For Phase Busbar For Phase Busbar For Neutral Busbar Go back to Rules
Aluminium 130 Amp / Sq.cm or 800Amp / Sq.inch. Copper 160 Amp / Sq.cm or 1000Amp / Sq.inch Same as Phase Busbar up to 200 Amp than Size of Neutral Busbar is at least half of Phase Busbar.
5. Busbar Spacing
Between Phase and Earth Between Phase and Phase Busbar Support between Two Insulator Go back to Rules Advertisement 26mm (Min) 32mm (Min) 250mm.
7. IR Value of Transformer
Voltage >66KV 22KV to 33KV 6.6KV to 11KV <6.6KV 415V Go back to Rules IR Value of Transformer 30C 40C 600M 300M 500M 250M 400M 200M 200M 100M 100M 50M 50C 150M 125M 100M 50M 20M
MCB, MCCB, ELCB, RCCB, SFU, Fuse Standard Ratings Up to 63 Amp (80Amp and 100 Amp a per Request) Up to 1600 Amp (2000 Amp as per Request) Above 1000 Amp 6A,10A,16A,20A,32A,40A,50A,63A 0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A MCCB Rating (Domestic Max 6A) 6A,10A,16A,20A,32A,40A,50A,63A,80A,100A RCCB/ELCB 30ma (Domestic),100ma (Industrial),300ma Sen. of ELCB 5A,15A,30 A for 250V DPIC (Double Pole Iron Clad) main switch TPIC (Triple Pole Iron Clad) 30A, 60A, 100A, 200 A For 500 V main switch 5A, 10A, 16A, 32A and 63 A for 250V DPMCB 100A,200A, 300Aand 500 A For 660 V TPMCCB 30A, 60A, 100A, 200A, 300 A For 500 V TPN main switch 16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A, TPNMCB 200A, 300A, 500 A For 660 V TPN Fuse Unit (Rewirable) 16A,32A,63A,100A,200A 32A,63A,100A,200A,300A,400A,630A,800A Change over switch (Off Load) 32A,63A,100A,125A,160A,200A,250A,315A,400A,630A SFU (Switch Fuse Unit) 125A,160A,200A,250A,400A.630A HRC Fuse TPN (Bakelite) 16A,32A,63A HRC Fuse DPN (Bakelite) MCB/MCCB/ELCB Termination Wire / Cable Max. 25 Sq.mm Up to 20A MCB Max. 35 Sq.mm 20A to 63A MCB Max. 25 Sq.mm MCCB 16 Sq.mm 6A to 45A ELCB 35 Sq.mm 24A to 63A ELCB 50 Sq.mm 80A to 100A ELCB MCB MCCB ACB MCB Rating