AHMEDABAD Ph: 7414192 Email: Date: 01/02/2010 DOCUMENT : GRID EARTHING jptechnosoft@gmail.com CALCULATION RESULT SHEET(IEEE-80)

PROJECT :SIEMENS
Design ID 3Io Sf Df tc V G ts M.F. =

2
Symmetrical Earth Fault Current Fault Current Diversion Factor Fault Current Decrement Factor Earth Fault Clearing Time System Voltage System Grounding Shock Duration Multiplying Factor For Future Soil Resistivity Surface Resistivity Grid Length Grid Width Depth of Burial Surface Thickness No. Of Earth Pits Depth Of Earth Pit Earth Electrode Dia. Ambient Temperature Shape Of Electrode =

Revision No = = = = = = = = = = = = = = = = = =

R0

INPUT DATA : All nomenclature as per Table-12, IEEE-80, 2000


= = = = = = = = s Lg Wg h hs n l d Ta = = = = = = = = =

40.000 kA 1.0000 1.0000 1.0000 Sec 132.00 kV SOLID 0.5000 Sec 1.0000 40.000 Ohm-Mtr 2500.0 Ohm-Mtr 142.00 Mtr 74.000 Mtr 600.00 mm 100.00 mm 20.000 3.0000 Mtr 45.000 mm 50.000 o C
o

MATERIAL DATA :
Material = r Tm TJ CA B Ko AlphaR SH SW = = = = = = = = =

STRIP 20.000
= = = = = = = = = = C o

STEEL

Reference Temp. =

Resistivity at 20 Degree C Max Material Temperature Type Of Joint Corrosion Allowance Volumetric Heat Capacity Reciprocal of Temp. Co-efficient of Resistivity at 0 Degree C. Temp. Co-efficient of Resistivity at Ref. Temp. Specific Heat Capacity Specific Weight Thermal Co-efficient of Resistance at 0 Degree C.

15.000 MicroOhmCm 620.00 WELDED 10.000 % 0.0044 J/C mm 218.10 0.0042


o o C 3 C

0.1140Cal/Grm/C 7.8600Grm/cm 0.0065


3

AlphaZero = Page 1/3

Developed By : www.jptechnosoft.com

JP TECHNOSOFT
AHMEDABAD Ph: 7414192 Email:jptechnosoft@gmail.com Date: 01/02/2010 DOCUMENT : GRID EARTHING CALCULATION RESULT SHEET(IEEE-80)

PROJECT :SIEMENS
Sheet No

Revision No

R0

CALCULATION :
IG Asw TCAP S = Fault current for Design = Grid Area = = 3Io*Sf*Df Lg * Wg = 40.000 Mtr 2 =

10508 Mtr 2
(40)

3o = Thermal Capa. per Unit Volume = 4.184*SH*SW = 3.7490 J/cm / C = Conductor Area Required = IG * 1 TCAP * 10 r Actual Area after Corriosion Allowance = Required Ln = 454.93 sqmm

(37)

\ tc*AlphaR*
=

[ ]
Ko+Tm Ko+Ta = 500.42 sqmm

Grid Conductor Selected NL NW Lc LR LT LS = Length Wise Cond. = Width Wise Cond. = Conductor Length

75 X 10 MM

STRIP 36.000 Nos


= 19.000 Nos

= (NLxWg)+(NWxLg)+Lp

= 5794.0 Mtr = 60.000 Mtr = 5854.0 Mtr = 4396.5 Mtr

= Total Length of ground rod = Total Length of Conductor = 0.75 Lc + 0.85 LR

FACTORS :
km = 1 2*PI D*D (D+2h) h 1 + + 2/n \ 1+h/h 8Dd 4d ) (2n) [ (16hd Ln
eq eq eq

Ln

8 PI(2n-1)

(81)

= ks = = ki = 1 PI

0.4335

1 1 + + D+h 2h

1 n-2 (1-0.5 ) D

]
n c x n d

(94)

0.4140
0.644 + 0.148 n, Where n=na x n b x
(84-89)

= Kh = = Cs = = Page 2/3

4.7189
\(1+h/ho)

na = 2 Lc/Lp nb = Lp /(4x Asw) \ \ nc = n d = 1.0


(83)

1.2649
1 - 0.09 (1- / s) ] [ (2*hs+0.09)
(27)

0.6946
Developed By : www.jptechnosoft.com

JP TECHNOSOFT
AHMEDABAD Email: DOCUMENT : GRID EARTHIN jptechnosoft@gmail.com CALCULATION RESULT SHEET(IEEE-80) Ph:7414192 Date: 01/02/2010

PROJECT :SIEMENS
Sheet No

Revision No

R0

RESULT:
Conductor Spacing Grid Conductor Size Grid Resistance D = =

4.0000 Mtr
75 X 10 MM MM 1 h 20 1000 LgWg \ )))

1 1 ( 1 +( ) Rg = (( )+( LT 20LgWg 1+ \ =

0.1791 Ohm
Ig * Rg

(52)

Grid Potential Rise (GPR)

= =

7164.6027 Volt
(1000 + 1.5 Cs * \ ts s ) * 0.116
(32)

Touch Tolerable Potential Et 50 = = Step Tolerable Potential Es 50 = =

591.3675

Volts
(29)

(1000+6*Cs * s) * 0.116 \ ts

1873.3239
(

Volts
(29)

Mesh Potential

Emd = = (

* Km * Ki * IG * 1000) LM

559.1487

Volts
(29)

Step Potential

Esd = =

* Ks * Ki * IG * 1000) LS

711.0334

Volts

Remark: 75x10 STRIP, 20 EARTH PITS

Note :The number in bracket at right indicates Equation NO as per IEEE80-2000 Page 3/3 Developed By : www.jptechnosoft.com