You are on page 1of 34

Installation, commissioning and operator handbook

FireRay 5000 beam detector

116-P-FIRERAY5000/IGB, 2010-10-28

COPYRIGHT This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security AS. The information in this publication may be updated without notice. Product names mentioned in this publication may be trademarks. They are used only for identification.

Table of Contents

Table of Contents
1. Installation.........................................................................3
1.1 General Information........................................................................... 3 1.2 Fitting the Product ................................................................................ 4 1.2 Fitting the Product ................................................................................ 5 1.3 Wiring Diagrams ................................................................................... 6

2. Commissioning .................................................................7
2.1 Apply Power and Enter Pass Code................................................... 7 2.1.1 Apply power ............................................................................ 7 2.1.2 Enter Pass Code to Access Engineering Menu...................... 8 Select Power Mode and Distance ..................................................... 9 2.2.1 Select Power Mode................................................................. 9 2.2.2 Select Distance between Detector and Reflector ................... 9 LASER Targeting .............................................................................. 10 2.3.1 LASER Targeting .................................................................... 10 Auto Alignment and Set 0/100 (Calibrate) ..................................... 11 2.4.1 Auto Alignment ...................................................................... 11 2.4.2 Set 0/100 (Calibrate) ............................................................. 12 2.4.3 System is Aligned ................................................................... 12

2.2

2.3 2.4

3. In Use
3.1

13
Settings and Final Tests.................................................................... 13 3.1.1 Fire Threshold ......................................................................... 13 3.1.2 Fire/ Fault Delay...................................................................... 13 3.1.3 Fire Test .................................................................................. 14 Cleaning the System, Performing Manual Fire and Fault Tests ....... 14 3.2.1 Cleaning the System............................................................... 14 3.2.2 Manual Fire and Fault Tests ................................................... 15

3.2

4. Troubleshooting................................................................16
4.1 Error Codes ....................................................................................... 16 4.1.1 Detector Not Found................................................................. 16 4.1.2 Compensation Level Not Zero ................................................ 16 4.1.3 Signal Strength Out of Range ................................................. 16 4.1.4 Reflector Not Found................................................................ 17 4.1.5 Auto-Align Failed..................................................................... 17 4.1.6 Cannot Zero During S-00 in Set .......................................... 17 4.1.7 No Signal During S-01 in Set............................................... 17 4.1.8 Centre Stage of Alignment Failed ......................................... 18 LASER Not Visible ............................................................................ 18 Home position ................................................................................... 19

4.2 4.3

5.
Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 1

Table of Contents

Display and Indicators ...........................................................20


5.1 5.2 LCD Icon Layout................................................................................ 20 Detector and System Controller Status Indicators ............................ 20

6. Menu Layout......................................................................21
6.1 6.2 6.3 6.4 6.5 User Menu......................................................................................... 21 User Menu - Descriptions.................................................................. 22 Engineering Menu ............................................................................. 22 Detector Settings............................................................................... 23 System Controller Settings................................................................ 24

7. System Information ..........................................................25


7.1 Operating Parameters and Dimensions............................................ 25

8. Approval Information........................................................27
8.1 Territory-Specific Information ............................................................ 27 8.1.1 UL Approval Information ......................................................... 27 8.1.2 European Approval Information .............................................. 27

9. Readers Comments .........................................................29

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 2

Table of Contents

1. Installation
1.1 General Information
IMPORTANT! The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the detector initiating a fire or fault signal.

Ensure clear line of sight from Detector to Reflector

Mount on solid surfaces (structural wall or girder)

50100m = x4

1850m = x1

818m = x1 Use Short Range Mask

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 3

Installation

Check the beam spacing against local regulations Position beam as high as possible, but with a minimum distance of 0.5m from detector to ceiling Mount Detector and Reflector directly opposite each other Do NOT position detector where personnel or objects can enter the beam path

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 4

Installation

1.2 Fitting the Product

Options for Detector wiring orientation

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 5

Installation

1.3 Wiring Diagrams

Fire Resistor Contact Fire Control Panel manufacturer for values of Fire Resistor. Some Zone and Switch Interface Modules do not need a Fire Resistor replace Resistor with a short circuit. Refer to supplied CD for further information. Check operation of Fire and Fault connection on Fire Panel

ALWAYS use a seperate screened 2core cable for each detector head End of Line (EOL) component is supplied by Fire Control Panel manufacturer CAUTION: For system monitoring Do not use looped wire under any terminals. Break wire run to provide monitoring of connections.

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 6

Commissioning

2. Commissioning
2.1 Apply Power and Enter Pass Code

2.1.1 Apply power

Note a commissioned system will display:

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 7

Commissioning

2.1.2 Enter Pass Code to Access Engineering Menu


Press for Pass Code screen:

Default Pass Code: 1 2 3 4 Change digit Move between digits Accept An incorrect Pass Code will return the display to the Pass Code entry screen Three incorrect attempts will lock access for three minutes

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 8

Commissioning

2.2 Select Power Mode and Distance

2.2.1 Select Power Mode


All functions can be performed in `Lo A`(10mA) Mode (default) Select `Hi A`(50mA) to enable faster beam movement during Auto-Align and laser Targeting After installation, set the system back to `Lo A

2.2.2 Select Distance between Detector and Reflector

Select 8-50m (default) or 100m

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 9

Commissioning

2.3 LASER Targeting

2.3.1 LASER Targeting

The system will signal Fault while in this mode The LASER is used to align the Detector with the Reflector. It is an approximate alignment tool only. After Auto-Align the LASER may not be aimed directly at the Reflector.

Use to move the LASER as close to the Reflector as possible One press of n arrow key results in one movement of the Detector head Press or or turn off the LASER and return to the setting menu Refer to user Guide page 14 for troubleshooting if LASER is not visible

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 10

Commissioning

2.4 Auto Alignment and Set 0/100 (Calibrate)

2.4.1 Auto Alignment

Select Auto to automatically align the infrared beam Signal strength will be shown during alignment

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 11

Commissioning

2.4.2 Set 0/100 (Calibrate)


When Set is displayed press When S-00 is diplayed, cover the Reflector with a non-reflective material and leave covered, then press When S-01 is diplayed, uncover the Reflector and leave uncovered, then press

2.4.3 System is Aligned


It is recommended to set the system back to Lo A mode Green LED on the detector will flash every 10 seconds, and signal strength should be between 99% and 101% Default values: 35% Fire Threshold, 10 second delay to Fire and fault, Non-latching mode Refer to User Guide page 11-12 to change settings and for Fire and Fault Test

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 12

In Use

3. In Use
3.1 Settings and Final Tests

3.1.1 Fire Threshold


How to change the threshold at which the Detector will detect a Fire

3.1.2 Fire/ Fault Delay

How to change the delay the System Controller uses before signaling a Fire or Fault to the Fire Control Panel

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 13

In Use

3.1.3 Fire Test

How to perform a Fire Test from the System Controller, to test the wiring to the Fire Control Panel

Confirm screen Detector will signal Fire, System Controller will stay Normal. Press to exit without performing the test

Fire screen System Controller signals Fire to Fire Control Panel Press or to exit

3.2 Cleaning the System, Performing Manual Fault Fire Tests and

3.2.1 Cleaning the System


The system will automatically compensate for dust build-up by changing the Compensation Level. However, it is recommended that the Detector lenses and the Reflector are cleaned periodically with a soft lint-free cloth. If the Compensation Level remains above 130 for several days, this indicates that cleaning should take place. After cleaning, verify that the system is operating noramally: If the signal Strength is between 90% and 110% leave the system to compensate back to 100% (This should take no more than 12 hours) If the Signal Strength is above 110% reduce Compensation Level until Signal Strength is 90-110%, and wait for system to compensate back to 100% If the Signal Strength is below 90% perform LASER Targeting, Auto-Align, and Set.

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 14

In Use

How to change Compensation Level:

3.2.2 Manual Fire and Fault Tests


After installation or cleaning, it is recommended that a manual Fire and Fault Test is performed: Fire Test: Cover the Reflector slowly so that it takes longer than 2 seconds to coer. The System Controller will signal Fire to the Fire Control Panel. Fault Test: Cover the Reflector completely within 2 seconds. The System Controller will signal Fault back to the Fire Control Panel.

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 15

Troubleshooting

4. Troubleshooting
4.1 Error Codes

4.1.1 Detector Not Found

System Controller could not find Detector. Also displayed during power up. Wait 45 seconds for System to power up Check wiring between System Controller and Detector (Voltage to Detector should be 11-13V)

4.1.2 Compensation Level Not Zero

Compensation must be equal zero when Set is selected. Re-align beam using Auto-Align

4.1.3 Signal Strength Out of Range

Signal Strength is too low or too high after Auto-Align. Ensure correct distance has been set Ensure correct Reflector type has been used Ensure clear line of sight to Reflector Re-align beam using LASER and Auto-Align

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 16

Troubleshooting

4.1.4 Reflector Not Found

Detector could not align with Reflector Ensure correct distance has been set Ensure correct Reflector type has been used Ensure clear line of sight to Reflector Re-align beam using LASER and Auto-Align

4.1.5 Auto-Align Failed

Ensure correct distance between Reflector and roof structures Ensure clear line of sight to Reflector Re-align Detector using Auto-Align

4.1.6 Cannot Zero During S-00 in Set

The Reflector was not covered or the Detector was not aligned onto the Reflector. Ensure Reflector was completely covered with a non-reflective material Re-align Detector using Auto-Align

4.1.7 No Signal During S-01 in Set

The Reflector was not uncovered during S-01. Ensure Reflector was uncovered when S-01 was selected

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 17

Troubleshooting

4.1.8 Centre Stage of Alignment Failed

Detector is too far from the centre of the Reflector


Ensure clear line of sight to Reflector Ensure correct distance between path and roof structures

4.2 LASER Not Visible

If it is not possible to see the lASER because of the installation environment (for example, if you cannot see the Reflector from the System Controller or there is high ambient light) then use Hand Alignment. This option displays the signal strength value returned by the Detector, and allows the user to move the beam 1. 2. 3. Start Auto alignment and press after two seconds to exit. (This will maximize infrared power.) Select Hand alignement. Use to steer the beam until the signal strength is above 800. There is no auto-repeat function on any key. To move the motor in any given direction more than once, press the key multiple times. Cover the Reflector. If the Signal Strength does not drop by more than half, the beam is not aligned to the Reflector, so repeat Step 3. Perform Auto alignment, followed by Set.

4.

5.

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 18

Troubleshooting

4.3 Home position

If it is not known where the beam is pointing, use Home position o automatically steer the infrared beam to approximatly the centre of its range of movement.

Press or to exit this function This will take up to 15 minutes to complete When complete the display will return to the Engineering menu

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 19

Display and Indicators

5. Display and Indicators


5.1 LCD Icon Layout

5.2 Detector and System Controller Status Indicators

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 20

Menu Layout

6. Menu Layout
6.1 User Menu

Press Press

in this menu to enter the Pass Code to put the system into Sleep

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 21

Menu Layout

6.2 User Menu - Descriptions

6.3 Engineering Menu

The Pass Code must be entered to access the Engineering Menu This menu is navigated by using keys to move the cursor. Items are selected by using Pressing exits this menu and returns the system to a locked state

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 22

Menu Layout

6.4 Detector Settings

* ONLY AVAILABLE ON MULTI-DETECTOR UNIT ** WARNING: ENGINEERING USE ONLY. ALTERING MAY CAUSE MALFUNCTION

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 23

Menu Layout

6.5 System Controller Settings

Units of Measurement Changes between Metric and Imperial Change Pass Code Use to access each digit Use to change the digit Press to save the new Pass Code and return to the settings menu Press to cancel the change and return to the Engineering mneu

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 24

System Information

7. System Information
7.1 Operating Parameters and Dimensions
Parameter Operating Voltage Operating Current Low Power Mode Operating Current- High Power Mode Fire Threshold Range Delay to Fire Delay to Fault Operating Distance between Detector and Reflector Maximum angular misalignment of Detector Maximum angular misalignment of Reflector Maximum angular movement of Detector head Optical wavelength Rapid obscuration Fault threshold Operating Temperature (UL Approved) Operating Temparature (EN54-12 Approved) Storage temperature Relative Humidity (non condensing) IP Rating Relay Contact Voltage Relay Contact Current Maximum Cable Length (Controller to Detector) Cable Gauge Housing Flammability rating Value 14-28V DC 8-12 mA 48-52 mA 0.45-3.98 dB 10-60% 2-30 s 2-30 s 8-100 m 0.3 Deg 5 Deg 3.5 Deg 850 nm 87% 0 - + 37.8 Deg C - 10 - + 55 Deg C - 40 - + 85 Deg C 93% IP54 30V DC 100 mA 100m 24-14 AWG 0.5-1.5 mm UL94 VO

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 25

System Information

Parameter
Pass Code Power Mode

Description
User Code required to access Enigneering Menu Hi A: System will operate at 50mA constant current consumption Lo A: System will operate at 10mA constant current consumption Range 50 to + 205. level of amplification applied to compensate for dust build-up and building movement at 75 Auto-optimise is started Range 50 to 4095. Indicates the optical power output. Set automatically by Auto-Align Range 1 to 255. Indicates the optical power output. Set automatically by Auto-Align Range 10% to 60%. Sets the amount of obscuration required for the Detector to signal a Fire Range 2s to 30s. Sets the time the system needs to be below the Fire threshold before signalling a Fire Range 2s to 30s. Sets the time the system needs to be below the Fault threshold before a Fault is signalled Note the signal needs to fall to < =13% within 2s 8-50m orr 50-100m. Sets the distance between Detector and Reflector. Affects the initial transmit power at the start of Auto-Align Disables or enables Auto-Optimise (the automatic beam movement function) Sets if the system will latch Fire or automatically reset Faults are always non-latching.

Default
1234 Lo A

Compensation Level Transmit power Receive Gain Fire Threshold

35 % 10 seconds

Delay to Fire

10 seconds

Delay to Fault

Distance

8-50m

Auto-Optimise On/Off Latched/nonlatched

On Nonlatching

Dimensions
System Controller, including base Detector, including easy fit base Universal Bracket Reflector (Single) Protective Cage

Width, in (mm)
7.9 (200) 5.3 (135) 5.3 (135) 3.9 (100) 5.4 (136)

Height, in (mm)
9.3 (235) 5.3 (135) 5.3 (135) 3.9 (100) 6.2 (157)

Depth, in (mm)
2.8 (71) 5.3 (135) 2.8 (71) 0.4 (10) -

Weight, IB (kg)
2.0 (0.9) 1.1 (0.5) 0.4 (0.2) 0.2 (0.1) 0.3 (0.13)

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 26

Approval Information

8. Approval Information
8.1 Territory-Specific Information

8.1.1 UL Approval Information

UL File Number: S3417


Fire Threshold Range 10-18% 15-25% 15-35% 25-50% 35-50% 50%

Distance between Detector and Reflector 8-10m (26.2-32.8ft) 10-15m (32.8-49.2ft) 15-22m (49.2-72.2ft) 22-40m (72.2-131.2ft) 40-60m (131.2-196.8ft) 60-100m (196.8-328.1ft)

All installations should comply with NFPA72

8.1.2 European Approval Information

Complies with EN 54-12 for sensitivity levels between 25% and 35% with a maximum delay to fire of 20 seconds. Protective cage must be fitted to comply with EN 54-12.

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 27

Approval Information

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS Page 28

Readers Comments

9. Readers Comments
Please help us to improve the quality of our documentation by returning your comments on this manual: Title: Installation, commissioning and operator handbook, FireRay 5000 beam detector Ref. No.: 116-P-FIRERAY5000/IGB, 2010-10-28 Your information on any inaccuracies or omissions (with page reference):

Please turn the page

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS

Readers Comments

Suggestions for improvements

Thank you! We will investigate your comments promptly. Would you like a written reply? Name: Title: Company: Address: Yes No

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Telephone: Fax: Date:

----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Please send this form to:

Autronica Fire and Security AS P.O. Box 5620 NO-7483 Trondheim Norway Tel: + 47 73 58 25 00 Fax: + 47 73 58 25 01 www.autronicafire.com

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS

Readers Comments

Installation, commissioning and operator handbook, FireRay 5000 beam detector 116-P-FIRERAY5000/IGB, 2010-10-28, Autronica Fire and Security AS

Autronica Fire and Security AS is an international company, headquartered in Trondheim, one of the largest cities in Norway. The company is owned by United Technologies Corporation and employs more than 319 persons with experience in developing, manufacturing and marketing of fire safety equipment. Our products cover a broad range of systems for integrated solutions, including fire detection systems, integrated fire and gas detection systems, control and presentation systems, voice alarm systems, public address systems, emergency light systems, plus suppression systems. All products are easily adaptable to a wide variety of applications, among others, hospitals, airports, churches and schools, as well as to heavy industry and high-risk applications such as power plants, computer sites and offshore installations, world wide. The company's strategy and philosophy is plainly manifested in the business idea: Protecting life, environment and property.

Quality Assurance Stringent control throughout Autronica Fire and Security ASsures the excellence of our products and services. Our products are CE marked and developed for worldwide standards and regulations, and conform to the CEN regulation EN54. Our quality system conforms to the Quality System Standard NS-EN ISO 9001:2000 and is valid for the following product and service ranges: marketing, sales, development, engineering, manufacture, installation, commissioning and servicing of suppression, integrated fire and gas detection and alarm systems, plus petrochemical, oil and gas instrumentation systems for monitoring and control.

Autronica Fire and Security AS Headquarters, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01. Head Office Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99. Division Oil & Gas, Oslo, Norway. Phone: + 47 23 17 50 50, Fax: + 47 23 17 50 51 Division Oil & Gas, PO Box 416, Farnborough GU14 4AT, UK. Phone: + 47 51 84 09 00, Fax: + 44 84 52 80 20 55 Division Maritime, Suppression/New Build Detection & Alarm. Norway. Phone: + 47 31 29 55 00, Fax: + 47 31 29 55 01 Division Maritime, After Sales/Service Detection & Alarm, Norway. Phone: +47-73 58 25 00, Fax: +47-73 58 25 01

Visit Autronica Fire and Security AS's Web site: www.autronicafire.com