DNP V3.0-M3311 Communication Data Base for M-3311 Integrated Protection System Device I.D.

= 112

Specifications presented herein are thought to be accurate at the time of publication but are subject to change without notice.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.
Rev Rev 1 1.1 Preliminary release 04/08/02 Setpoints224 to 234 are added in Analog output with status (object 40,var 02). Setpoints 243-248 are added in Analog Inputs (obj 30,Var 02). Setpoint 24 in Analog output with status (obj 40,var 02) is removed. added setpoint78 in analog inputs (object 30,var 02) W2 Zero seq. current. Added Setpoints928 to 1071 in Binary Output Status Points. Removed the setpoints205 206 207 in object 30,variation 02 Analog inputs. added new setpoints1099 to 1146 in binary output status. Made read only points 179 & 180 in object40, variation 02. Setpoints46 48 51 53 56 &58 in object 40, variation 02 are not used. Points 179 & 180 are not used in obj40, variation 02. Point 235 added. Points 250 & 251 are added in object 30, variation 02 Points 1094-1097 are not used in object 10, variation 02. Setpoints109-124 rearranged in object30, variation 02. Added new read functions for points 16 & 20 in object 40,variation 02. Range check added for the setpoints21 103 & 223 in object 41,var 02. Point 54 communication channel lock status in object 30 is not used. Point 210 unlock communication lock access code in object 40 is not used. Added new Setpoint 236 in object 40. Added new Setpoints 252-260 in object 30.

Rev

1.2

Rev Rev Rev

1.3 1.4 1.5

Rev Rev Rev

1.6 1.7 1.8

"SCALE FACTOR" is the factor by which an integer value read from the control is divided to get the value of the variable in the indicated "UNITS". Points marked with a (U) appended to the scale factor field should be taken as unsigned value (0-65535) before scaling. "UNITS" unit of the described data point. All points defined as NOT USED can be read and will return 0 for data. The communication database profile in the M3311 with the DNPV3.0 protocol is grouped into five object types. These are Single bit binary inputs (status) (object 01,variation 01,02): They are considered as class0 data. 16bit Analog Output Block /Status (object 40,variation 01,variation 02/object 41,variation 01,variation 2) With these points, you can read and write all the set points & system setup. Binary outputs &Control relay output block(Direct control) (object 10, variation 02/object 12, variation 2): With these points, you can write all the configuration points. 16bit Analog inputs (object 30, variation 01,02,03,04): These points represent all the demand metering, target information &control information of the relay. 16Bit Binary counters (object 20,variation 02,variation 06): These points represent all the counters. You can reset the counters using freeze & clear function code. Date & time (read and write time using object 50, variation 01): Represents the system time & date. Static (Class 0) data (Obejct60, variation01) These points represent all the binary inputs, control information, demand metering, target information and counters. DNP Configuration Parameters: M3311 relays support DNP through the Rear RS232 (COM2) & RS485 (COM3) communication ports. These port support baud rates 1200,2400,4800,9600 and the default baud rate is set to 9600. M3311 Slave address: DNP3 Slave IED Address range is from 0 to 65519.Address 65535(hex FFFF) is used to broadcast messages to all devices .The communication address can be set through the HMI (Front panel).

1 DNP V3.00 DEVICE PROFILE


DNP V3.0 DEVICE PROFILE DOCUMENT Vendor Name: Beckwith Electric Co Inc Device Name: Transformer(3 Winding) Protection system Highest DNP Level Supported: Device Function: For Requests: Level 2 Master For Responses: Level 2 Slave Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): The read function code for Object 50 (Time and Date), variation 1, is supported. Maximum Data Link Frame Size (octets): Transmitted: 292 Received 292 Maximum Data Link Re-tries: Maximum Application Fragment Size (octets): Transmitted: 1536 Received: 1536 Maximum Application Layer Re-tries: None Configurable

None Fixed at _2___ Configurable from 0 to 255 Requires Data Link Layer Confirmation: Never Always Sometimes Configurable as: Never, Only for multiframe messages Requires Application Layer Confirmation: Never Always When reporting Event Data When sending multi-fragment responses Sometimes Configurable Timeouts while waiting for: Data Link Confirm: Complete Appl. Fragment: Application Confirm: Complete Appl. Response: Others : None None None None

Fixed at 3S___ Fixed at ____ Fixed at _5S___ Fixed at ____

Variable Variable Variable Variable

Configurable Configurable Configurable, Configurable

DNP V3.0 DEVICE PROFILE DOCUMENT Sends/Executes Control Operations: WRITE Binary Outputs SELECT/OPERATE DIRECT OPERATE DIRECT OPERATE NO ACK Count > 1 Pulse On Pulse Off Latch On Latch Off Queue Clear Queue Never Never Never Never Never Never Never Never Never Never Never Always Always Always Always Always Always Always Always Always Always Always Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable

Reports Binary Input Change Events when no specific variation requested: Never Only time-tagged Only non-time-tagged Configurable Sends Unsolicited Responses: Never Configurable Only certain objects Sometimes (attach explanation) ENABLE/DISABLE UNSOLICITED Function codes supported Default Counter Object/Variation: Static Object 20 , Var 2 Running Change Object 22,Var 2 Frozen change Object 23 , Var 2

Reports time-tagged Binary Input Change Events when no specific variation requested: Never Binary Input Change With Time Binary Input Change With Relative Time Configurable (attach explanation) Sends Static Data in Unsolicited Responses: Never When Device Restarts When Status Flags Change No other options are permitted. Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits 32 Bits Other Value: _____ Point-by-point list attached

Sends Multi-Fragment Responses: Yes No

DNP V3.0 DEVICE PROFILE DOCUMENT Sequential File Transfer Support: Append File Mode Custom Status Code Strings Permissions Field File Events Assigned to Class File Events Poll Specifically File Events Send Immediately Multiple Blocks in a Fragment Max Number of Files Open Yes Yes Yes Yes Yes Yes Yes No No No No No No No

OBJECT Object Number 1 Variation Number 1


(default see note 1)

REQUEST Description Function Qualifier Codes Codes (dec) (hex) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 5 (direct op) 00, 01 (start-stop) 6 (dir. op, noack) 07, 08 (limited qty) (index) 17, 28 1 (read) 00, 01 (start-stop) 9 (freeze clear) 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index)

RESPONSE Function Qualifier Codes Codes (dec) (hex) 129 (response) 00, 01 (start-stop) 17, 28 (index
see note 2)

Binary Input

Binary Input with Status

129

(response)

00, 01 17, 28

(start-stop) (index see note 2)

10

2
(default see note 1)

Binary Output Status

129

(response)

00, 01 17, 28

(start-stop) (index see note 2)

12 20

1 2

Control Relay Output Block 16-Bit Binary Counter

129 129

(response)

echo of request

(response)

00, 01 17, 28

(start-stop) (index see note 2)

20 20

5 6
(default see note 1)

32-Bit Binary Counter without Flag 16-Bit Binary Counter without Flag 1 9 1
(read) (freeze clear)

30

32-Bit Analog Input

(read)

30

2
(default see note 1)

16-Bit Analog Input

(read)

00, 01 (start-stop) 129 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 00, 01 (start-stop) 129 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 00, 01 (start-stop) 129 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index)

(response)

00, 01 17, 28 00, 01 17, 28 00, 01 17, 28

(start-stop) (index see note 2) (start-stop) (index see note 2) (start-stop) (index see note 2)

(response)

(response)

30

32-Bit Analog Input without Flag

(read)

00, 01 (start-stop) 129 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index)

(response)

00, 01 17, 28

(start-stop) (index see note 2)

OBJECT Object Number 30 Variation Number 4 Description 16-Bit Analog Input without Flag

REQUEST Function Qualifier Codes Codes (dec) (hex) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index) 00, 01 (start-stop) 5 (direct op) 07, 08 (limited qty) 6 (dir. op, noack) 17, 28 (index) 5 (direct op) 00, 01 (start-stop) 6 (dir. op, noack) 07, 08 (limited qty) (index) 17, 28

RESPONSE Function Qualifier Codes Codes (dec) (hex) 129 (response) 00, 01 (start-stop) 17, 28 (index
see note 2)

40

32-Bit Analog Output Status

129

(response)

00, 01 17, 28 00, 01 17, 28

(start-stop) (index see note 2) (start-stop) (index see note 2)

40

2
(default see note 1)

16-Bit Analog Output Status

129

(response)

41 41

1 2

32-Bit Analog Output Block 16-Bit Analog Output Block

129 129

(response)

echo of request

(response)

echo of request

50

Time and Date

129

(response)

00, 01 17, 28 00, 01 17, 28

(start-stop) (index see note 2) (start-stop) (index see note 2)

50

1
(default see note 1)

Time and Date

(read)

(write)

52 60 60 60

2 0 1 2

Time Delay Fine Class 0, 1, 2, and 3 Data Class 0 Data Class 1 Data 1

00, 01 (start-stop) 129 06 (no range, or all) 07 (limited qty=1) 08 (limited qty) 17, 28 (index) 00, 01 (start-stop) 07 (limited qty=1) 08 (limited qty) 17, 28 (index) 129 06

(response)

(response)

07

(limited qty) (qty = 1)

(read)

(no range, or all)

60

Class 2 Data

60

Class 3 Data

70 70 70 70 70 70 80 80

1 3 4 5 6 7 0 1

File Identifier File Command File Command Status File Transfer File Transfer Status File Descriptor Internal Indications(Variation 0 is used to request default variation) Internal Indications
) ) )

(read)

00, 01 (start-stop) 129 06 (no range, or all) 07, 08 (limited qty) 17, 28 (index)

(response)

00, 01 17, 28

(start-stop) (index see note 2)

OBJECT Object Number Variation Number Description

REQUEST Function Qualifier Codes Codes (dec) (hex) (write) 00 (start-stop) 2 (see note 4) 01 (start-stop) 07, 08 (limited qty) 17, 28 (index)

RESPONSE Function Codes (dec) Qualifier Codes (hex)

112 113

string Virtual Terminal Output Block length string Virtual Terminal Event Data length No Object (function code only) See Note 3 No Object (function code only) No Object (function code only)

13 14 23

(cold restart) (warm restart) (delay meas.)

Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded except for object 70 which responds with qualifier 1b or 5b.) Note 3: For a Cold, restart is implemented as a warm restart the executable is not restarted, but the DNP process is restarted. Note 4: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7), and indices 16 and beyond (user-defined indications).

DNP V3.0 POINT LIST


Binary Input Points Static (Steady-State) Object Number: 1 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary input without status) Point index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Name/Description Input status bit 0 input 1(52b) Input status bit 1 Input status bit 2 Input status bit 3 Input status bit 4 Input status bit 5 Input status bit 6 NA Input status bit 7 NA Output status bit 0 out1 Output status bit 1 out2 Output status bit 2 out3 Output status bit 3 out4 Output status bit 4 out5 Output status bit 5 out6 Output status bit 6 out7 Output status bit 7 out8 Front panel LED status Object/Variation 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Static class 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

16 17 18 19

Time sync Breaker closed Osc triggered Target Input status active state Bit0 = 0 IN1 active closed Bit0 = 1 IN1 active open Bit1-bit5 same as above for IN2-IN6 . Bit6-Bit15 not used (0)

1/2 1/2 1/2 1/2

0 0 0 0

20

IRIG-B time sync status 0 Invalid 1-Valid

1/2

Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks Object Number: 12 Request Function Code supported: 5(Direct operate)

Point index

Name/Description 24DT #1Volts per hertz outputs At least one OUT must be Selected to enable function. Bit 0 Out 1 Bit 1 Out 2 Bit 2 Out 3 Bit 3 Out 4 Bit 4 Out 5 Bit 5 Out 6 Bit 6 Out 7 Bit 7 Out 8

Obj/Var (Read)

Obj/Var (Write)

0 1 2 3 4 5 6

Out1 Out2 Out3 Out4 Out5 Out6 Out7

10/2 10/2 10/2 10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1 12/1 12/1 12/1

7 8 9 10 11 12 13 14 15 16-31 30 32-47 46 48-63 62 64-79 78 80-95 96-111 110 112-127 126 128-143 142 144-159 158 160-175 174 176-191 190 192-207 206 208-223 222 224-239 238 240-255 254 256-271 270 272-287 286

Out8 24DT #1Volts per hertz Block Writing 0 disables function In1 In2 In3 In4 In5 In6 Not used Function enable 24DT # 2 volts per hertz (See 0-15) Not used 24IT Volts per hertz(See 0-15) Not used 27 Phase undervoltage(See 0-15) Not used 46 DTW2 Negative sequence current(See 0-15) Not used 46 ITW2 Negative sequence current See 0-15 46 DTW3 Negative sequence current(See 0-15) Not used 46 ITW3 Negative sequence current(See 0-15) Not used 49(See 0-15) Not used 50W1 # 1 Inst Phase overcurrent(See 015) Not used 50W1 # 2 Inst Phase overcurrent(See 015) Not used 50W2 # 1 Inst phase overcurrent(See 015) Not used 50W2 # 2 Inst phase overcurrent(See 015) Not used 50W3 # 1 Inst phase overcurrent(See 015) Not used 50W3 # 2 Inst phase overcurrent(See 015) Not used 50GW2 #1 Inst overcurrent(See 0-15) Not used 50GW2 #2 Inst overcurrent(See 0-15) Not used 50GW3 #1 Inst overcurrent(See 0-15) Not used

10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1

288-303 302 304-319 318 320-327 326 328-335 334 336-351 350 352-359 360-367 366 368-383 382 384-391 392-399 398 400-415 414 416-431 430 432-447 446 448-463 462 464-479 478 480-495 494 496-511 510 512-527 526 528-543 542 544-559 558 560-575 574 576-591 590 592-607 606 608-623 622 624-639 638

50GW3 #2 Inst overcurrent(See 0-15) Not used 50BFW1 Breaker Failure (See 0-15) Not used 50BFW1 Output initiation(See 0-7) 50BF W1 input initiation(See 8-15) Not used 50BFW2 Breaker Failure(See 0-15) Not used 50BFW2 Output initiation See 0-7 50BF W2 input initiation(See 8-15) Not used 50BFW3 Breaker Failure(See 0-15) Not used 50BFW3 Output initiation See 0-7 50BF W3 input initiation(See 8-15) Not used 51W1 Inverse time overcurrent(See 0-15) Not used 51W2 inverse time overcurrent(See 0-15) Not used 51W3 inverse time overcurrent(See 0-15) Not used 51NW1 Inverse residual time overcurrent(See 0-15) Not used 51NW2 Inverse residual time overcurrent (See 0-15) Not used 51NW3 Inverse residual timeOvercurrent (See 0-15) Not used 51G W2 Invrese ground time overcurrent (See 0-15) Not used 51G W3 Invrese ground time overcurrent (See 0-15) Not used 59G #1 Neutral Overvoltage(See 0-15) Not used 59G #2 Neutral Overvoltage(See 0-15) Not used 81U #1 Underfrequency(See 0-15) Not used 81U #2 Underfrequency(See 0-15) Not used 81U #3 Underfrequency(See 0-15) Not used 81U #4 Underfrequency(See 0-15) Not used 87H High set phase differential(See 0-15) Not used

10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1

640-655 654 656-671 670 672-687 686 688-703 702 704-711

87T Phase differential(See 0-15) Not used 87GD W2 Ground differential(See 0-15) Not used 87GD W3 Ground differential(See 0-15) Not used EXT #1 External(See 0-15) Not used EXT #1 Gate config(See 0-7) Bit 0 Output initiate gate Bit 1 Picked up functions initiate gate Bit 2 Input initiate gate Bit 3 Blocking inputs gate Bit 4 Inputs main gate Bit 5-15 Not used (0) 0 gate configured for OR gate configured for AND

10/2 10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1 12/1

712-719 720-727 728-743 742 744-751

EXT#1 Output initiate See 0-7 EXT#1 Input initiate See 8-15 EXT #2 External(See 0-15) Not used EXT #2 Gate config (See 0-7) Bit 0 Output initiate gate Bit 1 Picked up functions initiate gate Bit 2 Input initiate gate Bit 3 Blocking inputs gate Bit 4 Inputs main gate Bit 5-15 Not used (0) 0 gate configured for OR gate configured for AND

10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1

752-759 760-767 768-783 782 784-791

EXT #2 Output initiate See 0-7 EXT#2 input initiate(See 8-15) EXT # 3 External(See 0-15) Not used EXT #3 Gate config (See 0-7) Bit 0 Output initiate gate Bit 1 Picked up functions initiate gate Bit 2 Input initiate gate Bit 3 Blocking inputs gate Bit 4 Inputs main gate Bit 5-15 Not used (0) 0 gate configured for OR gate configured for AND

10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1

792-799

EXT#3 Output initiate See 0-7

10/2

12/1

800-807 808-823 822 824-831

EXT#3 input initiate(See 8-15) EXT # 4 External(See 0-15) Not used EXT #4 Gate config (See 0-7) Bit 0 Output initiate gate Bit 1 Picked up functions initiate gate Bit 2 Input initiate gate Bit 3 Blocking inputs gate Bit 4 Inputs main gate Bit 5-15 Not used (0) 0 gate configured for OR gate configured for AND

10/2 10/2 10/2

12/1 12/1 12/1

832-839 840-847 848-863 862 864-871

EXT#4 output initiate See 0-7 EXT#4 input initiate(See 8-15) EXT # 5 External See 0-15 EXT #5 Gate config (See 0-7) Bit 0 Output initiate gate Bit 1 Picked up functions initiate gate Bit 2 Input initiate gate Bit 3 Blocking inputs gate Bit 4 Inputs main gate Bit 5-15 Not used (0) 0 gate configured for OR gate configured for AND

10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1

872-879 880-887 888-903 902 904-911

EXT#5 Output initiate See 0-7 EXT#5 input initiate(See 8-15) EXT # 6 External (See 0-15) Not used EXT #6 Gate config (See 0-7) Bit 0 Output initiate gate Bit 1 Picked up functions initiate gate Bit 2 Input initiate gate Bit 3 Blocking inputs gate Bit 4 Inputs main gate Bit 5-15 Not used (0) 0 gate configured for OR gate configured for AND

10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1

912-919 920-927 928-943 942 944-959 958

EXT#6 output initiate See 0-7 EXT#6 input initiate(See 8-15) 50NW1 #1 Inst. Neutral overcurrent(See 0-15) Not used 50NW1 #2 Inst. Neutral overcurrent(See 0-15) Not used

10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1

960-975 974 976-991 990 992-1007 1006 1008-1023 1022 1024-1039 1038 1040-1055 1054 1056-1071 1070 1072-1077

50NW2 #1 Inst. Neutral overcurrent(See 0-15) Not used 50NW2 #2 Inst. Neutral overcurrent(See 0-15) Not used 50NW3 #1 Inst. Neutral overcurrent(See 0-15) Not used 50NW3 #2 Inst. Neutral overcurrent(See 0-15) Not used BRKRW1 Breaker monitoring(See 0-15) Not used BRKRW2 Breaker monitoring(See 0-15) Not used BRKRW3 Breaker monitoring(See 0-15) Not used Input status active state Bit0 = 0 IN1 active closed Bit0 = 1 IN1 active open Bit1-bit5 same as above for IN2-IN6 . Bit6-Bit15 not used (0) Oscillograph recorder Trigger inputs ** Trigger outputs Not used Not used Not used Not used Recorder status If read 0 = no records available 1=at least 1 record available OSC REC led) If write 1 = remotely trigger recorder 2= Clear all records BRKRW1 Output initiate BRKRW1 Input initiate Not used BRKRW2 Output initiate BRKRW2 Input initiate Not used BRKRW3 Output initiate BRKRW3 Input initiate Not used

10/2 10/2 10/2 10/2 10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1 12/1 12/1 12/1 12/1

1078-1085 1086-1093 1094 1095 1096 1097 1098

10/2 10/2 10/2

12/1 12/1 12/1

10/2 (follows

12/1

1099-1106 1107-1112 1113-1114 1115-1122 1123-1128 1129-1130 1131-1138 1139-1144 1145-1146

10/2 10/2 10/2 10/2 10/2 10/2

12/1 12/1 12/1 12/1 12/1 12/1

Analog Inputs Static (Steady-State) Object Number: 30 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: Point Index Description 0 1 2 3 4 5 6 30 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92

2 (16-Bit Analog Input) Static Class 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Object/V ar 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 Units Scale factor 1 1U 1 100 1 1

Control identification Control serial number Control communication address Software version number(Major & Minor) Software version number(Build) User control number User Line 1 (6-29) User Line 2(30-53) Not used Options software Options Hardware Dip switch Checksum active profile setpoints Checksum calibration Checksum ROM Checksum profile1 Checksum profile2 Checksum profile3 Checksum profile4 Voltage W1 Phase A current W1 Phase B current W1 Phase C current W1 Positive Seq current W1 negative seq current W1 Zero seq current W2 Phase A current W2 Phase B current W2 Phase C current W2 Phase G current W2 Positive seq current W2 negative seq current W2 Zero seq current W3 Phase A current W3 Phase B Current W3 Phase C Current W3 Phase G current W3 Positive seq current W3 negative seq current W3 Zero Seq current Phase A differential current Phase B differential current Phase C differential current W2 Ground differential current W3 Ground differential current Frequency Volts per hertz

1 1 1 1 1U 1U 1U 1U 1U 10 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 100 100 100 10

VOLTS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS PU PU PU AMPS AMPS HZ %

93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145

Phase A restraint current Phase B restraint current Phase C restraint current Phase A 2nd harmonic restraint current Phase B 2nd harmonic restraint current Phase C 2nd harmonic restraint current Phase A 4th harmonic restraint current Phase B 4th harmonic restraint current Phase C 4th harmonic restraint current Phase A 5th harmonic restraint current Phase B 5th harmonic restraint current Phase C 5th harmonic restraint current Voltage Phasor real Vx Voltage Phasor imaginary Vx Current phasor real IA W1 Current phasor imaginary IA W1 Current phasor real IB W1 Current phasor imaginary IB W1 Current phasor real IC W1 Current phasor imaginary IC W1 Current phasor real IA W2 Current phasor imaginary IA W2 Current phasor real IB W2 Current phasor imaginary IB W2 Current phasor real IC W2 Current phasor imaginary IC W2 Current phasor real IA W3 Current phasor imaginary IA W3 Current phasor real IB W3 Current phasor imaginary IB W3 Current phasor real IC W3 Current phasor imaginary IC W3 Current phasor real IG W2 Current phasor imaginary IG W2 Current phasor real IG W3 Current phasor imaginary IG W3 W1 Phase A current demand W1 Phase B current demand W1 Phase C current demand W2 Phase A current demand W2 Phase B current demand W2 Phase C current demand W2 Phase G current demand W3 Phase A current demand W3 Phase B current demand W3 Phase C current demand W3 Phase G current demand Number of partitions (osicllograph) Post trigger delay Recorder status Record #1 status (latest) Record #2 status Record #3 status

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02

PU PU PU PU PU PU PU PU PU PU PU PU

AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS %

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1 1 1 1 1 1

146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195

Record #4 status Download Record #1 block Download Record #2 block Download Record #3 block Download Record #4 block Function status (pick up)Least significant word D0 Function status (pick up) Next significant word D1 Function status (pick up) Next significant word D2 Function status (pick up) Most significant word D3 Function timer Least significant word D0 Function timer Next significant word D1 Function timer Next significant word D2 Function timer Most significant word D3 Last selftest error code Last selftest error code 1 Last selftest error code 2 Last selftest error code 3 Last comm error code Target LED status Receive packet errors EEPROM selftest counter Target 1- 32 relay status Target 1 32 input status Function status (picked up) 0 Function status 1 Function status 2 Function status 3 Function timer 0 Function timer 1 Function timer 2 Function timer 3 Target 1-32 Active Profile Target 1-32 ,50W1 #1, #2 Target 1-32 ,50W2 #1, #2 Target 1-32 ,50W3 #1, #2 Target 1-32 51 Phase status/timer W1 Target 1-32 51 Phase status/timer W2 Target 1-32 51 Phase status/timer W3 Target 1-32 ,87H and 87T timer Target 1-32 ,87H and 87T status Target 1-32,Phase A W1 current Target 1-32,Phase B W1 current Target 1-32,Phase C W1 current Target 1-32,Phase A W2 current Target 1-32,Phase B W2 current Target 1-32,Phase C W2 current Target 1-32,Phase G W2 current Target 1-32,Phase A W3 current Target 1-32,Phase B W3 current Target 1-32,Phase C W3 current

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02

1 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1 1 1 1 1 1 1 1 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 100 100 100 100 100 100 100 100 100 100

AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS

196 197-202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244-249

Target 1-32,Phase G W3 current Target 1-32Target date and time stamp(DNP format) Not used Not used Not used Not used Not used Precompensated phasor IA W1 real Precompensated phasor IA W1 imag. Precompensated phasor IB W1 real Precompensated phasor IB W1 imag. Precompensated phasor IC W1 real Precompensated phasor IC W1 imag. Precompensated phasor IA W2 real Precompensated phasor IA W2 imag. Precompensated phasor IB W2 real Precompensated phasor IB W2 imag. Precompensated phasor IC W2 real Precompensated phasor IC W2 imag. Precompensated phasor IA W3 real Precompensated phasor IA W3 imag. Precompensated phasor IB W3 real Precompensated phasor IB W3 imag. Precompensated phasor IC W3 real Precompensated phasor IC W3 imag. Postcompensated phasor IA W1 real Postcompensated phasor IA W1 imag. Postcompensated phasor IB W1 real Postcompensated phasor IB W1 imag. Postcompensated phasor IC W1 real Postcompensated phasor IC W1 imag. Postcompensated phasor IA W2 real Postcompensated phasor IA W2 imag. Postcompensated phasor IB W2 real Postcompensated phasor IB W2 imag. Postcompensated phasor IC W2 real Postcompensated phasor IC W2 imag. Postcompensated phasor IA W3 real Postcompensated phasor IA W3 imag. Postcompensated phasor IB W3 real Postcompensated phasor IB W3 imag. Postcompensated phasor IC W3 real Postcompensated phasor IC W3 imag. W1 Phase A current Max Time (DNP format) drag_time (0)- W1 Phase A current Max drag_time (1)- W2 Phase A current Max drag_time (2)- W3 Phase A current Max drag_time (3)- W1 Phase B current Max drag_time (4)- W2 Phase B current Max drag_time (5)- W3 Phase B current Max drag_time (6)- W1 Phase C current Max drag_time (7)- W2 Phase C current Max

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02 30/02

AMPS

100

1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U

drag_time (8)- W3 Phase C current Max drag_time (9)- W2 Phase G current Max drag_time (10)- W3 Phase G current Max 250 251 252 253 254 255 256 257 258 259 260 Ct sec rating(Read only) 0 = 1Amp 1 = 5Amp Nominal freq(Read only) 0 = 50HZ 1 = 60HZ Phase A W1 Breaker monitoring arc current acc. Phase B W1 Breaker monitoring arc current acc. Phase C W1 Breaker monitoring arc current acc. Phase A W2 Breaker monitoring arc current acc. Phase B W2 Breaker monitoring arc current acc. Phase C W2 Breaker monitoring arc current acc. Phase A W3 Breaker monitoring arc current acc. Phase B W3 Breaker monitoring arc current acc. Phase C W3 Breaker monitoring arc current acc. 0-1 0-1 0-50000000/1 0-50000000/1 0-50000000/1 0-50000000/1 0-50000000/1 0-50000000/1 0-50000000/1 0-50000000/1 0-50000000/1 30/02 30/02 30/01 30/01 30/01 30/01 30/01 30/01 30/01 30/01 30/01 AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS AMPS 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U

Binary Counters Static (Steady-State) Object Number: 20 Request Function Codes supported: 1 (read), 9 (freeze and clear) Point index 0 1 2 3 4 5 6 Name/Description Processor reset counter Powerloss counter OUT1 counter OUT2 counter OUT3 counter OUT4 counter OUT5 counter Static class 0 0 0 0 0 0 0 Object/Var 20/02 20/02 20/02 20/02 20/02 20/02 20/02

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

OUT6 counter OUT7 counter OUT8 counter Alarm counter Clear target history Clear oscillograph recorder Clear target led Pre and Post compensated phasors set update trigger Phasor set update trigger W1 Phase A current Max W2 Phase A current Max W3 Phase A current Max W1 Phase B current Max W2 Phase B current Max W3 Phase B current Max W1 Phase C current Max W2 Phase C current Max W3 Phase C current Max W2 Phase G current Max W3 Phase G current Max

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02 20/02

16Bit/32 bit Analog output with status(Obj 40, Var 02,Var 01) Request Function Code supported: 1 (read) 16 Bit/32 bit Analog output block(obj 41, Var 02, Var 01) Request Function code supported: 5(Selexe)

Point index 0 1 2 3 4 5 6

7 8 9 10 11 12

13 14

15 16

17

18 19

20

21 22 23 24

Range 100-200 30-8160 100-200 30-8160 100-150 1-4 if curve=1 10-1000 / 10 else if curve=2,3,4 0-90 24IT reset rate 1-999 27 Undervoltage Pickup 5-140 27 Inhibit setting 0-1 27 undervoltage inhibit 5-140 27 Delay 1-8160 46DT W2 Pickup if C.T. secondary rating = 5Amp 10-2000 / 1 if C.T. secondary rating = 1Amp 2-400 / 1 46DTW2 Delay 1-8160 46 IT W2 Pickup if C.T. secondary rating = 5Amp 50-500 / 1 if C.T. secondary rating = 1Amp 10-100 / 1 46ITW2 Curve Type 1-8 46IT W2 Time dial if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 46DTW3 Pickup if C.T. secondary rating = 5Amp 10-2000 / 1 if C.T. secondary rating = 1Amp 2-400 / 1 46DTW3 Delay 1-8160 46ITW3 Pickup if C.T. secondary rating = 5Amp 50-500 / 1 if C.T. secondary rating = 1Amp 10-100 / 1 46ITW3 Time dial if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 46ITW3 Curve type 1-8 49 Time dial 10-9999 49 Maximum overload current 100-1000 Not used

Name/Description 24DT #1 Pickup 24DT #1 Delay 24DT #2 Pickup 24DT #2 Delay 24IT Pickup 24IT Curve 24IT Time dial

Scale Factor 1 1 1 1 1 1 10

Units % CYCLES % CYCLES

1 1 1 1 100

SEC VOLTS VOLTS CYCLES AMPS

1 100

CYCLES AMPS

1 100

100

AMPS

1 100

CYCLES AMPS

100

1 10 100

MINS AMPS

25 26

49 Winding select 50W1 #1 Pickup

27 28

50W1 #1 delay 50W1 #2 Pickup

29 30

50W1#2 delay 50W2 #1 Pickup

31 32

50W2#1 delay 50W2 #2 Pickup

33 34

50W2#2 delay 50W3 #1 Pickup

35 36

50W3#1 delay 50W3 #2 Pickup

37 38

50W3#2 delay 50GW2#1 Pickup

39 40

50GW2#1 delay 50GW2#2 Pickup

0-2 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp

1 10

AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

41 42

50GW2#2 delay 50GW3#1 Pickup

43 44

50GW3#1 delay 50GW3#2 Pickup

45 46 47

50GW3#2 delay Not used 50BFW1 Phase pickup

2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200/1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200/1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 If C.T. secondary rating =

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 100

CYCLES AMPS

48 49

Not used 50BFW1 Residual Pickup

100

AMPS

50 51 52

50BFW1 delay Not used 50BFW2 Phase pickup

1 100

CYCLES AMPS

53 54

Not used 50BFW2 Residual pickup

100

AMPS

55 56 57

50BFW2 delay Not used 50BFW3 Phase pickup

1 100

CYCLES AMPS

58 59

Not used 50BFW3 Residual pickup

100

AMPS

60 61

50BFW3 delay 51W1 Pickup

62

63

51W1 Curve type 1 = Definite time 2 = Inverse 3 = Very inverse 4 = Extremely inverse 5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51W1 Time dial

5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200/1 1-8160 If C.T. secondary rating = 5Amp 50-1200 / 1 if C.T. secondary rating = 1Amp 10-240 / 1 1-8

1 100

CYCLES AMPS

64

51W2 Pickup

65

66

51W2 Curve type 1 = Definite time 2 = Inverse 3 = Very inverse 4 = Extremely inverse 5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51W2 Time dial

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 If C.T. secondary rating = 5Amp 50-1200 / 1 if C.T. secondary rating = 1Amp 10-240 / 1 1-8

100

100

AMPS

67

51W3 Pickup

68

51W3 Curve type 1 = Definite time 2 = Inverse 3 = Very inverse 4 = Extremely inverse

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 If C.T. secondary rating = 5Amp 50-1200 / 1 if C.T. secondary rating = 1Amp 10-240 / 1 1-8

100

100

AMPS

69

5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51W3 Time dial

70

51NW1 Pickup

71

72

51NW1 Curve type 1 = Definite time 2 = Inverse 3 = Very inverse 4 = Extremely inverse 5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51NW1 Time dial

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 if C.T. secondary rating = 5Amp 50-600 / 1 if C.T. secondary rating = 1Amp 10-120 / 1 1-8

100

100

AMPS

73

51NW2 Pickup

74

75

51NW2 Curve type 1 = Definite time 2 = Inverse 3 = Very inverse 4 = Extremely inverse 5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51NW2 Time dial

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 if C.T. secondary rating = 5Amp 50-600 / 1 if C.T. secondary rating = 1Amp 10-120 / 1 1-8

100

100

AMPS

76

51NW3 Pickup

77

51NW3 Curve type 1 = Definite time 2 = Inverse

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 if C.T. secondary rating = 5Amp 50-600 / 1 if C.T. secondary rating = 1Amp 10-120 / 1 1-8

100

100

AMPS

78

3 = Very inverse 4 = Extremely inverse 5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51NW3 Time dial

79

51GW2 Pickup

80

81

51GW2 Curve type 1 = Definite time 2 = Inverse 3 = Very inverse 4 = Extremely inverse 5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51GW2 Time dial

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 if C.T. secondary rating = 5Amp 50-1200 / 1 if C.T. secondary rating = 1Amp 10-240 / 1 1-8

100

100

AMPS

82

51GW3 Pickup

83

84

51GW3 Curve type 1 = Definite time 2 = Inverse 3 = Very inverse 4 = Extremely inverse 5 = IEC Inverse 6 = IEC Very Inverse 7 = IEC Extremely inverse 8 = IEC Long time inverse 51GW3 Time dial

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 if C.T. secondary rating = 5Amp 50-1200 / 1 if C.T. secondary rating = 1Amp 10-240 / 1 1-8

100

100

AMPS

85 86 87 88 89

59G#1 Neutral Overvoltage pickup 59G #2 Neutral Overvoltage pickup 59G #1 delay 59G #2 delay 81 #1 Pickup

if curve = 1->4 50 1100 / 10 if curve = 5->8 5 110 / 1 5-180 5-180 1-8160 1-8160 if nominal frequency =60Hz

100

1 1 1 1 100

VOLTS VOLTS CYCLES CYCLES HZ

90

91

92

93 94 95 96 97 98 99 100 101 102 103 104

105 106 107 108

109 110

111 112 113 114 115

5500-6500 / 1 if nominal frequency=50 Hz 4500-5500 / 1 81 #2 Pickup if nominal frequency=60Hz 5500-6500 / 1 if nominal frequency=50 Hz 4500-5500 / 1 81 #3 Pickup if nominal frequency =60Hz 5500-6500 / 1 if nominal frequency=50 Hz 4500-5500 / 1 81 #4 Pickup if nominal frequency =60Hz 5500-6500 / 1 if nominal frequency=50 Hz 4500-5500 / 1 81 #1 delay 2-65500 81 #2 delay 2-65500 81 #3 delay 2-65500 81 #4 delay 2-65500 87H Pickup 50-200 / 1 87H Time delay 1-8160 87T Pickup 10-100 87T Slope #1 5-100 87T Slope #2 5-200 87T Slope break point 10-40 87T Even harmonic restraint 5-50 87T Even Harmonic Restraint 0-2 Enable (2nd & 4th ) (2nd & 4th ) 0 = Disable 1 = Enable 2 = Enable w/cross average 87T 5th harmonic Restraint 5-50 87T Pickup at 5th harmonic 10-200 restraint 87T 5th Harmonic Restraint Enable 87GD W2 Pickup If C.T. secondary rating = 5Amp 20-1000 / 1 if C.T. secondary rating = 1Amp 4-200 / 1 87GD W2 delay 1-8160 87GD W3 Pickup If C.T. secondary rating = 5Amp 20-1000 / 1 if C.T. secondary rating = 1Amp 4-200 / 1 87GD W3 delay 1-8160 BRKRW1 Pickup 0-50000 BRKRW1 Delay 1-40959 BRKRW2 Pickup 0-50000 BRKRW2 Delay 1-40959

100

HZ

100

HZ

100

HZ

1 1 1 1 10 1 100 1 1 10 1 1

CYCLES CYCLES CYCLES CYCLES PU CYCLES PU % % PU %

1 100

% PU

100

AMPS

1 100

CYCLES AMPS

1 1 10 1 10

CYCLES KAMPS CYCLES KAMPS CYCLES

116 117 118

BRKRW3 Pickup BRKRW3 Delay 50NW1 #1 Pickup

119 120

50NW1 #1 Delay 50NW1 #2 Pickup

121 122

50NW1 #2 Delay 50NW2 #1 Pickup

123 124

50NW2 #1 Delay 50NW2 #2 Pickup

125 126

50NW2 #2 Delay 50NW3 #1 Pickup

127 128

50NW3 #1 Delay 50NW3 #2 Pickup

129 130 131 132 133 134 135 136 137 138

50NW3 #2 Delay EXT #1 Delay EXT #2 Delay EXT #3 Delay EXT #4 Delay EXT #5 Delay EXT #6 Delay EXT #1 Picked up functions initiate mask (LSW) EXT #1 Picked up functions initiate mask (NSW) EXT #1 Picked up functions

0-50000 1-40959 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 If C.T. secondary rating = 5Amp 10-1000 / 1 if C.T. secondary rating =1Amp 2-200 / 1 1-8160 1-65500 1-65500 1-65500 1-65500 1-65500 1-65500 0-65535 0-65535 0-65535

1 10 10

KAMPS CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 10

CYCLES AMPS

1 1 1 1 1 1 1 1U 1U 1U

CYCLES CYCLES CYCLES CYCLES CYCLES CYCLES CYCLES

139 140

initiate mask (NSW) EXT #1 Picked up functions initiate mask (MSW) EXT #1 Switch profile

0-65535 0-4 0 not activated 1 swith to profile 1 2 switch to profile 2 3 switch to profile 3 4 - switch to profile 4 0-65535 0-65535 0-65535 0-65535 0-4 0-65535 0-65535 0-65535 0-65535 0-4 0-65535 0-65535 0-65535 0-65535 0-4 0-65535 0-65535 0-65535 0-65535 0-4 0-65535 0-65535 0-65535 0-65535 0-4 0-2

1U 1U

141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166

EXT #2 Picked up functions initiate mask (LSW) EXT #2 Picked up functions initiate mask (NSW) EXT #2 Picked up functions initiate mask (NSW) EXT #2 Picked up functions initiate mask (MSW) EXT #2 Switch profile EXT #3 Picked up functions initiate mask (LSW) EXT #3 Picked up functions initiate mask (NSW) EXT #3 Picked up functions initiate mask (NSW) EXT #3 Picked up functions initiate mask (MSW) EXT #3 Switch profile EXT #4 Picked up functions initiate mask (LSW) EXT #4 Picked up functions initiate mask (NSW) EXT #4 Picked up functions initiate mask (NSW) EXT #4 Picked up functions initiate mask (MSW) EXT #4 Switch profile EXT #5 Picked up functions initiate mask (LSW) EXT #5 Picked up functions initiate mask (NSW) EXT #5 Picked up functions initiate mask (NSW) EXT #5 Picked up functions initiate mask (MSW) EXT #5 Switch profile EXT #6 Picked up functions initiate mask (LSW) EXT #6 Picked up functions initiate mask (NSW) EXT #6 Picked up functions initiate mask (NSW) EXT #6 Picked up functions initiate mask (MSW) EXT #6 Switch profile Profile switching method

1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1U 1

167 168 169 170 171

172

173 174 175 176 177 178 179 180 181

Active profile copy active profile to Nominal voltage Nominal current V.T. Configuration 0 =AB 1 = BC 2 =AC 3 =AN 4 =BN 5 =CN 6=LG to LL CT connection type W1 0- Y connection 1- Delta AB connection 2- Delta AC connection 3- Y inverse connection 4- Delta AB inverse connection 5 Delta AC inverse connection CT connection type W2 CT connection type W3 PT connection type W1 PT connection type W2 PT connection type W3 Phase rotation 0 = ACB 1 = ABC Not used Not used Demand time interval 1 = 15 Minutes 2 = 30 Minutes 3 = 60 Minutes V.T.x Phase ratio C.T. W1 Phase ratio C.T. W2 Phase ratio C.T. W3 Phase ratio C.T. W2 Ground ratio C.T. W3 Ground ratio C.T. W1 tap correction

0-3 1-4 60-140 50-600 0-6

1 1 1 100 1

VOLTS AMPS

0-5

0-5 0-5 0-5 0-5 0-5 0-1

1 1 1 1

1-3

182 183 184 185 186 187 188

189

C.T. W2 tap correction

10-65500 10-65500 10-65500 10-65500 10-65500 10-65500 if C.T. secondary rating = 5Amp 100-1000 / 1 if C.T. secondary rating = 1Amp 20-200 / 1 if C.T. secondary rating = 5Amp 100-1000 / 1 if C.T. secondary rating = 1Amp 20-200 / 1

10 1 1 1 1 1 100

100

190

C.T. W3 tap correction

191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221

C.T. W2 Ground correction (87GD) C.T. W3 Ground correction (87GD) Sealin Delay OUT1 Sealin Delay OUT2 Sealin Delay OUT3 Sealin Delay OUT4 Sealin Delay OUT5 Sealin Delay OUT6 Sealin Delay OUT7 Sealin Delay OUT8 W1 Phase A breaker monitoring arc current acc W1 Phase B breaker monitoring arc current acc W1 Phase C breaker monitoring arc current acc W2 Phase A breaker monitoring arc current acc W2 Phase B breaker monitoring arc current acc W2 Phase C breaker monitoring arc current acc W3 Phase A breaker monitoring arc current acc W3 Phase B breaker monitoring arc current acc W3 Phase C breaker monitoring arc current acc Not used EXT #1 Communication initiate EXT #1 Communication block EXT #2 Communication initiate EXT #2 Communication block EXT #3 Communication initiate EXT #3 Communication block EXT #4 Communication initiate EXT #4 Communication block EXT #5 Communication initiate EXT #5 Communication block EXT #6 Communication initiate

if C.T. secondary rating = 5Amp 100-1000 / 1 if C.T. secondary rating = 1Amp 20-200 / 1 10-799 / 1 10-799 / 1 2-8160 2-8160 2-8160 2-8160 2-8160 2-8160 2-8160 2-8160 0-50000/1 0-50000/1 0-50000/1 0-50000/1 0-50000/1 0-50000/1 0-50000/1 0-50000/1 0-50000/1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1 0-1

100

100 100 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 CYCLES CYCLES CYCLES CYCLES CYCLES CYCLES CYCLES CYCLES KAMPS KAMPS KAMPS KAMPS KAMPS KAMPS KAMPS KAMPS KAMPS

222 223

224

225

EXT #6 Communication block 0-1 Target_Num 1-32 1- Target 1 info 2- Target 2 info .. 32-Target 32 info Winding Disable 0-3 0- All windings enabled 1- W1 disabled 2- W2 disabled 3- W3 disabled Transformer and CT 0-1 connection custom mode 0 custom mode disabled enable 1 custom mode enabled Transformer phase comp. type W1 Transformer phase comp. type W2 Transformer phase comp. type W3 CT phase/magnitude comp. W1 CT phase/magnitude comp. W2 CT phase/magnitude comp. W3 Zero Sequence Enable Bit 0 W1 zero seq. Enable Bit 1 W2 zero seq. Enable Bit 2 W3 zero seq. Enable Bits 3-7 Not used Wrtiteable only if 225 set to 1 Drag_time 0- W1 Phase A current Max Time 1- W2 Phase A current Max Time 2- W3 Phase A current Max Time 3- W1 Phase B current Max Time 4- W2 Phase B current Max Time 5- W3 Phase B current Max Time 6- W1 Phase C current Max Time 7- W2 Phase C current Max Time 8- W3 Phase C current Max Time 9- W2 Phase G current Max Time 0-11 0-11 0-11 0-23 0-23 0-23 0-255

1 1

226 227 228 229 230 231 232

1 1 1 1 1 1 1

233

0-10

234 235

236

10 W3 Phase G current Max Time Dnp_comm_addr Recorder trigger inhibit 0 = recorder active (running) 1 = recorder trigger inhibit Bit 0 inhibit by COM1 Bit 1 inhibit by COM2 Bit 2 inhibit by COM3 Bit 3-15 NA Breaker monitor timing method select Bit 0 W1 Bit 1 W2 Bit 2 W3 Bit3-Bit7 - Not Used 0 I*t method selected 1 I2*t method selected

0-65519 0-1

1 1

0-255

By writing the setpoint 233 drag_time(obj 40,var 02), will have corresponding phase current time. By writing the setpoint 223 Target_num(obj 40,var 02), will have corresponding target information. Points 201 to 209 can be written using object 41,Variation 01(32 bit).