No . 1110-3-174 9 April 1984
1. Purpose . This manual provides guidance for the design of gravity systems
for sanitary and industrial wastewater collection at U .S . Army mobilization
facilities .
~ 4 . ILA, ' -; .
~ <
Engineer Manual
9 April 1984
No . 1110-3-174
Paragraph Page
CHAPTER 1 . GENERAL
Paragraph Page
CHAPTER 1
GENERAL
CHAPTER 2
CHAPTER 3
(2) Average daily flow . The average daily flow will be computed
by multiplying the resident and nonresident contributing populations by
100 gallons per capita per day plus admissible daily flows from
commercial and industrial operations . The average daily flow will be
used only for designing sewers to serve the entire installation, or
large sections of the installation, and where a major portion of the
wastewater is generated by residents over a 24-hour period .
(90,000 gpd) . Note that the average daily flow would still be 30,000
gpd, or 30,000 gallons in 24 hours, but the sewer must be designed
hydraulically to carry the 30,000 gallons in 8 hours, not 24 hours .
r C
Q0 .167
where :
3-2
EM 1110-3-174
9 Apr 84
V = 1 .486 R 2 / 3 S 1/2
n
where :
V velocity in fps
n coefficient of pipe roughness
R hydraulic radius in feet, and
S slope of energy grade line in feet per foot
1 .0
1 .213
""/%ENO"
0.9
..
: " :
0.8
NSISTENT
MPAPHEI IANN
0
07 """""""""""" /
.%"""m""""~ 0
v
W
i
F- DISCHA W
W 0.6 H
W
Q a
0 0
0
05 0
x x
aW
11111momommmmmosommummmm
a
-
w
04 0
a
0 0
0 0
a Q3
I a
I """"""mu "mo"""""""""
0.2
HYDRAULIC PROPERTI~VS
0.1
"""""""""" CIRCULAR SEWERS
0 - r//""""""""""""
0 0.1 .2
0 0.3 0.5 0.6 0.7 0.8 0.9 1 .0 1 .1 1.2 1 .3
3- 5
EM 1110-3-174
9 Apr 84
3- 6
EM 1110-3-174
9 Apr 84
CHAPTER 4
4-1 . Manholes .
b . Spacing . The distance between manholes must not exceed 400 feet
in sewers of less than 18 inches in diameter . For sewers 18 inches in
diameter and larger, and for outfalls from wastewater treatment
facilities, a spacing of up to 600 feet is allowed provided the
velocity is sufficient to prevent sedimentation of solids .
e. Design standards .
4-2
EM 1110- 3-174
9 Apr 84
CHAPTER 5
2
Wt = CtwBt
where :
Wt = HwBc
where :
In the absence of soil density measurements, the weight per cubic foot
of various materials may be taken as 120 pounds . The load coefficient
Ct is a function of the fill height H divided by the width of trench
E14 1110-3-174
9 Apr 84
Wd = CspFBc
where :
The load coefficient C s is dependent upon the area over which the load
p acts . It will be selected from table 5-1 as a function of the area
width D and length M, each divided by twice the height of fill H . The
impact factor F will be determined with the use of table 5-2 .
We = CSPF/L
EM 1110-3-174
9 Apr 84
-1-1111111"11ii~~
Ct (GRAPH ON LEFT/.,
25
20 2
15
10
_ ~ 1 .0
x1ar
9
8 rljhI~I~11U~~ 0.9
0.8
7 0.7 x~m
0 6
t
W
J 5 0.5
3 -I 0.3
/
2 . ' ' .r
.:
Granularlar materials
Tj-F
IFNA
without cohesion
Sand and gravel 0.15
Saturated top soil
b Or dinary damp clay
Ct (GRAPH ON RIGHT) Saturated clay
0I10 0.15 0.20 0.25 0.30 0.40 0.50 0.6 0.7 0.80.9 1.0 1
VALUES OF COEFFICIENT Ct
M L
or
v 2H 2H
Br 0 .1 0 .2 0 .3 0 .4 0 .5 0 .6 0 .7 0 .8 0 .9 1 . 1 .2 1 .5 2 .0 5 .0
c
2H
0 .1 0 .019 0 .037 0 .053 0 .067 0 .079 0 .089 0 .097 0 .103 0 .108 0 .112 0 .117 0 .121 0 .124 0 .128
0 .2 0 .037 0 .072 0 .103 0 .131 0 .155 0 .174 0 .189 0 .202 0 .211 0 .219 0 .229 0 .238 0 .244 0 .248
0 .3 0 .053 0 .103 0 .149 0 .190 0 .224 0 .252 0 .274 0 .292 0 .306 0 .318 0 .333 0 .345 0 .355 0 .360
0 .4 0 .061 0 .131 0 .190 0 .241 0 .284 0 .320 0 .349 0 .373 0 .391 0 .405 0 .425 0 .440 0 .454 0 .460
0 .5 0 .079 0 .155 0 .224 0 .284 0 .336 0 .379 0 .414 0 .441 0 .463 0 .481 0 .505 0 .525 0 .540 0 .548
0 .6 0 .089 0 .174 0 .252 `J .320 0 .379 0 .428 0 .467 0 .499 0 .524 0 .544 0 .572 0 .596 0 .613 0 .624
0 .1 0 .097 0 .189 0 .274 5 .349 0 .414 0 .467 0 .511 0 .546 0 .584 0 .597 0 .628 0 .650 0 .674 0 .688
0 .8 0 .103 0 .202 0 .292 0 .373 0 .441 0 .499 0 .546 0 .584 0 .615 0 .639 0 .674 0 .703 0 .725 0 .740
0 .9 0 .108 0 .211 0 .306 0 .391 0 .463 0 .524 0 .574 0 .615 0 .647 0 .673 0 .711 0 .742 0 .766 0 .784
1 .0 0 .132 0 .219 0 .318 0 .405 0 .481 0 .544 0 .597 0 .639 0 .673 0 .701 0 .740 0 .774 0 .800 0 .816
1 .2 0 .117 0 .229 0 .333 0 .425 0 .505 0 .572 0 .628 0 .674 0 .711 0 .740 0 .783 0 .820 0 .849 0 .868
1 .5 0 .121 0 .238 0 .345 0 .440 0 .525 0 .596 0 .650 0 .703 0 .742 0 .774 0 .820 0 .861 0 .894 0 .916
2 .0 0 .124 0 .244 0 .355 0 .454 0 .540 0 .613 0 .674 0 .725 0 .766 0 .800 0 .849 0 .894 0 .930 0 .956
*Influence c=efficients for solution of Holl's and Newmark's integration of the Boussinesq equation for
vertical stress .
Source : Design and Construct 4 r~n of Sanitary and Storm Sewers - GRCF Manual of Practice No . 9 by Water
Pollution Control Federation, 1970, p . 206 .
EM 1110-3-174
9 Apr 84
where :
(2) The load factor is the ratio of the field support strength
to the three-edge bearing test and will be selected from figure 5-2
depending on the class of bedding used .
(4) The total load calculated in paragraph 5-2 must not exceed
the safe supporting strength .
5-5
EM 1110-3-174
9 Apr 84
1 .25 B OR
c
M
Bc + 8" MIN.
CAREFULLY "
PLACED 20 12" MIN .
BACR'FILL
ASTN D 448
NO . 67 CRUSHED
STONE OR OTHER
MATERIAL: Bc /4
CONCRETE Bc/4
4" MIN.
LOAD FACTORS 2 .8 PLAIN CONCRETE -WAD FACTORS 2 .8 PLAIN CONCRETE
3 .4 REINFORCED CONCRETE P-0 .4% 3 .4 REINFORCED CONCRETE P-0.4%
(TRANSVERSE STEEL) (TRANSVERSE STEEL)
12" MIN.
12" MIN .
ASTM D 448
NO . 67 CRUSHED
STONE OR OTHER
MATERIAL:
Bc/2
Bc/8 Bc/8
4" MIN .
4" MIN.
Bc/6 MIN
Bc/8
4" `, :
5- 6
EM 1110-3-174
9 Apr 84
b. Special rigid conduit testing . For piping not tested and rated
by the TEBT method, other strength criteria will be applied as follows .
Reinforced concrete pipe strength will be based on D-loads at the
0 .01-inch crack load and/or ultimate load as described in the ACPA
Concrete Pipe Handbook . For ductile iron pipe, ANSI A21 .50 will be
used to calculate the required pipe thickness classification in
relation to field loadings . The strength of cast iron soil pipe, which
normally will be used for building connections only, should be
evaluated as outlined in the CISPI Cast Iron Soil Pipe and Fittings
Handbook .
d. Pipe installation .
overexcavate native soil to just below the trench bottom and replace
with a layer of crushed stone, gravel, or other coarse aggregate .
Concrete or wooden cradles can be used in lieu of aggregates .
CHAPTER 6
- Physical strength .
6-5 . Concrete .
6-6 . Asbestos-cement .
6-3
EM 1110-3-174
9 Apr 84
6-4
EM 1110- 3-174
9 Apr 84
and has the same jointing as composite pipe . However, it does not
match the stiffness of composite pipe .
APPENDIX A
REFERENCES
Nongovernment Publications .