You are on page 1of 16

✱ 074-SF-6A

YC✱
Library Service Literature

SERVICE Product Section


Product
Model
Unitary
Rooftop
YC✱

FACTS
Customer Property — Contains wiring and
Literature Type
Sequence
Date
File No.
Service Facts

January 1996
SV-UN-RT-YC✱074-SF-6A 1/96
6A

service information. Please retain.


Supersedes New

Models:
YCD074C4L0BE, ABE,BBE, CBE, FBE, GBE,
Packaged Cooling/Gas Heat
YCH074C4L0BE, BBE, FBE
YCD074C4H0BE, ABE, BBE, CBE, FBE, GBE
6 Tons-Downflow & Horizontal
YCH074C4H0BE, BBE, FBE
Micro-Electronic Controls
IMPORTANT NOTE: This unit is Table 2 - Product Specifications
equipped with advanced electronic RATED VOLTS / PHASE / HZ 208-230 / 3 / 60 Outdoor Fan - Type Propeller
controls which provide convenient A.R.I. Ratings CFM 4100
Cooling (1) No. Used / Dia. 1 / 24
service functions significantly different Net Capacity (BTUH) 68,000 Type Drive / No. Speeds Direct / 1
Indoor Air Flow (CFM) 2500 CFM No. Motors / HP 1 / 0.25
from conventional units. Refer to your System Power (KW) 6.8 Motor Speed R.P.M. 850
service literature carefully when EER (BTU per Watt) (2) 10.0 Volts / Ph / Hz 208-230 / 1 / 60
Heating (3) F.L. Amps / L.R. Amps 2.0 / 5.3
performing service or maintenance. Input BTUH (Low Heat) 120,000 INDOOR FAN–Type FC Centrifugal
Output BTUH (Low Heat) 97,000 No. Used / Dia. x Width (In.) 1 / 12.6 x 9.5
1st Stage Input BTUH (High Heat) 150,000 Drive / Speeds (No.) Belt / 1
Output BTUH (High Heat) 122,000 No. Motors / HP
2nd Stage Input BTUH (7) 205,000 Standard Motor 1 / 1.0
Table 1 - Contents Output BTUH 166,000 Oversize Motor 1 / 2.0
Temp. Rise - Min. F (L/H) 25 / 35 Motor Speed R.P.M. 1725
Page Temp. Rise - Max. F (L/H) 55 / 65 Volts / Ph / Hz 208-230 / 3 / 60
Type of Gas (4) Natural F.L. Amps / L.R. Amps
Contents .......................................... 1 POWER CONNS —V / PH / HZ 208-230 / 3 / 60 Standard Motor 5.9 / 32.2
Table 2 - Product Specifications ...... 1 Min. Circuit Ampacity (6) Oversize Motor 8.8 / 53.0
Table 3 - Optional Equipment .......... 2 Standard/Oversize Motor 35.2 / 38.1 COMBUSTION FAN - Type Centrifugal
Fuse Size - Max. (Amps) 50 No. Used 1
Sequence of Operation ................... 2 COMPRESSOR Drive/No. of Speeds (L/H) Direct 1/2
Unit Start-Up ................................... 2 No. Used 1 Motor HP / RPM (Low) 1/20 / 3350
Cooling Operation/Mechanical Volts/Ph/HZ 200-230 / 3 / 60 (High) 1/20 / 3000-3500
R.L. Amps 21.8 Volts / Ph / Hz 208-230 / 1 / 60
Compressor Cycle .......................... 2 L.R. Amps 118.0 F.L. Amps / L.R. Amps 0.4 / 1.4
Cooling Operation/ OUTDOOR COIL — TYPE Hi-Performance FILTER Furnished
Economizer Cycle ........................... 2 Rows / F.P.I. 2/16 Type Throwaway
Face Area (Sq. Ft.) 11.32 Filters Size 16 x 25 x 1
Continuous Fan Operation .............. 3 Tube Size (In.) 0.375 Quantity 3
Heating Operation/Gas Heat ........... 3 INDOOR COIL–Type Hi-Performance REFRIGERANT
Ignition Control Module Diagnostic . 3 Rows / F.P.I. 3/15 Charge (Lbs. of R-22) (5) 10.0
Operating Pressures Curves ........... 5 Face Area (Sq. Ft.) 7.88 GAS PIPE SIZE (In.) 1/2
Tube Size (In.) 0.375 DIMENSIONS HxWxL
Superheat Charging Chart .............. 5 Refrigerant Control Short Orifice Crated (In.) 39.0 x 54.5 x 89.7
Connection Diagram (Low Heat) ..... 6 Drain Conn. Size (In.) 3/4" NPT WEIGHT (Approx. Lbs)
Connection Diagram (High Heat) .... 8 Shipping / Net 956 / 767
Footnotes:
Power Schematic .......................... 10 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb and
Control Schematic ......................... 12 nominal cfm listed. ARI capacity is net and includes the effect of fan motor heat. Rated in accordance
Refrigerant Circuit Diagram .......... 14 with ARI Standard 210.
2. Rated at ARI conditions and in accordance with DOE test procedures.
3. Heating performance limit settings and rating data were established and approved under laboratory
test conditions using American National Standards Institute standards. Ratings shown are for elevations
up to 2000 feet.
4. Convertible to LP gas with orifice change.
5. Refrigerant charge shown is a nominal value; for a more precise value see the unit nameplate.
6. Values do not include power exhaust accessory.
7. Applies to High Heat models only.


! WARNING: HAZARDOUS VOLTAGE-DISCONNECT POWER BEFORE SERVICING
Failure to DISCONNECT SAFETY NOTICE RE-CONNECT
This information is intended for use by individuals ALL GROUNDING DEVICES
POWER before servicing possessing adequate backgrounds of electrical and
All parts of this product capable of conducting
could lead to severe personal mechanical experience. Any attempt to repair a central air electrical current are grounded. If grounding wires,
conditioning product may result in personal injury and/or prop- screws, straps, clips, nuts or washers used to
injury or death. erty damage. The manufacturer of seller cannot be respon- complete a path to ground are removed for
sible for the interpretation of this information, nor can it as- service, they must be returned to their original
sume any liability in connection with its use. position and properly fastened.

Notice: Since the manufacturer has a policy of continuous product improvement,


it reserves the right to change specification and design without notice. Page G-938-658
Table 3 - Optional Equipment 2) Cooling Operation/Mechanical
Compressor Cycle
Manual Change-over T’stat - Single Stage . ASYSTAT661B (For cooling without economizer operation)
Auto Change-over T’stat - 2 stage .............. ASYSTAT663B
Programmable T’stat ................................... ASYSTAT666A Note: The compressor is controlled to a minimum run
Stand Alone Unoccupied Timer ................... BAYCLCK001A time of three minutes, and once shut off will not start
Conventional T’stat Interface - again for three minutes.
Field Installed ........................... BAYCTHI001C
Roof Curb .................................................... BAYCURB022B Cooling Sequence—When mechanical cooling is
Clogged Filter Switch .................................. BAYDFPS001A required, the UCP energizes the Compressor Contactor
Fan Failure Switch ...................................... BAYDFPS002A (CC1) coil. When the CC1 contacts close, the
I/O Expansion Board ................................... BAYDIAG001A Compressor CPR1 and Outdoor Fan Motor (ODM)
Manual Outside Air Damper ........................ BAYDMPR029B start. CPR1 cycles on and off as required by cooling
Power Fresh Air .......................................... BAYDMPR045B demands, but within the time minimums mentioned
Economizers - (Downflow) .......................... BAYECON068B above.
Horizontal ................................. BAYECON070B
Without Controls for YCD ......... BAYECON072B Defrost Cycle in Cooling Mode
Reference Enthalpy Control ........................ BAYENTH003A During periods of low outdoor air temperature, the UCP
Comparative Enthalpy Control .................... BAYENTH004A performs an evaporator defrost cycle. This cycle is
High Temperature Sensor ........................... BAYFRST001A performed at temperatures below 55° F after each 10
Coil Guard ................................................... BAYGARD023A minutes of accumulated compressor run time. During the
High Static Motor ........................................ BAYHSMT049A defrost cycle the compressor(s) is turned off and the
TCI Accessory ............................................. BAYICSI001B supply fan stays energized. After completion of the
Horizontal Insulation Kit .............................. BAYINSL101A defrost cycle, which lasts approximately three minutes,
Quick Start Kit ............................................. BAYKSKT007B the compressor is allowed to operate as required.
Propane Conversion Kit .............................. BAYLPKT023B
Sensor Mounting Plate ................................ BAYMTPL002A Indoor Fan Operation
Power Exhaust for YCD .............................. BAYPWRX013A If the indoor fan is set to “AUTO”, the UCP energizes the
Zone Sensor - Single Stage Manual T’stat . BAYSENS006B Indoor Fan Contactor (F) coil approximately one second
Zone Sensor - 2 Stage Auto T’stat .............. BAYSENS008B after energizing the compressor contactor. The Indoor
Zone Sensor w/LED - 2 Stage Auto T’stat .. BAYSENS010B Fan Motor (IDM) starts when contacts of F close. When
Zone Sensor w/Button ................................ BAYSENS013B the cooling cycle is complete and CC1 is de-energized,
Zone Sensor w/Button and Setpoint ........... BAYSENS014B the UCP keeps the F coil energized for 60 seconds of
Temperature Sensor ................................... BAYSENS016A additional IDM operation to enhance unit efficiency.
Remote Sensor
for Auto Change-over T’stat . BAYSENS017B 3) Cooling Operation/Economizer Cycle
Zone Sensor - Programmable ..................... BAYSENS019A The economizer option allows cooling with outdoor air
Digital Dual Man/Auto ................................. BAYSENS022A when outdoor ambient is below 60(±2)° F. (This setting is
Service Tester - Selective Resistance ......... BAYSERV001A field adjustable to 55 or 65° F). This air is drawn into the
Remote Sensor for Programmable T’stat .... BAYSTAT021 unit through modulating dampers. When cooling is
Remote Rheostat ........................................ BAYSTAT023 required and economizing is possible, the UCP signals
the Unitary Economizer Module (UEM) to open/close the
Sequence of Operation ventilation damper(s) by energizing the Economizer
Actuator (ECA). The UCP tries to cool the space to
slightly below the cooling set-point. If the Supply Air
These units are equipped with an electronic control board Sensor (SAS) senses that supply air is below 50° F, the
“Unit Control Processor (UCP)” which is the brain of the dampers modulate closed until supply air temperature
unit control system. This board contains powerful control rises, or until dampers close to their minimum position.
logic information that manages the functioning of the unit and
system. If a power exhaust accessory is present, the power
exhaust fan motor is energized whenever the economizer
Note: The time delays mentioned below are controlled damper is at a position greater than 25% of the actuator
by the UCP, and are present to increase system stroke.
reliability. They protect the compressor and maximize
efficiency of unit performance. During simultaneous economizing and mechanical
compressor cooling, the UCP continues to modulate the
1) Unit Start-Up ECA to keep the supply air temperature in the 50-55° F
Each time power is applied to the system, the UCP range. When economizing is not possible, dampers go to
performs internal self-diagnostic checks. It determines minimum position.
the system configuration (including installed options), and
prepares for control of this configuration. It also checks Settings - The economizer is opened to minimum
itself for proper internal functioning. Within one second of ventilation position by the UCP every time F is
start-up, the UCP system indicator (a red light on the UCP energized. The amount of ventilation air required is set
board) glows if programming is intact and functional. by adjusting the minimum position potentiometer located
on the Unitary Economizer Module (UEM).
On units with the optional economizer, the damper(s) is
driven open for 15-20 seconds, and then closed for
approximately 90 seconds. This assures proper damper
calibration.

2
4) Continuous Fan Operation Limit Controls
High Limit (TCO1) and Fan Fail Limit (TCO2) protect
If the indoor fan switch is set to “ON”, the UCP keeps the
against overheating if the IDM fails to operate. (TCO2)
F coil energized for continuous fan operation. On units
will signal the UCP that a failure has occurred. The UCP
with an optional economizer, the UCP also causes the
will de-energize K5, H, and IGN, and energize the F
Economizer Actuator (ECA) to move to its proper
coil. The UCP also signals the heat failure by flashing the
operating position at minimum position or greater.
“HEAT” LED on the zone sensor.
5) Heating Operation/Gas Heat TCO1 is located in the bottom right corner of the gas
When the space temperature falls below the heating set- valve/burner compartment. This automatic reset control
point, the UCP initiates a heating cycle by energizing the protects against abnormally high leaving air temperature.
relay (K5) coil, the heat relay (H) coil, the Ignition Control
Module (IGN)., and relay (S) coil when present. The H TCO2 is located in the upper middle section of the indoor
contacts close to energize the Combustion Fan Motor fan panel. This automatic reset control protects against
(CFM). On units with 2-speed switching fans (3 & 4 ton abnormally high heat build up, which could be caused by
high heat models), the K5 (for 208/230V units) or S relay extended cycling of TCO1, or failure of the IDM to
(for 460/575V units) also energize the high speed operate.
windings of the Indoor Motor (IDM). On two stage units,
the K5 contacts close to energize the high speed Ignition Control Module Diagnostic
windings of CFM. (After a 60 second delay, K5 is de-
energized to revert the CFM to its low speed windings.)
There are two LED’s located on the Ignition Control Module.
The IGN starts the ignition process by preheating the hot The Table below list the diagnostics and the status of the
surface Ignition Probe (IP) for 30 seconds. After preheat LED’s during the various operating states.
of the IP, the Gas Valve (GV) is energized up to 7
seconds to ignite the burner. When the gas lights, the IP LED Status
is de-energized and then functions as a flame sensor. Diagnostics Green LED Red LED
1. Powered with no call for heat Off Off
If the burner fails to ignite, the ignition module will attempt
two retries. At the start of each ignition retry, the green 2. Call for heat - no fault detected Flashing (1) Off
LED will flash and the red LED will flash for five seconds 3. No Flame signal on try for ignition Off Flashing (2)
before locking out. An IGN lockout can be reset by; or flame signal established and lost
prior to a lockout condition.
1. Opening and closing the main power disconnect 4. Gas Valve miswired or flame Continuous Flashing (1)
switch, signal present at a call for heat
5. Internal Fault - anytime. Off Continuous
2. By switching the “Mode” switch on the zone sensor to
“OFF” and then to the desired position. Notes:
1. Flash at a 50% duty cycle.
3. Allowing the ignition control module to reset 2. At the start of each retry for ignition the red LED will flash
automatically after one hour. Refer to the “Ignition Control for five seconds along with the green LED
Diagnostics” section for the LED diagnostic diffinitions.

If the fan is set to “AUTO”, the UCP energizes the Fan Table 4
Contactor (F) 30 seconds after initiation of the heat Static Pressure Drops Through
cycle. When the F contacts close, the IDM starts. For Economizers (Inches Water Column)
units with automatic 2-speed fan switching, the fan runs in
high speed. CFM Full Return* Full Outside
1600 0.01 0.07
For 2-stage Gas Heat units only 1700 0.01 0.08
If the space temperature remains below the heating set-
2000 0.01 0.10
point with stage 1 heat operating, the UCP energizes the
K5 coil. This activates the high speed windings of CFM 2100 0.01 0.10
supplying stage 2 heat capacity. 2400 0.02 0.12
2500 0.02 0.13
When the space temperature rises above the heating set-
point, the UCP de-energizes K5, H, and IGN, and S if
3000 0.03 0.15
present, turning off the heat functions. The F coil remains 3600 0.03 0.20
energized for 90 seconds after which it is de-energized, *For Power Fresh Air, “Full Return” is zero.
provided the fan mode is AUTO. If the fan mode is “ON”
and automatic 2-speed fan switching is present, the fan
returns to low speed.

To reset an IGN lockout, power must be removed from


IGN by switching the unit mode on the zone sensor to
“OFF” and then to the desired position.

3
Table 5
Evaporator Fan Performance

Fan Speed (RPM)


Motor
Sheave Standard High Static Low Static
Position Motor & Sheave Motor & Drive Sheave *
5 Turns Open 735 923 525
4 Turns Open 805 992 575
3 Turns Open** 875 1060 625
2 Turns Open 945 1129 675
1 Turns Open 1015 1197 725
Closed 1085 1265 775
* Field Supplied
** Factory setting is 3 turns open.

Table 6
Evaporator Fan Performance

External Static Pressure (Inches of Water)


0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.25 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor & Field Supplied
Low Static Drive (1)
2000 615 0.37 663 0.41 710 0.45 756 0.49 799 0.52 843 0.55 884 0.58 924 0.60 965 0.62 1006 0.62 — — — —
4

YCD Low & 2250 681 0.52 723 0.56 766 0.61 807 0.65 848 0.69 886 0.73 925 0.76 964 0.79 1000 0.82 1035 0.84 1126 0.90 1209 0.92
High Heat/ 2500 748 0.69 785 0.74 824 0.79 862 0.84 899 0.89 936 0.93 971 0.98 1005 1.02 1041 1.06 1075 1.09 1154 1.16 1237 1.22
YCH Low 2750 816 0.91 849 0.96 884 1.02 920 1.08 954 1.13 988 1.18 1021 1.23 1053 1.28 1084 1.32 1116 1.37 1195 1.46 1266 1.54
Heat 3000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1235 1.80 — —
1 HP Standard Motor & Sheaves 2 HP Oversized Motor & Sheaves

External Static Pressure (Inches of Water)


0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.25 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field Supplied
Low Static Drive (1) 1 HP Standard Motor & Sheaves
2000 680 0.45 738 0.50 794 0.55 846 0.63 894 0.63 947 0.67 1003 0.70 1055 0.72 — — — — — — — —
YCH 2250 751 0.63 804 0.69 853 0.74 903 0.80 949 0.84 992 0.88 1037 0.92 1086 0.97 1135 1.00 1181 1.03 — — — —
High Heat 2500 824 0.84 872 0.91 917 0.97 961 1.03 1006 1.09 1047 1.14 1085 1.19 1126 1.24 1167 1.28 1212 1.33 — — — —
2750 899 1.11 940 1.18 984 1.25 1023 1.32 1064 1.39 1105 1.45 1142 1.51 1178 1.56 1214 1.61 1250 1.66 — — — —
3000 974 1.42 1010 1.50 1051 1.58 1089 1.65 1124 1.73 1162 1.80 1200 1.88 1235 1.94 1268 1.99 — — — — — —
2 HP Oversized Motor & Sheaves
Notes:
Motor efficiency: 72%
Data includes pressure Drop Due to Wet Coils and Filters.
1. Field supplied Browning fan sheave AL74 and Belt A48 required.
Operating Pressures Curves
COOLING CYCLE PRESSURE CURVE
(Based on 2500 CFM Indoor Airflow)
FULL LOAD
450

86/72 F IN DB/WB
80/67 F ID DB/WB
74/62 F ID DB/WB
68/57 F ID DB/WB
400
DISCHARGE PRESSURE, PSIG

115 F OD Ambient

350
105 F OD Ambient

300 95 F OD Ambient

85 F OD Ambient
250
75 F OD Ambient

200 65 F OD Ambient

55 F OD Ambient

150
60 65 70 75 80 85 90 95 100 105 110
SUCTION PRESSURE, PSIG

To Check Operating Pressures


1. Start the unit and allow the pressures to stabilize. 5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure the indoor DB/WB temperature entering the indoor coil. onto the chart.
3. Measure the outdoor air dry bulb temperature 6. At the point of intersection, read down for the suction
4. Take discharge and suction pressure readings. pressure and to the left for the discharge pressure.

Superheat Charging Chart

Charts Based on Indoor Airflow of 400 CFM / Ton


40
To Determine Required Superheat -
A) Plot the Outdoor Temp onto the bottom axis of the curve.
B) Move vertically to the appropreiate indoor DB/WB temp. (or
interpolated temp)
C) At the point of intersection, (OD & ID) read horizontally to the left
COMPRESSOR SUPERHEAT, (O F)

30 for the required superheat.

20

O
86 / 72 ID DB / WB F
10

O O O
68 / 57 ID DB / WB F 74 / 62 ID DB / WB F 80 / 67 ID DB / WB F
0
50 60 70 80 90 100 110 120
OUTDOOR AMBIENT TEMPERATURE, DB (O F)

1) REFRIGERANT CHARGE - ADD if the superheat is more than 5O above curve value.
- REDUCE if the superheat is more than 5O below curve value.
- OK if the superheat is within 5O of curve value.
2) Do not add refrigerant if the superheat is less than 5O F
3) Curves are based on 400 CFM/Ton Indoor Airflow @ 50% R.H.
4) system must be running at stablized conditions before measuring superheat.

5
Connection Diagram (Low Heat)
2307-5592

6
7
Connection Diagram (High Heat)
2307-5594

8
9
Power Schematic
2307-5615
10
11
Control Schematic
2307-5583
12
13
Table 7
Gas Heating Data

Model: YC074C LOW HEAT HIGH HEAT


Heating Input Rate – BTUH 120,000 205,000
Minimum Gas Supply Pressure Natural 3.5” W.C.
(Entering Gas Valve) LP 8.0” W.C.
Gas Pressure Leaving Gas Valve-Manifold Pressure
(See Note 1) -0.2” W.C.
Combustion Blower Suction High Fire -2.1 to -3.1” W.C.
(With Gas Valve Closed) Low Fire N/A -0.8 to -1.2” W.C.
Minimum Flame Sensing Current 1.0 Microamps D.C.
(See Note 2)
Normal Sensing Current Range 1 to 8.0 Microamps D.C.
Flue Gas Temperature Rise Above Ambient @ Deg. F 350 to 525° 350 to 475°
Flue Gas Content - %CO2 Natural 8.3 to 9.5 8.0 to 9.0
LP 10 to 11 9.5 to 10.5
Minimum Supply Air Temperature Across
Heat Exchanger 40° F
Notes:
1. This Unit has a negative regulation gas valve. Never adjust gas
manifold pressure to a positive pressure.
2. A voltage reading across pens (V+) & (V-) is equatable to the flame
sensing current. One volt equals one micro amp.

Refrigerant Circuit Diagram

14
15
© American Standard Inc. 1996 Technical Literature Printed in USA

16

You might also like