Energy Recovery Ventilator

Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Direct Drive Standard Construction Features. . . . . . . . . . . . . . . . . .3
Belt Drive Standard Construction Features . . . . . . . . . . . . . . . . . . .4
Construction Features with Optional Coil Section . . . . . . . . . . . . . .5
ERV Summer/Winter Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
ERV Summer/Winter Modes with Optional Coil Section . . . . . . . . .7
Annual Energy Savings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Payback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Arrangements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
System Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Direct Drive Specifications and Dimension Data . . . . . . . . . . . . . .12
Belt Drive Specifications and Dimension Data . . . . . . . . . . . . . . . .13
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-17
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Intake Hood Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Lorenized Fan Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Air Performance Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Energy Wheel Performance Notes . . . . . . . . . . . . . . . . . . . . . . . . .19
Direct Drive Performance Data
ERV 500 (200 - 500 CFM). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
ERV 1000 (400 - 1000 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Belt Drive Performance Data
ERV 1500 (500 - 1500 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
ERV 2500 (900 - 2500 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
ERV 3500 (1300 - 3500 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
ERV 4500 (1500 - 4500 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
ERV 5500 (2350 - 5500 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
ERV 7000 (2250 - 7000 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
ERV 8500 (3100 - 8500 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
ERV 10000 (3400 - 10000 CFM) . . . . . . . . . . . . . . . . . . . . . . . . . .29
Energy Recovery Cassette
ERC Product and Performance Data (200 - 10000 CFM) . . . . 30-31
ERV Belt Drive Ductwork Connections. . . . . . . . . . . . . . . . . . . . . .32

ERV Introduction
A challenge facing todays HVAC engineer is how to meet ASHRAE Standard 62, Ventilation for Acceptable Indoor Air Quality, while conserving valuable energy resources needed to condition that outdoor air. Loren Cook Companys Energy Recovery Ventilator (ERV) provides an economical solution to this design challenge. The ERV offers a wide performance range, high pressure capabilities, and high
energy recovery efficiencies. This product delivers where it counts most - first cost savings, performance efficiencies, durability, and easy
maintenance. The Cook ERV is available in two direct drive sizes and eight belt drive sizes ranging from 500 to 10,000 cfm.
The primary component of the ERV is a durable, rotating enthalpy wheel. The wheel features a spirally wound, fluted air channel design
providing ultra low pressure drop and eliminates lateral leakage within the wheel. The mass provided by the 4 wheel depth allows for
excellent sensible heat transfer. The manufacturing process used to create the wheel media is unique to the industry, allowing synthetic
absorption type desiccant to be combined with synthetic fiber substrate while it is still a liquid. This process distributes a much higher volume of desiccant throughout the media, not just on the surface, resulting in excellent latent heat transfer. This also assures that the media
will not suffer any degradation in adsorption performance during its long and trouble free operating lifetime.

Standard Construction Features

Direct Drive
ERV-500 and ERV-1000

Belt Drive
ERV-1500 through ERV-10000

Energy Recovery Wheel


Wheel media is constructed of a unique fluted synthetic fiber-based media
impregnated with a non-migrating water selective 4 angstrom () molecular
sieve desiccant (typical flute size is 6 mils).
Energy Recovery Cassette
The cassette assembly consists of an energy recovery wheel, drive motor,
and drive components which include pulleys, belts and bearings. The cassette assembly slides out for easy access.
Supply and Exhaust Blower Assemblies
All blowers are centrifugal forward curved type with painted steel housings.
The wheels are balanced in accordance with AMCA Standard 204-96, Balance Quality and Vibration Levels for Fans.
Cabinet
The cabinet is constructed of minimum 18 gauge galvanized steel panels
bolted to a minimum 16 gauge galvanized steel base. The entire cabinet is
insulated with 1 thick, 3 lb. density, foil faced insulation. A hinged door is
provided for access to the electrical control panel. Removable doors are
provided for access to all other internal components.
Filters
Filters are furnished in both the supply and exhaust airstreams. Standard 2
thick, 30 percent efficient pleated filters are utilized to maintain the efficiency of the energy recovery wheel. Air performance data includes the initial pressure drop of the air filters.
Controls and Electrical
All internal electrical components are pre-wired for single-point power connection. Control panel is UL listed with hinged access door and interlocking
NEMA 3R disconnect switch. Control panel is standard on belt drive units &
optional on direct drive units.
Certifications
Energy transfer ratings are ARI certified in accordance with the ARI Air-toAir Energy Recovery Ventilation Equipment Certification Program, based on
ARI Standard 1060-2000 and ASHRAE 84-1991. Air performance is
assured through compliance with the AMCA Certified Ratings Program. All
Cook ERV units are UL and cUL listed.

ERV Typical Applications


Libraries
Museums
Night Clubs
Smoking Lounges

Schools
Auditoriums
Offices
Gymnasiums
Hotels
Restaurants
Retail Stores

Convention Centers
Health Care Facilities
Manufacturing Plants

ERV with Coil Option - Typical Applications

Belt Drive
with Coil Option
ERV-1500 through ERV-10000

Typical applications include all those listed above while also adding the convenience
of installing one stand alone unit to supply air at the desired room conditions.
Eliminates the need for separate HVAC equipment by integrating it into the ERV
unit, minimizing the total number of roof penetrations in rooftop applications or the
total amount of floor space required in indoor applications.

Standard Construction Features ERV


Direct Drive
ERV-500/ERV-1000
Indoor installations
Shown in side access orientation

Sight window in cassette


allows for easy inspection and
maintenance of wheel, motor
and belts

18 gauge galvanized steel


housing

Fully insulated cabinet


Quick release
latches

Direct drive blower


assembly slides out in
seconds for easy maintenance

Electrical box with


single point power
connection and padlockable interlocking
disconnect switch

Duct collars

Hinges allow easy door


removal
Removable wheel
cassette
Rotary energy recovery
wheel with fluted air
channels

Industry standard size,


30% efficient, 2 thick
pleated air filters provided
on intake side of wheel for
both air streams
ERV-500/ERV-1000 Direct Drive
Shown in optional low profile,
bottom access orientation

Optional low profile


mounting brackets

Optional 24 volt
control center

16 gauge single side


hinged access panel

ERV Standard Construction Features


Belt Drive
ERV-1500 through ERV-10000
Indoor or outdoor installations

Fully insulated cabinet

Optional
exhaust hood
with bird screen

Minimum 18 gauge
galvanized steel
housing

Optional intake hood


with slide out 2
washable aluminum
filters
High voltage electrical
box with motor contactors, and 24 volt transformer for remote
starting

Painted steel forward


curved blowers
Slide out wheel cassette
with integral lifting lugs
Minimum 16
gauge galvanized
steel base
Integral lifting
lugs
Filter
access
panel

Rotary energy recovery


wheel with fluted air
channels

Industry standard size, 30%


efficient, 2 thick, pleated air filters
provided on intake side of wheel
for both airstreams

Easy to remove access


panels

Hinged electrical and blower


access panel with padlockable
interlocking disconnect switch
Cassette, filter,
and blower
access panel

Rotary energy recovery


wheel with fluted air
channels

Link type belt lasts up to 15 times


longer than conventional V-Belts.
Belts minimize down time with easy
replacement without cassette
teardown

Standard Construction Features with Optional Coil Section ERV


Belt Drive
with Coil Option
ERV-1500 through ERV-10000

Filter access panel

Optional DX, chilled


or hot water coils
(Electrical heat also
available)

Coil and Blower


Access Panel

Hinged electrical and blower


access panel with padlockable
interlocking disconnect switch

Access door for internal


DX liquid connections

Double wall construction


on supply airstream

Cassette, filter, and


electrical pre-heat
access panel

Optional electric pre-heater

Fully insulated cabinet

Minimum 18 ga. housing

Optional Lorenized finish

Painted steel forward curved blowers

Sloped stainless
steel drain pan with
external drain connection (secondary
drain pan on units
with stacked coils)
High voltage electrical box with motor
contactors, and 24
volt transformer for
remote starting

Rotary energy recovery wheel


with fluted air channels
Slide out wheel cassette
with integral lifting lugs

Optional tiered intake hood


with slide out 2 washable
aluminum filters
Integral lifting lugs

Welded, minimum
16 ga. steel base

Industry standard size, 30% efficient, 2 thick,


pleated air filters provided on intake side of
wheel for both airstreams

ERV Summer/Winter Modes


How the Energy Recovery Unit Works
The ERV has two separate airstreams, an exhaust airstream and a supply airstream. The primary feature of the ERV is an enthalpy wheel
that rotates slowly (45 RPM) through both airstreams. The wheel has small passageways or flutes that the air flows through. As air passes
through the wheel, the wheel captures heat and moisture from the warm airstream then releases it into the cool airstream. Positive seals
around the wheel assure minimal cross leakage between the exhaust and supply airstreams.
The mass of the wheel captures heat in one airstream and releases it into the cooler airstream. This is defined as sensible heat transfer.
The wheel also adsorbs moisture from one airstream and releases it into the dryer airstream. This is defined as latent heat transfer.
The total energy transferred from one airstream to the other is the sum of the sensible and latent energy transfer. This is defined as the
total heat transfer. The measure of an ERVs heat transfer performance is defined as the percent effectiveness. The examples below
illustrate the ERVs performance in both summer and winter modes.

4 Warm Humid
Exhaust Air

25

10

15
20

.018

75
70

.016
%

90

0%

65

70
%
70
%
0
65 6
%
50

55
50

25

30

.010

2
0%
Room Air 3

E
TIV
ELA
%R

IDIT
HUM

40

.006
.004

10%

35

.008

20

25

20

.012
4

40

35

.014

0%

45

35

30

.020

MP

50

45

55

60

65

70

75

.002

80

85

95

90

DRY BULB TEMPERATURE - F

Psychrometric Chart Illustrating Typical ERV Summer Performance


A = Energy required to condition outdoor air to indoor air conditions.
B = Energy reclaimed by an ERV.
h2 - h1 Note: For unequal airflow the effectiveness will increase in
B
the airstream with the lower airflow and will decrease in the
=
%Effectiveness =
h3 - h1 airstream with the higher airflow.
A

1 Warm Humid
Outdoor Air

3 Warm Moist
Exhaust Air
From Building

25

20

PE EN
R TH
PO A
UN LP
D Y (h
O )
F B
DR TU
Y
AI
R

Winter

55

15

F
RE
ATU
45
PER
M
TE
ON
40
ATI
UR
35
40
SAT
30
35
30

10

25

20

25

80

70

60 60%

50

55

50

50
2

45

IDITY

30

35

60
40
50
55
45
DRY BULB TEMPERATURE - F

.004

E HUM

ELATIV

20% R

.010

%
40
.008
Room
Air
%
30
.006
3

10% .002

25

20

5 1
5

90

65

70

75

HUMIDITY RATIO (W)


POUND MOISTURE PER POUND DRY AIR

1 95F dry bulb, 75F wet bulb, 40% RH, .014 (lb./lb.), 99 (grains/lb.), 38 (BTU/lb.)
2 78F dry bulb, 62F wet bulb, 41% RH, .008 (lb./lb.), 59 (grains/lb.), 28 (BTU/lb.)
3 75F dry bulb, 60F wet bulb, 40% RH, .007 (lb./lb.), 52 (grains/lb.), 26 (BTU/lb.)

Warms incoming outdoor air through sensible


heat transfer and raises humidity through latent
heat transfer. Effectiveness rates are up to 85
percent.
Allows building owners to conserve up to 60,000
BTU per 1,000 CFM.
The ERV is an ideal solution for reducing energy
use and maintaining relative humidity levels
above 25 percent.

4 Cool Dry
Exhaust Air

U
AT

TE

75

60

50
3

40
30

TE

R
PE

55

15

25

2
Cool Dry
Supply Air
to Building

IO
AT
R
U
T
60
SA

20

45

.022

80

FW
.B.

30

PE EN
R TH
PO A
UN LP
D Y (h
O )
F B
DR TU
Y
AI
R

3 Cool Dry
Exhaust Air
From Building

80
35

HUMIDITY RATIO (W) POUND MOISTURE PER POUND DRY AIR

Summer
Cools incoming outdoor air through sensible heat
transfer and lowers humidity through latent heat
transfer. Effectiveness rates are up to 85 percent.
Allows engineers to reduce HVAC equipment
peak load requirements by up to 4 tons per 1,000
CFM of exhaust air.
The ERV is an ideal solution for reducing HVAC
equipment size and maintaining relative humidity
levels below 50 percent.

Psychrometric Chart Illustrating Typical ERV Winter Performance


2
Warm Moist
Supply Air
to Building

1 Cold Dry
Outdoor Air

A = Energy required to condition outdoor air to indoor air conditions.


B = Energy reclaimed by an ERV.
%Effectiveness =

B h2 - h1
=
A h3 - h1

Note: For unequal airflow the effectiveness will increase in


the airstream with the lower airflow and will decrease in the
airstream with the higher airflow.

1 20F dry bulb, 18F wet bulb, 75% RH, .002 (lb./lb.), 11 (grains/lb.), 7 (BTU/lb.)
2 67F dry bulb, 54F wet bulb, 43% RH, .006 (lb./lb.), 42 (grains/lb.), 23 (BTU/lb.)
3 74F dry bulb, 59F wet bulb, 38% RH, .007 (lb./lb.), 48 (grains/lb.), 25 (BTU/lb.)

Summer/Winter Modes with Optional Coil Section ERV


Summer Cooling - Options include: DX or Chilled water coil

Warm Humid
Exhaust Air

Space Neutral
Air to Building

80

FW
.B.

30

1 Warm Humid
Outdoor Air

PE EN
R TH
PO A
UN LP
D Y (h
O )
F B
DR TU
Y
AI
R

25

4 Reheated Air Exits


Heating Coil
3 Over Cooled Air
Exits Cooling Coil
2 Preconditioned Outdoor Air Exits Wheel

30

.018

70

.016
%

90

0%

65

70

%
70
0%
65 6

30

50

.010

40

50

2
0%
Room Air 3

20%

IDIT
UM
EH

ATIV
REL

35

40

.008
.006
.004

10%

25

25

.014

.012

40

35

.020

MP

75

45

35

30

20

20

55

40

15

TE

U
AT

TE

75

60

50

10

ER

55

15

25

The cooling coil further cools and dehumidifies the


incoming air.
A heating coil can reheat the overcooled air to
space neutral conditions at the supply outlet.
Allows engineers to specify one unit for their
energy recovery and cooling needs.
Helps simplify the overall HVAC design from specification to final installation.
The ERV with Coil Option is an ideal solution for
applications that require 100% outdoor air.

IO
AT
R
U
T
60
SA

20

45

.022

80

35

50

45

55

60

65

70

75

.002

80

85

HUMIDITY RATIO (W) POUND MOISTURE PER POUND DRY AIR

Cool Dry Exhaust Air


from Building

95

90

DRY BULB TEMPERATURE - F

1 95F dry bulb, 75F wet bulb, 40% RH, .014 (lb./lb.), 99 (grains/lb.), 38 (BTU/lb.)
2 78F dry bulb, 62F wet bulb, 41% RH, .008 (lb./lb.), 59 (grains/lb.), 28 (BTU/lb.)
3 48.73F dry bulb, 48.7F wet bulb, 100% RH, 0.0073 (lb./lb.), 50.9 (grains/lb.),

19.6 (BTU/lb.)
4 74.45F dry bulb, 59F wet bulb, 39.3% RH, 0.0073 (lb./lb.), 49.7 (grains/lb.),

25.7 (BTU/lb.)

Winter Heating - Options include: Electric or hot water coil.


Warm Moist Exhaust Air
From Building

55

15

3 Heated Air Exits


Heating Coil
1 Cold Dry
Outdoor Air

10

2 Preconditioned Outdoor Air Exits Wheel

25

20

25

80

70

60 60%

30

35

50

55

50

50
2

45

IDITY

60
40
50
55
45
DRY BULB TEMPERATURE - F

.004

E HUM

ELATIV

20% R

.010

%
40
.008
Room
Air
%
30
.006
3

10% .002

25

20

5 1
5

The heating coil heats the air to space neutral conditions at the supply outlet.
Allows engineers to design and specify only one
unit for their energy recovery and heating needs.
Heating coils can also be utilized during the summer for re-heat.

F
RE
ATU
45
PER
M
E
T
ON
40
ATI
UR
35
40
SAT
30
35
30

90

65

70

75

HUMIDITY RATIO (W)


POUND MOISTURE PER POUND DRY AIR

25

20

PE EN
R TH
PO A
UN LP
D Y (h
O )
F B
DR TU
Y
AI
R

Cool Dry
Exhaust Air

Warm Moist Supply


Air to Building

1 20F dry bulb, 18F wet bulb, 75% RH, .002 (lb./lb.), 11 (grains/lb.), 7 (BTU/lb.)
2 67F dry bulb, 54F wet bulb, 43% RH, .006 (lb./lb.), 42 (grains/lb.), 23 (BTU/lb.)
3 76.9F dry bulb, 57.5F wet bulb, 31% RH, .006 (lb./lb.), 39.5 (grains/lb.), 24.78

(BTU/lb.)

ERV Annual Energy Savings


Ventilation rates prescribed by ASHRAE Standard 62 have required mechanical designers to significantly increase the amount of outdoor
air provided to occupied spaces. The high efficiencies of energy recovery ventilators allow engineers to meet the ASHRAE 62 Standard
and continue to design energy efficient structures. In the winter, heat and moisture recovered from the warm indoor exhaust air is transferred to the cold outdoor air being introduced into the building. With the heat transfer effectiveness as high as 85 percent, winter fuel bills
can be drastically reduced while providing a healthy and comfortable indoor environment. Similar energy savings can be realized in the
summer months as warm, humid outdoor air is cooled and dehumidified before it is introduced to the conditioned space, thus reducing air
conditioning load.
The annual energy savings map illustrates how operating cost savings can be substantial. While energy savings are very good across the
southern United States, they are excellent throughout the central and northern United States and all of Canada. Detailed analysis, including first cost and monthly heating and cooling savings for a specified application can be calculated using the Cook Compute-A-Fan selection software.

Annual Energy Savings Map

Operating Assumptions
This map illustrates typical annual energy savings (in dollars per 5,000 cfm)
by location. The analysis is based on the following assumptions.
Hours of operation: 6 a.m. to 10 p.m., five days per week
Cooling source EER: 10.0
Summer indoor design: 75Dry Bulb, 50 percent Relative Humidity
Electric cost: $.07/kwh
Winter indoor design: 72Dry Bulb, 35 percent Relative Humidity
Heating source: Gas, $.60/therm.
Wheel effectiveness: 75 percent latent and sensible
Calculations include ERV operating costs

Savings per Year


$0-500
$501-1500
$1501-2500
$2501-3500
$3501 +

Payback ERV
Energy savings and initial equipment savings can be combined to calculate an attractive payback on the Cook ERV. When an ERV is
incorporated into an HVAC system, air conditioning and heating equipment can be appropriately downsized. In the often hot and humid
climates shown in red on the payback map, initial ERV cost will be offset by a decrease in air conditioning equipment cost resulting in
immediate payback. In the climates indicated in yellow and green on the map, excellent operating cost savings allow ERV payback to be
realized in 1 to 3 years.
Weather data for this analysis is based on Typical Meteorological Year (TMY2) data obtained from the National Renewable Energy Laboratory. This data was derived from the National Solar Radiation Data Base. It represents hourly typical weather conditions for the 239
North American cities illustrated on both the annual energy savings map and payback map. Summer design conditions are based on
ASHRAE 97, 1 percent DB/MWB cooling conditions. Detailed analysis, including first cost and monthly heating and cooling savings for a
specified application can be calculated using the Cook Compute-A-Fan selection software.

Payback Map

Operating Assumptions
This map illustrates the time required to recover the ERV equipment cost.
The analysis is based on the following assumptions.
Hours of operation: 6 a.m. to 10 p.m., five days per week
Cooling source EER: 10.0
Summer indoor design: 75Dry Bulb, 50 percent Relative Humidity
Electric cost: $.07/kwh
Winter indoor design: 72Dry Bulb, 35 percent Relative Humidity
Heating source: Gas, $.60/therm.
Wheel effectiveness: 75 percent latent and sensible
ERV installed cost: $3/cfm
A/C equipment installed cost: $1,000/ton
Calculations include ERV operating costs

Payback Period in Years


Instant
Less than 1 year
Less than 3 years
More than 3 years

ERV Arrangements
Cook Energy Recovery Ventilators offer flexibility to meet a wide variety of installation requirements. One direct drive and three belt drive
ERV cabinet arrangements: V (vertical), H (horizontal) and C (combination), provide solutions for new, existing or future HVAC systems.
(Consult Factory for other arrangements)

Exhaust Air

Return Air

Supply Air
Outdoor Air

Direct Drive - Designed for indoor use and available


in a horizontal airflow configuration. Installation flexibility allows either airstream to be used for supply or
exhaust air.

Arrangement V - Provides vertical supply and return


duct connections for belt drive units.

Return Air

Exhaust Air

Supply Air

Supply Air

Exhaust Air

Return Air

Outdoor Air

Arrangement H - Provides horizontal supply and


return duct connections for belt drive units.

Outdoor Air

Arrangement C - Provides combination horizontal


supply and vertical return duct connections for belt
drive units.

10

System Applications ERV


ERV Operating Independently of the HVAC System
Outdoor air condition
95F dry bulb
78F wet bulb
117.4 grains/lb.

ERV

Packaged
Rooftop Unit

Exhaust air condition


92.9F dry bulb
76F wet bulb
108.1 grains/lb.

Indoor air condition


75F dry bulb
63F wet bulb
66.4 grains/lb.

Supply air condition


77.1F dry bulb
65.6F wet bulb
76 grains/lb.

ERV Supplying Ducted Air Handlers


ERV
Outdoor air condition
95F dry bulb
78F wet bulb
117.4 grains/lb.

Exhaust air condition


92.9F dry bulb
76F wet bulb
108.1 grains/lb.
Indoor air condition
75F dry bulb
63F wet bulb
66.4 grains/lb.

Supply air condition


77.1F dry bulb
65.6F wet bulb
76 grains/lb.

Ducted Air
Handler

ERV Supplying a Packaged Rooftop Unit


Packaged
Rooftop Unit
ERV
Outdoor air condition
95F dry bulb
78F wet bulb
117.4 grains/lb.
Supply air condition
77.1F dry bulb
65.6F wet bulb
76 grains/lb.

Exhaust air condition


92.9F dry bulb
76F wet bulb
108.1 grains/lb.
Indoor air condition
75F dry bulb
63F wet bulb
66.4 grains/lb.

11

ERV Specifications and Dimension Data


Energy Recovery Ventilator
Direct Drive

C
B
Energy recovery component rated in
accordance with ARI Standard 1060-2000
and certified to ARI. Actual performance in
packaged equipment may vary.
Loren Cook Company certifies that the
ERV shown herein is licensed to bear the
AMCA Seal. The ratings shown are based
on tests and procedures performed in
accordance with AMCA Publication 211
and comply with the requirements of the
AMCA Certified Ratings Program.
Type ERV is furnished standard with UL 1812 listing
(Ducted Heat Recovery Ventilators).

Description: Unit shall be a direct driven energy recovery ventilator.


Certifications: Unit shall be manufactured at an ISO 9001 certified facility. Unit
shall be listed by Underwriters Laboratories (UL 1812) and UL listed for Canada
(cUL 1812). Unit shall be ARI certified in accordance with the ARI Air-to-Air
Energy Recovery Ventilation Equipment Certification Program. Unit shall bear
the AMCA Certified Ratings Seal for Air Performance.
Construction: The unit shall be of bolted construction utilizing corrosion resistant
fasteners. Housing shall be minimum 18 gauge galvanized steel. Duct collars
shall be provided as standard. Unit shall be provided with insulated top, side
and interior panels utilizing 1 thick, three pound density foil faced insulation,
manufactured and tested to meet NFPA 90A and UL 181 requirements. Insulation shall be fastened to the panels with weatherproof adhesive and weld pins.
Energy recovery wheel shall be mounted in a slide track for easy inspection and
cleaning. Separate blower and motor shall be provided for supply and exhaust
airstream for independent system balancing. Blower and motor assemblies
shall slide out for easy inspection. Two inch thick, 30 percent efficient pleated filters shall be provided for supply and exhaust airstreams. Entire side panel shall
be hinged and removable for single side access to internal components. Unit
shall bear an engraved aluminum nameplate and shall be shipped in ISTA Certified Transit Tested Packaging.
Energy Wheel: Wheel shall be a total energy recovery wheel constructed of fluted
synthetic fiber-based media impregnated with a non-migrating water selective
4 angstrom molecular sieve desiccant. Wheels with the desiccant applied in a
secondary operation will not be accepted. Energy transfer ratings shall be ARI
certified in accordance with the ARI Air-to-Air Energy Recovery Ventilation
Equipment Certification Program, based on ARI Standard 1060-2000.
Fan Wheel: Wheel shall be SWSI centrifugal forward curved type, constructed of
painted steel. Wheel shall be balanced in accordance with AMCA Standard
204-96, Balance Quality and Vibration Levels for Fans.
Motors: Motors shall be heavy duty type with permanently lubricated sealed ball
bearings and furnished at the specified voltage, phase and enclosure.
Controls and Electrical: All internal electrical components shall be pre-wired for
single point power connection. Optional UL Listed control panel. Unit will
include hinged access door and interlocking NEMA 3R disconnect switch.
Product: Ventilator shall be model ERV as manufactured by Loren Cook Company
of Springfield, Missouri.

ERV - Direct Drive Dimension Data


Size
500
1000

23-13/16
22
50-3/32
28-13/16 28-1/4 50-3/32

Wheel
Diameter
18
24

All dimensions in inches. *Weight in pounds, less motor.


Type ERV is furnished standard with CUL
1812 listing (Ducted Heat Recovery
Ventilators).

12

Filter Quantity/
Filter Size
(2) - 16 x 20
(2) - 16 x 25

Approx.
Ship. Wt.
285
344

Specifications and Dimension Data ERV


Description: Unit shall be a belt driven energy recovery ventilator.
Certifications: Unit shall be manufactured at an ISO 9001 certified facility. Unit
shall be listed by Underwriters Laboratories (UL 1812) and UL listed for Canada
(cUL 1812). Unit shall be ARI certified in accordance with the ARI Air-to-Air
Energy Recovery Ventilation Equipment Certification Program. Unit shall bear
the AMCA Certified Ratings Seal for Air Performance.
Construction: The unit shall be of bolted construction utilizing corrosion resistant
fasteners. Housing shall be minimum 18 gauge galvanized steel, bolted to a
minimum 16 gauge galvanized steel base with integral lifting lugs. Unit shall be
provided with insulated top, side and interior panels utilizing 1 thick, three
pound density foil faced insulation, manufactured and tested to meet NFPA 90A
and UL 181 requirements. Insulation shall be fastened to the panels with
weatherproof adhesive and weld pins. Energy recovery wheel shall be mounted
in a slide track for easy inspection and cleaning. Separate blower and motor
shall be provided for supply and exhaust airstream for independent system balancing. Blower and motor assemblies shall be mounted on rubber vibration isolators. Two inch thick, 30 percent efficient pleated filters shall be provided for
supply and exhaust airstreams. Removable side panels shall be provided for
easy access to motors, blowers, filters and energy recovery wheel. Unit shall
bear an engraved aluminum nameplate and shall be shipped in ISTA Certified
Transit Tested Packaging.
Energy Wheel: Wheel shall be a total energy recovery wheel constructed of fluted
synthetic fiber-based media impregnated with a non-migrating water selective
4 angstrom molecular sieve desiccant. Wheels with the desiccant applied in a
secondary operation will not be accepted. Energy transfer ratings shall be ARI
certified in accordance with the ARI Air-to-Air Energy Recovery Ventilation
Equipment Certification Program, based on ARI Standard 1060-2000.
Fan Wheel: Wheel shall be DWDI centrifugal forward curved type, constructed of
painted steel. Wheel shall be balanced in accordance with AMCA Standard
204-96, Balance Quality and Vibration Levels for Fans.
Motors: Motors shall be heavy duty type with permanently lubricated sealed ball
bearings and furnished at the specified voltage, phase, and enclosure.
Coils: All heating and cooling coils shall be tested and rated in accordance with ARI
Standard 410 and certified in accordance with the ARI Certification Program.
DX coils shall be equipped with distributors to receive expansion valves at the
liquid connections.
Controls and Electrical: All internal electrical components shall be pre-wired for
single point power connection. Internal control panel shall be UL listed with
hinged access door and interlocking NEMA 3R disconnect switch. Each motor
shall have a motor starter combination providing fuseless disconnect, over-current, overload and motor starting functions. A 24 volt control circuit shall be provided to allow remote on/off control of ERV by building control system. Short
circuit protection shall be provided on primary and secondary of control power
transformer.
Bearings: Bearings shall be permanently lubricated, sealed ball type selected for a
minimum L50 life in excess of 200,000 hours at maximum cataloged operating
speed.
Belts and Drives: Belts shall be oil and heat resistant, non-static type. Drives shall
be precision machined cast iron type, keyed and securely attached to the wheel
and motor shafts. Drives shall be sized for 150 percent of the installed motor
horsepower. The variable pitch motor drive shall be factory set to the specified
fan RPM.
Product: Ventilator shall be model ERV as manufactured by Loren Cook Company
of Springfield, Missouri.

Energy Recovery Ventilator


Belt Drive

Energy recovery component rated in


accordance with ARI Standard 1060-2000
and certified to ARI. Actual performance in
packaged equipment may vary.

Loren Cook Company certifies that the ERV


shown herein is licensed to bear the AMCA
Seal. The ratings shown are based on tests
and procedures performed in accordance
with AMCA Publication 211 and comply with
the requirements of the AMCA Certified
Ratings Program.
Type ERV is furnished standard with UL
1812 listing (Ducted Heat Recovery
Ventilators) when furnished with factory
supplied motor.
Type ERV is furnished standard with CUL
1812 listing (Ducted Heat Recovery
Ventilators) when furnished with factory
supplied motor.

ERV - Belt Drive Dimension Data


Size

1500
2500
3500
4500
5500
7000
8500
10000

42-7/8
52-3/8
59
64-1/2
71
76-1/2
83
90

49-1/4
52
60-1/2
66-1/2
66-1/2
80
80
84-1/2

Standard
54-1/4
52
64-1/2
69-1/2
69-1/2
79-1/2
79-1/2
100

C
with Coils
90-1/4
88
100-1/2
105-1/2
105-1/2
115-1/2
115-1/2
136

Wheel
Diameter
28
36
42
48
54
60
66
72

Filter Quantity/
Filter Size
(2) - 12 x 24, (2) - 20 x 24
(4) - 20 x 25
(4) - 14 x 25, (4) - 16 x 25
(10) - 16 x 20
(12) - 16 x 20
(4) 20 x 20, (8) 20 x 24
(6) - 18 x 24, (6) - 20 x 24
(8) - 20 x 24, (8) - 18 x 20

All dimensions in inches. Weight in pounds, less motor and accessories.

13

Roof Curb Dimensions


Standard
with Coils
45-3/4 x 50-3/4
45-3/4 x 86-3/4
48-1/2 x 48-1/2
48-1/2 x 84-1/2
57 x 61
57 x 97
63 x 66
63 x 102
63 x 66
63 x 102
76-1/2 x 76
76-1/2 x 112
76-1/2 x 76
76-1/2 x 112
81 x 96
81 x 132

Approx.
Ship. Wt.
604
722
990
1111
1235
1609
1734
3000

ERV Accessories
Roof Curbs
Treated Wood Nailer
CxD
AxB

Insulation

Size
1500
1-1/2"
2500
3500
13-1/2" 4500
(Std.)* 5500
7000
8500
10000

A
45-3/4
48-1/2
57
63
63
76-1/2
76-1/2
81

B
50-3/4
48-1/2
61
66
66
76
76
96

C
49-3/4
52-1/2
61
67
67
80-1/2
80-1/2
85

D
54-3/4
52-1/2
65
70
70
80
80
100

Coil Section
Dimensions
B
D
86-3/4 90-3/4
84-1/2 88-1/2
97
101
102
106
102
106
112
116
112
116
132
136

*Other heights available.

Duct Adapter

Duct Flanges
Duct Flanges are available for
easy attachment of ductwork.
Flanges are standard on all direct
drive units and optional on belt
drive units.

Duct Adapters are available for ERVs


in Arrangement V or C. Adapters allow
for proper placement and attachment
of ductwork prior to unit installation.

Intake Weather Hood

Tiered Intake Weather Hood


Optional Intake Weather Hood is
available for outdoor installations.
Hood is provided with 2 thick
washable aluminum filters. See
page 19 for pressure drop.

Optional Tiered Intake Weather


Hood is available for outdoor
installations. Hood is provided
with 2 thick washable aluminum
filters mounted in a V-bank style
configuration with an easily
removable access door. See
page 19 for pressure drop.

Lorenized Finish

Exhaust Weather Hood

Optional LorenizedFinish is available for the


exterior surfaces of the
ERV. See page 19 for
Lorenized powder coat
specifications.

Optional Exhaust Weather Hood


is available for outdoor installations. Hood is provided with birdscreen and available with
optional automatic or motorized
discharge shutters.

Dampers
Internal Factory Installed
Gravity and motorized dampers are available factory installed in the supply and exhaust airstreams. Low leakage and insulated dampers
are also available. All damper motor actuators are prewired to the unit control panel.

External Duct Mounted


Gravity and motorized dampers are available for field mounting in the supply and exhaust ductwork. Dampers will ship loose and motorized
damper actuators will require field wiring.

14

Accessories ERV
COIL PRESSURE DROP
Unit Size

CFM

500
750
ERV-1500 1000
1250
1500
900
1300
ERV-2500 1700
2100
2500
1300
1850
ERV-3500 2400
2950
3500
1500
2250
ERV-4500 3000
3750
4500
2400
3175
ERV-5500 3950
4725
5500
2300
3475
ERV-7000 4650
5825
7000
3100
4450
ERV-8500 5800
7150
8500
3400
5050
ERV-10000 6700
8350
10000

COIL OPTIONS:

Velocity COOLING COIL


HEATING COiL
(FPM) Max Air PD in W.G. Max Air PD in W.G.
160
0.11
0.03
240
0.2
0.05
320
0.32
0.08
400
0.46
0.11
480
0.62
0.15
195
0.15
0.04
281
0.26
0.06
368
0.41
0.1
455
0.57
0.14
541
0.75
0.18
198
0.15
0.04
282
0.26
0.06
366
0.4
0.1
450
0.56
0.13
533
0.73
0.17
180
0.13
0.03
270
0.25
0.06
360
0.39
0.09
450
0.56
0.12
540
0.75
0.16
263
0.24
0.05
346
0.37
0.08
431
0.52
0.12
515
0.7
0.15
600
0.89
0.2
181
0.13
0.03
273
0.25
0.06
366
0.4
0.09
458
0.58
0.13
551
0.77
0.17
209
0.16
0.04
300
0.29
0.07
391
0.45
0.11
483
0.62
0.15
573
0.82
0.2
198
0.15
0.04
294
0.28
0.07
390
0.44
0.11
486
0.63
0.15
582
0.84
0.2

Values for pressure drop were obtained using the following assumptions:
1. Six row coolling coil and two row heating coil.
2. A fin style that provides a medium efficiency heat transfer rate with lower air pressure drop and
lower fan BHP requirements.

Coil options include cooling coils and heating coils. All


coils have a casing constructed of galvanized steel
with a minimum material thickness of 0.06. The coil
tubing is seamless copper with a minimum of 0.016
wall thickness and aluminum plate fin material thickness a minimum of 0.006 with 12 FPI or less. All coils
have a recessed vent and drain located on exterior
connections.

COOLING COILS:
Cooling coils are available 2, 4, or 6 rows deep. All
cooling coils are provided with a stainless steel drain
pan and condensate drain pipe that extends out
through the side of the unit to allow connection to a PTrap (by others).
Cooling coils in the ERV-4500 and larger include an
upper drain pan with a drainage pipe that drains into
the lower pan.

DX COILS:
DX coils are provided with distributors to receive
expansion valves at the liquid connections. An access
door is provided to allow liquid line connections to be
made in the interior of the unit.

HOT WATER COILS:


Hot water coils are available 1 or 2 rows deep.

ELECTRIC HEAT COILS:


Electric heat coils are available and include the following features: UL Listed, multiple stage control, air proving switch, 24 volt control circuit, fusing when over 48
amps. Heater shall require a separate power connection from the ERV control panel.

ELECTRIC POST-HEATERS AVAILABLE (KW)


Single Phase
115v
208v
230v
ERV-1500
C/F
C/F
C/F
ERV-2500
C/F
C/F
C/F
ERV-3500
C/F
C/F
C/F
ERV-4500
C/F
C/F
C/F
ERV-5500
C/F
C/F
C/F
ERV-7000
C/F
C/F
C/F
ERV-8500
C/F
C/F
C/F
ERV-10000 C/F
C/F
C/F
Unit Size

15

Three Phase
208
230
460
4.5, 9
5, 10
5, 10
9, 13.6
10, 15 10, 15
13.6, 22.6 15, 25 15, 25
13.6, 27.1 15, 30 15, 30
18.1, 31.7 20, 35 20, 35
22.6, 40.7 25, 45 25, 45
27.1, 36.2 30, 55 30, 55
27.1, 58.8 30, 65 30, 65

ERV Accessories
Rubber-in-Shear Isolators - Ceiling Mounted
D Dia. rod

F
Dia.
E

A
B

Isolator
Model
RC-75
RC-125
RC-175
RC-300
RC-450
RC-700
RC-1100

Rated Load
Each (lbs.)
75
125
175
300
450
700
1100

2-5/32
2-5/32
3-5/32
3-5/32
3-5/32
4
4

1-1/2
1-1/2
2-1/4
2-1/4
2-1/4
4-3/4
4-3/4

2-23/32
2-23/32
5-11/16
5-11/16
5-11/16
8
8

11/16
11/16
3/4
3/4
3/4
3/4
3/4

15/32
15/32
1-31/64
1-31/64
1-31/64
1-1/2
1-1/2

3/8
3/8
3/4
3/4
3/4
3/4
3/4

Approx. Ship
Wt. Lbs.
1
1
2
2
2
3
5

All dimensions in inches.

Fan Speed Control - Direct Drive


Cooks Fan Speed Control (FSC) is a variable speed controller which allows operation of
direct drive ERV units from 100 percent of capacity down to approximately 50 percent.
The FSC can offer excellent energy conservation and lower sound levels when 100 percent operation is not required. The FSC employs solid state circuitry for long-life and
dependability and is available only on direct drive models. The FSC is normally shipped
loose for field installation and optional pre-wiring is available.

230 V (5 AMP)

115 V (10 AMP)

Variable Speed - Belt Drive


Two-speed Motors - consult factory.
Variable Frequency Drives - consult factory.

Typical Disconnect Switches


Standard
Factory Installed

NEMA 3R/12

Optional Field Installed

NEMA 1
NEMA 1
(Heavy)
(Lockable)
NEMA 3R/12 - Standard factory installed padlockable for indoor or outdoor use
NEMA 1

NEMA 3R

NEMA 4

NEMA 1 - Indoor general purpose


NEMA 1 - Indoor general purpose with locking capability
NEMA 1 - Indoor heavy duty with locking capability and visible blade
NEMA 3R - Rain-tight
NEMA 4 - Water-tight and dust-tight

Motors
Belt Drive Units
Single phase ODP motors are available from 1/6 to 1-1/2 HP
Three phase ODP motors are available from 1/4 to 10 HP
Single phase TEFC motors are available from 1/6 to 1 HP
Three phase TEFC motors are available from 1/4 to 10 HP

Other Accessories:
Hinged Access Doors - Standard on sizes 500 and 1000, available on sizes 1500 through 10000.
Quarter Turn Latches - Available on hinged access doors only.
Double Wall Construction - Unit is lined with 20 gauge galvanized steel.
Sensible Only Wheels - Desiccant free wheel media for sensible only heat transfer.
Purge Section - Allows contaminated air to be purged from within the wheel flutes and diverted back into the exhaust airstream. The
addition of a purge section will slightly increase cfm requirements. For more information refer to ERV selection included in Compute-AFan selection software.
16

Accessories ERV
Control Options
Dirty Filter Sensor - Senses fan compartment pressure change, which actuates a dirty filter warning light. Sensor requires field calibration after initial system start-up.
Rotation Sensor - If wheel rotation stops the sensor sends a 24 volt signal to a remote indicator (by others).
Economizer Mode - Stops wheel rotation during periods when outdoor air conditions are close enough to indoor air conditions that
sensible and latent heat transfer no longer occurs. Available with a temperature sensor or an enthalpy sensor. (The enthalpy sensor
senses temperature and humidity conditions)
Economizer Automatic Override Sensor - Temperature sensor provides automatic override of economizer mode during the winter
heating season when energy recovery is required. Economizer manual override can also be set up with a manual override switch,
by wiring a remote switch to the energy recovery wheel terminal block.
Remote Panels are available in many different custom combinations of status indicator lights, manual
switches, and automatic programmable controls. All remote panels come complete with a custom stainless
steel wall plate and a junction box. The remote panel requires field wiring connections to the low voltage terminal block located in the ERV control panel.
Status Indicator Lights are available for rotation sensor, dirty filter sensors, economizer mode and frost
control on/off.
Two-Way Switches are available for remote on/off, and economizer override.
Three-Way Switches are available for selecting on, off, or automatic operation of the ERV. For units supRemote Panel
plied with two-speed motors, three-way switches are available for selecting high speed, low speed, or unit off.
7-Day Time Clocks are available and feature easy programming for automatic control of ERV operation.
Manual Timed Override Switches are available for manual override of 7-day time clocks with an adjustable
on time setting of up to two hours.
Frost Control Options
On/Off Frost Control - When the outside air is below a preset temperature the controller shuts off the entire unit. The unit will automatically restart when the outdoor air temperature climbs above the set point.
Exhaust Only Frost Control - When the outside air is below a preset temperature the controller shuts off the supply side blower
until the temperature climbs above the set point.
Timed Exhaust Frost Control - When the temperature measured is below the thermostat adjustable temperature setting, the thermostat shuts off the supply side blower motor and engages an on/off recycling timer with independent adjustment of both the on
and off periods (1-100 minutes). The supply side blower then turns on and off based on timer settings. When the temperature
measured climbs above the set point temperature, then the supply side blower motor returns to continuous operation.
Pre-Heat Frost Control - When the outside air is below a preset air temperature an open coil duct heater is energized that preheats
the intake air to prevent frost buildup. This option is only available on ERV sizes 1500 through 10000.
Field Installed Duct Heater - Consult factory for availability and options.
Electric Pre-Heater Sizing - Once the volume of airflow (CFM) and the required temperature rise (T) through the heater are
known, the required kilowatt rating (KW) of the heater can be determined from the formula:
KW = (CFM x TF) / 3193 or (Liters/second x TC)/837

Frost Control Map

Note: Use map as an informational guideline and a quick estimating tool.


For exact information on frost control, refer to ERV selection included in
Compute-A-Fan software.

Preheat Frost Control


On/Off or Exhaust Only Frost Control
No Frost Control Required
17

ERV Electrical Requirements


Motors
Supply and Exhaust Blower Motors (2 per unit)
Model
ERV-500
ERV-1000
ERV-1500
ERV-2500
ERV-3500
ERV-4500
ERV-5500
ERV-7000
ERV-8500
ERV-10000

115V, 1 Phase
1/2 HP
1 HP
1/6 HP to 1 HP
1/6 HP to 1 HP
1/6 HP to 1 HP
1/6 HP to 1 HP
1/6 HP to 1 HP
1/6 HP to 1 HP
1/6 HP to 1 HP
1/6 HP to 1 HP

230V, 1 Phase
1/2 HP
1 HP
1/6 HP to 1-1/2 HP
1/6 HP to 3 HP
1/6 HP to 3 HP
1/6 HP to 3 HP
1/6 HP to 3 HP
1/6 HP to 3 HP
1/6 HP to 3 HP
1/6 HP to 3 HP

230/460V, 3 Phase
1/4 HP to 1-1/2 HP
1/4 HP to 3 HP
1/4 HP to 3 HP
1/4 HP to 5 HP
1/4 HP to 5 HP
1/4 HP to 7-1/2 HP
1/4 HP to 7-1/2 HP
1/4 HP to 10 HP

Voltage and phase of exhaust and supply blower motors must be the same. Horsepower of supply and exhaust blowers can vary.

Single Phase Alternating-Current Motors (Table 1)


HP
1/6
1/4
1/3
1/2
3/4
1
1-1/2
2
3

115V
4.0
5.0
7.0
9.0
11.8
12.8
18.0
20.4
-

Motor Full Load Amperage


208V
2.2
2.8
3.9
5.0
6.5
7.1
10.0
11.3
13.9

Three Phase Alternating-Current Motors (Table 2)


HP

230V
2.0
2.5
3.5
4.5
5.9
6.4
9.0
10.2
12.6

208V
2.7
3.1
4.0
5.5
7.3
10.0
15.5
23.9
31.6

1/2
3/4
1
1-1/2
2
3
5
7-1/2
10

Motor Full Load Amperage


230V
2.4
2.8
3.6
5.0
6.6
9.0
14.0
21.6
28.6

460V
1.2
1.4
1.8
2.5
3.3
4.5
7.0
10.8
14.3

Values taken from typical motors and are approximate. Use only for preliminary estimates. For exact values consult motor nameplate and local codes.

Energy Wheel Motors (1 per unit) (Table 3)


Motor Full Load Amperage
Model
500-1500
2500-5500
7000-8500
10000

RPM
585
1140
1140
1140

HP
1/15
1/3
1/2
3/4

115
2.0
7.0
9.0
11.8

1 Phase
208
1.1
3.9
5.0
6.5

230
1.0
3.5
4.5
5.9

208
2.4
2.7
3.1

3 Phase
230
2.2
2.4
2.8

460
1.1
1.2
1.4

All energy wheel motors are end mount. Single phase motors include thermal protection. For three phase motors, thermal overload protection is provided on the control panel.

Electric Pre-Heaters Available (KW)


Model
ERV-500
ERV-1000
ERV-1500
ERV-2500
ERV-3500
ERV-4500
ERV-5500
ERV-7000
ERV-8500
ERV-10000

115V
1.0
2.0
-

Single Phase
208V
0.9
1.8
-

230V
1.0
2.0
-

208V
4.5, 8.1
4.5, 9.0, 13.6
4.5, 9.0, 13.6
6.8, 13.6
9.0, 13.6
9.0, 13.6
13.6
-

Three Phase
230V
460V
5.0, 9.0, 12.0
5.0, 9.0, 12.0
5.0, 10.0, 15.0
5.0, 10.0, 15.0
5.0, 10.0, 15.0
5.0, 10.0, 15.0
7.5, 15.0
7.5, 15.0, 22.5
10.0, 15.0
10.0, 20.0, 25.0
10.0, 15.0
10.0, 20.0, 25.0, 30.0
15.0
15.0, 25.0, 30.0, 40.0
15.0, 25.0, 30.0, 40.0, 45.0

KW values for ERV-500 and ERV-1000 are for field installed duct heaters only and should not be added to the full load amperage of the ERV unit.

Minimum Circuit Amperage (MCA) Worksheet

Supply motor amperage (see table 1 or 2 above)


Exhaust motor amperage (see table 1 or 2 above)
Energy wheel motor amperage (see table 3 above)
Control component amperage (115v = .86 amps, 208v = .48 amps, 230v = .43 amps, 460v = .22 amps)
KW x 1000
Heater amperage (see table 3 for KW): 1 phase: amperage = KW x 1000
3 phase: amperage =
heater voltage
unit voltage x 1.732
Total Unit Amperage
x 1.25 Service Factor
Minimum Circuit Amperage

Maximum Overload Circuit Protection (MOCP) Calculation


To obtain the MOCP of the ERV, take the Total Unit Amperage of the ERV (also used to calculate the MCA). Then, take the FLA of the largest motor on the ERV X 1.25 and add it to the Total Unit Amperage. Take the resulting number and round it down to the nearest available
circuit protector. For instance, if the Total Unit Amperage is 22, and the largest motor is a 1 horsepower 3 phase 208 volt (4 X 1.25=5), then
22+5=27. Compare this number to a list of available circuit protectors. A 25 amp protector is available, therefore, the MOCP=25.
18

Additional Information ERV


Intake Hood Pressure Drop
Use this chart to determine the pressure drop of the optional intake hood. The value should be added to the external static pressure for
the supply air stream.
Intake Hood Pressure Drop
0.250
0.225

Static Pressure (in. W.G.)

0.200

ERV-1500
ERV-2500

0.175

ERV-3500

0.150

ERV-4500
0.125

ERV-5500

0.100

ERV-7000
ERV-8500

0.075
ERV-10000
0.050
0.025
0
10500

10000

9500

9000

8500

8000

7500

7000

6500

6000

5500

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

Flow (CFM)

LorenizedFan Finish Specification (Optional)


All steel fan components shall be finished with an electrostatically applied, baked polyester powder coating. Each component shall be
subject to a five stage environmentally friendly wash system, followed by a minimum 2 mil thick baked powder finish. Paint must exceed
1,000 hour salt spray under ASTM B117 test method.
Standard Color - Gray
Final Coat Thickness - Minimum 2 mils
Polyester Powder Testing Information
Impact Resistance
Test - ASTM D2794
Value - 100 inch-pounds
Pencil Hardness
Test - ASTM D3363
Value - 2H (Mar or Gouge)
Crosshatch Adhesion
Test - ASTM D3359 Method B
Value - 100%
Humidity Resistance
Test - ASTM D2247
Value - 1000+ Hours
Salt Spray
Test - ASTM B117
Value - 1000+ Hours
Continuous Service Temperature
Test - N/A
Value - 230F (110C)

Air Performance Notes


Air tests were performed with 30 percent efficient filters
installed in both the exhaust and supply airstreams. Air performance data includes the initial pressure drop of the air filters.
Supply air tests were performed at station X2 with stations X1,
X3, and X4 at 0 S.P. (in. W.G.). Exhaust air tests were performed at station X3 with stations X1, X2, and X4 at 0 S.P.
(in.W.G.). Performance tables show external static pressure
values only.

Exhaust air
leaving.

Energy Wheel Performance Notes


Energy transfer ratings are ARI certified in accordance with the
ARI Air-to-Air Energy Recovery Ventilation Equipment Certification Program, based on ARI Standard 1060-2000 and ASHRAE
84-1991. Published effectiveness ratings correspond to total
energy transfer. Sensible only effectiveness will be higher.

19

Supply air
entering.

Exhaust air
entering.

Supply air
leaving.

ERV - 500 Data


2.5

2.0
Static Pressure (In W.G.)

2.0

Static Pressure (In W.G.)

Energy Recovery Wheel Diameter - 18


Direct Drive
Maximum MHP - 1/2
Maximum Input Watts: 520 - Supply
566 - Exhaust
Cabinet - 18 ga. steel
Shipping Weight - 285 lbs.

ERV - 500 Exhaust

ERV - 500 Supply


2.5

17
5
16 0 R
6
15 1 R PM
7
14 2 R PM
83 PM
13 R
13 94 R PM
0
12 5 R PM
1116 R PM
27 PM
R
95 PM
0R
PM

1.5

1.0

0.5

17

50
16 RP
6
M
15 1 R
P
7
14 2 R M
83 PM
13 RP
13094 RPM
12 5 R M
11216 R PM
7 R PM
950 PM
RP
M

1.5

1.0

0.5

23-3/4

50-3/32

22

0
0

200

400
600
Flow (CFM)

800

1000

200

400
600
Flow (CFM)

800

1000

ERV - 500 Supply


Catalog
Number

RPM

ERV-500

950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750

0.125 SP
CFM
EFF
453
73%
484
71%
514
70%
544
68%
574
67%
603
66%
632
65%
660
64%
689
62%
717
61%
745
60%
774
59%
802
58%
830
57%
857
56%
885
55%
913
54%

0.250 SP
CFM
EFF
375
76%
411
75%
446
73%
481
71%
515
70%
548
68%
581
67%
613
65%
645
64%
676
63%
706
62%
737
60%
766
59%
796
58%
825
57%
854
56%
883
55%

0.375 SP
CFM
EFF
259
82%
313
79%
365
77%
409
75%
449
73%
486
71%
521
69%
556
68%
591
66%
625
65%
658
64%
692
62%
724
61%
756
60%
788
58%
819
57%
849
56%

0.500 SP
CFM
EFF
138
89%
187
86%
246
83%
302
80%
357
77%
409
75%
455
72%
497
71%
535
69%
571
67%
607
66%
641
64%
676
63%
710
61%
744
60%
777
59%
810
58%

0.750 SP
CFM
EFF

1.000 SP
CFM
EFF

1.250 SP
CFM
EFF

1.500 SP
CFM
EFF

57
113
157
202
258
317
373
427
481
530
574
615
653
689
725

57
106
158
201
249
306
365
421
475
530
582
628

69
122
174
216
262
317
376
434
489

56
93
153
200
243
289
344

94%
90%
88%
85%
82%
79%
76%
74%
71%
69%
67%
65%
64%
62%
61%

94%
91%
88%
85%
83%
80%
77%
74%
72%
69%
67%
65%

93%
90%
87%
84%
82%
79%
76%
73%
71%

94%
91%
88%
85%
83%
81%
78%

Speed (RPM) is nominal. Performance is based on actual speed of test. Performance for speeds shown are obtained with an FSC. Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Performance ratings include the effects of filters in the airstream.

ERV - 500 Exhaust


Catalog
Number

RPM

ERV-500

950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750

0.125 SP
CFM
EFF
393
75%
421
74%
448
73%
475
72%
502
70%
529
69%
555
68%
581
67%
608
66%
634
65%
660
64%
685
62%
711
61%
737
60%
762
59%
788
58%
813
58%

0.250 SP
CFM
EFF
320
79%
353
77%
385
76%
416
74%
446
73%
475
72%
504
70%
532
69%
560
68%
588
67%
615
65%
642
64%
669
63%
696
62%
723
61%
749
60%
776
59%

0.375 SP
CFM
EFF
205
85%
259
82%
305
80%
346
78%
382
76%
416
74%
449
73%
480
71%
511
70%
541
69%
570
67%
599
66%
628
65%
656
64%
684
63%
712
61%
739
60%

0.500 SP
CFM
EFF
58
93%
113
90%
172
87%
241
83%
294
80%
341
78%
384
76%
421
74%
457
72%
490
71%
522
69%
554
68%
585
67%
615
65%
644
64%
673
63%
702
62%

0.750 SP
CFM
EFF

1.000 SP
CFM
EFF

1.250 SP
CFM
EFF

1.500 SP
CFM
EFF

57
107
171
228
299
352
400
444
485
522
557
591
623

89
141
205
262
333
390
439
485
528

90
140
204
261
324
394

42
106
155
220

94%
91%
87%
84%
80%
77%
75%
73%
71%
69%
68%
66%
65%

92%
89%
85%
82%
78%
76%
73%
71%
69%

92%
89%
85%
82%
79%
75%

94%
91%
88%
84%

Speed (RPM) is nominal. Performance is based on actual speed of test. Performance for speeds shown are obtained with an FSC. Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Performance ratings include the effects of filters in the airstream.

20

Data
ERV - 1000 Supply

2.5

2.5

170
2.0

1700 RP

1611 RP
M
1522 RPM

1.5 1433
RPM
1344 RPM
1255 RP
M
1.0 1166 RPM
1077 RPM
0.5

161

2.0

Static Pressure (In W.G.)

28-3/4

ERV - 1000 Exhaust

Static Pressure (In W.G.)

Energy Recovery Wheel Diameter - 24


Direct Drive
Maximum MHP - 1
Maximum Input Watts: 1090 - Supply
1115 - Exhaust
Cabinet - 18 ga. steel
Shipping Weight - 344 lbs.

1000 - ERV

900 RPM

152

0R

1R

2R

PM

PM

PM
3 RP
M
1344
RPM
1255
RPM
1166
107 RPM
7R
PM
143

1.5

1.0

900
0.5

RPM

50-3/32

28-1/4

300

600
900
Flow (CFM)

1200

1500

300

600
900
Flow (CFM)

1200

1500

ERV - 1000 Supply


Catalog
Number

RPM

ERV-1000

900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700

0.125 SP
CFM
EFF
637
77%
681
76%
725
75%
768
74%
811
73%
854
72%
896
71%
939
70%
981
69%
1023
68%
1065
67%
1107
66%
1148
65%
1190
64%
1231
63%
1273
62%
1314
61%

0.250 SP
CFM
EFF
576
79%
618
78%
661
77%
705
76%
748
74%
792
73%
837
72%
881
71%
925
70%
969
69%
1012
68%
1056
67%
1099
66%
1142
65%
1185
64%
1228
63%
1270
62%

0.375 SP
CFM
EFF
534
80%
577
79%
620
78%
662
77%
704
76%
746
75%
788
73%
832
72%
875
71%
919
70%
963
69%
1007
68%
1051
67%
1096
66%
1140
65%
1184
64%
1227
63%

0.500 SP
CFM
EFF
454
83%
529
80%
580
79%
626
78%
669
77%
711
75%
754
74%
795
73%
837
72%
880
71%
923
70%
966
69%
1010
68%
1053
67%
1097
66%
1141
65%
1186
64%

0.750 SP
CFM
EFF

1.000 SP
CFM
EFF

1.250 SP
CFM
EFF

1.500 SP
CFM
EFF

475
552
631
687
734
779
822
864
906
948
990
1032
1075
1117

606
687
755
807
854
898
941
984
1026
1068

603
681
763
833
887
935
981
1024

696
772
854
921
974

82%
80%
78%
76%
75%
74%
73%
71%
70%
69%
68%
67%
66%
65%

78%
76%
74%
73%
72%
71%
70%
69%
68%
67%

78%
76%
74%
72%
71%
70%
69%
68%

76%
74%
72%
70%
69%

Speed (RPM) is nominal. Performance is based on actual speed of test. Performance for speeds shown are obtained with an FSC. Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Performance ratings include the effects of filters in the airstream.

ERV - 1000 Exhaust


Catalog
Number

RPM

ERV-1000

900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700

0.125 SP
CFM
EFF
555
80%
594
79%
633
78%
671
77%
709
76%
747
74%
784
74%
821
73%
858
72%
895
71%
932
70%
968
69%
1005
68%
1041
67%
1077
66%
1114
65%
1150
65%

0.250 SP
CFM
EFF
482
82%
523
81%
564
79%
605
78%
646
77%
686
76%
727
75%
766
74%
806
73%
845
72%
884
71%
922
70%
960
69%
998
68%
1036
67%
1074
66%
1111
66%

0.375 SP
CFM
EFF
425
83%
467
82%
507
81%
548
80%
589
79%
630
78%
671
77%
712
75%
753
74%
793
73%
834
72%
874
71%
914
70%
954
69%
993
68%
1032
67%
1071
66%

0.500 SP
CFM
EFF
338
86%
406
84%
457
83%
500
81%
541
80%
582
79%
623
78%
664
77%
705
76%
746
75%
787
73%
827
72%
868
71%
909
70%
950
69%
990
68%
1030
67%

0.750 SP
CFM
EFF

1.000 SP
CFM
EFF

1.250 SP
CFM
EFF

1.500 SP
CFM
EFF

312
411
481
536
582
624
665
706
747
788
828
869
910
951

279
445
518
582
633
677
720
761
802
842
883

373
501
574
640
693
739
782
824

271
488
573
645
709
761

87%
84%
82%
80%
79%
78%
77%
76%
74%
73%
72%
71%
70%
69%

88%
83%
81%
79%
78%
76%
75%
74%
73%
72%
71%

85%
81%
79%
77%
76%
75%
74%
72%

88%
82%
79%
77%
76%
74%

Speed (RPM) is nominal. Performance is based on actual speed of test. Performance for speeds shown are obtained with an FSC. Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Performance ratings include the effects of filters in the airstream.

21

ERV - 1500 Data


ERV - 1500 Exhaust

2.5

Static Pressure (In W.G.)

1
10 210
96 88 R RP
84 6 R PM M
72 4 R PM
2R P
475
RPM PM M

0.5

0
0

600

1200

1800

2400

3000

M
RP M
P
76
R
M
15
54 RP
32
13

1.0

14

1
9 05
78 21 5 R
7 R RP P
520
PM M M
RP
M

0.5

1.5

P
1 .5 H

2.0

M
RP
25 RPM
M
17
P
91
15 57 R PM
R PM
14
23 R
13 189
1

1.0

P
1H
HP
.75
P
.5 H
HP P
.334 .25 H

1.5

HP
1.5

1 HP
P
.75 H
P
.5 H
HP P
.334 .25 H

2.0
Static Pressure (In W.G.)

Energy Recovery Wheel Diameter - 28


Belt Drive
Maximum RPM - 1725
Maximum MHP - 1.5
Maximum Motor Frame - 145T
Housing - 18 ga. steel
Base - 16 ga. steel
Shipping Weight (less motors) - 604 lbs.

ERV - 1500 Supply

2.5

600

1200

Flow (CFM)

1800

2400

42-7/8

3000

54-1/4

49-1/4

Flow (CFM)

ERV - 1500 Supply


CFM

OV

500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500

594
654
713
773
832
892
951
1010
1070
1129
1189
1248
1308
1367
1427
1486
1546
1605
1665
1724
1784

0.125 SP
RPM BHP
475
.03
491
.03
508
.04
525
.05
543
.06
562
.06
581
.07
600
.09
620
.10
640
.11
661
.12
683
.14
705
.16
728
.18
751
.20
774
.22
798
.24
821
.27
846
.30
870
.33
894
.36

0.250 SP
RPM BHP
623
.05
630
.05
640
.06
654
.07
669
.08
685
.09
701
.10
718
.11
736
.13
754
.14
772
.16
790
.18
809
.20
828
.22
848
.24
868
.26
888
.29
908
.32
929
.35
950
.38
972
.41

0.375 SP
RPM BHP
749
.07
756
.08
762
.09
768
.09
776
.10
788
.12
802
.13
817
.14
833
.16
849
.18
866
.20
883
.21
900
.24
918
.26
936
.28
954
.31
973
.34
992
.37
1011
.40
1031
.43
1050
.46

0.500 SP
RPM BHP
850
.10
860
.11
869
.12
875
.12
880
.13
886
.15
895
.16
906
.17
919
.19
934
.21
949
.23
965
.25
981
.27
998
.30
1015
.32
1032
.35
1050
.38
1068
.41
1086
.44
1105
.48
1123
.52

0.750 SP
RPM BHP
1010
.14
1025
.16
1038
.17
1049
.19
1059
.20
1066
.22
1072
.23
1077
.24
1083
.26
1090
.28
1100
.30
1112
.32
1125
.35
1140
.38
1155
.41
1171
.44
1187
.47
1203
.51
1220
.54
1237
.58
1254
.62

1.000 SP
RPM BHP
1142
.19
1158
.21
1173
.23
1188
.25
1200
.27
1211
.29
1221
.31
1229
.33
1235
.34
1241
.36
1246
.38
1252
.41
1259
.43
1269
.46
1281
.49
1294
.53
1308
.56
1323
.60
1338
.64
1354
.68
1370
.73

1.250 SP
RPM BHP
1257
.24
1274
.26
1290
.29
1306
.31
1320
.33
1334
.36
1346
.38
1357
.41
1366
.43
1374
.46
1381
.48
1386
.50
1391
.53
1397
.56
1403
.58
1412
.62
1422
.65
1434
.69
1447
.74
1462
.78
1476
.83

1.500 SP
Wheel
RPM BHP Effectiveness
1362
.29
85%
1378
.32
84%
1394
.34
83%
1411
.37
82%
1427
.40
81%
1442
.43
80%
1456
.46
79%
1468
.49
78%
1480
.52
77%
1490
.55
76%
1499
.58
75%
1506
.60
74%
1513
.63
73%
1518
.66
72%
1523
.69
71%
1529
.72
70%
1535
.76
69%
1543
.80
68%
1552
.84
68%
1564
.88
67%
1576
.93
66%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 1500 Exhaust


CFM

OV

500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500

594
654
713
773
832
892
951
1010
1070
1129
1189
1248
1308
1367
1427
1486
1546
1605
1665
1724
1784

0.125 SP
RPM BHP
520
.04
539
.05
559
.05
581
.06
604
.07
628
.09
652
.10
676
.12
702
.13
727
.15
753
.17
780
.19
807
.22
834
.24
861
.27
889
.30
917
.33
945
.37
974
.41
1003
.45
1031
.49

0.250 SP
RPM BHP
667
.07
683
.08
700
.09
717
.10
733
.11
751
.12
771
.14
792
.16
814
.17
836
.19
859
.22
882
.24
906
.27
931
.30
956
.33
981
.36
1006
.39
1032
.43
1058
.47
1084
.51
1111
.56

0.375 SP
RPM BHP
793
.10
801
.11
813
.12
828
.13
845
.15
862
.16
879
.18
896
.20
913
.22
932
.24
952
.26
974
.29
995
.32
1018
.35
1041
.38
1064
.41
1088
.45
1111
.49
1136
.54
1160
.58
1185
.63

0.500 SP
RPM BHP
895
.13
910
.14
919
.16
928
.17
941
.19
956
.20
973
.22
990
.25
1007
.27
1024
.29
1041
.32
1059
.34
1078
.37
1098
.40
1119
.44
1140
.47
1163
.51
1185
.55
1208
.60
1232
.65
1255
.69

0.750 SP
RPM BHP
1052
.19
1072
.21
1092
.23
1108
.25
1120
.27
1128
.29
1137
.31
1150
.34
1165
.36
1182
.39
1199
.43
1216
.46
1233
.49
1249
.53
1266
.57
1283
.60
1302
.64
1321
.69
1341
.73
1362
.78
1383
.84

1.000 SP
RPM BHP
1190
.25
1205
.28
1224
.30
1244
.33
1264
.36
1280
.39
1291
.41
1300
.44
1309
.47
1319
.50
1333
.53
1349
.57
1365
.61
1383
.65
1400
.70
1417
.74
1433
.79
1450
.84
1467
.88
1484
.94
1503
.99

1.250 SP
RPM BHP
1318
.32
1329
.35
1343
.38
1360
.41
1380
.44
1401
.48
1419
.51
1434
.55
1445
.58
1454
.62
1462
.65
1472
.69
1485
.73
1500
.77
1516
.82
1534
.87
1551
.93
1568
.98
1585 1.04
1601 1.10
1618 1.16

1.500 SP
Wheel
RPM BHP Effectiveness
1434
.40
85%
1445
.43
84%
1455
.46
83%
1468
.49
82%
1486
.53
81%
1505
.57
80%
1526
.61
79%
1545
.65
78%
1562
.70
77%
1575
.74
76%
1585
.78
75%
1594
.82
74%
1602
.86
73%
1612
.90
72%
1625
.95
71%
1640 1.00
70%
1656 1.06
69%
1673 1.12
68%
1691 1.19
68%
1708 1.25
67%
1725 1.32
66%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

22

Data 2500
ERV - 2500 Exhaust

2.5

2.5

Static Pressure (In W.G.)

Static Pressure (In W.G.)

7R

PM

3 HP

52

73

49

2 HP

0.5

M
RP M
P
60
15 42 R M
14 4 RP M
P
2
13 06 R PM
R
12 88 PM
R M
10
0
P
97 2 R
85

1.0

1.5

52

1 HP
P
.75 H P
.5 H
HP P
.334 .25 H

8
76 73
R
5
65
R P
7 R PM M
444
PM
RP
M

0.5

H
1.5

3 HP

M
RP
M
13
14
RP
PM
05
13 97 R PM
R PM
11
89 R
1 0 981

1.0

2.0

1.5

2 HP

2.0

1.5 H

52-3/8

ERV - 2500 Supply

1 HP
P
.75 H
.5 HP
P
.334 H.25 HP

Energy Recovery Wheel Diameter - 36


Belt Drive
Maximum RPM - 1560
Maximum MHP - 3
Maximum Motor Frame - 145T
Housing - 18 ga. steel
Base - 16 ga. steel
Shipping Weight (less motors) - 722 lbs.

- ERV

RP

0
0

900

1800
2700
Flow (CFM)

3600

4500

900

1800
2700
Flow (CFM)

3600

4500

ERV - 2500 Supply


CFM

OV

900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

868
964
1060
1157
1253
1350
1446
1543
1639
1736
1832
1929
2025
2121
2218
2314
2411

0.125 SP
RPM BHP
444
.06
469
.08
494
.09
519
.12
546
.14
573
.17
600
.20
629
.24
658
.28
688
.32
718
.37
748
.43
779
.49
811
.56
841
.63
874
.71
906
.80

0.250 SP
RPM BHP
559
.09
574
.11
591
.13
612
.15
635
.18
660
.21
684
.25
710
.29
735
.33
761
.38
788
.43
815
.49
843
.55
871
.62
900
.70
929
.78
959
.87

0.375 SP
RPM BHP
655
.12
668
.14
684
.17
699
.19
715
.22
734
.25
756
.29
780
.33
804
.38
829
.43
854
.49
879
.55
905
.62
931
.69
958
.77
985
.85
1013
.95

0.500 SP
RPM BHP

0.750 SP
RPM BHP

1.000 SP
RPM BHP

1.250 SP
RPM BHP

763
779
794
809
825
844
866
889
913
938
963
988
1013
1039
1065

929
943
959
974
989
1004
1022
1042
1064
1088
1112
1136
1161

1072
1086
1102
1117
1132
1147
1163
1181
1201
1223
1246

1202
1216
1232
1247
1262
1277
1293
1310
1328

.20
.23
.27
.30
.34
.38
.43
.48
.54
.61
.68
.76
.84
.93
1.02

.36
.40
.45
.49
.55
.60
.66
.73
.80
.89
.98
1.07
1.17

.55
.60
.67
.73
.80
.86
.94
1.02
1.11
1.21
1.32

.78
.85
.93
1.01
1.09
1.18
1.27
1.37
1.47

1.500 SP
Wheel
RPM BHP Effectiveness
84%
83%
82%
80%
79%
78%
77%
76%
74%
1309
.98
73%
1322 1.06
72%
1336 1.15
71%
1352 1.24
70%
1368 1.34
69%
1383 1.44
68%
1398 1.54
67%
1413 1.64
66%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 2500 Exhaust


CFM

OV

900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

868
964
1060
1157
1253
1350
1446
1543
1639
1736
1832
1929
2025
2121
2218
2314
2411

0.125 SP
RPM BHP
497
.08
524
.11
553
.13
582
.16
612
.19
644
.23
677
.27
711
.32
745
.38
780
.44
815
.51
850
.58
886
.67
921
.75
957
.85
993
.96
1029 1.07

0.250 SP
RPM BHP
610
.12
632
.15
656
.18
682
.21
710
.25
738
.29
766
.34
794
.39
824
.45
854
.51
885
.59
918
.67
951
.75
984
.85
1018
.95
1053 1.06
1087 1.18

0.375 SP
RPM BHP
704
.16
725
.19
746
.22
769
.26
792
.30
817
.35
844
.40
872
.46
899
.53
927
.60
956
.67
985
.76
1014
.84
1045
.94
1076 1.05
1108 1.16
1141 1.29

0.500 SP
RPM BHP

0.750 SP
RPM BHP

1.000 SP
RPM BHP

1.250 SP
RPM BHP

825
846
868
891
914
939
966
993
1021
1049
1077
1105
1134
1164
1194

1001
1022
1043
1065
1088
1111
1135
1161
1188
1215
1243
1271
1299

1156
1176
1198
1220
1242
1264
1288
1312
1338
1365
1392

1297
1317
1339
1361
1383
1405
1428
1452
1478

.27
.31
.36
.41
.46
.52
.60
.67
.76
.85
.94
1.04
1.15
1.27
1.40

.47
.53
.60
.67
.74
.82
.91
1.01
1.11
1.23
1.36
1.49
1.63

.73
.81
.89
.98
1.08
1.18
1.29
1.40
1.54
1.68
1.83

1.04
1.14
1.25
1.36
1.48
1.60
1.73
1.87
2.03

1.500 SP
Wheel
RPM BHP Effectiveness
84%
83%
82%
80%
79%
78%
77%
76%
74%
1409 1.30
73%
1428 1.41
72%
1449 1.54
71%
1471 1.67
70%
1493 1.80
69%
1515 1.94
68%
1537 2.08
67%
1560 2.24
66%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

23

ERV - 3500 Data


ERV - 3500 Exhaust

ERV - 3500 Supply

2.5

66

RP

M
RP
M
02
14
RP
97 RPM
M
12
92 RP
87
10

11

Static Pressure (In W.G.)

HP

0.5

453

3 HP

1.5

0.5

1.0

2 HP

10
RP
90 13
RP M
4
79
R
M
68 5 R PM
6R P
467
PM M
RP
M

1.5

HP

22

.5 HP 4 HP HP
.25
.33

M
M
RP
RP M
49
14
40
RP
31
12
13

11

.75

2.0

HP

1.0

P
1H

3 HP

1 .5

2 HP

P
.5 H
HP HP
.334 .25

1.5

P
1H
HP

.75

2.0
Static Pressure (In W.G.)

Energy Recovery Wheel Diameter - 42


Belt Drive
Maximum RPM - 1449
Maximum MHP - 3
Maximum Motor Frame - 184T
Housing - 18 ga. steel
Base - 14 ga. steel
Shipping Weight (less motors) - 990 lbs.

2.5

77
7

98

87

RP

RP

59

M
RP PM
M

0
0

1000

2000
3000
Flow (CFM)

4000

5000

1000

2000
3000
Flow (CFM)

4000

5000

64-1/2

60-1/2

ERV - 3500 Supply


CFM

OV

1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500

891
960
1028
1097
1165
1234
1303
1371
1440
1508
1577
1645
1714
1783
1851
1920
1988
2057
2126
2194
2263
2331
2400

0.125 SP
RPM BHP
453
.10
470
.12
489
.15
509
.17
530
.20
552
.23
575
.26
598
.30
621
.34
646
.39
669
.43
694
.49
718
.54
743
.61
768
.67
793
.75
818
.82
843
.90
868
.99
894
1.09
919
1.18
945
1.29
971
1.40

0.250 SP
RPM BHP
550
.15
567
.17
585
.19
602
.22
618
.25
635
.28
651
.32
669
.36
687
.40
707
.45
728
.50
749
.56
771
.62
793
.68
816
.75
839
.82
862
.90
886
.99
910
1.08
934
1.18
958
1.28
983
1.39
1007 1.50

0.375 SP
RPM BHP
625
.19
640
.22
657
.24
675
.27
692
.31
709
.34
727
.38
744
.42
760
.47
777
.52
793
.57
810
.63
828
.69
847
.76
867
.83
888
.91
909
.99
930
1.07
953
1.17
975
1.27
998
1.37
1021 1.48
1044 1.60

0.500 SP
RPM BHP
698
.24
709
.26
722
.29
737
.33
753
.36
771
.40
788
.44
806
.49
823
.54
840
.59
857
.64
874
.71
890
.77
907
.84
923
.91
941
.99
959
1.08
978
1.17
998
1.26
1018 1.36
1039 1.47
1061 1.58
1082 1.70

0.750 SP
RPM BHP
828
.33
837
.36
846
.40
856
.44
866
.48
879
.52
893
.57
909
.62
926
.68
943
.73
961
.80
978
.86
995
.93
1013 1.01
1030 1.09
1047 1.17
1064 1.26
1080 1.35
1096 1.45
1113 1.56
1130 1.67
1147 1.79
1165 1.91

1.000 SP
RPM BHP
938
.44
947
.47
956
.51
965
.55
974
.60
983
.65
994
.70
1005
.76
1018
.82
1032
.88
1048
.95
1065 1.02
1082 1.10
1099 1.18
1117 1.27
1134 1.35
1152 1.45
1169 1.55
1186 1.65
1203 1.76
1220 1.88
1237 2.00
1253 2.13

1.250 SP
RPM BHP
1038
.55
1045
.59
1053
.63
1062
.68
1071
.73
1080
.78
1089
.83
1098
.90
1108
.96
1119 1.03
1131 1.11
1145 1.18
1160 1.27
1176 1.35
1193 1.44
1210 1.54
1228 1.64
1245 1.75
1263 1.86
1280 1.97
1298 2.10
1315 2.22
1332 2.36

1.500 SP
Wheel
RPM BHP Effectiveness
1129
.67
84%
1135
.71
83%
1142
.76
82%
1150
.81
81%
1158
.86
80%
1167
.92
79%
1176
.98
78%
1186 1.04
77%
1195 1.11
76%
1204 1.18
76%
1214 1.26
75%
1225 1.35
74%
1237 1.44
73%
1250 1.53
72%
1265 1.63
71%
1281 1.73
71%
1297 1.83
70%
1314 1.95
69%
1332 2.07
68%
1349 2.19
67%
1367 2.32
67%
1384 2.45
66%
1402 2.59
65%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 3500 Exhaust


CFM

OV

1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500

891
960
1028
1097
1165
1234
1303
1371
1440
1508
1577
1645
1714
1783
1851
1920
1988
2057
2126
2194
2263
2331
2400

0.125 SP
RPM BHP
467
.12
485
.14
502
.16
520
.18
539
.21
558
.24
578
.27
599
.31
621
.35
642
.40
665
.45
687
.50
710
.56
733
.63
755
.69
779
.76
802
.84
825
.92
848
1.01
872
1.10
895
1.20
918
1.30
942
1.42

0.250 SP
RPM BHP
571
.17
587
.19
603
.22
620
.25
637
.28
654
.32
672
.36
689
.40
706
.44
724
.49
742
.54
761
.59
780
.65
800
.72
820
.79
841
.86
863
.94
884
1.03
906
1.12
928
1.22
951
1.32
973
1.43
996
1.55

0.375 SP
RPM BHP
659
.22
672
.25
686
.28
701
.31
717
.35
733
.39
750
.43
766
.48
783
.52
801
.58
818
.64
835
.70
852
.76
870
.83
888
.90
906
.97
924
1.05
943
1.14
963
1.23
983
1.33
1003 1.44
1024 1.55
1046 1.67

0.500 SP
RPM BHP
732
.27
748
.31
761
.34
774
.38
788
.42
802
.46
818
.50
834
.55
850
.61
867
.67
883
.73
900
.79
918
.86
935
.94
952
1.01
969
1.09
987
1.18
1004 1.27
1022 1.37
1040 1.47
1058 1.57
1077 1.68
1096 1.80

0.750 SP
RPM BHP
846
.38
863
.42
881
.46
898
.51
913
.56
927
.61
941
.66
954
.72
967
.77
982
.84
997
.91
1013
.98
1029 1.06
1046 1.14
1062 1.23
1079 1.32
1096 1.42
1113 1.52
1130 1.62
1148 1.74
1165 1.86
1182 1.98
1199 2.10

1.000 SP
RPM BHP

1.250 SP
RPM BHP

977
993
1011
1029
1045
1060
1074
1087
1100
1113
1128
1143
1158
1174
1190
1207
1224
1241
1257
1274
1292

1081
1096
1113
1130
1148
1165
1180
1194
1207
1220
1234
1247
1262
1276
1292
1308
1324
1340
1357
1374

.58
.63
.69
.75
.82
.88
.95
1.02
1.10
1.17
1.26
1.35
1.44
1.54
1.64
1.75
1.87
1.99
2.11
2.25
2.39

.77
.83
.90
.97
1.04
1.12
1.20
1.29
1.37
1.46
1.56
1.66
1.76
1.87
1.99
2.11
2.24
2.37
2.51
2.66

1.500 SP
Wheel
RPM BHP Effectiveness
84%
83%
82%
81%
80%
1191 1.05
79%
1207 1.12
78%
1224 1.20
77%
1242 1.29
76%
1259 1.38
76%
1276 1.47
75%
1291 1.57
74%
1305 1.67
73%
1319 1.78
72%
1332 1.88
71%
1345 1.99
71%
1358 2.11
70%
1372 2.23
69%
1387 2.36
68%
1402 2.49
67%
1417 2.63
67%
1433 2.78
66%
1449 2.93
65%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

24

Data 4500
2.5

Static Pressure (In W.G.)

Static Pressure (In W.G.)

4R

PM

PM

66-1/2

68
0

45

5 HP

RP

0.5

3 HP

1.0

PM
8R M
147
P
4R M
136 RP
M
50
12 6 RP M
3 RP
11
M
22
10 RP M
8
P
90 4 R
79

62

1.5

2 HP
P
1.5 H
1 HP
HP
P
.75
.5 H
P
HP
.334 H .25

413

2.0

PM
1R M
134 8 R P
M
1 2 3 RP
35
PM
11 2 R M
3
P
10
9 R PM
92 6 R M
P
82 3 R
72

1.0

5 HP

1.5

3 HP

2.0

0.5

69-1/2

ERV - 4500 Exhaust

2.5

2 HP
P
1.5 H

64-1/2

ERV - 4500 Supply

1 HP
HP
.75
.5 HP334 HP 5 HP
.
.2

Energy Recovery Wheel Diameter - 48


Belt Drive
Maximum RPM - 1478
Maximum MHP - 5
Maximum Motor Frame - 184T
Housing - 18 ga. steel
Base - 14 ga. steel
Shipping Weight (less motors) - 1111 lbs.

- ERV

R
PM

0
0

1500

3000
4500
Flow (CFM)

6000

7500

1500

3000
4500
Flow (CFM)

6000

7500

ERV - 4500 Supply


CFM

OV

1500
1650
1800
1950
2100
2250
2400
2550
2700
2850
3000
3150
3300
3450
3600
3750
3900
4050
4200
4350
4500

1028
1131
1234
1337
1440
1543
1645
1748
1851
1954
2057
2160
2263
2366
2468
2571
2674
2777
2880
2983
3086

0.125 SP
RPM BHP
413
.12
435
.15
457
.18
481
.22
505
.26
529
.31
554
.37
578
.42
604
.49
630
.57
656
.65
682
.74
709
.85
736
.96
763
1.08
790
1.21
818
1.35
845
1.50
873
1.66
900
1.83
928
2.02

0.250 SP
RPM BHP
508
.16
525
.20
543
.24
562
.28
582
.33
603
.39
625
.45
648
.51
671
.59
695
.67
719
.76
743
.85
767
.96
792
1.07
817
1.20
843
1.34
868
1.48
894
1.63
920
1.80
947
1.98
973
2.17

0.375 SP
RPM BHP
588
.21
602
.25
618
.29
635
.34
653
.39
671
.46
690
.52
709
.59
730
.68
752
.76
774
.86
797
.96
821
1.07
844
1.19
868
1.32
892
1.46
917
1.61
941
1.77
966
1.94
991
2.13
1016 2.32

0.500 SP
RPM BHP
663
.26
672
.30
685
.35
700
.40
716
.46
733
.52
750
.59
769
.67
787
.76
806
.85
827
.96
848
1.07
870
1.18
892
1.31
915
1.44
938
1.59
962
1.75
986
1.91
1009 2.09
1034 2.28
1058 2.48

0.750 SP
RPM BHP
798
.37
804
.42
810
.47
819
.53
830
.59
843
.66
858
.74
874
.83
891
.92
909
1.03
926
1.14
945
1.26
963
1.39
982
1.53
1002 1.68
1023 1.84
1044 2.00
1066 2.18
1089 2.37
1112 2.57
1135 2.79

1.000 SP
RPM BHP

1.250 SP
RPM BHP

917
925
931
937
945
956
969
983
999
1016
1033
1050
1068
1086
1105
1124
1143
1163
1184
1205

1022
1031
1037
1043
1050
1059
1070
1083
1098
1113
1129
1146
1164
1181
1199
1217
1236
1255
1274

.54
.60
.67
.73
.81
.89
.99
1.09
1.20
1.32
1.45
1.58
1.74
1.89
2.07
2.25
2.44
2.64
2.85
3.08

.73
.81
.89
.97
1.06
1.15
1.26
1.38
1.50
1.64
1.78
1.94
2.11
2.29
2.48
2.68
2.90
3.13
3.36

1.500 SP
Wheel
RPM BHP Effectiveness
85%
84%
83%
1118
.95
82%
1128 1.04
81%
1135 1.14
80%
1140 1.23
79%
1146 1.33
78%
1154 1.44
77%
1164 1.56
76%
1176 1.70
75%
1189 1.84
74%
1204 1.99
73%
1219 2.15
72%
1235 2.33
71%
1252 2.51
70%
1270 2.72
69%
1287 2.92
68%
1305 3.15
67%
1323 3.39
66%
1341 3.63
65%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 4500 Exhaust


CFM

OV

1500
1650
1800
1950
2100
2250
2400
2550
2700
2850
3000
3150
3300
3450
3600
3750
3900
4050
4200
4350
4500

1028
1131
1234
1337
1440
1543
1645
1748
1851
1954
2057
2160
2263
2366
2468
2571
2674
2777
2880
2983
3086

0.125 SP
RPM BHP
454
.14
477
.17
502
.21
529
.26
556
.31
583
.37
612
.43
641
.51
670
.59
700
.68
730
.78
761
.90
791
1.02
822
1.15
853
1.29
885
1.46
917
1.63
948
1.81
980
2.01
1012 2.22
1044 2.45

0.250 SP
RPM BHP
558
.20
579
.24
599
.28
618
.33
639
.39
662
.45
686
.52
711
.60
737
.69
764
.79
791
.90
819
1.01
847
1.14
876
1.28
905
1.43
934
1.59
964
1.77
994
1.96
1024 2.16
1055 2.38
1085 2.60

0.375 SP
RPM BHP
642
.25
659
.30
679
.35
700
.41
720
.47
739
.54
759
.62
779
.70
802
.79
825
.90
850
1.01
876
1.14
902
1.27
928
1.41
955
1.57
983
1.74
1011 1.92
1039 2.11
1068 2.32
1097 2.54
1126 2.77

0.500 SP
RPM BHP
724
.32
735
.36
749
.41
767
.48
787
.55
808
.62
828
.71
847
.80
867
.90
887
1.00
908
1.12
931
1.25
955
1.39
979
1.54
1004 1.70
1030 1.87
1057 2.06
1084 2.26
1111 2.48
1139 2.70
1167 2.95

0.750 SP
RPM BHP
863
.45
876
.51
885
.57
894
.63
907
.70
922
.79
941
.88
961
.99
981
1.10
1002 1.22
1022 1.35
1041 1.49
1061 1.64
1080 1.80
1101 1.97
1123 2.15
1147 2.36
1170 2.56
1195 2.79
1220 3.03
1246 3.28

1.000 SP
RPM BHP
965
.57
987
.65
1004
.73
1015
.81
1023
.88
1033
.97
1045 1.07
1060 1.18
1077 1.29
1097 1.43
1117 1.57
1138 1.73
1158 1.89
1178 2.06
1197 2.25
1217 2.44
1236 2.65
1257 2.87
1278 3.10
1300 3.35
1323 3.61

1.250 SP
RPM BHP
1052
.69
1075
.78
1097
.88
1116
.98
1129 1.08
1139 1.17
1147 1.27
1157 1.38
1169 1.50
1184 1.64
1202 1.79
1221 1.95
1241 2.13
1262 2.32
1283 2.52
1303 2.73
1323 2.95
1342 3.18
1361 3.42
1381 3.68
1401 3.95

1.500 SP
Wheel
RPM BHP Effectiveness
1133
.82
85%
1153
.91
84%
1176 1.02
83%
1199 1.14
82%
1219 1.26
81%
1233 1.38
80%
1244 1.49
79%
1252 1.61
78%
1261 1.73
77%
1272 1.87
76%
1285 2.02
75%
1301 2.19
74%
1318 2.37
73%
1337 2.56
72%
1358 2.78
71%
1378 3.00
70%
1399 3.24
69%
1420 3.49
68%
1439 3.74
67%
1459 4.02
66%
1478 4.30
65%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 1, Port 3 with Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

25

ERV - 5500 Data


ERV - 5500 Exhaust

2.5
P

Static Pressure (In W.G.)

5H

3 HP

48

97

89

81

4R

RP

RP

7 R PM
PM
0R
PM
663
586 RPM
509 RPM
RP
M
351
RP
M

1.0

0.5

56 647
1
RP RP
392
RP
M M
M

10

1.5

P
.5 H 34 HP25 HP
.
.3

0.5

2 HP
P
H
1.5
P
1H
.75 HP

1.0

2.0

M
RP RPM
63
PM
11 1077
1R
99 RPM
M
5
RP
90
9
81 RPM
3
73

1 HP.75 HP
P
.5 HP334 HP.25 H
.

1.5

5 HP

3 HP

2 HP HP
1.5

2.0
Static Pressure (In W.G.)

Energy Recovery Wheel Diameter - 54


Belt Drive
Maximum RPM - 1163
Maximum MHP - 5
Maximum Motor Frame - 184T
Housing - 18 ga. steel
Base - 14 ga. steel
Shipping Weight (less motors) - 1235 lbs.

ERV - 5500 Supply

2.5

74

71

0
0

1600

3200
4800
Flow (CFM)

6400

8000

1600

3200
4800
Flow (CFM)

6400

8000

69-1/2

66-1/2

ERV - 5500 Supply


CFM

OV

2350
2500
2650
2800
2950
3100
3250
3400
3550
3700
3850
4000
4150
4300
4450
4600
4750
4900
5050
5200
5350
5500

1096
1166
1236
1306
1376
1446
1516
1586
1656
1726
1796
1866
1936
2006
2076
2146
2216
2286
2356
2426
2496
2566

0.125 SP
RPM BHP
351
.22
364
.26
379
.30
395
.34
412
.40
430
.46
447
.52
465
.59
484
.67
502
.76
520
.85
538
.94
557
1.05
576
1.17
594
1.28
613
1.42
631
1.55
650
1.70
669
1.86
689
2.04
708
2.21
727
2.40

0.250 SP
RPM BHP
433
.30
441
.34
452
.39
462
.44
472
.49
482
.54
491
.60
503
.66
517
.74
532
.82
547
.90
564
1.00
581
1.11
598
1.22
616
1.35
633
1.48
651
1.62
669
1.77
688
1.93
706
2.10
724
2.28
742
2.46

0.375 SP
RPM BHP
506
.40
513
.44
520
.48
526
.53
534
.58
543
.65
554
.72
564
.79
574
.86
584
.94
593
1.02
603
1.11
615
1.21
628
1.31
642
1.43
658
1.56
674
1.70
691
1.85
708
2.01
724
2.17
742
2.35
760
2.54

0.500 SP
RPM BHP

0.750 SP
RPM BHP

1.000 SP
RPM BHP

1.250 SP
RPM BHP

581
588
595
602
608
616
625
635
646
657
667
676
685
695
707
719
734
748
764
780

711
719
726
733
739
746
754
763
773
783
794
804
814
824
833
842

819
826
834
841
847
854
860
868
877
886
896
907
918

916
924
931
938
945
951
958
965
973
981

.59
.64
.69
.76
.82
.90
.98
1.07
1.16
1.27
1.37
1.47
1.58
1.69
1.82
1.95
2.11
2.27
2.44
2.63

1.08
1.16
1.24
1.33
1.42
1.52
1.64
1.76
1.89
2.03
2.18
2.32
2.48
2.64
2.79
2.95

1.63
1.73
1.84
1.95
2.06
2.20
2.33
2.48
2.64
2.80
2.98
3.17
3.37

2.29
2.42
2.55
2.68
2.83
2.98
3.15
3.32
3.51
3.71

1.500 SP
Wheel
RPM BHP Effectiveness
83%
82%
81%
80%
79%
78%
78%
77%
76%
75%
74%
74%
73%
72%
999
2.92
71%
1006 3.06
71%
1014 3.22
70%
1021 3.38
69%
1028 3.54
69%
1035 3.72
68%
1041 3.90
67%
1048 4.10
66%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 5500 Exhaust


CFM

OV

2350
2500
2650
2800
2950
3100
3250
3400
3550
3700
3850
4000
4150
4300
4450
4600
4750
4900
5050
5200
5350
5500

1096
1166
1236
1306
1376
1446
1516
1586
1656
1726
1796
1866
1936
2006
2076
2146
2216
2286
2356
2426
2496
2566

0.125 SP
RPM BHP
392
.28
407
.32
422
.37
438
.42
454
.48
470
.54
486
.61
502
.69
519
.77
535
.86
552
.96
569
1.06
586
1.17
603
1.29
621
1.42
639
1.56
656
1.70
674
1.85
692
2.01
710
2.18
728
2.37
746
2.56

0.250 SP
RPM BHP
480
.38
488
.43
497
.48
507
.53
519
.59
532
.66
547
.74
561
.82
577
.91
592
1.00
608
1.11
624
1.22
640
1.34
655
1.46
672
1.60
688
1.74
704
1.89
720
2.04
737
2.22
753
2.39
770
2.58
787
2.78

0.375 SP
RPM BHP
560
.51
568
.56
576
.61
584
.67
592
.74
600
.81
609
.88
619
.96
630
1.05
643
1.15
657
1.26
671
1.37
686
1.49
701
1.62
717
1.77
733
1.92
748
2.07
764
2.24
780
2.41
796
2.60
812
2.80
828
3.00

0.500 SP
RPM BHP
627
.63
635
.69
643
.75
651
.82
659
.89
667
.97
675
1.04
683
1.13
691
1.22
700
1.32
709
1.42
720
1.54
732
1.66
745
1.79
759
1.94
773
2.09
788
2.25
803
2.42
819
2.61
834
2.80
850
3.00
866
3.22

0.750 SP
RPM BHP
734
.86
745
.94
755
1.02
764
1.11
772
1.20
780
1.29
788
1.39
796
1.49
804
1.59
812
1.70
820
1.82
828
1.94
836
2.06
844
2.20
852
2.34
861
2.49
871
2.65
882
2.83
893
3.00
907
3.21
920
3.41
934
3.63

1.000 SP
RPM BHP
819
1.09
831
1.18
842
1.28
854
1.38
864
1.49
874
1.60
883
1.72
891
1.84
899
1.96
907
2.09
915
2.22
923
2.36
931
2.50
939
2.65
947
2.80
955
2.96
963
3.13
971
3.31
979
3.49
988
3.69
997
3.89
1007 4.11

1.250 SP
RPM BHP
894
1.32
906
1.43
917
1.54
929
1.65
941
1.78
952
1.91
963
2.04
973
2.18
982
2.32
991
2.47
999
2.62
1007 2.77
1014 2.93
1022 3.09
1030 3.26
1038 3.44
1047 3.63
1055 3.82
1063 4.01
1071 4.22
1079 4.43
1087 4.65

1.500 SP
Wheel
RPM BHP Effectiveness
963
1.55
83%
974
1.67
82%
985
1.80
81%
997
1.93
80%
1009 2.07
79%
1020 2.21
78%
1032 2.36
78%
1043 2.51
77%
1054 2.67
76%
1064 2.83
75%
1074 3.01
74%
1082 3.17
74%
1091 3.36
73%
1098 3.53
72%
1106 3.73
71%
1114 3.92
71%
1122 4.12
70%
1130 4.33
69%
1138 4.54
69%
1146 4.76
68%
1155 5.00
67%
1163 5.23
66%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

26

Data 7000
ERV - 7000 Exhaust

2.5

Static Pressure (In W.G.)

Static Pressure (In W.G.)

80

6
53 11 R
3
P
45
5 RP M
30
RP M
1R
M
PM

0.5

79-1/2

M
RP
01
10 RPM
3 PM
92
5R M
84 RP
M
7
76 RP
9
68

1.0

7.5 H

1.5

5 HP

57
4 0
42 98 RP
6 RP M
279
RP M
RP
M
M

0.5

P
3H

PM
0 R PM
93
8R
85 RPM
6
PM
78
4R M
71 RP
2
64

1.0

2.0

2 HP
P
1.5 H
HP
1 HP
.75
HP HP
.5 HP
.334 .25

1.5

7.5 HP

2.0

2.5
5 HP

76-1/2

ERV - 7000 Supply

3 HP
2 HP
P
1.5 H
1 HP.75 HP P
.5 H 4 HP.25 HP
.33

Energy Recovery Wheel Diameter - 60


Belt Drive
Maximum RPM - 1001
Maximum MHP - 7-1/2
Maximum Motor Frame - 184T
Housing - 16 ga. steel
Base - 12 ga. steel
Shipping Weight (less motors) - 1609 lbs.

- ERV

0
0

2500

5000 7500
Flow (CFM)

10000 12500

2500

5000
7500
Flow (CFM)

10000 12500

ERV - 7000 Supply


CFM

OV

2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
5500
5750
6000
6250
6500
6750
7000

784
871
959
1046
1133
1220
1307
1395
1482
1569
1656
1743
1830
1918
2005
2092
2179
2266
2354
2441

0.125 SP
RPM BHP
279
.15
288
.18
300
.21
314
.26
330
.31
346
.37
362
.44
378
.52
393
.60
409
.69
426
.80
443
.91
460
1.03
478
1.17
496
1.32
515
1.49
534
1.68
552
1.87
572
2.09
591
2.31

0.250 SP
RPM BHP
352
.22
362
.26
374
.31
387
.37
397
.43
406
.49
417
.56
430
.64
445
.74
461
.84
477
.96
493
1.08
509
1.22
524
1.36
540
1.52
555
1.68
571
1.86
588
2.07
604
2.27
621
2.50

0.375 SP
RPM BHP
416
.30
423
.35
431
.40
441
.46
453
.54
465
.62
477
.71
487
.79
496
.89
506
.99
518
1.10
533
1.24
548
1.38
564
1.54
580
1.71
596
1.90
612
2.09
628
2.31
643
2.52
659
2.76

0.500 SP
RPM BHP
471
.39
478
.45
484
.50
492
.57
501
.64
511
.73
523
.83
535
.93
547
1.05
558
1.17
568
1.29
577
1.42
587
1.55
599
1.71
614
1.89
629
2.08
645
2.29
661
2.51
677
2.75
693
3.00

0.750 SP
RPM BHP
560
.55
569
.63
577
.72
583
.80
590
.88
597
.97
605
1.07
614
1.19
624
1.31
636
1.46
648
1.61
660
1.78
672
1.96
683
2.14
693
2.32
702
2.51
711
2.70
722
2.91
735
3.16
749
3.42

1.000 SP
RPM BHP
635
.70
643
.80
652
.91
660
1.03
668
1.14
675
1.24
681
1.35
688
1.47
696
1.61
704
1.75
714
1.91
725
2.09
737
2.29
749
2.50
761
2.72
773
2.95
784
3.19
795
3.44
804
3.68
813
3.93

1.250 SP
RPM BHP
710
717
726
735
743
750
757
763
770
778
786
796
806
818
830
842
855
866
878

.98
1.09
1.23
1.38
1.52
1.65
1.79
1.92
2.07
2.24
2.42
2.62
2.84
3.08
3.33
3.60
3.89
4.17
4.48

1.500 SP
Wheel
RPM BHP Effectiveness
86%
84%
778
1.29
83%
786
1.44
82%
794
1.59
81%
803
1.77
80%
811
1.94
79%
819
2.10
78%
825
2.26
77%
832
2.42
76%
839
2.60
74%
846
2.78
73%
854
2.99
72%
862
3.20
71%
872
3.45
70%
882
3.70
70%
894
3.99
69%
906
4.29
68%
918
4.61
67%
930
4.94
66%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 7000 Exhaust


CFM

OV

2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
5500
5750
6000
6250
6500
6750
7000

784
871
959
1046
1133
1220
1307
1395
1482
1569
1656
1743
1830
1918
2005
2092
2179
2266
2354
2441

0.125 SP
RPM BHP
301
.17
315
.22
330
.27
345
.32
360
.38
376
.45
393
.53
411
.63
428
.73
447
.85
466
.98
485
1.13
504
1.28
523
1.45
543
1.64
563
1.85
583
2.07
603
2.30
623
2.56
644
2.84

0.250 SP
RPM BHP
381
.27
391
.32
403
.37
416
.44
430
.51
444
.60
458
.69
473
.80
488
.91
504
1.04
519
1.16
536
1.32
553
1.48
570
1.66
587
1.85
605
2.06
624
2.30
642
2.54
661
2.81
680
3.09

0.375 SP
RPM BHP
449
.37
457
.42
466
.49
477
.56
488
.64
501
.74
514
.84
527
.95
541
1.08
556
1.22
570
1.37
585
1.53
600
1.70
616
1.89
632
2.09
648
2.30
665
2.54
681
2.78
699
3.06
716
3.34

0.500 SP
RPM BHP
508
.48
515
.54
523
.61
531
.69
541
.78
552
.88
564
.99
576
1.11
589
1.24
602
1.39
616
1.55
630
1.73
645
1.92
660
2.13
674
2.33
690
2.57
705
2.81
721
3.07
737
3.34
753
3.63

0.750 SP
RPM BHP
604
.71
614
.80
622
.89
629
.98
636
1.07
645
1.18
654
1.31
664
1.45
674
1.59
686
1.76
698
1.93
711
2.12
724
2.32
737
2.54
751
2.78
765
3.04
779
3.31
794
3.61
809
3.92
824
4.25

1.000 SP
RPM BHP
681
.95
694
1.06
704
1.17
713
1.29
720
1.40
728
1.52
735
1.65
743
1.79
752
1.96
761
2.13
772
2.33
783
2.53
794
2.75
807
2.99
819
3.23
832
3.49
846
3.79
859
4.09
873
4.43
887
4.78

1.250 SP
RPM BHP
746
1.18
761
1.32
773
1.45
784
1.59
794
1.74
802
1.88
809
2.03
816
2.18
823
2.34
831
2.52
840
2.73
850
2.95
860
3.19
871
3.44
883
3.72
895
4.00
907
4.29
920
4.61
933
4.95
946
5.31

1.500 SP
Wheel
RPM BHP Effectiveness
803
1.42
86%
819
1.57
84%
834
1.73
83%
847
1.90
82%
858
2.07
81%
867
2.24
80%
875
2.41
79%
883
2.59
78%
890
2.77
77%
897
2.95
76%
905
3.16
74%
913
3.39
73%
922
3.63
72%
932
3.91
71%
942
4.19
70%
953
4.49
70%
965
4.82
69%
976
5.14
68%
989
5.51
67%
1001 5.87
66%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

27

ERV - 8500 Data


ERV - 8500 Exhaust

2.5

2500

Static Pressure (In W.G.)

31

1R

83

PM

PM

0
0

45

7.5 HP

PM

RP

P
5H

4R

0.5

M
RP
958 RPM
6
PM
88
4 R PM
81
2 R PM
74
0R M
67 RP M
8 P
59 6 R
52

32

1.0

3 HP

47

1.5

2 HP .5 HP
1
P
1 H.7
5 HP
P
HP HP
.5 H .334 .25

0.5

2.0

PM
M
3R
100 8 RP M
P
92
3 R PM
85
8R M
77 RP
M
3
70 RP M
8 P
62 R
3
55

1.0

P
7.5 H

1.5

5 HP

3 HP
2 HP
1.5 HP P
1 H .75 HP HP HP HP
.5 334 .25
.

2.0
Static Pressure (In W.G.)

Energy Recovery Wheel Diameter - 66


Belt Drive
Maximum RPM - 1003
Maximum MHP - 7-1/2
Maximum Motor Frame - 184T
Housing - 16 ga. steel
Base - 12 ga. steel
Shipping Weight (less motors) - 1734 lbs.

ERV - 8500 Supply

2.5

5000 7500
Flow (CFM)

10000 12500

2500

5000 7500
Flow (CFM)

10000 12500

79-1/2

80

ERV - 8500 Supply


CFM

OV

3100
3400
3700
4000
4300
4600
4900
5200
5500
5800
6100
6400
6700
7000
7300
7600
7900
8200
8500

1081
1185
1290
1395
1499
1604
1708
1813
1918
2022
2127
2232
2336
2441
2545
2650
2755
2859
2964

0.125 SP
RPM BHP
311
.26
329
.33
346
.40
365
.49
384
.58
404
.69
424
.82
444
.96
465
1.12
486
1.29
507
1.48
528
1.69
550
1.92
572
2.18
593
2.44
616
2.75
637
3.06
659
3.40
681
3.77

0.250 SP
RPM BHP
373
.35
388
.42
403
.51
419
.60
436
.71
453
.83
470
.96
488
1.11
506
1.28
525
1.46
544
1.66
564
1.88
584
2.12
604
2.38
624
2.65
645
2.96
666
3.29
687
3.65
708
4.02

0.375 SP
RPM BHP
427
.45
439
.52
452
.61
467
.72
482
.83
497
.96
513
1.11
530
1.27
547
1.45
564
1.63
582
1.85
600
2.08
618
2.32
637
2.59
656
2.88
675
3.19
695
3.53
715
3.89
735
4.27

0.500 SP
RPM BHP
479
.55
487
.63
497
.72
510
.83
523
.95
538
1.09
553
1.25
568
1.41
584
1.60
601
1.81
617
2.02
634
2.26
651
2.51
669
2.80
687
3.10
705
3.41
724
3.76
743
4.13
762
4.53

0.750 SP
RPM BHP
580
.82
581
.89
585
.98
591
1.09
600
1.21
612
1.37
624
1.53
638
1.71
652
1.91
667
2.13
682
2.37
698
2.63
714
2.91
730
3.21
746
3.52
763
3.87
780
4.23
797
4.61
815
5.03

1.000 SP
RPM BHP
662
1.09
668
1.20
670
1.30
672
1.40
676
1.52
682
1.66
691
1.83
702
2.03
714
2.24
727
2.47
741
2.72
755
2.99
770
3.28
786
3.61
801
3.94
817
4.31
833
4.69
849
5.10
866
5.54

1.250 SP
RPM BHP
730
1.33
739
1.49
745
1.63
748
1.76
750
1.88
752
2.01
757
2.18
764
2.36
773
2.58
784
2.82
796
3.08
809
3.36
823
3.67
837
4.00
852
4.36
867
4.74
882
5.14
898
5.57
913
6.01

1.500 SP
Wheel
RPM BHP Effectiveness
791
1.57
84%
800
1.75
83%
808
1.93
82%
815
2.11
81%
819
2.27
80%
821
2.42
79%
823
2.57
78%
827
2.75
76%
832
2.95
75%
840
3.19
74%
850
3.46
73%
861
3.75
72%
873
4.07
71%
886
4.41
70%
900
4.78
69%
914
5.17
68%
928
5.58
68%
943
6.03
67%
958
6.50
66%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 8500 Exhaust


CFM

OV

3100
3400
3700
4000
4300
4600
4900
5200
5500
5800
6100
6400
6700
7000
7300
7600
7900
8200
8500

1081
1185
1290
1395
1499
1604
1708
1813
1918
2022
2127
2232
2336
2441
2545
2650
2755
2859
2964

0.125 SP
RPM BHP
324
.30
342
.37
361
.46
380
.55
400
.66
421
.79
442
.94
463
1.10
484
1.27
506
1.48
527
1.69
549
1.93
571
2.19
592
2.47
615
2.79
637
3.12
659
3.48
681
3.86
703
4.27

0.250 SP
RPM BHP
393
.41
406
.49
421
.58
436
.69
453
.81
471
.95
489
1.10
508
1.27
527
1.46
547
1.67
567
1.89
588
2.15
609
2.43
630
2.73
651
3.05
672
3.39
693
3.76
715
4.17
736
4.59

0.375 SP
RPM BHP
453
.53
464
.62
477
.72
490
.84
504
.96
519
1.11
534
1.26
551
1.44
569
1.65
587
1.87
605
2.10
624
2.36
644
2.65
663
2.95
683
3.28
704
3.65
724
4.02
745
4.44
766
4.88

0.500 SP
RPM BHP
507
.65
517
.75
528
.86
539
.98
552
1.13
565
1.28
579
1.45
593
1.63
609
1.84
625
2.06
642
2.31
659
2.57
677
2.86
696
3.18
715
3.53
734
3.89
754
4.29
774
4.72
794
5.17

0.750 SP
RPM BHP
599
.89
609
1.01
618
1.14
628
1.29
638
1.45
649
1.63
660
1.81
673
2.02
686
2.24
699
2.47
713
2.73
728
3.02
744
3.33
760
3.67
776
4.01
793
4.40
811
4.81
829
5.25
848
5.73

1.000 SP
RPM BHP
677
1.15
686
1.28
696
1.43
705
1.60
715
1.78
724
1.97
734
2.18
745
2.41
756
2.65
768
2.91
781
3.20
794
3.49
808
3.82
822
4.17
836
4.53
852
4.94
867
5.36
884
5.83
901
6.32

1.250 SP
RPM BHP
747
1.42
755
1.57
764
1.73
773
1.91
783
2.11
793
2.33
802
2.56
812
2.81
822
3.07
832
3.35
844
3.66
855
3.97
868
4.32
881
4.69
894
5.07
908
5.49
922
5.93
937
6.40
952
6.90

1.500 SP
Wheel
RPM BHP Effectiveness
810
1.71
84%
818
1.87
83%
827
2.05
82%
836
2.24
81%
845
2.45
80%
854
2.68
79%
864
2.94
78%
873
3.20
76%
883
3.50
75%
893
3.80
74%
903
4.12
73%
914
4.47
72%
925
4.83
71%
937
5.22
70%
949
5.62
69%
962
6.06
68%
975
6.51
68%
989
7.01
67%
1003 7.52
66%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

28

Data 10000
2.5

2.5

Static Pressure (In W.G.)

Static Pressure (In W.G.)

6R

84-1/2

3000

6000 9000
Flow (CFM)

12000 15000

PM

100

42

3000

P
10 H
P

28

RP
M

7.5 H

0.5

M
RP
908 PM
R
PM
839
0 R PM
77
1R M
70
P
2 R PM
63 3 R M
56 RP
4
49

1.0

P
5H

PM

1.5

3 HP
P
2 HP
1.5 H P
P HP
P
1 H .75 H .5 HP334 H
.25
.

0R

40
6

27

2.0

M
RP
868 PM
R
802
PM
6R
73 RPM
0
PM
67
4R M
60 RP
M
8
53 RP
2
47

0.5

P
7.5 H

1.0

10 H

1.5

2.0

5H

90

ERV - 10000 Exhaust

ERV - 10000 Supply

3 HP
2 HP
P
1.5 H
P P
P
P
1 H .75 H 5 HP 334 H25 H
.
.
.

Energy Recovery Wheel Diameter - 72


Belt Drive
Maximum RPM - 908
Maximum MHP - 10
Maximum Motor Frame - 215T
Housing - 16 ga. steel
Base - 10 ga. steel
Shipping Weight (less motors) - 2817 lbs.

- ERV

PM

6000 9000
Flow (CFM)

12000 15000

ERV - 10000 Supply


CFM

OV

3400
3700
4000
4300
4600
4900
5200
5500
5800
6100
6400
6700
7000
7300
7600
7900
8200
8500
8800
9100
9400
9700
10000

799
869
940
1010
1081
1151
1222
1292
1363
1433
1504
1575
1645
1716
1786
1857
1927
1998
2068
2139
2209
2280
2350

0.125 SP
RPM BHP
270
.26
282
.31
296
.38
309
.45
324
.53
338
.62
353
.72
368
.84
383
.96
398
1.10
414
1.25
430
1.42
445
1.59
461
1.78
477
1.99
493
2.22
509
2.46
525
2.71
542
3.00
558
3.29
574
3.61
590
3.93
607
4.30

0.250 SP
RPM BHP
330
.37
341
.43
351
.50
362
.58
373
.66
385
.76
398
.87
411
.99
425
1.13
439
1.28
453
1.44
467
1.61
482
1.80
496
2.00
511
2.22
526
2.46
542
2.72
557
2.99
572
3.27
588
3.59
604
3.92
619
4.25
635
4.63

0.375 SP
RPM BHP
381
.49
389
.56
399
.64
409
.72
420
.82
431
.93
441
1.04
452
1.16
464
1.30
476
1.46
489
1.63
502
1.81
515
2.00
529
2.21
543
2.44
557
2.69
572
2.96
586
3.23
601
3.54
616
3.86
631
4.20
646
4.55
661
4.93

0.500 SP
RPM BHP
429
.61
435
.69
442
.78
450
.87
460
.97
471
1.09
481
1.21
492
1.35
502
1.49
513
1.65
524
1.82
536
2.01
548
2.21
561
2.44
574
2.67
587
2.92
601
3.20
614
3.47
628
3.78
643
4.13
657
4.47
671
4.83
686
5.22

0.750 SP
RPM BHP
510
.88
516
.97
522
1.07
528
1.18
534
1.30
541
1.42
550
1.57
559
1.71
569
1.88
580
2.06
590
2.24
601
2.45
611
2.66
622
2.89
633
3.14
644
3.40
656
3.69
668
3.99
681
4.32
693
4.64
707
5.02
720
5.40
734
5.81

1.000 SP
RPM BHP
582
1.15
586
1.27
591
1.39
596
1.51
602
1.64
608
1.78
614
1.93
621
2.10
629
2.28
637
2.46
647
2.67
657
2.89
668
3.13
678
3.37
689
3.64
700
3.93
710
4.21
721
4.53
732
4.87
743
5.21
755
5.59
767
5.99
779
6.40

1.250 SP
RPM BHP
649
653
657
663
669
675
680
687
693
701
709
719
728
739
749
760
770
781
792
802
813
824

1.56
1.70
1.85
2.00
2.16
2.33
2.50
2.70
2.90
3.12
3.35
3.61
3.86
4.15
4.44
4.76
5.08
5.44
5.82
6.19
6.60
7.02

1.500 SP
Wheel
RPM BHP Effectiveness
85%
84%
710
2.01
83%
714
2.19
82%
718
2.36
81%
723
2.54
80%
729
2.73
79%
735
2.92
78%
741
3.13
77%
747
3.35
77%
753
3.58
76%
760
3.83
75%
767
4.09
74%
776
4.38
73%
785
4.67
72%
795
4.98
71%
805
5.31
71%
815
5.65
70%
826
6.02
69%
837
6.42
68%
847
6.81
67%
858
7.24
67%
868
7.67
66%

Gross supply air performance ratings (airflow, pressure and power) are at Port 2 with Port 1, Port 3, and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

ERV - 10000 Exhaust


CFM

OV

3400
3700
4000
4300
4600
4900
5200
5500
5800
6100
6400
6700
7000
7300
7600
7900
8200
8500
8800
9100
9400
9700
10000

799
869
940
1010
1081
1151
1222
1292
1363
1433
1504
1575
1645
1716
1786
1857
1927
1998
2068
2139
2209
2280
2350

0.125 SP
RPM BHP
286
.31
301
.37
316
.44
331
.53
347
.62
362
.72
378
.84
394
.97
411
1.12
427
1.27
444
1.45
461
1.64
478
1.84
495
2.06
513
2.31
530
2.57
547
2.84
565
3.14
583
3.47
601
3.82
618
4.17
636
4.56
654
4.97

0.250 SP
RPM BHP
344
.43
355
.50
367
.58
380
.68
394
.79
409
.91
423
1.03
439
1.18
454
1.33
469
1.50
485
1.69
500
1.88
516
2.10
532
2.34
548
2.59
565
2.87
581
3.16
597
3.46
614
3.80
631
4.16
648
4.54
665
4.94
682
5.36

0.375 SP
RPM BHP
395
.56
405
.64
415
.73
426
.83
437
.95
450
1.08
463
1.22
476
1.37
491
1.54
505
1.72
520
1.92
535
2.13
551
2.37
566
2.61
581
2.87
597
3.16
613
3.47
628
3.78
644
4.13
660
4.49
676
4.88
693
5.31
709
5.73

0.500 SP
RPM BHP
441
.70
449
.79
459
.89
469
1.00
479
1.12
489
1.25
501
1.40
513
1.57
525
1.74
539
1.94
552
2.14
567
2.38
581
2.61
596
2.87
611
3.15
626
3.44
642
3.77
657
4.10
673
4.46
688
4.83
704
5.24
720
5.67
735
6.10

0.750 SP
RPM BHP
528
1.01
531
1.11
536
1.22
543
1.34
552
1.48
562
1.63
572
1.80
582
1.97
592
2.16
603
2.37
614
2.59
626
2.84
639
3.11
652
3.39
666
3.70
680
4.02
694
4.36
708
4.71
723
5.09
738
5.50
753
5.92
768
6.36
784
6.85

1.000 SP
RPM BHP

1.250 SP
RPM BHP

608
610
613
618
626
634
644
654
663
673
683
694
706
718
730
743
756
770
784
798
812
827

679
681
683
687
693
700
709
718
728
738
747
758
768
779
791
803
815
828
841
854
868

1.47
1.59
1.72
1.86
2.03
2.20
2.40
2.62
2.83
3.07
3.32
3.60
3.91
4.23
4.56
4.93
5.31
5.73
6.16
6.60
7.06
7.57

1.99
2.14
2.29
2.46
2.65
2.85
3.08
3.31
3.58
3.85
4.13
4.45
4.77
5.12
5.51
5.92
6.34
6.79
7.26
7.75
8.28

1.500 SP
Wheel
RPM BHP Effectiveness
85%
84%
83%
743
2.56
82%
745
2.74
81%
747
2.92
80%
750
3.11
79%
755
3.33
78%
761
3.55
77%
769
3.81
77%
778
4.09
76%
787
4.37
75%
797
4.69
74%
807
5.02
73%
817
5.36
72%
827
5.73
71%
837
6.11
71%
848
6.52
70%
859
6.96
69%
871
7.43
68%
883
7.92
67%
895
8.42
67%
908
8.98
66%

Gross exhaust air performance ratings (airflow, pressure and power) are to Port 3 with Port 1, Port 2 and Port 4 at 0.0 In. W.G. Power rating (BHP) does not include drive losses.
Performance ratings include the effects of filters in the airstream.

29

ERC Energy Recovery Cassette


ERC
The Cook model ERC (Energy Recovery Cassette) offers an alternative way to incorporate an Energy Recovery Wheel into an HVAC
system. The ERC houses an Energy Recovery Wheel Cassette and provides 1 inch duct flanges for attachment of both the intake and
exhaust air ductwork. The housing is fully insulated and includes an access door allowing the wheel cassette to slide out for cleaning and
maintenance. The ERC also includes a wiring box, a twistlock wheel motor disconnect plug, and mounting brackets.

Installation
The ERC must be installed with the wheel oriented vertically. It is important that filters are provided to maintain the efficiency of the
energy recovery wheel. Refer to ERV Installation, Operation and Maintenance manual for cassette clearance dimensions.

A
C

E
2-3/8"

Size

ERC-500
ERC-1000
ERC-1500
ERC-2500
ERC-3500
ERC-4500
ERC-5500
ERC-7000
ERC-8500
ERC-10000

27-5/16
32-5/16
52-3/16
54-11/16
63-1/2
69-11/16
69-11/16
82-11/16
82-11/16
87-1/4

22-5/8
28-5/8
35-5/8
45-5/8
51-5/8
57-5/8
63-5/8
69-5/8
75-5/8
81-5/8

16-5/8
16-5/8
18-9/16
18-9/16
18-9/16
18-9/16
18-9/16
21-1/8
21-1/8
27-7/8

Duct Connection
D
E
19-9/16 8-15/16
25-9/16 11-7/16
32-9/16
21-3/8
42-9/16
22-5/8
48-9/16
27
54-9/16
30-1/8
60-9/16
30-1/8
66-9/16
36-5/8
72-9/16
36-5/8
78-9/16
38-7/8

Approx.
Ship. Wt.
120
163
278
379
466
553
636
781
868
1064

All weights in pounds.

Typical
Mounting Detail

30

Optional vibration
isolation

Performance Data ERC


Pressure Drop
Pressure Drop vs. CFM
0.8

0.7

0.7

0.6

0.6
SP (IN. W.G.)

SP (IN. W.G.)

Pressure Drop vs. CFM


0.8

0.5
0.4
0.3
ERC-500
ERC-1000
ERC-1500
ERC-2500
ERC-3500

0.2
0.1

0.5
0.4
0.3
ERC-4500
ERC-5500
ERC-7000
ERC-8500
ERC-10000

0.2
0.1
0

Effectiveness vs. CFM

Effectiveness vs. CFM


85

85
ERC-500
ERC-1000
ERC-1500
ERC-2500
ERC-3500

80

Percent Effectiveness

Percent Effectiveness

11000

10000

9000

8000

7000

6000

5000

4000

3000

2000

1000

3750

3500

3250

3000

2750

2500

2250

2000

1750

1500

1250

1000

750

500

250

CFM

CFM

Effectiveness

75

70

ERC-4500
ERC-5500
ERC-7000
ERC-8500
ERC-10000

80

75

70

65

CFM

CFM

Dimensions - Direct Drive


Mounting Housing
Rail Length
Width
A
B
ERV 500
52
22
ERV 1000
52
26
Unit

Housing
Height
C
23-13/16
28-13/16

Exhaust Opening
D
7
10-3/8

E
5-11/16
6-7/8

Mounting
Holes
J
K
H
50
4
5-5/16
50
6-11/16 11-7/16

Intake Opening
F
7
7

G
12
20

1-1/2
1-1/2

4
4

All dimensions in inches.

B
E

A
Exhaust Air
Discharge

Right

Outdoor Air
Intake

Back
G

Right View
Front

Hinged Access to
All Internal Components
Left

Removable Plug
For Field
Electrical
Connections
(Bottom Panel)

31

G
Return Air
Intake
Supply Air
Discharge

Left View

10500

10000

9500
9000

8500

8000

7500
7000

6500

6000

5500

5000
4500

4000

3500

3000
2500

2000

3500

3250

3000

2750

2500

2250

2000

1750

1500

1250

1000

750

500

250

1500

65

ERV Belt Drive Ductwork Connections


Size

Std. w/coils

1500 40-1/2 49-1/4 54-1/4


2500 50
52
52
3500 59 60-1/2 64-1/2
4500 64-1/2 66-1/2 69-1/2
5500 71 66-1/2 69-1/2
7000 75-1/2 80 79-1/2
8500 83
80 79-1/2
10000 90 84-1/2 100

F G H J

90-1/4 10-1/4 11-13/16 18 14 14 18 19


13
5-5/16
6
5-1/8 18/5/8 6/1/8 21-1/8 6-1/16 6-11/16 3-3/16 3
4-1/16 15-5/8
88
11-3/8 13-1/8 28 20 20 28 22 12-3/4 9-7/8
7-3/8 5-9/16 13-1/4 5-1/16 29-5/16 7-5/16 7-1/16 4/1/4 3-1/4 2-7/8 18-1/4
100-1/2 13-7/16 15-5/8 34 20 20 34 23 16-1/2 10-7/8 8-13/16 5-5/16
18
5-7/8 33-13/16 8-13/16 7-13/16 4-1/16 4-1/16 6-1/4 18-1/16
105-1/2 13-7/16 15-5/8 34 4 24 34 26 18-3/4 10-13/16 7-3/16 4-5/16 23-13/16 7-5/16 38-5/8
10
8-1/8 4-1/16 4-1/16 5-1/4 23-7/8
105-1/2 15-7/8 18-5/8 44 24 23 42 26 18-3/4 12-1/4 8-7/8 4-5/16
22
5-7/16
41
8-13/16 9-3/8 4-3/4 4-3/16 5-1/4 20-1/8
115-1/2 18-7/8 21-7/8 44 29 27 42 32
24
14-1/4 9-1/16 7-1/8 27-7/8 6-3/16 14-3/16 8-15/16 11-1/8 4-1/8 4-1/8 6-15/16 25-15/16
115-1/2 18-7/8 21-7/8 53 29 27 46 32
24
14-1/4 9-3/16 7-1/8 29-7/8 6-3/16 14-3/16 8-15/16 11-1/8 4-1/8 4-1/8 6-15/16 22-15/16
136 24-3/4 24-3/4 50 37 32 48 34-1/2 33 15-7/16 8-1/4 4-3/8 33-7/8 9-1/8 15-1/4
8
12-3/4 4-1/8 4-1/8 3-1/4 31-15/16

32