TOTAL DEMAND CALCULATION : FOR , NNH Fixtures type :

private Weight in Fixture units Cold 6 3 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1 10 5 3 Hot Total 6 3 1 1 1 2 2 2 2 1 2 1.5 10 5 3 Quantity Total weight in fixture units Cold 24 Hot Total 24

FIXTURES Water closet (flush valve) Water closet (flush tank) Water Bidet Hose for W.C Lavatory (& H.B., J.S.) Service sink Shower Bath tub Kitchen sink Dishwashing machine Laundry Ablution (Public) Urinal (1" flush valve) Urinal (3/4" flush valve) Urinal (flush tank) Total Fixture Units WATER DEMAND ( GPM ) WATER DEMAND ( m3 / h )

0.75 0.75 0.75 1.5 1.5 1.5 1.5 1 1.5 1

10 1 3 1 1 1

7.5 1.5 4.5 1.5 1.5

7.5 1.5 4.5 1.5 1 1.5

10 2 6 2 1 2

40.5 25.0 GPM

17.5 12.5 GPM

5.68 m3/h

2.84 m3/h

47 27.8 GPM 6.31 m3/h

Assuming Peak factor : Duration : The mean demand Overhead tank size Transfer pump capacity

1.5 60 18.5 556 2.10 18.5 4.21 1.17

min gpm gallon m3 gpm m3/h l/s


(mean demand = peak demand / peak factor ) ( Overhead tank size = (peak demand - mean demand) x duration }

( Transfer pump capacity = mean demand , Assuming one pump running & one standby)