You are on page 1of 3

Outdoor Power System

TP48200A
Introduction
TP48200A is an outdoor telecom power system which configures 48V/50A rectifier modules to supply rated 200A output current. TP48200A has different cooling modes to meet various scenarios, such as heat exchanger, direct ventilation, TEC, etc, providing stable and reliable integrated or distributed power supply solution for various outdoor communication devices. The system has excellent performances such as wide range of AC input voltage, high power efficiency, surge protection, temperature control, intelligent battery management, and remote monitoring, etc.

Features Features
High rectifier efficiency: >96% Excellent environmental adaptability with IP55 class protection Rectifier Supports hot-swap, easy to install and maintain Support environment monitoring and remote management, saving OPEX Excellent fault protection and alarm reporting function Cooling unit self-control to save energy and lower noise, increasing system reliability Multiple anti-theft measures, ensuring the safety of battery and equipment Series of cabinet size/material/thermal system for different scenarios Split Type Equipment Cabinet Integrated Power Cabinet

Application Scenarios
Wireless outdoor macro base station or distributed base station Split Type Battery Cabinet

Specifications
Type
Dimension Weight Cooling mode Installation mode Cabling mode

TP48200A-H15A3

TP48200A-H15A5

TP48200A-D15A1

650mm (W) 650mm (D) 1500mm (H) (excluding base) <120kg (excluding rectifier and battery) Equipment cabin: heat exchanger, Battery cabin: direct ventilation On ground / on roof / against wall, not support stack & pole mounted At the bottom, inlet/outlet downwards In front, supporting modular replacement Satisfied GR487, noise65dBA@1.5m Equipment cabin:IP55, battery cabin: IP45 2150Ah 8U 200,000 hours -10~+45 C -40~+70 C 5%~95%(non-condensing) 0~4000m Single phase / Three phase 85~300V AC, rated:220V AC 45~65Hz, rated: 50Hz/60Hz 163A/3P MCB 20kA / 40kA, 8/20s 42~58V DC, default value:53.5V DC 12000W(43000W) 2125A MCB 263A, 232A MCB 216A MCB 20kA / 40kA, 8/20s 3000W >96%* -40~+75 C 103mm (W)243mm (D)88.9mm (H) 2.8kg >0.99 5% 8 dry contact, 8 digital signal detection RS485/RS232, SNMP, FE, BIN protocol 1000 history records, 200 thousand real time records LCD screen/WEB -40~+45 C -10~+45 C IP55 Direct ventilation

System

Maintenance mode Noise level Protection level Battery space User space MTBF Operating temperature Storage temperature

Environment
Operating humidity Altitude AC input mode AC input voltage

AC Distribution

AC input frequency AC input MCB AC input SPD Output voltage Maximum capacity

DC Distribution

Battery branch LLVD BLVD DC output SPD Output power Efficiency Operating temperature

Rectifier

Dimension Weight Power Factor THD I/O port Communication port

Controller
Storage capacity Display mode

*Remark: Normal efficiency (>92%) rectifier is optional

Specifications
Type
Dimension Weight Cooling mode Installation mode Cabling mode

TP48200E-H09A1

TP48200E-D09A1

TBC300A-DCA1

TBC300A-TCA1

650mm (W) 650mm (D) 900mm (H) (excluding base) <70kg (excluding rectifier and battery) Heat exchanger Direct ventilation Direct ventilation TEC

On ground/on roof/against wall, not support stack & pole mounted At the bottom, inlet/outlet downwards In front, supporting modular replacement Satisfied GR487, noise65dBA@1.5m IP55 N/A 8U 200,000 hours -40~+45 C -40~+70 C 5%~95%(non-condensing) 0~4000m Single phase / Three phase 85~300V AC, rated:220V AC -48V N/A -10~+45 C IP55 IP34 2150AH N/A N/A -10~+45 C -10~+45 C IP55 Fan replaceable TEC fixed in door, easy to maintain

System

Maintenance mode Noise level Protection level Battery space User space MTBF Operating temperature

Environment

Storage temperature Operating humidity Altitude AC input mode AC input voltage

AC Distribution

AC input frequency
AC input MCB AC input SPD Output voltage Maximum capacity

45~65Hz, rated:50Hz/60Hz
163A/3P MCB 20kA / 40kA, 8/20s 42~58VDC, default value:53.5VDC 12000W(43000W) 2125A MCB 2 63A, 232A MCB 216A MCB 20kA / 40kA, 8/20s 3000W > 96%* -40~+75 C 103mm (W)243mm (D)88.9mm (H) 2.8kg > 0.99 5%

N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

DC Distribution

Battery branch LLVD branch BLVD branch DC output SPD Output power Efficiency Operating temperature

Rectifier

Dimension Weight Power Factor THD

I/O port

8 dry contact, 8 digital signal detection,


RS485 / RS232, FE 1000 history records, 200 thousand real time records LCD screen/WEB

Inside temperature, fan alarm, door open alarm


RS485 N/A N/A

Controller

Communication port Storage capacity Display mode

*Remark: Normal efficiency (>92%) rectifier is optional

Copyright Huawei Technologies Co., Ltd. 2013. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang Shenzhen 518129, P.R. China Tel; +86-755-28780808 www.huawei.com

General Disclaimer
The information in this document may contain predictive statements including, without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.

You might also like