AB-5467

Specifications/Instructions

Direct-coupled Damper Actuator (Voltage Input, Spring Return) MY7045A


General
MY7045A direct-coupled damper actuator is a motorized actuator to open and close dampers. If the power supply is interrupted, the return spring in the actuator moves the damper back to its safe position.

Features
Return-spring moves the damper back to its close

position if the power is off.


The voltage signal (2 to 10 V DC) controls the damper

openings.
Torque limit circuit enables the motor to stop

automatically when over-loaded.


Manual open/close function allows easy adjustment. Simple configuration facilitates installation on most

types of damper shafts.


Direction of rotation can be reversed by changing the

2 to 10V DC position feedback output available. The brushless DC motor provides stable

mounting side.

characteristics.

Model No.
Model No. MY7045A2001 Specification Direct-coupled damper actuator (Voltage input, spring return)

Specifications
Item Power supply Angle of rotation Power consumption Torque Holding torque Input signal Specification 24V AC 20 %, 50/ 60 Hz max. 95 (adjustable 25 to 95 with a supplied mechanical stopper) 6 W (motoring) 2.5 W (holding) 15 Nm (motor : at rated voltage) 15 Nm (spring return)

(1/2) Item Ambient operating conditions Ambient shipment conditions Protection Wiring Weight Ordering specifications Parts included

(2/2) Specification Temperature: -20 to +50 C Humidity: 10 to 90 %RH (non-condensing) Vibration: 4.9 m/s Temperature: -40 to +80 C Humidity: 5 to 90 %RH (non-condensing) Vibration: 9.8 m/s Dust proof, Drip proof IP42 0.75 mm, 5-core, approx.1 m long Approx. 2.7 kg 1. Model No. 2. Whether the AT72-J1 transformer is required or not. 1. Universal bracket (10093) 2. Vinyl cover for curing during work 3. M4 tapping screw (2) 4. Mechanical stopper ZDB-AF 5. Hexagonal wrench for manual open/close

15 Nm 2 to 10V DC (Linearly proportional to 0 to 100% openings) Input resistance 100 k Feedback 2 to 10V DC signal (Linearly proportional to 0 to 100% openings) Timing Approx. 150 seconds (fully closed fully open, when motor driven) Approx. 16 seconds (fully open fully closed, spring return) Applicable 10 to 20 mm, 10 to 16mm damper shaft

Dimensions

92.5 23 57

10 to16mm 10 to20mm

230 210 172 150 112 20 10 8

10

12.5

20 115

10 9

248 67 6.5 148.5 4.4 4 screws 49 3 2 10 7 5

98 80

50

Slotted Tapping Screws, flat, JIS B 1115-1976 equivalent M4, pitch1.4, 12 mm long

(2)

Figure 1 Dimensions (mm)

Figure 2 Universal bracket (mm)

Safety Instructions
Please read instructions carefully and use the product properly. Please keep this instruction on hand for reference at any time. Usage Restrictions This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in clean rooms or places where reliability or control accuracy is particularly required, please contact Yamatakes sales representatives. Yamatake Building Systems Co., Ltd. bears no responsibility for any benefit, or lack of benefit, derived from the operation by the customer. CAUTION

Do not do withstand pressure test or insulation resistance measurement to prevent equipment damage or accidents. Installer must be a trained, experienced technician. Check the ratings given in this instructions to prevent equipment damage. Check the environment given in this instructions to prevent equipment damage. All wiring must comply with applicable codes and ordinances. Use crimp contacts with insulation jackets for wire terminals. Disconnect the power supply before wiring to prevent electrical shock and equipment damage.

AB-5467

Wiring IMPORTANT: Do not connect any wires to the Not-Used terminal.


2 to 10V DC input + 2 to 10V DC + 1 2 24V AC 3 4 5

(Change the direction of rotation) Remove the C-clip. Take out the clamp and refit in on the other side. Replace the clip.

Not-Used

Figure 6

* Cable 1 is power supply, system common line * Insulate unused cable terminals. Figure 3 Wiring

If the damper spindle is 20 mm to 90 mm long Set the hexagonal nut side of the damper bracket to the damper side before installation (refer to Fig. 7 to 9).

Installation
If the damper spindle is 90 mm or more long Run the damper spindle through the output spindle of the actuator and fasten it using the hexagonal nut. To prevent the actuator from wobbling, install the attached bracket on the duct to fasten the actuator (refer to Fig. 4 and 5).
20 to 90mm Figure 7

min. 90 mm

Figure 4 Figure 8

Figure 5 Figure 9

AB-5467

Adjustment of maximum position


To set the angle up to 90 degrees to the maximum position, use the attached mechanical stopper. The stopper allows setting in 5-degree increments within the range of 30 to 90 degrees. 1) Set the mechanical stopper to the desired angle and install into the hollow of the output spindle. 2) Insert the attached tapping screw into the mechanical stopper and fasten to the actuator. The position where the tapping screw is inserted is one of the X marks (three locations) on the pointer label of the actuator.

Manual operation
Use the included hexagonal wrench to open and close the actuator (damper) and hold it in the desired position. Set the opening from close to open by inserting and turning the hexagonal wrench into the hexagonal hole on the top and bottom of the actuator. To lock the position, turn the wrench in the reverse direction immediately after the opening reaches the designated angle.

Figure 11 Manual Open/Close

Figure 10 Adjustment of rotational angle (mechanical stopper)