You are on page 1of 10

SECTION 16269 VARIABLE FREQUENCY CONTROLLERS PART 1 - GENERAL Read and conform to all electrical sections of these specifications,the

general instructions for electrical division, section 16010, apply to and form part of all electrical sections. These shall be read in conjunction with design drawings. 1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply to this Section. 1.02 SUMMARY

A. This Section includes solid-state, VFCs for speed control of three-phase, squirrelcage induction motors. 1.03 A. 1. Product Data: For each type of VFC, provide dimensions; mounting arrangements; location for conduit entries; shipping and operating weights; and manufacturer's technical data on features, performance, electrical ratings, characteristics, and finishes. 2. Submit relevant documents for EMI compatibility, Surge protection requirements & Harmonic filteration . All relevant data to be provided. B. Shop Drawings: For each VFC. 1. Include dimensioned plans, elevations, sections, and details, including required clearances and service space around equipment. Show tabulations of installed devices, equipment features, and ratings. Include the following: a. Each installed unit's type and details. b. Nameplate legends. c. Short-circuit current ratings of integrated unit. d. UL listing for series rating of over current protective devices in combination controllers. e. Features, characteristics, ratings, and factory settings of each motorcontrol center unit. 2. Wiring Diagrams: Power, signal, and control wiring for VFC. schematic wiring diagram for each type of VFC. Provide SUBMITTALS

WB4733 Al Ghurair City Expansion Phase II

16269 April 2008 Rev - 0

Variable Frequency Controllers. Page 1 of 10

C. Coordination Drawings: Floor plans showing dimensioned layout, required working clearances, and required area above and around VFCs where pipe and ducts are prohibited. Show VFC layout and relationships between electrical components and adjacent structural and mechanical elements. Show support locations, type of support, and weight on each support. Indicate field measurements. D. Qualification Data: For testing agency and manufacturer. E. Manufacturer's field service report. F. Operation and Maintenance Data: For VFCs, all installed devices, and components to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 1 include the following: 1. Routine maintenance requirements for VFCs and all installed components. 2. Manufacturer's written instructions for testing and adjusting overcurrent protective devices. 3. Interfacing provisions for BMS. G. Load-Current and List of Settings of Adjustable Overload Relays: Compile after motors have been installed and arrange to demonstrate that dip switch settings for motor running overload protection suit actual motor to be protected. 1.04 QUALITY ASSURANCE

A. Manufacturer Qualifications: Manufacturer shall have an own office in the country of installation to provide complete product support and after sales service. B. Source Limitations: Obtain VFCs of a single type through one source from a single manufacturer. C. Comply with the following standards. 1. The VFD shall conform to international standards and meet the recommendations of the following: a. EMC Immunity: 1) IEC 1000-4-2/EN 61000-4-2 Level 3 2) IEC 1000-4-3/EN 61000-4-3 Level 3 3) IEC 1000-4-4/EN 61000-4-4 Level 4 4) IEC 1000-4-5/EN 61000-4-5 Level 3 b. EMC, conducted and radiated emissions: 1) IEC 1800-3-2/EN 61800-3, environment 1 (public sector) and 2 (industrial sector) under restricted distribution 2) EN 55011 class A (RFI filters included) 3) EN 55022 class B, with additional filters c. Vibrations: 1) IEC 68-2-6, 1.5 mm peak from 2 to 13 Hz, 1g from 13 to 200Hz 2. The VFD shall have UL and CSA , ISO 9001, ISO 14001, Stick product certification approvals. 3. The VFD shall consist of a variable Frequency Controller, a circuit breaker, a line contactor and necessary indicating lights and switch/pushbuttons.
WB4733 Al Ghurair City Expansion Phase II 16269 April 2008 Rev - 0 Variable Frequency Controllers. Page 2 of 10

4. The VFD along with associated components shall be installed in an enclosure having sufficient ventilation for heat dissipation. 1.05 DELIVERY, STORAGE, AND HANDLING

A. Deliver VFCs in shipping splits of lengths that can be moved past obstructions in delivery path as indicated. B. Store VFCs indoors in clean, dry space with uniform temperature to prevent condensation. Protect VFCs from exposure to dirt, fumes, water, corrosive substances, and physical damage. C. If stored in areas subject to weather, cover VFCs to protect them from weather, dirt, dust, corrosive substances, and physical damage. Remove loose packing and flammable materials from inside controllers; install electric heating of sufficient wattage to prevent condensation. 1.06 COORDINATION

A. Coordinate layout and installation of VFCs with other construction including conduit, piping, equipment, and adjacent surfaces. Maintain required workspace clearances and required clearances for equipment access doors and panels. B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. C. Coordinate installation of roof curbs, equipment supports, and roof penetrations. D. Coordinate features of VFCs, installed units, and accessory devices with pilot devices and control circuits to which they connect. E. Coordinate features, accessories, and functions of each VFC and each installed unit with ratings and characteristics of supply circuit, motor, required control sequence, and duty cycle of motor and load. 1.07 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Spare Fuses: Furnish one spare for every five (5) installed, but not less than one set of three (3) of each type and rating. 2. Indicating Lights: two (2) of each type installed.

WB4733 Al Ghurair City Expansion Phase II

16269 April 2008 Rev - 0

Variable Frequency Controllers. Page 3 of 10

PART 2 - PRODUCTS 2.01 OUTPUT CHARACTERISTICS

A. Start-up and Permanent Operation 1. The VFC shall be capable of continuously delivering its rated output voltage to the motor in the limit of acceptable input voltage variations. 2. The VFC shall be able to control a 3-phase squirrel cage motor over a speed range of 3. 1% (minimal speed) to 100% (maximum speed), continuously and smoothly. 4. Within this speed range no derating of nominal torque value is accepted. 5. The VFC shall be adaptable to various types of applications and in particular it shall be possible to select on site, one of the three following operating modes: a. For low speed machines and heavy loading, (i.e.: high U/f ratio)* b. For machines with average loading operating at low speed (i.e.: constant torque, U/f ratio)* c. For pumps and fans (i.e.: variable torque, progressive U/f ratio)* (*): U= output voltage in Volt, f = output frequency in Hz. B. Transient Conditions: 1. For application requesting the VFC to operate in a constant torque configuration, transient over torque (for 60 sec.) shall be possible: 15% of nominal torque of motor. 2. For application requesting the VFSD to operate in a variable torque configuration, transient over torque of 120% of nominal torque shall be possible. 3. To protect the network against transient current, a current limitation function shall be used: a. For constant torque applications, limitation at 150% of motor nominal current for 60 s b. For variable torque applications, limitation at 120% of motor nominal current for 60 s. C. Inverter protections: 1. The VFC shall include the following auto protections against short-circuits: a. Between phase to phase, b. Between phase to earth, c. On internal supplies, d. On analogue and logic outputs. 2. It shall also include the following protections: a. Overheating, b. Mains over voltage and undervoltage, c. Loss of input phase. d. Underload. e. External fault.
WB4733 Al Ghurair City Expansion Phase II 16269 April 2008 Rev - 0 Variable Frequency Controllers. Page 4 of 10

D. Motor protections: 1. The VFC shall include the following motor protections: a. Protection by continuous calculation of I2t, as a function of speed b. Saving of motor thermal state when the VFC is powered off, c. Loss of output phase. d. Protection via PTC probes 2. Motor protection mode shall be adaptable to type of motor cooling, forcecooled or self-cooled. 2.02 INPUT CHARACTERISTICS

A. Input voltage 1. The VFC shall be capable of maintaining its output performances when powered under the following conditions: a. Mains voltage 400V +/- 5%, b. Mains frequency 50. 2. In case of mains undervoltage, the VFC shall operate in the following mode: 3. The VFC shall have a minimum AC undervoltage power loss ride through of 200 milliseconds (10 cycles) B. Input current 1. During start-up sequences speed shall increase smoothly and limitation current can be reached. a. All VFDs shall have built in chokes. 1) To reduce harmonic currents feedback, 2) To limit input voltage spikes. 2. In installation where harmonic current circulation may affect the operation of sensitive equipment, global or local compensation of harmonic currents shall be provided. 3. In this case only auto adaptable harmonic compensators are acceptable to cope with permanent modification of harmonic content. (e.g.: active harmonic compensators). The VFC shall have an RFI Filter. 2.03 ENVIRONMENTAL CONDITIONS

A. The VFC shall be able to operate without derating under the following conditions: 1. Ambient temperature: 0 to 40 oC, without derating 2. Altitude from see level: 1000 m, without derating 3. Relative humidity: 93% with no condensation or dripping water (IEC 68-2-3). 2.04 KEYPAD DISPLAY INTERFACE

A. The keypad display interface shall offer the modification of AC Controller adjustments via a touch keypad. All electrical values, configuration parameters, I/O assignments, application and activity function access, faults, local control, and adjustment storage, and diagnostics shall be in plain English. There will be

WB4733 Al Ghurair City Expansion Phase II

16269 April 2008 Rev - 0

Variable Frequency Controllers. Page 5 of 10

a standard selection of 2 additional languages built-in to the operating software as standard. B. The display will be a high resolution, LCD backlit screen. The keypad shall be detachable. C. The AC Drive model number, torque type, software revision number, horsepower, output current, motor frequency and motor voltage shall be listed on the controller identification portion of the LCD display. D. The keypad display shall consist of programmable function keys that allow both operating commands and programming options to be preset by the operator. A hardware selector switch and password setting shall allow the terminal keypad to be locked out from unauthorized personnel. E. A RUN key and a STOP key will command a normal starting and stopping as programmed when the AC Controller is in keypad control mode. The STOP key must be active in all control modes. Provisions for covering the RUN and STOP keys must be available for applications that do not allow starting and stopping from the keypad. F. The AC Controller shall have two LEDs mounted on the front panel to indicate functional status. A green LED will verify that the AC Controller power supply is on. A red LED indicator will indicate an AC Controller fault. G. KWH and MWH shall be indicated. 2.05 ADJUSTMENTS & CONFIGURATIONS

A. The AC Controller will be factory programmed to operate all specified optional devices. B. The output frequency of the VFC is ranging from 1 to 250 Hz, for power ratings up to 75KW, and from 1 to 250 Hz for powers between 75 kW to 630 kW. C. The acceleration and deceleration ramp times shall be variable from 0.1 to 1800 seconds. D. The memory shall retain and record run status and fault type of the past fault. The VFC will record the 16 last faults for all rating. E. The software shall have an Energy Economy function that, when selected, will reduce the voltage to the motor when selected for variable torque loads. A constant volts/Hz ratio will be maintained during acceleration. The output voltage will then automatically adjust to meet the torque requirement of the load. F. As an option the VFC shall also include facility for communication with industrial networks or PLCs, using various communication protocols.

WB4733 Al Ghurair City Expansion Phase II

16269 April 2008 Rev - 0

Variable Frequency Controllers. Page 6 of 10

2.06

REMOTE INFORMATION

A The following minimum features shall be incorporated in the VFC: 1. Analogue inputs: a. 1 analogue voltage input, 0-10 V impedance 30 k, b. 1 analogue current input X-Y mA (X and Y programmable from 0 to 20), maximum impedance 250 k, 2. Reassignment of these values shall be possible from the keypad of the VSD. 3. Frequency resolution not greater than 0.1 Hz for 100 Hz 4. Sampling time 4 or 5m 5. Logic inputs: a. 5 logic inputs, impedance 3.5 k, 6. It shall be possible to reassign all of these inputs from the keypad of the equipment. a. Analogue outputs: 1) For all VFDs, 1 analogue output 0-20 mA or 4-20 mA 2) For power rating higher than 75 kW, 2 analog outputs 0-20 mA or 4-20 mA 7. Unless differently specified, these shall be factory set up to: Output frequency 8. It shall also be possible to reassign these outputs to other functions. 9. Logic outputs: a. 1 or 2 PLC compatible logic outputs, which can be reassigned from the keypad of the equipment to different functions. 2.07 OPERATING SEQUENCES

A. Acceleration and Deceleration: 1. The VFC shall be capable of smooth motor start and stop by controlling acceleration and deceleration ramps. 2. As a minimum the VFC shall be capable of the following adjustable ramps shapes: a. Linear, S shaped, U shaped. 3. Duration of the ramps shall be factory set up at 3 s, and shall be site adjustable from 0.1 to 1800 (resolution 0.1s). 4. For precise load performance, the VFC shall include the possibility to dynamically change the ramp shape through logic input or frequency threshold. Adaptation of ramp times shall be automatic in the event of exceeding available braking torque. B. Breaking to Standstill from Low Speed 1. For all VFDs, the braking shall be automatic by DC injection for 0.5 s when frequency passes below 0.1 Hz. 2. The following shall be site adjustable from the keypad of the equipment: a. Level of current b. Frequency threshold, c. Injection time. C. Automatic current limitation: 1. The VFC shall include a feature to adapt the current limitation according to the thermal characteristics of the motor to avoid nuisance tripping.
WB4733 Al Ghurair City Expansion Phase II 16269 April 2008 Rev - 0 Variable Frequency Controllers. Page 7 of 10

D. Skip frequencies: 1. It shall be possible to program 3 preset frequency to be skipped by the VFC, so that they will not be applied to the motor (protection against mechanical resonance). E. Type 2 Co-Ordination: 1. The VFC starter panel should have a bypass starter with type 2 co-ordination as per relevant IEC standard and selection of Circuit breaker and line contactor should be accordingly. F. Enclosure : 1. The VFC shall be located inside the motor Control Center as shown with the following specification. 2. In case it has to be located outside the following details shall be followed. 3. The VFC along with associated components like Circuit breaker, semi conductor fuses, line contactor, indicating lights, push button, Auto-manual selector switch to configure with BMS system and other necessary wiring and terminations, should be enclosed in a sheet steel enclosure suitable for VFC application. The enclosure should have sufficient ventilations for proper heat dissipation.

WB4733 Al Ghurair City Expansion Phase II

16269 April 2008 Rev - 0

Variable Frequency Controllers. Page 8 of 10

PART 3 3.01

EXECUTION

EXAMINATION

A. Examine areas, surfaces, and substrates to receive VFCs for compliance with requirements, installation tolerances, and other conditions affecting performance. B. Examine roughing-in for conduit systems to verify actual locations of conduit connections before VFC installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.02 APPLICATIONS

A. Select features of each VFC to coordinate with ratings and characteristics of supply circuit and motor; required control sequence; and duty cycle of motor, Controller, and load. B. Select rating of controllers to suit motor controlled. 3.03 INSTALLATION

A. Anchor each VFC assembly to steel-channel sills arranged and sized according to manufacturer's written instructions. Attach by bolting. Level and grout sills flush with VFC mounting surface. B. Install VFCs on concrete bases. C. Control Fuses: Install fuses in each fusible switch. 3.04 IDENTIFICATION

A. Identify VFCs, components, and control wiring according to Section 16010. B. Operating Instructions: Frame printed operating instructions for VFCs, including control sequences and emergency procedures. Fabricate frame of finished metal, and cover instructions with clear acrylic plastic. Mount on front of VFC units. 3.05 CONTROL WIRING INSTALLATION

A. Bundle, train, and support wiring in enclosures. 3.06 CONNECTIONS

A. Ground equipment.

WB4733 Al Ghurair City Expansion Phase II

16269 April 2008 Rev - 0

Variable Frequency Controllers. Page 9 of 10

B. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. 3.07 FIELD QUALITY CONTROL

A. Prepare for acceptance tests as follows: 1. Test insulation resistance for each VFC element, bus, component, connecting supply, feeder, and control circuit. 2 Test continuity of each circuit. B. Testing: Perform the following field quality-control testing: 1. Perform each electrical test and visual and mechanical inspection stated in NETA ATS, Sections 7.5, 7.6, and 7.16. Certify compliance with test parameters. 2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest. C. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment installation, including pretesting and adjusting VFCs. D. Test Reports: Prepare a written report to record the following: 1. Test procedures used. 2. Test results that comply with requirements. 3. Test results that do not comply with requirements and corrective action taken to achieve compliance with requirements. 3.08 STARTUP SERVICE

A. Engage a factory-authorized service representative to perform startup service. B. Verify that electrical wiring installation complies with manufacturer's submittal and installation requirements in Division 16 Sections. C. Complete installation and startup checks according to manufacturer's written instructions. 3.09 ADJUSTING

A. Set field-adjustable switches and circuit-breaker trip ranges. 3.10 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain VFCs.

END OF SECTION
WB4733 Al Ghurair City Expansion Phase II 16269 April 2008 Rev - 0 Variable Frequency Controllers. Page 10 of 10

You might also like