1. Introduction
1.1 What is Multi V? 1.2 External Appearance 1.3 System Layout 1.4 Nomenclature
. 04 .. 05 .. 10 . 11
2. Line Up
2.1 Line Up 2.2 Specification
..
13 .. 15
3. USP
3.1 Major USP 3.2 Minor USP 3.3 Product Comparison 3.4 Benefits . . 16 .. 42 .. 44 . 52
4. General Information
4.1 Item Inside Product Box . 54
Multi V
Contents
5. Product Details
5.1 Cycle Diagram 5.2 Part & Dimensions 5.3 Control Parts 5.4 Wiring Diagram : Outdoor Unit . 55 .. 56 .. 57 . 58
6. Installation
6.1 Installation Scene 6.2 Installation of Outdoor Unit 6.3 Piping & Wiring: Outdoor Unit 6.4 System Set-up . 59 .. 60 .. 69 . 97
7. Start up
7.1 Start up 7.2 Checking point 7.3 Special Functions . 103 .. 106 .. 108
8. Trouble Shooting
8.1 Error Codes . 120 . 121 .. 123 .. 126
9. New Functions
9.1 Cool/ Heat selector 9.2 New Dry contact 9.3 Independent power module
Multi V
1. Introduction
Multi V III is the latest technology, with Worlds Best Efficiency, Largest Capacity, Compact Design and Green Energy Solution.
Multi V III
Energy Saving & Environment Friendly
Multi V
1. Introduction
3,380~415,50/60Hz
UX2 + UX2
1. Introduction
3,380~415,50/60Hz
UX3 + UX2
UX3 + UX3
1. Introduction
3,380~415,50/60Hz
1. Introduction
3,380~415,50/60Hz
1. Introduction
Type
6HP 8HP 10HP 12HP 14HP 16HP 18HP 20HP
Chassis H/P
UX2 UX2 UX2 UX3 UX3 UX3 UX3
H/P
1 2 2 2 3 3 3
C/O
1 1 1 2 2 2 3 3
C/O
2 2 2 2 2 2 2 2
Multi V
1. Introduction
Max. 80 HP
Refrigerant Pipes Y Branch Low static duct High static duct 1Way CST 2Way CST 4Way CST ARTCOOL Mirror ARTCOOL Gallery
Console
Multi V
10
1.4 Nomenclature
1.4.1 Outdoor Unit
3
Serial number Air Discharge Type S : Side Discharge T : Top Discharge Electrical rating 8 : 3, 380 ~ 415V, 50Hz 9 : 3, 380V, 60Hz A : 3, 220V, 50HZ B : 3, 220V, 60HZ L : 3, 380 ~ 415V, 50Hz / 3, 380V, 60Hz D : 3, 460V, 60Hz
1. Introduction
Total cooling capacity in Horse Power (HP) unit Ex) 10HP '100' Combination of Inverter Type and Cooling Only or Heat Pump N : Inverter and H/P V : Inverter and C/O B : Inverter and Heat Recovery System with Outdoor Unit using R410A
Multi V
11
1.4 Nomenclature
1.4.2 Indoor Unit
1. Introduction
Generation
Combinations of functions
A : Basic function L : Neo Plasma (Wall Mounted) C : Plasma Ceiling Cassette) G : Low Static U : Floor Standing without Case ART COOL Type Panel Color B : Blue R : Mirror V : Silver Chassis Name Electrical rating 1 : 1, 115V, 60Hz 6 : 1, 220 ~ 240V, 50HZ 3 : 1, 208/230V, 60Hz 2 : 1, 220V, 60Hz 7 : 1, 100V, 50/60HZ
Total cooling capacity in Btu/h Ex) 5,000 Btu/h '05 ' 18,000 Btu/h ' 18' Combination of Inverter Type and Cooling Only or Heat Pump N : AC Inverter and H/P V : AC Inverter and C/O B : DC Inverter and H/P and C/O System with Indoor Unit using R410A * LGETA : U Ex) URN Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
12
2.1 Line-up
2.1.1 Outdoor Unit
Capacity (HP) 6
2. Line-up
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
C/O
M+M
L+M
L+L
M*3 L+M+M
L+L+M
L+L+L
H/P
M+M
L+M
L+L
L+L+M
L+L+L
Capacity (HP)
62
64 66 68
70 72 74
76 78 80
UX1 Chassis
C/O
L+M*3 L+L+M+M
L+L+L+M
L+L+L+L
UX2 Chassis
H/P
L+L+L+L L
UX3 Chassis
Multi V
13
2.1 Line-up
2.1.2 Indoor Unit
kW Btu/h ART COOL Gallery Series Mirror SRAC Wall Mounted 1Way (Art) Ceiling Cassette 2Way 4Way Ceiling & Floor Ceiling Suspended High Static Ceiling Concealed Low Static Duct Built-in Floor Standing Console Fresh air Intake Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
2. Line-up
1.6 5k
2.2 7k
2.8 9k
3.6 12k
4.2 15k
5.6 18k
7.1 24k
8.2 28k
10.6 12.3 14.1 23.9 30.2 36k 42k 48k 76k 96k
14
2.2 Specification
Unit System (HP)
Combination unit Model Independent unit kg Product Charge
2. Line-up
1 Outdoor Unit 6 ARUN60LT3 ARUN60LT3 4.0 10 160 1
(618X1,680X760)X1 (26.8X66.1X29.9)X1
Max. Connectable No. Of Indoor Units kg Net Weight mm Dimensions inch (WxHxD) Connecting Pipes Unit System (HP)
Combination unit Independent unit kg Product Charge Liquid Pipes [mm (inch)] Gas Pipes [mm (inch)]
9.52(3/8) 19.05(3/4)
9.52(3/8) 19.05(3/4)
9.52(3/8) 22.2(7/8)
12.7(1/2) 28.58(1-1/8)
Model
Max. Connectable No. Of Indoor Units kg Net Weight mm Dimensions inch (WxHxD) Connecting Pipes
Liquid Pipes [mm (inch)] Gas Pipes [mm (inch)]
(48.8X66.1X29.9)X1
(48.8X66.1X29.9)X1
(48.8X66.1X29.9)X1
(48.8X66.1X29.9)X1
12.7(1/2) 28.58(1-1/8)
12.7(1/2) 28.58(1-1/8)
15.88(5/8) 28.58(1-1/8)
15.88(5/8) 28.58(1-1/8) 15
Note: Refer PDB for entire specifications of all the models. Copyright 2010 @LG Electronics / AC Company All Rights Reserved Multi V
3. USP
Heating Capacity
4.25
4.13
4.55
25%
9%
3.31
4.16
3/36
Multi V
16
3. USP
New
Suction
HP
Discharge Suction
LP
LSS Compressor HSS Compressor
Input Power
100% 11% 9% 15% 88%
11% 5.5% 6%
LSS Compressor Low temp. Low Press. Sump Increase in Suction Gas Temp. Oil Viscosity decreases with Temp.
HSS Compressor High Temp. High Press. Sump no change in Suction Gas Temp. no change in Oil Viscosity (Stable Discharge Temp.)
65%
Compressor
65%
Old
New
Multi V
17
3. USP
15Hz
4 3
Multi V Plus II
24 25 26 27 28 29 30 31 32 33 34 35
Comp. Freq.
Outdoor temp.()
5 4
25 20
Standard
5Hz
Multi V Plus II Multi V III
COP 3
2 1
Multi V Plus II
-1515 -1212-10 -7 -5 -3 0
3 5
9 11
Outdoor temp.()
Multi V
18
3. USP
Multi V III
Oil Separator
HiPOR TM
5/36
Multi V
19
3. USP
Nd Magnet
By adoption of the Sine Wave which smoothes rotation of motor, Operation efficiency is improved sharply.
Multi V
3. USP
Cyclone Sub-cooler
Multi V
21
3. USP
Non-uniform Distribution
Uniform Distribution
Multi V III
Multi V
22
3. USP
R12
R22
Multi V
Multi V
23
3. USP
Total piping length Max 1000m Longest piping length Max 225m
M
Longest piping length after 1st branch Max 90m
Multi V
24
3. USP
New Octagon Grill Air Flow Resistance reduced Robust Structure Design
Low torque ripple design of motor, resonant frequency shift, optimal current angle control
Multi V
3. USP
Conventional
Multi V III
Multi V
26
3. USP
Multi V III
Multi V III
Multi V
27
3. USP
28
3. USP
20mm
20mm
Multi V
29
3. USP
Wrong piping
Malfunction
Back-up
Wrong wiring
Multi V
30
3. USP
Conventional
Multi V III
Conventional Multi V
Multi V III
Conventional
Multi V III
Conventional
Multi V III 31
3. USP
Multi V III
Multi V
32
3. USP
50
A hr
Measuring Temp.
B hr
Function On
Load(%)
0 50 Mode 1 A : 8.0 hr, B : 9.0 hr 47 Mode 2 A : 6.5 hr, B : 10.5 hr Mode 3 A : 5.0 hr, B : 12.0 hr 41 Mode start 8:00
Multi V
Step 1 : max A Step 2 : max B Step 3 : max C Mode End 4:00 8:00
12:00
16:00
20:00
0:00
33
3. USP
Multi V
34
3. USP
Multi V
35
3. USP
Crane Slot
Elevator
Multi V
36
3. USP
50%
Front SVC Area 900
C/Box Open area
500
SVC Area
Multi V
37
3. USP
3hrs
60% Time save
Setting LGMV PC 100% operation 1 Unit operation Report
1hr
Start Report
Auto Test Run Check List Cycle Electric Ref. charging Sensor check Parts (s/w, valves, etc.)
LGMV
Multi V
38
3. USP
Repair!
Pump Out
When Outdoor unit is failed, all refrigerant in failed ODU can be pumped out to Indoor Units.
Refrigerant Flow
Refrigerant Flow
Failed
Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
39
3. USP
LG MV Cycle View
Cycle View
Indoor control
Multi V
40
3. USP
Slave
Slave
Indoor Control
Multi V
41
3. USP
D Company M Company 3 3
Unit Capacity
Multi V
42
3. USP
Multi V
43
3. USP
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 64 80
1unit
Plus LG
2unit
3unit
4unit
Multi V
Daikin VRV
M.E
City Multi
4.0 3.0
Plus II
m2
Multi V III
2.0 1.0 0.0
24/36
Multi V
5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80
44
3. USP
Item Max. COP (Cooling / Heating) Longest Pipe Length Total Pipe Length Difference in height (Indoor Outdoor) Control 1Unit Max Capacity Outdoor Max Capacity Compressor
Multi V 4.27 / 4.58 200 m 1,000 m 110m Inv. + Const. Speed 20 HP Max 80Hp V-Scroll(DC Inverter) Hi-POR tech.
VRV 4.29 / 4.50 200 m 1,000 m 50 m(90 m) Inv. + Const. Speed 18 Hp Max 54 Hp DC Inverter Scroll type
City Multi 3.62 / 4.02 165 m 1,000 m 50 m Inverter 18 Hp Max 50 Hp DC Inverter Scroll type
45
25/36
Multi V
3. USP
3.5 7
Multi V III
Multi V Plus II
VRV
City Multi
26/36
Multi V
46
3. USP
29%
4.5
COP
3.5
27%
2.5
90
100
110
Multi V
3. USP
4.00
3.50
COP
3.00 2.50 2.00 0 10 20 30 40 50 60 70 80 Capacity [Hp]
Multi V III_50Hz ME City Multi_50Hz/60Hz Multi V Plus II_50Hz Toshiba SMMS_50/60Hz Daikin VRV III ss_50Hz Samsung (Compact Model (50Hz)
Multi V
48
3. USP
Cooling
Power consumption [kW]
25
15%
20
15
Operating range
10 70 80 90
MV III
Location : Sacramento, California - Outdoor Temperature : -1 ~ 38 HVAC system - LG Multi V III, 26HP 2each - DAIKIN VRV III, 26HP 2each Energy simulation : Energy Pro Ver.5.0
30
100
Plus II VRV III
110
120
Temperature [F]
Heating
25
20
13%
15
Operating range
10 10 20 30
MV III
40
Temperature [F] Plus II
50
VRV III
60
70
29/36
Multi V
49
3. USP
13,000
143,510
134,391
14% 125,319
VRV III
Plus II
MV III
30/36
Multi V
50
3. USP
No. of ODU 20 HP Foot print area Weight Max. Connecting IDU No. of ODU 40 HP Foot print area Weight Max. Connecting IDU No. of ODU 50 HP Foot print area Weight Max. Connecting IDU No. of OD U 54 HP Foot print area Weight Max. Connecting IDU
Multi V
66.2% 82.0% 32
100% 100% 32
98.3% 93.7% 43
79.5% 87.1% 64
100% 100% 64
87.1% 84.0% 50
99.3% 91.3% 64
100% 100% 64
97.7% 76.2% 50
99.3% 98.8% 64
Over 54Hp, only LG provides
100% 100% 64
51
3.4 Benefits
3.4.1 LATS - Multi V
3. USP Consultant
Convenient model selection Highly user-friendly design (Autocad Version) Automatic piping design & check Download & auto upgrade from Sales Supporting System (http://www.lgeaircon.com)
Multi V
52
3.4 Benefits
3.4.2 LG Monitoring Viewer (LGMV)
3. USP Installer
Easy start-up, Easy trouble shooting Monitoring whole system such as compressor, fan, valves, etc
Multi V
53
4. General Information
Multi V
54
5. Product Details
55
5.2 Dimensions
5. Product Details
ARUV60LT3 ARUV80LT3
Unit (mm)
4 oblong holes
Multi V
5. Product Details
CN05CN05- Jig connection terminal LGMV SW02VSW02V- Auto addressing switch SW01SSW01SReset button CN41CN41- Central Control terminal CN36CN36- PFC- IPM CN 33 SCSC- ININ- SC circuit inlet temp. sensor SCSC- OUTOUT- SC circuit outlet temp. sensor CN 34
CN12CN12- Const comp hearer 2 CN11CN11- Const comp hearer 1 CN10CN10 - INV comp hearer CN09CN09- 4 way reversing valve CN08CN08- 220V power input terminal JIG1,JIG2JIG1,JIG2- JIG power terminal : AC 220V CN 3131 Pressure sensor (Mid) CN 3232 - Low Pressure sensor CN 3030 - High Pressure sensor
DIS(I)DIS(I) - Inv comp dis temp. SUCSUC- Suc temp. sensor CN 2828 - Const comp current sensor 1 CN 2727 - Const comp current sensor 2 IPM CN 35 HEXHEX- ODU hex temp. sensor DIS(C)DIS(C) - Const comp dis temp. sensor
Multi V
57
5. Product Details
Multi V
58
6. Installation
Refrigerant Pipes Y Branch Low static duct High static duct 1Way CST 2Way CST 4Way CST ARTCOOL Deluxe ARTCOOL standard
Floor standing
Multi V
59
6. Installation
Multi V
60
6. Installation
The vacuum pump must have the capacity to achieve vacuuming pressure of 5 torr for more than 1 hour.
61
6. Installation
A) Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust. Use the H-beam support as a base support B) Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200mm).
C) The corner part must be fixed firmly. Otherwise, the support for the installation may be bent. - Get and use M10 Anchor bolt. - Put Cushion Pad between the outdoor unit and ground support for the vibration protection in wide area. D) Space for pipes and wiring (Pipes and wirings for bottom side) E) H-beam support Note: Refer PDB for more details. Multi V F) Concrete support 62
6. Installation
Install at places where it can endure the weight and vibration/noise of the outdoor unit. The outdoor unit supports at the bottom shall have width of at least 100mm under the unit legs before being fixed. The outdoor unit supports should have minimum height of 200mm. Anchor bolts must be inserted at least 75mm.
Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
63
6. Installation
Select space for installing outdoor unit, which will meet the following conditions: No direct thermal radiation from other heat sources No possibility of annoying the neighbors by noise from unit No exposition to strong wind With strength which bears weight of unit Note that drain flows out of unit when heating With space for air passage and service work shown next. Because of the possibility of fire, do not install the system to the space where generation, inflow, stagnation, and leakage of combustible gas is expected. Avoid unit installation in a place where acidic solution and spray (sulfur) are often used. Do not use unit under any special environment where oil, steam and sulfuric gas exist. Don't operate heating mode when the outdoor air temperature is -20 C or lower. It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the outdoor unit. If installation site is area of heavy snowfall, then the following directions should be observed. - Make the foundation as high as possible. -Fit a snow protection hood. Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation. 1. Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the product at a place with a high humidity in winter (near beach, coast, lake, etc). (Ex) Rooftop where sunshine always shines.
Multi V
64
6. Installation
2. Performance of heating will be reduced and preheat time of the indoor unit may be lengthened in case of installing the outdoor unit in winter at following location: (1) Shade position with a narrow space (2) Location with much moisture in neighboring floor. (3) Location with much humidity around. (4) Location where ventilation is good. It is recommended to install the outdoor unit at a place with a lot of sunshine as possible as. .
Multi V
65
6. Installation
During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space as shown in the figures below. Category Installation Space Case 1 (10mm Side Space 49mm) A10 B300 C10 D500 A10 B300 C10 D500 E20 4 sides are walls A10 B300 C10 D500 E20 F600 A50 B100 C50 D 500 E100 F 500 Case 2 (Side Space 49mm) A50 B100 C50 D500 A50 B100 C50 D 500 E100
Multi V
66
6. Installation
A 10 B 300
Multi V
67
6. Installation
The height of the wall on the front side must be 1500mm or less. The height of the wall on the inlet side must be 500mm or less. There is no limit to the wall on the side. If the height of the walls on the front and the side are higher than the limit, there must be additional space on the front and the side. - Additional Space on the inlet side by 1/2 of h1. - Additional Space on the front side by 1/2 of h2 - h1 = A (Actual height) - 1500 - h2 = B (Actual height) - 500
68
6. Installation
When connecting to high low pressure common pipe, connect pipes using connecting elbows.
Multi V
69
6. Installation
Model
ID rId5 .
Gas Pipe
ID rId4 .
Liquid Pipe
2 Unit
ARCNN21
Multi V
70
6. Installation
Gas Pipe
ID rId4 .
Liquid Pipe
ID rId7 .
3 Unit
ARCNN31
ID rId5 .
ID rId6 .
ID rId8 .
4 Unit
ARCNN41
Multi V
71
6. Installation
Outdoor Unit
ARUN420LT3 ARUN440LT3 ARUN460LT3 ARUN480LT3 ARUN500LT3 ARUN520LT3 ARUN540LT3 ARUN560LT3 ARUN580LT3 ARUN600LT3
Multi V
72
6. Installation
Example : 5 Indoor Units connected : Outdoor Unit : 1st branch (Y branch) : Indoor Units
Multi V
73
6. Installation
Example : 5 Indoor Units connected : Outdoor Unit : 1st branch (Y branch) : Indoor Units : Downward Indoor Unit : Connection branch pipe between Outdoor units: ARCNN21
Multi V
74
6. Installation
Piping length from outdoor branch to outdoor unit 10m, equivalent length : max 13m(for 22HP or more) Conditional Application To satisfy below condition to make 40m ~ 90m of pipe length after first branch. Diameter of pipes between first branch and the last branch should be increased by one step, except pipe diameter B,C,D is same as Diameter A 6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 *: it is not necessary to size up. 2) While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice. A+B2+C2+D2+a+b+c+d+e 1,000m 3) 4) Length of pipe from outdoor unit to the farthest indoor unit 5(abcd) 40m [Length of pipe from outdoor unit to the farthest indoor unit 5(A + B + C + D + e) -[Length of pipe outdoor unit to the closest indoor unit 1 (A + a) 40m
75
6. Installation
Example : 6 Indoor Units connected : Outdoor Unit : 1st branch : Indoor Units : Sealed piping
Multi V
76
6. Installation
Example : 6 Indoor Units connected : Outdoor Unit : Header branch : Indoor Units : Sealing : Connection branch pipe between Outdoor units: ARCNN21
Multi V
77
6. Installation
L l H H h1
Longest pipe length after 1st branch F 40m Difference in height (Outdoor Unit Indoor Unit) H 110m Difference in height (Indoor Unit Indoor Unit) H 15m Difference in height (Outdoor Unit Outdoor Unit) H1 5m
*: Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
78
6. Installation
Example : 5 Indoor Units connected : Outdoor Unit : 1st branch (Y branch) : Y branch : Indoor Unit : Header : Sealed piping
Multi V
79
6. Installation
Example : 5 Indoor Units connected : Outdoor Unit : 1st branch : Y branch : Indoor Unit : Connection branch pipe between Outdoor units: ARCNN21 : Header : Sealed piping
Multi V
80
6. Installation
Longest pipe length after 1st branch B + b 40m(90m**) Difference in height (Outdoor Unit Indoor Unit) H 110m Difference in height (Indoor Unit Indoor Unit) h 15m ) Difference in height ( Outdoor Unit Outdoor Unit) h1 5m
* : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose ** : To apply Conditional Application
81
6. Installation
Multi V
82
6. Installation
Gas pipe
ID rId4 .
Liquid pipe
ARBLN01621
ID rId5 . ID rId6 .
ARBLN03321
ID rId7 .
ID rId8 .
ARBLN07121
Multi V
83
6. Installation
Gas pipe
ID rId4 .
Liquid pipe
ARBLN14521
ID rId5 .
ID rId6 .
ARBLN23220
Multi V
84
6. Installation
Gas pipe
ID rId4 .
Liquid pipe
4 branch ARBL054
ID rId5 .
ID rId6 .
7branch ARBL057
ID rId7 .
ID rId8 .
4 branch ARBL104
Multi V
85
6. Installation
Gas pipe
ID rId4 .
Liquid pipe
7 branch ARBL107
ID rId5 .
ID rId6 .
10 branch ARBL1010
ID rId7 .
ID rId8 .
10 branch ARBL2010
Multi V
86
6. Installation
The calculation of the additional charge should take into account the length of pipe and CF (Correction Factor) value of indoor unit.
Total liquid pipe :25.4mm
= + +
0.480(kg/m)
Total liquid pipe :22.2mm Total liquid pipe :22.2mm Total liquid pipe
0.354(kg/m)
0.266(kg/m)
+ + + + +
Multi V
:15.88mm Total liquid pipe :12.7mm Total liquid pipe :9.52mm Total liquid pipe :6.35mm CF value of indoor unit
0.173(kg/m)
0.118(kg/m)
0.061(kg/m)
0.022(kg/m)
87
6. Installation
Unit : kg
CAUTION
Use only 2-series of indoor unit. Ex) ARNU***2
Multi V
88
6. Installation
Main PCB Inverter Fan PCB Noise Filter Reactor Bridge diode Magnet switch Inverter PCB Take care of the phase sequences of 3-phase 4-wire power system
- Connect transmission line between main and sub outdoor unit through the terminal block. - Connect transmission lines between outdoor unit and indoor/HR units through the terminal block. - When the central control system is connected to the outdoor unit, a dedicated PCB must be connected between them. - When connecting transmission line between outdoor unit and indoor/HR units with shielded wire, connect the shield ground to the earth screw
The temperature sensor for outdoor air should not be exposed to direct sunlight. - Provide an appropriate cover to intercept direct sunlight. Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
89
6. Installation
If transmission and power lines are run alongside each other then there is a strong likelihood of operational faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic coupling. The tables below indicates our recommendation as to appropriate spacing of transmission and power lines where these are to be run side by side
Current capacity of power line 10A 50A 100V or more 100A Exceed 100A 1,000mm 1,500mm Spacing 300mm 500mm
The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m the figures will have to be recalculated in direct proportion to the additional length of line involved. 90
Multi V
6. Installation
Note: Refer PDB for the electrical characteristics of all models. Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
91
6. Installation
Multi V
92
6. Installation
Multi V
93
6. Installation
Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7kgf/cm2). If the pressure does not drop for 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method, refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gas pipe and high/low pressure common pipe) The test result can be judged good if the pressure has not be reduced after leaving for about one day after completion of nitrogen gas pressurization.
Multi V
94
6. Installation
Note : Always add an appropriate amount of refrigerant. (For the refrigerant additional charge) Too much or too little refrigerant will cause trouble. To use the Vacuum Mode (If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)
Note: Refer PDB for more details. Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
95
6. Installation
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement or IDU addition/replacement.
Caution: ODU operation stops during vacuum mode. Compressor can't operate.
Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
96
6. Installation
Multi V
97
6. Installation
Model Code
Model Code 11 12 13 14 15 16 17 18
Unit (HP) 6 8 10 12
Unit
Ref.
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
R410A
Multi V
6. Installation
Heat pump If the Dip switch is set when power is on, the changed setting will not be applied immediately. The changed setting will be enabled only when Power is reset or by pressing Reset button.
ID rId4 .
Multi V
Function
99
6. Installation
Multi V
Function
100
6. Installation
Multi V
101
6. Installation
1. X mark means that the dip switch must be turned OFF. If not, the function may not work properly. 2. If the applicable dip switch is not set properly, the product may not work properly. 3. When executing the test operation, check the operating condition of the indoor unit and only execute the operation when all indoor units are stopped. 4. Auto test operation function does not work for the product where only one indoor unit is connected for use. 5. Cooling Only model is not working on functions of Heat Pump model.
Multi V
Function
102
7.1 Start up
7. Start up
1. Installation information
-. Supervisors must check if the real installers name plate and piping diagram is attached on the outdoor unit.
Multi V
103
7.1 Start up
3. Refrigerant piping diagram
7. Start up
The refrigerant piping diagram can make services more quickly and correctly. The refrigerant piping diagram is certainly attached on the inside of the outdoor unit in order to avoid the direct sunlight.
Multi V
104
7.1 Start up
4. Attaching the real installers name plate on the outdoor unit
7. Start up
The name plate includes an installer name, his store name, commissioner and added refrigerant amount. It should be attached on the outdoor unit.
<example> The name plate can offer the detailed information for the installation and it can make service more quickly. To make quick service, the position of breaker should be shown on the column.
Multi V
105
7. Start up
Confirm that 500 V shows 2 M or more between power supply terminal block and ground. Do not operate in the case of 2 M or less. NOTE: Never carry out M check over terminal control board. Otherwise the control board would be broken. Immediately after mounting the unit or after leaving it turned off for an extended length of time, the resistance of the insulation between the power supply terminal board and the ground may decrease to approx. 2 M as a result of refrigerant accumulating in the internal compressor. If the insulation resistance is less than 2 M, turning on the main power supply and energizing the crankcase heater for more than 6 hours will cause the refrigerant to evaporate, increasing the insulation resistance. Check if high/low pressure common pipe, liquid pipe and gas pipe valves are fully opened. NOTE: Be sure to tighten caps. Check if there are any problems in automatic addressing or not: Check and confirm that there are no error messages in the display of indoor units or remote controls and LED in outdoor units. CAUTION
3 4
While cutting main power of the Multi V, Always apply main power of the outdoor unit during use of product (cooling season/heating season). Always apply power 6 hours in advance to heat the crank case heater where performing test run after installation of product. It may result in burning out of the compressor if not preheating the crank case with the electrical heater for more than 6 hours. (In case of the outdoor temperature below 10 C)
Multi V
106
7. Start up
Compressor
Motor failure, bad ventilation Check the outdoor fan operation after being turned the outdoor units off for some time. exchanger Remove obstacles around the outdoor units Bad connector contact Coil failure EEV clogged EEV clogged Check connector Check resistance between terminals Service necessary Service necessary
Outdoor EEV
No operating sound at applying power Heating failure, frozen outdoor heat exchanger part Low pressure error or discharge temperature Error
When system fault occurs, the error code is displayed at indoor unit display or remote control display, the trouble Shooting guide is in the service manual Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
107
7. Start up
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or not (Note 1). 3 indoor temperature sensors, 9 outdoor temperature sensors, 2 outdoor pressure sensors. It is used for judging sensor abnormality (Note 2).
Multi V
108
7. Start up
Multi V
109
7. Start up
Note 2. Please check the sensor that is found abnormal. Note 3. Each step is displayed on the Main PCB LED. Note 4. Please refer to the sensor error descriptions on the next page.
Multi V
110
7. Start up
Displaying error content Indoor unit error display 1.1st and 2nd number represents indoor unit number. 2. Last number represents sensor. 1: Pipe inlet temperature sensor 2: Pipe outlet temperature sensor 3: Air temperature sensor Displaying outdoor unit error 1.1st and 2nd number represents error content (code). 2.Last number represents outdoor unit number. 1 : Master 2 : Slave 1 3 : Slave 2 4 : Slave 3 * Indoor unit number follows auto addressing number. (To check the LGMV Data)
Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
111
Ex) IDU No.2 Pipe inlet temperature sensor error and Master ODU suction temperature sensor, Master ODU high pressure sensor error
Caution
Up to 5 number of errors is displayed continuously and repeatedly. IN case 5 error occurs, again perform sensor checking after solving errors. IDU in which error occurred operates air circulation mode.
Multi V
112
7. Start up
This function charges appropriate amount of refrigerant automatically through cycle operation. It can be used when refrigerant amount is not proper because of SVC and leakage..
ID rId3 .
Multi V
113
7. Start up
Note 1. After installing the refrigerant charging device, as shown in figure, open the valve 2. In case air temperature is out of guaranteed temperature, it may end without performing Auto charging 3. Refrigerant charging Time may change according to the charging amount. (Abt. 1.5min/lb)
Note: For more information refer PDB. Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
114
7. Start up
This function judges refrigerant leakage and overcharging. It can be used with refrigerant auto charging function.
Multi V
115
7. Start up
Note 1. In case air temperature is out of guaranteed temperature, refrigerant checking function may end without performing refrigerant checking. Use guaranteed temperature range only. 2. During the process of judging refrigerant amount, if the cycle isn't stable, refrigerant checking function may end without performing refrigerant checking.
Note: For more information refer PDB. Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
116
7. Start up
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Setting Complete
Multi V
117
7. Start up
Caution: 1. Request installer to set the function during installation. 2. In case the function is not used, set the dip S/W OFF and reset the power. 3. If ODU RPM changes, cooling capacity may go down.
Multi V
118
7. Start up
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan discharge of ODU.
Multi V
119
8. Troubleshooting
Error Indicator This function indicates types of failure in self-diagnosis and occurrence of failure for air condition. Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table. If more than two troubles occur simultaneously, lower number of error code is first displayed. After error occurrence, if error is released, error LED is also released simultaneously. Error Display 1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number. Ex) 211 : No.21 error of master unit 213 : No.21 error of slave2 011 051 : No.105 error of master unit
Note: Refer PDB or Service Manual for all the Error Codes. Multi V
Copyright 2010 @LG Electronics / AC Company All Rights Reserved
120
9. New Functions
Multi V III series provides all off function instead of Fan mode.
[Installation] - Connect wires to the cool/heat selector as shown in below figure - Insert the wire in terminal by pushing "push" button - Set the DIP Switch of main PCB in master outdoor unit.
Multi V
121
9. New Functions
[Setting] - Set DIP S/W according to DIP S/W setting table. - Push black button on SVC PCB - Select number as follow at 7-segment 0 : Selector does not use 1 : Cooling/ Heating & Fan mode 2 : Cooling/ Heating & All OFF mode
Multi V
122
9. New Functions
This function gives partial load operation easily using simple switch and co-working with digital demand controller. [Installation] - Connect wires to the PI485 Gate-way on Main PCB as shown. - New ODU dry contact is using DC 12V (Using 12V Adaptor) - Choice control module; Simple switch or DDC module
ID rId4 .
Multi V
123
9. New Functions
This function control outdoor fan speed manually. Night silent operation is automatic after setting the DIP switch. But this function is operated manually by simple switch or timer. [Installation] - Connect wires to the PI485 Gate-way on Main PCB as shown. - New ODU dry contact is using DC 12V (Using 12V Adaptor) - Choice control module; Simple switch or timer. - Set DIP S/W as same as Night Silent Operation
ID rId4 .
Multi V
124
9. New Functions
This function indicates system fault information by buzzer or warming lamp, when any error is occurred in the system (Buzzer or warning light is not provided). Faults occur not only in ODUs but also in IDUs. New ODU dry contact operates with relay output. [Installation] - Connect wires to the PI485 Gate-way on Main PCB as shown. - New ODU dry contact is using DC 12V (Using 12V Adaptor) - Choice control module; buzzer or warning lamp
Multi V
125
9. New Functions
Multi V
126
Multi V