SECTION 16511 INTERIOR LIGHTING PART 1 - GENERAL

Read and conform to all electrical sections of these specifications,the general instructions for electrical division, section 16010, apply to and form part of all electrical sections. These shall be read in conjunction with design drawings. 1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply to this Section. Requirements of all relevant sections of Division 16 apply to this section. B. ID & Electrical lighting layout drawings. 1.02 SUMMARY

A. Installation, coordination, testing and commissioning of various light fixtures as described in the schedule of light fixtures and as shown on the electrical lighting layout drawings and related typical installation drawing including all fixings , accessories, ceiling roses/socket outlets, heat resistant flexible cables for final connections and terminations. B. Coordinate with other Divisions to ensure the correct location and installation of the plaster frames and rings. C. This Section includes lighting fixtures, lamps, ballasts, emergency lighting units, and accessories. D. Provide 5% spare lamps for all of fixtures (minimum 2 Nos. for each type). E. CODES AND STANDARDS CIBSE BS 7671 BS 7430 BS 6141 Lighting Guides Requirements for electrical installation. Earthing system Insulated cables and flexible cords for use in high temperature zones.

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 1 of 11

1.03

SUBMITTALS

A. General: Submit the following in accordance with Conditions of Contract and Division 1 Specification Sections. B. Product data describing fixtures, lamps, ballasts, and emergency lighting units. Arrange product data for fixtures in order of fixture designation. Include data on features and accessories and the following information: 1. Outline drawings of fixtures indicating dimensions and principal features. 1.04 QUALITY ASSURANCE Design, manufacture, testing and method of installation of all apparatus and materials furnished under requirement of these specification shall conform to latest publications or standard rules of the following: a) DEWA regulations for electrical installation works b) Regulations for Electrical equipment of building IEE, BS London c) British Standards. A. The Quality Control/Quality Assurance duties shall be performed by the Contractor. The system of quality control verification shall be in accordance with ISO 9000 standards of quality assurance.

B. Manufacturers Qualifications: Firms experienced in manufacturing fixtures that are similar to those indicated for this Project and that have a record of successful in-service performance.

C. Lamps Manufacturers : 1. General Electric 2. Osram 3. Philips

USA Germany Holland

Lamps of one type to be supplied from one manufacturer and from the same production run.

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 2 of 11

PART 2 - PRODUCTS 2.01 FIXTURES:

A. Lighting fixtures schedule shall be as shown on Luminaire schedule( Back Of House Only).Refer separate specifications issued by ID designer for Front of House. B. All luminaires shall carry ENEC certification or approved equivalent certification as appropriate. C. All luminaries shall be fully compliant with relevant codes, related reports and codes of practices prevalent in the industry. D. Luminaires shall generally be IP 20 if located indoor within the buildings and IP 65 (Weather proof) when located in external out door location, however if instructed otherwise to suit any specific requirement it shall be binding on the contractor to comply accordingly. E. All external luminaire must be suitable to operate at 50C ambient and must be anti- corrosive. F. Pertaining to specific requirements on flame propogation & flammability of transluscent covers, contractor shall be liable to provide material test certificates adhering to BS 2782. G. SCHEDULES: 1. LUMINAIRES SCHEDULE (Back of house areas-BOH)

Lumi n Code AE

Luminaries Picture

Locations

Lamp

Color Temp 3500 K

Description

Staircase

1X28W TCDDEL

IP65 1X28W surface mounted fitting with TC-DDEL HF compact fluorescent fitting, HF Electronic, integral emergency gear with polycarbonate body & opal polycarbonate diffuser

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 3 of 11

B1

Toilets

2X26W TCDEL

3500 K

B1E B3

Toilets WC Cubicles 1X26W TCDEL 2X36 T26 3500 K

2X26 W Recessed Horizontal Down lights with compact fluorescent TC-Del lamps body of die cast Aluminum, ceiling ring white polycarbonate, reflector of semi matt aluminum with silver anodized finish Ballast of COM HF same as Thorn Corsa 245 or approved Equivalent Ditto as B1 but with Emergency version Ditto as B1 but 1X26W lamp

F1

Car park/ Plant rooms

4000 K

F1E F4 Offices 4X18W T16 4000K

F8

Stores

1X36W T26

4000 K

F8E

IP 65 2X36W Fluorescent Fitting with injection moulded polycarbonate body & acrylic diffuser with 2xT 26 HF Lamp, HFG Control Gear and HF Ballast same as Siteco Monsun or approved Equivalent Ditto as F1 but with Emergency version 4X18W recessed modular fluorescent luminaire(T 16) white painted steel body reflector-Aluminum louver in mirrorbite Finish with Electronic Ballast same as Thorn Omega T8 or approved Equivalent IP65 1X36W Fluorescent Fitting with injection moulded polycarbonate body & acrylic diffuser with T26 HF Lamp, HFG control Gear & HF Ballast same as siteco Monsun or approved equivalent Ditto but with Emergency version

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 4 of 11

EXIT

Emergency Escape route

1X8W T5

Corridors/ Offices/

1x8W T5 Lamps

Maintained type Exit sign luminaries with single/double sided legend. Slim brushed Aluminum modular base, polycarbonate diffuser, Same as egress maxi of whitecroft or approved equivalent 1X8W Emergency non Maintained type polycarbonate diffuser, high impact polycarbonate body same as white croft Sentry or approved equivalent IP65 Optical Round Bulk Head with Visor body of Poly carbonate bowl Enclosure, wall Mounted as Thorn Roller 96009900 or Equivalent

Roof/ Terrace

1x75W A60 RD SIL VS

Flood Lights on Roof

1X250 W HIT

IP65 floodlight with gear & optical compartiments, black technopolymer body, flat glass enclosure, Al textturebrite symmetric reflector, magnetic MAG ballast same as Thorn PRT A41 or equivalent.

Mirror Lights

1x14 W T16 Lamp

IP44 Slim & Aesthetic Luminaries with Electronic Ballast, body in white finished extruded Aluminum end caps in white finish die cast Aluminum & diffuser in opal polycarbonate same as thorn Cimi or approved equivalent

2. LUMINAIRES SCHEDULE (Front of house areas-FOH) Refer separate document for Lighting schedule issued by ID

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 5 of 11

2.02 A. B. C. D.

BALLASTS

Ballasts shall be approved by internationally accredited laboratories . Ballasts shall have sound rating A unless indicated otherwise. All ballasts shall be High frequency, High power factor type. All ballasts part of the luminaries controlled through intelligent lighting control system and interfaced with BMS shall be digital addressable type. E. Ballast voltage shall be as required by circuit connection shown on drawings. F. The manufacturer of the fluorescent ballasts shall provide a full 5-year manufacturers warranty. FLUORESCENT BALLASTS Ballasts for tubular fluorescent fixtures shall be suitable for their specific use suiting to type of luminaire and its lighting control methodology as per design intent as shown on the drawing including ID lay outs. .1 These shall be of Digital addressable type, Electronic type or low loss no noise, high power factor and high frequency type to Engineers approval unless instructed or shown otherwise. Total harmonic distortion shall not exceed 15%. Lamp current crest factor shall not exceed 1.6. Ballast shall comply with all relevant European standards: BS EN 60920, 60921 BS EN 60924, 60925 for d.c supplied electronic ballasts. BS EN60928, 60929 for fluorescent lamp to BS 1853 Part 1 (EN 60081) BS 6982 (EN 60901) Supply thermal protectors where necessary for lamps to BS 60730-2-3 H.I.D. BALLASTS .1 Ballasts shall be totally encapsulated, constant voltage, regulated output type, matched to their respective lamp. Ballasts: BS EN 60922 & BS EN 60923 Starters: BS EN 60926 & BS EN 60927

.2 .3 .4

2.03

LAMPS a. b. Tungsten Filament Lamps : BS 161 (EN 60064), BS 5971 (EN 60432) & BS6179 Fluorescent Lamps: 1.Tubular lamps (Intl specs) to BS EN 60081,

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 6 of 11

(UK) to BS 1863 Part-2 2.Self ballasted lamps to BS EN 60968(BS 7173) BS EN 60969(BS 7199) 3.Single capped lamps to BS EN 60901, 61199 c. Sodium Vapour Lamps: 1.High pressure 2.Low pressure BS EN 60662 BS EN 60192

A. All lamps shall be Triphosphere type in general. The lumen output shall be the highest available in that category from the proposed manufacturers range. B. Fluorescent lamps shall be warm white and of good colour rendering index as approved by Engineer. C. Guidance Data: Following lamp data is for guidance only & subject to Engineers acceptance & approval. 1. INCANDESCENT: .1 Standard A shape bulb, medium base, inside frosted, 2000 h life, 230 V. Reflector R shape bulb, medium base, inside frosted, 2000 h life, 230V. Parabolic aluminized reflector PAR shape bulb, medium skirted base, clear, 2000 h life, spot or flood, as required, 240V.

.2

.3

2.

TUNGSTEN HALOGEN: .1 PAR shape bulb, medium base, 240 V, 2000 h life, 50W or 75W, narrow spot, spot or flood, as required.

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 7 of 11

.2

PAR shape bulb, medium skirted base, 240 V, 4000 h life for 150W, 6000 h life for 250W, spot or floor, as required. PAR shape bulb, mogul end prong, 240V, 4000 h life for 500W, spot or flood, as required. T4 shape, clear bulb, single ended mini-can base, 240V, 2000 h life, 250W, 5000 lms, 500W 10,000 lms. T3 shape, clear bulb, double ended RSC base, 240V, 500W, 2600 h life, 10,000 lms, 1000W, 2000 h life, 21,500 lms. Low voltage halogen reflector lamps 12V, with integral front glass and metal bayonet cap, with the following light reflector systems: 6433 6o 20W 6434 13o 20W 6435 32o 20W 6465 6o 50W 6438 10o 50W 6439 25o 50W

.3

.4

.5

.6

3.

FLUORESCENT: .1 High efficiency 26 mm dia. Tube, 15,000 h life, with the following minimum initial lumens: Triphosphate 18W 1450 LUMENS 3500oK 600 mm Long Triphosphate 30W 2400 LUMENS 3500oK 900 mm Long Triphosphate 36W 3450 LUMENS 3500oK 1200 mm Long Triphosphate 58W 5400 LUMENS 3500oK 1500 mm Long .2 Halophosphate 18W 1225 LUMENS 3500oK 600 mm Long Halophosphate 30W 2300 LUMENS 2500oK 900 mm Long Halophosphate 36W 3000 LUMENS 3500oK 1200 mm Long Halophsphate 58W 4800 LUMENS 3500oK 1500 mm Long

4.

COMPACT FLUORESCENT: .1 Single end pin, 10,000 h life, with the following characteristics: 10W 600 LUMENS PLC 10W/3000oK 13W 900 LUMENS PLC 13W/3000oK 18W 1200 LUMENS PLC 18W/3000oK 26W 1800 LUMENS PLC 26W/3000oK

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 8 of 11

10W 600 LUMENS PL L40/3000oK

5.

HIGH PRESSURE SODIUM: .1 1000W, E-25 shape bulb, Mogul base, clear, 24,000 h life, 14 KIL, 12.6 KML. 400W, E-18 shape bulb, Mogul base, clear, 24,000 h life, 50 KIL, 45 KML. 250W, E-18 shape bulb, Mogul base, S, clear, 24,000 h life, 30 KIL, 27 KML. 150W, E-17 shape bulb, Medium base, clear, 24,000 h life, 16 KIL, 14.4 KML. 100W, E-17 shape bulb, Medium base, Med., clear, 24,000 h life, 9.5 KIL, 8.55 KML. 70W, E-17 shape bulb, Medium base, Med., clear, 24,000 h life, 5.8 KIL, 5.22 KML. 50W, E-17 shape bulb, Medium base, clear, Med., 24,000 h life, 4.0 KIL, 3.6 KML. 35W, E-17 shape bulb, Medium base, Med., clear, 16,000 h life, 2.25 KIL, 2.025 KML.

.2

.3

.4

.5

.6

.7

.8

6.

METAL HALIDE Multi-Vapour II .1 .2 .3 .4 175W, E-23 shape bulb, Mogul base, diffuse coated, 10,000 h life, 16.6 KIL, 13.3 KML. 250W, E-28 shape bulb, Mogul base, diffuse coated, 10,000 h life, 20.5 KIL, 16.0 KML. 400W, E-37 shape bulb, Mogul base, diffuse coated, 20,000 h life, 36.0 KIL, 27.7 KML. 1000W, BT56 shape bulb, Mogul base, diffuse coated, 12,000 h life, 105.0 KIL, 79.8 KML.

7.

MERCURY LAMPS: .1 .2 .3 75W, E17 shape bulb, Medium base, Deluxe white, 16,000 h life, 2.8 KIL, 2.25 KML. 100, E23 shape bulb, Medium base, Deluxe white, 24,000 h life, 4.2 KIL, 3.2 KML. 125W, E23 shape bulb, Medium base, Deluxe white, 24,000 h life, 6.35 KIL, 2.25 KML.
16511 April 2008 Rev - 0 Interior Lighting. Page 9 of 11

WB4733 Al Ghurair City Expansion Phase II

.4

175W, E28 shape bulb, Medium base, Deluxe white, 24,000 h life, 8.6 KIL, 7.2 KML. 250W, E28 shape bulb, Medium base, Deluxe white, 24,000 h life, 12.1 KIL, 9.8 KML. 400W, E37 shape bulb, Medium base, Deluxe white, 24,000 h life, 22.5 KIL, 12.8 KML. 1000W, BT56 shape bulb, Medium base, Deluxe white, 24,000 h life, 63.0 KIL, 40.0 KML.

.5

.6

.7 Notes:

All lamps shall be supplied from an approved manufacturer. .1 .2 .3 .4 .5 Refer to Luminaire Schedule for lamp requirement. Install lamps only after luminaires have been cleaned. Ensure that all lamps are suitable for luminaires before energization. Ensure that lamps are of the type specified, and report any discrepancies to the Engineer. Provide 5% spare lamps for each and every type used. These lamps are to be handed over to the Engineer on completion of contract.

2.04 A. B. C. 2.05

STARTERS Starters shall be Deos type or equal. To be selected in conjunction with respective lamp & Ballast. BS EN 60926 & BS EN 60927 compliant for Discharge lamps. CAPACITORS Appropriate capacitors complying with BS EN 61048 & 61049, in high pressure mercury, Low pressure sodium vapour and tubular fluorescents lamping circuits.

2.06

CONTROL GEAR Control gears shall be in accordance with specifications & the approved manufacturers recommendation as may be the case for integral or remote gear. In case of remote gear it should generally be housed in appropriately IP rated, lockable sheet steel housing distanced with in the manufacture recommended limits from the lamp.

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 10 of 11

PART 3 - EXECUTION 3.01 A. B. INSTALLATION Submit method statement for installation and testing of lights based on final selection of lighting luminaries. Submit complete details of lighting controls and required interfaces.

C. Setting and Securing: Set units plumb, square, and level with ceiling and walls, and secure according to manufacturer's printed instructions and approved shop drawings. D. Install support clips for recessed fixtures, securely fastened to ceiling grid members, at or near each fixture corners. E. Provide plug in ceiling roses for all lights mounted in a suspended ceiling. Location of plug in ceiling rose shall be above ceiling such that it is accessible from the opening of the ceiling. Roses that are too high or concealed by ducts etc. will not be accepted. F. Support for Suspended Fixtures: Brace pendants and rods that are 4-feet long or longer to limit swinging. Support stem mounted single-unit suspended fluorescent fixtures with twin-stem hangers. For continuous rows, use tubing or stem for wiring at one point and tubing or rod for suspension for each unit length of chassis, including one at each end. G. Lamping: Lamp units according to manufacturer's instructions. 3.02 FIELD QUALITY CONTROL Replace damaged fixtures and

A. Inspect each installed fixture for damage. components. 3.03 ADJUSTING AND CLEANING

A. Clean fixtures upon completion of installation. Use methods and materials recommended by manufacturer. B. Adjust amiable fixtures to provide required light intensities.

END OF SECTION

WB4733 Al Ghurair City Expansion Phase II

16511 April 2008 Rev - 0

Interior Lighting. Page 11 of 11