Metasys Connectivity Technical Manual 629.

5
Metasys Integrator Section
Application Note
Issue Date 0900

APPLICATION NOTE


Metasys Integrator
 AFP-200 Fire Panel Application
Notifier

Introduction Page *3
• Application Details *3
• Component Requirements *5
• Vendor Contact Information *6
• Design Considerations *6

Cable Connections 9
• Cable Pinouts *9
• Connecting the Cable *9

Metasys Integrator Setup *11

Point Mapping Tables 13


• Detector Points *13
• Module Points *13
• Bell/System Trouble Points *14

Metasys Network Setup *17


• Mapping to a CS Object *17

Custom Integration *19

*Indicates those sections where changes have occurred since the last printing.

© 2000 Johnson Controls, Inc. 1


Code No. LIT-6295402 www.johnsoncontrols.com
2 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Introduction

This document explains the Metasys Integrator Notifier AFP-200 Fire


Alarm Panel application. Use this document with the Metasys Integrator
technical bulletins that provide information on installing and
commissioning the Metasys Integrator unit. For information on the
AFP-200 Fire Panel, see the Notifier documentation. Please note that this
application will also work with the Johnson Controls IFC-200 Fire Panel.
Note: If you are using a Universal Packaging Module (UPM), you must
install the Metasys Integrator 300 Series in a two high enclosure
(EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0)
as shown in the figures in this application note.

Application The Metasys Integrator unit allows the Notifier AFP-200 Fire Alarm Panel
Details to communicate with the Metasys and Metasys Companion Networks.
Once a Notifier AFP-200 Fire Panel is connected to a Metasys or
Companion Network via the Metasys Integrator unit, its data is available
to the full complement of Metasys Building Automation System (BAS)
features, including Change-of-State (COS) monitoring, secondary
reporting, alarm and trouble notification, trend, and totalization.
Each Metasys Integrator vendor port can connect to one AFP-200 Fire
Panel. The AFP-200 Fire Panel has a single Signaling Line Circuit (SLC)
that supports up to 99 detectors and 99 modules, plus four Notification
Appliance Circuits (NACs) designated “Bell Circuits” on the panel.
When the AFP-200 Fire Panel is reset, all Binary Input (BI) points are
reset to an open or 0 value and any trouble status is cleared.

! CAUTION: The Metasys Integrator unit is not Underwriters


Laboratories (UL) 864 Listed as a fire alarm control
unit. It is designed to provide only secondary ancillary
monitoring, while the AFP-200 Fire Control Panel
provides UL 864 Listed notification and control
functions.

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 3


N1LAN

Standard NCU

RS-232 AFP-200
Fire Panel

Metasys
Integrator

UNT

afp1
Note: If you are using a UPM, you must install the Metasys Integrator
300 Series in a two high enclosure (EN-EWC25-0) rather than
a one high enclosure (EN-EWC13-0) as shown in the figures in
this application note.

Figure 1: AFP-200 Fire Panel and Metasys Integration

Panel Unit Workstation

RS-232
(50 ft maximum) AFP-200
Fire Panel
Metasys
Integrator

UNT

N2 Bus

Note: A PC version and converter may be substituted for the Panel unit.
afp200comp

Note: If you are using a UPM, you must install the Metasys Integrator 300 Series
in a two high enclosure (EN-EWC25-0) rather than a one high enclosure
(EN-EWC13-0) as shown in the figures in this application note.

Figure 2: AFP-200 Fire Panel and Metasys Companion


Integration

4 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application


Component To integrate the AFP-200 Fire Panel, you need the following:
Requirements • properly installed AFP-200 Fire Panel with firmware Version 2.4
• RS-232 cable (for connecting the AFP-200 Fire Panel’s RS-232 port to
the Metasys Integrator unit)
• Metasys Integrator unit
• B&B Optical Isolator, Model RS232 OP4
• N2 Bus (for connecting the Metasys Integrator unit to the Metasys
Network Control Module [NCM] or Companion Network)
• portable Personal Computer (PC) for downloading vendor
communication tables (.VCT files) and network setup information into
the Metasys Integrator unit, and for running diagnostics
• cable for connecting the portable PC to the Metasys Integrator unit
• cables for connecting AFP-200 Fire Panel to the Metasys Integrator
unit (see pin requirements in the Cable Connections section of this
document)
• standard duplex 120 VAC outlet, required within one foot of the
B&B Optical Isolator, Model RS232 OP4 to power this device. This
device has two plug-in power supply transformers.
This document describes the RS-232 cable and vendor communication
tables. Notifier documentation describes their equipment. The remaining
components are described in the Metasys Integrator technical bulletins.

Metasys Release To integrate the AFP-200 panel into the Metasys Network, you need:
Requirements
• Metasys Operator Workstation (OWS) software Release 7.0 or higher
• Metasys Integrator software/firmware Release 9.0 or higher

Metasys To integrate the AFP-200 panel into the Metasys Companion Network,
Companion you need:
Release
Requirements • Metasys Companion Release 6.0 or higher
• Metasys Integrator software/firmware Release 9.0 or higher

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 5


Vendor Integration between the Metasys Integrator unit and Notifier AFP-200
Component Fire Panel application has been tested with Notifier AFP-200 Firmware
Requirements Release Version 2.4 and B&B Optical Isolator Model RD232 OP4.
B&B Optical Isolator Model RS232 OP4 is required between
AFP-200 panel RS-232 port and Metasys Integrator vendor port to
eliminate the ground fault. Changes to this equipment or integration of
either Notifier or B&B products not discussed in this document require
additional software development and testing by Johnson Controls Systems
Products. For information on integrating other products, refer to the
Custom Integration section of this application note.

Vendor Contact Notifier


Information One Fire-Lite Place
Northford, CT 06472
Phone: (203) 484-7161
FAX: (203) 484-7118
B&B Electronics Company
707 Dayton Road
P. O. Box 1040
Ottawa, IL 61350
Phone: (815) 433-5100
FAX: (815) 434-7094

Design When integrating the AFP-200 Fire Panel, consider the following:
Considerations • Make sure that the AFP-200 Fire Panel is set up and running properly
with Version 2.4 firmware before integrating with a Metasys or
Companion system. This includes configuring the
AFP-200 Fire Panel’s RS-232 printer port in remote terminal mode.
(The Notifier representative is responsible for the configuration and
operation of Notifier equipment.)
• The Metasys Integrator unit is not UL 864 Listed as a fire alarm
control unit. It is designed to provide secondary ancillary monitoring
only, while the AFP-200 Fire Panel provides notification and control
functions.
• When the AFP-200 Fire Panel is reset, all BI points are set to open
state and the trouble status is reset.
• The AFP-200 Fire Panel must be reset to clear alarms.
• RS-232 cable distance between the Metasys Integrator unit and the
AFP-200 Fire Panel cannot exceed 50 feet.
• The trouble status is cleared when a device reports a normal or off
state.

6 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application


• Programming at the AFP-200 Fire Panel will cause the Notifier
AFP-200 Fire Panel to go offline. Also, continuous pressing of the
panel keys (e.g., Ack/Step) may cause the AFP-200 Fire Panel to go
offline at the Metasys Integrator unit.
• The AFP-200 Fire Panel, when used alone without the Metasys
Integrator unit, has a feature that scrolls through trouble messages
when multiple messages exist on the system. This feature is not
present when the Metasys Integrator unit is connected to the
AFP-200 Fire Panel. If multiple messages exist on the system, the
Ack/Step key must be pressed to view each individual message.

! WARNING: Some change-of-state messages may be missed


while running the Diagnostic Analyzer on the
Metasys Integrator commissioning PC. Do not run
the Metasys Integrator Diagnostic Analyzer after
commissioning is complete. Disconnect the
Metasys Integrator unit from the AFP-200 printer
port while programming the Fire Panel, then reset
the AFP-200 panel after reconnecting the
Metasys Integrator unit.

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 7


8 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Cable Connections

Cable Pinouts Use the following cable pinouts for the RS-232 connection between the
Metasys Integrator unit and the AFP-200 Fire Panel. You must connect
the male end of the converter to the Metasys Integrator unit.
Duplex
12 VDC/ Outlet
Vendor Port A or B of 120 VAC
Metasys Integrator
RS-232 Printer Port
DB-9 Female on APF-200 (TB4)

Male Female
Signal Pin (25 Pin)
(25 Pin)
3 Optical Isolator 3 TX
RD 2 RX
2 2
TD 3 RF
7 Model 2320 P4 7
GND 5

(50 ft maximum)
afp3

Figure 3: Cable Pinouts

Connecting the Connect the female end of RS-232 cable to either Vendor Port A or
Cable Vendor Port B on the Metasys Integrator unit. Connect the other open end
(no connector) of the cable to terminal TB4 of the panel as specified in
AFP-200 Fire Panel installation documentation.

Metasys AFP-200
Integrator Fire Panel

Optical
RS-232 Printer
Isolator
Vendor Port Terminal Port
A or B TBA
(EIA-232)

afp4

Figure 4: Port-to-Port Connection

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 9


10 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Metasys Integrator Setup

To set up the Metasys Integrator unit, use a portable PC connected to


Metasys Integrator Terminal Port. Metasys Integrator setup involves:
• downloading the correct vendor communication tab (.VCT files)
• setting up the ports
• setting up the network addressing
The following table provides information specific to the AFP-200 Fire
Panel application. For detailed procedures, see the Metasys Integrator
technical bulletins.

Table 1: Metasys Integrator Setup for AFP-200 Fire Panel


Vendor Communication Table (.VCT File)
Detector Points IFC2_DET.VCT
Module Points IFC2_MOD.VCT
Bell (NAC) and System Trouble
Points IFC2_BEL.VCT
Port Setup
Baud Rate 2400
Word Length 7
Stop Bit 1
Parity Even
Interface RS-232
Network Setup
Vendor Address
Detectors D*
Modules M*
Bell (NAC) and System Trouble
Points B*
Timeout Value 3000 ms
Poll Delay 0 ms
Retries 5
Approximate Scan Time
(for an N2 address)
Detectors 60 seconds
Modules 60 seconds
Bell (NAC) and System Trouble
Points 10 seconds
Time to Receive Alarm/Trouble 2 seconds
(after the message generated at the
panel)
* Be sure to use uppercase characters.

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 11


12 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Point Mapping Tables

The following tables show the points available for mapping on the
AFP-200 Fire Panel:

Detector Points BI points for each sensor have corresponding Binary Data (BD) points,
which are used to map the pre-alarm status of the sensor. These BI points
also indicate the trouble status of the detector.

Table 2: Detector Points


NPT1 NPA2 Description Value Mapped
BI 1-99 Detector SLC Address-LPA 0-Normal, 1-Alarm
BD 1-99 Pre-alarm status of detector at LPA 0-Normal, 1-Alarm
1 Network Point Type
2 Network Point Address

When any detector point goes in or out of trouble, its value remains as it
was before the trouble occurred.

Module Points BI points also indicate the trouble status. These BI points also indicate the
trouble status of the module.

Table 3: Module Points


NPT1 NPA2 Description Value Mapped
BI 1-99 Module SLC Address-LPA 0-Normal, 1-Alarm
(Monitor Modules)
0-Off, 1-On
(Control Modules)
1 Network Point Type
2 Network Point Address

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 13


Bell/System When any system trouble occurs, you must reset the IFC-200 Fire Panel
Trouble Points manually after clearing the trouble. Table 4 is a list of all the bell circuits
and system trouble status points.

Table 4: Bell/System Trouble Points


NPT1 NPA2 Description Value Mapped
BI 1 Bell Circuit 1 0-Off, 1-On
BI 2 Bell Circuit 2 0-Off, 1-On
BI 3 Bell Circuit 3 0-Off, 1-On
BI 4 Bell Circuit 4 0-Off, 1-On
BI 5 Ground Fault 0-Normal, 1-N/A
BI 6 AC Fail 0-Normal, 1-N/A
BI 7 Battery 0-Normal, 1-N/A
BI 8 Style 6 0-Normal, 1-N/A
BI 9 Option Module 0-Normal, 1-N/A
BI 10 Term. Supervisory 0-Normal, 1-N/A
BI 11 Annunciator 1 No Answer 0-Normal, 1-N/A
BI 12 Annunciator 1 Trouble 0-Normal, 1-N/A
BI 13 Annunciator 2 No Answer 0-Normal, 1-N/A
BI 14 Annunciator 2 Trouble 0-Normal, 1-N/A
BI 15 EPROM Error 0-Normal, 1-N/A
BI 16 Internal RAM Error 0-Normal, 1-N/A
BI 17 External RAM Error 0-Normal, 1-N/A
BI 18 Program Corrupted 0-Normal, 1-N/A
BI 19 No Device Installed 0-Normal, 1-N/A
BI 20 AVPS. Trouble 0-Normal, 1-N/A
1 Network Point Type
2 Network Point Address

Note: All system trouble points remain unreliable once a device goes
offline/online, until the panel is reset using the system-reset button.
Individual points report online when a trouble status is reported for
that point.

14 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application


Getting Point The commissioning person should have the details of point summary at the
Summary time of commissioning. If they are not available, collect the status
Information from summary from the panel using the following steps:
AFP-200 Fire
Panel to Map 1. Disconnect the Metasys Integrator unit from the AFP-200 Fire Panel.
Points with the 2. Connect a serial printer at printer port (the same serial port which is
Metasys used for Metasys Integrator interface).
Network
3. Press the Enter key at the panel.
4. Select 2 - read status.
5. To print all points, press 1 (print points), then Enter. A summary will
be printed for all programmed points with their current status. The last
three characters in each line of the message are the actual point SLC
address.
(For example:
D01 is detector at SLC address 01, which is BI-1 in vendor table file
IFC2_DET.VCT.
M01 is module at SLC address 01, which is BI-1 in vendor table file
IFC2_MOD.VCT.
B01 is Bell Circuit 1, which is BI-1 in vendor table file IFC2_BEL.VCT.)
See Table 2 for detector points, see Table 3 for module points, and see
Table 4 for bell/system trouble points.

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 15


16 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Metasys Network Setup

Metasys Network setup is described in the Metasys Integrator technical


bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). This
section contains details specific to the AFP-200 Fire Panel. We
recommend that all points that report an alarm or trouble status be directly
mapped to BI objects.

Mapping to a Table 5: Software Model and CS Object Definition


CS Object Application Software Model Display NT Command
(on Tables and Attributes Attributes
Models CD-ROM) (recommended)
AFP-200 Detector IF2_DLOP.DDL BI1 BI1
SLC Status of Detector 1 Status of Detector 1
AFP-200 IF2_MLOP.DDL NI1 BI1
Module SLC Status of Module 1 Status of Module 1
AFP-200 Bell (NAC) IF2_SYST.DDL BI17 BI17
and System Network Fail Network Fail
Trouble Points

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 17


18 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Custom Integration

For information on integrating products which are not discussed in this


document, first refer to the Metasys Compatible Global Catalog, an online
list of released Connectivity products. If this list does not provide the
information you require, consider using the System Integration Project
Data Sheet to request a custom contract from the System Integration
Team.
Both the Metasys Compatible Global Catalog and the System Integration
Project Data Sheet can be accessed from The Advisor by performing the
following steps:
1. Click on the Systems Products button located on the left side of
The Advisor home page.
2. Click on the Product Literature link.
3. Click on the Manuals-FANS link.
4. Click on the 629.0 Metasys Connectivity Sales Resource Manual link.
5. Find the System Integration Project Data Sheet link in the Table of
Contents. Click on this link to view an online copy of the System
Integration Project Data Sheet, or click on the Metasys Compatible
Global Catalog link below it to view a list of released Connectivity
products.
The System Integration Project Data Sheet (LIT-6290052) can also be
found in the Metasys Connectivity Sales Resource Manual (FAN 629).
If you need further assistance, contact the Johnson Controls Field Support
Center.

Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application 19


Notes

www.johnsoncontrols.com
Controls Group FAN 629.5
507 E. Michigan Street Metasys Connectivity Technical Manual
P.O. Box 423 Metasys Integrator Release 9.0
Milwaukee, WI 53201 Printed in U.S.A.

20 Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application