUTARY AREA (ft2) ROOF ZONE 0 - 20 1 2 3 OVERHANG ZONE 0 - 20 2 3 10.0 10.0 -34.7 -34.7 21 - 100 10.0 10.0 -33.6 -33.6 10.0 10.0 101 + -31.5 17.2 17.2 17.2 -18.8 -21.9 -21.9 21 - 100 16.7 16.7 16.7 -17.7 -20.9 -20.9 15.6 15.6 15.6 101 + -15.6 -18.7 -18.7

PL PLF PSF

FOUNDATION NOTES
1. 2. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS IN THE GEOTECHNICAL REPORT PREPARED BY CMT LABORATORIES AND DATED OCTOBER 10, 2011 WITH MARCH 21, 2012 REVISIONS. FOUNDATIONS HAVE BEEN DESIGNED TO BEAR ON EXISTING NATURAL BEDROCK, CAPABLE OF SUPPORTING A NET ALLOWABLE DESIGN BEARING PRESSURE OF 8000 PSF. WHERE COMPETENT BEDROCK IS NOT ENCOUNTERED AT A FOOTING LOCATION, CONTACT STRUCTURAL ENGINEER OF RECORD FOR DESIGN OF A FOOTING ON FIRM NATURAL SOIL OR ENGINEERED FILL. PRIOR TO PLACING FOUNDATION CONCRETE, THE CONTRACTOR SHALL ENSURE THAT THE FOUNDATION EXCAVATIONS ARE INSPECTED BY AN INDEPENDENT TESTING LABORATORY AND GEOTECHNICAL ENGINEER REGISTERED IN THE COMMONWEALTH OF PENNSYLVANIA TO EVALUATE THE EXTENT OF LOOSE, SOFT OR OTHERWISE UNSATISFACTORY SOIL MATERIAL AND TO VERIFY THE DESIGN BEARING CAPACITY. SOILS NOT SUITABLE FOR FOUNDATION SUPPORT SHALL BE UNDERCUT AND REPLACED WITH ENGINEERED FILL AS RECOMMENDED IN THE GEOTECHNICAL REPORT. ADEQUATELY PROTECT FOUNDATION EXCAVATIONS TO PREVENT WATER FROM ACCUMULATING AND STANDING IN THE EXCAVATION BOTTOMS. FROST PROTECTION SHALL BE PROVIDED BY ERECTING FOOTINGS ON SOLID ROCK. WHERE SOLID ROCK IS NOT ENCOUNTERED, BOTTOM OF FOOTING SHALL EXTEND BELOW FROST LINE ELEVATION OF 42" BELOW GRADE. DO NOT PLACE FOUNDATION CONCRETE ON FROZEN OR SATURATED SUBGRADES.

REINF REQD SCHED SD SF SIM

COMPONENT TRIBUTARY AREA (ft2)

SIMILAR SLAB SAWED (CONTRACTION) JOINT SLAB-ON-GRADE STANDARD TOP AND BOTTOM TOP OF CONCRETE TOP OF FOOTING TOP OF MASONRY TOP OF STEEL THICKENED SLAB TYPICAL UNLESS OTHERWISE NOTED VERTICAL WORKING POINT WELDED WIRE FABRIC

3. -31.5

SJ SOG STD T&B TOC TOF TOM

4. 5. 6. 7. 8. 9.

COMPONENT TRIBUTARY AREA (ft2) WALL ZONE 0 - 20 4 5 NOTES: 1. 2. POSITIVE AND NEGATIVE SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY BUILDING ZONES ARE DEFINED IN ASCE 7 18.8 18.8 -20.3 -25.1 21 - 100 17.9 17.9 -19.4 -23.3 15.9 15.9 101 + -17.5 -19.5

TOS ENSURE THAT EARTH-FORMED FOOTINGS CONFORM TO THE SHAPE, LINES, AND THICKNESSES INDICATED ON THE FOUNDATION PLAN. EXCAVATION WIDTHS SHALL BE A MINIMUM OF 4 INCHES GREATER THAN DIMENSIONS INDICATED. PLACE FOUNDATION CONCRETE THE SAME DAY EXCAVATIONS ARE MADE OR AS SOON AS PRACTICAL THEREAFTER. DO NOT INSTALL FOUNDATIONS UNTIL FOUNDATION WORK HAS BEEN COORDINATED WITH ADJACENT UNDERGROUND UTILITIES AND STRUCTURES. TS TYP UON VERT WP WWF

10. FOOTINGS SHALL BE LOWERED AS REQUIRED TO PASS UNDER UTILITY LINES. STEP CONTINUOUS FOOTINGS DOWN AS SHOWN IN THE TYPICAL STEPPED FOOTING DETAIL ON SHEET SB501.

DESIGN WIND PRESSURE FOR PARAPETS (PSF)


WALL ZONE 4 5 NOTES: 1. 2. 3. E. STRENGTH DESIGN BASED ON 50-YEAR MEAN RECURRENCE INTERVAL DEFLECTION (SERVICEABILITY) DESIGN BASED ON 10-YEAR MEAN RECURRENCE INTERVAL DEFLECTION CRITERIA FOR COLD-FORMED STEEL STUDS IS H/600 (SIMPLY SUPPORTED) AND H/300 (CANTILEVERED) STRENGTH 53.4 53.4 DEFLECTION 37.7 37.7

DELEGATED ENGINEERED SYSTEMS


1. THE DESIGN RESPONSIBILITY FOR THE FOLLOWING ENGINEERED SYSTEMS AND COMPONENTS IS DELEGATED TO A QUALIFIED ENGINEER SELECTED BY THE CONTRACTOR. THESE SYSTEMS AND COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO: A. B. C. D. E. F. G. 2. 3. STRUCTURAL STEEL CONNECTIONS, INCLUDING BRACED FRAME CONNECTIONS COLD-FORMED STEEL FRAMING AND CONNECTIONS METAL STAIRS AND STAIR FRAMING PERMANENT LADDERS HANDRAILS AND GUARDRAILS GLAZING SYSTEMS FALL-PROTECTION SYSTEMS

SEISMIC LOADS: OCCUPANCY CATEGORY SEISMIC IMPORTANCE FACTOR, Ie SPECTRAL RESPONSE ACCELERATION, Ss SPECTRAL RESPONSE ACCELERATION, S1 SPECTRAL RESPONSE COEFFICIENT, SDs SPECTRAL RESPONSE COEFFICIENT, SD1 SITE CLASS SEISMIC DESIGN CATEGORY BASIC SEISMIC FORCE-RESISTING SYSTEM II 1.0 0.147g 0.049g 0.118g 0.055g C A STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE (IN COMBINATION WITH ORDINARY REINFORCED CONCRETE SHEAR WALLS AT GROUND STORY) 3 0.01W EQUIVALENT LATERAL FORCE FOLLOWING DESIGN REQUIREMENTS OF ASCE 7-05 SECTION 11.7

SUBMIT SHOP DRAWINGS FOR ALL DELEGATED ENGINEERED SYSTEMS AND COMPONENTS TO THE STRUCTURAL ENGINEER OF RECORD. ALL SUBMITTALS FROM THE DELEGATED ENGINEER MUST BE SUBMITTED TO THE ENGINEER OF RECORD PRIOR TO THE START OF FABRICATION OF THE SYSTEM OR COMPONENT PART AND PRIOR TO ANY FIELD CONSTRUCTION THAT MAY BE AFFECTED BY THE SYSTEM OR COMPONENT PART. DELEGATED ENGINEERED SYSTEMS SHALL MEET ASCE 7-05 REQUIREMENTS FOR WIND, SEISMIC, AND LIVE LOADS. REFERENCE APPLICABLE SPECIFICATIONS FOR REQUIRED SUBMITTALS TO BE SIGNED AND SEALED BY QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR DELEGATED ENGINEERED SYSTEMS AND COMPONENTS.

4. 5.

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

7/2/2012 9:16:35 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

RESPONSE MODIFICATION FACTOR, R DESIGN BASE SHEAR, V=CsW ANALYSIS PROCEDURE

F.

DESCRIPTION OF LATERAL LOAD-RESISTING SYSTEM: LATERAL LOAD-RESISTING SYSTEM AND STABILITY OF THE COMPLETED STRUCTURE IS PROVIDED BY STRUCTURAL STEEL BRACED FRAMES AT ALL FLOOR LEVELS AND ROOF LEVEL, IN COMBINATION WITH ORDINARY REINFORCED CONCRETE SHEAR WALLS AT THE GROUND FLOOR LEVEL. COMPOSITE CONCRETE SLABS AT FLOOR LEVELS ARE HORIZONTAL DIAPHRAGMS THAT DISTRIBUTE LATERAL WIND AND SEISMIC FORCES HORIZONTALLY TO THE COLLECTING ELEMENTS FOR THE BRACED FRAMES AND SHEAR WALLS. AT ROOF LEVEL, STEEL DECK SERVES AS A HORIZONTAL DIAPHRAGM THAT DISTRIBUTES HORIZONTAL LOADS TO COLLECTING ELEMENTS AND INTO THE BRACED FRAMES AT THE ROOF AND INTO THE MOMENT FRAMES AT THE VESTIBULE CANOPIES.

LEGEND, NOTES, AND ABBREVIATIONS

S-001
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

DESIGN WIND PRESSURE FOR WALL COMPONENTS (PSF)

PENN STATE NEW RESIDENCE HALL

STEPPED FOOTING

STEEL DECK NOTES


1. COMPOSITE FLOOR DECK SHALL BE GALVANIZED STEEL CONFORMING TO ASTM A653-07 WITH A MINIMUM YIELD STRENGTH OF 50 KSI. COMPOSITE FLOOR DECK SHALL BE 2" DEEP WITH 3.5" OF LIGHTWEIGHT CONCRETE TOPPING, MINIMUM; TOTAL SLAB THICKNESS = 5.5" MINIMUM. DECK RIBS SHALL BE SPACED AT 12" ON CENTER. COMPOSITE FLOOR DECK SHALL HAVE THE FOLLOWING MINIMUM SECTION PROPERTIES: A. B. C. D. t=0.0358 in (20 Gage) Ip=0.406 in4/ft Sp=0.341 in3/ft Sn=0.346 in3/ft

PREFABRICATED COLD-FORMED STEEL TRUSS NOTES


1. 2. TOP AND BOTTOM CHORDS SHALL CONFORM TO THE PROFILE AS INDICATED. THE TRUSS MANUFACTURER MAY VARY TRUSS TYPE AND MEMBER SIZE AS REQUIRED TO ACHIEVE SPAN AND ROOF PITCH SPECIFIED. DESIGN COLD-FORMED STEEL TRUSSES FOR THE FOLLOWING SUPERIMPOSED LOADS IN ADDITION TO THE LOADS INDICATED IN "DESIGN NOTES": A. TOP CHORD DEAD LOAD: B. BOTTOM CHORD DEAD LOAD: C. BOTTOM CHORD LIVE LOAD: 12 PSF 12 PSF 10 PSF + ATTIC WALKWAY LOADING

Architecture & Engineering

E
2.

ATTACH DECK TO SUPPORTS USING 3/4" x 4 3/16" LONG HEADED STUDS AT THE QUANTITY INDICATED ON THE FRAMING PLANS. WHERE STUD SPACING EXCEEDS 12" ON CENTER, WELD DECK TO SUPPORTS USING 5/8" PUDDLE WELDS AT 12" ON CENTER. SIDE LAP CONNECTIONS SHALL BE MADE WITH (3) #10 SCREW CONNECTIONS PER SPAN. FASTEN DISCONTINUOUS SIDE OF FLOOR DECK TO SUPPORTING STRUCTURE WITH 5/8" PUDDLE WELDS AT 12" ON CENTER UNLESS OTHERWISE NOTED. COMPOSITE ROOF DECK SHALL BE GALVANIZED STEEL CONFORMING TO ASTM A653-07 WITH A MINIMUM YIELD STRENGTH OF 50 KSI. COMPOSITE ROOF DECK SHALL BE 2" DEEP WITH 3" OF LIGHTWEIGHT CONCRETE TOPPING, MINIMUM; TOTAL SLAB THICKNESS = 5" MINIMUM. DECK RIBS SHALL BE SPACED AT 12" ON CENTER. COMPOSITE ROOF DECK SHALL HAVE THE FOLLOWING MINIMUM SECTION PROPERTIES: A. t=0.0358 in (20 Gage) B. Ip=0.406 in4/ft C. Sp=0.341 in3/ft D. Sn=0.346 in3/ft 3. ROOF DECK SHALL BE GALVANIZED STEEL CONFORMING TO ASTM A653-07 WITH A MINIMUM YIELD STRENGTH OF 33 KSI. STEEL ROOF DECK SHALL BE 1 1/2" DEEP WIDE RIB DECK WITH THE FOLLOWING MINIMUM SECTION PROPERTIES: A. B. C. D. t=0.0358 in (20 Gage) Ip=0.201 in4/ft Sp=0.234 in3/ft Sn=0.247 in3/ft

INCLUDE SECONDARY BENDING STRESSES DUE TO SUPERIMPOSED LOADS IN DESIGN OF CHORD MEMBERS. 3. LIMIT MIDSPAN DEFLECTION OF THE BOTTOM CHORD OF EACH TRUSS DUE TO LIVE LOAD TO SPAN/360 WITH A MAXIMUM OF 1. LIMIT MIDSPAN DEFLECTION OF THE BOTTOM CHORD OF EACH TRUSS DUE TO TOTAL LOAD TO SPAN/240 WITH A MAXIMUM OF 1. WHERE OVERLAY FRAMING IS INDICATED ON DRAWINGS, DESIGN TRUSSES SUPPORTING OVERLAY FRAMING FOR ADDITIONAL SUPERIMPOSED DEAD LOADS OF OVERLAY FRAMING. USE ACTUAL DEAD LOAD OF FRAMING AND SHEATHING (MINIMUM 10 PSF). PROVIDE PERMANENT CONTINUOUS LATERAL BRACING OF THE WEB AND CHORD MEMBERS IN ACCORDANCE WITH THE TYPICAL DETAIL ON SHEET SF502 IN THE LOCATIONS SPECIFIED BY THE TRUSS DESIGNER ON THE TRUSS SHOP DRAWINGS. DESIGN ROOF TRUSSES TO SUPPORT LOAD OF FALL PROTECTION SYSTEM. COORDINATE WITH FALL PROTECTION SYSTEM SHOWN ON SHEET AE141 AND LOADS PROVIDED BY FALL PROTECTION SUPPLIER.

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

4.

5. 6.

POST-INSTALLED ANCHORS
1. ALL POST-INSTALLED ANCHORS (IN CONCRETE OR CMU) ARE TO BE INSTALLED IN STRICT CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS (INCLUDING BUT NOT LIMITED TO DRILL BIT SIZE, PROPER CLEANING OF HOLES, INSTALLATION TORQUE, AND TEMPERATURE CONSTRAINTS). WHEN ADHESIVE ANCHORS ARE USED, REMOVE EXCESS ADHESIVE AT THE TOP OF THE HOLE BEFORE IT HARDENS. POST-INSTALLED ANCHORS SHALL BE INSTALLED AT NOT LESS THAN MINIMUM EDGE DISTANCES AND SPACINGS INDICATED IN THE MANUFACTURER'S LITERATURE. CONTRACTOR TO HAVE MANUFACTURER'S REPRESENTATIVE PERFORM PRODUCT INSTALLATION TRAINING ON SELECTED SYSTEMS. THE INDEPENDENT TESTING AGENCY SHALL PROVIDE THE INSPECTION OF ALL ANCHORS DURING INSTALLATION TO VERIFY CONFORMANCE WITH THE MANUFACTURER'S INSTALLATION RECOMMENDATIONS. CONFIRM THE ABSENCE OF REINFORCING STEEL BY DRILLING A 1/4" DIAMETER PILOT HOLE FOR EACH ANCHOR OR BY NONDESTRUCTIVE METHODS. DO NOT CUT REINFORCING STEEL WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL OBTAIN APPROVAL FROM STRUCTURAL ENGINEER OF RECORD PRIOR TO USING POST-INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST-IN-PLACE ANCHORS OR FOR SUBSTITUTIONS. CALCULATIONS FOR SUBSTITUTION REQUESTS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND STANDARDS AS REQUIRED BY THE BUILDING CODE. POST-INSTALLED ANCHORS IN CONCRETE SHALL BE SPECIFIED IN ACCORDANCE WITH ACI 318 APPENDIX D AND APPROPRIATE MANUFACTURER'S TABLES FOR ANCHOR PERFORMANCE VALUES AS DETERMINED FROM TESTING IN ACCORDANCE WITH ICC-ES ACCEPTANCE CRITERIA. CALCULATIONS FOR THE SELECTED ANCHOR SYSTEM SHALL BE PREPARED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER AND SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD. CALCULATIONS SHALL INCLUDE ANCHOR DIAMETER, EMBEDMENT DEPTH, ANCHOR MATERIAL, ADHESIVE MATERIAL (IF APPLICABLE), AND ANCHOR SYSTEM CAPACITY. AN ICC-ES-REPORT (ESR-XXXX) SHALL BE SUBMITTED THAT INDICATES ANCHORS HAVE BEEN DESIGNED AND TESTED FOR USE IN CRACKED CONCRETE. ALL ICC-APPROVED ANCHORS SHALL BE SUITABLE FOR SEISMIC AND WIND LOADS.

ROOF DECK SHALL BE FASTENED TO THE SUPPORTING STRUCTURE WITH #12 SELF-DRILLING SCREWS AT A 36/7 PATTERN. SIDE LAP CONNECTIONS SHALL BE MADE WITH #10 SELF-TAPPING SCREWS WITH FIVE SCREWS PER SPAN. FASTEN DISCONTINUOUS SIDE OF ROOF DECK TO SUPPORTING STRUCTURE WITH #12 SELF-DRILLING SCREWS, TWO PER DECK RIB, IN EACH DECK RIB. 4. 5. 6. WHERE 4 OR MORE SUPPORTS ARE PROVIDED, STEEL DECK SHALL SPAN CONTINUOUSLY OVER A MINIMUM OF 4 SUPPORTS (3-SPAN CONDITION), UNLESS OTHERWISE NOTED. ALL COMPOSITE STEEL FLOOR DECK IS DESIGNED AS UNSHORED CONSTRUCTION, UNLESS OTHERWISE NOTED. CONSTRUCTION JOINTS RUNNING PARALLEL TO BEAMS OR GIRDERS SHALL NOT COINCIDE WITH THE CENTER LINE OF THE BEAM OR GIRDER. CONSTRUCTION JOINTS RUNNING PERPENDICULAR TO BEAMS OR GIRDERS SHALL BE LOCATED AT APPROXIMATELY THE 1/3 POINT OF THE BEAM OR GIRDER SPAN. 14 GAGE RIDGE PLATES, VALLEY PLATES, AND MISCELLANEOUS METAL DECK ACCESSORIES SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR IN ACCORDANCE WITH THE DECK MANUFACTURER'S RECOMMENDATIONS. PERMANENT SUSPENDED LOADS SHALL NOT BE SUPPORTED BY STEEL ROOF DECK.

2. 3. 4. 5. 6.

7.

7.

8.

COLD-FORMED STEEL FRAMING NOTES


1. COLD-FORMED STEEL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE AMERICAN IRON AND STEEL INSTITUTE (AISI) "COLD-FORMED STEEL DESIGN MANUAL," 2008 EDITION, AND THE NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS, 2007 EDITION. ALL MATERIAL 18 GAGE OR LESS IN THICKNESS SHALL HAVE A MINIMUM YIELD STRENGTH OF 33 KSI. ALL MATERIAL 16 GAGE OR GREATER IN THICKNESS SHALL HAVE A MINIMUM YIELD STRENGTH OF 50 KSI. ALL COLD-FORMED STEEL SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A924. ALL CONNECTION SCREWS SHALL BE ZINC COATED. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3, "STRUCTURAL WELDING CODE-SHEET STEEL." SAW CUT STUDS AND JOISTS SQUARE AND SET WITH FIRM BEARING AGAINST THE CONNECTING MEMBER. THE CONTRACTOR SHALL PROVIDE TEMPORARY BRACING AND GUYING OF COLD-FORMED STEEL FRAMING TO PROVIDE FOR THE SAFETY OF THE STRUCTURE AND WORK PERSONNEL. BRACING SHALL REMAIN UNTIL NO LONGER REQUIRED FOR SAFE SUPPORT OF FRAMING. FIELD MODIFICATIONS OF COLD-FORMED STEEL SYSTEMS SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ENGINEER OF RECORD.

8.

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

9.

2. 3. 4. 5. 6. 7. 8.

10. MASONRY ANCHOR INSTALLATIONS ARE LIMITED TO ONE PER MASONRY CELL. 11. CONCRETE ANCHORS: A. MECHANICAL AND SCREW ANCHORS FOR USE IN CRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. B. ADHESIVE ANCHORS FOR USE IN CRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC308. C. GAS AND POWDER-ACTUATED FASTENERS FOR USE IN CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC70. 12. MASONRY ANCHORS: A. ANCHORAGE TO SOLID-GROUTED CONCRETE MASONRY: i. MECHANICAL AND SCREW ANCHORS FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC01 OR AC106, RESPECTIVELY. ii. ADHESIVE ANCHORS FOR USE IN SOLID-GROUTED CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. B. ANCHORAGE TO HOLLOW CONCRETE MASONRY/UNREINFORCED CLAY BRICK MASONRY: i. SCREW ANCHORS FOR USE IN HOLLOW CONCRETE MASONRY SHALL HAVE BEEN TESTED AND QUALIFIED IN ACCORDANCE WITH ICC-ES AC106. C. ADHESIVE ANCHORS WITH SCREEN TUBES SHALL BE TESTED AND QUALIFIED IN ACCORDANCE WITH ICC-ES AC58 OR AC60, AS APPROPRIATE. THE APPROPRIATE SCREEN TUBE SHALL BE USED AS RECOMMENDED BY THE ADHESIVE MANUFACTURER. D. ANCHORS SHALL BE CHOSEN TO RESIST MIN ALLOWABLE STRESS DESIGN (ASD) LOADS INDICATED ON DRAWINGS. ASD LOADS INDICATED TO NOT INCLUDE LOAD ADJUSTMENT FACTORS. 13. GAS AND POWDER-ACTUATED FASTENERS FOR USE IN CONCRETE, CMU, OR STEEL SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC70. NOTE: COORDINATE LOCATIONS OF WALL REINFORCEMENT WITH LOCATIONS OF POST-INSTALLED ANCHORS TO AVOID CONFLICT WHEN PLACING ANCHORS.

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

9.

10. CONNECTION REQUIREMENTS FOR COLD-FORMED MEMBERS ARE AS FOLLOWS, UNLESS OTHERWISE NOTED: CONDITION STUD-TO-TRACK TRACK TO STEEL BEAM CONNECTION (2) #10-16 SELF -DRILLING SCREWS WITH STUD SECURELY INTO TRACK 1/8" WELD EACH SIDE, 2" LONG SPACED AT 32" OC OR (2) 0.145" DIA POWDER ACTUATED FASTENERS AT 16" OC (2) 0.145" DIA POWDER ACTUATED FASTENERS THROUGH TRACK AT EACH STUD. PROVIDE 1 1/2" MINIMUM EMBEDMENT. MINIMUM SPACING = 4". CONCRETE EDGE DISTANCE = 3"

EXTERIOR STUD TRACK TO CONCRETE SLAB OR FOUNDATION

11. MAINTAIN 3/4" MINIMUM DISTANCE BETWEEN CENTERS OF CONNECTION SCREWS AND 3/4" MINIMUM DISTANCE FROM THE CENTER OF SCREW TO EDGE OF CONNECTED PART. INSTALL FASTENERS FROM THINNER THROUGH THICKER MATERIAL. 12. SUBMIT SHOP DRAWINGS TO THE DESIGN PROFESSIONAL FOR APPROVAL INDICATING ALL COLD-FORMED STEEL MEMBERS, CONNECTIONS, FASTENERS, OPENINGS AND OTHER COLD-FORMED STEEL RELATED ITEMS. 13. STUD MATERIAL INDICATED ON THE DRAWINGS SHALL HAVE A MINIMUM OF 1 5/8" FLANGES AND 1/2" STIFFENING RETURN LIPS. TRACK MATERIAL SHALL HAVE A MINIMUM OF 1 1/4" FLANGES (NO STIFFENING RETURN LIP). 14. MECHANICAL BRIDGING AT INTERVALS NOT EXCEEDING 4'-0" ON CENTER SHALL BRACE ALL LOAD-BEARING AND CURTAIN TYPE COLD-FORMED STEEL WALLS. BRIDGING SHALL BE IN PLACE PRIOR TO PLACING ANY LOADS ON THE STUD WALL. 15. CALCULATIONS FOR COLD-FORMED STEEL FRAMING ELEMENTS SHALL BE PREPARED AND SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE COMMONWEALTH OF PENNSYLVANIA AND SUBMITTED TO THE ENGINEER OF RECORD.

PENN STATE NEW RESIDENCE HALL


REVISIONS
No. Date

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:16:36 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt
Description

GENERAL NOTES
A

S-002
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

3
SCHEDULE OF SPECIAL INSPECTION - MASONRY

5
SCHEDULE OF SPECIAL INSPECTION - SPRAYED FIRE-RESISTANT MATERIALS

STATEMENT OF SPECIAL INSPECTIONS


PROJECT: PENN STATE NEW RESIDENCE HALL LOCATION: THE PENNSYLVANIA STATE UNIVERSITY, PENNSYLVANIA OWNERS REPRESENTATIVE: BARTON MALOW COMPANY OWNERS ADDRESS: UNIVERSITY PARK, PA 16802 ARCHITECT OF RECORD: CLARK NEXSEN ARCHITECTURE & ENGINEERING STRUCTURAL ENGINEER OF RECORD: CLARK NEXSEN ARCHITECTURE & ENGINEERING THIS STATEMENT OF SPECIAL INSPECTIONS IS SUBMITTED AS A CONDITION FOR PERMIT ISSUANCE IN ACCORDANCE WITH THE SPECIAL INSPECTION REQUIREMENTS (CHAPTER 17) OF THE INTERNATIONAL BUILDING CODE. THE STATEMENT INCLUDES A SCHEDULE OF SPECIAL INSPECTIONS APPLICABLE TO THIS PROJECT AS WELL AS THE REQUIRED QUALIFICATIONS FOR THE SPECIAL INSPECTOR AND AGENTS OF THE SPECIAL INSPECTOR TO PERFORM ON THIS PROJECT.

ITEM
1. MATERIAL CERTIFICATIONS

QUALIFICATIONS
SI

SCOPE
- COLLECT MIX DESIGN FOR MORTAR - COLLECT MIX DESIGN FOR GROUT - CERTIFICATES OF COMPLIANCE FOR MASONRY CONSTITUENTS

ITEM
1. MATERIAL VERIFICATION AND QUALITY CONTROL

QUALIFICATIONS
SCSI SFSI S-EIT SE SI

SCOPE
- COLLECTING PRODUCT DATA ON SPRAY-APPLIED FIREPROOFING MATERIALS USED ONSITE AND VERIFYING THAT MATERIAL USED MATCHES APPROVED PRODUCT - COLLECTING ANY MATERIAL CERTIFICATIONS AND ACQUIRING ICC-ES FOR PRODUCT TO GUIDE SPECIAL INSPECTIONS

Architecture & Engineering

2. MIXING OF MORTAR & GROUT

SI SMSI C-TECH1 S-EIT SI SMSI C-TECH1 S-EIT

- VERIFY: PROPORTIONS OF SITE-PREPARED MORTAR - PERIODIC INSPECTION OF SITE PREPARED MORTAR AND BATCHING PROCEDURE 2. VERIFYING COMPLIANCE WITH APPROVED CONSTRUCTION DOCUMENTS SPRAY APPLIED FIREPROOFING MATERIALS SCSI SFSI SE - ENSURE THAT SUBSTRATES MATCH SURFACE PREPARATION AND CONDITION SPECIFIED BY FIREPROOFING MANUFACTURERS INSTRUCTIONS 100% VISUAL INSPECTION AND PERIODIC VERIFICATION OF SUBSTRATE TEMPERATURE - VERIFY THICKNESS AND DENSITY OF APPLICATION ON NOT LESS THAN 25% OF PROTECTED STRUCTURAL MEMBERS PER FLOOR, AND NO FEWER THAN 2 MEMBERS PER FLOOR. MEASUREMENTS SHALL BE MADE AT 9 LOCATIONS AROUND EACH BEAM AT EACH END OF A 12-INCH LENGTH. FOR APPLICATIONS <1 THICK, MINIMUM ALLOWABLE THICKNESS AT ANY POINT SHALL BE 25% LESS THAN SPECIFIED. FOR THICKNESSES OF 1 OR MORE, MINIMUM ALLOWABLE SHALL BE LESS THAN SPECIFIED. THICKNESS SHALL BE DETERMINED ACCORDING TO ASTM E605 - VERIFY BOND STRENGTH/ADHESION OF SPRAY-APPLIED FIREPROOFING (NOT LESS THAN 150 PSF) THROUGH PERIODIC PULLOFF TESTING, ACCORDING TO ASTM E 736. RATE OF TESTING SHALL BE ONE MEMBER PER 2500 SQUARE FEET OF SPRAYED AREA IN EACH STORY, BUT NOT LESS THAN ONE PER STORY - OBSERVING CONDITION OF FINISHED APPLICATION - PRIOR TO GROUTING, VERIFY LOCATION, SIZE, EXTENT, AND LAPS OF REINFORCEMENT IN WALLS, INCLUDING REINFORCEMENT AT CORNERS, INTERSECTIONS, EACH SIDE OF OPENINGS, ABOVE AND BELOW OPENINGS, AT WALL ENDS, AT CONTROL JOINTS, AND WITHIN BOND BEAMS - PRIOR TO GROUTING, VERIFY TYPE, SIZE, AND LOCATION OF ALL ANCHORS, EMBEDS, AND OTHER DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS, FRAMES, OR OTHER CONSTRUCTION - INSPECTOR SHALL TAKE NOTE OF ANY LOCATIONS WHERE REINFORCING STEEL PLACEMENT CONFLICTS WITH INSTALLATION OF OTHER ELEMENTS SHOWN ON DRAWINGS, AND REPORT THESE BEFORE GROUTING 3.INTUMESCENT AND MASTIC FIRE-RESISTANT COATINGS SCSI SFSI S-EIT SE

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

THE SPECIAL INSPECTOR SHALL KEEP RECORDS OF ALL INSPECTIONS, FURNISH INSPECTION REPORTS, AND IDENTIFY DISCREPANCIES AS DETAILED BY PROJECT SPECIFICATIONS AND RFP. A FINAL REPORT OF SPECIAL INSPECTIONS, DOCUMENTING THE COMPLETION OF ALL REQUIRED SPECIAL INSPECTIONS AND CONFIRMING THE CORRECTION OF ANY DISCREPANCIES, WILL BE SUBMITTED PRIOR TO ISSUANCE OF A CERTIFICATE OF USE AND OCCUPANCY. THE SPECIAL INSPECTIONS PROGRAM DOES NOT RELIEVE THE CONTRACTOR OF HIS OR HER RESPONSIBILITIES. JOB SITE SAFETY AND MEANS AND METHODS OF CONSTRUCTION ARE SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. SCHEDULE OF SPECIAL INSPECTION THE FOLLOWING SHEETS COMPRISE THE REQUIRED SCHEDULE OF SPECIAL INSPECTIONS FOR THIS PROJECT. THE CONSTRUCTION DIVISIONS WHICH REQUIRE SPECIAL INSPECTIONS FOR THIS PROJECT ARE AS FOLLOWS. SOILS SPECIAL FOUNDATIONS CAST-IN-PLACE CONCRETE STRUCTURAL LOAD BEARING PRECAST CONCRETE POST TENSIONED CONCRETE STRUCTURAL MASONRY WOOD SHEAR WALLS STRUCTURAL STEEL SEISMIC DESIGN CATEGORY: A BASIC WIND SPEED: 90 MPH WIND EXPOSURE CATEGORY: B QUALIFICATIONS OF INSPECTORS AND AGENTS OF SPECIAL INSPECTORS SITE RETAINING WALLS COLD-FORMED STEEL FRAMING WALL PANELS AND VENEERS SPRAYED FIRE-RESISTANT MATERIALS EXTERIOR INSULATION & FINISH SYSTEM (EIFS) PROGRESSIVE COLLAPSE BLAST RESISTANCE QUALITY ASSURANCE FOR PROGRESSIVE COLLAPSE POST-INSTALLED CONCRETE AND MASONRY ANCHORS

3. INSTALLATION OF MASONRY

- INSPECTION OF CONSTRUCTION OF MORTAR JOINTS, PRIOR TO BEGINNING MASONRY CONSTRUCTION - PERIODIC VERIFICATION OF MORTAR JOINT CONSTRUCTION PROCEDURES, SIZE, CONFIGURATION, AND TOOLING - VERIFICATION OF SIZE, LOCATION, AND EXTENT OF GROUTING OF STRUCTURAL ELEMENTS, INCLUDING BOND BEAMS, LINTELS, REINFORCED CELLS, BEAMS, HEADERS, CORNERS, INTERSECTIONS, AND CORBELS

4. REINFORCEMENT INSTALLATION

SI SMSI C-TECH1 S-EIT

- PERIODIC INSPECTION OF JOINT REINFORCING IN MASONRY WALLS - PERIODIC INSPECTION OF LAP LENGTHS OF REINFORCING IN MASONRY WALLS

* TESTING SHALL BE IN ACCORDANCE WITH AWCI 12-B

SCHEDULE OF SPECIAL INSPECTION - POST-INSTALLED ANCHORS FOR MASONRY OR CONCRETE

5. GROUTING OPERATIONS THE QUALIFICATIONS OF ALL PERSONNEL PERFORMING SPECIAL INSPECTION ACTIVITIES ARE SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL. THE CREDENTIALS OF ALL INSPECTORS SHALL BE PROVIDED IF REQUESTED. WHEN THE STRUCTURAL ENGINEER OF RECORD DEEMS IT APPROPRIATE THAT THE INDIVIDUAL PERFORMING A STIPULATED TEST OR INSPECTION HAVE A SPECIFIC CERTIFICATION OR LICENSE AS INDICATED BELOW, SUCH DESIGNATION WILL APPEAR ON THE SCHEDULE OF SPECIAL INSPECTIONS. THE SPECIAL INSPECTOR (SI) SHALL BE A LICENSED PROFESSIONAL ENGINEER WITH A MINIMUM OF 3 YEARS OF EXPERIENCE AS A SPECIAL INSPECTOR. 1. 2. SE GE S-EIT G-EIT G-TECH 1 G-TECH 2 C-TECH 1 C-TECH 2 S-TECH 1 STRUCTURAL ENGINEER: A LICENSED PE OR SE SPECIALIZING IN THE DESIGN OF BUILDING STRUCTURES. GEOTECHNICAL ENGINEER: A LICENSED PE SPECIALIZING IN SOIL MECHANICS AND FOUNDATIONS. STRUCTURAL ENGINEER-IN-TRAINING: A GRADUATE ENGINEER WHO HAS PASSED THE FUNDAMENTALS OF ENGINEERING EXAMINATION, WITH EXPERIENCE IN THE DESIGN OF BUILDING STRUCTURES AND WORKING UNDER THE SUPERVISION OF A LICENSED STRUCTURAL PE OR SE. GEOTECHNICAL ENGINEER-IN-TRAINING: A GRADUATE ENGINEER WHO HAS PASSED THE FUNDAMENTALS OF ENGINEERING EXAMINATION, WITH EXPERIENCE IN SOIL MECHANICS AND FOUNDATIONS AND WORKING UNDER THE SUPERVISION OF A LICENSED GEOTECHNICAL PE. GEOTECHNICAL TECHNICIAN 1: AN EXPERIENCED TECHNICIAN WITH NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET): LEVEL 2 SOILS CERTIFICATION. 8. WELDING REBAR 6. 7. 8. 9. GEOTECHNICAL TECHNICIAN 2: AN EXPERIENCED TECHNICIAN WITH NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET): LEVEL 2 GEOTECHNICAL ENGINEERING CERTIFICATION. CONCRETE TECHNICIAN 1: AN EXPERIENCED TECHNICIAN WITH AMERICAN CONCRETE INSTITUTE GRADE I CONCRETE FIELD TESTING TECHNICIAN OR GRADE I CONCRETE LABORATORY TESTING TECHNICIAN CERTIFICATION. CONCRETE TECHNICIAN 2: AN EXPERIENCED TECHNICIAN WITH AMERICAN CONCRETE INSTITUTE GRADE II CONCRETE LABORATORY TESTING TECHNICIAN OR ICBO REINFORCED CONCRETE SPECIAL INSPECTOR CERTIFICATION. STEEL TECHNICIAN 1: AN EXPERIENCED AMERICAN WELDING SOCIETY CERTIFIED ASSOCIATE WELDING INSPECTOR (CAWI) OR NON-DESTRUCTIVE TESTING TECHNICIAN ASNT-TC-1A LEVEL I. STEEL TECHNICIAN 2: AN EXPERIENCED AMERICAN WELDING SOCIETY CERTIFIED WELDING INSPECTOR (CWI) OR NON-DESTRUCTIVE TESTING TECHNICIAN ASNT-TC-1A LEVEL II OR ICBO CERTIFIED STRUCTURAL STEEL AND BOLTING SPECIAL INSPECTOR. STEEL TECHNICIAN 3: AN EXPERIENCED TECHNICIAN WHO IS AN AMERICAN WELDING SOCIETY CERTIFIED WELDING INSPECTOR (CWI) WITH A MINIMUM OF10 YEARS OF WELD INSPECTION EXPERIENCE OR A NON-DESTRUCTIVE TESTING TECHNICIAN ASNT-TC-1A LEVEL III OR ICBO CERTIFIED STRUCTURAL WELDING SPECIAL INSPECTOR. STRUCTURAL MASONRY SPECIAL INSPECTOR: AN EXPERIENCED MASONRY INSPECTOR WHO IS AN ICBO CERTIFIED STRUCTURAL MASONRY SPECIAL INSPECTOR. ICBO CERTIFIED SPRAY-APPLIED FIREPROOFING SPECIAL INSPECTOR. ICBO CERTIFIED PRESTRESSED CONCRETE SPECIAL INSPECTOR. CONCRETE TECHNICIAN WITH POST TENSIONING INSTITUTE LEVEL 2 CERTIFICATION. INSPECTION/TESTING COMPANY WITH FIRE PROTECTION ENGINEERING EXPERIENCE, MECHANICAL ENGINEERING EXPERIENCE, AND CERTIFICATION AS AIR BALANCERS. 7. OBSERVATION EVALUATION OF MASONRY STRENGTH 6. WEATHER PROTECTION

SI SMSI C-TECH1 S-EIT

- PRIOR TO GROUTING, PERIODICALLY VERIFY CLEANLINESS OF GROUT SPACE - CONTINUOUS OBSERVATION OF THE PLACEMENT OF ALL GROUTING OF REINFORCED BUILDING WALLS, VERIFYING CORRECT EXTENT OF GROUTING - PERIODIC INSPECTION OF FULLY-GROUTED FOUNDATION WALLS AND WALL CAVITIES AT FOUNDATION, WHICH NEED NOT MEET REQUIREMENTS FOR CLEANLINESS OF GROUT SPACE

ITEM
1. MATERIAL VERIFICATION

QUALIFICATIONS
S-TECH 1 S-EIT SE SI S-TECH 1 S-EIT SE SI

SCOPE
- VERIFY AND RECORD PRODUCT DATA FOR 100% OF POST-INSTALLED ANCHORS, AND VERIFY THAT PRODUCT INSTALLED MATCHES APPROVED PRODUCT

3. 4. 5.

SI SMSI C-TECH1 S-EIT SI SMSI C-TECH1 S-EIT SI AWS-CWI

- PERIODICALLY VERIFY PROTECTION TECHNIQUES FOR MASONRY CONSTRUCTION BELOW 40F AND ABOVE 90F

2. POST-INSTALLED ANCHOR INSTALLATION

- VERIFY DRILL BIT TO BE USED, HOLE DEPTH, PREPARATION, AND CLEANING ACCORDING TO MANUFACTURERS INSTRUCTIONS CONTAINED IN ICC-ES REPORT 100% OF ANCHORS - OBSERVE PROCEDURES USED IN ANCHOR INSTALLATION, CHECK AMBIENT TEMPERATURE AND SURFACE TEMPERATURE PERIODICALLY, VERIFY THAT ANCHORS ARE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS 100% OF ANCHORS

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

- CONTINUOUS OBSERVATION OF THE PREPARATION OF GROUT SPECIMENS, MORTAR SPECIMENS AND/OR PRISMS

3. ANCHOR TORQUE

S-TECH 1 S-EIT SE SI

- WHERE ANCHOR TORQUE IS SPECIFIED, VERIFY TORQUE 100% OF ANCHORS

- CONTINUOUS INSPECTION BY AWS-CWI OF REBAR WELDING, VERIFYING THAT WELDABLE REINFORCING IS USED AND APPROPRIATE PROCEDURES ARE FOLLOWED

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

SCHEDULE OF SPECIAL INSPECTION - STRUCTURAL STEEL

ITEM
1. FABRICATOR CERTIFICATION/ QUALITY CONTROL PROCEDURES

QUALIFICATIONS
S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI

SCOPE
- ENSURE FABRICATOR IS AISC CERTIFIED PER CONTRACT DOCUMENTS TO SATISFY REQUIREMENTS OF IBC 1704.2.2 - COLLECT CERTIFICATE OF COMPLIANCE FROM FABRICATOR AT COMPLETION OF FABRICATION

10. S-TECH 2 11. S-TECH 3

12. SMSI 13. SFSI 14. PCSI 15. PTI 16. SCSI

2. WELDING

- COLLECT CERTIFICATE OF COMPLIANCE FOR WELD FILLER MATERIAL AND CONFIRM COMPLIANCE WITH CONTRACT DOCUMENTS - CONFIRM WELD FILLER MATERIAL IDENTIFICATION MARKINGS CONFORM TO AWS SPECIFICATION IN THE CONTRACT DOCUMENTS - CONTINUOUS VISUAL INSPECTION OF ALL COMPLETE AND PARTIAL PENETRATION WELDS - CONTINUOUS VISUAL INSPECTION OF ALL MULTIPLE PASS FILLET WELDS - CONTINUOUS VISUAL INSPECTION OF ALL SINGLE FILLET WELDS GREATER THAN 5/16"

C
SCHEDULE OF SPECIAL INSPECTION - SOILS (SPECIAL INSPECTION OF SOILS IS ONLY REQUIRED FOR SUBGRADE AND FILL PLACEMENT UNDER STRUCTURES REQUIRING SPECIAL INSPECTIONS.)

- PERIODIC (25% OF ALL) VISUAL INSPECTION OF FILLET WELDS 5/16 OR SMALLER - PERIODIC (25% OF ALL) VISUAL INSPECTION OF ROOF AND FLOOR DECK WELDS - PERIODIC (50% OF ALL) VISUAL INSPECTION OF WELDED REINFORCING STEEL

ITEM
1. SITE PREPARATION

QUALIFICATIONS
SI G-TECH S-EIT G-EIT GE SE

SCOPE

- PERIODIC INSPECTION OF TESTING OF FILL MATERIAL PLACEMENT INCLUDING PERIODIC OBSERVATION OF TESTING AGENCYS DENSITY TESTING METHODS AND FREQUENCY OF TESTING TO VERIFY COMPLIANCE WITH PROJECT SPECIFICATIONS/GEOTECHNICAL REPORT.

4. METAL DECK

S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI

- COLLECT MATERIAL DATA SHEETS FOR DECKING AND CONNECTORS OR FASTENERS - PERIODIC INSPECTION OF CONNECTIONS OF DECKING

SCHEDULE OF SPECIAL INSPECTION - CAST-IN-PLACE CONCRETE

5. BOLTING

- COLLECT MATERIAL DATA SHEETS FOR A325 AND A490 BOLTS, NUTS, AND WASHERS, AND CONFIRM COMPLIANCE WITH CONTRACT DOCUMENTS - COLLECT CERTIFICATE OF COMPLIANCE FROM BOLT SUPPLIER AT COMPLETION OF FABRICATION - PERIODIC (10% OF ALL) INSPECTION OF BOLTED CONNECTIONS TO CONFIRM BOLT MARKINGS CONFORM TO ASTM STANDARDS - PERIODIC (50% OF ALL) INSPECTION OF A325/A490 BOLTED (BEARING TYPE) CONNECTIONS - CONTINUOUS INSPECTION OF INSTALLATION OF A325/A490 BOLTED (SLIP CRITICAL) CONNECTIONS

ITEM
1. MIX DESIGN VERIFICATION

QUALIFICATIONS
SI C-TECH 1 C-TECH 2 S-EIT SE SI C-TECH 2 S-EIT SE

SCOPE
- COLLECT ACCEPTED MIX DESIGNS AND VERIFY APPROPRIATE MIX IS USED DURING SPECIFIC INSTALLATION

2.

REINFORCEMENT INSTALLATION

- PERIODIC INSPECTION OF REINFORCING STEEL AND WELDED WIRE FABRIC TO CONFIRM SIZE, SPACING, AND DETAILS CONFORM TO CONTRACT DOCUMENTS AT FOLLOWING FREQUENCY: - FOOTINGS AND FOUNDATIONS 50% OF ALL - FOUNDATION WALLS, BASEMENT WALLS, AND PEDESTALS 75% OF ALL - SLABS ON METAL DECK 50% OF ALL - COLUMNS AND SHEARWALLS 75% OF ALL - ELEVATED SLABS, JOISTS, AND BEAMS 75% OF ALL 6. MATERIAL CERTIFICATION S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI

- CONTINUOUS INSPECTION OF ALL PRE-TENSIONED BOLTS TO CONFIRM TENSIONING CONFORMS TO CONTRACT DOCUMENTS - COLLECT CERTIFIED MILL TEST REPORTS FOR ALL TYPES OF STRUCTURAL STEEL SPECIFIED IN THE CONTRACT DOCUMENTS AND CONFIRM COMPLIANCE WITH CONTRACT DOCUMENTS

3.

CONCRETE PLACEMENT/MONITORING FRESH CONCRETE, SAMPLING, & PREP OF TEST SAMPLES

SI C-TECH 2 S-EIT SE

- CONTINUOUS INSPECTION OF CAST-IN-PLACE CONCRETE PLACEMENT - CONTINUOUS MONITORING OF SAMPLING OF FRESH CONCRETE, SLUMP TEST, AIR CONTENT TEST, TEMPERATURE OF CONCRETE, AND CREATION OF STRENGTH TEST SPECIMENS SCHEDULE OF SPECIAL INSPECTION SERVICES - SITE RETAINING WALLS

ITEM
SI C-TECH 2 S-EIT SE - PERIODIC INSPECTIONS OF CURING TECHNIQUES - PERIODIC INSPECTIONS OF COLD AND HOT WEATHER CONCRETING TECHNIQUES ALL SITE RETAINING WALLS RETAINING MORE THAN 5-0 OF EARTH REQUIRE SPECIAL INSPECTIONS. THIS INCLUDES FOOTINGS AND WALLS. SEE APPROPRIATE MATERIAL SPECIAL INSPECTION SCHEDULES FOR SPECIFIC REQUIREMENTS.

4. CURING & PROTECTION

5.

CONCRETE STRENGTH VERIFICATION

SI C-TECH 2 S-EIT SE

- VERIFY WITH TESTING AGENCY REPORTS IN-SITU CONCRETE STRENGTH OF ELEVATED BEAMS AND SLABS PRIOR TO REMOVAL OF SHORINGS AND FORMS.

SCHEDULE OF SPECIAL INSPECTION - COLD-FORMED STEEL FRAMING

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

7/2/2012 9:16:36 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

ITEM
1. PLANT CERTIFICATION/ QUALITY CONTROL PROCEDURES

QUALIFICATIONS
S-EIT SE SI

SCOPE
- ENSURE FABRICATOR IS AISI AND SSMA CERTIFIED PER CONTRACT DOCUMENTS TO SATISFY REQUIREMENTS OF IBC 1704.2.2 - COLLECT CERTIFICATE OF COMPLIANCE FROM FABRICATOR AT COMPLETION OF FABRICATION

2. MECHANICAL CONNECTIONS

A
3. FRAMING DETAILS

S-EIT SE SI S-EIT SE SI

- PERIODIC INSPECTION (50% OF ALL) OF FIELD CONNECTIONS INCLUDING ANCHORAGE TO THE STRUCTURAL FRAME

- PERIODIC INSPECTION FRAMING AND DETAILS

S-003
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

- SITE STRIPPING AND SUBGRADE PREPARATION - FILL MATERIAL (ON-SITE AND/OR IMPORTED) CLASSIFICATION - FILL MATERIAL PLACEMENT (LIFT THICKNESS, MOISTURE CONTENT AND COMPACTION) - ALLOWABLE BEARING CAPACITY FOR FOOTINGS AND FOUNDATIONS

o 10% OF ALL BEAM-TO-BEAM CONNECTIONS o 25% OF ALL BEAM-TO-COLUMN CONNECTIONS o 50% OF ALL COLUMN SPLICE CONNECTIONS o 100% OF ALL CONNECTIONS OF MEMBERS WITHIN VERTICAL FRAMES

PENN STATE NEW RESIDENCE HALL

- COLLECT TESTING AGENCYS FIELD AND LABORATORY TEST REPORTS DURING SITE PREPARATION AND VERIFY THE FOLLOWING COMPLIES WITH THE PROJECT SPECIFICATIONS/GEOTECHNICAL REPORT:

3. STRUCTURAL DETAILS

S-TECH 1 S-TECH 2 S-TECH 3 S-EIT SE SI

- PERIODIC INSPECTION OF STEEL FRAMING JOINT DETAILS TO CONFIRM MEMBER SIZES AND CONNECTION DETAILS PER THE FOLLOWING:

SPECIAL INSPECTIONS

3
8" "B" BARS 1'-4" UON "C" BARS FINISHED GRADE (PAVING) SEE CIVIL 8" MIN [SEE CIVIL] FIN GRADE

PLAN NOTES
1. 2. 3. 4. NOTE: SITE WALLS ARE DESIGNED AS CANTILEVERED FOR FINAL BACKFILL CONDITIONS. CONTRACTOR TO ENSURE THAT BACKFILL IS EQUALIZED BELOW LOWER FINISHED GRADE ELEVATION ON EACH SIDE OF WALL BEFORE BACKFILLING REMAINING HEIGHT "H." MASONRY VENEER, SEE ARCH FINISHED GRADE SEE CIVIL ALL ELEVATIONS REFERENCED FROM GROUND FLOOR ELEVATION 1120-0 = [0-0]. TOP OF FOOTING ELEVATION SHALL BE [-1-4] UNLESS OTHERWISE NOTED. SPREAD FOOTINGS AND WALL FOOTINGS ARE NOTED ON PLAN AS FX.X AND WFX.X, RESPECTIVELY. SEE FOOTING SCHEDULES ON SFB501 FOR SIZE AND REINFORCING. SLAB ON GRADE SHALL BE 4 THICK REINFORCED WITH 6x6 W2.1xW2.1 WWF PLACED 1 1/2 BELOW TOP OF SLAB. PLACE SLAB ON 10 MIL VAPOR RETARDER OVER 6" OF COMPACTED PENNDOT 2A STONE. FOR TYPICAL FOUNDATION DETAILS, SEE SHEETS SB501 AND SB502. STEP FOOTINGS SO THAT UTILITIES PASS OVER TOP OF FOOTING AS PER TYPICAL DETAIL ON SHEET SB501. COORDINATE ALL FOOTING LOCATIONS WITH CIVIL, PLUMBING, AND ELECTRICAL DRAWINGS. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SAWED CONTROL JOINTS SPACED AT 15'-0" OC MAX WITH 1.5 MAX GRID ASPECT RATIO. JOINTS (SJ) MAY OPTIONALLY BE CONSTRUCTION JOINTS (CJ). SEE SHEETS SB501 AND SB502 FOR TYPICAL DETAILS. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501.

Architecture & Engineering

MASONRY VENEER, SEE ARCH

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

5. 8" "A" BARS, MOW 1'-4" "B" BARS, MOW FINISHED GRADE (PAVING) SEE CIVIL [SEE CIVIL] FIN GRADE 9. 7. 8. 6.

E
"B" BARS

30"

PENNDOT 2A STONE FILL "A" BARS

FINISHED GRADE SEE CIVIL

CLASS "B" LAP SPLICE, TYP SEE "TOP BAR TENSION REINFORCING" LAP SPLICE ON SB502
3'- 0"

10. SEE SHEETS SF201 AND SF202 FOR BRACED FRAME "BF-X' ELEVATIONS. 2x4 CONT KEYWAY B [SEE PLAN] TOF 1'-1" FTG LONGITUDINAL BARS 2x4 CONT KEYWAY GEOTEXTILE FILTER FABRIC WASHED STONE FILL T T EQ EQ [SEE PLAN] TOF #

KEY NOTES
DEPRESSED SLAB. SEE "TYPICAL SLAB ON GRADE DEPRESSION" ON SB502 SEE "TYPICAL THICKENED SLAB AT STAIR LANDING" ON SB502 SEE "TYPICAL THICKENED SLAB UNDER CMU WALL" ON SB502 HSS4x4x1/4 POST UNDER STAIR STRINGER BY STAIR ENGINEER. SEE "TYPICAL THICKENED SLAB AT STAIR LANDING" ON SB502 FOR SLAB THICKNESS AND REINFORCING OPENING IN SLAB FOR LINT TRAP, SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION GALVANIZED STEEL BAR GRATING WITH 1"x1/8" BEARING BARS AT 1 3/16" MAX SPACING AND 1/4" CROSS BARS AT 4" SPACING. SEPARATE BAR GRATING INTO FOUR REMOVABLE, EQUAL SECTIONS GALVANIZED STEEL LADDER IN MECHANICAL PIT, SEE ARCH FILL CAVITY BELOW GRADE WITH 3000 PSI CONCRETE, TYPICAL AT VESTIBULE

6" SLEEVE INVERT=[+6'-0"] 3" SLEEVE INVERT=[+8'-0"] 1 1/2" SLEEVE INVERT=[+7'-0"] 3" SLEEVE INVERT=[+7'-0"] 8" SLEEVE INVERT=[+7'-0"] 6" SLEEVE INVERT=[+6'-0"]

FTG TRANSVERSE BARS

FTG TRANSVERSE BARS FTG LONGITUDINAL BARS W W 6" PERFORATED DRAIN PIPE

1 2 3 4

DOWELS WITH STD 90 HOOK TO MATCH SIZE AND SPACING OF VERT WALL REINFORCING

TYPE 1 SITE WALL SCHEDULE


FOOTING REINFORCING WALL REINFORCING A #6 AT 12" OC #6 AT 12" OC #4 AT 12" OC #6 AT 12" OC #6 AT 12" OC B #4 AT 14" OC #4 AT 14" OC #4 AT 12" OC #4 AT 14" OC #4 AT 14" OC C #4 AT 10" OC #4 AT 10" OC MARK SW1 SW2 SW3 SW4 TYPE H (MAX) 1 1 2 1 1 7'-6" 4'-0" 10'-0" 8'-0" W 8'-0" 5'-0" 3'-0" 10'-0" 10'-0" B 2'-5" 1'-5" 3'-0" 6'-3" T 1'-10" 1'-6" 1'-4" 1'-10" 1'-10" LONGITUDINAL TRANSVERSE #4 AT 10" OC #4 AT 12" OC #4 AT 12" OC #4 AT 10" OC #4 AT 10" OC #6 AT 6" OC #6 AT 8" OC #4 AT 12" OC #6 AT 6" OC #6 AT 6" OC

TYPE 2
5

6" SLEEVE INVERT=[+6'-0"]

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

7 8

#4 AT 10" OC #4 AT 10" OC

D1

PLAN DETAIL
NOT TO SCALE NOT TO SCALE

SW5

TYPICAL RETAINING WALL DETAILS


[+1'-4"]

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

10
24'-3" 22'-11" [+5'-4"]
SW3

11
13'-6" 8'-3" 8'-10"

12

TOP OF CONCRETE WALL TO SLOPE 16" ABOVE TOP OF STAIR TREAD NOSING

1
24'-6" 18'-0"

2
14'-0" 11'-6"
SW3

3
9'-5"

3.9

4
1'-3" 16'-6"

5
8'-5" 2'-8" 2'-8"

6
8'-1" 14'-3" [ -6'-6" ]

7
16'-6" 2'-8" 2'-8" 2'-8" [ -4'-0" ] [ -5'-4" ] [ -2'-8" ] 7'-1"

8
1'-3"

8.1
9'-5"

9
14'-1"
[+6'-0"]

4'-0" SF SF

4'-0" SF

4'-0" SF SF

[+0'-8"]

4'-0" 8'-6" SW5 18'-6" SW2 1'-0" 6'-0" SW4

SW2

STAIR TREADS, SEE ARCH, TYP [-0'-8"]

10'-8" [+4'-0"]

[+2'-8"]

1'-0"
CW2

SF

A1 [ -4'-0" ] [ -5'-4" ] [ -2'-8" ] SB301 [ -2'-0" ] 6 P1 GALV W8X10 ( -0'-1" ) SF SF SF SF SF SF

A1 SB301

[-2'-0"]
CW2

4'-9" P1

[+ "] -0 6'

P1

P1

P1

F6.5

P1

1"

A
8'-4" 1'-4" SF

2'-0"

A.1

WF4.0 D1 SB101 2"

2'-6"

B5 CW2 F9.5 C3 SB301 2" DEEP SUMP SB301

SB301 F9.5 7 F9.5 2" 2"

SJ CW3 F9.5 5

WF4.0

F3.0 P3 2'-6" F4.0 P3

3'-0"

1'-4"

1'-0"

P5

A6

[ -2'-0" ] SF D1 SB302
[ -1'4" ]

[+ "] -0 6'

[+

"] -0 6'

SW3

1"

4'-8"

6'-0"

SF 4'-0" [+8'-0"] SF

13'-10"

4'-0"

16" CONCRETE SHEAR WALL 9'-4"

[+6'-8"] SF [+5'-4"] SF [+4'-0"]

[ +6'-0" ] 1"
[+ "] -0 6'

9'-10"

SJ, TYP 6" 10" WF4.0 F6.0 P7 F6.0 WF4.0 MW3 TS 8" CONCRETE SHEARWALL 6" F5.5 SJ, TYP F5.5 4" SOG SJ, TYP F5.0

4'-0"

2'-6 1/2"

7'-6"

6'-0"

SW2

4'-0"

4'-8"

SJ, TYP 8" SLEEVE INVERT=[-1'-7"]

D2 SB302

1'-8" CW3 WF4.0

[+2'-8"] SF 2'-6" [+1'-4"] SF


[+

[0'-0"]

4'-0"

14'-6"

P3 F4.0
6' -0 "]

1"

SJ, TYP SJ, TYP WF3.0


"] '-0 2 [-

SJ, TYP [ -2'-8" ] [ -3'-4" ] 2'-1"


2' -8 "]

8'-4"

F4.0x3.0 P3 P5 0" BF-4

SJ, TYP

A3 F5.5 2'-0" F4.0 SB301

D.9
1'-4" 10'-11"

F4.0

MW3 WF4.0

SF

1'-0"

[ -1'-4" ]

8'-8"

[ -4'-0" ]

CW2 4'-0"

SB301 P1

F9.5 F6.0 P1 CW2

SF [ -4'-0" ]

16'-0"

1'-0"

2'-2"

[ -2'-8" ]

[ -2'-8" ]

TS

D1 17'-2" SB302 4'-8"

TS

MW4

WF4.0

2'-8"

D4 SB302

F5.5 TS

F5.5

TS

P6

BF-8

2"

WF4.0

F3.0 SJ, TYP [ -1'-4" ] WF2.0 9'-4" 7'-5"

H
7'-0" 13'-4"

7'-6"

2"

MW2

1'-4 1/8"

1'-0"

6'-0"

TOC

8"

SF [ -1'-4" ]

MW1

8'-8"

MW2

F9.5 SJ

[+0'-6"]

SUMP ELEV PIT 8" CONCRETE SHEARWALL

1'-9"

2'-5 1/2"

1"

MW1

8" SLEEVE SF INVERT=[-3'-0"]

2"

F4.5

F4.0

[ -1 '-4

"]

SF [-2'-8"]

18'-0"

SJ, TYP

8'-4"

[ -2'-8" ] 1'-0" F6.0 SF CW4 [ -1'-4" ]

1'-0"

P1 1'-4"

A3
SW3

MW3

WF3.0

WF4.0 1 2'-8" 12'-1 1/2" MW2 TS

MW1 1'-2 1/2"

"] -0 ' -4

1'-8" F4.0

1'-9"

] '-8" [ -2

[ -2 '-8

7'-8"

8'-10"

[ -4'-0" ] SF

F9.5

F3.0

[- 2 '-8 "

1'-4"

1"

TS

F4.0

5"

2"

1'-0"

8'-8"

TS

TS

SW1

SF

SF

SF

A1

8'-2 1/2"

1'-9 1/2"

10'-8"

2'-8"

SF

[-1'-4"]

SF

F3.0

2'-0 1/4"

[ -2'-8" ]

2'-2"

P1

1'-4" TYP

F4.0

F4.5 WF3.0

8" SLEEVE INVERT=[-3'-1"]

F4.5

[-

17'-2"

D
SW2

8" CONC SHEAR WALL

SF

6' -0 WF2.0 " ] P4

[+

CW1

BF-C

4"

1'-0"
"] -0 6' [+

2'-0"

E
2 WF3.0

SF
]

SB301

F F.1

"]

[-3'-8"]

8" SLEEVE INVERT=[-3'-2"]

6'-0"

WF2.0

SW3

8" SLEEVE INVERT=[-3'-5"]

3'-6"

MW2

WF4.0

1' -4 "]

11'-3"

6"

1' -4

CW1

[-

3
"]

4'-0" 4'-0"

P2 F8.0

4"

2'-0" TYP.

H CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW J
8'-4"

1'-8" H-3.9 PIER TOC = [-0'-10"] MW1

F6.0

BF-H D2 SB302
[

[-

"] -4 F5.5 ' -1

1" 4" SOG [ -1'-4" ] F3.0

EJ

H.5
1'-8" 4'-8" F6.5 BF-1 SJ, TYP 4" SOG

MW2 SJ, TYP

SB301 1'-9"

A5 SB301

7/2/2012 9:16:39 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

1"

F4.5

6'-0"

SJ, TYP

E5

1'-0"

SW3

[-2'-8"]

13'-10"

16'-6"

A3 WF4.0 9'-0" SB301

WF2.0
[] 4" 1'-

17'-0"

11'-1"

10'-11"

REVISIONS
No. Date Description

F4.0

"]

SW2

1'-0"

2'-0"

2'-0"

WF3.0

WF3.0

WF3.0

1'-0"

F5.0

F5.0

F5.0

F6.0

1'-9"

F3.0 P3 DN

SF

SW2

[-

1' -4

J.9
1'-4"

1'-0"

3'-0" 1'-5" -4 '-8 "

K
F5.5 [ -1'-4" ] [ -1'-4" ] 1'-0" 3'-0"

SW2 [-4'-8"] TOP OF CONCRETE WALL TO SLOPE 16" ABOVE TOP OF STAIR TREAD NOSING 9'-8" 6'-11 1/2" STAIR TREADS, SEE ARCH, TYP N 7'-5"

FOUNDATION PLAN

SW2

1'-0" 10'-10"

A3 11'-2" SB301

J.9-9 PIER TOC = [-1'-4"]

10'-0 1/2"

FOUNDATION PLAN
1/8" = 1'-0"

GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'

SB101
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

4'-0"

WF2.0

CW4 F6.5

3'-6"

F3.0

PENN STATE NEW RESIDENCE HALL

40'-2"

12" CONC SHEAR WALL

SB301 F3.0

BF-12

WF4.0

WF2.0 F4.0x3.0 P4 A5

8" SLEEVE INVERT=[+6'-0"]

8'-1"

23'-6"

[+9'-4"]
"] -0 6' [+

2'-0"

SJ, TYP CW3 1'-8"

8" CONC SHEAR WALL

F9.5

" -0 5' []

2
3

4
3.9
SEE PLAN

Architecture & Engineering


8 SEE PLAN 8.1

STEEL COLUMN, SEE PLAN #4 CONT. FILL CAVITY BELOW GRADE WITH 3000 PSI CONCRETE MASONRY VENEER, TYP, SEE ARCH STEEL COLUMN, SEE PLAN CFS STUD WALL, SEE ARCH CONCRETE SLAB-ON-GRADE TOC [SEE PLAN] PENNDOT 2A STONE FILL FILL CAVITY BELOW GRADE WITH 3000 PSI CONCRETE 1'-0" 4" JOINT SEALANT 1/2" PREMOLDED JOINT FILLER 3/4" WWF

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

1 1 3'-0" #5 AT 32" OC WITH STD 90 DEG HOOK 8" PENNDOT 2-A BASE COURSE VAPOR RETARDER, TYP.

GRADE TOC [SEE PLAN]

8" CMU GROUT SOLID BELOW GRADE #5 VERT AT 32" OC SEE CONCRETE PIER SCHEDULE FOR REINFORCEMENT L5x3x1/4 (LLV) CONT WITH 3/4"x3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX

E5

SECTION
3/4" = 1'-0"

36 REINFORCING IN STEM WALL NOT SHOWN FOR CLARITY. SEE A5/SB301 FOR REINFORCING

#5 HOOKED 36 BAR AT 10" OC

JOINT SEALANT 1/2" PREMOLDED JOINT FILLER #4 CONT

3.9
SEE PLAN

VENEER, SEE ARCH GRADE, SEE CIVIL

COLUMN PER PLAN FILL CAVITY BELOW GRADE WITH 3000 PSI CONC TOC [SEE PLAN]

DOWELS WITH STD 90 HOOK TO MATCH VERT CMU REINF SIZE AND SPACING

48x BAR MIN LAP

SLAB ON GRADE, SEE PLAN TOC [SEE PLAN]

3" CLR

3" CLR

SEE CONCRETE PIER SCHEDULE FOR REINFORCING (4) #4 DOWELS WITH STD 90 HOOK

1'-0"

1 1 VAPOR RETARDER 8"

36 #5 HOOKED BAR AT 10" OC 36

TOF [SEE PLAN]

2x4 KEYWAY, CONT PENNDOT 2-A STONE FILL 2x4 CONT KEY

L5x3x1/4 (LLV) CONT WITH 3/4" x 3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX ROUGHEN SURFACE TO 1/4" AMPLITUDE

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

SLAB AND DECK PER PLAN L5x3x1/4 (LLV) CONT WITH 3/4" x 3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX FACE OF CONC WALL BEYOND SEE CONC PIER SCHEDULE FOR REINF RETAINING WALL, SEE A1/SB301 FOR REINFORCING FOOTING SHALL BEAR ON BEDROCK ALONG COLUMN LINE 3 SEE FOOTING SCHEDULES OF SB501 FOR REINFORCING. FTG REINF NOT SHOWN FOR CLARITY FACE OF BEDROCK

PENNDOT 2A COMPACTED FILL UNDER FOOTING

RETAINING WALL, SEE A1/SB501 FOR REINFORCING

D5
RETAINING WALL. SEE A1/SB501 FOR REINFORCING

SECTION
3/4" = 1'-0"

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

NOTE: THIS IS SECTION IS ALSO APPLICABLE AT COLUMNS D-3 AND D-3.9.

PROTECTION BOARD, SEE ARCH

NOTE: THIS SECTION ALSO APPLICABLE AT COLUMN D.9-3.9

C1

SECTION
3/4" = 1'-0" #4 CONT MASONRY VENEER, SEE ARCH GROUT SOLID BELOW GRADE

C3

SECTION
3/4" = 1'-0" #4x3'-0" WITH STANDARD HOOK AT TOP AT 12" OC # 4 CONT ROUGHEN SURFACE TO 1/4" AMPLITUDE 1'-4" 2'-6"

L5x3x1/4 (LLV) GALV CONT WITH 3/4" x 3" EMBEDDED HEAVY SCREW ANCHORS AT 24" OC MAX 1'-0" TYP

2x4 CONT KEY TOP AND BOTTOM, TYP REMOVABLE GALVANIZED STEEL BAR GRATING, SEE PLAN

1-#4 CONT ALL AROUND #4 AT 12" OC, TYP CONCRETE SLAB-ON-GRADE, TYP TOC [SEE PLAN]

MASONRY VENEER, SEE ARCH RIGID INSULATION, SEE ARCH ROUGHEN SURFACE TO 1/4" AMPLITUDE GROUT SOLID BELOW GRADE TOP OF SLAB [SEE PLAN] FINISHED GRADE [SEE CIVIL] 8" MIN 3" 4" EOS 2'-6"

L5x3x1/4 (LLV) CONT WITH 3/4" DIA x 3" EMBED HEAVY SCREW ANCHORS AT EA FRAME, 24" OC MAX #4 HOOKED BAR AT 12" OC, BEND DOWN AFTER PLACING DECK

1 TOP OF SLAB [SEE PLAN] 3'-0" TYP 2

TURN DOWN SLAB BEYOND GALV STEEL LADDER, SEE ARCH

VAPOR RETARDER, TYP CONT SELF-EXPANDING WATERSTOP AT TOP AND BOTTOM OF WALL DAMP PROOFING SEE ARCH

8" MIN

#4 BAR WITH STD 90 HOOK AT 12" OC L5x3x1/4 (LLV) CONT WITH 5/8" DIA x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC 1'-10" TYP LAP (2) #4 CONT

(2) #4 CONT 10" 1'-7"

#4 AT 12" OC EACH WAY EACH FACE, TYP SUMP, SEE PLAN 1'-0" SLUMP TO SUMP DOWELS TO MATCH SIZE AND SPACING OF VERT WALL REINF CONTINUOUS SELF-EXPANDING WATERSTOP AT TOP AND BOTTOM OF WALL, TYP TOF [SEE PLAN]

1'-5"

TOPSOIL, SEE CIVIL PENNDOT 2A FILL FILTER FABRIC, DRAINAGE BOARD, AND PROTECTION BOARD BACKFILL FOW

L3x3x1/4 AT 24" OC 2'-0" 1/4 1/4 4" 8" CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF 1 1 L3x3x1/4 x 10" WITH (2) 5/8" DIA WEDGE-TYPE EXPANSION ANCHORS TYP EA END

ASTM A706 #3 AT 16" OC W/ 180 HOOK AT END, WELD TO ANCHOR BAR

1'-0"

1/4 1/4

3 3

3 - 1/2" DIA x 3" EMBED HEAVY SCREW ANCHORS

ASTM A706 #4 ANCHOR BAR AT 16" OC

1'-0"

1'-0"

4" 1'-10" TYP CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF

1'-4" #7 AT 12" OC EACH WAY, TOP AND BOTTOM

B1

SECTION
3/4" = 1'-0" 1'-0" FACE OF BEDROCK 1'-4"

B2

SECTION
3/4" = 1'-0"

B5

SECTION
3/4" = 1'-0"

B
PENNDOT 2A STONE FILL PROTECTION BOARD, SEE ARCH FILTER FABRIC AND DRAINAGE BOARD, SEE ARCH CLASS "B" LAP SPLICE, TYP. SEE "TOP BAR TENSION REINFORCING" LAP SPLICE ON SB502
2'- 5"

SEE "TYPICAL CONTROL JOINT AT RETAINING WALL" ON SB501 FOR LOCATING CONTROL JOINTS ALONG WALL SEE WALL REINFORCING SCHEDULE ON SF601 FOR WALL REINFORCING #4 CONT 1/2" JOINT FILLER MATERIAL SEE PLAN #4 BAR AT 12" OC CONC SLAB ON GRADE COLD-FORMED STEEL FRAMING, SEE ARCH DWGS 4" TOC [SEE PLAN] STOREFRONT, SEE ARCH 1 #4 CONT MASONRY VENEER, SEE ARCH GRADE VARIES TOC
3/ 4 "

MASONRY VENEER, SEE ARCH DWGS SLAB ON GRADE


125/ 2 56"

POCKET BEAM INTO WALL. WIDTH OF POCKET SHALL BE 4 1/4" (1/8" GAP ON EA SIDE OF BEAM FLANGE). DO NOT GROUT SOLID REMOVABLE GALVANIZED STEEL BAR GRATING, SEE PLAN TOS [SEE PLAN]

0" 0"
1/ 2 "

TOC [SEE PLAN] #4 CONTINUOUS DOWELS TO MATCH SIZE AND SPACING OF VERT WALL REINF WITH STD 90 HOOK 3" CLR GROUT SOLID BELOW GRADE

CONCRETE TURNED-DOWN SLAB #5 @ 32" OC WITH 6" HOOK PERIMETER INSULATION, SEE ARCH DRAWINGS VAPOR RETARDER 8" 3'-0" 3/4" CLR [SEE PLAN] 8" MIN DAMP PROOFING SEE ARCH 8" CONCRETE STEM WALL 6" CMU, GROUT SOLID BELOW GRADE #4 HORIZ AT 12" OC EQ EQ 1

3'-0" VAPOR RETARDER CONT SELF-EXPANDING WATERSTOP DAMP PROOFING, SEE ARCH 2x4 CONT KEY

CONTINUOUS SELF-EXPANDING WATERSTOP GEOTEXTILE FILTER FABRIC

CONCRETE TURNED-DOWN SLAB SEE PLAN #5 x 3'-0" @ 32" OC WITH 6" HOOK 3/4"

GALV STEEL BEAM TO BE REMOVABLE FOR ACCESS TO EQUIPMENT IN PIT, SEE PLAN

8"

GRADE VARIES TOF [SEE PLAN] 4" SOLID CMU

7/2/2012 9:16:45 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

TOC [SEE PLAN]

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

SEE B5/SB301 FOR WALL REINF

1'-2"

WASHED STONE FILL

8" STEM WALL BELOW GRADE STD 90 HOOK, EACH END REINFORCING, SEE SCHEDULE DAMP PROOFING SEE ARCH

VAPOR RETARDER 1 PERIMETER INSULATION, SEE ARCH DRAWINGS ROUGHEN SURFACE TO 1/4" AMPLITUDE #4 VERT AT 18" OC WITH STD 90 HOOK TOF [SEE PLAN] 0"
5/ 8 "

1 1 ROUGHEN SURFACE TO 1/4" AMPLITUDE

A6

SECTION
3/4" = 1'-0"

6" PERFORATED DRAIN PIPE

2x4 CONT KEYWAY, TYP GROUT SOLID IN 2" x 16" MIN DEEP CORES IN BEDROCK

SURFACE OF BEDROCK

#4 HORIZ AT 12" OC, EF

8" EQ

1'-4" EQ

2x4 CONT KEYWAY, TYP TOF [SEE PLAN] GEOTEXTILE FILTER FABRIC WASHED STONE FILL 6" PERFORATED DRAIN PIPE

#8 DOWEL BAR AT 24" OC WITH STD 90 DEG HOOK

NOTE: 1. ANCHORS SHALL BE DESIGNED FOR 18 KIP SHEAR LOAD PARALLEL TO ROCK SURFACE AND 10 KIP TENSION LOAD. LOADS ARE SERVICE-LEVEL.

WASHED STONE FILL 6" PERFORATED DRAIN PIPE

0"

GEOTEXTILE FILTER FABRIC

2x4 CONT KEYWAY CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING

9/ 1 6"

CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING #4 VERT AT 18" OC WITH STD 90 HOOK, EF

A1

GROUND FLOOR RETAINING WALL


3/4" = 1'-0"

A3

EXTERIOR WALL SECTION


3/4" = 1'-0"

A5

VESTIBULE SLAB SECTION


3/4" = 1'-0"

GRAPHIC SCALE(S)
0 3/4" = 1' - 0" 6" 1' 2' 3' 4' 5'

SB301
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

ASTM A706 #4 AT 16" OC WELDED TO ANCHOR BAR AT EDGE OF SHELF

24" 24"

PENN STATE NEW RESIDENCE HALL

FOUNDATION SECTIONS

Architecture & Engineering


SEE PLAN MASONRY VENEER, SEE ARCH DRAWINGS CLASS "B" LAP SPLICE. SEE TENSION REINF. LAP SPLICE ON SB502 GROUT SOLID BELOW GRADE DAMP PROOFING SEE ARCH GRADE VARIES
2'- 167/ 2 56"

8" CONC WALL, SEE PLAN CONC WALL, SEE PLAN DOWELS TO MATCH SIZE AND SPACING OF VERTICAL WALL REINF. W/ STD 90 HOOK SLAB ON GRADE, SEE PLAN VAPOR RETARDER TOC [SEE PLAN]
2'- 167/ 2 56"

SEE PLAN 48"xBAR MIN LAP 8" MASONRY VENEER, SEE ARCH DRAWINGS SLAB ON GRADE, SEE PLAN GROUT SOLID BELOW GRADE
1'- 1015/ 256"

SEE PLAN

CMU WALL, SEE PLAN #4, CONT #5 @ 32" OC WITH STD 90 HOOK SLAB ON GRADE, SEE PLAN VAPOR RETARDER TOC [SEE PLAN] 1

MASONRY VENEER, SEE ARCH RIGID INSULATION, SEE ARCH ROUGHEN SURFACE TO 1/4" AMPLITUDE GROUT SOLID BELOW GRADE 4" EOS

#4 CONT

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

CLASS "B" LAP SPLICE. SEE TENSION REINF. LAP SPLICE ON SB502 2x4 CONT KEYWAY, TYP

#4 HOOKED BAR AT 12" OC, BEND DOWN AFTER PLACING DECK SLAB ON DECK, SEE PLAN 2'-6" TOP OF SLAB [SEE PLAN]

VAPOR RETARDER 4" SOLID CMU TOC [SEE PLAN] GRADE VARIES

4" SOLID CMU EQ EQ TOF [SEE PLAN] GEOTEXTILE FILTER FABRIC PERIMETER INSULATION, SEE ARCH DRAWINGS CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING 2x4 CONT KEYWAY, TYP DOWELS TO MATCH SIZE AND SPACING OF VERTICAL WALL REINF. W/ STD 90 HOOK CONCRETE FOOTING, SEE SCHEDULE ON SHEET SB501 FOR SIZE AND REINFORCING 6" PERFORATED DRAIN PIPE 2x4 CONT KEYWAY, TYP #4 VERT AT 18" OC WITH STD 90 HOOK EQ EQ TOF [SEE PLAN] GEOTEXTILE FILTER FABRIC DOWELS TO MATCH SIZE AND SPACING OF VERTICAL WALL REINF. W/ STD 90 HOOK 1 PERIMETER INSULATION, SEE ARCH DRAWINGS TOF [SEE PLAN] ROUGHEN SURFACE TO 1/4" AMPLITUDE #4 HORIZ AT @ 6" OC, MOW WASHED STONE FILL CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING

TOPSOIL, SEE CIVIL

EQ

EQ

FILTER FABRIC, DRAINAGE BOARD, AND PROTECTION BOARD, SEE ARCH

8" MIN

L5x3x1/4 (LLV) CONT WITH 5/8" DIA x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC MAX

WASHED STONE FILL

CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF

6" PERFORATED DRAIN PIPE

D1
D

SECTION
3/4" = 1'-0"

D2

SECTION
3/4" = 1'-0"

D4

SECTION
3/4" = 1'-0"

D5

SECTION
3/4" = 1'-0"

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

#4 CONT ROUGHEN SURFACE TO 1/4" AMPLITUDE PAVING OR FINISHED GRADE, SEE CIVIL DWGS SLAB ON DECK, SEE PLAN #4 AT 12" OC TOP OF SLAB [SEE PLAN] FILTER FABRIC, DRAINAGE BOARD, AND PROTECTION BOARD, SEE ARCH 2'-0" 5 1/2" 1 1/4" CURTAIN WALL, SEE ARCH #4 CONT ROUGHEN SURFACE TO 1/4" AMPLITUDE #5 AT 12" OC TOP OF SLAB [SEE PLAN]

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

1'-0"

4"

2'-0"

NOTE: SEE PLAN VIEW OF "TYPICAL SLAB AT EXTERIOR OPENING" ON SB502 FOR SLAB REINF.

2'-6"

L5x3x1/4 (LLV) CONT WITH 5/8" DIA x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC MAX FILTER FABRIC, DRAINAGE BOARD, AND DAMPPROOFING, TYP 1'-4" CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF

L5x5x1/4 (LLV) CONT WITH 3/4" x 3" EMBED HEAVY SCREW ANCHORS AT 24" OC MAX

C1
C

SECTION
3/4" = 1'-0"

C2

SECTION
3/4" = 1'-0"

PENN STATE NEW RESIDENCE HALL


REVISIONS
No. Date

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:16:49 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt
Description

SB302
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

FOUNDATION SECTIONS

1
SLAB OR WALL REINFORCING, SEE PLAN OR SCHEDULE
YP

2
3" OC SPACING BETWEEN BARS, TYP

"T -0 2'

SEE PLAN EOS SLAB OR WALL REINFORCING INTERRUPTED BY OPENING

STEEL COLUMN, SEE PLAN #4 CONT

Architecture & Engineering

MASONRY VENEER, SEE ARCH TOP OF SLAB [SEE PLAN] TOS DECK NOT SHOWN FOR CLARITY 1/4" FULL DEPTH STIFFENERS

2'-0" TYP

1-#5 EACH FACE FOR WALLS, 2-#5 MID-DEPTH FOR SLABS

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

2" CLR, TYP

2" CLR, TYP

[SEE PLAN]

LEVELING NUT AND WASHER, TYP 12" LONG CORBEL STEEL BEAM, SEE PLAN 1-#5 EACH FACE FOR WALLS, 2-#5 MID-DEPTH FOR SLABS AT EACH SIDE OF SLAB OR WALL OPENING ADD 1/2 OF REINFORCING INTERRUPTED BY OPENING [+9'-10"] UON 10" TOC (2) #4x8" LONG, EA END

WALL REINFORCING NOT SHOWN FOR CLARITY

ADDED REINFORCING AT OPENINGS IN CONCRETE SLAB OR WALL WHERE MAIN REINFORCING IS NOT INTERRUPTED

2' -0 "

ADDED REINFORCING AT OPENINGS IN CONCRETE SLAB OR WALL WHERE MAIN REINFORCING IS INTERRUPTED
NOTES: 1. COORDINATE OPENING SIZE AND LOCATION WITH MECHANICAL DWGS. 2. NO SPECIAL REINFORCING REQUIRED FOR OPENINGS 4" OR LESS.

SEE SHEET SF601 FOR BASE PLATE AND ANCHOR ROD DETAILS

GROUT POCKET SOLID TO FACE OF COLUMN

ASTM A706 #3 AT 6" OC (2 TOTAL) WITH 180 HOOK AT END, WELD TO ANCHOR BAR ASTM A706 #4 ANCHOR BAR AT 6" OC

ASTM A706 #4 AT 6" OC (2 TOTAL) WELDED TO ANCHOR BAR AT EDGE OF SHELF 20" 8" 20" 1'-6" TYP

PIER REINFORCING NOT SHOWN FOR CLARITY

WALL BEYOND PIER CONC WALL BEYOND

TYPICAL SLAB OR WALL OPENING


NOT TO SCALE

TYPICAL COLUMN BEARING ON PIER


NOT TO SCALE

SEE PLAN EOS

TYPICAL BEAM BEARING ON CORBEL


NOT TO SCALE #4 CONT 1/4" FULL DEPTH STIFFENERS 1/4 TYP TOP OF SLAB [SEE PLAN]

1'-6" TYP

3. REINFORCING FOR ROUND OPENINGS SIMILAR.

8"

REINFORCING, TYPICAL. SEE WALL FOOTING SCHEDULE ON THIS SHEET

PLAN AT CORNER
1'-6" TYP 1'-6" TYP

8" MIN 16" MAX

D
SJ OR CJ
P TY

16" MIN FOR 8" STEP 32" MIN FOR 16" STEP
-

MASONRY VENEER, SEE ARCH 3" CLR TYP 0" 36 BAR DIAMETER LAP, TYP MATCH SIZE AND SPACING OF FOOTING TOP BAR REINFORCING NUT AND WASHER

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

SJ OR CJ

M 8"

,T IN

YP

M 8"

,T IN

YP J C

M 8"

, IN

STEEL BEAM, SEE PLAN 'A' BARS NOTES: GROUT POCKET SOLID 1 2 1 2 CONTINUOUS WALL FOOTING REINFORCING, SEE SCHEDULE ON THIS SHEET 12" MIN CONTINUOUS WALL FOOTING REINFORCING LEVELING NUT AND WASHER, TYP 8" CONCRETE RETAINING WALL, SEE A1/SB301 FOR REINF 2" 'B' BARS 3/4" x 4" STEEL BEARING PLATE EXTENDING MIN 3" EA SIDE OF BEAM BOTTOM FLANGE 1" NON-SHRINK GROUT (2) 3/4" DIA ANCHOR RODS WITH 9" MIN EMBED AND HEAVY HEX NUT AT BOTTOM 1. WHERE THREE BARS OCCUR, CENTER BAR SHALL BE TREATED AS AN INNER FACE BAR. 2. 'B' AND 'D' BARS NOT SHOWN FOR CLARITY.

EOS

SJ OR CJ
C
J C

SJ OR CJ
J

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

C J

EOS

EOS

SJ OR CJ

CORNER

TYPICAL COLUMN ISOLATION JOINT


NOT TO SCALE SEE ARCH FOR TREADS #4 CONT, TYP #4 AT 12" OC, EW SEE ARCH FOR RISERS #4 AT 12" OC CONCRETE SLAB-ON-GRADE
SLOPE

24 BAR 12" MIN

24 BAR 12" MIN, TYP

0" BETWEEN BARS, TYP

1 13 / 25 6"

0" BETWEEN BARS, TYP


1"

6" MIN FOR 8" WALLS

36 BAR

#4 AT 12" OC

IN "M 6 ' 1

2" CLR 24 BAR 12" MIN 24 BAR 12" MIN CORNER DOWELS SAME SIZE AND NUMBER AS HORIZONTAL WALL REINFORCING DOWELS SAME SIZE AND NUMBER AS HORIZONTAL WALL REINFORCING KEY CUT EVERY OTHER HORIZONTAL BAR AT JOINT

" 1'-6

N MI

8"

8"

8"

NOTES: 1. PROVIDE JOINTS AT 25'-0" OC ALONG WALL. 2. PROVIDE JOINTS 12'-0" FROM WALL CORNERS. 3/4" CHAMFER ON EACH FACE OF WALL

3/4" CHAMFER, TYP

TYPICAL CONCRETE EXTERIOR STAIR SECTION


NOT TO SCALE PRE-MOLDED JOINT FILLER AROUND COLUMN CONCRETE INFILL, SEE PLAN DETAILS ON THIS SHEET SEE TYPICAL ANCHOR ROD AND BASE PLATE DETAIL ON SF601 CONCRETE SLAB-ON-GRADE T NOT TO SCALE CL COLUMN AND FOOTING, UNLESS OTHERWISE NOTED CONSTRUCTION JOINT, TYP

EXTERIOR FACE

PLAN AT CORNER

PLAN AT INTERSECTION

TYPICAL CONTINUOUS WALL REINFORCING

TYPICAL CONTROL JOINT AT RETAINING WALL


NOT TO SCALE

TYPICAL CONCRETE WALL CONSTRUCTION JOINT


NOT TO SCALE

3" MIN SEE PLAN TOC [SEE PLAN]

MARK
F3.0 F4.0 F4.0x3.0 F4.5 F5.0 F5.5 F6.0 F6.5 F8.0 F9.5

W
3'-0" 4'-0" 3'-0" 4'-6" 5'-0" 5'-6" 6'-0" 6'-6" 8'-0" 9'-6"

FOOTING SCHEDULE - COLUMN DIMENSIONS REINFORCING L T 'A' BARS 'B' BARS 'C' BARS
3'-0" 4'-0" 4'-0" 4'-6" 5'-0" 5'-6" 6'-0" 6'-6" 8'-0" 9'-6" 1'-4" 1'-4" 1'-4" 1'-4" 1'-6" 1'-10" 1'-10" 1'-10" 1'-10" 1'-10" (5) #5 (7) #5 (5) #5 (8) #5 (7) #6 (7) #7 (8) #7 (8) #7 (10) #7 (12) #7 (5) #5 (7) #5 (7) #5 (8) #5 (7) #6 (7) #7 (8) #7 (8) #7 (10) #7 (12) #7 (8) #7 (12) #7

MARK
P1

DIMENSIONS W D
2' - 0" 1' - 5" 1' - 4" 1' - 4" 2' - 0" 2' - 8" 2' - 0" 2' - 0" 1' - 10" 1' - 4" 2' - 6" 2' - 6" 5' - 8" 2' - 6"

PIER SCHEDULE REINFORCING VERTICAL TIES


(8) #8 (8) #7 (8) #6 (12) #6 (8) #7 (18) #8 (12) #8 #4 TIES @ 16" OC MAX AND (3) SETS @ 3" OC TOP #4 TIES @ 14" OC MAX AND (3) SETS @ 3" OC TOP #4 TIES @ 12" OC MAX AND (3) SETS @ 3" OC TOP #4 TIES @ 12" OC MAX AND (3) SETS @ 3" OC TOP #4 TIES @ 14" OC MAX AND (3) SETS @ 3" OC TOP #4 TIES @ 16" OC MAX #4 TIES @ 16" OC MAX AND (3) SETS @ 3" OC TOP

NOTES
TYPE 1 TYPE 1 TYPE 1 TYPE 2 TYPE 1 TYPE 3 TYPE 2

'D' BARS
(8) #7 (12) #7 P2 PRE-MOLDED JOINT FILLER AROUND COLUMN CONCRETE INFILL, SEE PLAN DETAILS ON THIS SHEET SEE TYPICAL ANCHOR ROD AND BASE PLATE DETAIL ON SF601 3" MIN CONCRETE SLAB-ON-GRADE T SEE PLAN TOC [SEE PLAN] P3 CL COLUMN AND FOOTING, UNLESS OTHERWISE NOTED CONSTRUCTION JOINT, TYP P4 P5 P6 P7

PENNDOT 2A BASE COURSE VAPOR RETARDER

TOF [SEE PLAN] CONCRETE FOOTING, SEE SCHEDULE ON THIS SHEET FOR SIZE AND REINFORCING

TYPICAL COLUMN FOOTING


7/2/2012 9:16:56 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt
NOT TO SCALE PREVIOUS POUR NEW POUR 3-#5x4'-0" TOP CENTERED ON JOINT WHERE THERE IS NO CONT TOP REINFORCING 2" CLR TOP

MARK
WF2.0 WF3.0 WF4.0

FOOTING SCHEDULE - WALL DIMENSIONS REINFORCING W T 'A' BARS 'B' BARS 'C' BARS
2'-0" 3'-0" 4'-0" 1'-0" 1'-4" 1'-6" (2) #5 CONT (4) #5 CONT (4) #6 CONT #5 @ 11" OC #5 @ 7" OC #6 @ 9" OC (2) #6 CONT

NOTE: PROVIDE TYPICAL CONTINUOUS HORIZONTAL WALL REINFORCING THROUGH CONCRETE PIERS.

'D' BARS
#6 @ 18" OC PENNDOT 2A BASE COURSE VAPOR RETARDER #4 TIES AT 3" OC 2" TOP OF PIER [SEE SCHEDULE] D D CONCRETE PIER, SEE SCHEDULE ON THIS SHEET FOR SIZE AND REINFORCING CONCRETE FOOTING, SEE SCHEDULE ON THIS SHEET FOR SIZE AND REINFORCING TOF 0" TYP [SEE PLAN] 1 1/2" CLR 1 1/2" CLR PROVIDE STD 90 HOOK AT TOP OF FOUR CORNER BARS 2" CLR D

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

'B' AND 'D' BARS SEE PLAN COLUMN, WALL SIMILAR 'C' BARS T 'D' BARS L WALL (CONT) 'B' AND 'D' BARS

CONCRETE PIER, SEE SCHEDULE

T/3

T/3

'A' AND 'C' BARS CONT

'A' BARS BOTTOM (AND TOP) REINFORCING CONTINUOUS THRU JOINT 4" 4" TIE BAR EACH SIDE OF CONSTRUCTION JOINT W

'B' BARS

W W

11/ 1 6"

2"

'A' AND 'C' BARS

STANDARD 90 HOOK, TYP

TYPICAL FOUNDATION/SLAB DETAILS


PIER TYPE 3

T/3

SECTION SECTION

PLAN AT COLUMN

PLAN AT WALL

PIER TYPE 1

PIER TYPE 2

TYPICAL CONCRETE FOOTING CONSTRUCTION JOINT


NOT TO SCALE

SB501
SHEET OF

TYPICAL FOOTING REINFORCING DIAGRAM AND SCHEDULES


NOT TO SCALE

TYPICAL COLUMN PIER ON FOOTING


NOT TO SCALE

TYPICAL PIER REINFORCING DETAIL AND SCHEDULE


NOT TO SCALE

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

#5 DOWELS AT 12" OC.

NOTE: WHERE THREE BARS OCCUR, CENTER BAR SHALL BE TREATED AS AN INNER FACE BAR

PENN STATE NEW RESIDENCE HALL

2-#5 CONT

1/3 1/3 1/3

WALL THICKNESS, SEE PLAN

C J C J

PLAN AT INTERSECTION

EDGE

INTERIOR

'Z' BARS SAME SIZE AND NUMBER AS CONTINUOUS FOOTING REINFORCING, BEND AS SHOWN

TYPICAL STEPPED FOOTING


NOT TO SCALE 36 BAR

TYPICAL BEAM BEARING ON WALL


NOT TO SCALE

TYPICAL CONTINUOUS FOOTING REINFORCING


NOT TO SCALE

6" N MI

SEE PLAN FOR SPACING

3
DEVELOPMENT LENGTH CONCRETE f'c SIZE #3 #4 #5 #6 #7 3000 PSI 17" 22" 28" 33" 48" 55" 62" 70" 78" 93" 124" 4000 PSI 15" 19" 24" 29" 42" 48" 54" 61" 67" 81" 107" 5000 PSI 13" 17" 22" 26" 37" 43" 48" 54" 60" 72" 96" #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 SIZE 17" 22" 28" 33" 48" 55" 62" 70" 78" 93" 124" 3000 PSI CLASS A CLASS B 22" 29" 36" 43" 63" 72" 81" 91" 101" 121" 161" Ld LAP SPLICE

4
Ls DEVELOPMENT LENGTH CONCRETE f'c 4000 PSI CLASS A 15" 19" 24" 29" 42" 48" 54" 61" 67" 81" 107" CLASS B 19" 25" 31" 37" 54" 62" 70" 79" 87" 105" 140" 13" 17" 22" 26" 37" 43" 48" 54" 60" 72" 96" CONCRETE f'c 5000 PSI CLASS A CLASS B 17" 22" 28" 33" 49" 55" 63" 70" 78" 94" 125" SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 3000 PSI 22" 29" 36" 43" 63" 72" 81" 91" 101" 121" 161" 4000 PSI 19" 25" 31" 37" 54" 62" 70" 79" 87" 105" 140" Ld

5
Ls LAP SPLICE CONCRETE f'c 4000 PSI CLASS A 19" 25" 31" 37" 54" 62" 70" 79" 87" 105" 140" CLASS B 24" 32" 40" 48" 71" 81" 91" 102" 113" 136" 181" 17" 22" 28" 33" 49" 55" 63" 70" 78" 94" 125"

Architecture & Engineering


5000 PSI CLASS A CLASS B 22" 29" 36" 43" 63" 72" 81" 91" 101" 122" 162" 1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204
7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

5000 PSI 17" 22" 28" 33" 49" 55" 63" 70" 78" 94" 125"

SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 22" 29" 36" 43" 63" 72" 81" 91"

3000 PSI CLASS A CLASS B 28" 37" 47" 56" 81" 93" 105" 118" 131" 157" 209"

#8 #9 #10 #11 #14 #18


CL WALL DOWELS WITH STD 90 HOOK TO MATCH VERT WALL REINFORCING SIZE AND SPACING VERTICAL REINFORCING MOW, SEE SCHEDULE ON SHEET SF601 NON LOAD-BEARING CMU WALL CONCRETE SLAB-ON-GRADE 48 x BAR LAP MIN #4 AT 18" OC 0"
1/ 2 "

101" 121" 161"

BOTTOM BAR TENSION REINFORCING

TOP BAR TENSION REINFORCING NOTES:

2-#5 CONT

1 1/2" UON

WELDED WIRE FABRIC

SIZE
SEE PLAN TOC [SEE PLAN]

STANDARD HOOKS STIRRUPS 90 180 AND TIES L L L=12 d b L=4 d b L=6 d b /12 d b 2 1/2" 2 1/2" 2 1/2" 2 1/2" 3" 3 1/2" 4" 4 1/2" 5" 5 1/2" 7" 9" 3" 4" 9" 10 1/2" 12" N/A N/A N/A N/A N/A

BEND DIAMETERS STIRRUPS TYP AND TIES d d

DEVELOPMENT OF HOOKED BARS SIZE

Ldh 90 CONCRETE f'c 4000 PSI 6" 7" 9" 11" 12" 14" 16" 18" 19" 24" 31" 180

Ldh DEVELOPMENT LENGTH CONCRETE f'c 5000 PSI 5" 7" 8" 10" 11" 12" 14" 16" 17" 21" 28" SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18 3000 PSI 9" 11" 14" 17" 20" 22" 25" 28" 31" 37" 50" 4000 PSI 8" 10" 12" 14" 17" 19" 22" 24" 27" 33" 43"

Ld LAP SPLICE ALL f'c 13"

Ls 30db

1. 2.

DESIGN METHOD IS BASED ON ACI 318-08. TOP BAR IS WHERE HORIZONTAL REINFORCING IS PLACED SUCH THAT MORE THAN 12 INCHES OF FRESH CONCRETE IS CAST BELOW THE DEVELOPMENT LENGTH OR SPLICE. BOTTOM BAR IS WHERE HORIZONTAL REINFORCING IS PLACED SUCH THAT LESS THAN 12 INCHES OF FRESH CONCRETE IS CAST BELOW THE DEVELOPMENT LENGTH OR SPLICE. LAP SPLICES OF DEFORMED BARS AND DEFORMED WIRE IN TENSION SHALL BE CLASS B SPLICES EXCEPT THAT CLASS A SPLICES ARE ALLOWED WHEN: A. THE AREA OF REINFORCEMENT PROVIDED IS AT LEAST TWICE THAT REQUIRED BY ANALYSIS OVER THE ENTIRE LENGTH OF THE SPLICE. TWICE THE AREA OF REQUIRED REINFORCING CANNOT BE ASSUMED UNLESS SPECIFICALLY INDICATED OTHERWISE ON THE DRAWINGS; AND ONE-HALF OR LESS OF THE TOTAL REINFORCING IS SPLICED WITHIN THE REQUIRED LAP LENGTH.

3000 PSI 7" 8" 10" 12" 14" 16" 18" 20" 22" 27" 35"

5000 PSI 7" 9" 12" 14" 16" 18" 21" 23" 26" 31" 41"

3.

#3 #4 #5 #6

4 1/2" 6" 7 1/2" 9" 10 1/2" 12" 13 1/2" 15" 16 1/2" 21" 27"

2 1/4" 3" 3 3/4" 4 1/2" 5 1/4" 6" 9 1/2" 10 3/4" 12" 18 1/4" 24"

1 1/2" 2" 2 1/2" 4 1/2" 5 1/4" 6" N/A N/A N/A N/A N/A

#3 #4 #5 #6 #7 #8 #9 #10 #11 #14 #18

4.

1'-0"

0"

15" 19" 23" 27" 30"

1/ 2 "

3" CLR

COMPACTED PENNDOT 2A BASE COURSE VAPOR RETARDER

#7
1'-0" 2'-0" 8"

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

1'-0" 8"

#8 #9 #10 #11

B.

34" 39" 43"


6. 5.

MINIMUM LENGTHS AND BENDS INDICATED, BENDS SHALL COMPLY WITH ACI 318. INDICATED BEND DIAMETERS ARE MEASURED ON THE INSIDE OF THE BAR.

TYPICAL THICKENED SLAB (TS) UNDER CMU WALL


NOT TO SCALE

51" 68"

#14 #18

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

HOOKED TENSION REINFORCING


1-#4 CONT ALL AROUND CMU WALL, SEE PLAN, TYP. BAR TO MATCH SIZE AND SPACING OF VERT CMU WALL REINF, TYP. 3/4" CLR TYP
3/ 4 "

COMPRESSION REINFORCING

48 x BAR MIN LAP, TYP.


2'- 015/ 64"

CONCRETE SLAB-ON-GRADE, TYP #5 AT 24" OC, TYP WELDED WIRE FABRIC, TYP VAPOR RETARDER, TYP TOC #4 AT 12" OC EACH WAY EACH FACE

1'-0"

8"

2'-6" SQUARE

1'-0"

8" TYP

2x4 CONT KEY TOP AND BOTTOM, TYP

[SEE PLAN]

1 3'-0" TYP 2

1'-6" TYP

0" TYP
9/ 1 6"

SEE COMPRESSION REINFORCING LAP SPLICE ON THIS SHEET, TYP.

DAMP PROOFING SEE ARCH


1'- 735/ 64"

#5 DOWELS AT 12" OC AT SUMP ONLY

1'-6"

#5 AT 12" OC EACH WAY TOP AND BOTTOM

#4 AT 12" OC EACH WAY EACH FACE, TYP 1'-0"

TOF [SEE PLAN] #4 AT 12" OC EACH WAY 3'-0". FACE OF EQUIPMENT 6" MIN, TYP 0" TYP
5/ 8 "

C
1'-6" TYP

0" TYP
1/ 2 "

8" TYP 1'-0" TYP

2" CLR

CONTINUOUS SELF-EXPANDING WATERSTOP AT TOP AND BOTTOM OF WALL, TYP

#4 DOWELS AT 12" OC, TYP

#5 TIES AT 12" OC

EQUIPMENT PAD 3/4" CHAMFER, TYP ROUGHEN SURFACE TO 1/8" AMPLITUDE AND APPLY BONDING AGENT 6"

8"

#5 AT 12" OC EACH WAY TOP AND BOTTOM

TOF NOTE: FOR DETAILS NOT NOTED, SEE TYPICAL SECTION THROUGH ELEVATOR PIT ON THIS SHEET #5 AT 12" OC EACH WAY EACH FACE 1'-0"

CONCRETE SLAB-ON-GRADE

0" TYP

[SEE PLAN]

1'-0" TYP

TOC

1'-0" TYP

#5 AT 12" OC EACH WAY TOP AND BOTTOM

TYPICAL SECTION THROUGH ELEVATOR PIT


NOT TO SCALE

TYPICAL ELEVATOR SUMP


NOT TO SCALE STAIR STRINGER, SEE ARCHITECTURAL DWGS FOR SIZE 3 SIDES #4 AT 18" OC 3-#5 CONT CONCRETE SLAB-ON-GRADE

NOT TO SCALE

PREVIOUS POUR

NEW POUR 2" CLR


2"

CONCRETE SLAB-ON-GRADE WELDED WIRE FABRIC, TYP

2" CLR
2" 2"

SAWCUT JOINT, DEPTH EQUAL TO 1/4 OF SLAB THICKNESS 1 1/2" UON

1 1/2" UON

[SEE PLAN] T

TOC [SEE PLAN] 1'-0"

[SEE PLAN]

6"

6"

TYPICAL SLAB-ON-GRADE SAWED (CONTRACTION) JOINT (SJ)


NOT TO SCALE

COMPACTED PENNDOT 2A BASE COURSE

VAPOR RETARDER

VAPOR RETARDER

8" TYP

3" CLR

COMPACTED PENNDOT 2A BASE COURSE

VAPOR RETARDER

COMPACTED PENNDOT 2A BASE COURSE

6"

NOTE: EXTEND THICKENED SLAB 1'-6" BEYOND EACH STRINGER 1'-4" 1'-4"

COMPACTED PENNDOT 2A BASE COURSE

8"

6"

6"

8"

VAPOR RETARDER

TYPICAL SLAB-ON-GRADE (SOG)


NOT TO SCALE

TYPICAL THICKENED SLAB (TS) AT STAIR LANDING


NOT TO SCALE ROUGHEN SURFACE TO 1/4" AMPLITUDE

TYPICAL SLAB-ON-GRADE CONSTRUCTION JOINT (CJ)


NOT TO SCALE

6"

TOC

WELDED WIRE FABRIC

1 1/2" UON

SEE PLAN

SUPPORTS FOR WELDED WIRE FABRIC AT 3' - 0" OC MAX EACH WAY

CONCRETE SLAB-ON-GRADE

L3x3x1/4x0'-4" WITH (1) 3/4" EXPANSION ANCHOR WITH 3" MIN EMBEDMENT

APPLY LIQUID CURING COMPOUND TO ENTIRE FACE OF PREVIOUS POUR TO PREVENT BONDING WELDED WIRE FABRIC, TYP

2x4 CONT KEY CONCRETE SLAB-ON-GRADE SEE PLAN TOC [SEE PLAN]

SEE PLAN SEE PLAN TOC

SLAB ON DECK

CMU WALL BEYOND #4 CONT

7/2/2012 9:17:02 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

#4 AT 12" OC

CONCRETE SLAB-ON-GRADE #4 AT 12" OC

WALL BEYOND 1-#4 CONT PAVING OR FINISHED GRADE, SEE CIVIL DRAWINGS

#5 HORIZ AT 16" OC, EF CONCRETE SLAB-ON-GRADE #4 AT 12" OC WITH STD 180 HOOK

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

ELEVATOR SHAFT

2'-6"

1-#4 AT RE-ENTRANT CORNER, MIDDLE OF SLAB, EACH SIDE

2'-6"

1-#4 AT RE-ENTRANT CORNER, MIDDLE OF SLAB, EACH SIDE 14" CONC STEM WALL DAMP PROOFING SEE ARCH GEOTEXTILE FILTER FABRIC 8"

3/4" CLR

TOC [SEE PLAN] WELDED WIRE FABRIC #4 VERT AT 18" OC WITH STD 90 HOOK CONCRETE FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING TOF [SEE PLAN] #4 HORIZ AT 12" OC, EF 2x4 KEYWAY TOC [SEE PLAN] 1 1/2" UON

CONCRETE SLAB-ON-GRADE SEE PLAN FOR DEPTH OF SLAB DEPRESSION

2'-6"

45

2" C

LR

45

STEEL BEAM, SEE PLAN

2" C

1-#4

LR

12" LAP MIN CMU WALL, SEE PLAN ELEVATOR DOOR OPENING SEE ARCH DWGS LIMESTONE VENEER, TYP

12" LAP MIN WALL OPENING SEE ARCH DWGS

SEE PLAN 1 1

0"

6" PERFORATED DRAIN PIPE WASHED STONE FILL

PLAN

SECTION

EDGE OF SLAB

PLAN

COMPACTED PENNDOT 2A BASE COURSE

6"

EQ

EQ

CMU WALL, SEE PLAN

2"

1-#4

TYPICAL FOUNDATION/SLAB DETAILS

1'-0" MIN

VAPOR RETARDER

SB502
SHEET OF

5/ 8 "

TYPICAL ELEVATED SLAB AT ELEVATOR DOOR


NOT TO SCALE

TYPICAL SLAB AT EXTERIOR OPENING


NOT TO SCALE

SECTION

TYPICAL SLAB ON GRADE DEPRESSION (SD)


NOT TO SCALE

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

TYPICAL CONCRETE SLAB-ON-GRADE EQUIPMENT PAD

PENN STATE NEW RESIDENCE HALL

[SEE PLAN]

9/ 1 6"

" -4 1'

" -4 1'

PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5. REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+12-0]. LOW-SLOPE ROOF AREAS ARE 1 1/2" WIDE RIB, 20 GAGE STEEL ROOF DECK SUPPORTED ON STRUCTURAL STEEL FRAMING. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SLAB ON GRADE SHALL BE 4" THICK REINFORCED WITH 6x6 W2.1xW2.1 WWF PLACED 1 1/2" BELOW TOP OF SLAB. PLACE SLAB ON 6" OF COMPACTED PENNDOT 2A STONE. SEE SHEETS SF201 AND SF202 FOR BRACED FRAME "BF-X" ELEVATIONS. SEE SHEET SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES.

Architecture & Engineering

2. 3.

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

4. 5. 6. 7.

8. 9.

10. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS AND DEPRESSION CORNERS" ON SF501. 11. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

KEY NOTES
LOW SLOPE ROOF AREA POCKET COLUMN INTO WALL. WIDTH OF POCKET SHALL EQUAL WIDTH OF PIER. SEE "TYPICAL COLUMN BEARING ON PIER "DETAIL ON SB501 DEPRESSED SLAB COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 TOP OF CONCRETE ELEVATION AT SHEAR WALL BELOW = [+9'-10"]. SEE BRACED FRAME ELEVATIONS ON SF202 POCKET BEAM INTO WALL. WIDTH OF POCKET SHALL EXTEND MIN 4" EA. SIDE OF BEAM FLANGE. SEE "TYPICAL BEAM BEARING ON WALL" DETAIL ON SB501 SEE "TYPICAL BEAM BEARING ON CORBEL" DETAIL ON SB501 TOP OF CONCRETE WALL ELEVATION = [+5'-8"]. SEE B5/SF201 FOR ELEVATION OF THE WALL TOP OF CONCRETE WALL ELEVATION = [+10'-3"] SITE WALL, SEE SB101 FOR DESIGN SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

10
24'-3"

11
13'-6"

12

3 4

1
24'-6"

2
14'-0"

3
9'-5"

3.9

4
1'-3" 16'-6"

5
8'-5"

6
8'-1" B2

7
16'-6" 1'-3"

8.1
9'-5"

9
14'-1"

10 DN

STAIR TREADS, SEE ARCH, TYP 10

D5 SB302 TYP 6 B2 SB301

10

SB301

C1 SB302 A-12 PIER TOC = [+9'-6"] 7 8

1'-4"

C1 SB301 W12X14 BF-12 8'-4" 8

A
9 10 11 W12X26 (14) W12X45 (44) 23'-6" W12X14 W16X45 (16)

A.1

W12X26 (22)

W12X26 (22)

W12X26 (22)

W12X26 (22)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (22)

W12X26 (16)

1"

SB301

EJ 13'-10" SJ, TYP D5 1"

W12X26 (14)

W12X26 (14)

C3

TYP SIM A5 SF301 W14X61 (34) 4'-9 1/2" 5 W14X82 (32) 2" W10X12 W10X12 W10X19 (12) W10X19 (12) W12X19 (-0'-2") W12X19 (-0'-2") 2" 3'-9" BF-C 2" A3 SF301 W12X16 W12X16 W12X16 W12X16 W14X48 (50)

TYP

W12X14

SIM W14X48 (46) W14X30 (12)

SB301

7'-6"

4" SOG A5 1" SB301 C-4 PIER TOC = [+9'-4"] W12X19 (10)

8'-4"

B1 BF-4 1'-4" SB301 B2 SB301

4 4'-4" W10X12 3"

B6 SF301

TYP

W10X12

B6 SF301 W12X26 (24) W12X26 (8)

SIM

D.9 E
8'-8"

W12X19 (12) 6'-9" W10X26 B5 EJ SF301 W12X26 (10) (-0'-2") 6'-1"

W12X26 (10) 4" EOS (-0'-2") STAIRWELL 4" EOS

W12X26 (8) (-0'-2")

W12X26 (26)

17'-2"

W16X45 (14)

W10X12 W12X16 W12X16 W12X16

E
8'-8"

TYP 6

C2 SB302

A6 SF301

W8X13

W12X14 (+2'-0") 1 W10X12 (+2'-0") W12X14 (+2'-0") W12X14 (+2'-0") W12X14 (+2'-0") W12X14 (+2'-0") 1'-0" CANTILEVER, TYP D4 SF302 TYP C2 SF302

F
W10X12 9 W10X12 W12X26 (14) W12X26 (22) W12X26 (22) W12X16 W12X16 17'-2" W12X16 W12X16 TYP 2 3'-0"

W12X26 (8) (-0'-2") W10X12 ( +2'-0" ) W10X19 (12) (-0'-2") W18X40 (10) (-0'-2")

W14X30 (10)

F
1'-4"

W12X19 (10)

B2 W12X19 SF301 W12X16

W10X19 (12)

W10X12

(-0'-2") W10X12 (-0'-2") BF-8

(-0'-2")

W10X12 (+2'-0") ( +3'-0" )

8'-4"

2"

W10X12

F.1

W12X14 W12X14 6'-0"

G
W12X14 (+2'-0") W16X26 WITH (2) HSS8X4X3/16 (LSH) 7'-6"

ELEV. SHAFT 11

A3 SF301

6'-3"

B1 SF302 W14X82 (48) W14X43 (40)

2"

3 W14X61 (38)

W12X26 (10)

H
C1 7'-0" SF302

W14X82 (32) BF-H 5 A5 SF301 W10X12 B3 SF301 W12X26 (14) SIM

B3 SF301

OPP ( +3'-0" )

H
W16X31 WITH (2) HSS8X4X3/16 (LSH)

OPEN

H.5
SIM

W10X12 W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (20) W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (14)

W10X12

OPP D2 SF302 ( +3'-0" ) W12X14 (+2'-0") W16X26 WITH (2) HSS8X4X3/16 (LSH) W12X14 (+2'-0") 1'-0" CANTILEVER, TYP W12X14 (+2'-0") 1'-4"

TYP

TYP

W10X12 C2

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW J REVISIONS
No. Date Description

7/2/2012 9:38:20 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

W10X12

16'-6"

SF302 W18X40 (14) BF-1 W10X12

W10X12 (+2'-0")

8'-4"

W10X12

13'-10"

SIM

B6 SF301

J.9 K

W14X30 (42)

W14X30 (18)

W18X35 (20)

W14X30 (38) 1 W10X12 (+2'-0") W12X14 (+2'-0") 1'-0" CANTILEVER, TYP W12X14 (+2'-0") W10X12 (+2'-0") N

B6

C2 SF302

B6 SF301

C2 SF302

B6 SF301 D4 SF302 TYP

SF301

FIRST FLOOR FRAMING PLAN

FIRST FLOOR FRAMING PLAN


1/8" = 1'-0"

GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'

SF101
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

PENN STATE NEW RESIDENCE HALL

W12X19

PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5. REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+24-0]. LOW-SLOPE ROOF AREAS ARE 1 1/2" WIDE RIB, 20 GAGE STEEL ROOF DECK SUPPORTED ON STRUCTURAL STEEL FRAMING. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.

Architecture & Engineering

2. 3.

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

4.

5. 6. 7. 8. 9.

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

KEY NOTES
LOW SLOPE ROOF AREA COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 DEPRESSED SLAB SEE "TYPICAL BEAM END CONNECTION - TORSION CLIP" ON SF302, WHERE INDICATED IN STAIRWELLS, TYP SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

1 2

3 4

1
24'-6"

2
14'-0"

3
9'-5"

3.9

4
1'-3" 16'-6" C2

5
8'-5"

6
8'-1"

7
16'-6" 1'-3"

8.1
9'-5"

9
14'-1"

10
24'-3"

11
13'-6"

12
5

W12X14 (+2'-6 1/2") 1'-0" CANTILEVER, TYP TYP W12X14 (+2'-6 1/2") W12X14 (+2'-6 1/2") 1'-4" D4 SF302

B6 SF301 2'-10" EOS W18X35 (20)

SF302 2'-8" EOS W14X30 (40) 1'-4" EOS

B6 SF301 2'-1" EOS W14X30 (32)

C2 SF302 END OF VENEER SHELF ANGLE 2" EOS W18X35 (20) W12X26 4 7" STAIRWELL TYP 16'-5 1/2" BF-12 W21X57 (16)

W10X12 (+2'-6 1/2") W12X14 (+2'-6 1/2") 1'-0" CANTILEVER, TYP

A
A1 SF301

A.1
8'-4"

W12X14 (+2'-6 1/2") W16X26 WITH (2) HSS8X4X3/16 (LSH) W12X14 (+2'-6 1/2") D2 W14X30 (16) SF302

W10X12 W10X12 (+2'-6 1/2") W12X26 (16) W12X26 (16) W12X26 (16)

W12X26 (16)

W12X26 (16)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

B6 SF302

13'-10"

W16X31 WITH (2) HSS8x4x3/16 (LSH)

(+3'-6 1/2")

SF301

W10X12

B3 SF301 OPEN

A5 W10X12 6'-6"

C1 SF302

7'-6"

W16X26 WITH (2) HSS8X4X3/16 (LSH) W12X14 (+2'-6 1/2") W10X12 (+2'-6 1/2") W12X14 (+2'-6 1/2") 1'-0" CANTILEVER, TYP TYP D4 SF302 W12X14 (+2'-6 1/2")

B3 SF301 W10X12 (+2'-6 1/2") W12X19 (10) W10X12 W18X40 (12) BF-4 ( +3'-6 1/2" )

4'-4" W10X12 3"

2"

2" 3 1/2"

BF-C

1'-4" EOS 1'-0" EOS W10X12 W12X26 (14)

2" W10X19 (12) A3 W12X16 W12X16 W12X16 W12X16 W12X16 W12X19 W12X16 W12X16 (-0'-2") SF301

W10X19 (12)

2 W12X19 W10X12

4'-8" EOS

3'-6" EOS

9"

W14X30 (12)

W12X19

D
8'-4"

(-0'-2")

C4 SF301

SIM 17'-2"

3" 3"

TYP

1'-4" EOS

W10X12

W10X12

3'-8 3/4"

2-#4x20'-0" W12X26 (12)

2"

D.9
1'-4"

W10X12 9" 9"

2-#4x20'-0" W14X30 (12) 2'-8 1/2" W10X12 W10X12 2'-1" EOS W14X30 (24)

A2 SF301

W14X30 (34)

W12X26 (8)

C2 4'-0" END OF VENEER SHELF ANGLE 10'-10" EOS W18X35 (8) 12'-5" A1 W18X35 SF301 7" W12X26 (19) SF302

W12X14 (+2'-6 1/2") 11'-2" EOS

W12X26 (8) B1 SF301 W12X26 (16) W10X12 3'-0"

3'-0 1/2" W10X12 W10X12

W12X19 (10) W10X12

E
8'-8"

8'-8"

TYP

B1 SF301 W12X26 (8) A2 SF301 SF302 C6 SF301

2" EOS C4 SF301

W12X26 (10) 6'-1"

W12X19 (10) 9" 6'-3" W12X19 (10) W12X19

W14X30 (12) 2" W10X19 (12) (-0'-2") W18X40 (14) (-0'-2")

F
9'-8" A1 W12X14 (-2'-0") 1'-7" CANTILEVER, TYP W12X14 (-2'-0")

B6 SF301 W12X16 W12X16 TYP W12X16

W10X19 (12)

W10X12 B2 W12X16 SF301 ELEV. SHAFT 5

2" (-0'-2")

W10X12 (-0'-2") W10X12 (-0'-2") BF-8

B6 SF302

STAIRWELL

W10X12

( -2'-0" )

A3 SF301 3

1'-0" 1'-4"

G
W12X14 (-2'-0") D1 SF302 TYP 7'-6"

TYP

8 1/2"

B1 SF302 W14X43 (40)

W12X26 (10)

H
9'-10" EOS

W14X61 (38) 9"

2"

W18X55 (30) BF-H A5 SF301 C4 1'-8" 11" W12X19 (-2'-0")

W14X61 (26)

W10X12 (-2'-0") W12X14 (-2'-0") W8X10 (-2'-0") W12X14 (-2'-0") 1'-7" CANTILEVER, TYP 13'-10"

H CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW J
9'-8"

C1

W10X12 (-2'-0")

H.5
23'-6"

SF302

W10X12 TYP W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (20) W12X26 (14) W12X26 (14) W12X26 (20) W12X26 (14) TYP

W12X26 (14)

4'-8" EOS

1'-0" EOS W10X12

W14X30 (30)

1'-4" EOS

SF302

W10X12 W12X40 (-2'-0") 1'-0" W12X14 (-2'-0") 1

W10X12

7/2/2012 9:17:07 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

C4 SIM SF301

REVISIONS
No. Date Description

W18X40 (14)

BF-1

W10X12 1'-4" EOS 1'-4" EOS

W10X12 A2 SF301 W18X35 (28) W10X12 (-2'-0") W12X14 (-2'-0") W12X14 (-2'-0") 1'-7" CANTILEVER, TYP

A2 SF301

W18X35 (26)

W18X35 (18)

W18X40 (40)

C6 SF301

10'-10" EOS

11'-2" EOS

11'-1" EOS C6 SF301 C4 SF301

10'-11" EOS C6 SF301

SECOND FLOOR FRAMING PLAN

C4 SF301

SECOND FLOOR FRAMING PLAN


1/8" = 1'-0"

GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'

SF102
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

4'-1 1/4"

W14X61 (34)

W18X55 (30)

W14X48 (50)

W14X48 (46)

PENN STATE NEW RESIDENCE HALL

W12X26 (8)

W12X16

W12X16

17'-2"

1'-4" EOS

9"

9"

6 1/2"

W10X12

TYP

TYP

23'-6"

( +3'-6 1/2" )

W14X34 (24)

W10X12

1'-4" EOS

PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5. REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+36-0]. LOW-SLOPE ROOF AREAS ARE 1 1/2" WIDE RIB, 20 GAGE STEEL ROOF DECK SUPPORTED ON STRUCTURAL STEEL FRAMING. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.

Architecture & Engineering

2. 3.

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

4.

5. 6. 7. 8. 9.

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

KEY NOTES

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

1 2

LOW SLOPE ROOF AREA COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 DEPRESSED SLAB SEE "TYPICAL BEAM END CONNECTION - TORSION CLIP" ON SF302, WHERE INDICATED IN STAIRWELLS, TYP SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502

1
24'-6"

2
14'-0"

3
9'-5"

3.9

4
1'-3" 16'-6" C4

5
8'-5"

6
8'-1"

7
16'-6"

8
10'-8"

9
14'-1"

10
24'-3" C4

11
13'-6"

12

C6 SF301 2'-10" EOS W12X19 (-4'-0 1/2")

C6 SF301 2'-8" EOS 2'-1" EOS W18X35 (28)

SF301

SF301 2" EOS W12X26 1'-4" EOS W18X35 (30)

A1 SF301

W12X14 (-4'-0 1/2") 9'-8" W12X14 (-4'-0 1/2")

1'-4" EOS

W12X14 (-4'-0 1/2") 1'-7" CANTILEVER, TYP A1 SF302 W10X12

W18X35 (34)

W18X35 (28)

4 7"

TYP W21X57 (16) BF-12

A1 SF301 16'-5 1/2" B6 SF302

W10X12 (-4'-0 1/2") W12X26 (14) W14X30 (28) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W12X26 (14) W10X12 ( -4'-0 1/2" )

STAIRWELL W14X34 (24)

B
W12X14 (-4'-0 1/2") W12X35 (-4'-0 1/2") 13'-10" D1 SF302

W10X12 C4 SF302

TYP

TYP

A5 SF301 9" 4'-4" 4'-1 1/4"

W10X12

W10X12

( -4'-0 1/2" )

W10X12

7'-6"

W10X12 (-4'-0 1/2") W12X14 (-4'-0 1/2")

W8X10 (-4'-0 1/2") W10X12 W12X19 (10)

2" W10X12 3" 3 1/2"

2"

1'-4" EOS A3 W10X12 W12X26 (14) W12X16 W12X16 W12X16 W12X16 W12X16 W12X16 W12X16 C4 SF301 SIM

BF-C

2" W10X19 (12) SF301 W12X19 (-0'-2")

W10X19 (12)

W12X19

W10X12

W10X12 (-4'-0 1/2") 9'-8" W12X14 (-4'-0 1/2") W12X14 (-4'-0 1/2") W12X14 (-4'-0 1/2") 1'-7" CANTILEVER, TYP A2 SF301

W18X40 (14) BF-4

W12X19

3"

(-0'-2")

W10X12

2 3'-8 3/4" 2-#4x20'-0" 3" W10X12 9" W12X19 (10)

TYP

W10X12

1'-0" EOS

2-#4x20'-0" 2" W14X30 (12) 9" 2'-8 1/2" W10X12 W10X12 1'-4" EOS B1 SF301 W12X26 (8) A2 W18X40 (14) (-0'-2") SF301 W10X12 W10X19 (12) W10X19 (12) (-0'-2") (-0'-2") (-0'-2") C6 SF301 2'-1" EOS C4 SF301 W14X30 (24) W14X30 (34) W12X26 (8) 2" EOS

A2 SF301

E
A1 8'-8" SF301 10'-10" EOS

W12X26 (12) C4 SF301 11'-2" EOS C6 SF301 B1 SF301 3'-0" W12X26 (8) 3'-0 1/2" W10X12 W10X12

W10X12

F
12'-5" A1 W18X35 SF301 17'-2"

W12X26 (10) W10X12 1'-4" EOS W21X57 (8) 7" W12X26 (20) W12X16 W12X16 W14X30 (42) 6'-1"

W12X19 (10) 9" 6'-3" W12X19 (10) W12X19

9"

W14X30 (12) 2"

W12X16

W12X16

W12X16

TYP

W10X12 B2 SF301 ELEV. SHAFT 5 W14X61 (38) 3 W12X16

2"

B6 SF302 TYP 4

STAIRWELL

1'-0" EOS 4'-0" EOS

A3 SF301

W10X12 (-0'-2") BF-8

B1 8 1/2" SF302 W14X43 (40) W14X61 (26)

W12X26 (10)

H
C1 9'-10" EOS SF302

W18X55 (30) 9" BF-H A5 1'-8" EOS C1 SF301 W10X12 1'-4" EOS SF302

10" EOS 7'-2" EOS

3'-4" EOS

2"

1'-4" EOS

SIM

4'-8" EOS

3'-6" EOS

9"

W12X26 (14)

W12X26 (20)

W12X26 (20)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (20)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

23'-6"

4'-8" EOS

SIM C4 W18X40 (14) SF301 BF-1 W10X12

7/2/2012 9:17:08 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

C4 SF301 W14X30 (26) W10X12

4'-0" EOS

TYP

1'-0" EOS W10X12

SIM

3'-4" EOS

H.5

W10X12

1'-4" EOS 1'-0" EOS

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

TYP W10X12 1'-4" EOS 1'-4" EOS A2 SF301

A2 SF301

W18X35 (26)

W18X35 (18)

W18X40 (40)

W18X35 (28)

C6 SF301

10'-10" EOS C4 SF301

11'-2" EOS

C6 SF301

11'-1" EOS C4 SF301

10'-11" EOS

C6 SF301

THIRD FLOOR FRAMING PLAN

THIRD FLOOR FRAMING PLAN


1/8" = 1'-0"

GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'

SF103
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

W12X14 (-4'-0 1/2") 1'-7" CANTILEVER, TYP

W14X61 (34)

W18X55 (30)

W14X48 (50)

W14X48 (46)

W14X30 (12)

6'-6"

SF302

6 1/2"

11"

C1

PENN STATE NEW RESIDENCE HALL

W12X26 (8)

PLAN NOTES
1. TYPICAL FLOOR CONSTRUCTION IS 3.5 LIGHTWEIGHT CONCRETE ON 2 DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5.5 REINFORCE SLAB WITH 6x6 W2.1xW2.1 WWF PLACED 3/4 CLEAR OF TOP OF SLAB, FULLY SUPPORTED. COMPOSITE SLAB ON DECK IS DESIGNED AS UNSHORED COMPOSITE CONSTRUCTION. TOP OF STRUCTURAL STEEL ELEVATION IS 5.5 BELOW TOP OF SLAB, UNLESS OTHERWISE NOTED. TOP OF STEEL, WHERE NOTED THUS (+/-X-X), IS RELATIVE TO TOP OF STEEL ELEVATION AT THIS FLOOR. TOP OF FLOOR SLAB ELEVATION = [+48-0]. UNLESS OTHERWISE NOTED, FLOOR BEAMS ARE EQUALLY SPACED BETWEEN COLUMN LINES. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULES. SEE "TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS, AND DEPRESSION CORNERS" ON SF501. CMU ELEVATOR SHAFT WALLS ARE TYPE MW1. SEE WALL REINFORCING SCHEDULE ON SHEET SF601.

Architecture & Engineering

2. 3.

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

4. 5. 6. 7. 8.

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

KEY NOTES
COORDINATE OPENINGS WITH ARCH AND MECH. SEE "TYPICAL DECK SUPPORT AT FLOOR OPENING" ON SHEET SF502 DEPRESSED SLAB SEE "TYPICAL BEAM END CONNECTION - TORSION CLIP" ON SF302, WHERE INDICATED IN STAIRWELLS, TYP SEE "TYPICAL MOMENT CONNECTION AT COLUMN" ON SHEET SF501 SEE "TYPICAL ELEVATED SLAB AT ELEVATOR DOOR" ON SHEET SB502

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

2 3

1
24'-6"

2
23'-5"

3.9
1'-3"

4
16'-6"

5
8'-5"

6
8'-1"

7
16'-6"

8
24'-9"

10
24'-3" C4

11
13'-6"

12

4 5

C6 SF301 2'-10" EOS

C4 SF301 2'-8" EOS

C6 SF301 2'-1" EOS W18X35 (44)

SF301 2" EOS W21X44 (24)

A1 SF301

1'-4" EOS

SIM C4 SF301 W10X12 1'-0" EOS

1'-4" EOS

W18X40 (48)

W18X40 (38)

W12X26 A1 BF-12 7" 3 TYP W21X57 (16) SF301 16'-5 1/2" B6 SF302

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

23'-6"

W18X35 (28)

W10X12

TYP

TYP

W12X26 (14)

W14X34 (24)

3'-7" EOS

STAIRWELL W12X26 (8) W10X12

3'-4" EOS

4'-4" W14X61 (34) 9" W18X55 (30) 2" 9" BF-C 2" A3 W10X19 (12) W10X19 (12) SF301 W12X16 W12X16 W12X16 W12X16 W12X16 W12X19 W12X16 TYP W14X48 (50) W14X48 (46) 4'-1 1/4"

SF302

1'-3" EOS 3'-4" EOS

2" W10X12 3" 3" 3 1/2"

1'-4" EOS 1'-0" EOS W10X12 W12X16

3'-7" EOS

W18X40 (14)

W12X19 (10)

C4 SF301

SIM

W12X19

W10X12

(-0'-2")

W12X19

(-0'-2")

17'-2"

BF-4

3'-8 3/4"

A2 SF301

2-#4x20'-0" W12X26 (10)

3"

C4 8'-8" A1 SF301 10'-10" EOS W21X57 (12) 12'-5" A1 W18X40 W12X16 W12X16 SF301 17'-2" W12X26 (20) 1'-4" EOS SF301 11'-2" EOS

C6 SF301

3'-0 1/2" W10X12 W10X12 W10X12

9"

W10X12 9" W12X19 (10)

2-#4x20'-0" 2" W14X30 (12) 2'-8 1/2" W10X12 W10X12 B1 SF301 W12X26 (8) A2 W18X40 (14) (-0'-2") SF301 C6 SF301 2'-1" EOS W14X30 (42)

1'-4" EOS

1'-0" EOS

W10X12

W10X12

W12X26 (14)

A2 SF301

W18X35 (16)

W12X26 (8) 2" EOS

W12X26 (8) B1 SF301 3'-0"

C4 SF301

W12X26 (10) W10X12 W18X35 (22) 6'-1"

W12X19 (10) 9"

9"

W14X30 (12) 2"

W12X19 (10)

W12X16

W12X16

W12X16

TYP

W10X19 (12)

W10X19 (12)

W10X12 B2 SF301 ELEV. SHAFT 5 W12X16

6'-3" W12X19 (-0'-2") (-0'-2")

W10X12 (-0'-2")

B6 SF302

STAIRWELL

1'-0" EOS 4'-0" EOS

A3 SF301 2

W10X12 (-0'-2") BF-8

8 1/2"

W12X26 (10)

H
9'-10" EOS C1 SF302

W14X43 (40) W14X61 (26)

W14X61 (38) 9"

2"

SF302

W18X55 (30) BF-H A5 SF301 1'-8" EOS SF302 W18X35 (28) W10X12 10" EOS 7'-2" C1

3'-4" EOS

TYP

7"

B1

2"

1'-4" EOS

4'-8" EOS

W10X12

3'-6" EOS

1'-4" EOS

W12X26 (20)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (14)

W12X26 (20)

W12X26 (14)

W12X26 (20)

1'-4" EOS

W12X26 (14)

W12X26 (14)

SIM 23'-6" 4'-8" EOS C4 SF301 W10X12 1'-0" EOS W18X40 (14) BF-1

TYP

TYP

W12X26 (14)

W10X12

7/2/2012 9:17:10 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

SF301 W10X12 1'-0" EOS A2 SF301

4'-0" EOS

C4

SIM

3'-4" EOS

H.5

W10X12

1'-4" EOS

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

W10X12

A2

SF301

W18X40 (38)

1'-4" EOS

W18X35 (38)

W21X44 (33)

1'-4" EOS

W18X40 (38)

C6 SF301

10'-10" EOS C4 SF301

11'-2" EOS C6 SF301

11'-1" EOS C4 SF301

10'-11" EOS

C6 SF301

FOURTH FLOOR FRAMING PLAN

FOURTH FLOOR FRAMING PLAN


1/8" = 1'-0"

GRAPHIC SCALE(S)
0 1/8" = 1' - 0" 5' 10' 15' 30'

SF104
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

W14X30 (12)

6'-6"

SF302

7'-7" EOS

1'-4" EOS 1'-8" EOS

6 1/2"

C1

W10X12

A5 SF301

C1

PENN STATE NEW RESIDENCE HALL

PLAN NOTES
LOCATE AND COORDINATE MECHANICAL DUCTS 12 F E WP 1'-0" MIN 6" TOP CHORD 7 PROVIDE SUPPORT FOR MECHANICAL DUCTS K A RAFTER TAIL, WP OMIT AT RT-2 4'-8" F 7 1'-0" RAFTER TAIL, OMIT AT RT-2 LOCATE AND COORDINATE MECHANICAL DUCTS PROVIDE SUPPORT FOR MECHANICAL DUCTS 2. K 1. TYPICAL ROOF FRAMING IS 1 1/2 WIDE RIB, 20 GAGE, STEEL ROOF DECK ON ENGINEERED COLD-FORMED STEEL TRUSSES, SUPPORTED ON STRUCTURAL STEEL FRAMING. LOW-SLOPE ROOF AREA AND ELEVATOR CAP ARE 3" LIGHTWEIGHT CONCRETE ON 2" DEEP COMPOSITE STEEL DECK WITH TOTAL MINIMUM SLAB THICKNESS EQUAL TO 5". REINFORCE SLAB WITH 6x6-W2.1xW2.1 WWF PLACED 3/4" CLEAR OF TOP OF SLAB, FULLY SUPPORTED. MAXIMUM TRUSS SPACING IS 4-0 UON. COORDINATE LAYOUT OF COLD-FORMED TRUSSES WITH MECHANICAL DRAWINGS. TYP TOS AND TRUSS BEARING ELEVATION = [+60-0]. SEE SF601 FOR COLUMN SCHEDULE AND WALL REINFORCING SCHEDULE. RT-X = ROOF TRUSS TYPE. SEE ROOF TRUSS PROFILES THIS SHEET. SEE "TYPICAL DRAG TRUSS TYPE A" ON SF501 AND "TYPICAL DRAG TRUSS TYPE B" ON SF502

Architecture & Engineering

MIN 6" TOP CHORD 12

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

3. 4.

4'-8"

4"

17'-2" 40'-8" AT ATTIC WALKWAY, PROVIDE 12" DEPTH IN BOTTOM CHORD FOR INSULATION THICKNESS

4"

17'-2"

ELEV SHAFT 40'-8" AT ATTIC WALKWAY, PROVIDE 12" DEPTH IN BOTTOM CHORD FOR INSULATION THICKNESS

5. 6. 7.

RT-1 AND RT-2


FASTEN EDGE OF DECK TO TOP CHORD WITH #12 SCREWS, MIN 2 PER DECK RIB F E FRAME AROUND MECH PLENUM FOR CIRCULAR LOUVER OPENING IN GABLE END K A WP F 7 1'-0" 12 ROOF HATCH LOCATION BETWEEN TRUSSES, SEE PLAN

RT-3
LOCATE AND COORDINATE MECHANICAL DUCTS MIN 6" TOP CHORD PROVIDE SUPPORT FOR MECHANICAL DUCTS 600S162-33, CONT, TYP. KEEP AREA CLEAR OF DIAGONAL MEMBERS

VERTICAL TRUSS MEMBERS

DESIGN TRUSS FRAMING TO TRANSFER LATERAL DIAPHRAGM LOADS TO BOTTOM CHORD

RAFTER TAIL, OMIT AT RT-2

WALKWAY SURFACE MADE OF 43 MIL STUDS, SIDE-TO-SIDE, FASTENED TO TRUSS BOTTOM CHORD

4'-8"

TRUSS BOTTOM CHORD

TWO-PLY TRUSS, MIN

SUPPORT CONDITIONS MAY VARY FOR DIMENSIONS AND OTHER ELEMENTS, SEE RT-1 DETAIL

4"

17'-2" 40'-8"

GABLE END

PROVIDE ADDITIONAL VERTICAL FRAMING TO SUPPORT WALKWAY HANDRAILS

RT-4

ATTIC WALKWAY
600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

TRUSS PROFILES
NOT TO SCALE #

12"

PROVIDE FRAMING TO SUPPORT LADDER, SEE ARCH

12" DEPTH IN BOTTOM CHORD ATTIC WALKWAY

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

KEY NOTES
LOW-SLOPE ROOF AREA STEEL KNEE-BRACED FRAME. SEE "TYPICAL STEEL-FRAMED KNEE BRACE" ON SHEET SF501 SLAB-ON-DECK ELEVATOR CAP. TOC = 6'-8" ABOVE TOP OF STEEL. SEE AE421 FOR ELEVATOR SUPPORT MEMBERS PROVIDED BY ELEVATOR SUPPLIER ROOF ACCESS HATCH. SEE DETAIL ON SHEET AE106 AND "TYPICAL DECK SUPPORT AT ROOF OPENING" ON SF502 OPENING IN CMU WALL FOR MECHANICAL DUCT. COORDINATE SIZE AND LOCATION WITH MECH DRAWINGS ATTIC ACCESS, SEE ARCH. SEPARATE TRUSSES AROUND OPENING MECHANICAL DUCTWORK IN ATTIC. COORDINATE LOCATIONS AND SIZES WITH MECHANICAL PLANS MECHANICAL SHAFT THROUGH ATTIC. LOCATE TRUSSES ON BOTH SIDES OF SHAFT (MANTAIN CLEAR AREA ABOVE SHAFT)

1 2

1
24'-6"

2
23'-5"

3.9

4
1'-3" 16'-6"

5
8'-5"

6
8'-1"

7
16'-6"

8
24'-9"

10
24'-3"

11
13'-6"

12

6 GABLE-END DRAG TRUSS. WIND LOAD = 20.6 K SEISMIC LD = 1.5 K D1 SF301 D3 SF301 2 W14X38 RT-1 12 7 12 RT-1 RT-1 7 W12X22 W12X26 W12X26 W12X22 TYP RT-2 W12X35 RT-1 RT-1 W18X60 RT-1 8'-9" DRAG TRUSS TYPE A 2 W10X22 2 GABLE-END DRAG TRUSS. WIND LOAD = 20.6 K SEISMIC LD = 1.5 K 7

W14X38 D2 W18X60 8'-9" SF301 7 12 12 7

W14X38

4'-6"

W10X12 W12X22 9" 5'-4" 23'-6" C6X10.5 W10X12 HSS6X6X3/16 ( +2'-8" ) 3'-8" 4'-6"

BF-12

RT-2

SF301 W10X12 6 W12X22 W10X12 HSS6X6X3/16 ( +2'-8" ) C6X10.5

W12X26

3'-8"

5'-4"

C1
W8 0 X1

DRAG TRUSS TYPE B

5'-2"

12

W10X12

ATTIC WALKWAY

D4 SF301

W10X12

D4 SF301

C6X10.5 C1

W10X12

TYP

BF-C

TYP 12 7

TYP

W12X22

5'-4"

W10X22

W10X22

W12X22

W10X22

W10X22

17'-2"

12

W10X12 W18X40

W12X22

SF301

C6X10.5 W14X34

W12X22

12 7 12 7

8'-9"

BF-4

D2 SIM SF301

E
3'-0 1/2" W12X26 8'-8"

W14X30

W14X30

W14X30 2'-8 1/2"

W14X34

W12X30

W10X22

W10X12

W10X12

W10X12

W10X12

W10X12

W12X26

D5 SF301

C3 SF301

TYP

TYP

TYP

C3 1 SF301

COLD-FORMED STEEL TRUSSES AT 4'-0" OC MAX, TYP

F
4'-6" W14X34 8'-9"

W14X34 7

12

12 7

W14X30 3

W14X30

W14X30

W14X30 W18X40 8'-9"

W10X22

W10X22

W10X22

W10X22

W10X12 5'-4"

W12X22

W12X22

TYP 12 7

17'-2"

C2 SF301 5

W10X12 5'-4" C1 SF301 BF-8 W10X12 C6X10.5 HSS6X6X3/16 ( +2'-8" ) D4 SF301 5'-2" 3'-8"

TYP

W10X12 HSS6X6X3/16 ( +2'-8" ) 3'-8" W10X12 W12X22 W12X26 W14X38

12

C6X10.5

DRAG TRUSS TYPE B W14X48 BF-H

W14X38

W14X48

W10X12

5'-2"

12

D4 SF301

ATTIC WALKWAY 7 W12X26 7 12 W10X12 W10X12 W12X22 4'-6" W10X12 RT-1 W18X60

8'-9"

5'-4"

10 8X W

W10X12

W10X12 W12X30

3'-8"

W10X12 W12X22 TYP RT-2

W12X45

W12X26

23'-6"

TYP RT-2

C6X10.5

3'-8"

H.5

RT-4

RT-4

5'-4"

C1 SF301 BF-1 W10X12 W18X60

7/2/2012 9:17:12 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

5'-4"

9"

C6X10.5

GABLE-END DRAG TRUSS. WIND LOAD = 18.5 K SEISMIC LD = 1.4 K

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

RT-1

RT-1

RT-3

RT-3

RT-1

RT-2

RT-2

RT-2

RT-1

12 7

12 7

12 7 12 7

8'-9"

RT-1

GABLE-END DRAG TRUSS. WIND LOAD = 18.5 K SEISMIC LD = 1.4 K

D2 SF301

D2 SF301

K
2

W14X38

W14X38

W14X43

W14X38

2 DRAG TRUSS TYPE A

2 D3 SF301 COLD-FORMED STEEL TRUSSES AT 4'-0" OC MAX, TYP

8'-9"

ROOF FRAMING PLAN

GRAPHIC SCALE(S)

ROOF FRAMING PLAN


1/8" = 1'-0" 1/8" = 1' - 0"

5'

10'

15'

30'

SF105
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

3'-8"

3'-8"

W14X43

W14X48

W14X38

W14X38

W12X22

W10X12

PENN STATE NEW RESIDENCE HALL

12

5'-2"

1
K
16'-6"

2
H.5 E
17'-2"

3
C H

4
F
17'-2"

5
C
23'-6"

6
A

Architecture & Engineering

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


W18X60 V=10k ROOF LEVEL [SEE PLAN] W18X40 V=10k ROOF LEVEL [SEE PLAN] W18X40 V=10k ROOF LEVEL [SEE PLAN] W18X60 V=10k ROOF LEVEL [SEE PLAN] 7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

HS S5 X5 X3 /1 P= 6 20 k

HS S5 X P= 30 k

5X 1/4

1/4 5X X S5 k HS 20 P=

1 /4 5X X S5 HS k 20 P=

W18X40 (14) V=20k

FOURTH FLOOR [SEE PLAN]

W18X40 (14)

V=30k

FOURTH FLOOR [SEE PLAN]

C5 SF202

TYP W18X40 (14) V=30k FOURTH FLOOR [SEE PLAN] W21X57 (16) V=50k FOURTH FLOOR [SEE PLAN]

HS S

5X 5

HS
X3 /16

P= 40 k

P= 50 k

S5 X5 X

1/4

/4 X1 5 X S5 S k H 40 P=

/4 X1 X5 5 S HS k 40 P=

W18X40 (14)

V=20k

THIRD FLOOR [SEE PLAN] D4 SF202 TYP

W18X40 (14)

V=20k

THIRD FLOOR [SEE PLAN]

W18X40 (14) V=20k

THIRD FLOOR [SEE PLAN]

W21X57 (16) V=40k

THIRD FLOOR [SEE PLAN]

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

HS S

5X

HS S5

P= 60 k

5X

1/4

P= 70 k

X5 X5 /1

/8 X3 5 X S5 k HS 70 P=

/4 X1 X6 6 S HS k 70 P=

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

TYP C5 SF202 W12X26 (10) V=20k SECOND FLOOR [SEE PLAN]

W18X40 (12) V=20k

SECOND FLOOR [SEE PLAN]

W18X40 (14) V=20k

SECOND FLOOR [SEE PLAN] W21X57 (16) V=40k

SECOND FLOOR [SEE PLAN]

TYP

D4 SF202 OPP

HS S

5X

P= 80 k

5X

3/8

HS S6 X6 X3 P= /8 14 0k

1/2 5X X S5 k HS 80 = P

THROUGH PLATE CONNECTION TO TRANSFER MIN 50k TENSION B4 SF202 B4 SF202

3/8 6X X S6 HS 0k 10 P=

W12X26 (10) V=20k

FIRST FLOOR [SEE PLAN]

FIRST FLOOR [SEE PLAN]

W18X40 (10)

V=20k

FIRST FLOOR [SEE PLAN]

W16X45 (16)

V=40k

FIRST FLOOR [SEE PLAN]

COORDINATE WALL OPENINGS FOR DUCTWORK WITH MECHANICAL DRAWINGS BEAM BEYOND, TYP.
HS S5 X3 P= /8 11 0k X5

8"

9'-0" TOC [SEE PLAN]

COLUMN BEYOND

GROUND FLOOR [SEE PLAN]

GROUND FLOOR [SEE PLAN]

GROUND FLOOR [SEE PLAN]

GROUND FLOOR [SEE PLAN]

8" CONCRETE SHEAR WALL

12" CONCRETE SHEAR WALL

8" CONCRETE WALL CORNER OF CONCRETE WALL

B1
B

BRACED FRAME "BF-1" ELEVATION


1/4" = 1'-0"

B2

BRACED FRAME "BF-4" ELEVATION


1/4" = 1'-0"

B4

BRACED FRAME "BF-8" ELEVATION


1/4" = 1'-0"

B5

BRACED FRAME "BF-12" ELEVATION


1/4" = 1'-0"

NOTES: 1. 2. BRACED FRAME CONNECTION DESIGN IS DELEGATED TO THE CONTRACTOR. AXIAL LOAD INDICATED AS P=x. DESIGN CONNECTION FOR TENSION AND COMPRESSION. VERTICAL SHEAR REACTION INDICATED AS V=x. FORCES ARE IN KIPS. FORCES SHOWN ARE FACTORED.

3.

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:17:17 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt REVISIONS
No. Date Description

BRACED FRAME ELEVATIONS

GRAPHIC SCALE(S)
0 1/4" = 1' - 0" 1' 5' 10' 15'

SF201
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

SLAB BEYOND

PENN STATE NEW RESIDENCE HALL

1/2 5X X S5 k HS 90 P=

1
6
24'-7"

2
8 6
24'-7"

3
8

CL OF FRAME

Architecture & Engineering

CL COL

TYP 1/4" FULL DEPTH STIFFENER EA SIDE OF BEAM AT EA END OF GUSSET PL BEAM, SEE PLAN TOS ERECTION BOLT, TYP

WORKING POINT 2'-6" BEAM, SEE PLAN TOS [SEE PLAN]

CAP PLATE

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

W14X48 V=20k

ROOF LEVEL [SEE PLAN]

W14X48 V=20k

ROOF LEVEL [SEE PLAN] WORKING POINT

[SEE PLAN]

COL, SEE PLAN

CL BEAM

CL BEAM

HS

HS S5 X5 X1 P= /4 30 k

/4 X1 X5 k S5 30 P=

HS S5 X5 X1 P= /4 30 k

HS /4 X1 X5 S5 3 P= 0k

GUSSET PLATE, 3/8" MIN. CENTER ON BEAM. FS NS ERECTION BOLT 6" MIN CL BRACE BRACE, SEE BRACED FRAME ELEVATION GUSSET PLATE, 3/8" MIN. CENTER ON BEAM. TYP. BRACE, SEE BRACED FRAME ELEVATION, TYP FS NS, 6" TYP MIN

C5 SF202

TYP W18X55 (30) V=40k FOURTH FLOOR [SEE PLAN]

C5 SF202

TYP W18X55 (30) V=40k FOURTH FLOOR [SEE PLAN]

CL BRACE, TYP

HS S5 X5 X1 P= /4 60 k

HS S5 X5 X1 P= /4 60 k

D4

CONCENTRICALLY BRACED FRAME CONNECTION


NOT TO SCALE

D5

ECCENTRIC BRACED FRAME CONNECTION


NOT TO SCALE

/4 X1 X5 S5 k HS 60 P=

/4 X1 X5 S5 k 60 HS P=

CL COLUMN GUSSET PLATE, 3/8" MIN. CENTER ON BEAM. SIZE TO SUIT. TOS [SEE PLAN] SLAB NOT SHOWN ERECTION BOLT CL BRACE

W18X55 (30) V=40k

THIRD FLOOR [SEE PLAN]

W18X55 (30) V=40k

THIRD FLOOR [SEE PLAN]

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

HS S5 X5 X1 P= /4 70 k

HS S5 X5

P=

D5 SF202

D5 SF202

L5x3x1/4 (LLV), 8" LONG AT 36" OC WITH 2 BOLTS AT EACH 6 1/2" TOC [SEE PLAN]

TYP

TYP

STEEL BEAM SEE ELEVATION FOR BRACE SIZE, SLOT HSS AS REQ'D AT GUSSET
/2" 1 1 IN M

70

T/STEEL 1/2" 1/4 1/4 8 TYP 2-6 [SEE PLAN]

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

X1 /4

/4 X1 X5 S5 k HS 70 P=

/4 X1 X5 S5 k HS 70 P=

CL BEAM

3/4" BOLT IN LONG-SLOTTED VERTICAL HOLES W18X55 (30) V=40k SECOND FLOOR [SEE PLAN] W18X55 (30) V=40k SECOND FLOOR [SEE PLAN] CONT WT4x10.5 WITH 3/4"x9" HEADED STUDS AT 18" OC

SEE PLAN FOR COL ORIENTATION WORKING POINT BEAM, SEE PLAN 6" MIN TYP EA SIDE 6" MIN

HS S5 X5 X1 P= /4 80 k

HS S5 X5 X1 P= /4 80 k

C4

BRACED FRAME CONNECTION AT TOP OF CONCRETE SHEAR WALL


1" = 1'-0"

/4 X1 X5 S5 k HS 80 P=

/4 X1 X5 S5 k HS 80 P=

C5

BRACED FRAME CONNECTION


NOT TO SCALE

C4 SF202

C4 SF202 W14X82 (32) V=40k FIRST FLOOR [SEE PLAN] W14X82 (32) V=40k FIRST FLOOR [SEE PLAN] 3/4" HEADED STUDS, SEE PLAN 12 SLAB ON DECK, SEE PLAN SEE PLAN #4 HAIRPIN BARS @ 48" OC. #4 CONT 1/4" BENT PLATE, CONT 1" GAP, FILL WITH COMPRESSIBLE MATERIAL

1/4" FULL-DEPTH STIFFENER AT 48" OC MAX STEEL BEAM, SEE PLAN, TYP. GROUND FLOOR [SEE PLAN] GROUND FLOOR [SEE PLAN] 5/16 3-12

VENEER, SEE ARCH

PENN STATE NEW RESIDENCE HALL


REVISIONS
No. Date

COORDINATE WALL OPENINGS FOR DUCTWORK WITH MECHANICAL DRAWINGS

COORDINATE WALL OPENINGS FOR DUCTWORK WITH MECHANICAL DRAWINGS

TOP OF SLAB [SEE PLAN]

1/2" A307 BOLT OR BLIND BOLT @ 48" OC MAX FOR ERECTION

DOOR OPENING, SEE ARCH FOR SIZE AND LOCATION

L6x4x5/8" (LLV), CONT WITH 2" VERT SLOTS FOR ANCHORS AT 6" OC (FILL 1/2 OF HOLES WITH ANCHORS)

4"

1" HEAVY-DUTY EXPANSION ANCHOR @ 12" OC, 4" NOM. EMBEDMENT WITH 12.2k SHEAR CAPACITY, PLACE AT BOTTOM OF SLOT.

B1

BRACED FRAME "BF-C" ELEVATION


1/4" = 1'-0"

B2

BRACED FRAME "BF-H" ELEVATION


1/4" = 1'-0"

B4

SECTION
3/4" = 1'-0"

NOTES: 1. 2. BRACED FRAME CONNECTION DESIGN IS DELEGATED TO THE CONTRACTOR. AXIAL LOAD INDICATED AS P=x. DESIGN CONNECTION FOR TENSION AND COMPRESSION. VERTICAL SHEAR REACTION INDICATED AS V=x. FORCES ARE IN KIPS. FORCES SHOWN ARE FACTORED.

3.

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW 7/2/2012 9:17:21 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt
Description

GRAPHIC SCALE(S)
0 1/4" = 1' - 0" 0 3/4" = 1' - 0" 0 1" = 1' - 0" 6" 1' 2' 3' 6" 1' 2' 3' 4' 5' 1' 5' 10' 15'

BRACED FRAME ELEVATIONS AND DETAILS

SF202
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

1
COPING CAP, SEE ARCH

STEEL ROOF DECK, SEE PLAN 6"

Architecture & Engineering


FRP CORNICE, SEE ARCH MASONRY VENEER, SEE ARCH WP 6" CFS STUD, SEE ARCH CFS STUDS, SEE ARCH HSS6x6x3/16, CONT L2x2x1/4, GALV, CONT

1
CFS TRUSS OVER FRAMING COPING CAP, SEE ARCH

6"

CONT 14 GA BENT PLATE

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

E
CFS STUDS MASONRY VENEER, SEE ARCH STEEL STUD FRAMING NOT SHOWN STEEL ROOF DECK, SEE PLAN

CFS CLIP BY STUD DESIGNER

CFS TRUSSES, SEE PLAN

4'-8" HEEL HEIGHT

MASONRY VENEER, SEE ARCH CHANNEL, SEE PLAN

TOS [+62'-8"]

CFS TRUSS

3 5/8" CFS BLOCKING AT 24" OC

SEE ARCH FOR OTHER ELEMENTS

L6x6x5/16, GALV, CONT LOOSE LINTEL DRAG TRUSS CONNECTION BY TRUSS SUPPLIER PL1/4"x12" CONT CONCRETE SLAB ON DECK, TYP. MASONRY VENEER, SEE ARCH 1'-0" L6x4x3/8 GALV LLH SHELF ANGLE 1-12 7 1/2" (2) 3/4" BOLTS AT EA. CONNECTION STL PLATE 1/4"x8"x12" AT 4'-0" OC MAX, COORD W/ TRUSS BRG LOCATIONS TOS [SEE PLAN]

MASONRY VENEER, SEE ARCH TOS [SEE PLAN] 3 5/8" CFS BLOCKING AT 24" OC

SHELF ANGLE [SEE ARCH] CFS TRUSS TOS [SEE PLAN] TOS [SEE PLAN] CFS ROOF TRUSS, SEE PLAN MASONRY VENEER, SEE ARCH 3 5/8" CFS BRACE AT EA TRUSS DEFLECTION TRACK DEFLECTION TRACK CFS STUDS BACKING UP MASONRY VENEER 4" TOS [SEE PLAN] L3x3x1/4, CONT 10"

CFS TRUSS 3 5/8" CFS BRACE AT EA TRUSS 3 5/8" CFS BRACE AT 24" OC

CURTAIN WALL, SEE ARCH (3) 3/4" BOLTS IN HORIZ SLOTS, SLIP CRITICAL L2x2x1/4, CONT C10x15.3 CANTILEVER STUB, SHOP WELD TO BEAM AT EA CHANNEL

STEEL BEAM, SEE PLAN MOMENT CONNECTION, SEE TYP DTL

D1

SECTION
3/4" = 1'-0"

CFS STUDS BACKING UP MASONRY VENEER

WIDE FLANGE BEAM BEYOND

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

MASONRY VENEER, SEE ARCH 6" CFS STUD WALL, SEE ARCH 2-12 HSS6x6x3/16, CONT PL3/16"x6" AT 16" OC FRP CORNICE, SEE ARCH TOS [+62'-8"] CFS TRUSSES, SEE PLAN L2x2x1/4, GALV

D2

SECTION
3/4" = 1'-0"

D3

SECTION
3/4" = 1'-0"

D4

SECTION
3/4" = 1'-0"

D5

SECTION - FLAT ROOF


3/4" = 1'-0"

VARIES 8" 16" MAX

#3 HAIRPIN BAR @ 48" OC EOS SEE PLAN #4 CONT 11" EOS 16 GA POURSTOP FASTENED TO DECK TOS [SEE PLAN] EA END, TYP WIND CONNECTION FOR CURTAIN WALL BY SUPPLIER SEE "TYPICAL VENEER SHELF ANGLE" DETAIL ON SF501 1/4" BENT PLATE, CONT 4" EOS TOP OF SLAB #4 CONT 1/4 2'-6" 3/4" TOP OF SLAB [SEE PLAN] 2-12 SEE "TYPICAL VENEER SHELF ANGLE" DETAIL ON SF501 TOP OF SLAB [SEE PLAN] SHELF ANGLE [SEE ARCH] #4 CONT

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

L6x6x5/16, CONT DRAG TRUSS CONNECTION BY TRUSS SUPPLIER PL1/4"x12" CONT, BREAK AT EACH PERPENDICULAR BEAM

[SEE PLAN] 8" CMU BOND BEAM WITH (2)#5 CONT 5/8" CARBON STEEL SCREW ANCHOR W/ 5" EMBED @ 24" OC. MAX W/ 3.4 KIP SHEAR CAPACITY PER ANCHOR ALONG FOUR SIDES OF ELEVATOR CAP LIGHT GAGE TRUSS PER PLAN, TYP TOP OF STEEL [ROOF]

10"

ELEVATOR CAP (SLAB ON DECK, SEE PLAN) L6x3 1/2x5/16 (LLV) CONT ON FOUR SIDES OF ELEVATOR CAP

TOS [SEE PLAN]

2-12 MASONRY VENEER, SEE ARCH (3) 3/4" BOLTS IN HORIZ SLOTS, SLIP CRITICAL

EA SIDE CMU SHAFT WALL

STEEL BEAM, SEE PLAN MOMENT CONNECTION, SEE TYP DTL SEE PLAN FOR WALL TYPE AND REINF.

L2 1/2x2 1/2x1/4 AT EACH STIFFENER, 48" OC MAX

DECK DIRECTION VARIES 3 SIDES, TYP STEEL BEAM, SEE PLAN, WITH FULL DEPTH BOLTED CONNECTION, SLIP CRITICAL AT EXTERIOR END WALL STUDS BELOW OMITTED FOR CLARITY

FULL-DEPTH STIFFENER AT EA BEAM CONN, ONE SIDE

BOLTED SHEAR CONNECTION, FULL DEPTH OF SUPPORTED MEMBER, WITH SLIP-CRITICAL BOLTS TO PREVENT ROTATION

C
C10x15.3 CANTILEVER STUB, SHOP WELD TO BEAM AT EACH CHANNEL

CFS STUD BELOW WITH DEFLECTION TRACK, SEE ARCH

C1

SECTION
3/4" = 1'-0" ALUMINUM CURTAIN WALL SYSTEM, SEE ARCH DWGS 4" 1/4" CONT BENT PLATE TOP OF SLAB [SEE PLAN] CURTAIN WALL CONNECTION BY SUPPLIER WEDGE-INSERT ANCHOR AT EA CURTAIN WALL CONNECTION, COORDINATE LOCATIONS WITH CURTAIN WALL SUPPLIER

C2

SECTION
3/4" = 1'-0"

C3

SECTION
3/4" = 1'-0"

C4

SECTION
3/4" = 1'-0"

1/4" FULL DEPTH STIFFENER AT EACH SUPPORTED BEAM AND AT 48" OC MAX

C6

SECTION - SLAB EDGE


3/4" = 1'-0"

16" BOND BEAM

L2 1/2x2 1/2x1/4 x 12" LONG AT EACH CORNER AND AT 3'-0" OC MAX WITH (2) 1/2" DIA x 4" HEADED STUDS

SEE PLAN 1/4 1/4

#4 CONT. AT EDGE SLAB AND DECK PER PLAN

SEE PLAN 2-12 2-12 TOP OF SLAB MASONRY VENEER, SEE ARCH DWGS

STL PLATE 1/4"x3"x6" ON TOP FLANGE OF BEAM

4"

COLD-FORMED STEEL POUR STOP BY DECK SUPPLIER #4 CONT TOC [SEE PLAN]

RECESS SLAB 1/4" AT EACH ANCHORAGE #4 BAR, CONTINUOUS, EXTEND 2'-0" PAST EACH CORNER BEAM, SEE PLAN 1/2" JOINT, FILL WITH FIRE CAULK

L3 1/2x2 1/2x1/4 (LLV), 12" LONG WITH (2) 1 1/2" VERTICAL SLOTS FOR ANCHORS, 2" FROM EACH END COORDINATE LOCATIONS AND REQUIREMENTS OF EMBEDS FOR ELEVATOR RAIL SUPPORTS WITH ELEVATOR SUPPLIER ELEVATOR SHAFT

COLUMN PER PLAN 3/16

EA END

[SEE PLAN] TOP OF STEEL [SEE PLAN] TOP OF STEEL [SEE PLAN] FULL-DEPTH STIFFENER AT EA BEAM CONN, ONE SIDE

HSS3x2x3/16, CONT (LSH) 1/4" STIFFENER NS/FS, ALIGN WITH HORIZ PLATE 3/8"x6"x8" VERT STL PLATE, CENTERED ON HORIZ PLATE 3/8"x8"x9" HORIZ STL PLATE W10 STL BEAM, SEE PLAN 1 1/2" MIN 3/16 POUR STOP AND OTHER ELEMENTS NOT SHOWN FOR CLARITY BEAM PER PLAN

BOLTED SHEAR CONNECTION, FULL DEPTH OF SUPPORTED MEMBER, WITH SLIP-CRITICAL BOLTS TO PREVENT ROTATION DEEP-LEG DEFLECTION TRACK AT HEAD OF WALL, TYP

STEEL BEAM, SEE PLAN NOMINAL 8" CONCRETE MASONRY WALL, SEE PLAN

B1

SECTION
3/4" = 1'-0"

B2

ELEVATOR SHAFT SECTION


1" = 1'-0"

B3

VESTIBULE FRAME LATERAL CONNECTION


1" = 1'-0"

B5

SECTION
3/4" = 1'-0"

B6

SECTION
3/4" = 1'-0" F 3/16" BENT PLATE RECESSED SLAB FOR JOINT COVER, SEE 4/AE514 1"

3/16" BENT PLATE

TOS [SEE PLAN] L7x4x3/8 GALV, CONT 3/16 3-8 1-12 NOTE: FOR OTHER ELEMENTS, SEE "TYPICAL VENEER SHELF ANGLE" ON SF501 TOC [SEE PLAN] 3-8 2-12 FULL-DEPTH STIFFENER, NS/FS. LOCATE AT CONNECTION FOR SUPPORTED BEAM AND AT 48" OC BEAM, SEE PLAN 2-12 SEE PLAN BOTTOM OF SHELF [SEE ARCH] SEE PLAN #3 AT 24" OC, 1/4 2-12 18" 18" VARIES 18" VARIES TOP OF SLAB [SEE PLAN] TOS [SEE PLAN] 1/4 1/4 1/4 1/4 L3x3x1/4, CONT STEEL BEAM, SEE PLAN STEEL BEAM, SEE PLAN 18" 1/4 2-12 SEE PLAN SEE PLAN 8" TYP 3/16 3/16 5/16"X2" PLATE, NS/FS (2) 3/4" BOLTS IN LONG SLOTS 1/4 TYP AT EA BEAM LOW-FRICTION STRUCTURAL BEARING WITH 10 KIPS CAPACITY, MIN 1/2" BEARING PLATE (3) 3/8" STIFFENERS 1/4 1/4 3/8" STIFFENER PLATE SECTION A-A 1/2" CLR

1/4

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

7/2/2012 9:17:28 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

BOTTOM OF SHELF [SEE ARCH] TOS [SEE PLAN]

HSS8x6x3/8 LSH

#3 AT 24" OC,

L3x3x1/4, CONT TOP OF SLAB [SEE PLAN] 2"

A
4"

3/8" FULL DEPTH STIFFENER

STEEL BEAM, SEE PLAN

MASONRY VENEER, SEE ARCH DWGS

TOS [SEE PLAN]

STAIR C8x11.5

DEEP-LEG DEFLECTION TRACK AT HEAD OF WALL, TYP

L3 1/2x3 1/2x1/4 x 6" MIN AT 30" OC

A6

SECTION
1 1/2" = 1'-0"

FRAMING SECTIONS AND DETAILS

GRAPHIC SCALE(S)
0 3/4" = 1' - 0" 6" 6" 3" 6" 1' 1' 9" 1' 2' 2' 3' 4' 3' 2' 5' 0 1" = 1' - 0" 0 1 1/2" = 1' - 0"

A1

SECTION
3/4" = 1'-0"

A2

SECTION
3/4" = 1'-0"

A3

SECTION
3/4" = 1'-0"

A5

SECTION
3/4" = 1'-0"

SF301
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

3/16

2 #5 CONTINUOUS

FOUR 3/4" A325 BOLTS, FINGER TIGHTEN IN LONG VERT SLOTS, PRETENSION AFTER CONCRETE IS PLACED ON FLOOR DECK

PENN STATE NEW RESIDENCE HALL

5/8" x 4" HEAVY SCREW ANCHOR AT TOP OF VERTICAL SLOT, BACK OFF 1/4 TURN AFTER INSTALLATION

Architecture & Engineering

FRP CORNICE, SEE ARCH

L4x4x3/8, CONT

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


MOMENT RESISTING CONNECTION WITH 10 KIP-FT CAPACITY ALUMINUM STOREFRONT, SEE ARCH 1'-0" END OF BEAM TOS [SEE PLAN] TYP 3-12 3-12 HSS MEMBER, TOP AND BOTTOM, SEE PLAN CFS STUDS, SEE ARCH BEAM, SEE PLAN 3/16 3/16 L2x2x3/16 AT EA CONN 3 3 SEE PLAN W12x14 SHOP ATTACHED TO GIRDER, TYP AT EA BEAM MOMENT RESISTING CONNECTION WITH 10 KIP-FT CAPACITY 1" L3x3x1/4" CONT 7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM MIN 16 GA CFS CLIP AT EA STUD WITH MIN (3) SELF-DRILLING SCREWS IN EACH LEG, TYP CFS FRAMING, SEE ARCH

MOMENT-RESISTING CONNECTION, WITH 10 KIP-FT CAPACITY TOS [SEE PLAN] 1"

SEE ARCH FOR CFS FRAMING

MIN 14 GA CFS CLIP AT EA STUD W/ MIN (3) #12 SELF-DRILLING SCREWS, MIN IN EA LEG

TOS [SEE PLAN]

3/16

EA END

3/16

3 W12x14, TYP SEE PLAN L4x4x3/16 HANGER AT EA BEAM INTERSECTION

L2 1/2x2 1/2x1/4 x 4" 3/16 L2x2x3/16 L4x4x1/4 CONT

MIN 14 GA CFS ANGLE CLIPS WITH MIN (3) #12 SCREWS, EA LEG

D1

SECTION
3/4" = 1'-0"

D2

SECTION
3/4" = 1'-0"

D4

SECTION
3/4" = 1'-0"

VARIES

D
WEDGE-INSERT ANCHOR AT EA CURTAIN WALL CONNECTION, COORDINATE LOCATIONS WITH CURTAIN WALL SUPPLIER EOS SEE PLAN

8"

16" MAX

3.9

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com
#4 HAIRPIN @ 32" OC 8"
4'-0"

#3 HAIRPIN BAR @ 48" OC 1/4" BENT PLATE 8" EOS SEE PLAN L4x4x1/4" 3'-0" TOP OF SLAB 1/4" BENT PLATE CONT 1/4 2-12 DECK DIRECTION VARIES TOP OF SLAB [SEE PLAN] EA END, TYP BOLTED CONNECTION WITH VERTICAL SLOTS TO ALLOW DEFLECTION

8.1
VARIES

1/4

2-12 TOP OF SLAB [SEE PLAN]

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

1/4"x1'-2" CONT PLATE

EA END, TYP L2 1/2x2 1/2x1/4 AT EACH STIFFENER, 48" OC MAX WALL STUDS BELOW OMITTED FOR CLARITY 3 SIDES, TYP WALL STUDS BELOW OMITTED FOR CLARITY L3x3x1/4 AT EA STIFFENER 1/4" FULL DEPTH STIFFENER AT EACH SUPPORTED BEAM AND AT 48" OC MAX STEEL BEAM, SEE PLAN, WITH FULL DEPTH BOLTED CONNECTION, SLIP CRITICAL AT EXTERIOR END 3/16 3/16 2-12 2-12 11" 3 1/2" WELDED TRIANGULAR ANGLE FRAME CONSTRUCTED WITH L2-1/2x2-1/2x1/4 SHAPES

SEE PLAN L3x3x1/4 AT EACH STIFFENER

STEEL BEAM, SEE PLAN 3 SIDES, TYP

1/4" FULL DEPTH STIFFENER AT EACH SUPPORTED BEAM AND AT 48" OC MAX

C1

SECTION
3/4" = 1'-0"

C2

SECTION
3/4" = 1'-0"

C4

SECTION
3/4" = 1'-0"

VARIES

CURTAIN WALL CONNECTION BY SUPPLIER

[SEE PLAN]

2 - 3/4" DIA BOLTS TOP AND BOTTOM

L2 1/2x2 1/2x1/4 x 12" LONG AT EACH CORNER AND AT 3'-0" OC MAX WITH (2) 1/2" x 4" HEADED STUDS 3/16 #3 HAIRPIN BAR @ 48" OC 16" MAX 8" RECESS SLAB 1/4" AT EA ANCHORAGE #4 BAR, CONT, EXTEND 2'-0" PAST EA CORNER 2'-6" 3/4"

L3 1/2x2 1/2x1/4 (LLV) 12" LONG WITH (2) 1 1/2" VERTICAL SLOTS FOR ANCHORS, 2" FROM EACH END 5/8" x 4" HEAVY SCREW ANCHOR AT TOP OF VERTICAL SLOT, BACK OFF 1/4 TURN AFTER INSTALLATION

1" 3/16 3/16 BOTTOM OF SHELF L4x4x1/4 [SEE ARCH] TOS HSS COL, SEE PLAN [SEE PLAN] 1/4 AT BF-12, STOP CHANNEL SHORT OF GUSSET PLATE OF BRACED FRAME BEAM, SEE PLAN L3x3x3/8 AT 2'-6" OC 1/4" FULL-DEPTH STIFFENER 3" NOTE: FOR ELEMENTS NOT NOTED, SEE A1/SF301. 1/4 1/4 1/4 1/4 3 3 STAIR 1-12 3-8 8" 1/4 C4x7.2 L6x6x3/8 CONT

1"

1/2" JOINT, FILL WITH FIRE CAULK 1/4 2-12 EA END, TYP CMU WALL, SEE PLAN 1/4" CONT PLATE

STEEL BEAM, SEE PLAN

L3x3x1/4 AT EA STIFFENER SEE PLAN 1/4" STIFFENER ON EA SIDE OF BEAM WEB @ 36" OC MAX

2 2

EA END

MOMENT RESISTING CONNECTION, SEE "TYPICAL MOMENT CONNECTIONS" DETAIL ON SHEET SF501

B1

ELEVATOR SHAFT SECTION


1" = 1'-0"

B2

TYPICAL BEAM END CONNECTION - TORSION CLIP


NOT TO SCALE

VARIES 2'-0" MAX

B6

SECTION
3/4" = 1'-0"

(3) 1/2" HEAVY SCREW ANCHOR WITH 3" EMBEDMENT TOC

7/2/2012 9:17:36 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

G
1/4 L3x3x1/4 1/4" x 4' GUSSET PLATE 5'-8" A2 SF302 5'-8" TOC [SEE PLAN] 2-8 1 1 6" 4

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

[SEE PLAN] L6x4x5/16 LLV (2) 3/4" BOLTS, FINGER TIGHT, IN LONG VERT SLOTS WITH DOUBLE NUT TO PREVENT BACKING TOS [SEE PLAN]

TOS [SEE PLAN] L6x4x5/16, PART OF SHOP WELDED ANGLE FRAME 3/16 3/16 2 2

FRAMING SECTIONS AND DETAILS


GRAPHIC SCALE(S)
0 1" = 1' - 0" 0 1/8" = 1' - 0" 5' 10' 15' 30' 6" 1' 2' 3'

A1

ELEVATION - VESTIBULE BRACING TO BUILDING


1/4" = 1'-0"

A2

ELEVATION DETAIL
3/4" = 1'-0"

SF302
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

CHANNEL AND HSS LOCATED AT LENGTH OF BEAM ALONG STAIR

PENN STATE NEW RESIDENCE HALL

16" BOND BEAM

Architecture & Engineering


1" GAP SLAB ON DECK, SEE PLAN 1" GAP FILL GAP WITH COMPRESSIBLE MATERIAL TOC [SEE PLAN] TYP EA END 3/16 SLAB ON DECK, SEE PLAN FILL GAP WITH COMPRESSIBLE MATERIAL TOC [SEE PLAN] WALL END REINF. OFFSET FROM CL FOR RIGID ANCHOR (3)#5 MIN L3x3x1/4 @ 2'-0" OC WITH 1/2" CARBON STEEL SCREW ANCHOR WITH 4 1/4" EMBED CENTERED ON LOWER DECK FLUTE AT EA SIDE OF CMU WALL L6x3x1/4 (LLV) CONT BETWEEN L3x3 ANGLES. FIT L6x3 ANGLES SNUG TIGHT ON EA SIDE OF WALL 6" MIN LAP FACTORY PREFAB JOINT REINFORCING TEE UNIT RAKE JOINT AND FILL W/ FLEXIBLE SEALANT, EA FACE RIGID STEEL ANCHOR, GROUT ALL CELLS SOLID WALL END REINF CORNER BAR SHARED, MIN (3)#5, PLACE AS SHOWN 6" MIN LAP LADDER-TYPE JOINT REINF, TYP VERTICAL WALL REINFORCING FACTORY PREFAB JOINT REINFORCING CORNERS REINFORCING CONT THROUGH CJ RAKE JOINT AND SEAL, EA FACE

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

E
BOND BEAM, SEE CMU WALL SCHEDULE ON SF601 CMU WALL SEE PLAN L6x3x1/4 (LLV) CONT WITH 1/2" CARBON STEEL SCREW ANCHOR WITH 4 1/4" EMBED @ 2'-0" OC CENTERED ON LOWER DECK FLUTE AT EA SIDE OF CMU WALL. FIT ANGLES SNUG TIGHT TO WALL.

BUILD CMU WITH 1" CLEAR GAP AROUND STEEL ANGLE BOND BEAM, SEE CMU WALL SCHEDULE ON SF601 CMU WALL SEE PLAN

INTERLOCK MASONRY UNITS AT CORNER

AT BOND BEAM CORNER

INTERSECTION

GROUT TWO CELLS SOLID, EA SIDE OF OPENINGS EXCEEDING 1'-4" WIDE

INTERRUPT JOINT REINF AT CJ JOINT STABILIZING ANCHOR AT 16" OC RAKE JOINT AND SEAL, EA FACE

SEAL JOINT, EA FACE

TYP. INT. NON-BEARING CMU WALL BRACING (WALL PERPENDICULAR TO DECK)


NOT TO SCALE

TYP. INT. NON-BEARING CMU WALL BRACING (WALL PARALLEL TO DECK)


NOT TO SCALE REINF EA SIDE OF OPENING, MATCH VERT REINF STEEL BEAM, SEE PLAN ROOF TOS CL BEAM [SEE PLAN]

WALL END REINF MIN (1)#5 VERT

RUBBER CONTROL JOINT

WALL OPENING

CL COLUMN L4x4x1/4" KICKER @ 4'-0" OC SEE PLAN 1" GAP SEE PLAN SLAB ON DECK, SEE PLAN TOP OF SLAB [SEE PLAN] TYPICAL SHEAR CONNECTION AT BEAM ENDS 3/16 TYP EA END STEEL COL, SEE PLAN 4'-0"

3'-0"

CJ AT WALL INTERSECTION WHERE INDICATED

CONTROL JOINT

TYPICAL CONCRETE MASONRY WALL DETAILS


NOT TO SCALE MAKE BOND BEAM CONT THROUGH JOINT EXTEND LINTEL REINF 1'-4" MIN PAST OPENING. PROVIDE STD HOOK IF 1'-4" IS UNAVAILABLE CONTINUE WALL REINF ABOVE OPENING REINF EACH SIDE OF JOINT (#5 MIN) CONTINUE WALL REINF ABOVE OPENING C L CONTROL JOINT, SPACE 24'-0" FROM WALL ENDS, AND ON CENTER, MAXIMUM BOND BEAM AT TOP OF WALL 1/4" x 1 1/2" RIGID STEEL ANCHOR AT 4'-0" OC EXTENDING INTO INTERSECTING WALL, GROUT CELLS AT ENDS 2" 24" 2"

2"

WORKING POINT 1/2" ERECTION BOLT EA END 3/16 3/16 2L3x3x1/4 BRACE 3 3 EA END, TYP

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

BOND BEAM, SEE CMU WALL SCHEDULE ON SF601 1/4" PLATE, TYP. 3/8" CONT BENT PL CMU WALL SEE PLAN STEEL BEAM, SEE PLAN, TYP. 3/4" BOLT IN LONG LONGITUDINALLY SLOTTED HOLES IN BENT PL AT 2'-0" OC, SHOP ATTACHED. INSTALL BOLT IN MIDDLE OF SLOT 9" MAX 5/8" CARBON STEEL SCREW ANCHOR WITH 5" EMBED AT 24" OC IN LONG VERTICALLY SLOTTED HOLES IN BENT PLATE. BACK OFF SCREW 1/4" TO ALLOW SLIP

6"

WORKING POINT NEUTRAL AXIS OF BRACE

3/8" GUSSET PLATE, TYP 3/16 3/16 10 MIN TYP 10 MIN NOTE: DO NOT WELD BRACE TO GUSSETS UNTIL ROOF TRUSSES AND DECK HAVE BEEN PLACED.

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

TYP EXT NON-BEARING CMU WALL BRACING


NOT TO SCALE

TYPICAL STEEL FRAMED KNEE BRACE


NOT TO SCALE EOS VARIES 1/4" STEEL BENT PLATE MALLEABLE IRON WEDGE INSERT, EMBED IN SLAB AT 32" OC MAX. TACK TO BENT PLATE 3/4" DIA ASKEW HEAD BOLT, GALV AT EA WEDGE INSERT 1/4 #4 BAR, CONTINUOUS INTERSECTING WALL HORIZ JOINT REINF AT EACH COURSE IN PIER. VERT WALL REINF, SEE PLAN AND SCHED FOR SIZE AND SPACING REINF EACH SIDE OF OPENING (#5 MIN), #6 FIRST FLOOR #3 x 3'-0" WITH 135 HOOK AT END, EACH ANCHOR GROUT CELLS AT VERT REINF, TYP HORIZ JOINT REINF AT 16" OC, TERMINATE AT CONTROL JOINTS REINFORCE INTERSECTING WALL, #5 MIN., #4 MIN. FOR 6" CMU LINTEL OVER OPENING, SEE SCHED FOR REINF

2-12

TOP OF SLAB [SEE PLAN]

EDGE OF SLAB

2"

BOTTOM OF SHELF

C
3"

[SEE ARCH] 1/2"

BOND BEAM REINF. WITH 1-#4 BAR EXTEND REINFORCING 0'-8" MIN BEYOND OPENING. REINF. W/2-#5 BARS AT COMMONS, EXTENDED 1'-4" BEYOND OPENING.

(2)#4X4'-0" MIDDEPTH OF SLAB

L7x4x3/8 SHELF ANGLE, GALV, CONT, WITH 3/16" GAP BETWEEN SEGMENTS. PROVIDE HORIZ SLOTS, 1 1/2" LONG, FOR BOLTS AT 32" OC AND AT ENDS, COORD WITH WEDGE INSERTS

STEEL DECK, SEE PLAN

7/ 1 6"

TYPICAL VENEER SHELF ANGLE


NOT TO SCALE 1'-6" LAP TYPICAL

ADDITIONAL VERTICAL WALL REINFORCING TOP REINFORCING, SEE LINTEL SCHEDULE BOTTOM OF LINTEL [SEE ARCH] W SEE LINTEL SCHEDULE FOR SIZE AND REINFORCING BOTTOM REINFORCING, SEE LINTEL SCHEDULE D

NOT TO SCALE

0" TYP 1'-6" LAP TYPICAL

ADDITIONAL CORNER BARS AS SHOWN, SAME SIZE AS CONT REINF

CONT BOND BEAM REINF

0" TYP

JAMB VERTICAL REINFORCING, OFFSET AND LAP 48 BAR DIAMETERS


1'- 6137/ 256"

NOTE: FOR ADDITIONAL INFORMATION SEE "NOT AT CONTROL JOINT"

NOTE: VENEER MASONRY AND ANGLE LINTELS NOT SHOWN FOR CLARITY

GROUT SOLID 24" DEEP x16" WIDE 2 ADDITIONAL BARS AS SHOWN, SAME SIZE AS CONT REINF 1'-4" BRG 1'-4" BRG

SECTION

BOND BEAM LINTEL SCHEDULE


CLEAR SPAN DEPTH 'D'
8" 8"

PLAN AT CORNER
EXTERIOR COLUMN LINES A AND K: WIND LOAD = 0.6 KIP SEISMIC LOAD = 0.15 KIP PER BRACING BAY, MIN 6 BAYS EA LINE CJP CJP

PLAN AT INTERSECTION NOT AT CONTROL JOINT AT CONTROL JOINT

WIDTH 'W'
8" 8"

REINFORCING
2-#4 BOTTOM 2-#6 BOTTOM

0' 3' - 5"

3' - 4" 5' - 4"

TYPICAL BOND BEAM REINFORCING


NOT TO SCALE

TYPICAL BOND BEAM LINTEL


NOT TO SCALE

DRAG TRUSS IS COMPRISED OF MULTIPLE BRACING BAYS, SEE PLAN FOR EXTENTS

CFS TRACK, TOP OF PANEL, FASTEN TO STEEL DECK DIAPHRAGM ABOVE.

33/ 6 4"

CFS CHANNEL BRACES, EA WAY AT EA PANEL WITH MIN FOUR #12 SCREWS, EA END. FASTEN TO EA INTERMEDIATE STUD. SIZE MEMBER AND FASTENING FOR LOAD.

BRICK VENEER CONTROL JOINT, SEE ARCH DWGS VENEER, SEE ARCH DWGS 2-12 2-12

ANGLE LINTEL SCHEDULE FOR BRICK VENEER


CLEAR SPAN 0' 5'-1" 5-0" 8'-0" ANGLE L4x4x5/16 L6x4x5/16 (LLV)

CANTILEVER BEAM TYPICAL SHEAR CONNECTION BACKSPAN BEAM, WHERE SHOWN

7/2/2012 9:17:42 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

COLD-FORMED STEEL TRUSS, SEE PLAN AND TRUSS DETAILS

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
No. Date Description

DOUBLED STUD AT EA END TYP EACH END

AT BEAM/GIRDER - TYPE 1
STEEL ANGLE 5" MIN 5" MIN CJP TYPICAL SHEAR CONNECTION CJP TOP OF OPENING [SEE ARCH] ANGLE LINTEL TOP OF OPENING [SEE ARCH] FOM 3/4" 6 1/2" STEEL ANGLE

3/16" STL PLATE, CONT

NOTES: 1. 2. 3. 4. PROVIDE 8" MINIMUM BEARING AT EACH END OF ANGLE. TOE OF ANGLE SHALL BE LOCATED 3/4" FROM FACE OF BRICK. FOR EXACT SIZE AND LOCATION OF WALL OPENINGS, COORDINATE WITH ARCHITECTURAL DRAWINGS. ANGLE LINTEL SCHEDULE APPLIES ONLY TO ANGLE LINTELS NOT OTHERWISE SHOWN ON THE STRUCTURAL DRAWINGS. ANGLE LINTELS IN EXTERIOR WALLS SHALL BE HOT-DIP GALVANIZED. AT BRICK VENEER CONTROL JOINT, FORM SLIP PLANE BY PLACING FLASHING ABOVE AND BELOW ANGLE. PROVIDE 1/4" GAP AT EACH END OF ANGLE FOR THERMAL EXPANSION.

CFS TRACK, BOTTOM OF PANEL, WITH FASTENERS SPACED NO MORE THAN 6" OC.

STEEL HOLD-DOWN ANCHOR AT EACH END OF EACH BRACE

TYPICAL FRAMING DETAILS

1/4" MIN COVER PLATE TOP AND BOTTOM, SIZED BY FABRICATOR TO RESIST MOMENTS INDICATED ON PLAN STEEL BEAM, SEE PLAN

8" BRG CANTILEVER BEAM TYPICAL SHEAR CONNECTION BACKSPAN BEAM, WHERE SHOWN

CLEAR SPAN (BRICK VENEER OPENING)

8" BRG

CLEAR SPAN (BRICK VENEER OPENING)

ANGLE LINTEL

5. 6.

ELEVATION

ELEVATION AT BRICK VENEER CONTROL JOINT

SECTION

AT BEAM/GIRDER - TYPE 2

AT COLUMN

TYPICAL DRAG TRUSS TYPE A


NOT TO SCALE

TYPICAL MOMENT CONNECTIONS


NOT TO SCALE

TYPICAL BRICK ANGLE LINTEL


NOT TO SCALE

SF501
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

TYP REINFORCING AT RE-ENTRANT CORNERS, SLAB OPENINGS AND DEPRESSION CORNERS

STEEL BEAM, SEE PLAN

TYPICAL VERTICAL REINFORCING MOW (IF SPACING IS LESS THAN CLEAR SPAN)

PENN STATE NEW RESIDENCE HALL

GALV HORSESHOE SHIMS WHERE GAP EXCEEDS 1/16"

1/2" DIA A307 ERECTION BOLT AT EA END OF EA SLAB EDGE SEGMENT AT 48" MAX IN TRANSVERSE SLOTS

REINFORCED CMU WALL


NOT TO SCALE MASONRY CONTROL JOINT

4
4"x4" - 68 MIL CONTINUOUS BENT RIDGE PLATE BETWEEN TRUSSES, ALTERNATE WITH OPEN SPACE TO ALLOW VENTILATION. CONNECT TO EACH TRUSS WITH (4) #12 SCREWS.

BEARING WALL

30'-0" MAX OC TYPE 3 BRACING

LIGHT GAGE STEEL TRUSSES AT 48" OC MAXIMUM

STEEL ROOF DECK

COLD-FORMED STEEL BRACING IN VERTICAL PLANE CENTERED ON BRACED STEEL FRAME BELOW

COLD-FORMED STEEL BLOCKING BETWEEN TRUSSES

Architecture & Engineering

1 3 1 2 10'-0" MAX AT BOTTOM CHORD PANEL POINTS 2

CONTINUOUS 362S162-43 STEEL STUD BRACING FOR LIGHT GAGE STEEL TRUSS BOTTOM CHORD (SPACE 10'-0" OC MAX AT BOTTOM CHORD PANEL POINTS) "VERT" 362S162-43 STEEL STUD CROSS BRACING OF WEB MEMBERS AT EACH ROW OF BOTTOM CHORD BRACING. LOCATE AT ENDS OF THE BOTTOM CHORD BRACING AND REPEAT AT 20'-0" OC (MAX) INTERVALS. 362S162-43 STEEL STUD BOTTOM CHORD DIAGONAL BRACING. LOCATE AT END OF BUILDING AND REPEAT AT 30'-0" OC (MAX) INTERVALS. PROVIDE 362S162-43 STEEL STUD CROSS BRACING AT 20'-0" OC AT PERMANENT CONTINUOUS LATERAL BRACING AS SPECIFIED BY THE TRUSS ENGINEER. COLD-FORMED STEEL ROOF TRUSS

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM

E
3

TYPICAL SLOPED ROOF PEAK


NOT TO SCALE ROOF TRUSS, TYP STEEL BEAM, SEE PLAN TRUSS VERTICAL MEMBER

1 3 2

LAP ALL LATERAL BOTTOM CHORD BRACES OVER A MINIMUM OF 2 TRUSSES. ALL CONNECTIONS SHOULD BE MADE WITH (3) SELF DRILLING SCREWS FOR DIAGONAL BRACING, AND (2) SELF DRILLING SCREWS FOR LATERAL BRACING.

TRUSS BOTTOM CHORD

CONNECTION FROM BOTTOM TRUSS CHORD TO STEEL BEAM BY TRUSS MANUFACTURER

COLD-FORMED STEEL BLOCKING BETWEEN ROOF TRUSSES

BEARING WALL

20'-0" MAX OC TYPE 2 BRACING

NOTE: TRUSS MANUFACTURER SHALL DESIGN TRUSS-TO-BEARING CONNECTIONS FOR UPLIFT AS WELL AS 500 LBS MIN SHEAR AT EACH TRUSS-TO-BEARING CONNECTION ALONG EXTERIOR SUPPORTS

TRUSS BEARING ELEVATION STEEL BEAM

ROOF LEVEL [SEE PLAN]

NOTE: TRUSS MANUFACTURER SHALL DESIGN COMPLETE BRACING SYSTEM AND PROVIDE PLANS AND DETAILS OF BRACING AS PART OF SHOP DRAWING SUBMITTAL. STEEL COLUMN STEEL BEAM

MINIMUM LIGHT GAGE STEEL TRUSS BRACING DIAGRAM (PLAN VIEW)


NOT TO SCALE STEEL ROOF DECK, SEE PLAN

TYPICAL TRUSS-TO-BEARING AT STRUCTURAL STEEL


NOT TO SCALE

CONNECT COLD-FORMED STEEL DRAG TRUSS TO STEEL BEAM WITH 15 K SHEAR CAPACITY IN PLANE OF BRACED FRAME OVER LENGTH OF BRACED FRAME

STEEL COLUMN

TYPICAL DRAG TRUSS TYPE B


NOT TO SCALE CL SLEEVE 12"
2'- 0"

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

12"
2'- 0"

STEEL ROOF DECK, SEE PLAN CENTER LINE OF SUPPORT REINFORCING PLATE, WELD OR SCREW TO ADJACENT RIBS AROUND OPENING FFE
1 1/ 2"

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

36/7 PATTERN

SIDE LAP FASTENERS

DECK PENETRATION, SEE MECH AND PLUMBING FOR SIZE AND LOCATIONS

36/5 PATTERN FASTENER, TYP ROOF DECK OR COMPOSITE FLOOR DECK FASTENERS AROUND PERIMETER OF BUILDING PENETRATE SLAB AT THIN SECTIONS ONLY

36/4 PATTERN

36/3 PATTERN

CENTER LINE OF SUPPORT

(4) #3 x 48" LONG PLACED AT 45 DEG TO DECK DIRECTION 1-#5 IN EACH ADJACENT DECK RIB WHERE SLEEVE PENETRATION OCCURS - EXTEND MIN 30" EA END, OR 4" PAST METAL DECK SUPPORT BEAMS

36" COVER WIDTH OPENING SIZE UP TO 6" DIA 6" TO 14" 36" WIDE SHEETS TYP NOTE: SEE GENERAL STEEL DECK NOTES FOR STEEL DECK SIZE, GAGE, FASTENER SIZE, TYPE, AND PATTERN, AND SIDE LAP CONNECTIONS OVER 14" REINFORCING NOT REQUIRED 16 GA. PLATE NOTES NOT REQUIRED SEE DETAIL ABOVE NOTE:

SEE TYPICAL SLAB OPENING DETAIL, THIS SHEET

PENETRATIONS THROUGH SLAB IN THE OTHER DIRECTION (ALL WITHIN METAL DECK RIB) SHALL BE SPACED AT 3x PIPE (OR SLEEVE) DIAMETER ON CENTER, MINIMUM, EXCEPT AS PROVIDED IN "TYPICAL SLAB PENETRATION - MULTIPLE OPENINGS" DETAIL, THIS SHEET. PROVIDE STRUCTURAL SUPPORT FOR METAL DECK WHERE REQUIRED DUE TO CONDUIT OR SLEEVE PENETRATIONS.

ROOF DECK FASTENING PATTERNS


NOT TO SCALE

TYPICAL ROOF DECK ATTACHMENT


NOT TO SCALE

TYPICAL DECK REINFORCEMENT


NOT TO SCALE

TYPICAL SLAB PENETRATION


NOT TO SCALE

CL BEAM 30" MIN SPACING SEE FRAMING PLAN SHEAR STUDS IN STRONG POSITION SHEAR STUDS IN STRONG POSITION

#3x3'-0", EA SIDE OF OPENINGS, BOTTOM

1.5x DIA MIN

TYP

3/16 3/16

STEEL ROOF DECK, SEE PLAN

OPENING

CONT POUR STOP AT SLAB STEEL FLOOR DECK AND SLAB, SEE PLAN

ONE #5 BAR, EA SIDE OF OPENINGS, IN ADJACENT DECK RIB

REINFORCE DECK AROUND OPENINGS WITH 16 GA PLATE OPENING BLOCK OUT SLAB PENETRATIONS, DO NOT CORE SLAB. 8" DIA MAX. L4x4x1/4 FRAME AROUND OPENINGS, TYP NOTES: 1. WHERE DECK SPANS PERPENDICULAR TO BEAM, STUDS SHALL BE PLACED WITH ONE STUD IN ALTERNATE DECK FLUTES, STARTING AT ENDS. REMAINING REQUIRED STUDS SHALL BE PLACED, STARTING FROM ENDS, UNTIL TOTAL IS REACHED. USE SINGLE LINE OF STUDS, CENTERED OVER BEAM WEB, UNLESS MULTIPLE ROWS ARE NEEDED. STUD SPACING AT GIRDERS SHALL BE NO MORE THAN 24", NO LESS THAN 4 1/2", DISTRIBUTED EVENLY. WHERE MULTIPLE ROWS ARE NEEDED ON GIRDERS, STUDS SHALL BE STAGGERED 3" MIN. AXIS OF GROUP TO ALIGN WITH DIRECTION OF DECK RIBS

L5x5x5/16x0'-5" LONG EACH END OF L4x4, TYP JOIST OR BEAM, TYP STRONG POSITION 3. 4. 2.

STRONG POSITION

NOTE: SEE "TYPICAL SLAB PENETRATION" DETAIL, THIS SHEET, FOR SECTION AND OTHER ELEMENTS.

PLAN

SECTION A-A

TYPICAL DECK SUPPORT AT ROOF/FLOOR OPENING


NOT TO SCALE CL COLUMN

COMPOSITE BEAM DIAGRAM


NOT TO SCALE 1/4" STIFFENER PLATE EACH SIDE BEAM, SEE PLAN TOS [SEE PLAN] 1 1/2" TYP CL COLUMN BEAM, SEE PLAN FOR SIZE TOS [SEE PLAN]

TYPICAL SLAB PENETRATION MULTIPLE OPENINGS


NOT TO SCALE

7/2/2012 9:17:46 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

TOTAL SLAB THICKNESS

TOPPING THICKNESS

HEADED STUD TYP, SEE GENERAL STEEL DECK NOTES WELDED WIRE FABRIC

CL GIRDER

#4x4'-0" AT 16" OC AT ALL GIRDERS SUPPORTING COMPOSITE BEAMS ON BOTH SIDES STEEL DECK

1/4 1/4

3 3

CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW REVISIONS
3/8" CAP PLATE AT TOP OF COLUMN

No.

Date

3/4" CLR AT REBAR

DECK HEIGHT

4"

MILL FINISHED FACE 3/4" CAP PLATE WITH (4) 3/4" ASTM A325 BOLTS 1/4" STIFFENER PLATE EACH SIDE

PJP

4"

BEAM, SEE PLAN

AISC STANDARD SINGLE-PLATE SHEAR CONNECTION, TYP (BOTH SIDES IF APPLICABLE) NOTE: STEEL DECK OMITTED FOR CLARITY

AISC STANDARD SHEAR CONNECTION GIRDER, SEE PLAN FOR SIZE MILL FINISHED FACE

TYPICAL FRAMING DETAILS

4"

BEAM TYP, SEE PLAN

AISC DOUBLE ANGLE CONNECTION TYP, REFER TO GENERAL STEEL NOTES

HSS COLUMN, SEE PLAN HSS COLUMN, SEE PLAN

TYPICAL COMPOSITE BEAM-TO-GIRDER CONNECTION AND SLAB REINFORCING


NOT TO SCALE

TYPICAL BEAM-TO-COLUMN CAP CONNECTION


NOT TO SCALE

TYPICAL BEAM-TO-COLUMN SHEAR CONNECTION


NOT TO SCALE

TYPICAL BEAM-TO-GIRDER CONNECTION


NOT TO SCALE

TYPICAL COLUMN SPLICE


NOT TO SCALE

SF502
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802


Description

#3x48" AT 45 DEG ANGLE TO DECK ORIENTATION, EA CORNER

PENN STATE NEW RESIDENCE HALL

Architecture & Engineering


ROOF
8 R O F 11 0 " 8 ' 8 R O F 11 0 " 8 '

1523 ELIZABETH AVENUE SUITE 300 CHARLOTTE, NC 28204


7043778800 FAX 7043581037 WWW.CLARKNEXSEN.COM HSS5X5X3/16 HSS6X6X5/16 HSS6X6X5/16 HSS6X6X3/16 HSS6X6X3/16 HSS5X5X5/16 HSS8X6X5/16 HSS6X6X3/16 HSS5X5X5/16 HSS6X6X1/4 HSS5X5X3/8 HSS6X6X1/4 HSS8X6X1/4 HSS6X6X1/4 HSS5X5X3/8
11 2 " 6 1 / 7 '

HSS6X6X5/16

HSS6X6X3/8

FOURTH FLOOR
O F 7U H R T

O F 7U H R T

11 2 " 6 1 / 7 '

THIRD FLOOR
R H D T I 6 11 2 " 6 1 / 5 '

HSS6X6X1/4

R H D T I 6

11 2 " 6 1 / 5 '

NORTH HIGH CANOPY


G I H 5G I H Y P O N A CH 11 6 " 5 1 '

G I H 5G I H Y P O N A CH

11 6 " 5 1 '

NORTH LOW CANOPY


G I H 5O N A C HO L Y PW 11 1 " 4 6 '

G I H 5O N A C HO L Y PW

11 1 " 4 6 '

SECOND FLOOR
C E O S 4N D 11 2 " 6 1 / 4 3 '

C E O S 4N D

11 2 " 6 1 / 4 3 '

HSS6X6X5/16

HSS6X6X1/2

HSS8X6X5/8

HSS8X6X1/2

HSS6X6X5/8

HSS6X6X3/8

HSS6X6X3/8

HSS5X5X1/4

HSS5X5X3/8

HSS6X6X3/8

HSS5X5X1/2

HSS5X5X3/8

SOUTH HIGH CANOPY


O L 3W O N A CG I H Y PH 11 2 " 6 1 / 4 '

O L 3W O N A CG I H Y PH

HSS4X4X3/16

HSS4X4X3/16

HSS6X6X5/16

HSS5X5X1/2

HSS6X6X5/8

11 2 " 6 1 / 4 '

SOUTH LOW CANOPY


L O 3 -W C A N O P L Y -W 11 2 " 6 1 / 3 '

HSS6X6X5/16

HSS6X6X3/8

W10X33

HSS6X6X1/2

W10X33

L O 3 -W C A N O P L Y -W

11 2 " 6 1 / 3 '

FIRST FLOOR
T S R I F 2 11 2 " 6 1 / 3 '

T S R I F 2

11 2 " 6 1 / 3 '

W10X33

HSS4X4X3/16

HSS4X4X3/16

HSS4X4X3/16

W10X33

GROUND FLOOR
G 1R U O N D 11 0 " 2 '

HSS4X4X3/16

G 1R U O N D

300 West Pratt Street, Suite 310 Baltimore, MD 21201 Phone: 443.757.1000 Fax: 443.757.1011 www.bartonmalow.com

W10X33

11 0 " 2 '

BASE PLATE MARK Column Locations

BP-2

BP-2, TYP BP-8 AT C-4 A-6, A-8, A-10, C-4

BP-2

BP-5

BP-1

BP-1

BP-4

BP-4

BP-5, TYP, BP7 AT H-2 AND H-3.9

BP-7

BP-3

BP-2, TYP, BP-5 AT C-12 AND K-1

BP-6

BP-2

BP-2

BP-2 AT E-11 BP-8 AT H.5-1

BP-1

BP-2

BP-2

BP-2

BP-5

BP-1

BP-1

BP-4

BP-4

BP-8

BP-4

BP-1

BP-1

A-4

A-11

A-12

A.1-3, D.9-3

A.1-3.9, D.9-3.9

B-3, D-3

B-3.9, D-3.9

C-6, C-8, H-2, H-3.9, H-6

C-10

C-11, H-1, K-2, K-3.9, K-6

C-12, E-7, F-7, K-1, K-8

E-4

E-5

E-8, E-10

E-11, H.5-1

E-12

F-1, F-2

F-3.9

F-5

F-8

F.1-8.1

F.1-9

G-8.1

G-9, J-9

H-8

J-8.1

J.9-8.1

J.9-9

NOTES: 1. COLUMN SPLICES OCCUR AT LOCATIONS WHERE UPPER COLUMN SIZE AND LOWER COLUMN SIZE ARE INDICATED. SPLICE SHALL BE MADE AT AN ELEVATION OF 48" ABOVE TOP OF SECOND FLOOR SLAB. SEE "TYPICAL COLUMN SPLICE" DETAIL ON SF502. 2. SEE ANCHOR ROD AND BASE PLATE SCHEDULE ON SB501 FOR BASE PLATE TYPE.

600 Science Park Road State College, PA 16803 Phone: 814.237.6518 Fax: 814.237.1488 www.sweetland-eng.com

GRAPHICAL COLUMN SCHEDULE


NOT TO SCALE

ANCHOR ROD AND BASE PLATE SCHEDULE


BASE PLATE MARK WIDTH 'B'
11 12 12 16 14 14 14 14

CMU WALL REINFORCING SCHEDULE


BASE PLATE TYPE
TYPE I TYPE I TYPE I TYPE I TYPE III TYPE III TYPE I TYPE II NOTES: 1. SEE TYP. DETAILS ON SHEET SF501 FOR REINFORCING AT WALL ENDS, WALL OPENINGS, CONTROL JOINTS, INTERSECTIONS. AND 2. 3. AT ELEVATOR SHAFTS, CONTINUOUS REINFORCED BOND BEAMS SHALL BE LOCATED AT FLOOR LEVELS AND AT ANCHORAGE LOCATIONS FOR ELEVATOR RAIL SUPPORTS. COORDINATE WITH ELEVATOR DRAWINGS. BOND BEAM SHALL BE LOCATED AT TOP OF WALL. MW4 8" #5 AT 8" OC (2) W1.7 16" SEE NOTES 3 (2) #5 MW2 MW3 8" 6" #5 AT 48" OC #5 AT 48" OC (2) W1.7 (2) W1.7 8" 8" SEE NOTES 3 SEE NOTES 3 (2) #5 (1) #5

ANCHOR RODS ROD DIAMETER


3/4 3/4 1 1 1 1 1 1

LENGTH 'N'
11 12 12 16 14 14 14 26

THICKNESS 't'
3/4 3/4 1 1-1/4 1 1-1/4 1-1/2 2

EMBEDMENT 'L'
9 9 12 12 16 24 24 16

PROJECTION 'P'
6" 6" 6" 7" 6" 8" 8" 8"

MARK
MW1

CMU NOMINAL VERTICAL REINFORCING THICKNESS AND GROUT SPACING


8" #5 AT 8" OC

HORIZONTAL JOINT REINFORCING


(2) W1.7

BOND BEAM DEPTH


16'

BOND BEAM SPACING


SEE NOTES 2&3

BOND BEAM REINFORCING


(2) #5

BP1

BP2 BP3 BP4 BP5 BP6 BP7 BP8

PENN STATE NEW RESIDENCE HALL


REVISIONS
No. Date

CONCRETE WALL REINFORCING SCHEDULE


CL COL, BASE PLATE, AND FOOTING, UON 1 1/2" NUT AND WASHER 1 1/2" EQ EQ CL COL AND BASE PL EQ EQ B/2 CL COLUMN AND BASE PLATE 1 1/2"

MARK
CW1 CW2 CW3 CW4

CONCRETE WALL THICKNESS


8" 16" 8" 12"

VERTICAL REINFORCING
#5 AT 14" OC, MOW #6 AT 9" OC, EF #5 AT 10" OC, EF #5 AT 10" OC, EF

HORIZONTAL REINFORCING
#5 AT 14" OC, MOW #6 AT 18" OC, EF #5 AT 10" OC, EF #5 AT 10" OC, EF

END REINFORCING
(6) #5, 1/2 EACH FACE WITH #3 TIES AT 8" OC N/A (4) #5, 1/2 EACH FACE WITH #3 TIES AT 8" OC (4) #5, 1/2 EACH FACE WITH #3 TIES AT 8" OC

A
BASE PLATE, SEE SCHEDULE 'P'

1 1/2"

2" NON-SHRINK NON-METALLIC GROUT TOP OF FOOTING OR PIER [SEE PLAN]

N/2 LEVELING NUT AND WASHER, TYP

N/2

1/4

ANCHOR ROD WITH HEAVY HEX NUT, TYP. SEE SCHEDULE.

PLAN A-A

VERT REINF, TYP HORIZ REINF, TYP

TYPE I BASE PLATE

TIE REINF, TYP EA END END VERT REINF, TYP EA END

CL COL

A
GUSSET PLATE, CENTER ON COLUMN

A
CN NO: 4046 DATE: 06/29/2012 DESIGN: BSP DRAWN: BJT REVIEW: ECW
Description

HSS COLUMN CL BRACE ERECTION BOLT

BASE PLATE, SEE SCHEDULE CL COL FS NS

CL COLUMN AND BASE PLATE 2" GUSSET PL 4" 2" EQ EQ CL COL AND BASE PL EQ EQ B/2 2"

A
WALL END

7/2/2012 9:17:48 AM C:\Revit Projects\4046_PENN STATE PHASE 3 S12_bplatt.rvt

WORKING POINT NUT WITH 2x2x1/2 PLATE WASHER, TYP TOF/TOP OF PIER [SEE PLAN] STEEL SHEAR LUG, 2" THICK x 14" LONG IN GROUTED POCKET 3 1/2" L 2" N P B

5"

2"

B/2

TIE REINF HORIZ WALL REINF VERT WALL REINF

TIE REINF HORIZ WALL REINF VERT WALL REINF

5"

5"

5"

5"

2"

CJP

5/16

N/2

N/2

END VERT REINF

END VERT REINF

ANCHOR ROD WITH HEAVY HEX NUT, TYP. SEE SCHEDULE. TACK TYP

SECTION A-A
NOTE: PROVIDE 2x2x1/2 PLATE WASHERS WITH STANDARD HOLE AT EACH ANCHOR ROD

TYPE II BASE PLATE

TYPE III BASE PLATE

S/2 S/2

S/2 S/2

SECTION A-A, (1 LAYER OF REINF, MOW)

SECTION A-A, (2 LAYER OF REINF)

TYPICAL REINFORCING AT CONCRETE WALL


NOT TO SCALE

SF601
SHEET OF

THE PENNSYLVANIA STATE UNIVERSITY UNIVERSITY PARK, PA 16802

'L'

B/2

SCHEDULES