Specifications
N30 Supervisory Controller
Power Nominal 24 VAC +/- 10% at 50/60 Hz
Recommended VT-100 Class Terminal or
Local Terminal PC with VT-100 Emulation Software
Ambient Operating 0 to 50°C (32 to 122°F); 10 to 90 % RH
Conditions 30°C (86°F) maximum dew point
Ambient Storage -30 to 70°C (-22 to 158°F) ; 5 to 90 % RH
Conditions 30°C (86°F) maximum dew point
Dimensions N30: 64 x 168 x 236 mm (2.5 x 6.6 x 9.3 in.)
(H x W x D) LDT (optional): 108 x 108 x 27 mm (4.25 x 4.25 x 1.07 in.)
N30: Approximately 0.68 kg (1.5 lb)
N30 Supervisory Controller Shipping Weight N30 with LDT: Approximately 0.87 kg (1.93 lb)
LDT (cable included): Approximately 0.19 kg (0.43 lb)
Description UL Listed, CSA Certified CE Mark, and C-Tick Directive,
Agency
UL 916, CSA C222.2 No. 205, CFR47 FCC Part 15 Class A,
The N30 Supervisory Controller is designed to Compliance
CE Directive 89/336/EEC (EN50081/1, EN50082/1)
monitor and supervise Heating, Ventilating,
M-Series Workstation Release 5.0 or later
and Air Conditioning (HVAC) equipment as Accessories
M-Tool Release 5.0 or later
well as lighting, security, and building access.
The N30 efficiently supervises the networking n30.eps
of Application Specific Controllers (ASCs) and
provides building automation features Wiring Allowance
including time scheduling, alarm
To Order
management, controller data exchange, Specify the code number from the following
energy management, and remote selection chart.
communications. Equipment is operated at 244 m
peak efficiency while maintaining optimum
Selection Chart N30 (9.6 in
8 mm
occupant comfort. Code Number Description .6 in.)

Facility personnel can review the system Supervisory controller, base


MS-N301010-1
status and modify control parameters for the unit with N2 field bus
N30 Supervisory Controller and its associated Supervisory controller, base
ASCs using a VT100 Terminal, VT100 MS-N301012-1 unit with N2 field bus, and
Local Display Terminal (LDT)
Terminal Emulator, M-Series Workstation, or 236 mm (9.3 in.)
Supervisory controller, base n3
the Local Display Terminal (LDT).
MS-N301310-1 unit with N2 field bus and Dimensions
Ethernet peer bus
Features
Supervisory controller, base
• built-in energy management features such unit with N2 field bus, Ethernet
as Demand Limiting and Load Rolling MS-N301312-1
peer bus, and Local Display
(DLLR) and Optimal Start (OST) Terminal (LDT)
• network-wide interlocking to support
integrated control between distributed Accessories
controllers Code Number Description
• peer-to-peer communication (with network Ethernet Communication card
MS-NET 1300-0 Repair Parts
card) to provide direct communication for N30 unit
between N30s using BACnet® protocol Programming toolset for N30 Code Number Description
• dial in - dial out to allow access to/from and related ASC controllers Repair unit -- Supervisory
MW-MTOOL-0 (Replaces Configuration MS-N301010-701 controller, base unit with N2
remote sites
Tools). Includes M-Tool field bus
• local user interface such as Local Display Computer Based Training Repair unit -- Supervisory
Terminal or VT100 Terminal allows local Upgrade to Programming controller, base unit with N2
access to controller data and adjustment of toolset for N30 and related MS-N301012-701
field bus, and Local Display
operating conditions ASC controllers (Replaces Terminal
MW-MTOOL-6
Configuration Tools). Includes
• single seat user interface, M-Series Repair unit -- Supervisory
M-Tool Computer Based MS-N301310-701 controller, base unit with N2
Workstation, allows operator to review
Training field bus and Ethernet peer bus
entire system
M-Tool Computer Based Repair unit -- Supervisory
• password protection to allow system MW-MTCBT-0
Training package controller, base unit with N2
access to be tailored to the level needed by LDT Upgrade kit for N30 MS-N301312-701
MS-LDT1102-0 field bus, Ethernet peer bus,
various operators (cable included) and Local Display Terminal

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 09/01 Johnson Controls, Inc
1/2
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1900025

N30 Supervisory Controller (Continued)

Applications
network_n30.eps

Ethernet M-Series Workstation

esc

N30 N30 with LDT

VT100

N2 N2

UNT DX VMA VMA DX UNT

network n30

N30 Network Example

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 09/01 Johnson Controls, Inc