You are on page 1of 2

RECIRCULATING LOOP CHILLER

LOW PROFLE / WEATHER-RESISTANT


MODEL...................... PCP-750G-96-A-WP-LP
HERMETIC SCROLL MODEL SPECIFICATIONS Cooling Capacity: Btu/hr [min / max] .........................................................................................96,000 Watts [min / max] ..........................................................................................28,128 Rating Conditions: Coolant Discharge Temperature .................................................... 68OF [20OC] Ambient Air Temperature ................................................................. 90OF [32OC] Condensing Unit: Compressor HP .....................................................................7 1/2 Description: Lifetime lubricated, hermetic scroll type supplied with high/low pressure stat, freeze control, head and suction gauges, pump down solenoid valve, thermostatic expansion valve, refrigerant sight glass and dehydrator. Cooling Tank & Evaporator: Capacity ...........................................95 Gals. [360 L] Construction: Welded stainless steel shell with stainless steel immersion coil evaporator. Tank tested at 250# for 125# working pressure, supplied with drain connection and insulated with closed cell thermo-elastomer with an R factor of 3.7. Pump: Motor HP ..................................................................................................... 1-1/2 Capacity .................................................30 GPM @ 40 PSI [114 lpm @ 4 bar] Description: Bronze tted turbine pump mounted on a rubber pad over a stainless steel condensation tray and supplied with unions and service valves and a pressure relief bypass valve. All piping and ttings brass, copper or bronze, and insulated with closed cell thermo-elastomer with an R factor of 3.7. Adjustable Dierential Thermostat:............................. 40O to 90OF [4O to 32OC] Temperature Stability ....................................................................... 2OF [1.4OC] CABINET: Anodized aluminum panels with stainless steel corner legs and top on a welded angle iron frame. Panels removable without tools for access to all components. Supply Power: .........................................208-230/60/3 or 460/60/3 or 380/50/3 Full Load Amps ............................................................................................42 or 21 NOTE: FLA may vary depending on options. See MCA and MOP ratings on as-built unit. Plumbing Connections In & Out ........................................... 1-1/4 [31mm] MPT Decibel Rating [nominal at 5 ft.] .....................................................................74dBA Shipping Weight .............................................................................................. 2,200 lbs FAIL SAFE OPTIONS [Designated by sux] DUAL PUMPS: Automatic switchover to backup pump on loss of coolant ow. -LL LOW LEVEL INTERLOCK: Float switch in tank lights a warning light if coolant level drops below safe low limit. -LF LOW FLOW INTERLOCK: Flow switch lights a warning light if ow rate drops below safe low limit. -HT HIGH TEMPERATURE INTERLOCK: Thermostat lights a warning if coolant temperature rises above safe high limit. -AS AUTOMATIC SWITCHOVER TO CITY WATER: In case of pump or compressor failure, city water switchover solenoids are activated to allow for temporary cooling using city water. -WP-GF WEATHER-RESISTANT, GLYCOL-FREE: For outdoor installation; chiller with in-line heater and circulating pump connected to UPS stand-by electrical system. Insures recirculation of 50OF coolant even if power fails at below freezing temperatures. -DPA

TYPICAL LOW PROFILE CHILLER

FEATURES

Low Prole unit designed for rooftop mounting. Easily concealed by parapet... 44 overall height for low visibilty operating noise from inside building steel exterior for a lifetime of service
O

Outdoor chiller location removes heat and Standard anodized aluminum & stainless Ambient operating temps from -30 F to 120 F Uses 404a Refrigerant
O

DESCRIPTION
A closed loop, packaged chiller designed specically to recirculate a clean coolant at a constant temperature, pressure and ow. Ideal for all installations where a dependable source of clean cooling water is not available. Filtrine PCP chillers use a storage-type cooling tank, with immersion coil evaporator, to provide close temperature control of recirculating coolants. The tank is sealed to prevent coolant evaporation or fouling, and supplied with a liquid level gauge, ll port and clean out. The pump recirculates the coolant at a constant temperature, pressure and ow.

LIFETIME WARRANTY - Consult factory for details. ONE YEAR WARRANTY - All parts covered FOB jobsite for [12] months from start-up date or [15] months from date of shipment - whichever comes rst. Consult factory for details. START-UP and FIRST YEAR SERVICE - Filtrine can arrange start-up and rst year service on all parts and labor. To help prevent costly down-time, regular maintenance is available on a contractual basis. Consult factory for details. FILTRINE IS ISO 9001-2008 REGISTERED PRODUCT LINE APPROVED

MARK AVAILABLE

FILTRINE Mfg. Co. 15 Kit St. Keene, NH 03431 USA 800-930-3367 603-352-5500 FAX: 603-352-0330 w w w.filtrine.com cool@filtrine.com

LABOR & PARTS

608-7.5G-WP-LP [PCP-750G-WP-LP] REV B 08.12.11

TYPICAL WEATHER-RESISTANT, LOW PROFILE CHILLER SCHEMATIC


VENTILATION REAR
8

VENTILATION RIGHT END

LEGEND

1.........Fill Port 2.........Sight Glass 3.........Return 4.........Discharge 6.........Elect. Conn. 7.........Indicator Lamps 8.........Head Press. 9.........Suction Press.
7

H
FRONT

D
VENTILATION LEFT END
6

CHILLER DIMENSIONS and WEIGHTS


FILTRINE MODEL NUMBER PCP-750G-96-A-WP-LP W in 82 cm 239 in 87 D cm 221 in 44 H cm SHIP WT lb kg 112 2200 950

Dimensions & weights may vary depending on options installed-consult factory.

STANDARD OPERATING CONDITIONS OUTDOOR AMBIENT: -20OF to 90OF (10O to 32OC) OPTIONAL OPERATING CONDITIONS: OUTDOOR AMBIENT: Down to -30OF (-34OC) Up to 100OF (38OC) Up to 110OF (43OC) Up to 120OF (49OC) NOTE: Higher ambient options may aect unit dimensions.

VENTILATION PANELS TYPICAL VENTILATION: Air intake at Rear, air discharge at Right End and Left End. Manufacturer recommends 24 inch minimum clear space opposite all ventilation panels. REMOVABLE SERVICE PANELS Located on Front & Left End. Manufacturer recommends 36 inch clearance at Front for service and 36 inch clearance at Left End for access to controls. CHANNEL SKIDS Allow an additional 4 (10cm) to depth and 2 (5cm) to height for channel skids. Center of 5/8 (16mm) mounting holes located 6 (15cm) from chiller end and 1 (2.5cm) from chiller edge front and rear.

All information given on this bulletin is for general use only. Confirm specifications with factory for your specific requirement.

FILTRINE Mfg. Co. 15 Kit St. Keene, NH 03431 USA 800-930-3367 603-352-5500 FAX: 603-352-0330 w w w.filtrine.com cool@filtrine.com

LABOR & PARTS

608-7.5G-WP-LP [PCP-750G-WP-LP] REV B 08.12.11