Adust Banani Campus Total load (Basement to 6th floor) = 335.

40 KW Contingency load (for future) 20% of existing load= 335.40 X 20% = 67.08 KW. Total estimated load = 335.40 + 67.08 = 402.48 KW. Transformer Capacity will not less than 500 KVA. Load power factor= 0.80 lagging. Power factor to be improved= 0.95 lagging. KVAR Rating of Capacitor= KW {tan [cos-1 (old pf)]-tan [cos-1(new pf)]} = 402.48 {tan [cos-1 (0.80)]-tan [cos-1(0.95)]} = 169 KVAR The Capacitors shall be rated for 440V. Rating of Capacitor= (440/400)2 x 169 = 204.49 Say 205 KVAR. Detailed Specification for Substation Equipments: 11KV Metering Panel: Manufacture of 14 SWG Powder Coat painted louvered sheet steel, metal enclosed, free Standing, floor mounting, dust and vermin proof, completely factory assembled HT switchgear Panel comprising: 3 nos. 1-phase Cast resin Potential Transformer 11KV/3/110V/3. 3 nos. Cast resin CTs 30/5A, 15 VA, Class 0.5 M5 for Metering. Energy meter Elster A1800 ALPHA EC 62053 accuracy Class 0.2 % UV-protected, polycarbonate, IP54 enclosure Wide operating ranges: Voltage: 46 V to 498 V Current rating: 5(10)A Temperature: -40 C to +55 C (ambient) Energy plus demand for kWh, kVARh and kVAh 500 KVA Auxiliary Transformer: Three phase oil immersed Distribution Transformer according to IEC in Standard design with according to IEC in Standard design with Conservator, silica gel breather, rollers, off-load tap Changer, oil level indicator, rating plate, earthing terminals, lifting lugs, 3 sets. HT bushing & 4 sets. LT bushing, Arching horn, oil filling and drainage vents and dial type thermometer, first filling oil for indoor installation. Rated output: 500 KVA Voltage ratio: 11000/415/240 V Frequency: 50 HZ Vector group: Dyn 11 BIL: 75 KV Losses No load/Load: 1000 W/ 6000 W Tap changer: +1x2.5%, 0, - 3x2.5 % Impedance: 4.5 % Temp. Rise: (Oil/Winding): 60 Deg.C/ 65 Deg.C

Ambient temp. : 40 deg. C Type of Cooling: ONAN H.V Winding: Inter phase connection: Delta Inter phase connection: Delta Power Frequency withstands Voltage: 28 KV (for 1 minute) L.V Winding: Inter phase connection: Star Power Frequency withstands Voltage: 3 KV (for 1 minute) Neutral: Fully insulated LT Switchgear Panel: Manufacture of 14/ 16 SWG Powder Coat Painted louvered sheet steel, metal enclosed, free Standing floor mounting dust and vermin proof LT standing, floor mounting, dust and vermin proof LT switchgear panel with 1200 A TPN&E Hard Drawn Electrolytic copper bus bars & comprising: Incoming from Aux. Transformer: 1 nos.TP Moulded Case Circuit Breaker 1000 A, 65 KA with adjustable thermal overload and magnetic short circuit protection. 3 nos. Current Transformer 1200/5A, 3 nos. Moving iron Ammeter (0-1200A), 1 no. Moving Iron Voltmeter (0-600 V) with selector switch. 1 no. 3 phase, 3 wires Solid State Digital Multifunction Energy Meter to show KW, KWH, KVA, KVARH, A, V, PF etc. Type PM 710 (Schneider). Outgoing: 2 nos. 160/400A, 35 KA, 5 nos. 160A, 25 KA, 2 nos. 100A, 25 KA, 2 nos. 63A, 25 KA, TP Moulded Case Circuit Breaker (MCCB) with adjustable thermal overload and magnetic short circuit protection. Power Factor Improvement Plant: 6 Nos. 440V, 25 KVAR, 5 Nos. 10 KVAR, 1Nos. 5 KVAR, 50 Hz TP power capacitor bank with built in discharge resistor. 6 Nos. 50A, 5 Nos. 20A, 1nos. 10A, 415V, 50 Hz, TP magnetic contactor with AC3 duty. 6 Nos. 63A, 5 Nos. 25A, 1nos. 16A, 415V, 50 Hz, HRC fuse with base. Cable: MV system: 3Cx95 mm2stranded copper conductor XLPE insulated screened extruded PVC inners heated; galvanized steel armoured and extruded FRLSPVC overall sheathed. 1nos. 3 terminal 11KV rated outdoor type and 3nos. 3 terminal 11KV rated indoor type heat shrinkable HT cable termination kit. LV system: 1Cx185 mm2 NYY, PVC insulated and PVC sheathed 2 run per phase and 1 run for neutral. Drop out fuse: 3 Nos. 11 KV, 50 Hz, 100A (RMS) with fuse holder support. Lightning Arrester: 3 Nos. 9KV, 50 Hz, 10kA with insulating bracket. GROUNDING: All facilities for grounding of panel board, transformer and all electrical equipment enclosures. Two point grounding for each equipment, panel board and steel structure shall be provided. (1) Grounding wire for ground grid Hard drawn copper stranded wire in accordance with latest IEC Hard Drawn Copper wire for electrical purposes. Nominal cross sectional area: 95-sq. mm. (2) Grounding wire of the equipment to be connected with grounding grid. Annealed copper standard wire in accordance with latest IEC Annealed copper stranded wire for electrical purposes. Nominal cross sectional area: 25 sq. mm.

You might also like