PLC Connection Guide

Siemens S7-200 (Ethernet)


Supported Series: Siemens S7/200 Ethernet Series PLC (CPU212/214/215/216/221/222/224/226/226XM) with CP243-1 Ethernet module Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters PLC type PLC I/F Port no. PLC sta. no. Recommended Ethernet 102 1 0-31 Options Notes SIEMENS S7-200 (Ethernet)

PLC Setting:
S7/200 Ethernet Multi-Connection Settings Step 1: Launching the Ethernet Wizard 1. In the Micro/WIN main menu, click Tools / Ethernet Wizard.

PLC Connection Guide

2. Then, click Next.

3. Click Yes to proceed.

Step 2: Setting CP243-1 Module Position 1. Click Read Modules.

PLC Connection Guide

2. To view the results of Read Modules, select the Ethernet module. Click Next.

Step 3: Assigning Module Address 1. Click Next.

PLC Connection Guide

2. Enter the number of desired available connections for this device. If 0 is entered, the only connection available will be the PG mode. The image below shows there are 4 connections for this module.

3. Connection0 -> Select This is a Server Connection.... Notice the Local TSAP automatically incremented to 10.00.

4. Connection1Select This is a Server Connection....

PLC Connection Guide

Notice the Local TSAP automatically incremented to 11.00.

5. Upon completion of the settings above, set parameters in EasyBuilder. Set the value of Local TSAP here to the value of Remote TSAP in Micro/WIN and vice versa to realize multi-connection.

PLC Connection Guide

Device Address:
Bit/Word B B B B B B W DW W DW DW Byte W DW Byte W DW Device type Format I Q M VW_Bit S SM VW VD VW_String VD_String MD SB SW SD SMB SMW SMD DDDDo DDDDo DDDDo DDDDDo DDDDo DDDDo DDDDD DDDDD DDDDD DDDDD DDDDD DDDDD DDDDD DDDDD DDDDD DDDDD DDDDD Range 0 ~ 40957 0 ~ 40957 0 ~ 40957 0 ~ 102397 0 ~ 40957 0 ~ 40957 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 0 ~ 10239 Memo Input (I) Output (O) Bit Memory V Memory Bit Address SCR Special Memory V Memory V Memory Double Word String String Word Memory SCR SCR SCR Special Memory Special Memory Special Memory

Double word and floating point value must use VD device type.

Wiring Diagram:
Direct connect (crossover cable): HMI RJ45 Male 1 TX+ 2 TX3 RX+ 4 BD4+ 5 BD46 RX7 BD3+ 8 BD3Wire Color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown PLC RJ45 Male 3 RX+ 6 RX1 TX+ 4 BD4+ 5 BD42 TX7 BD3+ 8 BD3-

PLC Connection Guide

Through a hub: HMI RJ45 Male 1 TX+ 2 TX3 RX+ 4 BD4+ 5 BD46 RX7 BD3+ 8 BD3Wire Color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown PLC RJ45 Male 1 TX+ 2 TX3 RX+ 4 BD4+ 5 BD46 RX7 BD3+ 8 BD3-

Driver Version:
Version V1.20 V1.40 V1.60 Date Dec/30/2008 Nov/15/2011 Jan/07/2013 Add device type : MD Add device types : S,SB,SW,SD,SM,SMB,SMW,SMD Description